Applying the supply voltage 34
Current and voltage transformers 34
Programming current transformers 36
Programming voltage transformers 37
2
Programming parameters 38
TCP/IP configuration 39
Parameters 42
User password (addr. 050) 42
Mean value 43
Averaging method 43
Min. and max. values 44
Energy meter 44
Mains frequency (Addr. 034) 45
Harmonics 46
Measured value relay 47
Measured value displays 47
Reset energy meter (Addr. 507) 49
Phase sequence 49
LCD contrast (Addr. 035) 50
Backlight 50
Time recording 51
Operating hours meter 51
Serial number (Addr. 754) 52
Commissioning 53
Applying the supply voltage 53
Applying the measured voltage 53
Applying the measured current 53
Rotation field direction 54
Checking the phase assignment 54
Checking the power measurement 54
Checking the measurement 54
Checking the individual power ratings 54
Check the sum power ratings 55
Comparators and monitoring threshold values 55
Comparator in the GridVis software 59
Function parameters 72
Table 1 - Parameter list 74
Number formats 79
Dimensional drawings 80
Measured value displays overview 82
Declaration of conformity 88
Connection example 90
Basic functions quick guide 91
TCP/IP addressing quick guide 92
UMG 96RM-EL
3
UMG 96RM-EL
General
Copyright
This operating manual is subject to the legal requirements for copyright protection and may not be, either
in whole or in part, photocopied, reprinted, or reproduced by mechanical or electronic means, or in any other
manner be duplicated or redistributed without the legally
binding, written agreement of
Janitza electronics GmbH, Vor dem Polstück 1,
D 35633 Lahnau, Germany.
Trademarks
All trademarks and their resulting rights belong to the respective holders of these rights.
Disclaimer
Janitza electronics GmbH takes no responsibility for errors or defects within this operating manual and takes no
responsibility for keeping the contents of this operating
manual up to date.
4
Comments on the operating manual
We welcome your comments. In the event that anything
in this operating manual seems unclear, please let
us know and send us an EMAIL to: info@janitza.de
Meaning of the symbols
The following pictograms are used in the operating manual at hand:
Dangerous voltage!
c
m
Danger to life or risk of serious injury. Disconnect system and device from power
supply before beginning work.
Caution!
Please follow the documentation.
This symbol warns of possible dangers
that can arise during installation, commissioning and use.
Note!
C
Instructions for use
UMG 96RM-EL
Please read the operating manual at hand as well as all
other publications that must be drawn from for working
with this product (in particular for the installation, operation or maintenance).
Follow all safety regulations and warning information.
If you do not follow the information, it can result in bodily
injury and/or damage to the product.
Any unauthorized changes or use of this device, which
transcend the mechanical, electrical or otherwise stated
operating limitations, can result in bodily injury or/and
damage to the product.
Any of such unauthorized changes constitute „misuse“
and/or „negligence“ in terms of the warranty for the product and therefore eliminates the warranty for covering
any potential damage resulting from this.
This device is to be operated and maintained exclusively
by specialized personnel.
Specialized personnel are persons, that based on their
respective training and experience, are qualified to recognize risks and prevent potential dangers that can be
caused by the operation or maintenance of the device.
Additional legal and safety regulations required for
the respective application are to be following during the
use of the device.
If the device is not operated according to
c
m
m
the operating manual, protection is no longer ensured and danger can come from
the device.
Conductors made from single wires must
be fitted with wire-end ferrules.
Only pluggable screw terminals with
the same number of poles and the
same type of construction are permitted
to be connected together.
5
UMG 96RM-EL
Concerning these operating instructions
These operating instructions are a part of the product.
• Read the operating instructions before using the device.
• Keep the operating instructions throughout the entire service life of the product and have them readily
available for reference.
• Pass the operating instructions on to each subsequent owner or user of the product.
C
6
All screw-type terminals included in
delivery are attached to the device.
Inspection on receipt
The prerequisites of faultless, safe operation of this device are proper transport and proper storage, set-up and
assembly, as well as careful operation and maintenance.
If it can be assumed that risk-free operation is no longer
possible, the unit must be immediately put out of operation and secured against being put back into operation
again.
The packing and unpacking must be carried out with
the customary care without the use of force and only
using suitable tools. The devices should be visually checked for flawless mechanical condition.
It can be assumed that risk-free operation is no longer
possible if the device, for example,
• has visible damage
• no longer works despite the mains power supply
being intact
• has been exposed to long-term adverse conditions
(e.g. storage outside the permissible climate limits without being adapted to the room climate, condensation etc.) or rough handling during transportation (e.g.
fall from a height, even if there is no visible external
damage etc.)
• Please check the delivered items for completeness
before you start installing the device.
The UMG 96RM-EL is provided for the measurement
and calculation of electrical parameters such as voltage,
current, power, energy, harmonics, etc. for building
installations, to distributors, circuit breakers and busbar
trunking systems.
The UMG 96RM-EL is suitable for installation in
permanent, weatherproof switchboards. Conducting
switchboards must be earthed. It can be mounted in any
position.
Measurement voltages and measurement currents must
originate from the same grid.
The measurement results can be displayed and can
be read and processed over the Ethernet interface.
The voltage measurement inputs are designed
for measuring in low voltage grids in which nominal
voltages up to 300V phase can occur in countercurrent
with ground and overvoltages of overvoltage category
III.
The UMG 96RM-EL current measurement inputs are
connected via external ../1A or ../5A current transformers.
8
Measurements in medium and high voltage systems
generally use current and voltage transformers.
The UMG 96RM-EL can be used in residential and
industrial areas.
Device characteristics
• Installation depth: 45 mm
• Supply voltage:
20V - 250V (45..65Hz) or DC 20V - 300V
• Frequency range: 45-65 Hz
Device functions
• 3 voltage measurements, 300 V
• 3 current measurements
(via current transformer)
• Ethernet interface
Performance characteristics - UMG 96RM-EL
General
• Front panel integration device with dimensions
96x96 mm.
• Connection via pluggable screw terminals
• LCD display with backlighting
• Operation via 2 buttons
• 3 voltage measurements inputs (300V CATIII)
• 3 current measurement inputs for
current transformer.
• Ethernet interface
• Working temperature range -10°C .. +55°C
• Storage of minimum and maximum values
(without time stamp).
Uncertainty in measurement
• Active energy uncertainty in measurement class
0.5 for ../5A transformer
• Active energy uncertainty in measurement class 1
for ../1A transformer
• Reactive energy, class 2
UMG 96RM-EL
Measurement
• Measurement in IT, TN and TT networks
• Measurement in networks with nominal voltage
up to L-L 480V and L-N 277V
• Measuring range current 0 to 5A eff.
• True RMS (TRMS)
• Continuous sampling of the voltage and current
measurement inputs
• Frequency range of the mains frequency
45 Hz .. 65 Hz.
• Measurement of harmonics 1 to 40
for ULN and I.
• Uln, I, P (import/delivery), Q (ind./cap.).
• Fourier analyses 1 to 40. Harmonic for U and I.
• 7 Energiezähler für
Active energy (import)
Active energy (export)
Active energy (without a backstop)
Reactive energy (ind.)
Reactive energy (capacitive)
Reactive energy (without a backstop)
Apparent energy
each for L1, L2, L3 and total.
9
UMG 96RM-EL
Measuring method
The UMG 96RM-EL measures uninterrupted and
calculates all root mean squares over a 10/12-period
interval (200ms). The UMG 96RM-EL measures the true
root mean square (TRMS) of the voltages and currents
applied to the measuring inputs.
Operating concept
There are several ways to program the UMG 96RM-EL
and retrieve measured values.
• Directly on the device using two buttons.
• Via the programming software of the GridVis.
These operating instructions only describe the operation
of the UMG 96RM-EL using the 2 buttons.
The programming software of the GridVis has its own
“online help”.
10
GridVis network analysis software
The UMG 96RM-EL can be programmed and read with
the GridVis network analysis software which is part of the
scope of delivery. For this a PC must be connected to
the UMG 96RM-EL via Ethernet.
Characteristics of GridVis
• Programming the UMG 96RM-EL
• Graphic representation of measured values
Connection variants
(gedrehtes Patchkabel)
Direct connection of a UMG 96RM-EL to a PC via Ethernet.
UMG 96RM-EL
(Twisted patch cable)
(gedrehtes Patchkabel)
UMG 96RM-EL
Connecting a UMG 96RM-EL to a PC via Ethernet.
UMG 96RM-EL
Switch
11
UMG 96RM-EL
Assembly
Installation location
The UMG 96RM-EL is suitable for installation in permanent, weatherproof switchboards. Conducting switchboards must be earthed.
Installation position
The UMG 96RM-EL must be installed vertically in order
to achieve sufficient ventilation. The clearance to the top
and bottom must be at least 50 mm and 20 mm
at the sides.
The UMG 96RM-EL is mounted on the switchboard
by the side mounting brackets. These must be removed
before using the device. Mounting is carried out
by inserting and engaging the brackets.
Fig. UMG 96RM-EL
mounting bracket
(side view)
Failure to comply with the minimum
m
spacing can destroy the UMG 96RM-EL
at high ambient temperatures!
UMG 96RM-EL
13
UMG 96RM-EL
Installation
Supply voltage
A supply voltage is required to operate the UMG 96RMEL.
The voltage supply is connected via plug-in terminals
on the back of the device.
Before applying the supply voltage, ensure that
the voltage and frequency correspond with the details
on the nameplate!
The supply voltage must be connected via a UL/IEC
approved fuse (6 A, type C).
L
N
Fuse
Separator
Fig. Connection example of the supply voltage
to the UMG 96RM-EL
14
m
UMG 96RM-EL
• In building installations, the supply
voltage must be provided with a
disconnect switch or circuit breaker.
• The disconnect switch must be attached
near the device and must be easily
accessible by the user.
• The switch must be labelled as a
separator for this device.
• Voltages that exceed the permissible
voltage range can destroy the device.
