INTRODUCTION
DESCRIPTION
Up to three transmitters per output can be connected to the receiver. There are two outputs on each receiver. The system is compatible with 8K2 monitored safety edges or electromechanical safety edges (volt free safety contacts NC).
There is also a Vbat auxiliary power input to power the transmitter through the RB-BATPACK providing more operational autonomy.
The system complies with EN ISO 13849-1.
USE OF THE SYSTEM
This equipment is designed to be installed with a safety edge for door and gate installations. It is not guaranteed for directly activating equipment other than that specified. The manufacturer reserves the right to change the specification of the equipment without prior warning.
TECHNICAL CHARACTERISTICS
Frequency 868.90MHz Power supply 3V DC (2 x 1.5V LR6 AA) Operating consumption 12mA Radiated power < 25mW Operating temperature -20ºC - +55ºC Watertighness IP44 Size 40 x 194,5 x 20mm Range 10m Battery life (aprox) 2 Years Minimum time between two activations of RADIOBAND (to comply with the R&TTE Directive)
7 min
INSTALLATION AND WIRING
MECHANICAL INSTALLATION
Swipe the front cover following the indication of the box to open the equipment. Fix the back of the box to the door. Install the transmitter following the technical manual and avoid placing metallic surfaces between the receiver and the transmitter. Pass the cables through the holes indicated. Connect the safety edge following the electrical connections clause and ensure that the safety edge keeps totally waterproof. Swipe the front cover to the back to close the equipment.
1
COD. 1248044 / 1.2
RBAND TC
HOLE FOR WIRES
TERMINALS
PROGRAMMING BUTTON
BATTERIES
-
REMOVABLE PLASTIC
+
A
A
A
A
-
+
8k2 MONITORED SAFETY EDGE CONNECTION
Connect the safety edge to the S.EDGE terminal. Electromechanical safety edges with 8k2 output are also considered 8k2 monitored safety edges.
8k2
Sedge Detection Sedge Ok Sedge Open
0k - 5,8k
ΩΩ
7k - 9k
ΩΩ
11k - k
Ω∞Ω
VOLTAGE FREE CONTACT CONNECTION
When a voltage free contact is to be connected, (eg. photocells or electromechanical safety edges without resistive output), connect it to the SEC terminal.
Note: In order to comply with the EN 12453 safety standard for the use of motorized garage doors, the device connected to this
input must have some verification system to ensure its proper functioning.
2