Vor dem Polstück 1
D-35633 Lahnau
Support Tel. (0 64 41) 9642-22
Fax (0 64 41) 9642-30
e-mail: info@janitza.de
Internet: http://www.janitza.de
Table of contents
The meaning of symbols3
Hints for the user3
Receipt control3
Contents of delivery3
Hints for maintenance4
Service4
Product description5
Intended use5
Functional description5
Installation6
Mounting place6
Measuring and operating voltage6
Current measurement7
Sum current measurement7
Connecting options8
Putting into service10
Installation10
Attach measuring and operating voltage 10
Connect measuring current11
Check phase assignment11
Check current direction11
Check measurement11
Check phase power11
Check sum power11
Elimination of errors12
Error messages13
Usage and indication14
Indication mode14
Programming mode14
Key functions15
Table, measured value indication16
Current transformer18
Voltage transformer19
Averaging times20
Measured value indication21
Measured value rotation time21
Measured value selection22
Delete minimum and maximum values 23
Delete energy23
Working hours counter24
LCD contrast24
Software Release25
User password25
Uncertainty of measurement26
Configuration data28
Declaration of conformity29
Safety guidelines29
Test voltage29
EMC requirements29
Change current transformer ratio32
Call up measured values32
All rights reserved. No part of this manual may
be reproduced or duplicated without the written
permission of the author. Any contraventions
are punishable and will be prosecuted with all
legal means.
No liability can be taken for the faultless condition of the manual or damage caused by the
use of it. As failures cannot be avoided completely, we shall be very grateful for any advice.
We are anxious to remove all failures as soon
as possible. The mentioned software and hardware descriptions are registered trademarks in
the most cases and are subject to the regulations by law. All registered trademarks are property of the corresponding companies and are
fully recognized by us.
Page 2
Issue Note
13.01.2004First Edition.
The meaning of symbols
Receipt control
The symbols, which are used in this manual,
have the following meaning:
Beware of dangerous electrical voltage.
Ꮨ
Hints for the user
This device may be inserted and used by qualified personnel only according to the safety
regulations. Please follow the legal and safety
regulations for the corresponding application
while using the device.
Qualified personnel are persons, who are familiar with installation, mounting, putting into service and operation of the product and have qualifications according to their occupation, for example:
- Education or instruction resp. the right to
switch on or off, ground or characterize current
circuits or devices according to the standards
of safety techniques.
- Education or instruction in care and use of
safety equipment according to the standard
safety techniques.
This symbol shall warn you about possible danger, which can occur during installation, putting into service and usage.
In order to ensure a perfect and safe use of the
device, a proper transport, expert storage, erection and mounting and careful usage and maintenance is required. In case that a safe operation can no longer be granted, the device has
to be put out of service and has to be protected
against unintentional putting into service.
A safe operation can no longer be assumed, if
the device
• shows visible damage,
• does not work in spite of intact net supply,
• has been exposed to disadvantageous conditions for a longer time (e.g. storage beyond allowed climate without adaption to the room climate, dew etc.) or transport use (e.g. falling
from great height, even without visible damage).
Please test the contents of delivery for completion, before starting the installation of the device.
Contents of delivery
1 pc. UMG96L,
2 pcs. fixing brackets,
1 pc. manual.
As an option, a seal with part no. 29.01.907 can
be delivered.
All delivered options and versions are listed on
the delivery papers.
Ꮨ
Attention!
If the device is not used according to this
manual, a safe use cannot be granted,
and the instrument might cause danger.
Attention!
If a UMG 96L is installed in panels of
metal, the panel must be earthed.
This manual also describes options,
which have not been delivered and do
not belong to the contents of delivery.
Page 3
Hints for maintenance
Before delivery the device is tested in various
safety checks and marked with a seal. If the
device is opened, these checks must be repeated.
For instruments, which are opened outside the
manufacturing works, no warranty is granted
whatsoever.
Repairing and calibration
Repairing and calibration work can be carried
out in the manufacturing works only.
Front foil
The cleaning of the front foil has to be effected
with a soft cloth using a common cleansing
agent. Acid or acidic agents are not allowed for
cleaning.
Service
If there are questions, which are not described
in this manual, please contact us directly.
For an efficient handling we need the following
information:
- Description of device (see type plate),
- Serial digit (see type plate),
- Software Release,
- Measuring and operating voltage and
- detailed description of error.
You can reach us:
Monday until Thursday
between07:00 and 15:00
and Friday
between07:00 and 12:00
Waste management
The UMG96L can be disposed and recycled as
electronical waste according to the legal regulations.
The UMG96L is suitable for fix mounting and
the measurement of voltage, current, power
etc. in low voltage switchgear. The measurement is designed for 3 phase systems with neutral conductor (TN and TT-mains).
The UMG96L is suitable for mounting in fix and
weather protected panels. Conducting panels
must be earthed.
Due to the high resistance against interference,
the UMG 96L is suitable for continous and unsupervised operation.
As the UMG96L receives its power from phase
L1 of the measuring voltage, at least phase L1
and the neutral conductor N must be connected.
The attached voltage must be within the range
of the measuring and operation voltage shown
on type plate.
Either ../5A or ../1A current transformers can be
connected to the current measuring inputs.
The connection of the measuring and operating
voltage is carried out on the back side of the
UMG96L via all-insulated spring power clamps.
Functional description
The electronical three phase measurement system determines and digitalizes the effective values of voltages and currents in 50/60 Hz networks.
