Jay UDF, SCI-B, RSRA, URE Installation And Operating Instructions Manual

Page 1
Page 1 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
Wireless emergency stop system
Installation and operating instructions
manual
- TRANSLATED IN ENGLISH FROM ORIGINAL FRENCH VERSION -
RSRA
SCI-B
URE
UDF
Page 2
Page 2 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
TABLE OF CONTENTS
1 Guidelines for safe use ......................................................................... 4
2 Presentation of RADIOSAFE emergency stop system ....................... 6
2.1 Unpacking the product ............................................................................................................ 6
2.2 Configuration on delivery ........................................................................................................ 6
2.3 Product code ............................................................................................................................ 7
3 Technical characteristics ...................................................................... 7
3.1 Transmitter URE ....................................................................................................................... 7
3.1.1 Identity code ......................................................................................................................................................... 7
3.1.2 Electronic key ....................................................................................................................................................... 7
3.1.3 « Activity monitoring » function ............................................................................................................................. 8
3.1.4 Battery charge ...................................................................................................................................................... 8
3.2 Receiver RSRA ......................................................................................................................... 9
3.3 IR startup option (IR) .............................................................................................................. 11
3.3.1 Presentation of infrared module (UDF) ............................................................................................................... 11
3.3.2 Positioning the infrared module UDF .................................................................................................................. 12
3.4 Configuring the receiver ................................................................................................ ........ 12
3.4.1 Choice of receiver (RSRA) program ................................................................................................................... 12
3.4.2 Definition of receiver indicator lights and diagnostic outputs .............................................................................. 13
3.5 Presentation of charger ......................................................................................................... 14
4 Operating principle .............................................................................. 15
4.1 Intervention in equipment area. ............................................................................................ 15
5 Product safety and intervention conditions ................................ ...... 15
5.1 Product safety ................................................................................................ ........................ 15
5.2 Intervention conditions .......................................................................................................... 15
5.3 Indications .............................................................................................................................. 16
6 Receiver wiring diagram according to intervention condition ........ 16
6.1 Control of machine without area access control. ................................................................ 16
6.2 Wiring diagram ....................................................................................................................... 16
6.2.1 Diagram of functions according to program selected. ......................................................................................... 18
6.2.2 Control of machine with area access control. ..................................................................................................... 22
6.2.2.1 Recommended wiring diagram ......................................................................................................................................... 22
6.2.3 Diagram of functions according to program selected .......................................................................................... 24
7 Installation recommendations ............................................................ 26
7.1 General information ............................................................................................................... 26
7.2 Choice of utilization frequency ............................................................................................. 26
7.3 Receiver and charger installation precautions. ................................................................... 26
7.3.1 Special case – Equipment area access .............................................................................................................. 27
7.3.2 Receiver antenna installation position ................................................................................................................ 27
8 Commissioning .................................................................................... 28
8.1 Commissioning precautions ................................................................................................ . 28
8.2 Starting up the radio remote control ..................................................................................... 28
8.3 Configuring the transmitter. .................................................................................................. 29
8.3.1 Procedure for programming frequency ............................................................................................................... 29
8.3.2 Procedure for programming « transmitter activity monitoring » duration. ........................................................... 30
8.3.3 Procedure for « locking – unlocking » access to transmitter programming ................................ ......................... 31
8.3.4 Procedure for « validation of an electronic key ». ............................................................................................... 32
Page 3
Page 3 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
9 Maintenance ......................................................................................... 33
9.1 Spare parts ............................................................................................................................. 33
9.2 Fault isolation ......................................................................................................................... 33
9.2.1 Transmitter fault isolation.................................................................................................................................... 33
9.2.2 Fault isolation relative to receiver parameter definitions or configuration ........................................................... 34
9.2.3 Receiver input fault isolation ............................................................................................................................... 35
9.2.4 Receiver radio function fault isolation. ................................................................................................................ 36
10 Warranty ............................................................................................ 37
11 CE declaration of conformity ........................................................... 38
12 Appendix A : Intervention in equipment area ................................. 39
12.1 Purpose ............................................................................................................................... 39
12.2 Need ..................................................................................................................................... 39
12.3 Application diagram ........................................................................................................... 39
12.4 Wiring diagram .................................................................................................................... 39
12.5 Procedure. ........................................................................................................................... 40
12.6 Area access in manual mode ............................................................................................. 40
Page 4
Page 4 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
1 Guidelines for safe use
The European Machinery Directive states that a radio remote control must be considered
both as a control unit and as a safety component for stopping a system. Safe use of a radio remote control therefore calls for strict compliance of all applicable rules.
For maximum safety when handling the radio remote control, be sure to carefully observe
the instructions given in this manual.
The operator must be appropriately trained and qualified for use of the radio remote
control.
On an installation, an emergency stop button which is visible must always be
operational. When the transmitter is not being used, it must be placed on its charger ; its
emergency stop button is therefore no longer operational. For this reason, it is important to install the charger so that the transmitter emergency stop button is not visible when the transmitter is placed on its charger.
The operator must have an uninterrupted view of the manoeuvre which he is
performing. When the direct field of view is insufficient, the systems controlled must be
equipped with auxiliary devices improving visibility. When several moving systems are controlled simultaneously, the systems must be equipped to reduce the consequences of a possible collision. If all the safety areas are not always visible simultaneously, one of the following startup modes must be used :
Manual startup using a wired ON pushbutton placed at a location from which all the
safety areas are visible.
Radio-controlled startup by infrared. The IR receiver must also be placed to force the
user to go to a location where all the safety areas are visible.
Never leave the transmitter unattended in any haphazard location, especially when it is
switched on.
Never leave the transmitter on the ground. If doing so becomes indispensable, press the
stop palm switch on the transmitter.
If several radio remote controls are used at the same site, different radio frequencies
should be used, spaced by at least 2 channels (example, channels 5, 7, 9,. ….) of 5 channels if several systems are operating together within a radius of 10 meters.
When not in use, for safety purposes, remove the electronic key.  Do not forget to recharge the battery when discharged. Do not use the transmitter when it is in charge.In the event of a malfunction, immediately shut down the installation by pressing the
emergency stop palm switch on the transmitter.
Ensure your equipment is properly serviced and perform periodic checks in accordance
with the intensity of use of your equipment.
Page 5
Page 5 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
A functional test (automatic or manual) to detect failures shall be performed within the
following test intervals:
at least every month for PL e with Category 3 or Category 4 (according to EN ISO
13849-1) [or SIL 3 with HFT (hardware fault tolerance) = 1 (according to EN 62061)];
at least every 12 months for PL d with Category 3 (according to EN ISO 13849-1) [or
SIL 2 with HFT (hardware fault tolerance) = 1 (according to EN 62061)].“
Important :
As installer or manufacturer of the machine, you are also required to indicate these guidelines for safe use in your own user manual.
Caution :
This manual describes the functions of the RSRA / A002 receivers with a software version PN5910_BI_A_01_0F_01_03 or higher. Operating modes 8 and 9 (§ 6.2.2 «Control of machine with area access control») have been modified with respect to the previous versions of the RSRA modules. The modules having this new function carry the type designation « RSRA / A002 » engraved on the side of the housing. The software version is glued to the back of the housing.