15
UMG 96RM-EL
Voltage metering
The UMG 96RM-EL can be used for voltage measurement
in TN, TT and IT systems.
Voltage measurement in the UMG 96RM-EL is designed
for the 300 V overvoltage category CATIII (4 kV rated
pulse voltage).
L1
L2
277V/480V 50/60Hz
L3
N
PE
V1V3V2VN
AC/DC
4M
4M
4M
4M
DC
Measuring voltage
UMG 96RM-EL
Auxiliary energy
Fig. Principle circuit diagram - Measurement in three-phase
4-wire systems.
16
In systems without a neutral, measured values that
require a neutral refer to a calculated neutral.
L1
L2
480V 50/60Hz
L3
Impedanz
V3V2
VN
AC/DC
4M
4M
DC
System
earthing
V1
4M
4M
Measuring voltage
UMG 96RM-EL
Fig. Principle circuit diagram - Measurement in three-phase
Auxiliary energy
3-wire systems.
Rated mains voltage
Lists of the networks and their rated mains voltage
in which the UMG 96RM-EL can be used.
UMG 96RM-EL
Three-phase 4-wire systems
with earthed neutral conductor.
U
/ U
L-N
L-L
66 V/115 V
120 V/208 V
127 V/220 V
220 V/380 V
230 V/400 V
240 V/415 V
260 V/440 V
277 V/480 V
Fig. Table of the rated mains voltages suitable
for the voltage measuring inputs according
to EN60664-1:2003.
Maximum rated voltage
of the network
Unearthed three-phase, 3-wire systems.
U
L-L
66 V
120 V
127 V
220 V
230 V
240 V
260 V
277 V
347 V
380 V
400 V
415 V
440 V
480 V
Fig. Table of the rated mains voltages suitable
for the voltage measuring inputs according
to EN60664-1:2003.
Maximum rated voltage
of the network
17
UMG 96RM-EL
Voltage measurement inputs
The UMG 96RM-EL has three voltage measurement
inputs (V1, V2, V3).
Overvoltage
The voltage measurement inputs are suitable for
measurement in networks in which overvoltages of
overvoltage category 300V CATIII (4 kV rated pulse
voltage) can occur.
Frequency
The UMG 96RM-EL requires the mains frequency for
the measurement and calculation of measured values.
The UMG 96RM-EL is suitable for measurements in the
frequency range of 45 to 65 Hz.
18
L1
L2
L3
N
Fuse
Separator
Fig. Connection example for the voltage measurement
UMG 96RM-EL
When connecting the voltage measurement, the following
must be observed:
• A suitable separator must be provided in order
to switch off the power to the UMG 96RM-EL.
• The separator must be placed near the UMG 96RMEL, marked for the user and easily accessible.
• Use a fuse protected, UL/IEC approved 10A circuit
breaker (type C) as an overcurrent protection device
and separator.
• The overcurrent protection device must have
a nominal value that is designed for the short circuit
current on the connection point.
• Measurement voltages and measurement currents
must originate from the same grid
c
c
c
Attention!
Voltages that exceed the permitted
ratedmains voltages must be connected
via voltage transformers.
Attention!
The UMG 96RM-EL is not suitable for
the measurement of DC voltages.
Attention!
The voltage measurement inputs on
the UMG 96RM-EL are dangerous
to touch!
19
UMG 96RM-EL
Connection diagram, voltage measurement
• 3p 4w (addr. 509= 0), factory setting
L1
L2
L3
N
V1 V2 V3 VN
Fig. System with three-phase conductors and a
neutral conductor.
• 3p 4u (addr. 509 = 2)
L1
L2
L3
V1 V2 V3 VN
Fig. System with three-phase conductors and
no neutral conductor. Measured values that require a neutral refer to a calculated neutral.
20
• 3p 4wu (addr. 509 = 1)
L1
L2
L3
N
V1 V2 V3 VN
Fig. System with three-phase conductors and
a neutral conductor. Measurement via voltage
transformer.
• 3p 2u (addr. 509 = 5)
L1
L2
L3
V1 V2 V3 VN
Fig. System with three-phase conductors and
no neutral conductor. Measurement via voltage
transformer. Measured values that require a
neutral refer to a calculated neutral.
UMG 96RM-EL
• 1p 2w1 (addr. 509 = 4)
L1
N
V1 V2 V3 VN
Fig. Measured values derived from the V2 and
V3 voltage measurement inputs are assumed to
be zero and not calculated.
• 1p 2w (addr. 509 = 6)
L1
L2
V1 V2 V3 VN
Fig. TN-C system with single-phase, three-wire
connection. Measured values derived from the
V3 voltage measurement input Zero are assumed to be zero and not calculated.
• 2p 4w (addr. 509 = 3)
L1
L2
L3
N
V1 V2 V3 VN
Fig. System with uniform phase loading. The
measured values for the V2 voltage measurement input are calculated.
• 3p 1w (addr. 509 = 7)
L1
L2
L3
L1
L2
L3
L1
L2
L3
N
V1 V2 V3 VN
Fig. Three systems with uniform phase loading.
The measurement values L2/L3 resp. L1/L3 resp.
L1/L2 of the respective system are calculated.
21
UMG 96RM-EL
Current measurement
The UMG 96RM-EL is designed for connecting current transformers with secondary currents of ../1A and
../5A. The factory set current transformer ratio is 5/5 A
and may need to be adapted to the current transformers.
It is not possible to perform a direct measurement without a current transformer with the UMG 96RM-EL.
Only AC currents (and not DC currents) can be measured.
c
m
c
22
Earthing of current transformers!
If a connection is provided for the earthing
of secondary windings then this must
be connected to the earth.
Attention!
The UMG 96RM-EL is not suitable for the
measurement of DC voltages.
Attention!
The current measurement inputs are
dangerous to touch.
Load
Fig. Current measurement via current transformer
(connection example)
The attached screw terminal has to be
m
fixed sufficiently with two screws on the
device!
L1
L2
L3
N
Direction of the current
The current direction can be individually corrected
on the device or via the serial interfaces for each phase.
In the case of incorrect connection, the current transformer does not need to be subsequently reconnected.
Earthing of current transformers!
c
If a connection is provided for the earthing
of secondary windings then this must be
connected to the earth.
UMG 96RM-EL
c
Current transformer connections!
The secondary connection of the current
transformer must be short-circuited on this
before the current feed to the UMG 96RMEL is disconnected!
If a test switch, which automatically shortcircuits the secondary wires of the current
transformer, is available then it is sufficient
to set this to the „Test“ position insofar as
the short-circuiting device has been checked beforehand.
c
Open-circuit current transformers!
High voltage spikes that are dangerous
to touch can occur on current transformers
that are driven with open-circuit secondary
windings!
With “safe open-circuit current transformers” the winding insulation is rated such
that the current transformer can be driven
open. However, even these current transformers are dangerous to touch when they
are driven open-circuit.
Fig. Measurement in a three-phase net-work
with an unbalanced load.
• 3p 2i0 (addr. 510 = 2)
L1
L2
L3
I1I2I3
Fig. The measured values for the I2 current
measurementinput are calculated.
24
I1I2I3
Fig. System with uniform phase loading. The
measured values for the I2 current measurement
input are measured.
• 3p 3w3 (addr. 510 = 3)
L1
L2
L3
I1I2I3
Fig. Measurement in a three-phase net-work
with an unbalanced load.
UMG 96RM-EL
• 3p 3w (addr. 510 = 4)
L1
L2
L3
N
I1I2I3
Fig. System with uniform phase loading. The
measured values for the I2 and I3 current
measurement inputs are calculated.
• 1p 2i (addr. 510 = 6)
L1
L2
I1I2I3
Fig. Measured values derived from the I3 current
measurement input are assumed to be zero and
not calculated.
• 2p 4w (addr. 510 = 5)
L1
L2
L3
N
I1I2I3
Fig. System with uniform phase loading. The
measured values for the I2 current measurement
input are calculated.
• 1p 2w (addr. 510 = 7)
L1
N
I1I2I3
Fig. Measured values derived from the I2 and I3
current measurement inputs are assumed to be
zero and not calculated.
25
UMG 96RM-EL
Connection diagram, current measurement
• 3p 1w (addr. 510 = 8)
L1
L2
L3
L1
L2
L3
L1
L2
L3
I1I2I3
Fig. Three systems with uniform phase loading. The current measurement values of the
phases of the respective system where are no
CTs connected are calculated (I2/I3 resp. I1/I3
resp. I1/I2).
Caution!
c
The UMG96RM is only approved for
a current measurement using the
current transformer.
26
Ammeter
If you want to measure the current not only with the UMG
96RM-EL but also with the ammeter, the ammeter must
be connected in series with the UMG 96RM-EL.
UMG
I
S2
1
S
A
Einspeisung
Supply
(k)S
1S2(l)
2(L)(K)P1
P
Verbraucher
Consumer
Fig. Current measurement with an additional
ammeter (example).
Total current measurement
UMG 96RM-EL
If the current measurement takes place via two current
transformers, the total transformer ratio of the current
transformer must be programmed in the UMG 96RMEL.
UMG
I
S
S2
1
Einspeisung 1
Supply 1
1P1
(K)
(L)
1P2
Verbraucher A
Consumer A
1S1
1S
P1
1S1 1S22S1 2S2
(k)
(l)
2
P2
Einspeisung 2
Supply 2
2S1
(k)
(l)
2S2
Verbraucher B
Consumer B
2P
(K)
(L)
2P2
1
Fig. Current measurement via a total current transformer
(example).
Example: The current measurement takes place via two
current transformers. Both current transformers have
a transformer ratio of 1000/5 A. The total measurement
is performed with a 5+5/5 A total current transformer.
The UMG 96RM-EL must then be set as follows:
Primary current: 1000 A + 1000 A = 2000 A
Secondary current: 5 A
27
UMG 96RM-EL
Ethernet interface
The Ethernet network settings should be specified
by the network administrator and set on UMG 96RM-EL
accordingly.
