janitza UMG 605 PRO User Manual And Technical Data

Doc. no. 1.038.027.1.b 2017-09-19
Power Quality Analyser
UMG 605-PRO
User manual and technical data
Part no. 33.03.126
Janitza electronics GmbH Vor dem Polstück 6 D-35633 Lahnau Support tel. +49 6441 9642-22 Fax +49 64 41 9642-30 e-mail: info@janitza.com Internet: http://www.janitza.com
www.janitza.com
A B
UMG 605-PRO
www.janitza.de
I
1. Contents
1. General 1
1. 1 Disclaimer 1
1. 2 Copyright notice 1
1. 3 Technical changes 1
1. 4 Declaration of conformity 1
1. 5 Comments on the manual 1
1. 6 Meaning of symbols 1
2. Safety 3
2. 1 Safety information 3
2. 2 Safety measures 3
2. 3 Qualified staff 4
3. Proper use 5
3. 1 Inspection on receipt 5
3. 2 Scope of delivery 6
3. 3 Available accessories 6
4. Product description 7
4. 1 Measuring process 7
4. 2 Network failure detection 7
4. 3 Usage concept 7
4. 4 GridVis® network analysis software 7
4. 5 Features 8
4. 6 Product overview 9
4. 7 Installation location 10
5. Network systems 11
5. 1 Three-phase 4-conductor systems 12
5. 2 Three-phase 3-conductor systems 12
5. 3 Rated voltages 13
www.janitza.de
UMG 605-PRO
II
6. Installation 15
6. 1 Disconnectors 15
6. 2 Supply voltage 15
6. 3 Measured voltage 16
6. 4 Frequency measurement 16
6. 5 Current measurement 17
6. 5. 1 Ammeter 18
6. 5. 3 Direct measurement 18
6. 5. 2 Total current measurement 18
6. 5. 4 Current direction 18
6. 6 Connection variants 19
6. 6. 1 Baseline measurement, inputs 1-3 19
6. 6. 2 Supporting measurement, input V4 21
6. 7 Temperature measurement 22
7. Interfaces 23
7. 1 Shielding 23
7. 2 RS232 24
7. 3 RS485 24
7. 3. 2 Cable type 25
7. 3. 1 Termination resistors 25
7. 4 Bus structure 26
7. 5 Profibus 27
7. 5. 1 Connection of the bus wiring 27
8. Digital inputs and outputs 29
8. 1 Digital inputs 29
8. 2 S0 pulse input 30
8. 3 Digital outputs 31
9. Commissioning 33
9. 1 Connecting the supply voltage 33
9. 2 Frequency measurement 33
9. 3 Connecting the measured voltage 33
9. 4 Phase sequence 33
9. 5 Applying the measured current 34
9. 6 Checking the power measurement 34
10. Operation 35
10. 1 Button functions 35
10. 2 Display mode 35
10. 3 Programming mode 36
10. 4 Display password 36
10. 5 Homepage password 36
UMG 605-PRO
www.janitza.de
III
11. Configuration 37
11. 1 Measurement 37
11. 1. 1 Baseline measurement (measurement channels 1-3) 37
11. 1. 2 Supporting measurement (measurement channel 4) 37
11. 3 Voltage transformer ratio 38
11. 2 Current transformer ratio 38
11. 4 RS232 configuration 39
11. 5 RS485 configuration 39
11. 6 Ethernet configuration 40
11. 7 Profibus configuration 41
11. 7. 1 Profiles 41
11. 7. 2 Device master file 41
11. 7. 3 Pre-set profiles 42
11. 8 Recording configuration 45
12. System information 47
12. 1 Measurement range exceeded 47
12. 4 Serial number 47
12. 5 Date 47
12. 2 Firmware release 47
12. 3 Time 47
13. Device homepage 49
13. 1 Measured values 50
13. 1. 1 Short overview 50
13. 1. 2 Detailed measured values 51
13. 1. 3 Diagrams 52
13. 1. 4 Events 52
13. 1. 5 Transients 53
13. 2 Power quality 54
13. 3 Apps 55
13. 3. 1 Push Service 55
13. 4 Information 56
13. 4. 1 Device information 56
13. 4. 2 Downloads 56
13. 4. 3 Display 56
14. Service and maintenance 57
14. 1 Repair and calibration 57
14. 2 Front film 57
14. 3 Disposal 57
14. 4 Service 57
14. 5 Battery 57
14. 6 Firmware update 57
www.janitza.de
UMG 605-PRO
IV
15. Procedure in the event of faults 59
16. Technical data 61
16. 1 General 61
16. 2 Environmental conditions 61
16. 3 Transport and storage 61
16. 4 Supply voltage 62
16. 5 Protection class 62
16. 6 Digital inputs and outputs 63
16. 7 Temperature measurement input 64
16. 8 Interfaces 65
16. 9 Voltage measurement inputs 66
16. 10 Current measurement inputs 66
16. 11 Function parameters 67
16. 11. 1 Measurement in the frequency range 50/60 Hz 67
16. 11. 2 Measurement in the frequency range of 15 to 440 Hz 68
16. 12 Specifications per IEC 61000-4-30 class S 69
17. Parameter list 71
18. Measured value indications 75
19. Dimension diagrams 77
19. 1 Front view 77
19. 2 Side view 78
20. Connection example 79
21. Short introduction (setting primary current) 81
UMG 605-PRO
www.janitza.de
1
1. 1 Disclaimer
Observing the information products for the devices is the prerequisite for safe operation and in order to obtain the specified performance and product features. Janitza electronics GmbH accepts no liability for injuries to personnel, property damage or financial losses arising due to a failure to comply with the information products. Ensure that your information products are accessible and legible.