Page 6
Page 6 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
2 Presentation of RADIOSAFE emergency stop system
2.1 Unpacking the product
The RADIOSAFE product comprises:
One receiver RSRA (1)  One transmitter URE (2)  One 24VDC-5VDC voltage adapter UCC4 (3)  One charger support SCI-B (4)  Two sheets of labels UWE202 and UWE207 (5)  One key identification sheet (6)  One CD (or USB memory key) including the installation and operating instructions manual (7)  One BNC elbow VUB060 (8)  One antenna extension VUB170 (9)  One ¼ quarter wave antenna VUB084 (10)
2.2 Configuration on delivery
Product
• The product is supplied factory-set for radio channel 01, i.e. 433.100 MHz. Transmitter
The transmitter “activity monitoring” function (transmitter automatically stops if not used for an extended period of time) is factory-set for 15 min.
To modify the duration or change the counting unit to « seconds », refer to the “Transmitter activity monitoring function”
section.
• Electronic key number :
- A unique number is engraved on the key.
IMPORTANT : When unpacking the products, be sure to stick the electronic key identification label on the key sheet supplied with the product.
• Locking the transmitter :
- The transmitter is supplied « unlocked » ; the « activity monitoring » and « frequency » configurations corresponding to the electronic key can be directly modified by a qualified operator.
Receiver
• The receiver has 10 different application programs. It is supplied factory-set for program « 0 » selectable by 2 selectors "B". For information on the different programs, refer to the section entitled “Choice of receiver (RSRA) program”.
• The receiver has a time delay function. It is supplied with a time delay of 10 seconds for transmitter take-over according to the position "0" of 2 selectors A. Refer to the section covering “adjustment of time delay” if this duration is not sufficient.
1 2 3
4 5 6
7 8 9
10
Page 7
Page 7 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
2.3 Product code
Refer to the technical sales brochure ref. E800 For all information concerning the product code. This information is accessible on our internet site at http://www.jay-electronique.com/
3 Technical characteristics
3.1 Transmitter URE
Housing
Material Tightness
ABS IP65
Radio Carrier Frequencies Frequency band HF power Average range
Complies with ETS 300 220 UHF, frequency modulated (FM) 64 programmable frequencies
433.1 to 434.675 MHz < 10 mW (without license) 150 m in typical industrial environment 400 m in open space
Battery Storage type Charge / Discharge cycles Fast charge time Full charge time
Lithium ion 500 cycles min. 2h max. (80%) 4 h max. (100%)
Endurance For typical use of function buttons
50 H at 50% utilisation at +20°C Storage temperature
-20°C to +50°C
Battery charge temperature range
0°C to +40°C
Caution ! : Fast charging outside this temperature range can result in damage to battery.
Operating temperature range
-20°C to +45°C
Weight (with battery)
240 g
Dimensions
46 x 78 x 143 mm
3.1.1 Identity code
The transmitter and receiver are linked by a frequency and an identity code. A receiver will only recognize and execute commands from the associated transmitter (same identity code and frequency).
- The frequency is programmable by the user
- The transmitter identity code is contained in the electronic key and in the transmitter (URE).
- The receiver identity code is unique and frozen ; this code is programmed in factory. The identity code can have 65536 different combinations.
3.1.2 Electronic key
The electronic key used with the RADIOSAFE radio remote control system ensures a dual function :
- It enables startup of the transmitter while limiting access to the remote control to trained, qualified persons only.
- It contains all the information defined for operation of the product, including :
- the last frequency programmed
- the system identity code
- The “activity monitoring” function
- the configuration of the function buttons on the transmitter and the type of button (button or rotary).
- When removed, the electronic key prevents use of the transmitter and cuts off the transmitter power supply. If the identity code of the electronic key matches the identity code stored in the URE, the transmitter can be started up.
- If the identity code of the electronic key and that of the transmitter do not match, the transmitter indicates the problem by its two indicator lights (3 flashes); you must then perform the key programming procedure.
Page 8
Page 8 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
In the event of a transmitter failure
You can recover the electronic key and connect it to a « maintenance » transmitter which buttons are configured in the same way as those of the failed transmitter. When this is not the case, the differing buttons will not operate. To perform this procedure, you must re-program the identity code of the key in a new transmitter (URE) by following the procedure described in the corresponding section.
In the event of loss of electronic key
You can order a new electronic key (reference RSWE21 B), by specifying the unique 6-digit number of the old key on the order (written down when you unpacked your product). Caution, the initial key is supplied programmed on frequency channel 01 with « activity monitoring » duration set for 15 minutes. You must define these parameters again on your new key.
3.1.3 « Activity monitoring » function
The « Activity monitoring » function automatically deactivates the remote control (radio transmission cut off) when the buttons (BPSV, BPDV and “ON”) are not actuated for a duration defined for N minutes or seconds. The N parameter is configurable by the user and can take the values of 01 to 98 minutes or seconds. In its standard configuration, the time delay unit is defined for minutes. On delivery, this duration is defined for 15 minutes.
- If the time delay unit is defined for minutes and the N value is defined for 99 minutes, the transmitter considers that the time delay duration is infinite (up to complete discharge of its battery).
- If the time delay unit is defined for seconds (configured by you), and the N value is defined for 99 seconds, the transmitter will be deactivated after 99 seconds if none of the function buttons or the “ON” button is used.
Note 1 : The switches (COM2, COM3) do not act on the « Activity monitoring » function. Note 2: The duration and the type of counting unit for the « Activity monitoring » function (minute or second) are stored in
the electronic key of the transmitter (URE).
3.1.4 Battery charge
To ensure optimum battery performance, start by charging and fully discharging the battery the first time. During the charge, the orange indicator light on the transmitter comes on continuously ; the green indicator light
indicates the charge level :
Green indicator light flashes : fast charge Green indicator light on steady : slow or upkeep charge (URE charge greater than 80%)
Display of transmitter battery charge status (when not charging)
Two battery charge status display functions are provided on the transmitter.
- On power up of the remote control (emergency stop palmswitch up), the orange indicator light on the transmitter indicates the charge level of the storage batteries :
Orange indicator light off : ........................... battery charge is > 50%
Orange indicator light flashes slowly : ....... battery charge is between 50% and 10 %
Orange indicator light flashes fast : ........... battery must be recharged (battery charge < 10%)
Orange indicator light on for 2 seconds : ... transmitter initialization as soon as the stop palmswitch is raised.
- During operation of the remote control (radio transmission), a LOW BATT level (charge < 10%) is indicated by the orange indicator light which flashes quickly. This indication is used to inform you that the remote control will soon be unavailable (within less than 15 minutes).
Display of transmitter battery charge status (transmitter charging)
Transmitter status
Red indicator light
Green indicator light
Function
Battery charging
ON
Flashing
Fast charge
Battery charging
ON
ON
Slow or upkeep charge
Page 9
Page 9 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
3.2 Receiver RSRA
Housing ABS, black/yellow
IP 40
Weight 495 g (approx.) Dimensions 67 x 84 x 129mm (not including antenna) Operating temperature range 0 °C to + 50 °C Storage temperature range - 30 °C to + 70 °C Connection Spring terminals for wires 0.08² to 2.5²
Characteristics compliant with ETS 300 220
Frequency 64 frequencies programmable in 433-434 MHz Antenna Sensitivity < -100 dBm
Power supply voltage Un 24 VDC Voltage range (at max., 5% ripple) 0.85 to 1.15 Un Consumption max., 120 mA (Static output, not loaded)
Contacts 3 NO Type of contacts Linked contact relays Pull-in time at Un
Automatic start 800 ms max. (power up)
Automatic restart 70 ms max.