The operating voltage for operation of UMG96L
is generated by the measuring voltage L1-N. A
random test measurement is carried out each
second at all current and voltage inputs. Measuring signal interruptions, which last longer than
one second are safely recognized.
For each random test one period is scanned.
From those sampled values the microprocessor
calculates the electric quantities. These measured values are indicated within the programmable display. The energy as well as the minimum and maximum values are stored every 15
minutes whereas the programmed data are
stored immedately is a none volatile memory
(EEPROM).
The scanning frequency for all measuring inputs is calculated from the net frequency of
phase 1. At a net frequency of 50Hz the scanning frequency is 2,5kHz and for 60Hz it is
3,0kHz.
The measuring and operating voltages must be
connected to the UMG 96L via a separation
(switch or power switch) and an overcurrent
protection fuse (2-10A) in the building installation. The separation (switch or power switch)
must be near the UMG 96L and easily accessible.
L1
L2
L3
N
PE
3M
3M
Voltage measurement
Generation of oper-
ating voltage
3M
UMG96L
Diagr. Generation of the operating voltage from
measurement voltage.
Page 5
Installation
Mounting place
The UMG96L is suitable for a fix insertion into
low and medium voltage switchgear. Any
mounting position is possible.
Measuring and operating voltage
The operating voltage of the UMG96L is generated by the measuring voltage. The measurement is designed for three phase systems with
neutral conductor (TN and TT mains). The
measuring and operating voltages must be connected to the UMG 96L via a separation (switch
or power switch) and an overcurrent protection
(2-10A) within the building installation.The connection of the measuring and operating
voltages is carried out at the back side of the
UMG 96L via shock protected spring clamps.
230V/400V Standard version
Phase L1 and the neutral conductor N must be
connected, and the attached voltage must be
within the range of the measuring and operating voltage.
- The connection wires for the operating voltage leading to the UMG96L must be suitable for
voltages up to 300V against ground.
- The measuring and operating voltage has to
be protected by a fuse, which must be in the
range of 2A to 10A.
- A switch or power switch for the operating voltage must be provided within the building installation.
- The switch has to be near the instrument and
easily accessible.
- The switch must be marked as separation for
this instrument.
120V/220V Special version
Phase L1 and the neutral conductor N must be
connected, and the attached voltage must be
within the range of the measuring and operating voltage.
60V/110V Special version
Phase L1 and the neutral conductor N must be
connected, and the attached voltage must be
within the range of the measuring and operating voltage.
Attention!
Ꮨ
The limits indicated in the technical data
may not be exceeded, not even while
checking and putting into service of the
UMG 96L.
Ꮨ
Attention!
Before the device is connected to voltage for the first time, it should be deposited the installation room for at least 2
hours, to create a temperature assimilation and avoid condensation and dew.
Page 6
Current measurement
The current measurement is carried out via ../
5A or ../1A current transformers. In case that
the current has to be measured by an Amperemeter in addition to the UMG96L, the Amperemeter has to be connected in series to the
UMG96L.
In mains with voltage up to 300VAC against
ground, currents up to 5A can be connected
and measured directly to the UMG 96L.
Verbraucher
Consumer
L l
K k
A
Einspeisung
Supply
Diagr. Connection example: UMG96L with
Amperemeter in series.
l
UMG96L
k
Sum current measurement
If the current measurement is carried out via
two current transformers, the total transformer
ratio must be set to the UMG96L.
Example: Sum current transformer
A current measurement is carried out via one
current transformer with a ratio of 1000/5A and
another one with a ratio of 200/5A. The sum
measurement is carried out with a sum transformer 5+5/5A.
The UMG96L has to be programmed as follows:
The inaccuracy of the current measuring input
is +- 1% of the measuring range (5A). Therefore, the inaccuracy of the current measurement is +-50mA.
Example: Inaccuracy
With a current transformer 200/5A, the measuring range is 200A. The inaccuracy is +-1% of
200A = +-2A.
Resolution
The maximum resolution of the current measuring inputs is 10mA. The indication changes in
0.01A steps.
Example: Resolution current transformer 200/
5A
With a current transformer ratio of 200/5A, a
resolution of 10mA*40 = 400mA is effected.
The display changes in 0.4A steps.
Small currents
The minimum working current is 20mA. At short
circuited or open current measurement input,
the UMG 96L can indicate a small current. This
current is within the range of the allowed measurement inaccuracy.
Ꮨ
Ꮨ
K k
Einspeisung 1
Supply 1
AK AL
K l
k l
UMG96L
BK Bl
K k
Einspeisung 1
Supply 1
Attention!
Current transformers may not be handled
in open condition of the secondary, as
the secondary clamps can lead live voltage.
Attention!
Prior to connecting or exchanging the
UMG 96L, the secondary clamps of the
external current transformers have to be
short circuited.
Attention!
The program allows current and voltage
transformer ratio setting only, if the maximum phase power can reach up to
50.0MW and the sum power can reach a
maximum value of 150.0MW.
Page 7
Connecting options
UMG96L
Voltage Measure-
ment
see type plate
12345678910
L1 L2 L3 N
L1
L2
L3
PEN
Diagr.: Connection example 1
Four wire measurement with three current
transformers
Current
measurement
0,02 .. 5A
1k 1l 2k 2l 3k 3l
kl
k
../5(1)A
../5(1)A
l
../5(1)A
k
l
Consumer
Verbraucher
UMG96L
Voltage Measure-
ment
see type plate
12345678910
L1 L2 L3 N
L1
L2
L3
PEN
Diagr: Connection example 2. Four wire measurement with two current transformers.