1. 2 Copyright notice
© 2017 - Janitza electronics GmbH - Lahnau. All rights reserved. Duplication, editing, dissemination and other utilisation, also in part, is prohibited. All trademarks and the resulting rights are the property of their respective owners.
1. 3 Technical changes
• Please ensure that your device complies with the installation manual.
• Please read and understand the documents enclosed with the product first.
• Keep the documents enclosed with the product available throughout the entire service life of the product and pass them on to subsequent users if applicable.
• Inform yourself of any new device versions and the associated updates to the documentation enclosed with the product at www.janitza.de.
1. 4 Declaration of conformity
For information on the laws, standards and directives that Janitza electronics GmbH has applied for the device, see the declaration of conformity on www.janitza.de.
1. 5 Comments on the manual
We welcome your comments. If anything in this manual seems unclear, please let us know by sending us an e-mail to:
info@janitza.de
1. 6 Meaning of symbols
This manual uses the following pictograms:
1. General
Ground wire connection.
Inductive.
The current lags behind the voltage.
Capacitive.
The voltage lags behind the current.
www.janitza.de
UMG 605-PRO
2
UMG 605-PRO
www.janitza.de
3
Please read this operating manual and all other publications that must be consulted to work with this product.
Observe all safety instructions and warnings. Failure to comply with the instructions can result in personal injuries and/or damage to the product.
Any unauthorised changes or use of this device, which go beyond the mechanical, electrical or otherwise stated operating limitations, can result in bodily injury and/or damage to the product.
Any such unauthorised change constitutes "misuse" and/or "negligence" according to the warranty for the product and thus excludes the warranty for covering possible damage resulting from this.
The user manual:
• must be read before using the device.
• must be kept throughout the entire service life of the product and be readily available for reference.
Follow additional legal and safety regulations required for the respective application when using the device.
2. 1 Safety information
Symbols used:
c
This symbol is used as an addition to the safety instructions and warns of an electrical hazard.
C
This symbol with the word note describes:
• Procedures that do not pose any risk of injures.
• Important information, procedures or handling steps.
Safety information is highlighted by a warning triangle and is indicated as follows depending on the degree of danger:
m
DANGER!
Indicates an imminent danger that causes severe or fatal injuries.
m
WARNING!
Indicates a potentially hazardous situation that can cause severe injuries or death.
m
CAUTION!
Indicates a potentially hazardous situation that can cause minor injuries or damage to property.
2. Safety
www.janitza.de
UMG 605-PRO
4
2. 2 Safety measures
When operating electrical devices, certain parts of these devices are invariably subjected to hazardous voltage. Therefore, severe bodily injuries or damage to property can occur if they are not handled properly.
m
WARNING!
If the device is not operated according to the user manual, protection is no longer ensured and hazards can be posed by the device.
2. 3 Qualified staff
This device must only be operated and repaired by specialised personnel.
Specialised personnel are people who are qualified to recognise risks and prevent potential dangers that can be caused by the operation or maintenance of the device based on their respective training and experience.
c
WARNING!
Risk of injury due
to electric voltage!
Severe bodily injuries or death can occur due to dangerous voltages.
Therefore, note the following:
Before connecting connections, earth the device at the ground wire connection if present.
Hazardous voltages may be present in all switching parts that are connected to the power supply.
Hazardous voltages may also be present in the device even after disconnecting the supply voltage.
Provide single core conductors with sleeves.
Only connect screw-type terminals with a matching number of pins and of the same type.
De-energise the system before starting work.
UMG 605-PRO
www.janitza.de
5
3. 1 Inspection on receipt
The prerequisites of faultless, safe operation of this device are proper transport and proper storage, set-up and installation, as well as careful operation and maintenance.
Packing and unpacking must be carried out with customary care without the use of force and only using suitable tools. The devices should be visually checked for flawless mechanical condition.
Please check the delivered items for completeness before you start installing the device.
If it can be assumed that risk-free operation is no longer possible, the device must be immediately put out of operation and secured against being put back into operation again. It can be assumed that risk-free operation is no longer possible if the device, for example:
• has visible damage,
• no longer works despite the mains power supply being intact,
• has been exposed to prolonged adverse conditions (e.g. storage outside the permissible climate limits without being adapted to the room climate, condensation, etc.) or rough handling during transportation (e.g. falling from a height, even if there is no visible external damage, etc.)