Manual start 110 ms max.
Trip time (reaction)
S12-S14, S22-S24, S32-S34 25 ms max.
Stop (remote control): 170 ms max.
Assigned output voltage AC250V Low voltage switching
> 100 mV
Thermal current Ith 5 A Switching capacity
Per AC 15 : AC 3A/230 V for NO contacts EN60947-5-1
AC 2A/230 V for NC contacts EN60947-5-1
Per DC 13 : DC 8A/24 V at 0.1 Hz EN60947-5-1
Electrical service life
Per AC15 at 2A, AC230V 100 000 cycles EN60947-5-1
Short-circuit rating
Maximum fuse rating 6 A gL EN60947-5-1
Mechanical service life 10 x 10^6 cycles
Type of outputs Static outputs, PNP Nominal voltage Un (A3, A4) DC 24 V Voltage range 0.85 to 1.15 Un Output voltage DC 24V, max. 100mA thermal
max. 400 mA for 0.5s Overload and temperature protection
Indicators 2 yellow indicator lights: state of safety module
2 red indicator lights: state of safety relays
1 green indicator light: radio reception quality
Radio characteristics
Electrical characteristics
1 red indicator light: wrong identity code or diagnostic
Secure relay outputs (terminals 13-14, 23-24, 33-34 or 31-32)
Static outputs (terminals 48, 58, 17, 27, 37, 47, 57, 67, 77)
1/4 wave, as accessory, plugs in to BNC connector
Mechanical characteristics and environmental withstand capacity
Page 10
Page 10 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
The RSRA receiver has the following outputs : 100 mA opto-coupled static outputs :
6 function outputs Safety relays :
2 guided-contact safety relays « 3 N0 ».
Safety outputs and inputs
Terminals
Function
A1+
24VDC power supply for safety modules of receiver (RSRA)
A2-
Common ground
48
24V static output: safety module status
58
24V static output: safety module status ( of witch catch transmitter of charger)
S11 S12
Input 1 for 1st emergency stop or 1st safety barrier
S13 S14
Input 2 for 1st emergency stop or 1st safety barrier
S21 S22
Input 1 for 2nd emergency stop or 2nd safety barrier
S23 S24
Input 2 for 2nd emergency stop or 2nd safety barrier
S31 S32
Input for test of 1st charger
S33 S34
Input for test of 2nd charger
S42
Input for wired “ON” button
Y1 Y2
Input for auxiliary relay return loop
13 14
1st safety output (NO contact)
23 24
2nd safety output (NO contact)
33 34
3rd safety output (NO contact)
Removable connection
block, screw terminals
White. lights, V1 & V2
«Safety module status»
Green ind. lights, K1 and K2
«Safety relay status»
Green indicator light V4
«Radio reception quality»
Antenna BNC connector
Red indicator light V3
«wrong identity code»
Page 11
Page 11 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
Static outputs assigned to remote control
Terminals
Function
A3+
24VDC power supply for static outputs assigned to remote control
A2-
Common ground
17
Detection transmitter on charger
27
B1, 1st point of contact
37
B2, 1st point of contact
47
B1 or B2, 2nd point of contact (1)
57
B3, 1st point of contact (1)
67
B4, 1st point of contact (1)
77
B3 or B4, 2nd point of contact (1)
(1) = Only for pushbuttons
Connection for IR module (UDF)
Terminals
Function
A5+
12 VDC output
IR
Receiver signal
A2-
Common ground
3.3 IR startup option (IR)
As an added feature to start up in normal mode, IR startup is performed by pointing the transmitter toward an IR module located on the equipment to be controlled.
When this option is chosen, the receiver waits for a dual condition before activating the safety and function relays :
1st condition :
- Radio reception of a message requesting startup sent by transmitter to receiver.
2nd condition :
- IR reception of same startup message sent simultaneously from transmitter to receiver via IR module. The IR emission takes place when the green “ON” button is pressed. At the end of the startup phase, the system operates on reception of radio messages only.
3.3.1 Presentation of infrared module (UDF)
The UDF infrared module is supplied with a shielded 10m cable which is connected to the receiver connectors. Connection:
Black wire : A2­White wire : A5+ Blue wire : IR
The link can be extended up to 2x10m, i.e. 30m in all by means of the UDWR10 accessory comprising a shielded cable and its connector.
The wiring of the IR module must be separate from the power cables and all other sources which may generate interference (power regulator, for example).
Page 12
Page 12 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
3.3.2 Positioning the infrared module UDF
3.4 Configuring the receiver
The receiver module inputs and outputs can be configured in accordance with your applications. To configure this parameter, you must remove the front panel of the product.
3.4.1 Choice of receiver (RSRA) program
The receiver has 10 programs which are user-definable by two « B » selectors.
Selector
« B »
position
Reset mode
for
protection
circuits
« S11-S14 »
and « S21-
S24 » (1)
Reset
mode after
radio
emergency
stop (2)
wireless
Number of
wired
emergency
stops
Dangerous
area access control
IR startup
recommended
Remarks
0
Manual
Radio 2 NO
YES
1
Manual
Control
panel
2
NO
NO
2
Automatic
Radio 2 NO
YES
.
3
Automatic
Control
panel
2
NO
NO
4
Manual
Radio 2 NO
YES
Special application.
5
Not used
6
Not used 7
Not used
8
Manual
Radio 1 YES
YES
Receiver module controls access to dangerous area with radio remote control.
9
Manual
Control
panel
1
YES
NO
Receiver module controls access to dangerous area with radio remote control.
Page 13
Page 13 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
(1) Reset mode for protection circuits « S11-S14 » and « S21-S24 »
Manual start : Once the protection circuits connected across S11-S14 and S21-S24 are again active, you must restart the equipment using the ON button wired on the control panel.
Automatic start : Once the protection circuits connected across S11-S14 and S21-S24 are again active, the system is automatically restarted provided the remote control is on its charger.
(2) Reset after wireless emergency stop
Control panel : Following an emergency stop using the radio remote control, the equipment must be restarted using the ON button wired on the control panel.
Wireless : Following an emergency stop using the radio remote control, the equipment can be restarted using the radio remote control without returning to the control panel.
Setting transmitter activation time and gate or safety barrier inhibit time
The transmitter activation, protected area access request and gate or safety barrier inhibit times are configurable by two « A »selectors. The two selectors must always be placed in the same position.
Position of 2 « A » selectors:
Position of
"A" selectors
0 1 2 3 4 5 6 7 8
9
Transmitter activation or access request time
5S
6S
7S
8S
9S
10S
15S
20S
25S
30S
Inhibit time (1) (muting)
5S
10S
20S
40S
1min
2min
3min
4min
5min
10min
(1) : maximum gate or safety barrier inhibit time.
3.4.2 Definition of receiver indicator lights and diagnostic outputs
The various states and faults of the safety receiver are indicated by 4 leds and by 3 static outputs.