Current
measurement
0,02 .. 5A
1k 1l 2k 2l 3k 3l
kl
../5(1)A
../5(1)A
k
l
Consumer
Verbraucher
UMG96L
Voltage Measure-
ment
see type plate
12345678910
L1 L2 L3 N
uu
u
xx
x
X
XX
L1
L2
L3
PEN
UUU
Current
measurement
0,02 .. 5A
1k 1l 2k 2l 3k 3l
kl
k
../5(1)A
../5(1)A
l
../5(1)A
UMG96L
Voltage Measure-
ment
see type plate
12345678910
L1 L2 L3 N
uu
u
xx
x
X
XX
L1
L2
k
l
Verbraucher
Consumer
L3
PEN
UUU
Current
measurement
0,02 .. 5A
1k 1l 2k 2l 3k 3l
kl
../5(1)A
../5(1)A
k
l
Consumer
Verbraucher
Diagr.: Connection example 3
Measurement with three voltage transformers
and three current transformers.
Page 8
Diagr.: Connection example 4
Measurement with three voltage transformers
and two current transformers.
UMG96L
UMG96L
Voltage Measure-
ment
see type plate
12345678910
L1 L2 L3 N
uu
u
x
X
XX
L1
L2
L3
UUU
xx
Current
measurement
0,02 .. 5A
1k 1l 2k 2l 3k 3l
kl
../5(1)A
k
../5(1)A
../5(1)A
l
k
Consumer
Verbraucher
Diagr.: Connection example 5
Medium voltage measurement with three voltage transformers and three current transformers.
Voltage Measure-
ment
see type plate
12345678910
L1 L2 L3 N
uu
u
x
X
XX
L1
L2
L3
UUU
xx
Current
measurement
0,02 .. 5A
1k 1l 2k 2l 3k 3l
kl
../5(1)A
../5(1)A
kl
Consumer
Verbraucher
Diagr.: Connection example 6
Medium voltage measurement with three voltage transformers and two current transformers.
UMG96L
Voltage Measure-
ment
see type plate
12345678910
L1 L2 L3 N1k 1l 2k 2l 3k 3l
L1
L2
L3
N
PE
Current
measurement
0,02 .. 5A
kl
../5(1)A
k
../5(1)A
../5(1)A
UMG96L
Voltage Measure-
ment
see type plate
12345678910
L1 L2 L3 N
uu
u
x
xx
X
XX
l
k
l
Consumer
Verbraucher
L1
L2
L3
PE
UUU
Current
measurement
0,02 .. 5A
1k 1l 2k 2l 3k 3l
kl
k
../5(1)A
../5(1)A
l
../5(1)A
k
l
Consumer
Verbraucher
Diagr.: Connection example 7
Measurement in IT networks via three current
transformers.
Diagr.: Connection example 8
Measurement in IT networks with three volta-
ge transformers and three current transformers.
Page 9
Putting into service
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
The putting into service of the UMG 96L should
be carried out as follows:
Installation
The UMG96L is designed for mounting in low
voltage distributions, which contain overvoltage
in measurement category III. The UMG96L is
suitable for installation in fixed and weather
proof panels. Conducting panels must be
earthed. Any mounting position is possible. For
mounting on front panels or doors, the delivered
fixing brackets have to be used.
Panel max. 6
Fixing brack-
ets
90
42
Diagr. Side view
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
23
96
6
Attach measuring and operating voltage
The allowed measuring and operating voltage
of UMG 96L is indicated on the type plate.
Attention!
Ꮨ
Mesuring and operating voltage, which
do not correspond to the indication on
the type plate, can lead to malfunction
and damage of the instrument.
The connection wires for measuring voltage
leading to the UMG96L must be suitable for
voltages up to 300V against ground and 520V
phase to phase.
After connecting the stated measuring and operating voltage to the UMG 96L, all segments
of the display appear. After approx. two seconds, the UMG 96L switches to the first measured value indication.
In case that no indication appears, please
check, if the attached operating voltage is within
the rated voltage range.
S V J M A D E P
UMG96L
45-65Hz IP20
2,5VA
Made in Germany
4
N
Spannungsmessung
Voltage Measurement
1
2
3
L3
L1
L2
2-10A
Strommessung/Current Measurement
k l
L2L3L1
k l
k l
57 10896
Program current and voltage transformers
When the device leaves the manufacturer, a
current transformer of 5/5A is set.
The set voltage transformer ratio has to be
changed only, if a voltage transformer is connected.
When connecting voltage transformers, please
observe the allowed measuring and operating
voltage stated on type plate!
Page 10
Connect measuring current
The UMG96L is designed for the connection of
../1A and ../5A current transformers. With the
current inputs, only alternating current but no
direct current can be measured.
Attention!
Ꮨ
Current transformers may not be handled in open condition, as there might be
live voltage at the secondaries.
Check current direction
Short circuit two current transformers on the
secondary. The real power in the connected
phase has to be:
Positive (+) for consumption of real power and
negative (-) for supply of real power (power station service).
In case that no real power is indicated, the assignment of voltages and currents may be
wrong.
Please connect the current inputs one after the
other, and compare the indicated current of the
display with the actual current. Please note,
that the current transformer ratio is set to 5/5A
and has to be adapted to the existing current
transformers.