3. Proper use
C
NOTE!
All supplied options and versions are described on the delivery note.
C
NOTE!
The installation and commissioning manual also describes options that are not supplied as standard.
C
NOTE!
All screw-type terminals included in the scope of delivery are attached to the device.
www.janitza.de
UMG 605-PRO
6
3. 2 Scope of delivery
Number Part no. Designation
1 52.16.xxx
1)
UMG 605-PRO
1 33.03.337 Installation manual
1 33.03.351 “GridVis software” quick guide
1 10.01.807 Screw-type terminal, pluggable, 2-pin
1 10.01.808 Screw-type terminal, pluggable, 3-pin
1 10.01.809 Screw-type terminal, pluggable, 5-pin
1 10.01.810 Screw-type terminal, pluggable, 6
1 89.10.051 Slotted screwdriver (0.40 x 2 mm), ESD
1 08.01.505 2m patch cable, twisted, grey (UMG PC/switch connection)
1 52.00.008 RS485 termination resistor, 120 ohms
1)
For the item number, see the delivery note
Part no. Designation
21.01.058 CR2032 lithium battery, 3 V (approval according to UL 1642)
08.02.427 RS232, connection cable (UMG604-PRO - PC), 2 m, 5-pin
3. 3 Available accessories
UMG 605-PRO
www.janitza.de
7
The device is intended for:
• measuring power quality according to EN61000-4-30 in building installations, on distribution units, circuit breakers and busbar trunking systems.
• measuring measured voltages and currents that derive from the same network.
• measurements in low voltage networks where rated voltages of up to 300 V and surge voltages of overvoltage category III can occur.
• installation in fixed switching cabinets or small installation distributors. It can be installed in any position.
• current measurement, for which it is provided with external ../1 A or ../5 A current transformers.
• use in 2, 3 and 4-conductor networks and in TN and TT networks.
• measurements in medium and high­voltage networks via current and voltage transformers only.
The measurement results can be displayed, read out and further processed via the device's interfaces.
4. 1 Measuring process
The device measures continuously and calculates all effective values over a 200 ms interval.
The device measures the real effective value (TRMS) of the voltages and currents connected to the measurement inputs.
4. 2 Network failure detection
Network failure detection is carried out via the voltage measurement inputs. The selection of voltage measurement inputs can be configured using the GridVis® software.
The device bridges the following network failures on the auxiliary voltage input:
• Supply voltage: 230 V AC
• Bridging time: max. 80 ms
4. Product description
C
NOTE!
Use the parameter list from “17. Parameter list” for configuration on the device and use the Modbus address list on www.janitza.de for configuration via a serial interface
4. 3 Usage concept
You can program and call up the measured values via many routes using the device:
Directly on the device via 2 buttons and the display
• Using the GridVis® programming software
• Using the device homepage
• Using the Modbus protocol. You can modify and call up the data using the Modbus address list. The list can be called up from www.janitza.de.
This user manual only describes how to operate the device using the 2 buttons. The GridVis® programming software has its own "online help" system.
4. 4 GridVis® network analysis software
You can use the GridVis® network analysis software that is available at www.janitza. de to program the device and read out data. To do this, a PC must be connected to the device via a serial interface (RS485/ Ethernet).
You can use the GridVis® network analysis software to:
• program the device.
• configure and read out recordings.
• save the data to a database.
• display measured values graphically.
• program customer-specific applications.
www.janitza.de
UMG 605-PRO
8
4. 5 Features
General
• Installation on a 35 mm DIN rail
• LCD display and operation via 2 buttons
• 4 voltage and 4 current measurement inputs
• 1 temperature measurement input
• 2 digital outputs and 2 digital inputs
• RS485 interface (Modbus RTU, Modbus master, BACnet (optional))
• RS232 interface (Modbus slave)
• Profibus DP/V0
• Ethernet (web server, e-mail, BACnet (optional))
• Suitable for installation in installation distributors
• Working temperature range -10 °C to +55 °C
• Analysis and evaluation in accordance with DIN EN50160 with the GridVis® programming software that is supplied as standard
• Data logger / event store (128 MB flash drive)
• Capture events such as overvoltages, voltage dips, network failures and overcurrent
Measurement
• Measurement of the power quality in accordance with DIN EN61000-4-30:2009 class S
• Measurement in IT, TN and TT networks
• Measurement of the harmonics and interharmonics (Uln, Ull, I) in accordance with DIN EN61000-4-7
• Flicker measurement in accordance with DIN EN61000-4-15:2011 Class F3
• Measurement of ripple control signals (U, I, P, Q)
• Continuous sampling of the voltage and current measurement inputs
• Capture transients >50 µs and store up to 16,000 sampling points
• Capturing more than 2400 measured values per measurement cycle (200 ms)
• Fourier analysis 1st to 63rd Harmonics for Ull, Uln, I, P (consumption/delivery) and Q (ind./capacitive)
• Temperature measurement
• Active energy; measurement uncertainty in accordance with DIN EN62053-22, class 0.5 S for ../5A converter
• Reactive energy; measurement uncertainty in accordance with DIN EN62053-23, class 2
• Programming separate applications in Jasic
UMG 605-PRO
www.janitza.de
9
4. 6 Product overview
1
7
2
8
3
11
10
9
4
5
6
12
1 RS232 interface 2 Temperature measurement input 3 Hidden service button 4 Profi bus interface 5 Ethernet interface 6 Current measurement inputs I1 to I4 7 RS485 interface 8 Digital inputs / outputs 9 Supply voltage 10 Button 1 11 Button 2 12 Voltage measurement inputs L1 to L4
Fig. Front view of UMG605-PRO
www.janitza.de
UMG 605-PRO
10
4. 7 Installation location
The device can be installed in switching cabinets or in small installation distributors in accordance with DIN 43880 .