If the network settings are not known, the UMG 96RMEL may not be integrated into the network through
the patch cable.
Ethernet
Connection
PC / Switch
28
m
m
Caution!
Connection of the UMG96RM-EL to the
Ethernet may only be carried out after discussion with the network administrator!
Caution!
The UMG 96RM-EL is factory-programmed
for the dynamic allocation of the IP settings
(DHCP mode).
Settings can be changed as described
in TCP/IP Configuration or, for example,
via an appropriate Ethernet connection
by means of GridVis software.
UMG 96RM-EL
29
UMG 96RM-EL
Operation
The UMG 96RM-EL is operated via buttons 1 and 2 with
the following functions:
• briefly pressing button 1 and 2:
next step (+1)
• pressing and holding button 1 and 2:
previous step (-1)
Measured values and programming data are displayed
on an LCD display.
There are display and programming modes. You can
avoid an unintentional change of programming data
by entering a password.
Display mode
In display mode, you can scroll through the programmed
measured values by pressing buttons 1 and 2. When
the device is delivered, all measured value indications
of profile 1 can be retrieved. For each measured value,
up to three measured values are indicated. The measured
value rotation can display selected measured value indications one after the other with a selectable changing
time.
30
Programming mode
You can view and change the necessary settings
of the UMG 96RM-EL in programming mode. Press button 1 and 2 simultaneously for about 1 second to switch
to programming mode after entering the password. If no
password is programmed, you get directly to the programming mode menu. Programming mode is marked
by the text „PRG“ on the display.
Press button 2 to switch between the following menus:
- Current transformer,
- Voltage transformer,
- Parameter list,
- TCP/IP device address,
- Subnet mask,
- Gateway address,
- Dynamic TCP/IP addressing (in/out).
If no button was pressed for about 60 seconds when you
are in programming mode, or button 1 and 2 are pressed
simultaneously for about 1 second, the UMG 96RM-EL
will switch back to display mode.
Supply
Max. value, HT/reference
Min. value, NT/supply
Mean value
Programming
mode
Total measurement
External conductor
External conductor
Password
CT: current transformer
VT: voltage
transformer
Button 2
Button 1
UMG 96RM-EL
31
UMG 96RM-EL
Parameters and measured values
All parameters necessary for operating the
UMG 96RM-EL, e.g. the current transformer data, and
a selection of frequently required measured values are
stored in the table.
The contents of most addresses can be accessed via the
serial interface and the buttons on the UMG 96RM-EL.
Only the first 3 significant digits of a value can be entered
on the device. Values with more digits can be entered
using GridVis.
The device always only displays the first 3 significant
digits of a value.
Selected measured values are summarised in measured
value display profiles and can be shown in display mode
using buttons 1 and 2.
The current measured value display profile and the
current display change profile can only be read and
changed via the Ethernet interface.
32
Example of the parameter display
On the UMG 96RM-EL
display the value “006” is
shown as the content of address “036”. This parameter
reflects the brightness of
the backlighting (0=dark, 9=
bright).
Example of the measured
value display
In this example, the UMG 96
RM-EL display shows the voltages L to N with 230 V each.
Button functions
UMG 96RM-EL
Display mode
Change mode
simultaneous
Browse
short
long
Measured
values 1a
Measured
values 2a
longshort
Measured
values 2b
Password
Programming
menu 1
(flashes)
Programming mode
short
long
(flashes)
Change mode
simultaneous
Browse
Programming
menu 1
Programming
menu 2
Programming
menu 3
Programming
Confirm selection
Short: digit +1
Long: digit -1
Short: value x 10
(decimal to the right)
Long: Value /10
(decimal to the left)
33
UMG 96RM-EL
Configuration
Applying the supply voltage
To configure the UMG 96RM-EL, the supply voltage
must be connected.
The level of supply voltage for the UMG 96RM-EL can
be found on the nameplate.
If no display appears, check the operating voltage
to determine whether it is within the rated voltage range.
Current and voltage transformers
A current transformer is set to 5/5 A in the factory.
The pre-programmed voltage transformer ratio only
needs to be changed if voltage transformers are
connected.
When connecting voltage transformers, the measurement voltage on the UMG 96RM-EL nameplate must be
observed!
34
c
C
m
Attention!
Supply voltages that do not correspond
to the nameplate information can lead
to device malfunction or destruction.
The adjustable value 0 for the primary
current transformer does not produce
any useful energy values and must not
be used.
Devices, which are programmed to automatic frequency detection, need approximately 20 seconds to detect grid
frequency. During this period, the measured values do not keep the confirmed
measuring accuracy.
UMG 96RM-EL
C
Current and voltage transformers
The GridVis software included with delivery can be used to individually program
the current and voltage transformer input
transformer ratios.
Only the transformer ratio of the respective group of the current inputs I1-I3 and
the voltage measurement inputs V1-V3 can
be adjusted on the device.
Fig. Indication to configure the current and
voltage transformers in the GridVis software.
35
UMG 96RM-EL
Programming current transformers
Switching to programming mode
• Simultaneously press buttons 1 and 2 in order
to switch to programming mode. If a user password
was programmed, the password request will appear
with “000”. The first digit of the user password flashes
and can be changed with button 2. The next digit is
selected by pressing button 2 and will begin flashing.
If the correct combination was entered or if no user
password was programmed, the device will enter programming mode.
• The symbols for the programming mode (PRG) and for
the current transformer (CT) appear.
• Confirm the selection with button 1.
• The first digit of the input area for the primary current
starts flashing.
Current transformer primary current input
• Change the flashing digit with button 2.
• Select the next digit to be changed with button 1.
The selected digit to be changed starts flashing.
If the entire number is flashing, the decimal point can
be moved with button 2.
Current transformer secondary current input
36
• Only 1 A or 5 A can be set as the secondary current.
• Select the secondary current with button 1.
• Change the flashing digit with button 2.
Leaving programming mode
• Simultaneously press buttons 1 and 2 to exit the programming mode.
UMG 96RM-EL
Programming voltage transformers
• Switch to the programming mode as described. The
symbols for the programming mode (PRG) and for the
current transformer (CT) appear.
• Use button 2 to switch to the voltage transformer
setting.
• Confirm the selection with button 1.
• The first digit of the input area for the primary current
starts flashing. The ratio of primary to secondary
voltage of the voltage transformer can be set in the
same way as the assignment of the current transformer
ratio of primary to secondary current.
Current transformer, primary
Programming mode
Units display
Current transformer, secondary
Current transformer symbol
Voltage transformer, primary
Programming mode
Units display
Voltage transformer,
secondary
Voltage transformer,
symbol
37
UMG 96RM-EL
Programming parameters
Switching to programming mode
• Switch to the programming mode as described. The
symbols for the programming mode (PRG) and for the
current transformer (CT) appear.
• Use button 2 to switch to the voltage transformer
setting. The first parameter of the parameter list
is shown by repeatedly pressing button 2.
Changing parameters
• Confirm the selection with button 1.
• The most recently selected address is displayed with
the associated value.
• The first digit of the address flashes and can be
changed using button 2. Button 1 provides a selection
of digits that, in turn, can be changed with button 2.
Changing the value
• Once the desired address is set, a digit of the value
is selected with button 1 and changed with button 2.
Leaving programming mode
• Simultaneously press buttons 1 and 2 to exit the
programming mode.
38
Fig. Password request
If a password was set,
it can be entered using
buttons 1 and 2.
Fig. Current transformer
programming mode
The primary and
secondary currents can
be changed using buttons
1 and 2 (cf. page 36).
Fig. Programming mode
Voltage transformer
The primary and
secondary currents can
be changed using buttons
1 and 2 (cf. page 37).
Fig. Programming mode
Parameter display
The individual parameters
can be changed
using buttons 1 and 2
(cf. page 32).
UMG 96RM-EL
TCP/IP configuration
Within an Ethernet, each device has a unique TCP / IP
address that can be assigned manually or from a DHCP
server. The 4-byte device address (0 to 3 byte) can
be extended in the TCP / IP configuration using the subnet mask and gateway data.
Setting the TCP / IP device address (addr) manually
• Select in the programming mode as described.
The symbols for the programming mode PRG
and the current transformer mode CT appear
on the display.
• Press button 2 three times to get to the TCP / IP settings for the device addressing.
• Press button 1 to select the desired digit. The selection is indicated by a flashing digit.
• Press button 2 to adjust the selected digit.
• Use button 1 to select the next digit and set it again
by pressing button 2.
• If byte is set to 0, the TCP / IP address can be set from
1 to 3 by pressing button 1. Then the display jumps
back to Byte 0 (no digit is flashing).
Description
Byte identification
(e.g. byte 0) of the address
Address value, byte 0
Fig. TCP/IP address, byte 1
A TCP / IP address consists
of 4 bytes with the following
structure:
Byte 1Byte 0Byte 2 Byte 3
xxx.xxx.xxx.xxx
192.168.003.177Example:
Fig. TCP / IP address,
byte 2, value 003
Fig. TCP / IP address,
byte 3, value 177
39
UMG 96RM-EL
Manual setting of the subnet mask (SUb)
• When in the programming mode, press button 2 to get
to the subnet mask settings (SUb display).
• Use button 1 to select the desired digit and set
it by pressing button 2. Repeat this step for each digit
in bytes 0 to 3 in a way similar to setting the TCP / IP
device address.
• After repeated display of byte 0 (no digit is flashing)
one can set the gateway address.
Manual setting of the gateway address (GAt)
• When in the programming mode, press button 2 to get
to the gateway address settings (GAt display).
• Press buttons 1 and 2 to set the desired gateway address in bytes 0 to 3 as described above.
The dynamic IP allocation must also be deactivated to
ensure that the manual settings of the TCP / IP device
address, subnet mask and gateway address are not
overwritten by a DHCP server. To do so set the parameter „dyn IP“ to a value of 0 or 3 (see „IP mode configuration“ table) as described under „Dynamic IP allocation“.