In case that the current transformer is short
circuited on the secondary, the indicated current at the corresponding conductor at UMG
96L has to decrease to a value, that corresponds to the secondary current plus tolerance.
The current indicated by UMG 96L, has to conform to the input current, under consideration
of the current transformer and tolerance.
S V J M A D E P
UMG96L
45-65Hz IP20
2,5VA
Made in Germany
4N3
Spannungsmessung
Voltage Measurement
1
2
L1
L2
L3
2-10A
Strommessung/Current Measurement
k l
57 10896
L2L3L1
k l
k l
Check measurement
Provided that all voltage and current inputs are
connected correctly, the phase and sum power
is calculated and displayed correctly.
Check phase power
In case that a current transformer is assigned
to the wrong outer conductor, the corresponding power is measured and indicated incorrectly.
The assignment of the outer conductor and current transformer is correct, if no voltage is
measured between the outer conductor and the
primary of the corresponding current transformer.
To ensure that the outer conductor at the voltage input is assigned to the right current transformer, please short circuit the secondary of the
corresponding current transformer. The apparent power of this phase at UMG 96L must be
indicated by zero.
If the apparent power is indicated correctly, but
the real power has a „-“ sign, the current transformer clamps are interchanged, or power is
supplied to the energy supplier.
Check phase assignment
The assignment of the outer conductors to the
current transformer is correct, if a current transformer is short circuited on the secondary, and
the indicated current in the corresponding
phase decreases to a value at the UMG96L,
which corresponds to the secondary current
plus tolerance.
Check sum power
Provided that all voltage, current and power in
the corresponding phase is indicated correctly,
the sum power must be displayed correctly by
UMG 96L either.
For verification, the sum power measured by
UMG96L should be compared to the energy
stated by the real and reactive energy counters
of the supplier.
Page 11
Elimination of errors
Error
Display dark.
Measured value cannot be called up.
No current indication.
Current too small.
Current incorrect.
Reason
Prefuse released.
Device defective.
The indication has been deleted from measured value selection.
Corresponding voltage is not
connected.
Current measurement in wrong
phase
Current measurement in wrong
phase
Current transformer programmed incorrectly.
Measuring range exceeded.
Elimination
Insert fuse.
Send the device to the producer for repair.
Add the required measured value indication to the measured value selection.
Connect corresponding voltage.
Check and correct connection.
Check and correct connection.
Read ratio of current transformer and program accordingly.
Insert a current transformer with a higher
ratio.
Voltage L-N incorrect.
Voltage L-L too small
/ too high.
The current peak at measuring
input was exceeded caused by
harmonic waves.
The current at measuring input
was below measuring range.
Measurement in wrong phase.
Voltage transformer ratio programmed incorrectly.
Phase conductors interchanged.
N not connected.
Voltage transformer ratio programmed incorrectly.
Insert a current transformer with a higher
ratio.
Attention! Please ensure, that the measuring inputs are not overloaded.
Insert a current transformer with a smaller
ratio.
Check and correct connection.
Check and correct connection.
Read the voltage transformer ratio at the
voltage transformer and program accordingly.
Check and correct connection.
Check and correct connection.
Read voltage transformer ratio at the voltage transformer and program accordingly.
Page 12
Error
Reason
Elimination
Phase shift ind/cap.
Programmed data
get lost.
Real power too small
/ too high.
Real power supply /
consumption interchanged.
„Err“ in display.
Current path is assigned to the
wrong voltage path.
The device was exposed to
electro magnetical disturbance, which was higher than
those mentioned in the technical data.
Current transformer ratio is
programmed incorrectly.
Current path is assigned to the
wrong voltage path.
At least one current transformer connection is interchanged.
Current path is assigned to the
wrong voltage path.
See „error messages“
Check and correct connection.
Improve external protection measures
such as protection, filtering, earthing and
local separation.
Read current transformer ratio and program accordingly.
Check and correct connection.
Check and correct connection.
Check and correct connection.
The device does not
operate in spite of
the above.
Device defective.
Error messages
While exceeding an allowed measured value
range, the UMG 96L indicates the error message „Err“.
An exceeding of a measured value range
arises, if at least one of the three existing current or voltage inputs or the frequency is out of
the specified measuring range.
The symbols "V", "A" and „Hz“ indicate, which
measured value is out of range.
The phase is marked by the arrows upwards in
which the exceeding occured.
Attention!
Voltage and current beyond the specifications may destroy the device.
Please send the device back to the producer with a detailed description of the
error.
A = Current path
V = Voltage path
Hz = Frequency
L1
VA
Hz
L2
L3
Exceeding of measuring
range in phase L1/L2/L3
Page 13
Usage and indication
The usage of the UMG96L is carried out via the
keys one and two. Measured values and programming data are indicated on the liquid crystal display. You must distinguish between
Indication mode and
Programming mode.
By entering a password, you can avoid unintentional change of programming data.
Indication mode
In indication mode please scroll through the
programmed measured value indications by
using the keys 1 and 2. When the device is delivered, you can call up all measured values
shown in table 1. For each measured value indication, up to three measured values are indicated. The measured value rotation allows to
indicate all selected measured values on an alternate basis with a selectable changing time.