It is assembled on a 35 mm mounting rail in accordance with DIN EN 60715. It can be installed in any position.
Fig. Front view of UMG 605-PRO on mounting rail
UMG 605-PRO
www.janitza.de
11
5. Network systems
Three-phase four-
conductor systems
with earthed neutral
conductor
Three-phase four-
conductor systems
with non-earthed neutral
conductor (IT networks)
Three-phase three­conductor systems
not earthed
Three-phase three­conductor systems
with earthed phase
L1
L2
L3 EE
N
E
L1 L2
L3 E
N
R
L1
L2 L3 EE
L1
L2 L3 EE
E
L1
L2
L3 E
N
R
L1
L2 L3 EE
L1
L2 L3 EE
L1
L2 L3 EE
L1
L2 L3 EE
L1
L2 L3 EE
U
L-N
/ U
L-L
277 VLN / 480 VLL
U
L-N
/ U
L-L
277 VLN / 480 VLL
U
L-L
480 VLL
U
L-L
480 VLL
Dual-phase two-conductor
systems
not earthed
Single-phase two-
conductor systems
with earthed neutral conductor
Separated single-phase
three-conductor system
with earthed neutral conductor
The device can be used:
• in 2-, 3­and 4-conductor networks (TN, TT and IT networks).
• in domestic and industrial settings.
L1 L2
L3 EE
N
E
L1 L2
L3 E
N
R
L1
L2 L3 EE
L1
L2
EE
L
N EE
L1
L2 L3 EE
L1
L2
N
EE
E
L1 L2
L3 E
N
R
L1
L2 L3 EE
L
N
EE
L1
L2 L3 EE
L1
L2
N
EE
L1
L2 L3 EE
L1
L2 L3 EE
L1
L2
N
EE
U
L-L
480 VLL
U
L-N
480 VLN
U
L-N
/ U
L-L
277 VLN / 480 VLL
Suitable network systems and maximum rated voltages (DIN EN 61010-1/A1):
c
WARNING!
Risk of injury due to electric voltage!
If the device is subjected to measurement voltage surges higher than the permissible overvoltage category, safety-relevant insulations in the device can be damaged, which means that the product’s safety can no longer be guaranteed.
Only use the device in environments in which the permissible measurement voltage surge is not exceeded.
www.janitza.de
UMG 605-PRO
12
5. 1 Three-phase 4-conductor systems
The device can be used in three-phase 4-conductor systems (TN, TT networks) (50 Hz, 60 Hz) with an earthed neutral conductor. The bodies of the electrical system are earthed. The voltage between phase and neutral conductor may be a maximum of 300 V AC.
UMG605-PRO
Earthing of the system
DC
AC/DC
PE
230/400V 50/60Hz
L2
L3
N
L1
Auxiliary supply
Voltage measurement
4M
4M
4M
4M
L1 L3L2 N
4M
L4
N
L1
240V 50/60Hz
5. 2 Three-phase 3-conductor systems
The device can be used in non-earthed three­phase 3-conductor systems (IT network).
The voltage between phase and phase may be a maximum of 480 V AC (50 Hz, 60 Hz).
The IT network is not earthed at the neutral point of the voltage generator. The bodies of the electrical system are earthed. Earthing via a high ohm impedance is permitted.
IT networks are only permitted in certain systems with their own transformers or generators.
230/400V 50/60Hz
UMG605-PRO
Earthing of the system
DC
AC/DC
L2
L3
N
L1
Auxiliary supply
4M
4M
4M
4M
L1
L3L2 N
4M
L4
Impedance
Voltage measurement
400V 50/60Hz
DC
AC/DC
L2
L3
Auxiliary supply
Voltage measurement
4M
4M
4M
4M
L1
L3L2
4M
L4
Earthing of the system
Impedance
L1
UMG605-PRO
N
Fig. Schematic diagram, UMG 605-PRO in a TN network
Fig. Schematic diagram, UMG 605-PRO in an IT network with N
Fig. Schematic diagram, UMG 605-PRO in an
IT network without N.
