• To avoid electric shock or serious injury or property damage, isolate power before installing,
removing or servicing the product
• It is recommended that this product is installed by an electrician or a competent person with
sufcient experience to install this product
• To be installed in accordance with the local current wiring regulations and standards
• Any broken or damaged parts should be replaced as soon as possible
Utility Bulkhead
®
a
company
• JCC will not accept responsibility for claims arising from sub-standard installations; which will void the warranty
• Ensure that you have the tools and accessories required to complete the installation correctly
• This luminaire is suitable for indoor use or exterior use, wall or ceiling mounting
• Do not install in areas that are near to continual running water
• Do not carry out insulation tests with this product connected to the circuit
• It may be necessary to uprate your MCBs to allow for increased inrush current
ENGLISHINSTALLATION INSTRUCTIONS
Mains supply Input : 220-240V~ 50/60Hz Class 1
Fig. 1
Standard versions
Live = Brown
Neutral = Blue
Emergency versions
Switched Live: Brown
Ceiling
applications
1A Fused Unswitched Live
Live = Brown
Yellow/green
Neutral = Blue
DALI
DA DA
To Driver
1-10V
+-
Wall
application
WattageCCTCRI:RaLumensLpcW
12W4000K80700*/1150**58*/96**
21W4000K801350*/2000**64*/95**
Diffuser: Opal (WOP)* or Prismatic (WPR)**
Installation
Ensure the xing surface is at and even. Use adequate xings with regard to type of surface.
1. Remove diffuser from luminaire by loosening the three securing screws.
2. All termination points are under the LED tray and this can be removed by loosening the locating
screws and rotating the tray until keyhole slots allow removal.
3. Ensure incoming cables are weather protected.
4. Pass intended supply wires through grommet or CTS gland.
5. Fix base in desired location, taking care to avoid pipes and cables that may be hidden.
6. Make connections and connect dimming controls as required for DALI/1-10V versions (Fig.1).
7. Re-attach LED tray to mounts and tighten screws.
8. Replace diffuser and tighten screws evenly.
9. Switch on mains.
IP65
jcc.co.uk
V3_Jun_2022_RS
Sensor data can be set using DIP switches on the sensor. The settings are as follows:
Microwave On/Off operation and settings
Detection Area
I: Up to 8m
II: Up to 6m
III: Up to 4m
VI: Up to 3m
V: Up to 2m
II
III
IV
12
OnI
-
On
-
-
On
On
On
V
Note that reducing detection area
will also reduce sensitivity.
3
100%
On
75%
On
50%
On
-
25%
On
-
10%
-
-
On
Refers to the time period the lamp
remains at 100% illumination after
no motion detected.
Microwave Step Dim operation and settings - 12W version only
Microwave Step Dim operation and settings - 21W version only
Detection Area
On
I
II
III
IV
Ø16m x 6m High max
Detection area can be reduced by
selecting the combination on the
DIP switches to t precisely each
application.
12
OnOn
On
-
On
-
-
-
100%
75%
50%
10%
Hold Time
34
On
II
III
OnI
-
On
IV
Refers to the time period the lamp remains
at 100% illumination after no motion is
detected.
On
On
-
--
5s
90s
3min
10min
Corridor function(Stand-by period)
On
II
III
IV
Refers to the time period the lamp remains
at a low light level before it completely
switches off in the long absence of any
occupancy. When set to ”+
is maintained until motion is detected -Step
Dim Function. When set to “Os”, the light will
turn off after hold time.
Photocell operation and settings
When ambient light level is below the “On” lux level selected, the sensor automatically
switches on the luminaire at 100% brightness.
78
OnI
-
On
∞
0s
On
30s
On
10min
-
+
∞
--
”, the low light
Stand-by DIM Level
This is pre-set at 20%
and not adjustable
Prole & Dimensions
Daylight Sensor
56
On
II
III
OnI
-
On
IV
The sensor can be set to only allow the
lamp to illuminate below a dened ambient
brightness threshold. When set to Disable
mode, the daylight sensor will switch on the
lamp when motion is detected regardless of
ambient light level. 50Iux: twilight operation,
15Iux, 5Iux: darkness operation only.
