If you fail to follow the instructions
in this manual, a fire or explosion
may result causing property
damage, personal injury or loss of
life.
CERTIFIED AS VENTED GAS
ANSI Z21.88a-2012
INSTALLATION AND OPERATION GUIDE
DIRECT-VENTED GAS FIREPLACE
IF YOU SMELL GAS:
Do not turn on any appliance.
Do not touch any electrical switch;
do not use any phone in your
building.
From an external phone, call your
gas supplier immediately and
follow their instructions to the letter.
If your gas supplier is not available,
contact your local fire department.
Installation and service must be
performed by a qualified installer or
by the gas supplier.
FIREPLACES HEATERS
CSA 2.33a-2012
1
Reviewed on August 5th, 2015
7 GAS FIREPLACES MODELS
MISTRAL
(PENINSULA / RGP-25)
SUROIT
(SEE THRU / RGV-25)
SIROCCO
(PANORAMIC / RGB-25)
PAMPERO
(CENTRAL / RGC-25)
MOUSSON
(RIGHT CORNER /RGCD-25)
AUSTER
(LEFT CORNER /RGCG-25)
LOO
(INSERT / RGR-25)
2
INTRODUCTION
Read this manual before installing or using this product. Please keep this owner's
manual for future reference.
CONGRATULATIONS!
You are now the owner of a J. A. ROBY gas fireplace. J. A. ROBY products are made with first
grade components and materials and are put together by skilled professionals who care about the
quality of their work. Each component of your fireplace was tested and thoroughly inspected to
make sure you receive a high-quality product. For the past 30 years, we have been committed to
providing you with high-quality products and customer satisfaction. We offer a complete range of
gas and wood burning fireplaces, unique decorative cabinets and stylish accessories to
compliment any decor. At J. A. ROBY, we know that adding a fireplace is one of the best ways to
increase the value of your home, and we are proud to help you achieve your dreams with a network
of retailers all across the country. Not only are we committed to providing you with reliable and
well-functioning appliances; but we also have your safety at heart. This is why we offer you ongoing
assistance and support to make sure you can take full advantage of your J. A. ROBY gas fireplace.
Owner’s reference information
We recommend you write down the following information on your gas fireplace.
Model name: _______________________________
Date of purchase/installation: __________________
Serial number: ______________________________
Location of the gas fireplace: __________________
Retailer’s name: ____________________________
Retailer's phone number: _____________________
Notes: ___________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
1.2.2. USE .................................................................................................................................................. 10
3.1.2.1. LOO / RGR-25(INSERT) WITH BACK EXIT .............................................................................................................. 24
3.1.2.2. LOO / RGR-25(INSERT) WITH SIDE EXIT ............................................................................................................... 24
3.1.2.3. LOO / RGR-25(INSERT) WITH TOP EXIT................................................................................................................ 25
3.1.2.4. LOO / RGR-25(INSERT) CORNER INSTALLATION WITH TOP EXIT ................................................................................. 25
3.1.2.5. MISTRAL / RGP-25(PENINSULA) WITH BACK EXIT .................................................................................................. 26
3.1.2.6. MISTRAL/ RGP-25(PENINSULA) WITH TOP EXIT .................................................................................................... 26
3.1.2.7. AUSTER / RGCG-25(LEFT CORNER) WITH BACK EXIT ............................................................................................... 27
3.1.2.8. AUSTER / RGCG-25(LEFT CORNER) WITH SIDE EXIT ................................................................................................ 27
4
3.1.2.9. AUSTER / RGCG-25(LEFT CORNER) WITH TOP EXIT................................................................................................. 28
3.1.2.10. MOUSSON / RGCD-25(RIGHT CORNER) WITH BACK EXIT ......................................................................................... 28
3.1.2.11. MOUSSON / RGCD-25(RIGHT CORNER) WITH SIDE EXIT .......................................................................................... 29
3.1.2.12. MOUSSON / RGCD-25(RIGHT CORNER) WITH TOP EXIT........................................................................................... 29
3.1.2.13. SIROCCO / RGB-25(PANORAMIC) WITH BACK EXIT ................................................................................................. 30
3.1.2.14. SIROCCO / RGB-25(PANORAMIC) WITH TOP EXIT .................................................................................................. 30
3.1.2.15. PAMPERO / RGC-25(PAMPERO) WITH TOP EXIT .................................................................................................... 31
3.1.2.16. SUROIT / RGV-25(SEE THROUGH) WITH SIDE EXIT ................................................................................................. 31
3.1.2.17. SUROIT / RGV-25(SEE THROUGH) WITH TOP EXIT .................................................................................................. 32
3.2.3.2. VENT TO BE USE WITH APPLIANCE ....................................................................................................................... 36
3.2.3.3. CONDITIONS TO BE MET .................................................................................................................................... 36
3.2.3.4. ELBOW EQUIVALENT FOR HORIZONTAL VENT LENGTH .............................................................................................. 37
This equipment has been certified by ITS.
To:
ANSI Z21.88a-2012• CSA 2.33a-2012
Vented Gas Fireplace Heaters
If these instructions are not followed exactly, a fire or explosion may result
in property damage, personal injury or even death.
READ CAREFULLY AND KEEP FOR FUTURE REFERENCE.
THIS APPLIANCE MUST BE INSTALLED BY A CERTIFIED TECHNICIAN IN ACCORDANCE WITH THE
INSTRUCTIONS CONTAINED IN THE OWNER’S MANUAL PROVIDED BY THE MANUFACTURER AND IN
COMPLIANCE WITH THE APPLICABLE LOCAL AND NATIONAL INSTALLATION STANDARDS ALSO WITH
THE EFFECT BUILDING CODE.
1.1. WARNING
This unit can be installed in a prefabricated home that is already built if local regulations allow it.
This appliance must only be used with the type of gas indicated on the rating plate.
This appliance is not convertible for use with other gases unless a conversion kit is used.
Do not store or use gasoline or other flammable vapors or liquids in the vicinity of this or any other
appliance.
WHAT TO DO IF YOU SMELL GAS
- Do not turn on any appliance.
- Do not touch any electrical switch; do not use any phone in your building.
- From an external phone, call your gas supplier immediately and follow their instructions to
the letter.
- If your gas supplier is not available, contact the fire department.
- Installation and maintenance must be performed by a qualified installer or by the gas
supplier.
8
INSTALLER: LEAVE THIS MANUAL WITH THE EQUIPMENT.
WARNING
Improper installation, adjustment, alteration, repair or maintenance can cause material damage or
injury. Make sure to read and understand this manual. For assistance or additional information, consult
an installer, a licensed technician or your gas supplier.
BURN HAZARD!
Do not touch the fireplace when it is used.
You could get burned or clothes could catch fire.
Keep children away.
DO NOT DISCARD
• This document contains important instructions for the installation, use and maintenance of the appliance.
• You must read, understand and follow these instructions and details to ensure safe installation and use.
• You must refer to a qualified person for the installation, use and maintenance of the appliance.
1.2. SAFETY INSTRUCTIONS
• Make sure you follow the instructions in this manual to avoid any risk of fire, explosion, damage, injury
or death.
• This guide will tell you how to use your fireplace properly and safely. Keep it for future reference. This
unit is approved for installation in living rooms, bedrooms and bathrooms. Failure to comply with the
requirements that follow could pose a hazard.
1.2.1. INSTALLATION
CAUTION: Failure to follow these instructions voids the warranty.
• Installation must comply with local codes. If there are none, follow the National Fuel Gas Code ANSI
Z223.1 (latest edition) for the U.S. and the CAN / CSA B149 installation codes in Canada. Do not install
directly on carpet or on a combustible material other than wood. If you are installing the fireplace on a
flooring not adapted for this kind of appliance, you must install it on a piece of metal sheet, a wood floor
or a hearth as wide and as deep as the appliance.
• Your fireplace is designed to be used in zero clearance installations. Depending on your configuration,
insulation box is provided on the fireplace. Combustible materials can be placed against the clearance
post located on top of the appliance. Follow the installation instructions carefully to avoid any risk of fire.
• This appliance can be installed in any room of the house, provided that all local codes and installation
instructions are followed.
• The fireplace must be properly connected to a venting system. It is very important to correctly install the
vent pipe to ensure the appliance is working properly. You must strictly follow the instructions on the
vent pipe, whether vertical or horizontal. (See 3.2)
• Donot connect this fireplace’s vent with another vent appliance.
9
• The installation must be performed by a qualified installer or by trained professionals supervised by a
WARNING
Do not install any damaged or incomplete component, or any replacement component that was
not approved by the manufacturer.
technician, the service agency or the gas supplier.
• This unit can be installed as an original equipment in a prefabricated home (USA only). It must be installed
according to the manufacturer's instructions and in accordance with the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280.
• Verify building codes prior to installation.
• The installation must comply with local, regional, provincial and national codes and regulations.
• Consult local building and fire department authorities or officials who have jurisdiction over restrictions,
post-installation inspection and permit issuing.
• Install the appliance on a metal or wood hard surface that is as wide and as deep as the fireplace.
• Install the alcove in accordance with the guide’s clearance specifications.
• Install the fireplace in accordance with the guide’s clearance specifications.
• Make sure to leave a 3 inch space between combustible materials and the first 8 feet of the vent pipe
(except if protected by a fireguard). After the first 8 feet of the vent pipe, keep a 1 inch space between
the vent and combustible materials.
• Do not connect this gas appliance to a flue used for another fuel-fired appliance.
• Drain the gas from this unit directly to the outside.
• Use a standalone vent system for this appliance.
• Always make sure to leave the required clearances around the vent system and fireguard.
• Install the ceiling fireguard as specified in this manual.
• Overlap vent sections at least 1 ½ in. (3.8 cm).
• Vent sections might come off if they are not properly connected. Each vent sections should be sealed
and attached with screws.
• Verify that all vent and gas pipe connections are tightly sealed.
• Use only the accessories provided by the manufacturer inside the fireplace’s combustion chamber.
• Facing or trim materials must never extend above the removable glass door.
• Trim materials must not interfere with the operation of the doors for service access and maintenance.
• This appliance must be used ONLY with the type of gas indicated on the rating plate. Do not use this unit
with other gases unless it has been converted by a qualified technician.