UMG 605-PRO
www.janitza.de
13
5. 3 Rated voltages
The following illustrations show lists of networks and the corresponding rated network voltages in which the device can be used.
U
L-N
/ U
L-L
66 V / 115 V
120 V / 208 V
127 V / 220 V
220 V / 380 V
230 V / 400 V
240 V / 415 V
260 V / 440 V
277 V /480 V
U
L-L
66V
115V
120V
127V
200V
230V
240V
260V
277V
347V
380V
400V
415V
440V
480V
Fig. Table of suitable
rated voltages in a three-phase 4-conductor network
Fig. Table of suitable
rated voltages in a three-phase 3-conductor network
www.janitza.de
UMG 605-PRO
14
UMG 605-PRO
www.janitza.de
15
6. Installation
6. 1 Disconnectors
During building installation, provide a suitable disconnector in order to disconnect the device from the current and voltage.
• Install the disconnector close to the device so that it is easily accessible to the user.
• Label the switch as a disconnection device for this device.
6. 2 Supply voltage
The device requires supply voltage to operate.
Before connecting the supply voltage, ensure that the voltage and frequency correspond to the details on the rating plate!
The connection lines for the supply voltage must be protected using a UL-listed fuse or a circuit breaker.
c
WARNING!
Risk of injury due
to electric voltage!
Severe bodily injuries or death can occur due to
• touching bare or stripped wires that are live,
• device inputs that are dangerous to touch.
Therefore, note the following:
De-energise your system before
starting the work!
The inputs for the supply voltage are
hazardous if touched!
m
CAUTION!
Damage to property
due to not observing
the connection conditions
Failure to observe the connection conditions can damage or destroy your device.
Therefore, note the following:
Adhere to the specifi cations for voltage and frequency on the rating plate.
Connect the supply voltage via a fuse in accordance with the technical data.
Do not connect the supply voltage to the voltage transformers.
Supply voltage
Uh
Isolation device
Fuse
Fig. Example connection for the supply voltage Uh.
C
NOTE!
Devices that can be operated with DC voltage are protected against polarity reversal.
www.janitza.de
UMG 605-PRO
16
6. 3 Measured voltage
The device is designed to measure AC voltage in 300 V networks, in which overvoltages of category III can occur.
The device can only determine measured values if measured voltage of >10 Veff is present on at least one voltage measurement input.
c
WARNING!
Risk of injury due
to electric voltage!
Severe bodily injuries or death can occur due to a failure to observe the connection conditions for the voltage measurement inputs.
Therefore, note the following:
Do not use the device for voltage measurement in SELV circuits.
Connect the voltages higher than the#permitted network rated voltages using voltage transformers.
The voltage measurement inputs on the device are dangerous if touched!
Also install a disconnector for the measured voltage as described in “6. 1 Disconnectors”.
c
CAUTION!
Malfunction due to
incorrect connection
If the device is connected incorrectly, incorrect measured values may be returned.
Therefore, note the following:
Measured voltages and currents must derive from the same network.
The device is not suitable for measuring DC voltage.
L3
N
L1
L2
Disconnectors
Fig.23.1 Connection example: Voltage measurement via
short circuit-proof measurement wires
Note the following when selecting the measurement wires:
• Use measurement wires that are suitable for 300 V to earth and 520 V conductor to conductor.
• Fuse the normal measurement wires using an overcurrent protection device.
• Route normal short circuit-proof measurement wires via a disconnector.
L
N
Fig. Voltage measurement input with connected phase L
and neutral conductor N
6. 4 Frequency measurement
The device is suitable for measurements in networks in which the fundamental oscillation of the voltage is in the range of 15 to 440 Hz.
In order to determine the mains frequency automatically, a voltage L1-N of greater than 10 Veff must be applied to voltage input V1.
The mains frequency is only measured on the measurement inputs of the baseline measurement (V1, V2, V3).
UMG 605-PRO
www.janitza.de
17
6. 5 Current measurement
The device:
• is intended for connecting current transformers with secondary currents of ../1 A and ../5 A.
• does not measure DC.
• has current measurement inputs that are continuously loaded with 6 A or loaded with 100 A for 1 second.
m
WARNING!
Risk of injury due
to electric voltage
on current transformers!
On current transformers that are operated open on the secondary side, high voltage peaks that are dangerous to touch can occur, which can cause severe bodily injuries or death.
Therefore, note the following:
Avoid operating the current transformers open.
Short circuit all unloaded current transformers.
Connect the earthing connections provided on the current transformer to the earth.
You must short circuit the secondary connections on the current transformer before interrupting the power supply.
If a test switch, which automatically short-circuits the secondary wires of the current transformer is available, it is suffi cient to set this to the "Test" position as long as the short-circuiting device has been checked beforehand.
Ensure that the attached screw­type terminal is affi xed to the device suffi ciently using the two screws.
Safe open-circuit current transformers are also dangerous to touch when they are operated open.