40
Dynamic IP allocation (dyn)
The dynamic allocation of the TCP / IP settings (device/
gateway address and subnet mask) provides for a fully
automated integration of the device into an existing network with a DHCP server. TCP / IP settings do not need
to be configured manually as they are automatically assigned by the DHCP server when the device is started.
Addresses are read out in the programming mode
the same way as in the manual settings.
• Switch to the programming mode as described.
The symbols for the programming mode PRG
and the current transformer mode CT appear
on the display.
• Press button 2 several times to display the dynamic IP
allocation (dYn IP).
• Activate the parameter with button 1 (1st digit flashes)
and then select the last digit (digit flashes) with button 1. Use button 2 to set the parameter to 2 or 5 in
accordance with the „IP mode configuration“ table).
• Confirm the parameter with button 1 and exit programming mode or wait for ca. 60 seconds.
C
Changes will only take effect after you exit
the programming mode.
Fig. Subnet mask (Sub),
byte 0, value 255
Fig. Gateway (GAt),
byte 0, value 192
Fig. Parameter setting for
dynamic allocation (DHCP)
of a TCP/IP address
Parameter setting for
allocation of a fixed TCP/IP
address
UMG 96RM-EL
Caution!
m
m
IP mode configuration table
0Fixed IP address
1BootP
2DHCP
3Fixed IP with ARP-Probe and Gratuitous-ARP
4BootP with ARP-Probe and Gratuitous-ARP
5DHCP with ARP-Probe and Gratuitous-ARP
Connection of the UMG96RM-EL to the
Ethernet may only be carried out after discussion with the network administrator!
Caution!
The UMG 96RM-EL is factory-programmed
for the dynamic allocation of the IP settings
(DHCP mode).
Settings can be changed as described
in TCP/IP Configuration or, for example,
via an appropriate Ethernet connection
by means of GridVis software.
If the key symbol is displayed, the dynamic IP allocation is enabled.
Device / gateway address and subnet
mask are provided and automatically accepted by the DHCP server.
41
UMG 96RM-EL
Parameters
User password (addr. 050)
A user password can be programmed in order to impede
any accidental change to programming data. A switch
to the next programming menu can only be made after
entering the correct user password.
No user password is specified in the factory. In this
case, the password menu is skipped and the current
transformer menu is reached directly.
If a user password was programmed, the password
menu will appear with the display “000”.
The first digit of the user password flashes and can
be changed with button 2. The next digit is selected
by pressing button 1 and will begin flashing.
The programming menu for the current transformer can
only be accessed after entering the correct number
combination.
42
Forgotten password
If you have forgotten the password, the password can
only be cleared by using the GridVis PC software.
To do this, connect the UMG 96RM-EL to the PC via
a suitable interface. More information can be found
in the help section of GridVis.
UMG 96RM-EL
Mean value
Mean values are averaged over an adjustable period for the current, voltage and power measured values. The mean values are indicated by a bar over the
measured value.
The averaging time can be selected from a list with 9
fixed averaging times.
Averaging time, current (Addr. 040)
Averaging time, power (Addr. 041)
Averaging time, voltage (Addr. 042)
The applied exponential messaging method reaches at
least 95% of the measurement value once the reporting
time has run its course.
43
UMG 96RM-EL
Min. and max. values
All measured values are measured and calculated during all 10/12 periods. Minimum and maximum values are
determined for most measured values.
The min. value is the smallest measured value determined since the last deletion. The max. value is the highest measured value determined since the last deletion.
All minimum and maximum values are compared with
the corresponding measured values and overwritten
when exceeded or fallen short of.
The minimum and maximum values are saved every
5 minutes in an EEPROM without date and time. Thus,
the minimum and maximum values of the past 5 minutes
may be lost due to an operating voltage failure.
Delete min. and max. values (Addr.506)
If "001" is set for address 506, all minimum and maximum values can be deleted simultaneously.
One exception is the maximum value of the mean current. Press and hold button 2 to delete the maximum
value of the mean current in the display menu.
44
Energy meter
The UMG 96RM-EL has power meters for active energy,
reactive energy and apparent energy.
Active energy reading
Total active energy
The active energy given in this example
is 12 345 678 kWh
The active energy given in this example
is 134 178 kWh
Mains frequency (Addr. 034)
UMG 96RM-EL
For automatic ascertainment of the mains frequency, an
L1-N voltage larger than 10Veff must be applied to the
voltage measurement input V1.
The sampling frequency is computed for the current
and voltage inputs based on the mains frequency.
If the test voltage is missing, neither the network nor
the sampling frequency can be computed. An acknowledgeable error message "500" will be displayed.
Voltage, current and all resulting values are calculated
and displayed based on the most recent frequency measurement and/or possible power couplings.
The measured values that have been determined can
no longer guarantee the declared precision.
When another measurement of frequency can be carried out, the error message will automatically disappear
in about 5 seconds after the voltage returns.
The error is not displayed when a fixed frequency is set.
Setting range: 0, 45 .. 65
0 = automatic frequency determination.
The mains frequency is determined based
on the measurement voltage.
45..65 = fixed frequency
The mains frequency is pre-selected as a fixed value.
45
UMG 96RM-EL
TH
fund
TH
fund
Harmonics
Harmonics are the integer multiple of a mains frequency.
The voltage mains frequency for the UMG 96RMEL must be in the range between 45 and 65 Hz. The
calculated voltage and current harmonics refer to this
mains frequency.
Harmonics up to 40x the mains frequency are recorded.
The harmonics for currents are given in amperes
and the harmonics for voltages are given in volts.
Number of the harmonic
Phase L3
Current harmonic
Value
Fig. Display of the 15th harmonic of the current
in the L3 phase (example).
Harmonics are not displayed in the factory
default setting.
C
46
Total Harmonic Distortion (THD)
THD is the ratio of the root mean square value of
harmonics to the root mean square value of the mains
frequency.
Total Harmonic Distortion of the current (THDI):
M
1
D
=
I
∑
I
n
2
I
.
nHarm
2
=
Total Harmonic Distortion of the voltage (THDU):
M
1
D
=
U
∑
U
n
=
2
U
.
nHarm
2
Phase L3
Voltage
Value
Fig. Display of the total harmonic distortion
of the voltage from the L3 phase (example).
UMG 96RM-EL
Measured value relay
All measured values are calculated every nine periods
and can be recalled once per second on the measured
value displays. Two methods are available for retrieving
the measured value displays:
• The automatically changing display of selected
measured values, referred to here as measured value
relaying.
• Selection of a measured value display using buttons
1 and 2 from a preselected display profile.
Both methods are simultaneously available. Measured
value relaying is active if at least one measured value
display is programmed with a changeover time greater
than 0 seconds.
If a button is pressed, the measured value displays
of the selected display profile can be browsed. If no
button is pressed for about 60 seconds, the device
switches to the measured value relay and the measured
values from the selected display change profile
of the programmed measured value displays are shown
one after the other.
Changeover time (addr. 039)
Adjustment range: 0 .. 60 seconds
If 0 seconds are set, no changeover takes place between
the measured value displays selected for the measured
value relay.
The changeover time applies for all display change
profiles.
After return of the power supply, the UMG 96RM-EL
shows the first measured value panel from the current
display profile. In order to keep the selection of measured values to be displayed arranged in a clear manner,
only one part of the available measured values is preprogrammed for recall in the measured value display by
default. A different display profile can be selected if other
measured values are required to be shown on the UMG
96RM-EL display.
profile and display profile) can only be programmed using the GridVis software.
Profile setting
Both profiles (display rotation profile and display profile) are illustrated in the GridVis software included in the delivery package. The
profiles can be adjusted using the Device
Configuration function of the software; customizable display profiles are programmed
individually.
A connection between the UMG 96RM-EL
and the PC via an interface is required for
the use of the GridVis software
Fig. Profile setting in the GridVis software.
48
UMG 96RM-EL
Reset energy meter (Addr. 507)
The real, apparent and reactive energy meters can only
be reset simultaneously.
Set "001" for address 507 to reset the energy meter.
If you reset the energy meter, the data will
C
be lost.
To avoid data loss, you should read
and save the measured values before deletion using the GridVis software.
Phase sequence
The voltage phase sequence and the phase L1 frequency are displayed on the screen.
The phase sequence shows the three-phase system sequence. The rotary field usually rotates to the "right".
The voltage measurement input phase sequence is checked and displayed in the UMG 96RM-EL. If the string
moves in a clockwise direction, this means that the rotary field rotates to the "right"; if the string moves in a
counter-clockwise direction, this means that the rotary
field rotates to the "left".
The field rotation can only be determined when
the measurement and operating voltage inputs are fully
connected. If a phase is missing or two equal phases are
connected, then the phase sequence is not determined
and the string is not moving.
Fig. Indication of the supply frequency (50.0)
and the phase sequence.
Fig. Rotary field direction
can not be determined.
49
UMG 96RM-EL
LCD contrast (Addr. 035)
The preferred view for the LCD display is from "below".
The LCD display contrast can be adapted by the user.
The contrast can be set stepwise in the range from
0 to 9.
0 = very bright
9 = very dark
Factory default setting: 5
Backlight
The LCD backlight allows the display to be read easily
even in poor light. The brightness can be controlled by
the user in stages from 0 to 9.
The UMG 96RM has two different types of backlight:
- the operation backlight
- the standby backlight
50
Operation backlight (addr. 036)
The operation backlight is activated by pushing the appropriate button, or with a restart.
Standby backlight (addr. 747)
This backlight is activated after an adjustable period of
time (addr. 746). If no button is pressed within this period, then the device switches to the standby backlight.
If buttons 1 - 3 are pressed, the device switches to
the operation backlight and the defined period of time
begins again.
If the brightness settings for the two backlights are set to
the same value, then no change is discernible between
the operation and standby backlights.