• To ensure optimal performance, it is recommended to use a propane/LPG tank with a capacity of at least
100 gallons (379 L).
• When installed with electric accessories, all J. A. ROBY fireplaces must be grounded in compliance with
local codes, where applicable. If no such codes exist, consult the National Electric Code (ANSI/NFPA70)
or the Canadian Electrical Code (CSA C22.1).
1.2.2. USE
Supervise closely children who are in the same room as the appliance. Small children are more likely
to be subject to the risk of accidental burns. For maximum safety, add a barrier designed specifically
for children. This type of equipment is highly recommended if children are often near the appliance.
10
Explain the risks related to the fireplace’s high temperature to both children and adults.
WARNING:
Do not use the fireplace if a glass door is missing, cracked or broken.
WARNING:
For optimal combustion, the mandatory amount of glass (2 cups) on the burner is necessary.
Do not use the appliance without a protection system in the presence of small children.
Keep the appliance dry (mold and rust can cause odors and water could damage the controls).
Make sure the air inlets and the service access door are clear and uncluttered.
If any part of the fireplace is exposed to or immersed in water, refrain from using the appliance and
contact a qualified technician as soon as possible to have the damaged elements repaired or replaced.
If a log, a brick panel or any other accessory is damaged, do not use the fireplace until a qualified
technician has replaced it.
This direct-vented gas fireplace is balanced and sealed. About 10 to 20 minutes of operation are
required to stabilize the flame.
Do not use any accessory that has not been recommended by J. A. ROBY.
Do not add a fan, heat exchanger, or any other accessory that has not been approved for use with this
fireplace.
When the fireplace is not in use, it is recommended to place the control valve in the off position
(CLOSE).
Inspect the unit and its components to detect any damage; damaged parts may interfere with proper
operation.
This fireplace reaches high temperatures. To avoid burns and clothing catching fire, refrain from
touching hot surfaces. The fireplace will remain hot even after it is turned off. Never touch surfaces
before they have cooled down.
Supervise small children closely and make sure they do not touch or operate the gas fireplace. This
fireplace is designed for space heating; never use it for cooking or burning anything.
This fireplace is designed to be used with the type of gas indicated on the rating plate; never use solid
fuel (wood, coal, paper, cardboard, or other).
Do not use this appliance if any part has been immersed in water or any other liquid. Call a qualified
service technician immediately to have the appliance inspected and to replace any part of the control
system and any gas control mechanism that has been immersed.
1.2.3. FIRE HAZARD
• Cladding materials must be properly installed to prevent the risk of fire.
• Make sure that no debris are blocking the cap since restricted air flow affects gas combustion.
• Close the manual shutoff valve before installing the devices to test valve pressure. These tests must be
performed by a qualified technician.
• Do not store or use gasoline, any other flammable vapors or liquids in the vicinity of the unit.
• If the gas intake pressure at the valve is too high, it may cause overheating.
• Verify minimum gas intake pressure when other household gas appliances are operating. These
verifications must be performed by a qualified technician.
11
• Gas accumulation may ignite when purging the line.
WARNING:
It is important to handle all appliance components (doors, SmartCase®, burner, etc.) with care during maintenance.
THE INSTALLER MUST READ THIS MANUAL CAREFULLY BEFORE INSTALLING OR USING THIS
APPLIANCE. PLEASE REFER TO LOCAL CODES, WHERE APPLICABLE.
• Purge must be performed by a qualified technician.
• When purging gas lines, make sure there are no ignition sources such as sparks or open flames in the
same room as the fireplace.
• The adjustment of the valve is set at the factory. Do not modify.
• Do not connect 110 V wires to the fireplace’s valve.
• Never let any fuel or other volatile liquids (gasoline or alcohol) near your fireplace when it is operating.
• Do not obstruct fuel or air inlets in any way.
• Improper wiring will override the safety interlock system, which could cause an explosion.
• If you smell gas, carry out the steps indicated in paragraph 1.1 immediately.
• This unit is equipped with injectors sized specifically for use with natural gas (or propane gas). Do not
attempt to change the injectors in any way; this will cause abnormal operation of the unit and may cause
a fire.
1.2.4. MAINTENANCE
• You should have this fireplace inspected by a qualified technician every year. Make a habit of having
your gas fireplaces inspected once a year.
• If the glass door have to be replaced, we suggest to call a qualified technician to do it.
• Turn off the fireplace and let it cool before servicing or repairing it. Installation or repair of the fireplace
must be performed only by a qualified technician. Have the burner inspected every year.
• Always make sure the unit is working properly after every maintenance operation.
• Always keep the control boxes and burner clean. Turn off the gas supply before cleaning the fireplace.
• This unit is equipped to run on natural or propane gas. Conversion must be made by a qualified
technician.
• Have the exhaust system and the fireplace inspected by a qualified technician every year before the
heating season begins.
• Use a gentle cleaner on the windows. Do not use abrasive products; they will damage the surface of the
glass.
J. A. ROBY assumes no liability and makes no warranties in following cases:
A bad installation,
A usage with a damaged component,
A vent system installation that does not meet J. A. ROBY’s instructions,
Crushed glass was not placed properly on the burner,
A usage of any component not approved by J. A. ROBY.
12
1.3. GENERAL SAFETY INFORMATION
1.3.1. CARBON MONOXIDE
An installation that does not comply with the recommendations described in this manual can lead to carbon
monoxide emissions. As a safety measure, we strongly recommend for a carbon monoxide detector to be
installed near the unit.
Signs of a carbon monoxide poisoning (headaches, dizziness and nausea) are similar to those of influenza.
If you have these symptoms, your fireplace may not have been installed correctly. Turn off the gas fireplace
and go outside immediately for some fresh air! Have the fireplace inspected by a qualified technician.
1.3.2. GAS ODOR
Propane gas/LPG and natural gas are odorless. An odorant (usually sulfur) is added to each one of these
gases which makes them smell similar to rotten eggs. This will help you easily detect any eventual leak.
However, the odor added to these gases can fade. Gas may be leaking without releasing any smell. We
therefore strongly recommend that a gas detector be installed near the unit.
13
2. SPECIFICATIONS
2.1. TECHNICAL FEATURES
This fireplace is intended for use with the type of gas specified on the rating plate.
These fireplaces are approved for installations without changes at altitudes up to 2,000 feet (609
meters) in the U.S. and 1,370 meters (4,500 feet) in Canada.
If your system is installed at an altitude higher than 4,500 feet above sea level, please contact
your local authorities having jurisdiction over gas product installation to determine the specific
adjustments necessary at this higher altitude.
Fireplaces at 31,000 BTU/h or less are equipped with tempered glass. Tempered glass goes
through a quenching process (rapid cooling) that treats it to improve its mechanical properties; it
is more resistant than regular glass.
Fireplaces at 32,000 BTU/h are equipped with a glass-ceramic surface. Glass-ceramic is made
of microcrystals dispersed in a glassy phase. This particular structure gives this material higher
thermal shock resistance than tempered glass.
Do not use with solid fuel.
For use with glass door certified with this appliance only.
Not for use in Mobile Home.
Certified as:
Direct vent gas fireplace
CSA 2.33a-2012
ANSI Z21.88a-2012
LOCATION: Quebec, Qc, Canada
Vented gas Fireplace - Do not Use with Solid fuel.
15
Electrical requirement for optional fan (115 Volts, 60 Hz, and 0.20 Amps) normal power consumption is 23
watts. For Use with glass door certified with this appliance only. This appliance must be properly connected
to a venting system in accordance with the manufacturer’s installation instructions. WARNING: Failure to
position the part in accordance with these diagrams or failure to use only parts specifically approved with
this appliance may result in property damage or personal injury. Keep burner and control compartment
clean. See installation and operating instructions accompanying appliance. This appliance must be
installed in accordance with local code, if any; if none, follow the current ANSI Z223.1, or CSA B149,
Installation codes.
CAUTION: Hot while in operation. Do not touch the appliance. Severe burns may result. Keep children,
clothing and furniture away.
16
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing
properly damage, personal injury or loss of life.
1. This appliance is equipped with an ignition
device which automatically lights the pilot.
Do not try to light the pilot by hand.
2. BEFORE OPERATING smell all around the
appliance gas area. Be sure to smell next
to the floor because some gas is heavier
than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
Do not light any appliance.
Do not touch any electric switch; do not use
any phone in your building.
Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
If you cannot reach your gas supplier, call
the fire department.
3. Use only your hand to turn the gas
control knob. Never use tools. If the knob
will not push in or turn by hand, do not try
to repair it, call a qualified service
technician. Force or attempted repair
may result in a fire or explosion.
4. Do not use this appliance if any part has
been under water. Immediately call a
qualified service technician to inspect the
appliance and to replace any part of the
control system and any gas control which
has been under water.
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above
on this label.
2. Press the power button to the “OFF”
position or set the thermostat to the lowest
setting on the transmitter.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition
device which automatically lights the pilot.
Do not try to light the pilot by hand.
5. Turn off all electric power to the appliance.
6. Close the main gas valve. (Perpendicular
to pipe, 1/4 of turn)
7. Wait five (5) minutes to clear out any gas.
If you then smell gas, STOP!
Follow “B” in the safety information
above on this label. If you do not smell
gas, go to next step.
8. Open the main gas valve. (Parallel to
pipe, 1/4 of turn)
9. Turn on all electric power to the
appliance.
10. Close control access panel
11. Press the power button to the “ON”
position or set the thermostat to desired
setting on the transmitter
12. If the appliance will not operate, follow
the instructions “To Turn off Gas to
Appliance” and call your service
technician or gas supplier.
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if
service is to be performed.
3. Open control access panel.
4. Put the battery holder switch to the “OFF”
position.
5. Close the main gas valve. (Perpendicular
to pipe, 1/4 of turn)
6. Close control access panel.
17
2.3. FIREPLACE DIMENSIONS
2.3.1. LOO / RGR-25 (INSERT)
2.3.2. MISTRAL / RGP-25 (PENINSULA)
18
2.3.3. AUSTER / RGCG-25 (LEFT CORNER)
2.3.4. MOUSSON / RGCD-25 (RIGHT CORNER)
19
2.3.5. SIROCCO / RGB-25 (PANORAMIC)
2.3.6. PAMPERO / RGC-25 (CENTRAL)
20
2.3.7. SUROIT / RGV-25 (SEE THRU)
21
3. GAS FIREPLACE INSTALLATION
WARNING
No matter which vent system configuration you choose, you must absolutely install an insulating sleeve
over the first 8 ft. of vent, no exception. Always use the fireguard provided with the gas fireplace when
the vent is protected by the 8 ft. insulating sleeve and it goes through a wall/floor/ceiling/etc.