C
NOTE!
It is not necessary to confi gure a connection schematic for measurement inputs L4 and I4.
Consumer
L3
L1
L2
N
S1
S2
S1
S2
S1
S2
S1
S2
Fig.
Current measurement via current transformers
connection example.
m
WARNING!
Risk of injury due
to electric voltage!
Current measurement inputs are dangerous to touch.
www.janitza.de
UMG 605-PRO
18
6. 5. 1 Ammeter
If you wish to measure the current not only with the UMG but rather with an ammeter too, connect the ammeter to the UMG in series.
6. 5. 2 Total current measurement
F
or a summation measurement via two current transformers, first set their total transformation ratio on the device. For information on setting the current transformer ratios, see “11. 2 Current transformer ratio”.
Example:
The current is measured via two current transformers. Both current transformers have a transformation ratio of 1000 / 5 A. The summation measurement is performed using a 5+5 / 5 A total current transformer.
The device must then be set up as follows:
Primary current: 1000 A + 1000 A = 2000 A Secondary current: 5 A
UMG
S2
I
S
1
P1
P2
Einspeisung 1 Supply 1
Einspeisung 2
Supply 2
1P1
1P2
(K)
(L)
(k) (l)
1S
2
1S1
1S1 1S2 2S1 2S2
2S1
2S2
(k)
(l)
(K) (L)
2P
1
2P2
Verbraucher A Consumer A
Verbraucher B
Consumer B
Fig. Circuit diagram with additional ammeter switched
in series
UMG
S2
I
S
1
Einspeisung Supply
Verbraucher
Consumer
A
(k)S
1 S2(l)
P
2(L)(K)P1
Fig. Example for current measurement via a total current
transformer
Fig. Example of direct current measurement.
6. 5. 3 Direct measurement
Rated currents of up to 5 A can be measured directly on the device. When doing so, note that each current measurement input can be continuously loaded with 6 A or loaded with max. 100 A for 1 second.
The device does not have integrated protection for current measurement. Therefore, provide a 6 A line protection fuse or automatic circuit breaker as protection against overcurrent when installing.
UMG
S2
I
S
1
Einspeisung
Supply
Verbraucher Consumer
6. 5. 4 Current direction
You can correct the current direction directly on the device or via the existing serial interfaces for each phase individually.
If incorrectly connected, a subsequent re-connection of the current transformer is not required.
UMG 605-PRO
www.janitza.de
19
6. 6 Connection variants
6. 6. 1 Baseline measurement, inputs 1-3 Four-conductor connection
Fig. Measurement via 3 voltage transformers in a three-
phase 4-conductor network with asymmetric loading.
Fig. Measurement in a three-phase 4-conductor network
with asymmetric loading.
Fig. Measurement via 2 voltage transformers in a three-
phase 4-conductor network with asymmetric loading.
Fig. Measurement in a three-phase 4-conductor network
with symmetric loading.
Fig. Measurement in a three-phase 4-conductor network
with asymmetric loading.
Fig. Measurement via 2 current transformers in a three-
phase 3-conductor network with symmetric loading.
L1 L2 L3
N
L1 L2 L3 N
4w 3m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L
1 L2 L3 N
4w 3m
hv
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L
1 L2 L3 N
4w 2i
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L1 L2 L3 N
4w 3m
hv
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L
1 L2 L3 N
4w 2i
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L
1 L2 L3 N
4w 3m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L
1 L2 L3 N
4w 3m
hv
I
1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L
1 L2 L3 N
4w 2i
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L1 L2 L3 N
4w 2m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L
1 L2 L3 N
4w 2u
hv
I
1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L
1 L2 L3 N
4w 2u
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L
1 L2 L3 N
4w 3m
hv
I
1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L
1 L2 L3 N
4w 2i
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L1 L2 L3 N
4w 2u
hv
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L
1 L2 L3 N
4w 2u
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L1 L2 L3 N
4w 2i
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L
1 L2 L3 N
4w 2i
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L1 L2 L3 N
4w 2u
I1 I2 I3
S1 S2 S1 S2 S1 S2
www.janitza.de
UMG 605-PRO
20
Three-conductor connection
Fig. Measurement in a three-phase 3-conductor network
with asymmetric loading.
Fig. Measurement in a three-phase 3-conductor network
with asymmetric loading.
Fig. Measurement in a three-phase 3-conductor network
with asymmetric loading.
Fig. Measurement in a three-phase 3-conductor network
with asymmetric loading.
Fig. Measurement in a single-phase 3-conductor
network. I3 and U3 are not calculated and set to zero.
Fig. Measurement in a three-phase 3-conductor network
with asymmetric loading.
Fig. Measurement in a three-phase 3-conductor network
with asymmetric loading.
Fig. Measurement of one phase in a three-phase
4-conductor network.