Ind. light state
Off
Flashing
On steady
White ind. light
V1
All outputs inactive subsequent to a system fault
Error code : system fault. All outputs inactive
No system fault
White ind. light
V2
- charger contacts closed and relays activated
- all outputs inactive subsequent to a system fault
- Flashing as for output 58 if Led "V1" is on
- system fault if Led "V1" is off or flashing
Safety outputs activated
Red ind. light
V3
Not applicable
- Error code: error in reception module
- Flashing regularly: reception of incorrect identity code
Link with RS232 interface
Green ind. light
V4
No radio signal
-Flashing irregularly : poor reception
- Error code: error in reception module
Good radio reception
Green ind.
lights K1 and
K2
Safety relays K1 and K2 inactive
Not applicable
Safety relays K1 and K2 activated
Page 14
Page 14 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
2 NO contacts
N0 contact
connection
terminals
Ind. light state
Off
Flashing
On steady
Static output
17
Safety relays inactive or
charger monitoring
contacts open or
remote control
activated
Not applicable
Remote control
inactive, charger
monitoring contacts
closed and safety
relays activated
Static output
48
- Safety outputs activated
- System fault
Flashing regularly:
on standby for reactivation by
one of the ON pushbuttons
No output activation
authorization
Static output
58
Charger contacts
closed and relays
activated
- All outputs inactive
subsequent to a system
fault
- Error code. One of the safety functions does not allow activation of
safety outputs
- Flashing rapidly to indicate that transmitter must be
activated.
- Flashing slowly during area access inhibit condition
Safety outputs
activated
The 2 white indicator lights« V1 and V2 » indicate the state of the receiver safety functions.
o Receiver state when transmitter is on its charger: "V1" on and "V2" off. o Receiver state when transmitter is active: "V1 and V2" on.
3.5 Presentation of charger
In addition to charging the transmitter battery, the charger also has a transmitter detection function for detection of a transmitter when not used. When any of programs 0 to 4 are selected, the 2 NO contacts must be wired on inputs S31-S32 and S33-S34. If programs 8 or 9 are selected, the 2 NO contacts must be wired in series on input S31-S2 (See wiring diagram in appendix).
Page 15
Page 15 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
4 Operating principle
The safety receiver is equipped with a secure wireless reception module designed to interpret signals from a radio transmitter. In addition, depending on the program selected by the two B switches, the receiver (RSRA) will have one or two inputs (S31-S32 and S33-S34) with two control contacts indicating that the remote control is placed on its charger or not:
Transmitter « inactive » on its charger
When the transmitter is on its charger, the charger contacts are closed. Only the wired elements are taken into account
for protection. Output 58 is inactive (associated “V2” LED is off). Static outputs 27 to 77 remain inactive. Safety relays
« K1, K2 » are deactivated if the safety receiver has not been reset.
Transmitter « active » removed from its charger.
When the transmitter is removed from the charger, the « transmitter presence » contacts on the charger open and the receiver safety relays remain active. Output 58 and the "V2" LED flash rapidly to indicate that the remote control must be activated. The receiver safety relays
are deactivated if the transmitter is not activated after the maximum period of time set on the “A” switches has elapsed.
The safety relays are also deactivated if one of the charger contact remains close. Once the remote control is activated, output 58 and the “V2” LED come on steady.
From this moment on, the emergency stop function on the transmitter also acts on the receiver. So long as the safety relays are active, the auxiliary buttons on the remote control control the 6 static outputs (27 to 77) of the module. Depending on the operating mode selected, the safety receiver can also be activated by the « ON » button on the transmitter, if the charger contacts are open.
4.1 Intervention in equipment area.
See procedure in appendix
5 Product safety and intervention conditions
5.1 Product safety
The product is designed to satisfy the following requirements :
Wireless Emergency stop system in compliance with the standards:
o DIN ISO 13849-1 (2008) : Category 4 / Performance Level e o EN 61508-1 (-7 :2001): SIL 3 o CE declaration of conformity by notified body.
Key enabling use by a qualified operator.  Detection of presence of transmitter on charger, inhibiting operation of equipment if transmitter is not placed on
its charger after use.
5.2 Intervention conditions
The interventions with the product will be made according to provisions of the articles R233-8 and R233-9 of the employment law. To respect these rules, an organization of the work and the operating modes must be defined to protect the safety of the operators. Only the authorized persons can intervene in equipment area. A product can be used in two different modes described below.
« Monitoring – Diagnostic » mode Applications concerned.
This product can be used as a wireless stopping system by qualified personnel performing maintenance or inspection on machinery. Such machinery is generally mobile or large, preventing use of conventional wiring, and for which a diagnostic in downgraded operating mode may be required (example: conveyor or load transfer area). Access to this equipment in operation in the “monitoring – diagnostic” mode is acceptable provided:
The risk assessment shows that the intervening technician can be safety cleared in the event of an immediate
danger.
The equipment wireless emergency stop system does not create any additional hazard.  The operator can regularly press a « Activity monitoring » button requiring him to keep the transmitter in hand.
No change of tool or adjustment is performed by the intervening technician.
Page 16
Page 16 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
When these 4 conditions are satisfied, the operator can use the product. If any of the conditions for operation in the « monitoring – diagnostic » mode are not observed, the equipment must be stopped and the radio remote control must be used in manual equipment operating mode.
The « equipment area access » is managed by the safety receiver. Two inputs are provided on the receiver to temporarily inhibit the gate or barrier. If the speed of the equipment must be reduced and controlled, the signals supplied on outputs 58 and 17 indicate when the user has picked up or set down his transmitter on the charger.
« Manual » mode
This manual operating mode is possible using the product insofar as command of equipment movements using function buttons associated to an emergency stop function on the transmitter is sufficient to stop the equipment controlled if necessary.
The transition from automatic to manual control of the equipment can be achieved by removing the transmitter from the charger. Removal of the transmitter is detected by the safety receiver which supplies 2 information signals to the machine control station (output 17 and 58). So long as the transmitter has not been placed on its charger, the equipment remains in manual mode.
5.3 Indications
In certain cases of application for checking the access zone, an indication " indicator light column with 3 colours " type must be foreseen near the access to indicate the state of the equipment. (See end of this document).
Besides, it is recommended to affix a marking on the ground clarifying dangerous zones to the operators.
6 Receiver wiring diagram according to intervention condition
Reminder :
The program can be chosen using the two « B » switches on the front panel of the safety module. The various programs available allow the user to manage (or not) access to a dangerous area.
6.1 Control of machine without area access control.
Programs 0 to 4 of the safety receiver do not allow managing access to a dangerous area.
6.2 Wiring diagram
The manual control mode is only possible by programs 0 to 4 (defined by the two “B” switches). See § 3.4.1 Choice of receiver (RSRA) program.
Page 17
Page 17 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
Use of two wired emergency stops and a radio remote controlled emergency stop.
Ditto above with control of contacts of auxiliary relays « K3-K4 ».