Before starting the installation of the fireplace, make sure to read and understand section 1.2.1 describing
the safety precautions to take when installing this appliance.
This device is designed to operate with a remote control or a wall switch.
When planning the fireplace installation you must determine:
Where the appliance will be installed.
The ventilation system configuration you will use.
Make sure to check that it complies with the formulas
listed in section 0 VENT INSTALLATION.
The configuration of the gas supply pipe.
The configuration of the electrical wiring.
The configuration of the recessed installation.
The finishing details.
The list of tools and installation equipment required.
Inspect thoroughly the unit and its components. Report any damaged component to the merchant.
3.1. INSERT INSTALLATION OF THE GAS FIREPLACE
• The framework should rest on top of the fireplace’s upper clearance post as well as on the air circulation
boxes located on the sides and at the back of the unit (see section 3.1.4 TOP CLEARANCE.)
• The fireplace can be installed directly on a hard combustible floor (see section 1.2.1) or on a platform
with an appropriate height. Do not place the fireplace on carpeting, vinyl or other soft floor coverings. You
can however install it on wood floor, plywood, particle board or other hard surfaces. Make sure the unit is
placed on a continuous floor or a sturdy platform and that the framework offers adequate support. No cold
air should enter the room from under the fireplace.
22
3.1.1. CERAMIC MANTLE EXAMPLE
Here is a finish example then installing ceramic
tiles around the gas fireplace. (Indicative only)
Two transition moulding (4) come with the gas
fireplace. They must fix (5) onto the zero clearance
box. (See through configuration need 4)
Minimum 12 inch of fibrocement (1) must be
installed between the top of fireplace and drywall
(6). You can continue with fibrocement (1) to the
ceiling or to the desired height.
The weight of the structure can be supported by the
top spacer but it is not recommended. Fixing it to
the wall or the ceiling frame is preferred.
WARNING: For the design of the mantle you can
add some transition but NO DRILLING IS
ALLOWED ON THE RED ZONE. Inside is the
combustion chamber and it’s essential to keep it
sealed for your security.
Drilling is only allowed onto the green zone to fix the
fibrocement. Ceramic tiles can be glue on the red zone.
The detachable louver (3) must be installed after ceramic
installation.
3.1.2. DRAWINGS OF MINIMUM CLEARANCES FOR INSTALLATION
Some dimensions are minimum. You can add some extra inches to evolve to your desired design.
3.1.2.1. LOO / RGR-25(INSERT) WITH BACK EXIT
3.1.2.2. LOO / RGR-25(INSERT) WITH SIDE EXIT
24
3.1.2.3. LOO / RGR-25(INSERT) WITH TOP EXIT
3.1.2.4. LOO / RGR-25(INSERT) CORNER INSTALLATION WITH TOP EXIT
25
3.1.2.5. MISTRAL / RGP-25(PENINSULA) WITH BACK EXIT
3.1.2.6. MISTRAL/ RGP-25(PENINSULA) WITH TOP EXIT
26
3.1.2.7. AUSTER / RGCG-25(LEFT CORNER) WITH BACK EXIT
3.1.2.8. AUSTER / RGCG-25(LEFT CORNER) WITH SIDE EXIT
27
3.1.2.9. AUSTER / RGCG-25(LEFT CORNER) WITH TOP EXIT
3.1.2.10. MOUSSON / RGCD-25(RIGHT CORNER) WITH BACK EXIT
28
3.1.2.11. MOUSSON / RGCD-25(RIGHT CORNER) WITH SIDE EXIT
3.1.2.12. MOUSSON / RGCD-25(RIGHT CORNER) WITH TOP EXIT
29
3.1.2.13. SIROCCO / RGB-25(PANORAMIC) WITH BACK EXIT
3.1.2.14. SIROCCO / RGB-25(PANORAMIC) WITH TOP EXIT
30
3.1.2.15. PAMPERO / RGC-25(PAMPERO) WITH TOP EXIT
3.1.2.16. SUROIT / RGV-25(SEE THROUGH) WITH SIDE EXIT
31
3.1.2.17. SUROIT / RGV-25(SEE THROUGH) WITH TOP EXIT
MINIMUM CLEARANCE WITH COMBUSTIBLE MATERIALS
Glass doors to opposite walls
- All models
42" (107 cm)
Vent to walls - All models
3" (8 cm) for the first 8 ft. of vent
(unless protected by a firewall) and 1"
(25.4 mm) for the rest of the vent.
Top of fireplace to ceiling
- All models
21¼" (54 cm)
Back of fireplace to adjacent material
- Models: LOO, MISTRAL, AUSTER
MOUSSON, and SIROCCO
0" (0 mm)
WARNING
A combustible surface located above the visible faces of the fireplace must not overhand these
faces by more than 3/4” (2 cm). A surface exceeding this limit is considered a mantle and must
comply with the requirements on shelves described in section 3.1.5 of this manual.
3.1.3. CLEARANCE FROM COMBUSTIBLE MATERIALS
32
To make installation easier, put the appliance in place and install the vent system before framing the
WARNING
Before framing your fireplace, check dimensions, framing methods and finished wall facing
details. Determine the total thickness of the finishing material – drywall, ceramic, tile, slate, etc.
Make sure the finished surface will be flush with the front or side of the unit.
Figure 3.1.3.a
Figure 3.1.3.b
CAUTION
Never obstruct the air duct inlet or outlet. This could pose a risk of overheating, which could lead
to a fire.
CAUTION
Remote wiring (wall switch) must be before the facing materials to avoid costly reconstruction.
The appliance must not be completely enclosed in an alcove. Clearance above the top of the
fireplace is 0 in. from the top clearance post. This means that combustible building materials can
rest directly on top of the upper mounts.
You must leave a 3 in. clearance between the first 8 ft. of vent and combustible materials
(unless protected by a firewall). The rest of the vent requires a clearance of 1 in.
fireplace. Remember to install the required clearance post on top.
If you install your fireplace on an outside wall or in an alcove, use a firewall and drywall in compliance
with local building codes.
3.1.4. TOP CLEARANCE
Top clearance post are not installed when
you receive your fireplace. They must be
mounted before installing the unit. Eight
machine screws are already placed on top
of the fireplace where clearance post will
go (2 screws per spacer). Please see the
following illustrations.
3.1.5. FACING MATERIALS
Only non-combustible materials (brick, slate tile, steel or other non-combustible materials allowed by local
standards) can be used to cover the appliance’s non-removable/fixed surfaces.
33
3.1.6. SHELF SIZE
SHELF SIZE (IN.)
Distance from the
top of the fireplace
Authorized shelf
depth
0 2 1
3
2 4 3 5 4 6 5
7
6 8 7
9
Figure 3.1.5.b
Figure 3.1.5.a
A shelf may be installed above the fireplace as long as it complies with the authorized dimensions. Noncompliance could result in a fire.
3.2. VENT INSTALLATION
3.2.1. INSTALLATION PRECAUTIONS
•The installer must make sure to read and understand section 1.2.1 of this manual regarding
installation instructions.
•This appliance must be installed in combination with a ventilation system approved by J. A. ROBY.
Consult local building codes before starting the installation.
•The installer must use a vent configuration adapted to the installation.
Before installing the vent, the installer must read this fireplace’s and the vent kit’s manuals.
• Vents should only be installed by a qualified installer/technician. This person must comply with the
following safety rules:
• Wear gloves and safety glasses for his own protection.
• Be very careful when working on a roof or with ladders.
• Find where electrical wires are located in walls and ceiling.
The following actions will void your vent system’s warranty:
• Installation of any damaged vent system component.
• Unauthorized modification of the vent system.
• Installation that differs in any way from the one specified in section 3.2, INSTALLATION OF THE
VENT.
•Installation of any component not manufactured or approved by J. A. ROBY.
34
3.2.2. LOCATION OF WALL VENT OUTLETS
Installation in CANADA1
Installation in the US2
A
Clearance above a slope, veranda, porch, terrace or balcony.
12 in. (30 cm)
1
12 in. (30 cm)
2
B
Clearance to a window or door opening.
12 in. (30 cm)
12 in. (30 cm)
C
Clearance to a permanently closed window.
12 in. (30 cm)
9 in. (23 cm)
D
Vertical clearance under a ventilated soffit.
(For a vent outlet located within a horizontal distance of 2 feet (61 cm) from the
opening of the soffit to the center of the vent outlet.)
18 in. (46 cm)
5
18 in. (46 cm)
5
E
Clearance to a non-ventilated soffit.
12 in. (30 cm)
12 in. (30 cm)
F
Clearance under a veranda, porch, terrace or balcony.
12 in. (30 cm)
1-4
12 in. (30 cm)
5
G
Clearance to an inside corner.
3 in. (8 cm)
3 in. (8 cm)
H
Clearance to each side of the axis extending over a meter-regulator.
91 cm (3 ft) within a height of
4.5 m (15 ft.) above meterregulator
91 cm (3 ft) within a height of
4.5 m (15 ft.) above meterregulator
I
Clearance to a meter ventilation outlet.
3 ft. (91 cm)
1
3 ft. (91 cm) 5
J
Clearance to a non-mechanical air inlet adjacent to the building or to an air inlet
adjoining any other appliance.
12 in. (30 cm)
9 in. (23 cm)
K
Clearance to a mechanical air inlet.
6 ft. (1.83 m)
3 ft. (91 cm) above. If less
than 10 ft. (3m) horizontally
L
Clearance above a paved sidewalk or paved path located on a public property.
7 ft. (2.12m)
3
7 ft. (2.12m)
3
M
Clearance above the roof.
18 in. (46 cm)
18 in. (46 cm)
N
Clearance to adjacent walls, including neighbour’s houses
2 ft.
2 ft.
