Jantar REGIS F, REGIS F-1-B, REGIS F-3-B Series Manual

REGIS F – Access or time and attendance controller with integrated fingerprint reader
9/2016
Black line
www.jantar.si
REGIS F
REGIS F-1-B reading frequency
125kHz
REGIS F-1-B reading distance
Up to 10cm
REGIS F-1-9 current consumption in standby mode
200mA REGIS F-3-B reading frequency
13.56MHz
REGIS F-3-B reading distance
Up to 7cm
REGIS F-3-B current consumption in standby mode
230mA Dimensions (mm)
(WxHxD)
Protection
IP21
Operating voltage
From 9V to 14V DC
Operating temperature
From -20°C to 60°C
Display
3” TFT - resistive touch
Tamper
Accelerometer
Display resolution
Humidity
10-80%, non condensing
Memory
500 finger prints 30000 cards or codes 100000 events
Inputs
Door status Push button
Outputs
Transistor output for el. strike
0.5A
Clock
Real time clock, battery backup (max. ten hours)
Communication
RS485 Ethernet
Keypad
Configurable buttons and selectable colors – with Keypad Editor
Sensor protection
> 15kV ESD protection
Sensor usage
> 1 million wear cycles
Contact
Description
Specification
1 - UIN
9-14V DC
Power supply
2 - GND
GND
Ground
3 - CA
CA - RS485
Communication line
4 - CB
CB - RS485
Communication line
5 - O0
El. strike output
Max. 0,5A When active = GND
6 - O1
Alarm output
When active = GND
7 - I0
Door status switch input
Active when connected to GND
8 - I1
Push button input
Active when connected to GND
Contact
Description
Specification
RJ45 connector
9 - TXP
Ethernet
TXP
1 – white/orange
10 - TXN
Ethernet
TXN
2 – orange
11 - RXP
Ethernet
RXP
3 – white/green
12 - RXN
Ethernet
RXN
6 - green
REGIS F – ACCESS or TIME AND ATTENDANCE CONTROLLER with INTEGRATED FINGERPRINT
TECHNICAL DATA
400 x 240
ETHERNET
Power supply
The controller need’s external power supply to operate. The Spider W40 power supply is sufficient to power two controllers and two 12V electric strikes or two 12V magnetic locks (0.5A). If you will use it as a standalone controller and low consumption electric strike (0.25A) you can use power supply Spider W5.
Voltage drops and cable signal interferences
When you connect the controller, use cable with a diameter of at least 0.22mm2. If the cable length exceeds 25m, use one twisted pair of UTP cables for the positive (+) pole and one for the negative (-) pole. The cable length between power supply and the controller should not exceed 50m. Take into consideration that a 0.22mm2 cable has a resistance of approximately 9 ohm per 100m. The power supply at the end of cable should be a minimum of 9V. If you are using el. strike, it is highly recommended that the voltage drop is calculated. At greater distances, a thicker cable of 0.5mm2 or more should be used wherever possible. If the load is, for example, 0.5A (with el. strike) then, on the
0.22mm2 cable voltage drop will be 4.5V at 100m. For the device with 60mA consumption, the voltage drop is 0.5V.
Reading distance depends on where the controller is installed. The presence of metal or interferences can significantly reduce the reading distance. DO NOT install the controller directly on metal surfaces and/or cover it with a metal cover. It is not recommended to install controllers closer than 30cm from each other in any direction. Otherwise, it may result in inaccurate readings or, indeed, in the controller not reading at
all.
CONNECTOR DESCRIPTION
For the Regis F-3-B to comply with EMC directives (CE), you have to put ferrite core on the cable as close to the controller as possible, making two turns!
Inputs, outputs and environment
Inputs:
Inputs are realized with opto-isolators. The input is active, when pulled to ground with an open collector transistor or mechanical switch, which is connecting the input pin of the controller to the Ground.
Outputs:
Output has a pre-installed protection diode for an inductive load. It is also protected from current overload. The best way is to use a
0.25A el. strike or a 0.5A el. magnet, which has to be connected to the same positive pole (+) as the controller. Connect the negative pole (-) to the door strike output (wire 3). When the output is active it is pulled to ground. This can be changed with function 5 – negate output (for el. magnet).
Reading range:
The controller has a program algorithm that, at power start, sets parameters based on the installation environment, so as to ensure an optimal reading range. DO NOT install the controller directly on metal surfaces and/or cover it with a metal cover; it may stop working/reading. If you plan to test the controller and move it onto different surfaces, then you have to reset it (power off/on) on each surface.
