JB DM4-R REVOLVER, DM4-Z ZEPPELIN Operating Manual

Page 1
OPERATING MANUAL
DIGITAL MANIFOLDS
DM4-R/DM4-Z
DM4-R REVOLVER®
®
Page 2
2
JB INDUSTRIES • DM4 Operating Manual • 630.851.9444 • sales@jbind.com
Z E R O
JB INDUSTRIES
SPECIFICATIONS
Pressure Display Range 29 inHg to 400 psig
Temperature Display Range 100° F to 200° F
Operating Temperature -10° F to 120° F
Maximum Overpressure 1000 psi
Power Supply Three AA alkaline batteries
Refrigerant Data Source NIST REF PROP and Manufacturer Data
Dimensions 14" length x 13" width x 8.5" depth
Shipping Weight 9.75 lb (4.42 kg)
Warranty 1 year
FEATURES
Power Button
Zero Button
Display Screen
Hook
Up/Down
Arrow Buttons
DM4-R REVOLVER
®
(shown)
or DM4-Z ZEPPELIN
®
Battery Cover (back)
Universal
K-Type Clamp
Thermocouples
Enter Button
Page 3
3
JB INDUSTRIES • DM4 Operating Manual • 630.851.9444 • sales@jbind.com
OPERATING INSTRUCTIONS
Install Batteries
Remove battery cover with a Phillips head screwdriver. Insert three AA batteries.
Power Settings
To power on, press the POWER button for two seconds until unit beeps and displays welcome screen. To power off, press and hold the POWER button for two seconds until unit beeps and powers down.
MAIN MENU SETTINGS
Access Main Menu
From home screen press the ENTER button.
Main Menu Options
• Favorite List
• Refrigerant
• Back Light
• Display Mode
• Pressure Unit
• Temp Unit
• User Cal
• Factory Setting
Exit Main Menu
Press ZERO button until home screen is displayed.
Display Screen Features
High Side
Pressure
Low Side Pressure
Saturation
Temperature
Saturation Temperature
Subcooling Calculation
Superheat Calculation
Actual Temperature
High Side
Actual Temperature Low Side
RefrigerantRefrigerant
Page 4
4
JB INDUSTRIES • DM4 Operating Manual • 630.851.9444 • sales@jbind.com
Add Refrigerant to Favorites
1. Press the ENTER button to reach the main menu
2. Select and highlight Refrigerant
3. Press the ENTER button
4. Scroll to the desired refrigerant using UP s and DOWN t arrows
5. Press the ENTER button
6. Scroll to Add Favorite
7. Press ENTER button
8. On the left side of the screen “Data Saved” will appear when the list is updated
Remove Refrigerant from Favorites
1. Press the ENTER button to reach the main menu
2. Select and highlight Favorite List
3. Press the ENTER button
4. Scroll to the desired refrigerant using UP s and DOWN t arrows
5. Press the ENTER button
6. Scroll to Delete Favorite
7. Press ENTER button
8. On the left side of the screen “Data Saved” will show when the list is updated
Scroll through Favorites
From the home screen press the UP s and DOWN t arrows Once the favorite refrigerant is reached, all readings will correlate to selected refrigerant
Change Back light
1. Press the ENTER button to reach the main menu
2. Select and highlight Back Light
3. Press the ENTER button
4. Scroll to the desired time using UP s and DOWN t arrows
5. Press the ENTER button
6. On the left side of the screen “Data Saved” will show when the back light is updated
Change Display Mode
1. Press the ENTER button to reach the main menu
2. Select and highlight Display Mode
3. Press the ENTER button
4. Scroll to the desired display mode using UP s and DOWN t arrows
5. Press the ENTER button
6. On the left side of the screen “Data Saved” will show and the screens will be updated
Page 5
5
JB INDUSTRIES • DM4 Operating Manual • 630.851.9444 • sales@jbind.com
Change Pressure Units
1. Press the ENTER button to reach the main menu
2. Select and highlight Pressure Unit
3. Press the ENTER button
4. Scroll to the desired unit using UP s and DOWN t arrows
5. Press the ENTER button
6. On the left side of the screen “Data Saved” will show and the screens will be updated
Change Temperature Units
1. Press the ENTER button to reach the main menu
2. Select and highlight Temp Unit
3. Scroll to the desired unit using UP s and DOWN t arrows
4. Press the ENTER button
5. On the left side of the screen “Data Saved” will show and the screens will be updated
Zero Pressure to Atmosphere
To zero pressure to atmosphere press the ZERO button on the display The unit will beep to acknowledge the transducers are zeroed to atmosphere
User Defined Calibration (Temperature)
1. Press the ENTER button to reach the main menu
2. Select and highlight User Cal
3. Press the ENTER button
4. Select and highlight Temperature Cal
5. Select ADJ Left for the left thermocouple or ADJ Right for the right thermocouple
6. Press the ENTER button
7. Use the UP s to change the temperature reading up one digit
8. Use the DOWN t to change the place of the cursor
9. Press ENTER button when complete
Reset User Defined Calibration (Temperature)