O
Clearance to an outside corner
0
0
NOTE:
1) In accordance with the most recent National Installation Code for natural gas and propane, CSA B419.1
2) In accordance with the latest National Fuel Code, ANSI Z223.1 / NFPA 54.
3) A vent must not come out directly above a sidewalk or paved driveway located between two family residences serving both dwellings.
4) Permitted only if veranda, porch, deck or balcony is fully open on at least two sides beneath the floor.
5) Clearance complying with local installation codes and the requirements of the gas supplier.
Figure 3.2.2
35
3.2.3. VENT CONFIGURATION
- ≤: less than or equal
- ≥: greater than or equal
- <: less than
- >: greater than
- V: vertical rise
- H: horizontal run
3.2.3.1. LEGEND
3.2.3.2. VENT TO BE USE WITH APPLIANCE
Flexible vent
For a short distance installation when the fireplace is near the external wall of the house. It must be
covered by the 8 feet insulation sleeve include with the appliance.
Any installation beyond 8 feet must be do with rigid sections.
The Gas Fireplace is approved to use a gas certified aluminum flexible of 4”x7” x 8’ support centered.
N.B. You need to buy a 4” male to male connector to install the 4 inch flexible onto fireplace connector.
Rigid vent
The rigid direct vent recommend with the gas fireplace are:
• Selkirk Direct Temp / gas & pellet 4” x 6-5/8.
• DuraVent DirectVent Pro 4” x 6-5/8.
The 8 inch insulating sleeve must be installed imperatively on the first 8 inches of air vent.
You must put high-temperature sealer between the 6 5/8 inch collar, the rigid vent end and the first
screwed section on the stove collar.
3.2.3.3. CONDITIONS TO BE MET
• Total vent length, including elbows (see 3.2.3.3), must not exceed 40 ft. H + V ≤ 40 ft.
• The first 8 ft. of vent (from the fireplace) must always be covered with the insulating sleeve provided
with the fireplace; no matter the model or configuration type.
• The first 6 in. of vent (from the fireplace) must be vertical.
• The horizontal run, including elbow equivalents (see 3.2.3.3), must not exceed 3 times the vertical rise
when it is greater than or equal to 1.33 ft. (16 in.) and less than or equal to 10 ft.
H ≤ 3xV only if 1.33 ft. (16 in.) ≤ V ≤ 10 ft.
Exception: 6 in. ≤ V ≤ 16 in. Hmax. = 48 in. (4 ft.)
• Maximum of 4 elbows for the entire exhaust length.
• Minimum of 1 ft. (0.3 m) is required between two vent elbows.
• No vent section should have a downward slope.
36
3.2.3.4. ELBOW EQUIVALENT FOR HORIZONTAL VENT LENGTH
Elbow
angle
Horizontal vent length
equivalent (He)
in.
ft.
1º
0.4
0.033
15º 6 0.5
30º
12
1
45º
18
1.5
90º
36
3
Figure 3.2.3.4.a
CAUTION:
No vent section should slope downwards (from the fireplace to the exterior vent outlet).
Note1: The first elbow has a value of 0 in horizontal vent length. The above table is valid for the 2nd, 3rd,
and 4th elbows.
3.2.3.5. VENT SECTION LENGTHS
Section lengths must be calculated as shown in the following picture:
37
Figure 3.2.3.5.a
3.2.3.6.WALL VENT INSTALLATION
Install the ventilation system in accordance with the manufacturer's instructions included with the
components. (See 3.2.3).
Install the unit in the desired location. Check to determine if studs, structural walls or rafters could pose a
problem when fastening the vent system.
The flexible horizontal vent lengths must be supported every 3 ft. (90 cm). Wall ties are provided for this
purpose. The vent support can be used to fasten both hard and flexible vents.
A fireguard is included with the fireplace; it is adapted to receive both the vent and the insulating sleeve
that covers the first 8 ft. of vent.
If the first 8 ft. of vent must go through a wall, cut out an 11.75 x 11.75 in. (30 x 30 cm) square hole or an
Ø11.75 in. hole and use the fireguard provided with the fireplace.
38
Cut and frame the interior wall where the exhaust vent will go. If the wall the vent goes through is made of
Figure 3.2.3.5b
a non-combustible material, an Ø 9½ in. (Ø 24.2 cm) hole is sufficient for a flexible duct; the fireguard will
not be required.
The horizontal length of the vent must be level or have a ¼ in. per foot upward slope.
CAUTION: Never allow the vent to go downwards. This could lead to improper exhaust venting and cause
a fire.
A firewall is required at each floor level and wherever the
vent goes through a wall.
Slide the vent toward the wall and carefully insert the pipe
into the vent cap. It is important that the vent pipe overlaps
the vent cap on a minimum of 1 ½ in. (3.8 cm). Fasten both
parts together using three self-drilling screws.
39
3.2.3.7.WALL OUTLET CONFIGURATION EXAMPLE
ASSEMBLY WITH 1 90° ELBOW
For a horizontal exhaust where Vt is between 6 in.
and 16 in we have Ht <4’
Vertical rise
V1 =0.5 feet.
Horizontal run
H1 =4 feet.
Total vertical rise
Vt = 0.5 feet
Horizontal equivalent of elbows
He = 3 feet (for a 90°elbow)
N= 1 (qty of elbow)
HC= (N - 1) x He = 0 x 3 feet. = 0 feet.
Total horizontal run
Ht = 0 ft. + 4 ft. = 4 ft.
0.5 < vertical rise < 1.33 ft.
0.5< 0.5pi < 1.33pi
Because 0.5ft. < Vt < 1.33 ft. use Ht < 4 ft.
Total distance Ht + Vt <40 ft.
4 ft. + 0.5 ft. = 4.5 ft.
4.5 ft. < 40 ft.
This assembly is accepted.
40
3.2.3.8.ROOF EXHAUST CONFIGURATION EXAMPLE
MAX VERTICAL VENT
Therefore the formula Ht < 3V
t
is not
Direct vertical vent with no elbow
Vertical rise
V1 = 40 ft.
Horizontal run
H1 = 0 ft.
Total vertical rise
Vt = 40 ft.
Horizontal equivalent of elbows
Hc= (0 - 1) x 90° = 0 x 3 ft. = 0 ft.
Total horizontal run
Ht= 0 ft. + 0 ft. = 0 ft.
Vertical rise < 10 ft.
40t. > 10 ft.
applicable
Total distance Ht + Vt <40 ft.
40 ft. + 0 ft.= 40 ft.
40 ft. < 40 ft.
This assembly is accepted.
41
3.2.3.9.ROOF VENT INSTALLATION
Figure 3.2.3.8.C
Figure 3.2.3.8.a
Figure 3.2.3.8.b
If your vent is 8 ft. long or less, you can use a flexible vent 4"
x7" x 8 ft long centered by internal support to prevent 4"
central exit vent from touching the 7" inlet vent.
If the vent is longer than 8 ft. it must be rigid 4" x 6-7/8". This
fireplace is not approved for a longer flexible vent.
Start by determining where the outlet will be on the roof, and
cut an opening that fits the fireguard used. Be careful: the
opening on the roof will be oval due to the angle of the roof.
Build an interior frame 9 x 12.5 in. for a 45° slope) around
the opening to allow a minimum clearance of 1 in. from
combustible materials. It is best to set the opening between
the beams to minimize the work.
In attics, you may use an insulating shield for attic as well as
an insulating sleeve. However, use of the fireguard is
required when the vent goes through combustible materials.
For a vertical vent outlet, you must cut roof covering on a radius of 18 inches around the opening. Then
fix the roof support to the roof with screws provided for this purpose. (Figure 3.2.3.8.c)
42
Pass the vent vertically through the hole in the roof and fasten
Figure 3.2.4.2.a
Figure 3.2.4.2.c
Figure3.2.3.8.d
Figure 3.2.3.8.e
Figure 3.2.4.2.b
to the roof support. The top part of the vent must be at least
16 inches higher than the highest part of the hole.
Make sure you have the correct flashing model; different
models that will fit your roof’s slope are available at your
retailer. Slide the flashing on the connector to have it sit flat
on the roof. There must be a good layer of sealant between
the flashing and the roof to waterproof the assembly. The vent
must come up at least ¾ in. above the flashing. Paint the
flashing to increase useful life and tightness. Replace shingles
at the base of the flashing.
Adjust the storm collar to the vent connector and apply a
generous layer of latex-based sealant on the top edge of the
flashing and slide the collar to make contact. Apply pressure
to seal assembly (figure 3.2.3.8.e) Encase the vent on the
connector and tighten.
3.2.4. ASSEMBLY AND FASTENING OF VENT SECTIONS
3.2.4.1.HARD VENT SECTION ASSEMBLY
• Apply a generous bead high-temperature latex-based sealant inside the female part of each section
as shown in figures 3.2.4.2.a and 3.2.4.2.b.
• Connect the two sections and have them overlap on at least 1.5 in. (3.8 cm).
• Fasten both sections together with three self-drilling screws as shown in figure 3.2.4.2.c. Some
section have a twist lock, lock it and secure it with three screw. Follow your vent manufacturer
manual...
43
3.3. INSULATING SLEEVE INSTALLATION
Figure 3.3.c
Figure 3.3.b
Figure 3.3.a
WARNING
Whatever the model of home and vent configuration, the insulation sheath must always be installed.
All our gas fireplace models come with an 8 ft. insulating sleeve. It must be installed when assembling the
vent with the fireplace. Before putting the vent in place and fastening it, slide the sleeve around it, leaving
only a few inches of the vent exposed. Fasten the vent to the fireplace and slide the sleeve back down so
that it completely covers the base of the pipe. Using heat-resistant tape (aluminum), secure the sleeve to
the fireplace.
If the sleeve needs to be held upright, fasten the end of the sleeve with three self-drilling screws. Screw in
the vent.
The Flexible installation need a 4” male to male connector. None is required in rigid installation.
3.4. FAN INSTALLATION
Fans are used to circulate the heat from the fireplace in the room. They are sold by two at your retailer’s
(optional). Fans are installed in the lower part of the fireplace. They must be fixed to the fasteners located
at the bottom of the fireplace using screws and oriented toward the recessed sides of the fireplace. To do
this, remove the SmartCase® (see 5.1) and place the fans as well as the thermo-disc (7.4).