A1+ S11 S12 S14 S13 S21 S22 S24 S23 S31 S32 S34 S33 S42 A3 A4 13 23 33 Y1 Y2
A2- 58 48 17 27 37 A2- 47 57 67 77 A2- 34 24 14
K1
K2
Red (1) (Receiver code error)
Charger Contact
Safety receiver
RSRA
27 to 77 : control outputs for radio remote control function buttons
Emerg. stop 1 Emerg. stop 2
24V DC
Orange (1)
Radio transm.
active
Green (1)
Equipment
operating
Transmitter pickup information K3
K4
(1) Ind. light Antenna
start button
A2 -
A5 +
IR
K3 K4
(1) Ind. light
column
A1+ S11 S12 S14 S13 S21 S22 S24 S23 S31 S32 S34 S33 S42 A3 A4 13 23 33 Y1 Y2
A2- 58 48 17 27 37 A2- 47 57 67 77 A2- 14 24 34
K1
K2
Red (1) (Receiver code error)
Charger Contact
Safety receiver
RSRA
Emerg. stop 1 Emerg. stop 2
24V DC
Orange(1)
Radio transm.
active
Green (1)
Equipment operating
Detect transmitter on charger
Antenna
27 to 77 : control outputs for radio remote control function buttons
start button
A2 -
A5 +
IR
Page 18
Page 18 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
6.2.1 Diagram of functions according to program selected.
Reminder : The program is selected using the 2 « B » switches See § 3.4.1 Choice of receiver (RSRA) program.
Switch B = 0:
Protection circuits connected to S12-S14 and S22-S24 always active.  Manual startup only by “ON” button connected to S42 Transmitter acknowledged provided one of charger contacts connected to S32 or S34 opens.  Transmitter emergency stop reset by « ON » button : green
tmax.: maximum time for transmitter enable after it is picked up off charger.
Page 19
Page 19 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
Switch B = 1:
Protection circuits connected to S12-S14 and S22-S24 always active.  Manual startup only by «ON» button connected to S42  Transmitter acknowledged if one of charger contacts connected to S32 and S34 opens.  Reset of transmitter emergency stop by «ON» button connected to S42 after reset of remote control by its
“ON” button, green
tmax.: maximum time for transmitter enable after it is picked up off charger.
Page 20
Page 20 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
Switch B = 2:
Protection circuits connected to S12-S14 and S22-S24 always active, automatic startup.  Transmitter acknowledged if one of charger contacts connected to S32 and S34 opens.  Reset of transmitter emergency stop by its “ON” button, green.
tmax.: maximum time for transmitter enable after it is picked up off charger.
Page 21
Page 21 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
Switch B = 3:
Protection circuits connected to S12-S14 and S22-S24 always active, automatic startup.  Transmitter acknowledged if one of charger contacts connected to S32 and S34 opens.  Reset of transmitter emergency stop by «ON» button connected to S42 after reset of transmitter by its “ON”
button, green.
tmax.: maximum time for transmitter enable after it is picked up off charger.
Page 22
Page 22 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
Switch B = 4:
Protection circuits connected to S12-S14 and S22-S24 always active, manual startup by «ON» button
connected to S42
Transmitter acknowledged if one of charger contacts connected to S32 and S34 opens.  Manual startup by transmitter «ON» button possible for all functions.
tmax.: maximum time for transmitter enable after it is picked up off charger.
6.2.2 Control of machine with area access control.
Programs 8 and 9 of the safety receiver are used to manage access to a machine area. The difference between these two programs is in the reset mode following a wireless emergency stop. On the other hand, one of the two wired emergency stop inputs is used to manage dangerous area access.
See appendix “A” example application
6.2.2.1 Recommended wiring diagram
All the inputs must be wired, including the charger contacts, the « ON button» and the emergency stop input. If
emergency stop inputs « S11-S12 and S13-S14 » are not used, they must be bridged two by two.
Page 23
Page 23 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
Diagram for “area access” by gate
Diagram for « area access » by safety barrier
A1+ S11 S12 S14 S13 S21 S22 S24 S23 S31 S32 S34 S33 S42 A3 A4 13 23 33 Y1 Y2
A2- 58 48 17 27 37 A2- 47 57 67 77 A2- 14 24 34
K1
K2
Red (1) (Receiver error code)
Charger contacts
Safety receiver
RSRA
27 to 77 : Control outputs of radiocontrol function buttons
Emerg. stop
24V DC
Orange (1)
Radio transmitter
active
Green (1)
Equipment
operating
Detect transmitter on charger
K3
K3
(1) Ind. light column
Antenna
Start button
Output
Input
Passage request
BI
OSSD
Trans mitter
A2 -
A5+
IR
K3 K4
A1+ S11 S12 S14 S13 S21 S22 S24 S23 S31 S32 S34 S33 S42 A3 A4 13 23 33 Y1 Y2
A2- 58 48 17 27 37 A2- 47 57 67 77 A2- 14 24 34
K1
K2
Red (1) (Receiver error code)
Charger contacts
Safety receiver
RSRA
27 to 77 : Control outputs of radiocontrol function buttons
Emerg. stop 1
24V DC
Orange (1)
Radio transmitter
active
Green (1)
Equipment
operating
Detect transmitter on charger
K3
K3
(1) Ind. light column
Antenna
Start button
Gate contact open
Output
Input
Passage request
A2 -
A5 +
IR
K3 K4
Page 24
Page 24 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
6.2.3 Diagram of functions according to program selected
Reminder : The program is selected using the 2 « B » switches see § 3.4.1 Choice of receiver (RSRA) program.
Switch B = 8: Access to protected area
Protection circuits connected across S12-S14 and S22-S24 always active if charger contact connected
across S31 and S32 is closed.
Manual startup only by «ON» button connected to S42 following an area access request.  Transmitter acknowledged if charger contact across S31 and S32 is open.  Time-delayed inhibit of safety element connected to S22-S24.  Manual startup by «ON» button of remote control is possible.
tmax.: maximum time for enable of remote control after it has been picked up from charger and maximum time for inhibiting protection.
Page 25
Page 25 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
Switch B = 9: Access to protected area
Protection circuits connected to S12-S14 and S22-S24 always active if charger contact connected across
S31 and S32 is closed
Manual startup only by «ON» button connected to S42.  Transmitter acknowledged if charger contact across S31 and S32 is open.  Time-delayed inhibit of safety element connected to S22-S24 following area access request  Reset of remote control emergency stop only by «ON» button connected to S42 after reset of remote
control by its «ON» button, green
tmax.: maximum time for enable of remote control after it has been picked up from charger and maximum time for inhibiting protection.
Page 26
Page 26 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
7 Installation recommendations
7.1 General information
Experience has shown that functional reliability basically depends on the quality of the installation, in particular as concerns the following points :
- Interference suppression,
- Choice of utilization frequency,
- Identification of equipment controlled,
- Position of receiver and antenna,
- Quality of wiring of associated systems and receiver,
- Protection of electrical power supply,
- Maximum current of static outputs.
7.2 Choice of utilization frequency
The 64 radio channels of the RADIOSAFE system provide a wide choice among the available frequencies. For good operating quality, you must ensure that the radio channel used is free throughout the area where the unit will be controlled. If several products are operating on the same site, you should use frequencies that are spaced by at least 2 channels (for example : 5,7,9...), and if necessary, a frequency plan should be drawn up identifying the various machines controlled and their working frequencies. To change frequency, refer to the section 8.3.1 Procedure for programming frequency.
(1)= List of frequencies available for Denmark (2)= List of frequencies available for Singapore
7.3 Receiver and charger installation precautions.
The receiver and charger wiring must always be performed with all power shut down. Provide a fuse protection circuit connected in series on input A1 (24V DC) of the receiver. See section 3.2 Receiver RSRA”.
The product should be installed near the intervention area. For this purpose, we strongly recommend that the receiver be mounted in a housing.
On the front panel of the housing, we recommend wiring:
An emergency stop. A wired emergency stop should be mounted on the front panel of the housing. This emergency stop can be used when the radio remote control is set on its charger.