1. Press the ENTER button to reach the main menu.
2. Select and highlight User Cal
3. Press the ENTER button
4. Select and highlight Temperature Cal
5. Press the ENTER button
6. Select Reset Left for the left thermocouple or Reset Right for the right thermocouple
7. Press the ENTER button
8. This will reset to factory default settings; to reset both at the simultaneously select FACT Default
9. Press ENTER button when complete
Page 6
6
JB INDUSTRIES • DM4 Operating Manual • 630.851.9444 • sales@jbind.com
User Defined Calibration (Pressure)
1. Press the ENTER button to reach the main menu
2. Select and highlight User Cal
3. Press the ENTER button
4. Select and highlight Pressure Cal
5. Press the ENTER button
6. Select ADJ Left for the left pressure transducer (low side) or ADJ Right for the right pressure transducer (high side)
7. Press the ENTER button
8. Use the UP s to change the pressure reading up one digit
9. Use the DOWN t to change the place of the cursor
10. Press ENTER button when complete
Reset User Defined Calibration (Pressure)
1. Press the ENTER button to reach the main menu
2. Select and highlight User Cal
3. Press the ENTER button
4. Select and highlight Pressure Cal
5. Press the ENTER button
6. Select Reset Left for the left pressure transducer (low side) or Reset Right for the right pressure transducer (high side)
7. Press the ENTER button
8. This will reset to factory default settings; to reset both at the simultaneously select FACT Default
9. Press ENTER button when complete
Zero Pressure Transducers
1. Press the ENTER button to reach the main menu
2. Select and highlight User Cal
3. Press the ENTER button
4. Select and highlight Pressure Cal
5. Press the ENTER button
6. Select Zero Left for the left pressure transducer (low side) or Zero Right for the right pressure transducer (high side)
7. Press the ENTER button
Troubleshooting
For advanced diagnosis contact JB Industries.
Page 7
7
JB INDUSTRIES • DM4 Operating Manual • 630.851.9444 • sales@jbind.com
EVACUATION AND CHARGING
CAUTION: Always consult
manufacturer service manual or instruction sheet for recommended procedures
MANIFOLD COMPRESSOR
A B C D E F
LOW SIDE HIGH SIDE
EVACUATION
PORT
CHARGING
PORT
DISCHARGE
SERVICE VALVE
SUCTION
SERVICE VALVE
BLUE RED BLACK YELLOW RED BLUE
To observe operating pressures
Closed Closed Closed Closed
Back seated and cracked open
Back seated and cracked open
To charge refrigerant through suction valves
Open Closed Closed Open
Back seated and cracked open
Front seated
To charge oil through suction valve
Open Closed Open Closed Back seated Front seated
To charge liquid refrigerant through discharge valve
Closed Open Closed Open Midway open
To build low pressure; for control setting or leak detecting
Open Open Closed Closed
Back seated and cracked open
Midway open
To purge refrigerant from discharge valve
Closed Open Closed Open
Back seated and cracked open
To evacuate with auxiliary vacuum pump
Open Open Open Closed Midway open Midway open
A
C
D
B
E
F
Z E R O
JB INDUSTRIES
DM4-R
Page 8
8
JB INDUSTRIES • DM4 Operating Manual • 630.851.9444 • sales@jbind.com
PARTS LIST
RETURN FOR REPAIR
Every effort has been made to provide reliable, superior quality products. However, in the event your instrument requires repair, please contact JB Customer Service Department to obtain a Return Goods Authorization (RGA) number. Ensure that all returned products are packed to avoid any damage in shipment. Paperwork should be placed in a separate plastic bag and should include JB’s assigned RGA number, a description of the problem and any customer assigned repair or purchase order number, if applicable.
Contact Customer Service for RGA number:
800.323.0811 Toll
800.552.5593 Toll Fax
Products should be shipped with freight prepaid to:
JB Industries
RGA#_________
601 N. Farnsworth Ave. Aurora, IL 60505
630.851.9444 Tel
630.851.9448 Fax
WARRANTY
DM4 Digital Manifolds are warrantied against defects in materials and workmanship for 1 year from date of purchase. JB products are guaranteed when used in accordance with our guidelines and recommendations. Warranty is limited to the repair, replacement, or credit at invoice price, (our option) of products which in our opinion are defective due to workmanship and/or materials. In no case will we allow charges for labor, expense or consequential damage. Repairs performed on items out of warranty will be invoiced on a nominal basis; contact wholesaler for details. Additional product information available online at www.jbind.com.
WARNING: This product can expose you to chemicals including lead which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov.
JB INDUSTRIES
Part No. DM4-01-308 0418
©2018 JB Industries, Inc.
PART NO. DESCRIPTION
DM4-R REVOLVER® digital manifold with 60" KOBRA® 4-pack hose set
DM4-Z ZEPPELIN
®
digital manifold with 60" KOBRA® 4-pack hose set
DM4-CS Digital manifold carrying case
DM4-TC Temperature clamps
DM4-BRK Brackets for clamps and strap
DM4-STRP Strap with hook
DM4-BT Protective boot