L1
L2
L3
cap
cos
ind
cap
cos
ind
cap
cos
ind
Programming mode
ϕϕ
ϕ
ϕϕ
ϕϕ
ϕ
ϕϕ
ϕϕ
ϕ
ϕϕ
Key1
PRG
MkWh
MkVArh
Hz
S
L-L
CT VT
K1
K2
12
Key 2
Programming mode
In programming mode the settings, which are
necessary for the operation of the UMG96L,
can be indicated and changed. Pressing the
keys 1 and 2 simultaneously for about 1 second, you reach programming mode via the
password indication. If no user password is programmed, you reach the first programming
menu directly. The programming mode is
marked with the text „PRG“ in the display.
With key 2 you can shift between the programming menues.
If you are in the programming mode and no
keys are pressed for 60 seconds, or you press
the keys 1 or 2 simultaneously for approx. 1
second, you return to the indication mode.
Programming menus:
- Current transformer,
- Voltage transformer,
- Averaging times,
Measured value indications
- Changing time,
- Measured value selection,
- Measured value rotation,
- Delete minimum and peak values,
- Delete energy,
- LCD contrast,
- Software Release,
- User pasword.
Page 14
Key functions
Indication mode
Change mode
Measured
long
2
values
Measured
short
values
ScrollProgramming
Measured
values
simultaneous
21
Measured
values
Password
Programming mode
simultaneous
21
Program-
ming menu
Program-
ming menu
Program-
ming menu
long
2
short
long
1
short
Program-
ming menu
1
Confirm selection
2
short digit +1
long digit -1
2
short value *10
(decimal point to the
right)
2
flashing
long value /10
(decimal point to the left)
Page 15
Table, measured value indication
Measured values
L1-N Voltage
L2-N Voltage
L3-N Voltage
Measured values
L1-L2 Voltage
L2-L3 Voltage
L3-L1 Voltage
Measured values
L1 Current
L2 Current
L3 Current
Measured value
Σ Current in N
Mean values
L1 Current
L2 Current
L3 Current
Mean value
Σ Current in N
Maximum values
L1-N Voltage
L2-N Voltage
L3-N Voltage
Maximum values
L1 Real power
L2 Real power
L3 Real power
Maximum values
L1 Current
L2 Current
L3 Current
Maximum value
Σ Measured value
current in N
Minimum values
L1-N Voltage
L2-N Voltage
L3-N Voltage
Minimum values
L1 Real power
L2 Real power
L3 Real power
Max. values
L1 Curr. mean val.
L2 Curr. mean val.
L3 Curr. mean val.
Maximum values
Σ Mean value
current in N
Measured values
L1 Real power
L2 Real power
L3 Real power
Measured value
sum
real power
Measured values
L1 Apparent power
L2 Apparent power
L3 Apparent power
Measured value
sum
apparent power
Mean values
L1 Real power
L2 Real power
L3 Real power
Mean value
sum
real power
Mean values
L1 Apparent power
L2 Apparent power
L3 Apparent power
Mean value
sum
apparent power
Maximum values
L1 Real power
L2 Real power
L3 Real power
Maximum value
(Consumption)
sum
real power meas.
Maximum values
L1 Apparent power
L2 Apparent power
L3 Apparent power
Maximum value
sum meas. value
apparent power
Maximum value
(Consumption)
sum
real power, mean
Page 16
Measured values
L1 Reactive power
L2 Reactive power
L3 Reactive power
Mean values
L1 Reactive power
L2 Reactive power
L3 Reactive power
Max. values (ind)
L1 Reac. power
L2 Reac. power
L3 Reac. power
Measured value
Sum
reactive power
Measured value
L1 cos(phi)
L2 cos(phi)
L3 cos(phi)
Measured value
Sum
cos(phi)
Measured value
L1 Frequency
Mean value
Sum
reactive power
Max. value (ind)
Sum
reactive power
Measured value
(Consumption)
Sum
real energy
Measured value
Sum
reactive energy(ind)
Working hours
counter
Page 17
Current transformer
Current transformers with either 1A or 5A secondary can be connected to the UMG96L.
A transformer ratio of 5A/5A is preset by the
manufacturer. In programming mode the current transformer setting is marked by the symbol „CT“.
Primary (5.00kA = 5000A)
PRG
L1
k A
Programming
In programming mode please scroll to the current transformer ratio by pressing key 2. Confirm the selection by pressing key 1.
The first digit of the primary current flashes and
can be changed by pressing key 2.
If key 1 pressed again the next digit will be selected and flashes now.
If the entire digit flashes, the decimal point can
be moved.
Press key 2 shortly - The decimal point moves
to the right.
Press key 2 longer - The decimal point moves
to the left.
If no digit flashes anymore, you can shift to the
indication of the voltage transformer.
L2
CT
L3
Secondary
Example: Sum current transformer
A current measurement is carried out via two
current transformers, one with a ratio of 1000/
5A and another transformer with a ratio of 200/
5A. The sum measurement is carried out with a
sum current transformer 5+5/5A.
The UMG96L has to be programmed with the
following values:
The program allows current and voltage
transformer ratio setting only, if the maximum phase power can reach up to
50.0MW and the sum power can reach a
maximum value of 150.0MW.
Voltage transformer
The phase to phase voltage (L-L) is indicated
on display of the UMG 96L as secondary and
primary voltage. The transformer ratio is calculated from the programmed primary and secondary voltage. In programming mode, the voltage transformer settings are marked by the
symbol „VT“.
The standard version is preset by the manufacturer with a ratio of 400V/400V.
The secondary voltage is always indicated in
„V“. The corresponding symbol „V“ is not displayed.
The primary voltage is indicated in „V“ or „kV“.
The corresponding symbol is displayed in „V“ or
„kV“.