On
On
-
--
Disable
50Lux
15Lux
5Lux
When ambient light level is higher than the “Off” lux level selected, the sensor
automatically switches off the luminaire.
When set to disable, the sensor does not work.
O@
25Lux
50Lux
75Lux
100Lux
200Lux
300Lux
400Lux
On
II
III
IV
V
VI
VII
VIII
1234
OnI
On
OnOn
On
On
On
On
-
-
On
-
-
On
-
-
-
On
OnOn
On
On
-
--
On@
5Lux
10Lux
-
25Lux
On
50Lux
-
100Lux
-
150Lux
-
200Lux
-
-
Disable
JCC Lighting Products Ltd. Lux Park, Chichester Business Park, City Fields Way, Tangmere, Chichester, West Sussex, PO20 2FT
283
85
85
All dimensions in millimetres
Emergency range routine
Important warranty information
This product is supported by a 2-year standard warranty which will extend to 5-years if registered within the first year of pu
(2 year on batteries). Please register at jcc.co.uk/warranty (Terms and conditions apply).
The installer will be asked to provide the following information, which is detailed on a label attached to the luminaire’s chas
Product Code/Date Code.
inspection and test
All tests must be undertaken at times of least risk
and in accordance with EN 50172:2004 as
indicated below:
Weekly: Indicators of central power supply shall be
visually inspected for correct operation.
Monthly: (in addition to the daily check) If automatic
testing devices are used, the results of the
short duration tests shall be recorded. Test
shall be carried out as follows:
a) Switch the luminaire over to emergency mode to
operate from the batteries by simulating a failure
of supply to the normal lighting for a period
sufcient to ensure correct luminaire operation
NOTE: The period of simulation failure should be
sufcient for the purpose of this clause
whilst minimising damage to the system
components e.g lamps. During this period,
all luminaires and signs shall be checked
to ensure that they are present, clean
and functioning correctly. At the end of
this test period, the supply to the normal
lighting should berestored and any
indicator lamp or device should be checked
to ensure that is showing that the normal
supply has been restored.
Annually: If automatic testing devices are used, the
results of the short duration tests shall
be recorded. For all other systems the
monthly inspection shall be carried out
and the following additional tests made:
a) Each luminaire and internally illuminated
sign shall be tested monthly as above but
for its full duration in accordance with the
b) The normal supply for the luminaire should
c) The date of the test and its results shall
A copy of this report must accompany any tting returned to
the manufacturer for any reason.
manufacturer’s information.
be restored and any charge indicator
lamp or device should be checked to
ensure that it shows the normal supply
has been restored. The charging
arrangements should be checked for
proper functioning.
be recorded in the system logbook.
General Information
Our products are designed to comply with the requirements of UK law and the relevant industry national and international standards and should not be modied in any way. All emergency lighting
systems should comply with the recommendations of BS5266-1: Code of Practice for the Emergency Lighting of Premises and be installed by competent engineers in accordance with the relevant
wiring regulations. Before installing any type of Emergency Lighting always seek the advice and approval of the local Fire Prevention Ofcer (or equivalent authority).
Maintenance
Failed or faulty light sources connected to this equipment should be replaced immediately. These units are designed especially for a long and trouble free life. Under normal conditions, will require no
routine maintenance or service beyond the inspection and test regime of BS5266-1. Both mains supply and battery protection fusing is incorporated internally. Should access to these or any other
part of the circuitry be required this must be undertaken only by suitably qualied person. Special care must be taken when removing the cover to circuitry and battery. Only replacement components
authorised by the company must be used. Disposal of replaced components should be in accordance with the component manufacturers instructions.
You can help protect the environment. Please remember to respect the local regulations: hand in the non-working electrical equipment to an appropriate waste disposal centre.
The packaging material is recyclable. Dispose of the packaging in an environmentally friendly manner and make it available for the recyclable material collection service.
MonthTest TypeFirst YearSecond YearThird YearFourth YearFifth Year
Sign DateSignDateSign DateSignDateSign Date
JanuaryFunctional
FebruaryFunctional
MarchFunctional
AprilFunctional
MayFunctional
JuneFunctional
JulyFunctional
AugustFunctional
SeptemberFunctional
OctoberFunctional
NovemberFunctional
December3 hour
rchase.
sis:
Emergency test record sheet
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.