DIGITAL MICRON GAUGE CLEANING & REPAIRS
JB INDUSTRIES
If your micron gauge is acting erratic, for instance, vacuum readings at atmosphere, readings rising and falling during a steady pull down or holding vacuum, cleaning the sensor may be necessary.
Cleaning the sensor
Tools
Rubbing alcohol*
Step 1
Liberally pour rubbing alcohol into the sensor.
Step 4
Dump excess alcohol.
After following steps 1-6 if you’re still experiencing issues, an alternate method to clean the sensor is to soak the sensor in alcohol overnight.
Step 2
Cover tting opening with your thumb or nger.
Step 5
Repeat steps 1-4 at least twice.
Step 3
Agitate the rubbing alcohol in the sensor to clean by shaking for a few seconds.
Step 6
Allow to air dry or pull vacuum on gauge to expedite drying.
Use Isopropyl (Isopropanol) alcohol only. Do NOT use Denatured alcohol as it leaves residue after evaporation. Do not use other solvents as they may be too corrosive and permanently damage the sensor and or its surroundings. Isopropyl of 90% pure or better should be used. Hardware stores will sell 99% pure, found near the paint thinners & solvents.
2
TM
DIGITAL MICRON GAUGE CLEANING & REPAIRS
JB INDUSTRIES
If you have trouble getting an accurate reading after cleaning the sensor, please check your o-ring for damage, wear, or to see if it is missing.
Replacing the O-Ring
Tools
O-ring probe or thin implement & P90009 Replacement O-ring.
Step 1
Using probe get under the rubber O-ring.
Step 3
Place O-ring in the grove.
Step 2
Remove O-ring.
Step 4
Press O-ring to securely seat it in the groove.
TM 3
CONNECT WITH US
WWW.JBIND.COM
TM
JB INDUSTRIES INC.
Aurora IL 60505 USA
©2016 JB Industries, Inc.