UMG96L Setting range voltage transformer
VersionType plate L-L secondary L-L primary
Primary voltage
L1
L2
L3
Secondary voltage
Phase to phase
Voltage transformer ratio
PRG
V
L-L
VT
Standard version196 .. 255V400V100V .. 60kV (400V)
Special version 90 .. 160V200V, 220V100V .. 60kV (200V)
Special version 45 .. 80V100V, 110V100V .. 60kV (100V)
Programming
In programming mode, please scroll to the vol-
Primary voltage is 10,0kV
tage transformer setting by pressing key 2.
Confirm selection with key 1.
L1
PRG
kV
The first digit of the primary voltage flashes and
can be changed by pressing key 2.
If key 1 is pressed again the next digit will be
selected and flashes.
If the entire digit flashes, you can move the
decimal point.
L2
L3
L-L
VT
If no digit flashes anymore, you may shift to indication and programming of the outputs by
Secondary voltage is 100V
pressing key 2.
Example: Voltage transformer ratio 100V/10kV
Attention!
The program allows current and voltage
transformer ratio setting only, if the maximum phase power can reach up to
50.0MW and the sum power can reach a
maximum value of 150.0MW.
Page 19
Averaging times
A mean value is calculated for the most at the
current and power values. A common averaging time for the current measured values L1, L2,
L3 and N , as well as one for power measured
values, real power, apparent power and reactive power is programmable.
Method of taking the mean
The used exponential method reaches at least
95% of the measured value after the set averaging time.
MEn = ME
+ (MA-ME
n-1
n-1
) / N
Presettings:
Averaging time of currents = 900 seconds
Averaging time of power = 900 seconds
The following averaging times are selectable:
5, 10, 30, 60, 300, 480, 900 seconds
Programming of averaging time
Averaging time for real power
In programming mode please scroll to the averaging time for power with key 2. Confirm selection by pressing key 1.
The averaging time flashes and can be
changed by pressing key 2. Confirm changed
averaging time with key 1.
The averaging time stops flashing. The averaging time for power has been programmed.
By using key 2 you can now shift to programming menu „
Averaging time for current“
.
ME
= indicated mean value
n
MA= measured value
n= consecutive digit
N= digit of measured values, of witch
mean values shall be built.
PRG
L1
L2
L3
Example for the averaging time of real power
mean value, here 900 seconds.
W
S
Averaging time for Currents
In programming menu please scroll to the averaging time for currents. Confirm selection by
pressing key 1.
The averaging time flashes and can be
changed by pressing key 2. Confirm changed
averaging time with key 1. The averaging time
stops flashing. The averaging time for currents
has been programmed. By using key 2 you can
now shift to programming menu „
Rotation time“
Page 20
PRG
L1
PRG
MkWh
A
MkVArh
L2
L3
S
Example for the averaging time of current mean
value, here 30 seconds.
.
Measured value indication
Once in a second all measured values are calculated and can be indicated on the display.
Two methods are available for calling up the
measured value indications (see table 1).
- The selection of measured value indications
via the keys 1 and 2, herein called measuredvalue selection.
- The automatically rotating indications of selected measured value indications, herein
called measured value rotation.
A measured value rotation time has be programmed additionally for the measured value
rotation.
All mesured values for the measured value selection are preset by the manufactures. For the
automatic rotation nothing is preset by the
manufacturer. The rotation time is preset with 0
seconds.
Measured value rotation time
Both methods are available simultaneously.
The measured value rotation is programmed, if
at least one measured value indication and one
measured value rotation time bigger than 0 seconds is programmed. If no key is pressed for
about 60 seconds, an automatical change to rotation mode will be carried out, and all programmed measured values will be indicated
one after the other.
Setting range of measured value rotation time:
0 .. 250 seconds
If 0 seconds are programmed, no rotation will
be carried out. Nevertheless, measured value
indications which are not programmed in the
measured value selection
, can be used for
measured value rotation.
Rotation time in seconds indicated
PRG
L1
L2
L3
S
Abb.
Programming
In programming mode please scroll to the menu
measured value rotation, by using key 2. Confirm selection with key 1.
The first digit of the rotation time flashes and
can be changed by pressing key 2. By pressing
key 1 again the next digit will be selected and
flashes.
If no digit flashes anymore, you can shift to programming menu „
Measured value selection“
by
pressing key 2.
Page 21
Measured value selection
All measured values stated in table 1 (see page
16 and 17) can either be displayed via keep 1
and 2 measured value selection or automati-
cally measured value rotation.
All measured values for the measured valueselection are preset by the manufakturer. For
the automatical measured value rotation nothing is preset by the manufakturer.
The condition of the selection is indicated by
the output symbols. These symbols have the
following meaning:
Measured value selection
K1 The indication can be reached via the keys.
K1 The indication cannot be reached via keys.
Measured value rotation
K2 The indication changes automatically.
K2 The indication does not change automati-
cally.
PRG
L1
L2
L3
Programming
In programming mode please scroll to programming menu mesured value indication by
pressing key 2.
Confirm selection by pressing key 1.
The first measured value indicated stated in table 1 (see page 16 and 17) occurs.
A selection of the measured value indication is
carried out by pressing the keys quickly.
Key 1 - Scroll to the right within the measured
value indications.
Key 2 - Scroll downwards within the measured
value indications.
For the selected measured value indication, it
can now be determined whether it will be available for measured value selection and for automatic rotation.
The selection is carried out by an extended
push on keys 1 or 2.
