ADDITIONAL INSTALLATION REQUIREMENTS
for Fire-Rated Doors (JII111)
Fire-rated doors are certied according to independent standards as indicated on the permanent re certication label afxed to each door. To maintain the validity of this certication, the door installer must follow all of the standard installation instructions as well as comply with the following requirements.
Edge Seals and Gaskets
Building codes adopted in local areas may require the application of additional edge seals and/or gaskets. The following chart is provided for your convenience; consult your local building code ofcial (or authority having jurisdiction) for applicable building codes and regulations.
Steel Fire Door (wood edged) 20-min rated
UL 10 (b) - Neutral Pressure Doors
UL 10 (c) - Positive Pressure Doors
UBC 7-2 (97) Part 2 - Smoke and Draft Control Doors
CAN/ULC S104 (Canada) Category H gasket is required. No edge seal is required.
Vision Panel
Vision panels are permitted in all re doors (except wood-edged steel doors) using a listed and labeled light kit. To ensure a proper gasket seal, vision panels must be installed to lie on a at surface of the door; do not cut across proles when positioning a light kit. The rating of the light kit, in minutes, must coincide with the rating of the re door. Light kits must be installed per manufacturer’s installation instructions.
Frame
The door slab must be installed in a re rated frame to match installed door. The frame must have a minimum re-rating equivalent to the rating of the door. Frames must be installed plumb, square and level. Follow frame manufacturer's installation instructions.
Clearances
Clearances between the steel door edge and the frame must be at least 1/16 inch and no greater than 3/16 inch at the header and jambs. Other re door clearances must be at least 1/16 inch and no greater than 1/8 inch. Trimming is not allowed in the eld unless allowed by NFPA 80 standard.
Latch
Fire rated latch-sets that t the latch cut-out per hardware template are required. Follow the latch manufacturer’s installation instructions.
Closer
Listed surface mounted door closer may be installed using through bolts. Backer plate is recommended. If wood screws are the desired fastener, appropriate blocking must be manufactured in the door construction. Follow the closer manufacturer’s installation instructions.
General
Frame, hinges, passage sets, and hardware must be re rated and installed in accordance with manufacturer's installation instructions and NFPA 80 standard. Surface mounted hardware must be attached with through bolts unless inner blocking is provided.
No edge seal or gasket is required for doors with re label code “D2ON-BS.” Category H gasket is required for doors with re label code “D2ONH-BS.”
N/A (a) Category G edge seal must
N/A Category H gasket is required. In addition to Category G edge seal,
Steel Fire Door (steel edged) 20/45/60/90-min rated
Category H gasket is required. No edge seal is required.
be installed on the door edge or frame and Category H gasket must be installed on the frame per manufacturer's installation instructions, or
(b) Gasket which is eligible for both Category G and H can be installed in lieu of (a) above, or
(c) Pemko S88 or S52 can be installed in lieu of (a).
Other Fire Doors (ush, stile & rail, custom carved or molded wood, and berglass doors) 20/45/60/90-min rated
Category H gasket is required for exterior doors. No edge seal or gasket is required for interior doors.
Category G edge seal must be installed on the door edge or frame per manufacturer's installation instructions. Category H gasket is required for exterior doors.
Category H gasket must be installed on the frame per manufacturer's installation instructions.