44
3.5. DECORATIVE PANEL INSTALLATION
Figure 3.5.2.c
Figure 3.5.2.b
Figure 3.5.2.a
Figure 3.5.1.b
Figure 3.5.1.a
Figure 3.5.1.c
To make brick pattern plate installation easier a notch is made at the bottom of the plate to pass over the
burner without to remove it. But the surrounding burner plate or logs have to be removed. Otherwise you
cannot install the brick pattern plates.
Depending on the model, both plate sizes could be required. Always start by installing the small plate.
3.5.1. DECORATIVE BLACK GLASS INSTALLATION
It's possible to install black glass instead of brick decorative panel. You can buy it to your local retailer of
J.A. Roby product. The installation of the small glass panel is exactly the same than the small decorative
plate.
The installation of the large glass plate is slightly different. You have to insert the base of the glass plate
first then tilt it to the left or right to pass the door frame. Setting it down gently on the floor of the combustion
chamber and push it gently to the vertical position and secure it like the large decorative plate with the
tabs at the top of the fireplace.
3.5.2. SMALL DECORATIVE PLATE INSTALLATION
•Insert the plate from the top. To do so, tilt the plate and insert it between the beams, then push it up
(figure 3.5.1.a).
•Push the plate all the way to the back so that it stands vertically and press it against the base (figure
3.5.1.b).
•Fold the retaining tabs located at the top of the fireplace (figure 3.5.1.c).
3.5.3. LARGE DECORATIVE PLATE INSTALLATION
•Insert the plate from the top. To do so, tilt the plate and insert it between the little plates then push
up (figure 3.5.2.a).
•Push the plate all the way to the back so that it stands vertically and press it against the base (figure
3.5.2.b).
•Fold the retaining tabs located at the top of the fireplace (figure 3.1.2.c).
45
3.6. BURNER REMOVAL
Figure 3.7.a
Figure 3.7.b
WARNING
For optimal combustion, you must place the mandatory required amount of glass (2 cups) on
the burner.
• Remove the door as described in section 8.3.1.
• Unscrew the screw located on the left of the
burner (figure 3.6).
Move the burner completely to the left to remove
the hose from the air/gas mixture box and lift it
vertically.
3.7. BURNER INSTALLATION
To install the burner, place it completely on the left of the empty space located on the floor of the
combustion chamber. Then slide it to the right until the gas supply pipe fits into gas/air premix box of the
SmartCase
burner is in place, screw it in (figure 3.6)
®
(figure3.7.a). Make sure the pilot is aligned with the notch in the burner (figure 3.7.b). Once the
46
3.8. BURNER SURROUND INSTALLATION
WARNING
It is mandatory to install either the platform or imitation logs around the burner to maintain the
appropriate volume of the combustion chamber. Do not leave the space around the burner empty.
You can choose to install a platform with crushed glass or imitation logs around the burner.
3.8.1. IMITATION LOG INSTALLATION
Four log pieces are required to completely surround the burner (each one surrounds a corner of the
burner). If you have a recessed fireplace, two pieces will be enough (they will be installed in front of the
burner.) If you use four log pieces, start at the back. The large log goes on the left back corner and the
small one lines up on the right back corner of burner. Then install the other large log in front of the burner;
on the longer side, there is a clearance space to surround the pilot. The large log goes on the front right
corner of the burner. Finish installation by inserting the small log on the front left corner of burner, lining it
up with the large log (figures 3.8.a and 3.8.b). Finally, spread 3 cups of glass around the logs.
47
3.8.2. PLATFORM INSTALLATION
Figure 3.8.a
Figure 3.8.b
The platform is designed to be adapted to any configuration of the gas fireplace. Remove the glass door
(see 8.3.1) and install the platform as shown in the following images. Then, spread 3 cups of ember glass
evenly on the platform.
3.9. SAFETY SCREEN INSTALLATION
For maximum protection against burns that may be caused by touching the glass when the fireplace is
turned on, get safety screens for every glass side of your fireplace from your retailer and install them as
indicated in the figure below.
To install it you only have to insert the four holding screw at the same time in the corresponding diamond
hole and let in down to the corner of the diamond..
48
4. FIREPLACE SETTINGS
CAUTION
The screw must always remain in the threaded hole; never fully remove it.
Figure4.2.a
Figure 4.1
4.1. MAIN BURNER
The fireplace includes an adjustment for the air/gas premix (figure 4.1). It can be used when converting
from natural gas (NG) to propane gas (LP) or vice versa. For natural gas, the air/gas premix adjustment
screw must be completely screwed (toward the inside of the combustion chamber). For propane gas, the
adjustment screw must be unscrewed (do not remove it completely).
The air/gas premix adjustment screw is located under the combustion chamber. It can be accessed
through the small door located at the bottom (figure 4.1).
4.2. PROFLAMME 2 REMOTE CONTROL
The Proflamme2 remote control allows you to control the following functions on your gas fireplace:
Turning the main burner on/off.
Modulating the main burner flame (6 levels).
Controlling the thermostat and Smart thermostat functions.
Technical data:
Supply voltage: 4.5 V (3 x 1.5 V AAA batteries)
Room temperature range 0°C to 50°C (32°F to 122°F)
Radio frequency 315 MH
49
Remote control’s LCD screen:
Figure 4.2.1.b
Figure 4.2.1.a
CAUTION
The remote control and the receiver are radio frequency devices. Placing the receiver in or near
metal may considerably reduce the range of the signal.
4.2.1. REMOTE CONTROL AND FIREPLACE SYNCHRONIZATION
Push button 1 (figure 4.2.1.b) completely to the right.
Remove a battery from the remote control (figure 4.2.1.a)
Press the PRG button (button 2 in figure 4.2.1.b). You will hear three beeps.
Place the battery back in the remote control. You will hear three beeps again.
Put button 1 (figure 4.2.1.b) back in the center position.
The remote control is now synchronized.
Press the ON/OFF button on the remote control to turn the fireplace on (figure
4.2.2.).
50
4.2.2. REMOTE CONTROL SETTING
Figure 4.2.2.a
Figure 4.2.2.b
Temperature display:
With the system off, press both THERMOSTAT and MODE buttons at the same time (see figure 4.2.2.a).
Check the remote control’s LCD screen; a °C or °F symbol should have appeared at the right of the number
indicating room temperature (see figure 4.2.2.b).
Remote control of flame:
The PROFLAMME 2 system has six (6) flame intensity levels. When the system is on and the flame is at
its maximum level, each push on the downward arrow button (see figure 4.2.2.a) will bring flame height
one level lower until it there is no longer any flame.
The upward arrow button (see figure 4.2.2.a) increases flame height one level each time you push it. If
you press the upward arrow button when the system is on CPI mode (see section regarding IPI/CPI
modes), you will turn on the main burner at level six (6). Command reception is always confirmed by an
audible beep.
51
Room thermostat:
Figure 4.2.2.c
Figure 4.2.2.d
The remote control can act as a room thermostat. You can program a desired temperature on this
thermostat to control the comfort level in a room. To activate this function, press the Thermostat button
(figure 4.2.2.a). The remote control’s LCD screen will change to indicate that the room thermostat is turned
ON. The set temperature will be displayed (figure 4.2.2.c). To set the desired temperature, use the
upward/downward arrow buttons (figure 4.2.2.a).
Note: When room temperature drops below the set temperature, the fireplace will turn on automatically.
Smart thermostat:
The Smart Thermostat function adjusts flame height according to the difference between the set
temperature and the actual room temperature. When room temperature is close to set temperature, the
Smart function will lower flame.
To activate this function, press the Thermostat button until “SMART” on the right of the thermostat symbol
(figure 4.2.2.d).
To adjust set temperature, press the upward/downward arrow button (figure 4.2.2.a).
Note: When you turn on the Smart Thermostat function, manual flame height adjustment is deactivated.
52
Intermittent pilot (IPI) and continuous pilot (CPI) modes:
Figure 4.2.2.f
Figure 4.2.2.g
Figure 4.2.2.e
With the system turned off, press the Mode button to select the CPI or IPI function. Use the upward arrow
button to select the CPI mode and the downward arrow button to select the IPI mode.
Definition:
CPI Mode: The CPI mode keeps
the pilot turned on permanently,
no matter if the burner is turned on
or not.
IPI mode: During IPI mode, the
pilot only turns on to ignite the
main burner and when the
fireplace is operating.
Keylock:
This function locks the keys to prevent any unsupervised use.
A padlock is shown on the remote display when activated. (Figure 4.2.2.f)
To activate this function, press the Mode button and the upward arrow button
at the same time.
To deactivate this function, press the Mode button and the upward arrow button
at the same time.
Low battery alarm
How long batteries will last inside the remote control depends on several
elements: battery quality, how many times the appliance has been turned on,
how many times the room thermostat set temperature was changed, etc.
When batteries are low, a battery symbol appears on the LCD screen of the
remote control to warn you before the batteries die. This symbol disappears
once the batteries are replaced. (Figure 4.2.2.g)
53
5. FIREPLACE CONVERSION
CAUTION
You can make the fireplace less powerful (reduce the number of BTUs), but you cannot make it
more powerful due to the type of glass used for this fireplace.
Any changes to your fireplace must be performed by a certified professional.
It is forbidden to use damaged replacement parts or replacement parts not authorized by JA Roby.
Figure 5.1
To convert your propane gas fireplace to natural gas or vice versa, you need to contact your supplier to
get the SmartCase® required for the desired conversion.
5.1. CHANGING THE SMARTCASE®
If a component of the SmartCase® is broken, it is strongly recommended to completely remove the SmartCase®
for easier handling. For more complex problems, simply replace the SmartCase® by a new one.
Open the door as described in section 8.3.1.
Remove the burner as described in section 3.6
Disconnect the SmartCase® plug located on the
electrical box made of two power outlets; on the
left of the SmartCase®.
Close the manual gas valve.
Unscrew the gas intake pipe from the SmartCase®.
Unscrew the four screws from the SmartCase® as
illustrated in figure 5.1.
Then carefully remove the SmartCase® from the
fireplace.
Note: It is strongly recommended to plan for a 12 in. minimum additional length of gas pipe inside the
fireplace (under the combustion chamber) to make SmartCase® maintenance easier. This way, the
technician will not have to disconnect the gas supply to work on the SmartCase®.