Key 1 - Measured value selection.
Key 2 - Automatic rotation.
Measured value indication of
the current values
L1
L2
L3
Measured value selection
Measured value rotation
PRG
A
K1
K2
Once the programming is finished, you return
to indication mode by pressing keys 1 and 2 simultaneously.
Page 22
Delete minimum and maximum
values
In programming mode, „Deletion of minimum
and maximum values“ is marked by arrows upwards and downwards. All minimum and maximum values will be deleted simultaneously in
menu „Deletion of minimum and maximum values“.
An exception is the maximum value of the current mean value. The maximum value of the
current mean value can also be deleted directly
in indication menu by an extended pressing of
key 2.
Delete
In programming mode please scroll to
of minimum and maximum values”
key 2.
With key 1 you can shift between the indicated
digits 0 and 1. These digits have the following
meaning:
0 =Minimum and maximum values not to
be deleted.
1 =Minimum and maximum values to be
deleted.
“Deletion
by pressing
PRG
L1
L2
L3
PRG
L1
L2
L3
Leave menu “Deletion of minimum and maximum values” by pressing key 2. In case that
digit 1 was displayed, all minimum and maximum values were deleted.
Delete energy
The real and reactive energy can only be deleted together via the keys.
Delete
In programming mode please scroll to the menu
“delete energy”
By pressing key 1 you can shift between digits
0 and 1. These digits have the following meaning:
0 = Real and reactive energy not to be deleted.
1 = Real and reactive energy to be deleted.
by using key 2.
L1
L2
L3
L1
L2
PRG
Wh
PRG
Wh
Leave menu “Delete energy” by pressing key 2.
In case that digit 1 was displayed real and
reaktive energy were deleted.
L3
Page 23
Working hours counter
The working hours counter detects the time, in
which the UMG96L measures and indicates
data. The time is measured with a resolution of
15 minutes and is indicated in hours. The working hours counter cannot be deleted.
L1
h
L2
L3
Display example: The UMG96L indicates 40201
working hours.
LCD contrast
The favoured view for the LCD display is from
below. The LCD contrast of the LCD display
can be adapted by the user. The contrast setting is possible in the range from 0 to 7.
0 = very light
7 = very dark
Programming
In programming mode please scroll to LCD contrast by pressing key 2. Confirm selection with
key 1.
The first digit of the contrast setting is flashing.
Move to the right digit with key 1.
Now you can change the digit with key 2.
Afterwards you can shift to programming menu
„user password“
by pressing key 2.
PRG
L1
L2
L3
PRG
L1
L2
L3
Page 24
Software Release
The internal software of the UMG96L will be
improved and extended continuously. The software update is registered in the device by a
specific number the so called software release.
The software release cannot be changed by the
user.
PRG
L1
L2
L3
Example: In UMG96L, the software release
1.23 is installed.
User password
A user password can be programmed in order
to avoid an unintentional change of programming data. Only after entering the correct password, a shifting into the following programming
menues possible.
No user password by the manufacturer is preset (000). In this case, the password menu will
be skipped and you reach the current transformer menu directly.
In case that a user password was programmed,
a „000“ appears in the display of the password
menu.
The first digit of the password menu flashes and
can be changed with key 2. By pressing key 1,
the next digit will be selected and flashes.
Only after the correct password was entered,
you reach the programming menu for the current transformer.
In case that a changed password is not known
anymore, the device must be sent back to the
manufacturer.
The program allows current and voltage transformer ratio setting only, if the maximum phase
power can reach up to 50.0MW and the sum power can reach a maximum value of 150.0MW.
These specifications presuppose a yearly calibration and a warm up time of 10 minutes.
Used abbreviations:
rng= of measuring range
rdg= of measured value
1)
Measuring range with scale factor = 1, (Current tranformer = 5/5A, 1/1A)
2
) In the range of -10..18°C and 28..55°C, an additional error of +-0,5‰ of measured value has to
be considered per K.
3
) If the measured apparent power is in the range of 1% .. 100% of the measuring range, cos(phi)
is indicated with an accuracy of +-3%.
4)
Accuracy class according to DIN EN61036:2001-01, VDE0418part 7, IEC61036:1996 + A1:2000
5)
The maximum indication range and the resolution of real and reactive energy depends on
Transformer ratio v = vi * vu.
vi = Transformer ratio of current transformer.
vu = Transformer ratio of voltage transformer.
Example:200/5A -> vi = 40
1000/100V -> vu = 10
v = vi * vu
v = 40 *10
v = 400
Energy
/kvarh /kWh
999.999.999
210.000.000
21.000.000,0
2.100.000,00
Indication range and resolution for
real and reactive energy
1 10 100 400 v
Transformer ratio v
Page 27
Configuration data
Description DisplaySetting rangePresettings
Current transf., primaryCT1A .. 10,0kA5A
Current transf., secondaryCT1A, 5A5A
Voltage transf., primary
Type plate, 196 .. 255VVT100V .. 60.0kV400V
Type plate, 90 .. 160VVT100V .. 60.0kV200V
Type plate, 45 .. 80VVT100V .. 60.0kV100V
Voltage transformer, sec.
Type plate, 196.. 255VVT400V (not changeable)400V
Type plate, 90 .. 160VVT200V, 220V200V
Type plate, 45 .. 80VVT100V, 110V100V
Averaging time, current5, 10, .. 900Sec.900Sec.
Averaging time, power5, 10, .. 900Sec.900Sec.
