JCC JC070065, JC070095, JC070075, JC070086, JC070079 User Manual

...
RadiaLED® Rapid Range
LN
MAINS INPUT
Installation instructions for RadiaLED
WARNINGS AND CAUTIONS
To avoid electric shock or serious injury or property damage, isolate power before installing, removing or servicing the product
It is recommended that this product is installed by an electrician or a competent person with
sufcient experience to install this product
To be installed in accordance with the local current wiring regulations and standards
Any broken or damaged parts should be replaced as soon as possible
bulkhead
®
a company
JCC will not accept responsibility for claims arising from sub-standard installations; which will void the warranty
Ensure that you have the tools and accessories required to complete the installation correctly
This luminaire is suitable for indoor use or exterior use, wall or ceiling mounting
Do not install in areas that are near to continual running water
Do not carry out insulation tests with this prodcut connected to the circuit
ENGLISHINSTALLATION INSTRUCTIONS
Mains supply Input : 220-240V~ 50/60Hz Class 2 EM versions Class I
1. Isolate power supply.
2. Ensure that the body is installed in the correct orientation if wall mounted as indicated by the
“THIS WAY UP” arrow inside the body(see g.1.)This will ensure that the LED module is suspended correctly with security strap below the body when installing.(see g.6.)
3. Mains input cable entry options are in the centre of the body(see g.2.)or 4 conduit entry point
options on the side of the body(see g.3.), you will need to drill a Ø20mm hole and use the supplied grommet(s) to maintain the IP rating of the tting. It is recommended to drill this from
the back of the body.
4. To secure the body to the mounting surface you will also need to drill pilot holes of Ø4-6mm to
accomodate the xing screws. There are two mounting options: 4 x direct to the mounting surface or by using the option for BESA mounting in the centre of the body. The counter
sunk molded xing points are around the outside edge of the interior of the body adjacent to four conduit side entry points(see g.3.) and in the centre for BESA mounting(see g.2.)
5. Connect the mains input into the terminal block in the body(see g.4.) Terminal block is
loop-in /loop-out to allow for continuous wiring.
L1 = Unswitched Live L = Switched Live = Earth(EM versions) N = Neutral
6. For emergency versions, the batteries are enclosed in the invertor and are already connected so do
not require commissioning.
7. Once you have completed all of the connections, t LED tray into the body by aligning the 4
slots and press into place until clipped in.
8. To t the diffuser align the 4 captive screws in the diffuser with the holes in the body which
have corresponding lugs for alignment(see g.5.). Ensure that the screws are not over-tightened
as this could damage the gasket and effect the IP rating.
9. Turn on mains supply and test operation( allow 24hrs for the battery to charge before testing
emergency operation)
Wattage CCT CRI:Ra Lumens LpcW
8W 4000K 84 760 95
8W 3000K 84 760 95
12W 4000K 84 1250 104
12W 3000K 84 1250 104
16W 4000K 84 1600 100
16W 3000K 84 1600 100
24W 4000K 84 2360 98
24W 3000K 84 2360 98
Fig.1.
Fig.4. Fig.5.
Fig.2.
Ø20mm centre cable entry
1
L
Standard operation
mode
8W
12W
16W
24W
BESA Plate
xing holes
Ø4mm x 4
Battery charging operation mode
(initial charge 24hrs)
12W(8W+4W)
16W(12W+4W)
20W(16W+4W)
28W(24W+4W)
Fig.3.
Fig.6.
Diffuser
Alignments lugs
Body
Parasitic
Power
0.5W
0.5W
0.5W
0.5W
Ø4-6mm Body
xing holes
Technical Support: +44(0)1243 838986 Customer Services: +44(0)1243 838999
BS EN ISO9001 - 2015 - Registered Firm Certificate No. GB 1552
Microwave on/off version operation and settings
I: Up to 8m
II: Up to 6m
III: Up to 4m
VI: Up to 2m
Detection Area
On
II
III IV
1 2
OnI On
-
On
-
On
--
100%
75%
50%
25%
Hold Time
3 4 5
OnI
On
II
III IV
V
VI VII
VIII
Refers to the time period the lamp remains at 100% illumination after no motion detected.