A « system on » button. The « system on » button is used to reset the receiver module when commissioning or following a fault.
Channel
Frequency
MHz
Channel
Frequency
MHz
Channel
Frequency
MHz
01
433,100
23
433,650
45
434,200
(2)
02
433,125
24
433,675
(1)
46
434,225
(2)
03
433,150
25
433,700
47
434,250
(2)
04
433,175
26
433,725
(1)
48
434,275
(2)
05
433,200
27
433,750
49
434,300
(2)
06
433,225
28
433,775
(1)
50
434,325
(2)
07
433,250
29
433,800
(2)
51
434,350
(2)
08
433,275
30
433,825
(1) (2)
52
434,375
(2)
09
433,300
31
433,850
(2)
53
434,400
(2)
10
433,325
32
433,875
(1) (2)
54
434,425
(2)
11
433,350
33
433,900
(2)
55
434,450
(2)
12
433,375
34
433,925
(1) (2)
56
434,475
(2)
13
433,400
35
433,950
(2)
57
434,500
(2)
14
433,425
36
433,975
(1) (2)
58
434,525
(2)
15
433,450
37
434,000
(2)
59
434,550
(2)
16
433,475
38
434,025
(1) (2)
60
434,575
(2)
17
433,500
39
434,050
(2)
61
434,600
(2)
18
433,525
40
434,075
(2)
62
434,625
(2)
19
433,550
41
434,100
(2)
63
434,650
(2)
20
433,575
(1)
42
434,125
(2)
64
434,675
(2)
21
433,600
43
434,150
(2)
22
433,625
(1)
44
434,175
(2)
433-434MHz bands, with adjacent intervals of 0,025MHz
Page 27
Page 27 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
On the sides of the unit, we recommend:
Mounting the charger support To avoid any ambiguity when the radio remote control is inactive, placed on its charger, we recommend that you do not mount the charger support in a way which is directly visible by the operators. For example, a protective screen plate could be used as shown in the photo below.
On the top of the housing, we recommend :
Mounting an indicator light assembly. The indicator light column will show the state of the equipment and the radio remote control transmitter. The indicator light column information sheet should be fastened near the indicator light column (See example given on last page of manual).
7.3.1 Special case – Equipment area access
For an area access configuration (application program 8 or 9), an access authorization request pushbutton must be wired on either side of the area access. The two buttons will allow the operator to access and exit the intervention area. See wiring diagram in section 6.2.2 Control of machine with area access control.
7.3.2 Receiver antenna installation position
Supplied with the product is an antenna, a 50 cm antenna extender and a BNC-BNC elbow. If a metal electrical housing is used, the receiver antenna should be remote-mounted on the top of the housing. If a plastic housing is used, the receiver antenna can be connected directly on the RADIOSAFE receiver. In the event of poor radio wave propagation, for example when intervening in an enclosure, we recommend that the receiver antenna be remote-mounted inside the enclosure. Contact us for the choice of antenna extension.
Indicator light column information sheet
Product mounted in housing
Page 28
Page 28 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
8 Commissioning
8.1 Commissioning precautions
Before commissioning the system, the installer must :
Ensure : If several assemblies are installed, that the transmitter electronic key and the receiver have the same identity
code. Check that this information matches up on the key identification sheet and on the receiver label.
That the radio channel selected corresponds to the frequency plan defined for the site. The product is
supplied configured for channel 01 (433,1 MHZ). If necessary, refer to the section covering the frequency
change procedure. That the transmitter “activity monitoring time complies with your application (product supplied with activity
monitoring time configured for 15 min.). Refer to the section covering the procedure for programming this
duration.8.3.2 Procedure for programming « transmitter activity monitoring » duration.
That the application program selected on the receiver is consistent with your wiring.  That the transmitter battery is properly charged. The orange indicator light on the transmitter should be off
when the emergency stop palmswitch is unlocked.
8.2 Starting up the radio remote control
1- Place the transmitter on its charger. 2- Switch on the receiver and reset it by pressing the wired ON pushbutton connected to input S42 of the receiver.
On the receiver, indicator light V1 should come on and indicator light V2 should go off. 3- Remove the transmitter from its charger. 4- Unlock, press then unlock again the transmitter emergency stop palmswitch (1). 5- Wait until the orange indicator goes off before pressing on the green "On" button.
The green indicator light on the transmitter should flash
White indicator lights V1 and V2 on the receiver should come on steady
To stop the remote control : press the emergency stop palmswitch on the transmitter. Reminder : When the emergency stop palmswitch on the transmitter is pressed, the receiver safety relays
immediately change state.
(1) Procedure for checking correct operation of emergency stop palmswitch
NOK
NOK
OK
OK
OK
Page 29
Page 29 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
8.3 Configuring the transmitter.
8.3.1 Procedure for programming frequency
1-Switch on the receiver. 2- Insert the electronic key in the transmitter. 3-- Press and hold buttons B1 and B2,
- unlock the emergency stop palmswitch on the transmitter (fig.1),
- Wait until the orange indicator goes off before releasing buttons B1 and B2. The channel currently selected is indicated by two flashing indicator lights on the transmitter representing the
tens (orange) and the units (green). 4- Select the new channel using channels B1 and B2 (Figs.2&3). By pressing button B1, the tens are incremented ; by pressing button B2, the units are incremented. During these operations, the newly selected channel is indicated by the 2 indicator lights on the transmitter
which flash accordingly. 5- Once the desired channel is selected (choice of No. 01 to 64), press the “ON” button to validate your selection
(Fig. 4). Briefly press « ON » : The transmitter sends the number of the selected channel to the receiver and saves its
new working channel (Fig.5). By pressing and holding « ON » (3 seconds) : The transmitter sends the number of the selected channel to
the receiver (on each of the radio link channels) and saves its new working channel. Wait until the transmitter
indicator lights stop flashing (around 30 s.) (Fig.5) (this procedure, which is preferable but longer, should be
followed when you do not know the initial working channel of the receiver). 6- Exit the « frequency » programming mode by pressing the emergency stop palmswitch (Fig. 6).
Page 30
Page 30 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
8.3.2 Procedure for programming « transmitter activity monitoring » duration.
Note : The product is supplied with the “activity monitoring” duration set for 15 minutes.
Changing the counting unit
1-- Push and hold button B1. 2 - Unlock the emergency stop palmswitch on the transmitter, 3 - Wait until the orange indicator goes off before releasing button B1.
The counting unit is indicated by the two indicator lights on the transmitter. When ON, the orange indicator light indicates that the counting unit is in minutes. When ON, the green indicator light indicates that the counting unit is in seconds.
4-Select the new counting unit using button B2. 5- Once the new counting unit is selected, press the “On” button to validate your choice. 6-Exit the programming mode by pressing the emergency stop palmswitch.
Setting the duration
1-Switch off the receiver. 2- Insert the electronic key in the transmitter. 3-- Press and hold buttons B1 and "On”,
- unlock the emergency stop palmswitch on the transmitter (Fig.1),
- Wait until the orange indicator goes off before releasing buttons B1 and "On". The duration of the « activity monitoring » function is indicated by the two flashing indicator lights on the transmitter,
representing the tens (orange) and the units (green) of the number of minutes or seconds configured. 4- Select the new duration using buttons B1 and B2 (Fig.2&3). By pressing button B1, the tens are incremented, by pressing button B2, the units are incremented. During these operations, the newly selected duration is indicated by the two indicator lights on the transmitter.