54
6. GAS INSTALLATION AND ADJUSTMENT
CAUTION
Never connect the gas line directly to the fireplace operating on propane (LPG) or natural gas (NG).
This system requires an external regulator (not supplied). Install the external regulator directly on the
cylinder and adjust the pressure according to the table featured in section 6.4.
WARNING
Connection of gas lines to the appliance must be performed by a certified installer. Observe all local
installation codes.
Figure 6.2
6.1. CHECKING GAS TYPE
Use the type of gas suitable for the fireplace you are installing. If you use a type of gas not suitable for the
fireplace refer to a merchant who can recommend a fireplace suited to the type of gas you are using or
provide you with a conversion kit. Bring gas pipes to where the fireplace will be installed.
6.2. INSTALLATION EQUIPMENT REQUIRED FOR GAS LINES
Make sure you have on hand the following items before installing the fireplace:
•An external regulator. The installer must supply an external regulator for propane/LPG connection.
The purpose of the regulator is to reduce incoming gas pressure (Table 6.4). If intake pressure is
not adjusted properly, the SmartCase®’ automatic valve could be damaged (see section 6.4).
• A pipeline network (check local codes).
• CSA approved gas lines sealant.
• A manual valve has to be placed inside the lower compartment of the appliance (before SmartCase®)
(figure 6.2).
• A pressure gauge connection.
• A sediment trap (recommended) (figure 6.2).
• An approved flexible gas line equipped with a connector (figure 6.2).
55
Note: The gas line connection can be made of a 3/8 in. (12 mm) rigid tube or an approved flexible
Natural gas (NG)
Propane (PG)
Ideal intake pressure
7" w.c. / 1.74 kPa
11" w.c. / 2.8 kPa
Min. Intake pressure
3.5" w.c. / .87 kPa
8" w.c. / 1.99 kPa
Max. Intake pressure
10.5" w.c. / 2.61 kPa
13" w.c./3.23 kPa
IMPORTANT
Install the main gas valve (stop valve) in an accessible location. The valve allows you to block the
fireplace’s gas intake. Check building codes specifications regarding the location of the manual gas
CAUTION
Use a propane gas-resistant joins sealant (metallic compound) to secure your gas lines.
connector. It is possible that other codes apply in your area. Please consult local authorities and the
National Fuel Gas Code ANSI.z223.1, NFPA54 in force. In Canada, consult the CAN/CGA-B149 (1 or
2).
Note: It is strongly recommended to plan for a 12 in. minimum additional length of gas pipe inside the
fireplace (under the combustion chamber) to make SmartCase® maintenance easier. This way, the
technician will not have to disconnect the gas supply to work on the SmartCase®.
6.3. INSTALLATION CODE
Apply a light coat of joint sealing compound (metallic compound). Make attention to do not put excess
sealant. Excess sealant compound in pipes can lead to clogging the burner system.
We recommend installing a sediment trap in the supply line (figure 6.2). Install it where residues are not
likely to freeze. A sediment trap is designed to trap moisture and contaminants to prevent them from
reaching the gas burner control system.
6.4. GAS PRESSURE
• It is essential to use the type of gas specified on the nameplate of the unit. In case of discrepancy, STOP
EVERYTHING and contact your merchant to get a SmartCase® that matches the type of gas you are using.
• To make installation easier, a 12 in. (30 cm) flexible duct equipped with a manual valve is supplied with
the appliance. Install the 3/8 in. (12 mm) supply line and fasten it to the shutoff valve.
• Once gas line installation is completed, purge gas lines and check that all connections as well as the gas
meter (or tank) connected to the fireplace are tight. Make sure there are no leaks (see section 6.6).
• To adjust flame height, turn the HI/LO control knob located on the automatic valve.
56
• The fireplace must be disconnected from the gas supply system when components that measure
WARNING
Never use an open flame to check for gas leaks.
Figure 6.5
6.2).
intake gas pressure are being installed. Once the gas supply is reconnected, check all connections as
well as the gas meter (or tank) connected to the fireplace for tightness. Make sure there are no leaks
(sees section 6.6).
6.5. PROCEDURE FOR CHECKING GAS PRESSURE FROM THE
FIREPLACE VALVE
• Make sure the manual valve is closed.
• Loosen the input “IN” and/or the output “OUT”
pressure verification port(s) by turning counter
clockwise with a 1/8 in. (3 mm) wide screwdriver
(figure 6.5).
• Connect the pressure gauge to the input “IN”
and/or output “OUT” pressure verification port(s)
using a rubber hose with a 5/16 in. (8 mm) inner
diameter.
• Open the manual valve (you will get the intake
pressure).
• Turn on the fireplace to check outlet pressure.
• When you are done reading the pressure gauge,
turn off the fireplace, close the manual valve, disconnect the hose and tighten the screw(s) (clockwise)
with a small flat screwdriver (1/8 in. wide).
• Make sure the output pressure of the automatic valve is comprised between the numbers listed in this
table.
WARNING
Connection must be performed by a certified
installer.
A manual shut-off valve must be installed before
the SmartCase®. It must be easy to access (see figure
CAUTION
57
6.6. VERIFICATION OF GAS LINE TIGHTNESS
Figure 6.6
Figure 6.7
WARNING
Never use an open flame to check for gas leaks.
Fill a spray bottle (figure 6.6) with soapy water (5% soap, 95% water).
Spray liberally over all screwed gas line connections (from the tank to the
fireplace).
If no bubbles appear it means the assembly is tight.
If there are bubbles, it means there is a gas leak. If this occurs, immediately
refer to section 1.2.1 and follow instructions.
6.7. OPEN OR CLOSE MANUAL VALVE
To open or close manual valve, pull the little access panel at the base of the stove and turn the knob to
the require position as shown on Figure 6.7
58
7. ELECTRICAL INSTALLATION
WARNING
Electrical connections should only be performed by a qualified and licensed electrician. All wiring must
comply with local, provincial and municipal codes.
Figure 7.1
7.1. WIRING
Connecting the appliance is easy. Connect the thermodisc’s power cable (if your fireplace is equipped with
a ventilation kit) to the electrical box and connect the SmartCase® to the electrical box. Connect the electrical
boxes to the home electric panel with a 14-2 wire (figure 7.1).
7.2. ELECTRICAL BOX
The electrical box is used to power the SmartCase® and the heat circulation fans. The box is equipped with
two hook-ups and it must be wire to the home electric panel.
59
7.3. WALL SWITCH INSTALLATION & OPERATION
7.3.1. WIRING
You can put the Main Switch of the SmartCase® into a wall switch by disconnecting the main switch of the
smart case and wire it to the wall switch. (It's only a signal running into wire (DON'T use any POWER
SOURCE or you can permanently damage the SmartCase®)
7.3.2. OPERATION WITH WALL SWITCH
To use fireplace without remote you have to:
Set the 3 positions switch to the left position
(ON).
Use the wall switch to turn on and turn off the
fireplace.
N.B. The SmartCase® have an automatic 24 hours
auto extinguish. To ignite again simply turn off the
wall switch and turn it on again.
To use fireplace with remote and wall switch you
have to:
Set the three position switch to centered
position (remote)
Keep the wall switch on and operate the fireplace with the remote.
N.B. The wall switch now control the pilot and main power of the SmartCase. Like the bypassed main switch.
The SmartCase® have an automatic 24 hours auto extinguish. To ignite again simply push power button on
the remote.
60
7.4. ELECTRICAL DIAGRAM OF SMARTCASE®
61
7.5. THERMODISC BOX INSTALLATION
Figure 7.4.a
Figure 7.4.b
Figure 7.4.c
When installing your fan kit, you must install the thermodisc box. This box will turn fans on automatically
when the fireplace reaches ideal temperatures.
To install the thermodisc box, open the small door located at the
bottom of the unit.
Locate the two screws that secure the thermodisc box, as shown in the pictures below.
Screw the thermodisc box as illustrated in this image.
62
8. USE
Figure 8.1.2
8.1. FIRST USE OF THE FIREPLACE
8.1.1. ODOR
During the first fire, an odor caused by paint curing will be released. When you first use the fireplace, it is
suggested to let it operate for several hours before turning on the fans (if you fireplace is equipped with
fans). This will ensure proper curing of the paint. It could make your home’s smoke alarm go off. Open
windows to ventilate the room.
8.1.2. IGNITION
Before turning on your fireplace, you must make sure:
To have read and understood sections this manual.
Your fireplace was installed by a qualified or certified technician.
Your appliance is properly powered by a gas intake and that no manual valves are closed.
Your intake gas pressure complies with the ones listed on the fireplace’s nameplate (see table in
section 2.1).
Tightness of all gas lines was thoroughly checked as described in section 6.5.
Your fireplace is properly connected to the home’s electrical power supply.
You have 3 new AAA batteries in your remote control.
You have 4 new AA batteries in the "battery holders" box of the SmartCase
The remote control is properly synchronized with the fireplace (see 4.2.1 to synchronize the remote
control).
The SmartCase
The glass is properly placed in its frame. Never operate the appliance if the glass door is not in place.
®
is in the ON position (figure 8.1.2 below).
®
located inside the fireplace.
63
• To turn your fireplace on, simply press the ON/OFF button on your remote control or place the wall switch
During the first few uses, a white film may appear on the windows as a result of the elimination of
some paint particles. It is recommended to clean the windows after the unit has cooled, otherwise the
white film becomes difficult to remove. Use a non-abrasive cleaner and DO NOT ATTEMPT TO CLEAN
THE GLASS WHEN HOT.
Figure 8.1.3.
in the ON position if your fireplace is not equipped with a remote control.
• You will hear a beep: it means the fireplace received the signal. If you hear two beeps, it means the
batteries in the SmartCase® are low (change the batteries). (See 9.6)
• A few seconds after, you will hear the sparker "spark": pilot is being ignited. This generally takes 3 to 15
seconds. After 30 seconds, the sparker will stop “sparking” as a precaution measure; it will start another
30-second period. During the first ignition, gas lines may not be properly purged which would cause air to
remain inside the gas intake. The first ignition may therefore require two 30-second “sparking” periods. If after these two “sparking” periods the pilot is still not lit, turn off your fireplace and refer to the
troubleshooting guide (section 10).