REGIS F – Access or time and attendance controller with integrated fingerprint reader
9/2016
Black line
www.jantar.si
Code
Description
REGIS F-1-B
Standalone, access or time and attend ance controller in F box, capacitiv e touch screen display, Frequency 1 25kHz, fi ngerprint reader for CODEKS software, Integrated Ethernet
REGIS F-3-B
Standalone, access or time and attendance controller in F box, capacitiv e touch screen display, Frequency 1 3.56MHz, fingerprint read er, for CODEKS software, Integrated Ethernet
Environment:
It is designed for indoor, non-condensing, applications. Do not expose the controller to direct contact with the elements such as rain, snow or sunlight. If the plastic housing is in a different color
than black, then there is a chance that the color will change (to some extend) in a few months or years if exposed to direct sunlight. The sensor surface is hard and extremely robust, and will
withstand years of normal wear-and-tear. Do not subject the sensor to sharp or hard objects since this might cause permanent damage. Cleaning should be done with a lint -free cotton textile. Do not subject the sensor surface to mechanical force. You must assure good cable joints, protected against moisture, otherwise corrosion may damage the controller. Damage in such cases is not covered by the warranty.
Installation:
Install the holder on the wall with two supplied screws. Use diagonal holes - it enables a small correction of the position of the controller (up, down, left, right). Connect wires to the controller and place it on the holder and press – after you hear the click, it is fixed. If you want to remove the controller from the holder, put the screwdriver into the side hole in push a little to move the pin holding the controller.
AS AN ACCESS OR TIME AND ATTENDANCE CONTROLLER
Access controller
As an access controller, it is intend ed for controlling entries, exits and passes of users in the system and controlling sliding doors, ramp, el. strike, turning alarm on/off… It needs to be set with CODEKS software. Set the software according to your requirements (time tables, users...) and send the tables. The keypad will serve for entering user codes.
Time and attendance controller
As a time and attendance controller, it is intended to register the
employee’s arrivals and exit s from work, lunch break, private and
business exits, sick leave... It needs to be set with CODEKS
software. In software you need to choose option “Time and attendance” for controller and reader. Set the software according
to your requirements (time tables, users...) and send the tables. The keypad will serve for choosing different time intervals (private, business…).
The default address of the controller is the same as the last digit of the IP address. E.g. if the IP address of the controller is 192.168.110.105, then the controller's address is 105. If you have more controllers on the communication line,
don’t duplicate addresses.
Communication
Ethernet:
Connect the controller to the computer through your LAN via connector on the back side. Please check the connection scheme which can be found on Jantar Forum. Use at least UTP CAT 5e cable. Adjust network settings of the controller using the Codeks Device Manager software so that it will function properly in your network. Please consult Codeks Device Manager’s manual.
RS485:
Connect the controller to the computer, with one of the power supplies, with communication converter, from the Spider family: Spider W5-USB, Spider W5-NET, Spider W40+NET. The RS485 communication bus is used between the controllers and Jantar software. Up to 128 controllers can be lined up into one communication line. The maximum length of the communication
line is 1000 cable meters. It is recommended that you use an FTP or S-FTP cable. Only a serial connection of controllers in a single
communication line is allowed. Star (parallel) connection is not allowed. All shields of S-FTP cables must be wired together and at one point connected to the earth. Individual connections to the earth are not allowed. Do not connect the shield of the cable to the ground of the controller.
In the event of problems in communication, a termination resistor needs to be added. We recommend using 120 Ohm resistors on each side of the cable. Converters are, on the RS485 side, protected with slow-blow fuses and transient voltage suppressors.
Changing back to standalone controller from access controller:
In the Codeks Device Manager software do the “Brainwash” of the controller. Address of the controller’s switches back to 255.
Correct and incorrect position of the finger on the sensor
Correct: Incorrect:
ORDERING CODES
REGIS [box]-[card]-[software]
Box: F Card: 1 – reading frequency 125kHz (cards)
3 – reading frequency 13.56MHz (cards)
Model: B – Black line
OTHER
Warranty only applies when the controller Regis is used with power supply or/and communication converter from the Spider family.
Please read through our warranty and disclaimer statements.
Connection scheme and additional support for the use of this product can be found on:
http://www.jantar.si/forum/en