Addr. DescriptionSetting
036 Brightness for
operation backlight
746 Period of time after
which the backlight will
switch to standby
747 Brightness for
standby backlight
0 = min. brightness, 9 = max. brightness
range
0 .. 96
60 .. 9999
Sek.
0 .. 90
Default
setting
900
Sek.
UMG 96RM-EL
Time recording
The UMG 96RM-EL records the operating hours
and the overall runtime of each comparator,
• where the operating period is measured and displayed
in hours with a resolution of 0.1 h
• and the overall runtime of the comparators is displayed in seconds (when reaching 999999s is displayed
in hours).
The periods are marked by the digits 1 to 6 for
the measured value display enquiry:
In the measured value display, a maximum of 99999.9 h
(= 11.4 years) can be displayed.
Operating hours meter
The operating hours meter measures the UMG 96RM-EL
recording and displaying time.
The operating period is measured and displayed in hours
with a resolution of 0.1 h. The operating hours meter
cannot be reset.
Overall runtime of comparators
The overall runtime of a comparator is the sum of the runtimes exceeding the comparator result limit value.
The total running time of the comparators can only
be reset by the GridVis software. All running times are
reset simultaneously.
Fig. Measured value indications
Operating hours meter
The UMG 96RM-EL operating
hours meter reading is 140.8h.
This corresponds to 140 hours
and 80 industrial minutes. 100
industrial minutes = 60 minutes.
In this example, 80 industrial
minutes = 48 minutes.
51
UMG 96RM-EL
Serial number (Addr. 754)
The serial number displayed by the UMG 96RM-EL consists of 6 digits and is a part of the serial number given
on the rating plate.
The serial number cannot be changed.
Serial number
The serial number
is on the rating plate:
XX00-0000
Software release (Addr. 750)
The UMG 96RM-EL software is continuously improved
and extended. The software status in the device is identified with a 3 digit number, the software release. The
software release cannot be changed by the user.
52
UMG 96RM-EL
Commissioning
Applying the supply voltage
• The level of supply voltage for the UMG 96RM-EL can
be found on the nameplate.
• After applying the supply voltage, the UMG 96RM-EL
switches to the first measured value display.
• If no display appears, the supply voltage must
be checked to determine whether it is in the rated
voltage range.
Applying the measured voltage
• Voltage measurements in networks with rated voltages
above 300V AC to ground must be connected to a
voltage transformer.
• After the measured voltages are connected, the
measured values for the L-N and L-L voltages
displayed by the UMG 96RM-EL must match those at
the voltage measurement input.
Attention!
m
Voltages and currents outside the permissible metering range can result in personal
injury and damage to the device.
Applying the measured current
The UMG 96RM-EL is designed for connecting ../1 A
and ../5 A current transformers.
Only AC currents and not DC currents can be measured
via the current measurement inputs.
Short circuit all current transformer outputs except
for one. Compare the currents displayed on the UMG
96RM-EL with the applied current.
The current displayed by the UMG 96RM-EL must match
the input current, taking the current transformer ratio into
consideration.
In the short circuit current measurement inputs, the UMG
96RM-EL must show approx. zero amperes.
The factory-set current transformer ratio is 5/5 A and may
need to be adapted to the current transformer used.
Attention!
m
m
Supply voltages that do not correspond
to the nameplate information can lead
to device malfunction or destruction.
Attention!
The UMG 96RM-EL is not suitable for the
measurement of DC voltages.
53
UMG 96RM-EL
Rotation field direction
Check the direction of the voltage rotation field on the
measured value display of the UMG 96RM-EL.
Usually there is a "clockwise" spinning rotation field.
Checking the phase assignment
The assignment of the phase conductor to the current
transformer is correct if a current transformer is short
circuited at the secondary terminals and the current
shown by the UMG 96RM-EL in the corresponding
phase sinks to 0A.
Checking the power measurement
Short circuit all current transformer outputs except for
one and check the displayed power.
The UMG 96RM-EL must only show one rating in the
phase with the non-short-circuited current transformer
input. If this does not apply, check the measured voltage
connection and the measured current connection.
If the magnitude of the real power is correct but the sign
of the real power is negative, this can be due to two
causes:
• The connections S1 (k) and S2 (I) on the current
transformer are inverted.
• Active energy is being returned to the network.
54
Checking the measurement
If all voltage and current measurement inputs are
correctly connected, the individual and sum power
ratings are accurately calculated and displayed.
Checking the individual power ratings
If the current transformer is assigned to the wrong
phase conductor, the associated power rating will be
incorrectly measured and displayed.
The assignment of the phase conductor to the current
transformer on the UMG 96RM-EL is correct if there
is no voltage between the phase conductor and the
associated current transformer (primary).
In order to ensure that a phase conductor on the voltage
measurement input is assigned to the correct current
transformer, the respective current transformer can be
short-circuited at the secondary terminals. The apparent
power shown by the UMG 96RM-EL must then be zero
in this phase.
If the apparent power is correctly displayed but the real
power is shown with a "-" sign, the current transformer
terminals are inverted or power is being fed to the power
company.
UMG 96RM-EL
Check the sum power ratings
If all voltages, currents and power ratings for the
respective phase conductor are correctly displayed,
the sum power ratings measured by the UMG 96RMEL must also be correct. For confirmation, the sum
power ratings measured by the UMG 96RM-EL should
be compared with the energy of the active and reactive
power meters at the power feed.
Comparators and monitoring threshold values
Two comparator groups (1-2) and 3 comparators per
group (A – C) can be selected in order to monitor/control
the thresholds. The results of the comparators A to C
can be linked with AND or OR operators
Comparator group 1
Comparator A
Comparator B
Comparator C
Logic
Result
Addr. 616
UMG 96RM
0/1
Block diagram: Use of Comparator group 1
55
UMG 96RM-EL
Example: Current monitoring in the neutral line
If the current in the neutral line is greater than 100 A for
60 seconds, the result of the comparator group 1 should
be latched for at least 2 minutes.
The following must be programmed:
1. Comparator group 1
Select comparator group 1 for the limit value
monitoring. Since only one limit value is monitored,
select comparator A and program it as follows:
The address of the measured value to be monitored
by comparator A:
Address 110 = 866
(address of the current in the neutral line)
The measured values for the B and C comparators
are set to 0.
Address 116 = 0 (the comparator is inactive)
Address 122 = 0 (the comparator is inactive)
The limit value to be observed.
Address 108 = 100 (100 A)
56
For a minimum exposure time of 2 minutes, the result
of the comparator group 1 should be latched if the
limit value is exceeded.
Address 111 = 120 seconds
For the lead time of 60 seconds, any exceeding
should be minimised.
Address 112 = 60 seconds
The operator for comparison between the measured
value and the limit value.
Address 113 = 0 (corresponds >=)
2. Linking comparators
The B and C comparators have not been set and are
equal to zero.
The result of comparator A is issued as a comparator
result through the OR link of comparators A, B and C.
Address 107 = 0 (OR link)
Result
The result of the comparator group 1 is latched for at
least 2 minutes if the current in the neutral line is greater
than 100 A for more than 60 seconds.
Comparator group 1
UMG 96RM-EL
Comparator A
Measured value (addr. 110)
Limit value (addr. 108)
Minimum turn-on time (addr. 111)
Lead time (addr. 112)
Operator “>=”, “<” (addr. 113)
Comparator result (addr. 610)Comparator result (addr. 611)Comparator result (addr. 612)
Total running time
(addr. 5898)
Link the results from comparators A, B and C as AND or OR (addr. 107).
Measured value (addr. 116)
Limit value (addr. 114)
Minimum turn-on time (addr. 117)
Lead time (addr. 118)
Operator “>=”, “<” (addr. 119)
Link the results from comparators A, B and C
Comparator B
Total running time
(addr. 5900)
Linkage result (addr. 616)
Comparator C
Measured value (addr. 122)
Limit value (addr. 120)
Minimum turn-on time (addr. 123)
Lead time (addr. 124)
Operator “>=”, “<” (addr. 125)
Total running time
(addr. 5902)
57
UMG 96RM-EL
• Measured value (addr. 110,116,122,129,135,141)
The address of the measured value to be monitored
is in the measured value.
If measured value = 0, the comparator is inactive.
• Limit value (addr. 108,114,120,127,133,139)
Write the value in the limit that is to be compared with
the measured value.
• Minimum turn-on time
(addr. 111,117,123,130,136,142)
The linkage result (e.g. address 610) is maintained
for the duration of the minimum turn-on time.
Adjustment range: 1 to 32,000 seconds
• Lead time (addr. 112,118,124,131,137,143)
If a limit value violation is present for at least the
duration of the lead time, the comparator result is
changed.
Times in the range from 1 to 32,000 seconds can
be assigned to the lead time.
• Operator (addr. 113,119,125,132,138,144)
Two operators are available for comparing the
measured value and the limit value.
Operator = corresponds to 0 greater than or equal
to (>=)
Operator = corresponds to 1 less than (<)
58
• Comparator result (addr. 610,611,612,613,614,615)
The result from the comparison between the measured
value and the limit value is in the comparator result.
Therefore:
0 = there is no limit value violation.
1 = there is a limit value violation.
• Total running time
The sum of all times for which there was a limit value
violation in the comparator result.
• Linkage (addr. 107, 126)
Link the results from comparators A, B and C as AND
or OR.
• Total linkage result (addr. 616,617)
The linked comparator results from comparators A, B
and C are in the total linkage result.
Comparator in the GridVis software
UMG 96RM-EL
Limit value
Exceedance
Lead time
Minimum
turn-on time
Comparator result
Measured value
2 seconds
2 seconds
Fig.: Limit value exceeding
Configuration (adjustment) of the individual comparators
can also performed via GridVis in the menu of the device
configuration.
Fig.: Software GridVis, configuration menu
59
UMG 96RM-EL
Service and maintenance
The device is subjected to several different safety tests
before leaving the factory and is labelled with a seal. If a
device is opened then the safety checks must be repeated. Warranty claims will only be accepted if the device
is unopened.