• Once the pilot is lit, the sparker stops "sparking" and the main valve opens to ignite the main burner. It
should take 3 to 10 seconds, for the main burner to ignite. If the pilot has been lit for 10 seconds and the
burner is still not ignited, put the wall switch in the OFF position or press the OFF button on the remote
control and refer to the troubleshooting guide (section 10).
Note: When you turn on the fireplace, condensation forms on the inside surface of the glass. This
condensation is normal and will disappear within a few minutes as the glass heats up.
8.1.3. PILOT FLAME
Make sure the pilot flames are wide enough, they must reach the thermocouple and burner otherwise the
burner will not ignite (figure 8.1.3).
64
8.1.4. EXTINCTION
To turn off the fireplace, simply press the ON/OFF button of the remote control or put the wall switch in
the OFF position if your fireplace is not equipped with a remote control. You will hear a beep: it means the
fireplace received the signal.
If you do not hear a beep and the fireplace does not turn off, refer to the troubleshooting guide (section 1).
8.2. NOISES FROM THE USE OF THE FIREPLACE
Your fireplace may make cracking sounds when operating. They are caused by the thermal expansion of
the various metal components that make up your fireplace. These sounds are not the sign of a defect and
do not affect the durability of your fireplace.
The gas control valve makes a subtle clicking sound when going from the ON to the OFF position and vice
versa. This is completely normal for a regulator and an automatic gas valve.
65
8.3. HANDLING THE DOOR
NOTE:
If the glass is broken follow this procedure to remove it. Contact your retailer to replace the entire
door; the glass is sealed in the frame and therefore cannot be replaced separately.
Figure 8.3.1.a
Figure 8.3.1.b
Always be careful when handling the fireplace door. We recommend you to wait for the door to be cool
before handling it.
8.3.1. REMOVING THE DOOR
•Step 1: Open the access
door located at the bottom of
the fireplace and untighten
the wing nut without remove
them. (Figure 8.3.1.a)
•Step 2: Lift up the tabs and completely remove the upper wing nuts.
66
• Step 3: Then carefully bring the door
Figure 8.3.1.c
Figure 8.3.2a
Figure 8.3.2.b
toward you to remove it completely
(step 3).
8.3.2. DOOR INSTALLATION
Step 1: Install the door and make sure it sits
properly in its place.
Step 2: Press firmly the door on the gas
fireplace and tightly screw the wing nuts at the
top of the door.(Figure 8.3.2.b)
67
Step 3: Tightly screw the wing
Figure 8.4.1
Figure 8.3.2.c
nuts at bottom of the door and
close the access door.
8.4. INSTALLATION AND REMOVAL OF SIDE AND BACK WINDOW FRAME
8.4.1. INSTALLATION AND REMOVAL OF SIDE WINDOW FRAMES
Installation of side window frame:
Start by inserting the tabs of the window frame in the opening located at the bottom of the appliance
(Figure 8.4.1.Detail B).
Tilt the top of the window frame and slightly lift it (without removing the bottom tabs from their slots)
to positioning the hook (Figure 8.4.1 Detail A) in place.
Push down to secure it in place.
Removal of side window frame:
Raise vertically to disengage the hook (Figure 8.4.1 Detail A).
Pull outward the appliance.
Disengage the bottom tabs. (Figure 8.4.1 Detail B)
68
8.4.2. INSTALLATION AND REMOVAL OF BACK WINDOW FRAME
Figure 8.4.2
Installation of back window frame:
Start by inserting the tabs of the door in the opening located at the bottom of the appliance (figure
8.4.2.Detail B)
Tilt the top of the door and slightly lift it (without removing the bottom tabs from their slots) to
positioning the hook (Figure 8.4.2 Detail A) in place.
Push down to secure it in place.
Removal of back window frame:
Raise vertically to disengage the hook (Figure 8.4.2 Detail).
Pull outward the appliance
Disengage the bottom tabs.(Figure 8.4.2 Detail B)
69
8.5. THERMAL INSULATION PANEL INSTALLATION
Type
Model
Side thermal
insulation panel
Back thermal
insulation panel
INSERT
LOO / RGR-25
2
1
PENINSULE
MISTRAL / RGP-25
1
0
LEFT CORNER
AUSTER / RGCG-25
1
1
RIGHT CORNER
MOUSSON / RGCD-25
1
1
PANORAMIC
SIROCCO / RGP-25
0
1
CENTRAL
PAMPERO / RGC-25
0
0
SEE THRU
SUROIT / RGV-25
2
0
Figure 8.5.1
Corresponding window frame must be removed to install the insulation box (see 8.4 “INSTALLATION AND
REMOVAL OF SIDE AND BACK WINDOW FRAME”) to remove the window frame.
Depending on your configuration, you have to a variable quantity of thermal insulation panel; see the next
chart to know how many.
8.5.1. SIDE THERMAL INSULATION PANEL INSTALLATION
Screws are already in place and include with your appliance. Untighten it not completely. Two groves are
cut into the top tabs to insert it easily. (Figure 8.5.1 Detail A)
Put the tab behind the bottom frame and align the screws into the grooves and tighten it enough to keep
in place the thermal insulation panel.
70
8.5.2. BACK THERMAL INSULATION PANEL INSTALLATION
Figure 8.5.2
WARNING
For optimal combustion, you must spread the mandatory required amount of ember glass (2 cups) on
the burner.
WARNING
The proper positioning of ember glass is essential to good and safe operation of the appliance. Ember
glass must be distributed evenly over the burner. Do not add additional ember glass, ornaments or
vermiculite. Use only the amount of ember glass provided with the appliance.
Screws are already in place and included with your appliance. Untighten it not completely. Two groves are
cut into the tabs to insert it easily.
Put the tab behind the bottom frame and
align the screws into the grooves and tighten
it enough to keep in place the thermal
insulation panel (Figure 8.5.2)
8.6. PLACEMENT OF EMBER GLASS ON THE BURNER
Ember glass is provided with your device. Always wear gloves to prevent cutting yourself on the glass.
After handling ember glass, carefully wash your hands with soap and water to remove all traces of glass.
Remove the frame of the window. Refer to section 8.3.1 REMOVING THE DOOR
Carefully open the bag containing the ember glass.
Spread ember glass carefully on top of the burner. Use the entire bag and distribute it evenly over the
entire surface of the burner so as to cover the entire plate and grooves.
71
9. MAINTENANCE
WARNING
Do not clean the glass when hot. Do not use abrasive cleaners or cleaners that contain ammonia.
Do not strike or slam the glass door.
WARNING
For optimal combustion, you must place the required amount of ember glass (2 cups) on the burner.
9.1. PRECAUTION
A certified technician should perform the annual inspection and maintenance of your fireplace in addition
to the general installation of the fireplace and vent system to keep everything up and running safely. The
gas intake should be cut and the fireplace should be completely cool during any maintenance. All parts of
equipment that are set aside for maintenance must be secured before the next use.
9.2. VENTILATION SYSTEM
An inspection of the vent pipes should be part of the annual maintenance visit. The vent system must not
be blocked. The instructions of the vent system manufacturer can provide specific details regarding the
inspection of the system. Any disassembled section must be reassembled sealed as required.
9.3. CLEANING THE GLASS
Note: The glass manufacturer recommends using a microfiber cleaning cloth and water.
• A thin white film, caused by some paint particles, may appear the first hours the fireplace is being used.
It is recommended to clean the glass after the first two weeks of use.
• Use a mild glass cleaner. Do not use abrasive products; they would damage the glass surface.
9.4. CLEANING THE BURNER AND COMBUSTION CHAMBER
• Remove the door (section 8.3.1).
• Remove the burner surround or the logs.
• Remove the burner (section 3.6).
• Empty the ember glass in a container.
• Use a vacuum cleaner to clean the burner and the entire bottom of the combustion chamber.
• Using a microfiber cloth, dust the surfaces of the combustion chamber.
• Remove any lint from main burner and from the pilot.
• Put the burner back in place (section 3.7).
• Carefully put the ember glass back in place.
• Put the door back in place.
72
9.5. CLEANING THE PILOT AND THERMOCOUPLE
Figure 9.6
Figure 9.5
The pilot flame can create a carbon deposit on the pilot and
thermocouple. To remove that deposit, use a steel wool
and gently scrub the metal parts. This will make ignition
more efficient.
9.6. BATTERY REPLACEMENT IN THE SMARTCASE®
The electronic ignition system of this appliance requires four 1.5 V AA batteries to operate when it is not
plugged into a wall socket in the house (or during a power outage). If the batteries are dead and there are
no spark where the pilot is, replace the batteries.
73
10. TROUBLESHOOTING
Problem
Possible causes
Solutions
1. When I press the
ON/OFF button on the
remote control, there is
no beep and the
fireplace does not turn
on.
1A.The remote control is not
properly synchronized with the
fireplace.
1B. The batteries are installed
incorrectly in the remote control
and / or the SmartCase® of the
fireplace.
1C. the batteries are too low.
1D. You are too far from the
fireplace.
1A: Refer to section 4.2.1 of this
manual and synchronize the
remote control.
1B: Check if batteries are properly
positioned in the remote control
and the SmartCase
®
.
1C: Change batteries.
1D: Move closer to the fireplace.
2. When I press the
ON/OFF button on the
remote control, I hear a
beep but I do not hear
the sparker "sparking"
even after 15 seconds.
2A. The sparker is dirty from
previous uses and the sparker
cannot create a spark.
2B. The sparker wire is damaged or
defective.
2A: Clean sparker as described in
section 9.5.
2B: Call your J. A. ROBY retailer to
have the SmartCase® replaced.
3. When I press the
ON/OFF button on the
remote control, I hear a
beep followed by
"sparks" but the pilot
does not ignite even
after two periods of
"sparks".
3A. The gas tank is empty.
3B. Gas intake ducts were not
purged when the fireplace was
installed.
3C. The sparker is dirty from
previous uses and there is not
enough spark.
3A: Call your gas supplier to have
your tank refilled.
3B: Contact a certified technician to
have the purge performed.
3C: Clean sparker as described in
section 9.5.
4. When I press the
ON/OFF button on the
remote control, I hear a
beep and "sparks", the
pilot ignites but the
burner does not light up
even 10 seconds after
ignition of the pilot.