L1 L2 L3
L1 L2 L3 N
3w 3m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L
1 L2 L3 N
3w 2i
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L
1 L2 L3 N
3w 2m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L1 L2 L3 N
3w 2i
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L
1 L2 L3 N
3w 2m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L
1 L2 L3 N
3w 2m
hv
I
1 I2 I3
S1 S2 S1 S2 S1 S2
L1
N
L
1 L2 L3 N
2w 1m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L
1 L2 L3 N
3w 3m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L
1 L2 L3 N
3w 2i
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L
1 L2 L3 N
3w 2m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L1 L2 L3 N
3w 2u
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L
1 L2 L3 N
3w 2u
hv
I
1 I2 I3
S1 S2 S1 S2 S1 S2
L1
N
L
1 L2 L3 N
2w 1m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L
1 L2 L3 N
3w 2i
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L
1 L2 L3 N
3w 2m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L
1 L2 L3 N
3w 2m
hv
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L1 L2 L3 N
3w 2u
hv
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3 N
2w 2m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1
L2
L1 L2 L3
L1 L2 L3 N
3w 2m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L
1 L2 L3 N
3w 2m
hv
I
1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L1 L2 L3 N
3w 2m
hv
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1
N
L1 L2 L3 N
2w 1m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L
1 L2 L3 N
3w 2m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L
1 L2 L3 N
3w 2m
hv
I
1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3 N
2w 2m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1
L2
L1 L2 L3
L
1 L2 L3 N
3w 2m
hv
I
1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3 N
2w 2m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1
L2
UMG 605-PRO
www.janitza.de
21
6. 6. 2 Supporting measurement, input V4 Three-conductor connection
Fig. Measurement via a current transformer in a three-
phase 4-conductor network with symmetric loading.
Fig. Measurement via a current transformer in a three-
phase 3-conductor network with symmetric loading.
Fig. Measurement via a current transformer.
L1 L2 L3
N
L4 N
4w 1m
I4
S1 S2
L1 L2 L3
L
4 N
4w 1m
I4
S1 S2
L1 L2 L3
L4 N
4w 1m
I4
S1 S2
L1 L2 L3
N
L
4 N
4w 1m
I4
S1 S2
L1 L2 L3
L
4 N
4w 1m
I4
S1 S2
L
L4 N
2w 1n
I4
S1 S2
N
C
NOTE!
If the baseline measurement (inputs V1-V3) is connected to a three-phase 3-conductor network, the supporting measurement (input V4) can no longer be used as a measurement input.
C
NOTE!
For measurement with the supporting measurement (V4), a voltage must be connected to the baseline measurement for frequency determination.
C
NOTE!
Measured voltages and measured currents must derive from the same network.
www.janitza.de
UMG 605-PRO
22
KTY83
6. 7 Temperature measurement
The device has a temperature measurement input that is designed for a maximum total burden of 4 kOhm.
Fig.42.1 Example, temperature measurement with
a KTY83.
UMG 605-PRO
Analog Input
m
CAUTION!
Transmission errors and damage to property due
to electrical faults
If the line is longer than 30 m, there is an increased probability of transmission errors and damage to the device due to atmospheric discharge.
Use a shielded cable to connect to the temperature sensor.
m
CAUTION!
Risk of injury due
to electric voltage!
Insuffi cient insulation of the operating equipment at the temperature measurement input to the mains supply circuits can cause the temperature measurement input and interfaces RS232 and RS485 to be hazardous to touch.
Ensure that there is reinforced or double insulation to the mains supply circuits!
Fig. Connecting temperature sensor to the measurement
input
c
WARNING!
Risk of injury due to electric voltage!
RS232, RS485 and the temperature measurement input are not galvanically separated from each other.
Therefore, be aware that hazardous voltages on the inputs that are not galvanically separated may have effects on the other connections.
UMG 605-PRO
www.janitza.de
23
7. Interfaces
The device has the following interfaces:
• RS232
• RS485
• Ethernet
• Profibus
All interfaces can be used simultaneously.
7. 1 Shielding
A twisted, shielded cable should be used for connections via the RS232 and RS485 interfaces.
Earth the shields of all cables that lead to the cabinet and at the cabinet entry.
Connect the screens over a generous area and in a manner that will conduct well, to a low-noise earth.
Gather the cables mechanically above the earthing clamp in order to avoid damage due to cable movements.
Use suitable cable glands to feed the cables into the cabinet, for example, armoured conduit couplings.
Fig. Shielding procedure at cabinet entry.
Cable
Strain relief
Screen braid of the cable
Earthing clamp
Noiseless ground
c
WARNING!
Risk of injury due to electric voltage!
RS232, RS485 and the temperature measurement input are not galvanically separated from each other. The Profibus and Ethernet are functionally insulated from each other and the remaining interfaces.
Therefore, be aware that hazardous voltages on the inputs that are not galvanically separated may have effects on the other connections.
www.janitza.de
UMG 605-PRO
24
7. 2 RS232
You can use an RS232 connection cable to connect the device to a PC.
The achievable distance between two devices with RS232 interfaces depends on the cable used and the baud rate.
The maximum cable length that can be connected is 30 m!