Repair and calibration
Repair work and calibration can be carried out by the manufacturer only.
Front film
The front film can be cleaned with a soft cloth and standard household cleaning agent. Do not use acids and
products containing acid for cleaning.
Disposal
The UMG 96RM-EL can be reused or recycled as electronic scrap in accordance with the legal provisions.
The permanently installed lithium battery must be disposed of separately.
60
Service
Should questions arise, which are not described
in this manual, please contact the manufacturer directly.
We will need the following information from you to answer any questions:
- Device name (see rating plate),
- Serial number (see rating plate),
- Software release (see measured value display),
- Measuring-circuit voltage and power supply voltage,
- Precise description of the error.
Device calibration
The devices are calibrated by the manufacturer
at the factory - it is not necessary to recalibrate the device providing that the environmental conditions are
complied with.
Calibration intervals
It is recommended to have a new calibration carried out
by the manufacturer or an accredited laboratory every
5 years approximately.
Firmware update
If the device is connected to a computer via Ethernet,
then the device firmware can be updated via the GridVis
software.
Select a suitable update file (menu Extras / Update de-vice) and the device and the new firmware will be transferred.
Fig. GridVis firmware update assistant
UMG 96RM-EL
61
UMG 96RM-EL
Error messages
The UMG 96RM-EL shows three different error messages
on the display:
- warnings,
- serious error and
- metering range exceedances.
If there are warnings and serious errors, the error
message is indicated by the symbol "EEE" followed by
an error number.
The three-digit error number is composed of the error
description and (if detectable by the UMG 96RM-EL)
one or more error causes.
Symbol for an error
message
Error number
Fig. Error message
62
Symbol for an error
message
Error cause
Description of the error
Example of error message 911:
The error number is composed of serious error 910
and internal error cause 0x01.
In this example, an error occurred when reading the calibration from
the EEPROM. The device
must be sent to the manufacturer for inspection.
UMG 96RM-EL
Warnings
Warnings are minor errors that can be acknowledged by buttons 1 or
2. The measured values
continue to be retrieved
and displayed. This error
is displayed after each
voltage return.
ErrorsError description
EEE
500
The mains frequency could not be determined.
Possible causes:
The voltage at L1 is too small.
The mains frequency does not range
between 45 and 65Hz.
Remedy:
Check the mains frequency.
Select fixed frequency on the device.
Fig. Warning message with number 500
(mains frequency)
ErrorsError description
EEE
810
Major errors
When a major error occurs, the device must be sent
to the manufacturer's service center for inspection
and adjustment.
ErrorsError description
EEE
910
Internal causes:
The UMG 96RM-EL sometimes determines the cause
of a major internal error with the following error code.
ErrorsError description
0x01EEPROM does not respond.
0x02Address overrange.
0x04Checksum error.
0x08Error in the internal I2C bus.
A failure has been detected in the configuration.
The configuration will be reset and restored
to default values (factory setting) when that
failure was displayed.
Device has to be re-configured where
required.
Error while reading the calibration.
63
UMG 96RM-EL
Metering range exceedance
Metering range exceedances are displayed for as long
as they are present and cannot be acknowledged.
A metering range is exceeded if at least one of the three
voltage or current measuring inputs is outside of its
specified metering range.
The phase in which the metering range exceedance
occurred is indicated with the "up" arrow. The "V"
and "A" symbols show whether the metering range
exceedance occurred in the current or voltage circuit.
A = current circuit
V = voltage circuit
Display of the phase (L1/L2/
L3) with the metering range
exceedance.
Limit values for metering range exceedance:
I = 7 Aeff
UL-N= 520 VL-N
64
Examples
A = current circuit
Fig.: Display of the metering range exceedance
in the current circuit of the 2nd phase (I2).
V = voltage circuit
Fig.: Display of the metering range exceedance
in the voltage circuit L3.
Parameters of the metering range exceedance
A continuative error description is stored encoded
in the parameters of the metering range exceedance
(addr. 600) in the following format:
UMG 96RM-EL
FFFFFFFF
Phase 1:
Phase 2:
Phase 3:
Example: Error in phase 2 in the current circuit:
0xF2FFFFFF
Example: Error in phase 3 in the voltage circuit UL-N:
0xFFF4FFFF
0x
1
1
2
2
4
4
Current:
U L-N
65
UMG 96RM-EL
Procedure in the event of faults
Possible faultCauseRemedy
No displayExternal fusing for the power supply voltage has
No current displayMeasurement voltage is not connected.
Current displayed is too large or too
small.
Voltage displayed is too large or too
small.
Voltage displayed is too small.Overrange.Install voltage transformers.
Phase shift ind/cap.A current path is assigned to the wrong voltage
Effective power, consumption/supply
reversed.
tripped.
Measurement current is not connected.Connect measuring-circuit current.
Current measurement in the wrong phase.Check connection and correct if necessary.
Current transformer factor is incorrectly programmed.
The current peak value at the measurement input
was exceeded by harmonic components.
The current at the measurement input fell
short of.
Measurement in the wrong phase.Check connection and correct if necessary.
Voltage transformer incorrectly programmed.Read out and program the voltage transformer
The peak voltage value at the measurement input
has been exceeded by harmonic components.
path.
At least one current transformer connection
is mixed up/reversed.
A current path is assigned to the wrong voltage
path.
Replace fuse.
Connect the measuring-circuit voltage.
Read out and program the current transformer
transformation ratio at the current transformer.
Install current transformer with a larger transformation ratio.
Install current transformer with a suitable transformation ratio.
transformation ratio at the voltage transformer.
Caution! Ensure the measurement inputs are not
overloaded.
Check connection and correct if necessary.
Check connection and correct if necessary.
Check connection and correct if necessary.
66
Possible faultCauseRemedy
Effective power too large or too
small.
"EEE" in the displaySee error messages.
No connection with the device.- IP address is incorrect.
Device still does not work
despite the above measures.
The programmed current transformer transformation ratio is incorrect.
The current path is assigned to the wrong
voltage path.
The programmed voltage transformer transformation ratio is incorrect.
- Incorrect addressing mode
- Network cable is defective
Device defective.Send the device to the manufacturer for inspec-
Read out and program the current transformer
transformation ratio at the current transformer
Check connection and correct if necessary.
Read out and program the voltage transformer
transformation ratio at the voltage transformer.
- Adjust IP address at the device.
- Adjust the IP address assignment mode
- Replace network cable
tion and testing along with an accurate fault
description.
UMG 96RM-EL
67
UMG 96RM-EL
Technical data
General information
Net weight (with attached connectors)ca. 300g
Packaging weight (including accessories)ca. 600g
Service life of background lighting40000h (after this period of time the background lighting effici-
Transport and storage
The following information applies to devices which are transported or stored in the original packaging.
Free fall1m
TemperatureK55 (-25°C bis +70°C)
Relative humidity 0 to 90 % RH
Ambient conditions during operation
The UMG 96RM-EL is intended for use in weather-protected, fixed locations.
Protection class II according to IEC 60563 (VDE 0106, part 1).
Rated temperature rangeK55 (-10°C .. +55°C)
Relative humidity0 bis 75 % RH
Operational altitude0 .. 2000m über NN
Degree of pollution2
Installation positionvertical
VentilationForced ventilation is not required.
Foreign body and water protection
- Front
- Back
- Front with seal
ency will reduce by approx. 50 %)
IP40 according to EN60529
IP20 according to EN60529
IP42 according to EN60529
68
Supply voltage
Installation overvoltage category300V CAT II
Protection of the power supply (fuse)6 A, type C (approved by UL/IEC)
Nominal range20V - 250V (45..65Hz) oder DC 20V - 300V
Working area+-10% from the nominal range
Power consumptionmax. 5.5VA / 2W
Connection capacity of the terminals (power supply)
Connectable conductor. Only one conductor may be connected per contact point!
Three-phase, 4-wire systems with nominal voltages up to277V/480V (+-10%)
Three-phase, 3-wire systems, unearthed,
with nominal voltages up to
Overvoltage category300V CAT III
Rated surge voltage4kV
Metering range L-N 01) .. 300 Vrms
Metering range L-L 01) .. 520Vrms
Resolution0.01V
Crest factor2.45 (relative to the metering range)
Impedance4MOhm/phase
Power consumptionapprox. 0.1 VA
Sampling rate21.33kHz (50Hz), 25.6 kHz (60Hz) per measuring channel
IT 480V (+-10%)
(max. overvoltage 520 Vrms )
(max. overvoltage 900Vrms )
Mains frequency
- Resolution
1)
The UMG 96RM-EL can only determine values, if a voltage L-N greater than 10Veff or a voltage L-L of greater than 18Veff is present at least one voltage
Voltage harmonicsUhClass 1 (IEC61000-4-7)up to 2.5 kHz0 V .. 999 kV
THD of the voltage
THD of the voltage
3)
4)
IN---
INc1.0 (IEC61557-12)0.03 .. 25 A0.03 A .. 999 kA
Unba---
Unb---
THDu1.0 (IEC61557-12)up to 2.5 kHz0 % .. 999 %
THD-Ru---
72
UMG 96RM-EL
FunctionSymbolAccuracy classMetering rangeDisplay range
Current harmonicsIhClass 1 (IEC61000-4-7)up to 2.5 kHz0 A .. 999 kA
THD of the current
THD of the current
Mains signal voltageMSV---
1) Referred to amplitude.
2) Referred to phase and amplitude.
3)
4)
THDi1.0 (IEC61557-12)up to 2.5 kHz0 % .. 999 %
THD-Ri---
* The display returns to 0 W when the maximum total energy values are reached.
3) Referred to mains frequency.
4) Referred to root mean square value.
5) Accuracy class 0.5 with ../5 A transformer.
Accuracy class 1 with ../1 A transformer.
73
UMG 96RM-EL
Parameter and Modbus address list
The following excerpt from the parameter list contains
settings that are necessary for proper operation of
the UMG 96RM-EL, such as current transformers and
device addresses. The values in the parameter list can
be written and read.