5-Once the new duration is selected (between 01 and 99), press the “On” button to validate your choice (Fig. 4). Caution, No. 99 corresponds to an infinite « activity monitoring » duration when the counting unit is in
« minutes » (1) . When the counting duration is in “seconds”, the number 99 corresponds to 99 seconds. > The function is then deactivated ; if you forget to stop the transmitter, it will discharge completely. 6-Exit the « activity monitoring » duration programming mode by pressing the emergency stop palmswitch (Fig. 6).
(1) Caution: functioning mode without « activity monitoring » could be dangerous. Be sure to indicate the new transmitter activity monitoring duration on the key identification
sheet.
Page 31
Page 31 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
8.3.3 Procedure for « locking – unlocking » access to transmitter programming
1- Switch off the receiver. 2- Insert the electronic key in the transmitter. 3-- Press and hold buttons B1, B2 and " On ",
- Unlock the emergency stop palmswitch (fig.1),
- Wait until the orange indicator goes off before releasing buttons B1, B2 and "On". Led indications :
- transmitter locked : orange indicator light on, green indicator light off. - transmitter unlocked : orange and green indicator lights on.
4- Select the locked or unlocked state by pressing button B2 ; the selected mode is indicated on the indicator
lights (Fig. 2&3).
5-Validate the selected mode by pressing the “On” button (Fig.4). 6-The transmitter (URE) saves the new mode in the electronic key and switches off the indicator lights. 7-Exit the « lock-unlock » configuration mode by pressing the emergency stop palmswitch (Fig.6).
Note: If an operator attempts to program the frequency or the duration for the « activity monitoring » time delay
with the transmitter in the locked state, the transmitter will indicate an error by its indicator lights which will flash 4 times.
Page 32
Page 32 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
8.3.4 Procedure for « validation of an electronic key ».
Reminder : To use the RADIOSAFE radio remote control system, the identity code contained in the transmitter memory must be identical to the identity code of the electronic key, which is itself identical to that of the receiver.
If a maintenance transmitter is used or an electronic key is changed, you must copy the information contained in the electronic key to the transmitter memory.
Condition for using this procedure :
The maintenance transmitter buttons must be configured identically to that described in the electronic key (or in the original transmitter).
1- Switch off the receiver 2- Insert the electronic key in the transmitter. 3- - Push and hold buttons B2 and "On”,
- Unlock the emergency stop palmswitch on the transmitter (Fig.1),
- Wait until the orange indicator goes off before releasing buttons B2 and "On". The two indicator lights on the transmitter (URE) flash rapidly. 4- Press the ON button to automatically program the identity code : the two indicator lights on the transmitter go
off (Fig.2). The « identity code » information is copied from the electronic key to the transmitter memory.
5- Exit the programming mode by pressing the emergency stop palmswitch (Fig.4).
With a new key, the transmitter and receiver may not communicate. Check that the frequency channel has not been changed. If this is the case, refer to the previous chapter
covering the “Procedure for programming frequency”. In this respect, each new key is
supplied set for channel 01, i.e. frequency of 433.100 MHZ.
Page 33
Page 33 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
9 Maintenance
9.1 Spare parts
Reference & designation. RSWE21-B : Programmed electronic key (specify your key Nbr.)
PR0248 : Lithium-ion battery (1) SCI-B Industrial charger support UCC4 : 24VDC- 5V DC charger power supply UCCU : 230VAC- 5VDC charger power supply, European connector. UCCW : 230VAC- 5VDC charger power supply, UK connector
(1) It is the user’s responsibility to ensure that the batteries are correctly recycled. We will recycle your used
batteries if returned to our plant.
9.2 Fault isolation
9.2.1 Transmitter fault isolation
Transmitter state Orange ind. light Green ind. light Function
Before or after "On/Horn"
bt. pressed
OFF OFF
Shut down or
"Dead man" time exceeded or RESET for discharged battery
Before "On/Horn" bt.
pressed
OFF ON battery charge > 50%
Before "On/Horn" bt.
Pressed
Flashes SLOW ON 50% > battery charge > 10%
Before "On/Horn" bt.
Pressed
Flashes FAST ON battery charge <10%
Before "On/Horn" bt.
Pressed
ON OFF
The orange led is ON during 2 seconds
when the transmitter is initialized
Before "On/Horn" bt.
Pressed
ON ON Electronic key reading error
Before "On/Horn" bt.
Pressed
Flashes 3 times Flashes 3 times
Error, mismatch detected between electronic key and URE memory.,
Reprogramming is required, see procedure "validation of an electronic key".
Before or after "On/Horn"
bt. Pressed
Flashes 4 times Flashes 4 times Faulty button(s)
Before "On/Horn" bt.
Pressed
Flashes 5 times Flashes 5 times Stop or start-up error detected.
Before "On/Horn" bt.
Pressed
Flashes 6 times Flashes 6 times Stop or start-up error detected.
Before "On/Horn" bt.
Pressed
Flashes 7 times Flashes 7 times
Internal error, electronic key or transmitter URE
Before "On/Horn" bt.
pressed
Flashes 8 times Flashes 8 times Internal URE transmitter errror
After "On/Horn" bt.
pressed
OFF Flash Radio transmission
After "On/Horn" bt.
pressed
Flashes FAST Flash
Radio transmission +
battery charge below 10%
Page 34
Page 34 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
9.2.2 Fault isolation relative to receiver parameter definitions or configuration
The safety receiver has two redundant electronic circuits integrating 4 microprocessors. For this reason, the fault and error indications are divided into two groups on these 4 processors. The 2 white indicator lights « V1 and V2 » indicate the state of the receiver safety functions.
o Receiver state when transmitter is on its charger : "V1" On and "V2" Off. o Receiver state when transmitter is active : "V1 and V2" On.
Note : The states of indicator lights V3 and V4 is described in section 8.2.4. In the event of a fault, at least one of the two indicator lights « V1 » or "run2 « V2 » is off, or both indicator lights
flash. In this case, they may even flash with different error codes (No.).
Error code
(number of
consecutive
flashes of 2 white
indicator lights
« V1 and/or V2 »
Error
Cause
Off
Communication
error
In the event of a serious communication error, the 2 indicator lights « V1 » and « V2 » are off ; this is a serious error. The unit must be sent in for repair.
5
Adjustment error
V1 and V2 flash 5 times: the 10-position switches for the 2 circuits do not have the same positions.
6
Undervoltage or
overvoltage
V1 flashes 6 times: the power supply voltage is less than 0.85Un V1 flashes 6 times: the power supply voltage is greater than 1.15Un
7
Short-circuit
One of the inputs is short-circuited
8
Safety relay error
V2 flashes 8 times : the return loop for terminals Y1-Y2 is not closed when the safety outputs are inactive. One of the output relays or its control circuit is defective.
9
Safety output
control error
The 2 controls for the safety relays do not correspond.
10
Software program
error
One of the processors has recognised an error in the running of its program.
11
Parity error
The 2 processors take too much time to achieve the same state.
12
Version error
The software versions of the 2 processors do not match: the unit must be sent in for repair.
13
Software memory
error
The software memory is defective. The unit must be sent in for repair.