4A. The pilot flame is too weak and
does not reach the
thermocouple.
4B. The thermocouple is dirty from
previous uses and no longer
detects or has trouble detecting
the pilot flame.
4C. The thermocouple wire is
damaged or defective.
4D. The SmartCase® is in the OFF
position.
4A: Call your J. A. ROBY retailer to
have the SmartCase® replaced
4B: Clean the thermocouple as
described in section 9.5
4C: Call your J. A. ROBY retailer
have the SmartCase® replaced.
4D: Put the SmartCase
®
in the ON
position, figure 8.1.2.
5. My fireplace turns itself
off.
5A. There is poor combustion, the
flame is too dirty.
5B. Gas tank is empty.
5C. Vent is blocked or defective.
5A: Start by checking the gas/air
premix adjustment screw and
adjust as described in section
4.1
5B: Call your gas supplier to have
your tank refilled...
5C: Contact a certified technician to
have your vent ducts inspected.
6. Bright orange flames
are coming off the
6A. There is poor combustion, the
flame is too dirty.
6A: Start by checking the air/gas
premix adjustment screw and
74
burner and making
soot.
6B. Air restrictor is not open
enough.
6C. Vent is blocked or defective.
adjust as described in section
4.1.
6B: Adjust gas intake and exhaust
properly as described in section
4.1.
6C: Contact a certified technician to
have your vent ducts inspected.
7. When I turn on my
fireplace, there are long
blue flames coming off
the burner and the
fireplaces stops
working after a minute.
7A. Not enough air intake.
7B. Gas exhaust panel is not open
enough.
7C. Vent is blocked or defective.
7A: Start by checking the air/gas
premix adjustment screw and
adjust as described in section
4.1.
7B. Adjust gas intake and exhaust
properly as described in section
4.1.
7C: Contact a certified technician to
have your vent ducts inspected.
8. I smell gas.
8B. Refer to the front page of this
manual immediately and follow
instructions
9. My remote control
cannot turn off the
fireplace.
9A. Batteries in the remote control
are dead.
9B. You are too far from the
fireplace.
9C. A component of the SmartCase® is
defective.
9A. Change the batteries in the
remote control.
9B. Move closer to the fireplace.
9C. Close the manual valve
upstream from the fireplace and
call your J. A. ROBY retailer.
10. When I turn my
fireplace off, the pilot
light remains lit.
10A. Your fireplace is in CPI mode.
10A. Refer to section 4.2.2 to set
the remote control in IPI mode.
11. A lot of soot is
accumulating on the
inner walls of the
fireplace.
11A. The exhaust panel is not open
enough and causes poor
combustion.
11B. The vent is blocked
11A. Refer to section 4.1 to adjust
the gas exhaust panel in a
more open position.
11B: Contact a certified technician
to have your vent system
inspected.
12. The flame intensity
varies.
12A Your fireplace is in thermostat
mode
12A. Refer to section 4.2.2 to
deactivated thermostat mode
75
11. ANNEXES
11.1. DECORATIVE PYRAMIDAL DOCK INSTALLATION AND CLADDING
OF CHIMNEY VENT
A decorative pyramidal dock is available to your local J.A. Roby dealer for the PAMPERO and the RGC25 configuration.
IMPORTANT: The dock have to be drop onto the fireplace right after installing the first vent section and
the 8 feet isolation sleeve. To keep access to screwing plate you have to put the dock onto a temporary
frame. We suggest 24 inch for the first section of vent to pass the dock over easily
It's important to put the weight of the frame and cladding on the fireplace and/or the ceiling.
N.B.: The dock can't support any weight and you have to keep ½ inches clearance around the
cladding and the pyramidal dock.
Because of heat concentration at the top of the dock, use only non-combustible material to build the
cladding and framing of the chimney vent. Like fire-resistant gypsum panel and metallic stud.
Put Protection over the dock to prevent scratching and damage.
76
Example:
This example use fire-resistant gypsum panel (4) and 1-1/2 metallic stud (2) (2" x 2" wood equivalent) a
flat exterior finish, plaster and painting.
The frame height is calculated inside the screwing frame (1). And the fire-stop (7) at the ceiling level.
a. If you elevate the fireplace, build the base.
b. Install the fireplace on the base (if you have one) or on the floor.
c. Build the ceiling frame for the fire-stop and centering it with the vent with a plumb line
d. Install the fire-stop (7) into the ceiling frame
e. Install the first direct vent section like indicated in this manual
f. Pass the pyramidal dock (5) over the direct vent section and elevate it over a temporary frame
(6)
g. Install the insulation sleeve (8) over the vent and attach it to the base of the vent.
h. Install the rest of the vent section to the roof and install correctly the insulation sleeve, do
not cut the sleeve, pass it into the fire-stop if so.
i. Build the frame cladding with the metallic stud (2) and screw it into the corner of the screwing
plate (1) fixed onto the fireplace.
j. Level the stud (2) and attach it with metal angle to the ceiling. You probably need to screw it
over the fireguard to fix them to joist.
k. Remove the temporary frame (6) and sit the pyramidal dock (5) onto the fire place.
l. Install gypsum panel (4) over the metallic stud (2). Insert it by 1" into the pyramidal dock.
m. Do plaster to finish, sand and paint it.
77
WARRANTY
J. A. ROBY GAS FIREPLACE LIMITED LIFETIME WARRANTY
CONDITIONS & LIMITATIONS
The following materials and workmanship in your new J. A. ROBY gas fireplace are warranted against defects for as long as you own the fireplace. This
cover:
Electrical 110V and millivolts components and wearable parts such as blowers, gas valves, thermal switch, switches, wiring, remote control, ignitor, gasketing,
SmartCase®, safety screen and thermal insulation panel are covered and J. A. ROBY will provide replacement parts free of charge during the first year of the
limited warranty.**
- Labour related to warranty repair is covered free of charge during the first year. However, repair work requires the prior approval of an authorized company
official. Labour cost. To the account of J. A. ROBY are based on a predetermined rate schedule and any repair work must be done through an authorized J.
A. ROBY dealer.
*= Digital pictures required
**= Construction of models may vary. Warranty applies only to components included with your specific appliance.
J. A. ROBY warrants its gas fireplace against manufacturing defects to the original purchaser only. Registering your warranty is not necessary. Simply provide
your proof of purchase along with the model and serial number to make a warranty claim. J. A. ROB Y reserves the right to have its representative inspect
any product or part thereof prior to honoring any warranty claim. Provided that the purchase was made through an authorized J. A. ROBY dealer your fireplace
is subject to the following conditions and limitations:
• This factory warranty is non-transferable and may not be extended whatsoever by any of our representatives.
• This gas fireplace must be installed by a licensed, authorized service technician or contractor. Installation must be done in accordance with the installation
instructions included with the product and all local and national building and fire codes.
•This limited lifetime warranty does not cover damages caused by misuse, lack of maintenance, accident, alterations, abuse or neglect and parts installed
from other manufacturers will nullify this warranty.
•This Limited Lifetime Warranty further does not cover any scratches, dents, corrosion or discoloring caused by excessive heat, abrasive and chemical
cleaners, artificial logs and glass ember.
•J. A. ROBY warrants its burners against manufacturing defects: During the 10 first years, J. A. ROBY will replace or repair the defective parts covered
by the lifetime warranty at our discretion free of charge. From 10 years to life, J. A. ROBY will provide replacement burner at 50% of the current retail
price.
•During the first year only, this warranty extended to the repair or replacement of warranted parts which are defective in material or workmanship provided
that the product has been operated in accordance with the operation instructions and under normal conditions.
•After the first year, with respect to this Limited Lifetime Warranty, J. A. ROBY may, at its discretion, fully discharge all obligations with respect to this
warranty by refunding to the original warranted purchases the wholesale price of any warranted but defective part(s).
•J. A. ROBY will not be responsible for installation, labour or any other expenses related to the reinstallation of a warranted part and such expenses are
not covered by this warranty.
•Notwithstanding any provisions contained in this Limited Lifetime Warranty, J. A. ROBY’S responsibility under this warranty is defined as above and it
shall not in any event extend to any incidental, consequential or indirect damages.
•This warranty defines the obligations and liability of J. A. ROBY with respect to the J. A. ROBY gas fireplace and any other warranties expressed or
implied with respect to this product, its components or accessories are excluded.
•J. A. ROBY neither assumes, nor authorizes any third party to assume, on its behalf, any other liabilities with respect to the sale of this product.
78
•J. A. ROBY will not be responsible for : over-firing, downdrafts, spillage caused by environmental conditions such as rooftops, buildings, nearby trees,
hills, mountains, inadequate vents or ventilation, excessive venting configurations, insufficient makeup air, or negative air pressures which may or may
not be caused by mechanical systems such as exhaust fans, furnaces, clothes dryers, etc.
•Any damages to the fireplace, combustion chamber, heat exchanger, SmartCase
®
or other components due to water, weather damage, long periods of
dampness, condensation, damaging chemicals or cleaners will not be the responsibility of J. A. ROBY.
• All parts replaced under the Limited Lifetime Warranty Policy are subject to a single claim
• All parts replaced under the warranty will be covered for a period of 90 days from the date of their installation.
• The manufacturer may require that defective parts or products be returned or that digital pictures be provided to support the claim. Returned products
are to be shipped prepaid to the manufacturer for investigation. If a product is found to be defective, the manufacturer will repair or replace such defect.
•Before shipping your appliance or defective components, your dealer must obtain an authorization number. Any merchandise shipped without
authorization will be refused and returned to sender.
• Shipping cost are not covered under this warranty
• Additional service fees may apply if you are seeking warranty service from a dealer
• Warranty labour allowance is only for the replacement of the warranted part. Travel, diagnostic tests, shipping and other related charges are not covered
by this warranty.
DUE TO ON-GOING PRODUCT IMPROVEMENTS, ALL SPECIFICATIONS AND DESIGNS ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE.
AS REQUIRED BY THE DEPARTMENT OF ENERGY IN THE UNITED STATES, 10 CFR PART 430, THE WARRANTY IS VOID IF THIS PRODUCT IS
USED WITH A THERMOSTAT, THIS APPLIES TO PRODUCT INSTALLED IN THE UNITED STATES ONLY.