C
A complete overview of the parameters and
measured values as well as explanations
regarding the selected measured values
is filed in the document “Modbus Address
List” on the CD or Internet.
In the excerpt, the measured value list files the measured
and calculated measured values, output status data
and recorded values so that they can be read.
Table 1 - Parameter list
Address Format RD/WR Unit Note Adjustment Range Default
10 FLOAT RD/WR A Current transformer I1, primary 0..1000000
12 FLOAT RD/WR A Current transformer I1, sec. 1..5 5
14 FLOAT RD/WR V Voltage transformer V1, primary 0..1000000
16 FLOAT RD/WR V Voltage transformer V1, sec. 100, 400 400
18 FLOAT RD/WR A Current transformer I2, primary 0..1000000
20 FLOAT RD/WR A Current transformer I2, sec. 1..5 5
22 FLOAT RD/WR V Voltage transformer V2, primary 0..1000000 400
24 FLOAT RD/WR V Voltage transformer V2, sec. 100, 400 400
26 FLOAT RD/WR A Current transformer I3, primary 0..1000000 5
28 FLOAT RD/WR A Current transformer I3, sec. 1..5 5
30 FLOAT RD/WR V Voltage transformer V3, primary 0..1000000 400
32 FLOAT RD/WR V Voltage transformer V3, sec. 100, 400 400
74
(*1)
The values 0 and 248 to 255 are reserved and must not be used.
(*2)
The adjustable value 0 does not produce any sensible energy values and must not be used.
(*2)
5
(*2)
400
(*2)
5
UMG 96RM-EL
Address Format RD/WR Unit Note Adjustment Range Default
0..2=default display
change profiles
3=freely selectable
display change profile
39 SHORT RD/WR s Changeover time 0 .. 60 0
40 SHORT RD/WR - Averaging time, I 0 .. 8* 6
41 SHORT RD/WR - Averaging time, P 0 .. 8* 6
42 SHORT RD/WR - Averaging time, U 0 .. 8* 6
45 USHORT RD/WR mA Response threshold of 0 .. 50 5
I1 .. I3
50 SHORT RD/WR - Password 0 .. 999 0 (no password)
107 SHORT RD/WR - Result from comparator group 1; 0,1 0
Link A, B, C
(1=and, 0=or)
Address Format RD/WR Unit Note Adjustment Range Default
108 FLOAT RD/WR - Comparator 1A, Limit value -1012-1..+1012-1 0
110 SHORT RD/WR - Comparator 1A,
Address of the measured value 0..32000 0
111 SHORT RD/WR s Comparator 1A,
Minimum turn-on time 0..32000 0
112 SHORT RD/WR s Comparator 1A, Lead time 0..32000 0
113 SHORT RD/WR - Comparator 1A, Operator 0,1 0
“>=”=0, “<”=1
114 FLOAT RD/WR - Comparator 1B, Limit value -1012-1..+1012-1 0
116 SHORT RD/WR - Comparator 1B,
Address of the measured value 0..32000 0
117 SHORT RD/WR s Comparator 1B,
Minimum turn-on time 0..32000 0
118 SHORT RD/WR s Comparator 1B, Lead time 0..32000 0
119 SHORT RD/WR - Comparator 1B, Operator 0,1 0
“>=”=0 “<”=1
120 FLOAT RD/WR - Comparator 1C, Limit value -1012-1..+1012-1 0
122 SHORT RD/WR - Comparator 1C,
Address of the measured value 0..32000 0
123 SHORT RD/WR s Comparator 1C,
Minimum turn-on time 0..32000 0
124 SHORT RD/WR s Comparator 1C, Lead time 0..32000 0
125 SHORT RD/WR - Comparator 1C, Operator 0,1 0
“>=”=0 “<”=1
126 SHORT RD/WR - Result from comparator group 2; 0,1 0
Link A, B, C
(1=and, 0=or)
127 FLOAT RD/WR - Comparator 2A, Limit value -1012-1..+1012-1 0
129 SHORT RD/WR - Comparator 2A,
Address of the measured value 0..32000 0
76
UMG 96RM-EL
Address Format RD/WR Unit Note Adjustment Range Default
130 SHORT RD/WR s Comparator 2A,
Minimum turn-on time 0..32000 0
131 SHORT RD/WR s Comparator 2A, Lead time 0..32000 0
132 SHORT RD/WR - Comparator 2A, Operator 0,1 0
“>=”=0 “<”=1
133 FLOAT RD/WR - Comparator 2B, Limit value -1012-1..+1012-1 0
135 SHORT RD/WR - Comparator 2B,
Address of the measured value 0..32000 0
136 SHORT RD/WR s Comparator 2B,
Minimum turn-on time 0..32000 0
137 SHORT RD/WR s Comparator 2B, Lead time 0..32000 0
138 SHORT RD/WR - Comparator 2B, Operator 0,1 0
“>=”=0 “<”=1
139 FLOAT RD/WR - Comparator 2C, limit value -1012-1..+1012-1 0
141 SHORT RD/WR - Comparator 2C,
Address of the measured value 0..32000 0
142 SHORT RD/WR s Comparator 2C,
Minimum turn-on time 0..32000 0
143 SHORT RD/WR s Comparator 2C, lead time 0..32000 0
144 SHORT RD/WR - Comparator 2C, Operator 0,1 0
“>=” = 0 “<” = 1
500 SHORT RD/WR - Terminal assignment, I L1 -3..0..+3 +1
501 SHORT RD/WR - Terminal assignment, I L2 -3..0..+3 +2
502 SHORT RD/WR - Terminal assignment, I L3 -3..0..+3 +3
503 SHORT RD/WR - Terminal assignment, U L1 0..3 1
504 SHORT RD/WR - Terminal assignment, U L2 0..3 2
505 SHORT RD/WR - Terminal assignment, U L3 0..3 3
506 SHORT RD/WR - Clear min. and max. values 0..1 0
77
UMG 96RM-EL
Address Format RD/WR Unit Note Adjustment Range Default
507 SHORT RD/WR - Clear energy meter 0..1 0
508 SHORT RD/WR - Force write EEPROM. 0..1 0
Note: Energy values and minimum and maximum values are written to the EEPROM every 5 minutes.
509 SHORT RD/WR - Voltage connection diagram 0..7 0
510 SHORT RD/WR - Current connection diagram 0..8 0
511 SHORT RD/WR - Relative voltage for
THD and FFT 0, 1 0
The voltages for THD and FFT can be shown on the display as L-N or L-L values. 0=LN, 1=LL
600 UINT RD/WR - Metering range exceedance 0..0xFFFFFFFF
610 SHORT RD - Comparator result 1 Output A
611 SHORT RD - Comparator result 1 Output B
612 SHORT RD - Comparator result 1 Output C
613 SHORT RD - Comparator result 2 Output A
614 SHORT RD - Comparator result 2 Output B
615 SHORT RD - Comparator result 2 Output C
616 SHORT RD - Linkage result of comparator group 1
617 SHORT RD - Linkage result of comparator group 2
750 SHORT RD - Software Release
754 SERNR RD - Serial number
756 SERNR RD - Production number
746 SHORT RD/WR s Period of time after which the
backlight will switch to standby 60 .. 9999 900
747 SHORT RD/WR s Brightness of the standby backlight 0 .. 9 0
78
Number formats
UMG 96RM-EL
TypeSizeMinimumMaximum
short16 bit-2
ushort16 bit0216 -1
int32 bit-2
uint32 bit0232 -1
float32 bitIEEE 754IEEE 754
15
31
215 -1
231 -1
C
Notes on saving measurement values
and configuration data:
• The following measurement values are
saved at least every 5 minutes:
• Comparator timer
• S0 meter readings
• Minimum / maximum / mean values
• Energy values
• Configuration data is saved
immediately!
79
UMG 96RM-EL
Dimensional drawings
All dimensions in mm.
Rear viewBottom view
□ 91,5
97
80
UMG 96RM-EL
□
Side view
max. 6
96
□ 91,5
100
Cutout dimensions
+0,8
92
+0,8
92
42
81
UMG 96RM-EL
Measured value displays overview
Measured values
L1-N voltage
L2-N voltage
L3-N voltage
Measured values
L1-L2 voltage
L2-L3 voltage
L3-L1 voltage
Measured values
L1 current
L2 current
L3 current
Measured value
Current in N
Measured values
L1 effective power
L2 effective power
L3 effective power
Measured value
Effective power
Measured values
L1 apparent power
L2 apparent power
L3 apparent power
82
A01
A02
A03
A04
Sum
A05
A06
Sum
A07
B01
Mean values
L1-N voltage
L2-N voltage
L3-N voltage
B02
Mean values
L1-L2 voltage
L2-L3 voltage
L3-L1 voltage
B03
Mean values
L1 current
L2 current
L3 current
B04
Mean value
Sum
Current in N
B05
Mean value
L1 effective power
L2 effective power
L3 effective power
B06
Mean value
Sum
Effective power
B07
Mean values
L1 apparent power
L2 apparent power
L3 apparent power
C01
Max. values
L1-N voltage
L2-N voltage
L3-N voltage
C02
Max. values
L1-L2 voltage
L2-L3 voltage
L3-L1 voltage
C03
Max. values
L1 current
L2 current
L3 current
C04
Max. value
Max. value sum
Current in N
C05
Max. values
L1 effective power
L2 effective power
L3 effective power
C06
Max. value
Sum
Effective power
C07
Max. values
L1 apparent power
L2 apparent power
L3 apparent power
D01
Min. value
L1-N voltage
L2-N voltage
L3-N voltage
D02
Min. value
L1-L2 voltage
L2-L3 voltage
L3-L1 voltage
D03
Max. values (mean values)
L1 current
L2 current
L3 current
D04
Max. values
Mean value sum
Current in N
D06
Max. value
Sum
Effective power mean
value
UMG 96RM-EL
A08
Measured value
Sum
Apparent power
A09
Measured values
L1 reactive power
L2 reactive power
L3 reactive power
A10
Measured value
Reactive power sum
A11
Measured value
Total Harmonic Distortion
(THD)
U L1
A12
Measured value
Total Harmonic Distortion
(THD)
I L1
A13
Max. value
Total Harmonic Distortion
(THD)
U L1
A14
Max. value
Total Harmonic Distortion
(THD)
I L1
B08
Mean value
Sum
Apparent power
B09
Mean values
L1 reactive power
L2 reactive power
L3 reactive power
B10
Mean value
Reactive power sum
B11
Measured value
Total Harmonic Distortion
(THD)
U L2
B12
Measured value
Total Harmonic Distortion
(THD)
I L2
B13
Max. value
Total Harmonic Distortion
(THD)
U L2
B14
Max. value
Total Harmonic Distortion
(THD)
I L2
C08
Max. value
Sum
Apparent power
C09
Max. values (ind)
L1 reactive power
L2 reactive power
L3 reactive power
C10
Max. value (ind)
Reactive power sum
C11
Measured value
Total Harmonic Distortion
(THD)
U L3
C12
Measured value
Total Harmonic Distortion
(THD)
I L3
C13
Max. value
Total Harmonic Distortion
(THD)
U L3
C14
Max. value
Total Harmonic Distortion
(THD)
I L3
83
UMG 96RM-EL
A15
Measured value
L1 cos(phi)
L2 cos(phi)
L3 cos(phi)
A16
Measured value
Sum cos(phi)
A17
Measured value
Frequency L1
Rotary field indication
A18
Measured value
Total active energy
(without backstop)
A19
Measured value (ind)
Reactive power
A20
Operating hours
meter 1
A21
Measured value
1. Harmonics
U L1
B16
Mean value
Sum cos(phi)
B18
Measured value
Total active energy
(Consumption)
B19
Measured value
Sum
Reactive power
cap.