14
RAM error
The processor working memory is defective. The unit must be sent in for repair.
Page 35
Page 35 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
9.2.3 Receiver input fault isolation
The various operating states leading to deactivation of the safety outputs are indicated by an error code (No.) simultaneously by the white LED "V2" and static output 58.
The white LED « V1 » remains on. So long as the cause of the fault has not been eliminated, static output 48 is activated. It flashes regularly as soon as reactivation of the module by one of the ON button is possible.
Error code
(number of
consecutive
flashes of white
ind. light « V2 » )
State
Cause
1
Radio transmitter emergency stop
- A charger contact is open and the emergency stop palmswitch on the remote control is pressed.
- A charger contact is open and radio communication has not been activated.
2
System stopped by a wired protection component
One of inputs S12-S14 or S22-S24 is deactivated.
3
Time delay error
The contacts of a safety element have not been activated within the required time frame. The contacts of this component must first be deactivated before a new activation can be recognised.
- The charger contact has been opened, but radio communication has not been activated in time.
- In « protected area access » mode, the passage button or the ON button on the remote control has not been released after the passage request stop.
4
Error in one of the ON buttons
- Activation time greater than time delay duration selected.
- Activated on power up of module.
- Activated on appearance of a fault.
5
Passage button error
Protected area access mode, button (S34) activated at moment of power up.
6
Charger contact error
Only one of the two charger contacts is open.
Page 36
Page 36 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
9.2.4 Receiver radio function fault isolation.
The red and green led states describe a malfunction in the radio part of the safety receiver.
Name of Led
and colour
Mode
Indication
Message
State
Safety micro
led 1 (RED
V3)
Normal
Indicates validity of
identity code
Message not received
OFF
Message received with correct identity code
OFF
Message received with incorrect identity code
Flashing regularly
Serial link
ON
In case of
fault
Indicates a fault
Power supply error
2 flashes
Safety relay
3 flashes
EEPROM
4 flashes
RAM
5 flashes
ROM
6 flashes
Micro type
7 flashes
Safety micro
led 2 (GREEN)
V4
Normal
Indicates radio
reception quality
No radio reception
OFF
Bad radio reception
Flashing
Good radio reception
ON
Serial link
OFF
In case of
fault
Indicates a fault
Power supply error
2 flashes
Safety relay
3 flashes
EEPROM
4 flashes
RAM
5 flashes
ROM
6 flashes
Micro type
7 flashes
Page 37
Page 37 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
10 Warranty
All our devices are guarantied 2 years as of the date of manufacture indicated on the product (except for the transmitter URE battery which has 1 year warranty). No repair, modification or replacement of a product
during the warranty period can be understood as an extension of the warranty period.
Limits of warranty :
The warranty does not cover defects resulting from :
Transport  False operation or non-observance of connection diagrams when setting the equipment into service  Insufficient supervision or servicing, utilization not complying with the specifications detailed in the
technical manual and, as a general rule, storage, operation or environment conditions (atmospheric, chemical, electrical or other conditions).
Conditions not specified on order of the equipment
The warranty shall not apply subsequent to any modifications or additions to the equipment performed by the customer without written approval by JAY Electronique.
The JAY Electronique responsibility during the warranty period is limited to material and construction defects. This warranty comprises repair in the JAY workshops or replacement, free of charge, of parts recognized to be defective following expert inspection by the JAY Technical Department.
The warranty shall not give rise to any compensation for damage claims. Any disputes relative to a supply or settlement thereof shall be ruled by the COURT OF COMMERCE OF
GRENOBLE, solely competent, even in the event of an Appeal or a plurality of defendants.
Page 38
Page 38 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
11 CE declaration of conformity
Page 39
Page 39 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
12 Appendix A : Intervention in equipment area
Example : access to load transfer machine in « monitoring – diagnostic » mode.
12.1 Purpose
The product is designed to allow a trained operator to access a closed secure area in “monitoring-diagnostic” mode while holding a transmitter equipped with an emergency stop system.
12.2 Need
A maintenance operator may need to intervene (1) in a dangerous area where a load transferring machine is operating in automatic mode. This intervention may be aimed, for example, at determining the cause of a random fault or detecting a malfunction, or visually inspecting products manufactured without stopping the automatically­controlled system.
The operator’s safety is ensured by an individual portable protection device (transmitter) equipped with an
emergency stop palmswitch enabling him to stop the machine should he find himself in a dangerous situation. (1) Intervention condition described in section 5.2 Intervention conditions”.
12.3 Application diagram
12.4 Wiring diagram
See section 6.2.2.1 Recommended wiring diagram”.
Page 40
Page 40 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
12.5 Procedure.
1. The transmitter must be placed on its charger, the wired emergency stop must be unlocked and the gate must
be closed or the safety light barrier activated. This state is indicated by the white "V2" led and static output 58 which are off.
2. Before entering the protected area, the operator picks up the transmitter from the charger. The charger contact (S31- S32) opens. The operator has a certain period of time (set by the “A” switches on the receiver) to activate the transmitter. The activation waiting time is indicated by rapid flashing of the white “V2” led and static output 58.
3. Wait until the transmitter orange indicator light goes off before activating the transmitter with green “On” button. Once activated, the white “V2” led and static output 58 come on steady.
4. In order to pass through the protected access, the operator must simultaneously press the green ON button on the transmitter and the passage request button located outside the protected area. When the two buttons are released, the passage is inhibited. This state is indicated by a Led “V2” and static output 58 which flash slowly. The operator must move through the gate and close it or go through the safety light barrier before the end of the inhibit time which is realized by the blinking of the V2 indictor light and the output nb 58. This inhibit time is customizable by A selector.
5. This inhibit time is interrupted when the operator crossed the safety light barrier or closed the access zone gate. White indicator light “V2” and static output 58 are again on steady.
6. Once the intervention is completed, in order to come out of the area, the operator must again perform the passage request by simultaneously pressing the On button on the remote control and the passage request button located inside the equipment. Once the two buttons are released, the passage is again inhibited (slowly flashing “V2” led and static output 58).
7. Once outside the protected area, the operator sets the remote control on the charger and the charger contact closes. The transmitter should be deactivated within 1 second. On deactivation of the remote control, the white “V2” led and static output 58 go off.
Note: The inhibit time and the maximum time tolerated between the moment the transmitter is picked up off the charger and activation of the transmitter can be adjusted using the rotary “A” switches on the receiver. The two passage request buttons are connected in parallel across terminals S33-S34 of the safety receiver.
As indicated in section 7.3.1 Special case – Equipment area access, an indicator light column should be wired on the housing containing the safety receiver. Refer to the section covering 7.3 Receiver and charger
installation precautions.
12.6 Area access in manual mode
The procedure for access is the same, except that the equipment is stopped before the intervention using the portable transmitter. See section 5.2 Intervention conditions”.
Here below a sheet to be stuck up next to the indicator light column.
This sheet specifies the states of the equipment and the portable transmitter.
Page 41
Page 41 / 41
Ref doc : 330740F/EN
revision 01 29.09.2015
RADIOSAFE
Installation manual appendix 330740F
Ok
Equipement operating
In area
To intervene in area with transmitter.
STOP
A protected stopping of the
equipment is started
IMPORTANT
When the radio transmitter is set on its charger, it is stopped and its emergency stop function is INACTIVE !
d.a
Loading...