On On On
-
-
-
-
OnOnOn
-
-
On
On
-
-
Prole & Dimensions
A C
-
On
-
On
-
On
-
5s
30s
1min
3min
5min
10min
20min
30min
Daylight Sensor
I: 2lux (darkness operation only) II: 10lux (Darkness operation only) Ill: 25lux (twilight operation) IV: 50lux (twilight operation only) V: Disable* (darkness operation only)
*When set to Disable mode, the daylight sensor will switch on the lamp when motion is detected regardless of ambient light levels.
On
II
III IV
V
6 7 8
OnI
OnOnOn
On
On
-
On
2Lux
10Lux
-
25Lux
-
50Lux
--
Disable
---
B
Wattage A B C D
8W Ø232.1 93.3 Ø274 93.3
12W/16W/24W Ø301 98.3 Ø340 98.3
All dimensions in millimetres
JCC Lighting Products Ltd. Lux Park, Chichester Business Park, City Fields Way, Tangmere, Chichester, West Sussex, PO20 2FT
D
with rimwithout rim
Emergency range routine
Important warranty information
This product is supported by a 2-year standard warranty which will extend to 5-years if registered within the first year of pu (2 year on batteries). Please register at jcc.co.uk/warranty (Terms and conditions apply).
The installer will be asked to provide the following information, which is detailed on a label attached to the luminaire’s chas Product Code/Date Code.
inspection and test
All tests must be undertaken at times of least risk and in accordance with EN 50172:2004 as indicated below:
Weekly: Indicators of central power supply shall be
visually inspected for correct operation.
Monthly: (in addition to the daily check) If automatic
testing devices are used, the results of the short duration tests shall be recorded. Test shall be carried out as follows:
a) Switch the luminaire over to emergency mode to
operate from the batteries by simulating a failure of supply to the normal lighting for a period
sufcient to ensure correct luminaire operation
NOTE: The period of simulation failure should be
sufcient for the purpose of this clause
whilst minimising damage to the system components e.g lamps. During this period, all luminaires and signs shall be checked to ensure that they are present, clean and functioning correctly. At the end of this test period, the supply to the normal lighting should berestored and any indicator lamp or device should be checked to ensure that is showing that the normal supply has been restored.
Annually: If automatic testing devices are used, the
results of the short duration tests shall be recorded. For all other systems the monthly inspection shall be carried out and the following additional tests made:
a) Each luminaire and internally illuminated
sign shall be tested monthly as above but for its full duration in accordance with the
b) The normal supply for the luminaire should
c) The date of the test and its results shall
A copy of this report must accompany any tting returned to
the manufacturer for any reason.
manufacturer’s information.
be restored and any charge indicator lamp or device should be checked to ensure that it shows the normal supply has been restored. The charging arrangements should be checked for proper functioning.
be recorded in the system logbook.
General Information
Our products are designed to comply with the requirements of UK law and the relevant industry national and international standards and should not be modied in any way. All emergency lighting sys-
tems should comply with the recommendations of BS5266-1: Code of Practice for the Emergency Lighting of Premises and be installed by competent engineers in accordance with the relevant wiring
regulations. Before installing any type of Emergency Lighting always seek the advice and approval of the local Fire Prevention Ofcer (or equivalent authority).
Maintenance
Failed or faulty light sources connected to this equipment should be replaced immediately. These units are designed especially for a long and trouble free life. Under normal conditions, will require no
routine maintenance or service beyond the inspection and test regime of BS5266-1. Both mains supply and battery protection fusing is incorporated internally. Should access to these or any other
part of the circuitry be required this must be undertaken only by suitably qualied person. Special care must be taken when removing the cover to circuitry and battery. Only replacement components
authorised by the company must be used. Disposal of replaced components should be in accordance with the component manufacturers instructions.
You can help protect the environment. Please remember to respect the local regulations: hand in the non-working electrical equipment to an appropriate waste disposal centre. The packaging material is recyclable. Dispose of the packaging in an environmentally friendly manner and make it available for the recyclable material collection service.
Month Test Type First Year Second Year Third Year Fourth Year Fifth Year
Sign Date Sign Date Sign Date Sign Date Sign Date
January Functional
February Functional
March Functional
April Functional
May Functional
June Functional
July Functional
August Functional
September Functional
October Functional
November Functional
December 3 hour
IP65
jcc.co.uk
V10_JUNE_2022_RS
rchase.
sis:
Emergency test record sheet
Loading...