B20
Comparator 1A
Overall runtime
B21
Measured value
3. Harmon.
U L1
C18
Measured value
Total active energy
(Supply)
C19
Measured value
Sum
Reactive power
cap.
...
...
D18
Measured value
Sum
Apparent energy
G20
Comparator 2C
Overall runtime
H21
Measured value
15. Harmon.
U L1
Highlighted menus are not displayed with the factory presets.
84
UMG 96RM-EL
A22
Measured value
1. Harmonics
U L2
A23
Measured value
1. Harmonics
U L3
A24
Measured value
1. Harmonics
I L1
A25
Measured value
1. Harmonics
I L2
A26
Measured value
1. Harmonics
I L3
A27
Max. value
1. Harmonics
U L1
A28
Max. value
1. Harmonics
U L2
B22
Measured value
3. Harmon.
U L2
B23
Measured value
3. Harmon.
U L3
B24
Measured value
3. Harmon.
I L1
B25
Measured value
3. Harmon.
I L2
B26
Measured value
3. Harmon.
I L3
B27
Max. value
3. Harmonics
U L1
B28
Max. value
3. Harmonics
U L2
Measured value
...
...
...
...
...
...
...
Highlighted menus are not displayed with the factory presets.
15. Harmon.
Measured value
15. Harmon.
Measured value
15. Harmon.
Measured value
15. Harmon.
Measured value
15. Harmon.
15. Harmonics
15. Harmonics
H22
U L2
H23
U L3
H24
I L1
H25
I L2
H26
I L3
H27
Max. value
U L1
H28
Max. value
U L2
85
UMG 96RM-EL
A29
Max. value
1. Harmonics
U L3
A30
Max. value
1. Harmonics
I L1
A31
Max. value
1. Harmonics
I L2
A32
Max. value
1. Harmonics
I L3
Highlighted menus are not displayed with the factory presets.
Max. value
3. Harmonics
Max. value
3. Harmonics
Max. value
3. Harmonics
Max. value
3. Harmonics
Even and odd harmonics up to the 40th
C
order can be called up via the GridVis software and can be viewed in the software.
86
B32
B29
U L3
B30
I L1
B31
I L2
I L3
H29
Max. value
...
...
...
...
15. Harmonics
U L3
H30
Max. value
15. Harmonics
I L1
H31
Max. value
15. Harmonics
I L2
H32
Max. value
15. Harmonics
I L3
UMG 96RM-EL
87
UMG 96RM-EL
Declaration of conformity
The product fulfils the following EC Directives:
2004/108/EG Electromagnetic compatibility of electrical equipment.
2006/95/EG Electrical equipment for use within certain voltage limits.
Considered standards:
Noise immunity
IEC/EN 61326-1:2013 Class A: Industrial environment
IEC/EN 61000-4-2:2009 Electrostatic discharge
IEC/EN 61000-4-3:2011 Electromagnetic RF Field 80-1000MHz
IEC/EN 61000-4-3:2011, EMV-ILA V01-03 Electromagnetic RF Field 1000-2700MHz
IEC/EN 61000-4-4:2013, EMV-ILA V01-03 Burst
IEC/EN 61000-4-5:2007, EMV-ILA V01-03 Surge
IEC/EN 61000-4-6:2009, EMV-ILA V01-03 Conducted disturbances 0.15-80MHz
IEC/EN 61000-4-8:2010 Power frequency magnetic field
IEC/EN 61000-4-11:2005, EMV-ILA V01-03 Voltage dips, short interrupts, voltage variations and
frequency changes
Noise emission
IEC/EN 61326-1:2013 Class B: Residental environment
IEC/CISPR11/EN 55011:2011 Radio disturbance field strength 30-1000MHz
IEC/CISPR11/EN 55011:2011 Radio disturbance voltage 0.15-30MHz
EMV-ILA V01-03 Radio disturbance voltage 9-150kHz
EMV-ILA V01-03 Flicker
Equipment safety
IEC/EN 61010-1:2011 Safety requirements for electrical equipment for Measurement, control and laboratory use – Part 1: General requirements
IEC/EN 61010-2-030:2011 Particular requirements for testing and measuring circuits
88
UMG 96RM-EL
89
UMG 96RM-EL
UMG 96RM-EL
Versorgungs-
spannung
Ethernet
10/100Base-T
PC
Spannungsmessung
RJ45
Strommessung
V1
V2
V3
VN
3456
12
N/-L/+
S2
S1
S2S2S1
S1
L1
L2
L3
Verbraucher
230V/400V 50Hz
N
S2S1S2S1S2S1
Power supply
voltage
Measuring voltage
Current measurement
Consumer
Connection example
90
2)1)2) 2)
3)
3)3)
1)
UL / IEC approved overcurrent
protection system (6A type C)
2)
UL / IEC approved overcurrent
protection system (10A type C)
3)
Jumpers (external)
UMG 96RM-EL
Basic functions quick guide
Adjusting the current transformer
Switch to the programming mode:
• Press button 1 and 2 simultaneously for around 1 second to switch to the programming mode. The symbols for the programming mode PRG and the current
transformer mode CT appear on the display.
• Press button 1 to confirm the selection.
• The first digit of the input field for the primary current
is flashing.
Adjusting the primary current
• Press button 2 to change the flashing digit.
• Press button 1 to select the next digit to be changed. The selected digit to be changed is flashing.
If the entire number is flashing, press button 2 to move
the decimal point.
Adjusting the secondary current
• Only 1A or 5A can be set as secondary current.
• Press button 1 to select the secondary current.
• Press button 2 to change the flashing digit.
Exit programming mode
• Press button 1 and 2 simultaneously for around 1 second to switch to the display mode.
Adjusting current transformer,
primary current
Display
Programming mode
Adjusting current transformer, secondary current
Current transformer symbol
(in the programming mode
only)
View measured values
Switch to the display mode:
• If you are still in the programming mode (PRG and
CT icons displayed on the screen), press button 1
and 2 simultaneously for around 1 second to switch
to the display mode.
• A measured value display (e.g. voltage) appears
Button controls
• Press button 2 to change
the measured value display for current, voltage,
power, etc.
• Press button 1 to change
the mean values, max. values etc. associated with
the measured value.
91
UMG 96RM-EL
TCP/IP addressing quick guide
Manual TCP/IP settings
Switch to the programming mode:
• Press button 1 and 2 simultaneously for around 1 second to switch to the programming mode. The symbols for the programming mode PRG and the current
transformer mode CT appear on the display.
Adjust the TCP/IP address (Adr.)
• Press button 2 to select "Adr"
• Press button 1 to enable the first digit (byte 0)
of the address (digit is flashing). Press button 2 to set
the digit.
• Press button 1 to select the next digit (flashing) and set
the desired digit by pressing button 2.
• If byte is set to 0, the address can be set from 1 to 3
by pressing button 1. Then the display jumps back
to Byte 0 (no digit is flashing).
Subnet mask (SUb)
• Press button 2 to select the subnet mask and set it
in a manner similar to adjusting the address by pressing button 1 and 2.
Adjusting the gateway address (GAt)
• Use button 2 and 1 to set the gateway in a manner
similar to adjusting the address.
Deactivate dynamic IP allocation (cf. page 41)
• Set the parameter „dYn IP“ to the „Fixed IP address“
mode
Exit programming mode
92
Description
Byte identification
(e.g. byte 0) of the address
Address data, byte 0
Fig. TCP/IP address, byte 1
A TCP / IP address consists of 4
bytes with the following structure:
Byte 1Byte 0Byte 2 Byte 3
xxx.xxx.xxx.xxx
• Press button 1 and 2 simultaneously to exit the mode
or wait 60 seconds.
Activate/deactivate dynamic IP allocation (dyn)
Device/gateway address and subnet mask are assigned by a DHCP server and enable automatic integration
of the device into the existing mains.
• When in programming mode, press button 2 repeatedly to display the tab labelled „dYn IP“ and activate
the parameter with button 1.
• Select the parameter digit with button 1 and set the
value (e.g. 000=fixed IP address, 002 = Activated
DHCP mode) with button 2.
• Exit programming mode.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.