Measured value rotation0 .. 250seconds0 = no rotation
Measured value selectionAll indicationsall indications
LCD contrast0 .. 73
Software Releasenot changeablex.xx
User passwort000 .. 999„000“ = no password
Working hours counternot changeable0h
Page 28
Declaration of conformity
The UMG96L fulfills the protection guidelines of:
Guideline 89/336/EWG in combination with DIN EN61326 (2002-03) as well as
Guideline 73/23/EWG and 93/68/EWG in combination with EN 61010-1 (2002-08)
Safety guidelines
Safety requirements for electrical equipment for measurement, control, and laboratory use
Part1: General requirements: EN61010-1:2001, IEC 61010-1:2001
Test voltage
Enclosure against measuring inputs: 2kV AC
Between the inputs for measuring and auxiliary voltage and the current inputs exists a functional
separation of 2000V AC.
EMC requirements
Electromagnetic emission: DIN EN61326:2002-03, table 4, class B
Electromagnetic immunity: DIN EN61326:2002-03, table A.1
Measurement category: III (Measurement within building installation)
Pollution degree: 2
Protection class: II = with protective earth
Ambient temperature: -10°C .. +55°C
Storage temperature: -20°C .. +70°C
Humidity: 15% up to 95% without dew
Protection class
Front: IP50 according to IEC60529
Front with seal (Option): IP65 according to IEC60529
Back side: IP20 according to IEC60529
Mounting position: random
Operating height: 0 .. 2000m over sea level
Measurement
Measuring inputs
Measuring rate: 1 measurement per second
Rated pulse voltage: 4kV
Signal frequency: 45Hz .. 1000Hz
Scanning frequency: 2,5kHz/3,0kHz (Net frequency 50Hz/60Hz)
Measuring and operating voltage: see type plate
Fuse: 2A .. 10A (medium time lag type)
Frequency of fundamental: 45Hz .. 65Hz
Power consumption Phase (L1-N): ca. 2,5VA
230V/400V Standard version
Range L-N: 196 .. 255V AC
Range L-L: 340 .. 442V AC
120V/220V Special version
Range L-N: 90 .. 160V AC
Range L-L: 156 .. 277V AC
60V/120V Special version
Range L-N: 45 .. 80V AC
Range L-L: 78 .. 139V AC
Current measurement
Power consumption: approx. 0,2VA
Rated current at ../5A (../1A): 5A (1A)
Minimum working current: 20mA
Current limit at ../1A: 1,2A (sinus shape)
Current limit at ../5A: 6A (sinus shape)
Overload: 150A for 2 Sec.
Accuracy class of energy measurement: class 2
Connectable cables
One wire, multiple-wire, fine wire: 0,08 - 2,5mm
Pin contacts: 1,5mm2, only one conductor may be connected
per terminal!
Page 30
2
Dimensions
123
123
123
123
123
123
123
123
1
3
1
3
123
123
1
3
1
3
123
123
1
3
1
3
123
123
123
123
123
123
123
123
123
123
123
123
123
123
123
1
3
1
3
123
123
123
123
123
123
123
123
123
Cut out: 92
Fixing angles
+0,8
x 92
+0,8
mm
Panel max. 6
90
2
2
2
2
2
2
S V J M A D E P
UMG96L
45-65Hz IP20
2,5VA
Made in Germany
96
4N3
Spannungsmessung
Voltage Measurement
1
2
L3
L2
L1
2-10A
Strommessung/Current Measurement
k l
2
2
57 10896
Type plate
L2L3L1
k l
k l
42
Diagr. Side view
6
Diagr. Back view
All dimensions in mm
Connection example
UMG96L
Voltage Measure-
ment
see type plate
12345678910
L1 L2 L3 N
L1
L2
L3
PEN
Diagr.: Connection example 1
Four wire measurement with three current transformers.
Current
measurement
0,02 .. 5A
1k 1l 2k 2l 3k 3l
kl
../5(1)A
k
../5(1)A
../5(1)A
l
k
l
Consumer
Verbraucher
Page 31
Brief instructions
Change current transformer ratio
Shift to programming mode
If you are in the indication mode please press the keys 1 and
2 simultaneously for approx. 1 second. Now you reach programming mode.
The symbols for programming mode PRG and for the current
transformer CT appear.
Confirm selection with key 1.
The first digit of the primary flashes.
Current transformer symbol
Change primary current:
Change the flashing digit with key 2.
Select the next digit to be changed by pressing key 1.
The selected digit flashes.
If the entire number flashes, the decimal point can be
moved.
Change secondary current:
Only 1A or 5A can be set as secondary current.
Select secondary current with key 1.
Change flashing digit with key 2.
Leave programming mode:
Press both keys simultaneously for approx. 1 second.
The current transformer setting will be stored and you return
to indication mode.
Programming mode
L1
L2
L3
Primary current
L1
L2
L3
Secondary current
PRG
k A
CT
12
PRG
k A
CT
12
Call up measured values
Shift to indication mode
If you are in programming mode please press the keys 1 and
2 simultaneously for approx. 1 second. Now you reach the indication mode.
The symbol PRG for programming mode does not appear in
the display and the first measured value indication, e.g. for
the voltage appears.
Key 2
With key 2 you scroll between the different measured value
indications for current, voltage, power etc.
Key 1
With key 1 you scroll between the mean values, maximum
values etc., related to the corresponding measured value.
Page 32
L1
L2
L3
V
1
2
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.