As a guideline, if the transmission rate is 9600 Baud, a distance of 15 m to 30 m should not be exceeded.
The permissible ohmic load must be greater than 3 kOhm and the capacitive load caused by the transmission line must be lower than 2500 pF.
Fig. Plug arrangement for the PC connection cables
(item no. 08 02 427).
D-sub, 9-pin,
Receptacle
Mini Combicon
5-pin
PC
Com1
Fig. Example, connecting a UMG605-PRO to a PC
via the RS232 interface.
7. 3 RS485
In the UMG605, the RS485 interface is designed as a 2-pin plug contact.
RS485 bus
A
B
A
B
B
A
Fig. RS485 interface, 2 pin plug contact
RS485 bus
A
B
B
A
Fig. RS485 interface, 2-pin plug contact with
termination resistor (item no. 52.00.008).
120Ω
UMG 605-PRO
www.janitza.de
25
7. 3. 1 Termination resistors
The cable is terminated with resistors (120 Ohm 1/4 W) at the beginning and at the end of a segment.
The UMG605-PRO does not contain any termination resistors.
Correct
Incorrect
Terminal strip in the cabinet.
Device with RS485 interface. (without termination resistor)
Device with RS485 interface. (with termination resistor on the device)
7. 3. 2 Cable type
CAT cables are not suitable for bus wiring. Instead, we recommend the following cable types:
• Unitronic Li2YCY(TP) 2x2x0.22 (from Lapp Kabel)
• Unitronic BUS L2/FIP 1x2x0.64 (from Lapp Kabel)
The maximum cable length is 1200 m at a baud rate of 38.4 k.
m
WARNING!
Risk of injury due
to electric voltage!
Temperatures of up to 80 °C can occur on the connections if there are high measured currents.
Therefore, use lines that are designed for an operating temperature of at least 80 °C
www.janitza.de
UMG 605-PRO
26
7. 4 Bus structure
• All devices are connected in a bus structure (line).
• Up to 32 participants can be connected together in a single segment.
• The cable is terminated with resistors at the beginning and at the end of a segment.
• If there are more than 32 participants, repeaters (amplifiers) must be used to connect the individual segments.
• Devices for which the bus connection is switched on must be under current.
• It is recommended that the master be placed at the end of a segment.
• If the master is replaced with a bus connection, the bus must be switched off.
• Replacing a slave with a bus connection that is either switched off or de-energised can destabilise the bus.
• Devices that are not connected to the bus can be replaced without destabilising the bus.
Fig. Bus structure illustration
SlaveSlaveSlave
Slave
Slave Slave Repeater
Slave Slave Slave Slave
Master
Speisung notwendig / power supply necessary
Busabschluß eingeschaltet / bus terminator onT
T
T
T
T
UMG 605-PRO
www.janitza.de
27
7. 5 Profi bus
The UMG 605-PRO is equipped with a Profi bus connection that is designed as a 9-pin DSUB receptacle.
For the connection, we recommend a "SUBCON-Plus-Profi B/AX/SC" 9-pin Profi bus connector from Phoenix.
You can order this from us using Janitza item number 13.10.539.
Fig. UMG605-PRO with Profi bus interface.
Fig. Profi bus connector with termination resistors.
7. 5. 1 Connection of the bus wiring
The inbound bus wiring is connected to terminals 1A and 1B.
The bus wiring for the next device in line is connected to terminals 2A and 2B.
If there are no subsequent devices in the line, the bus wiring must be terminated with a resistor (switch to ON). With the switch set to ON, terminals 2A and 2B are switched off for further continuing bus wiring.
UMG 605-PRO
Profibus connector
Termination resistors
(external)
Screw-type terminals
D-Sub,
9-pin,
Receptacle
D-Sub,
9-pin,
Receptacle
Other
Profibus
participants
www.janitza.de
UMG 605-PRO
28
UMG 605-PRO
www.janitza.de
29
8. Digital inputs and outputs
8. 1 Digital inputs
The device has 2 digital inputs to which you can connect one signal generator each.
An input signal is detected on a digital input if a voltage of at least 10 V and maximum 28 V DC is applied.
The fl owing current is at least 1 mA and a maximum of 6 mA.
Pay attention to the supply voltage's polarity!
m
CAUTION!
Transmission errors and damage to property due
to electrical faults
If the line is longer than 30 m, there is an increased probability of transmission errors and damage to the device due to atmospheric discharge.
Use a shielded cable for connection to the digital inputs.
+
-
24V
DC
Fig. Connection example of digital inputs.
Fig. Example for the connection of external switch
contacts S1 and S2 to digital inputs 1 and 2.
+
-
S2
S1
24V
=
UMG 605-PRO
Digital inputs 1-2
4.4k
19
Digital
Input 1
3.9V
3.9V
20
21
Digital
Input 2
4.4k
m
CAUTION!
Damage to property due
to connection errors
Ensure that:
• the supply voltage is DC voltage.
• the supply voltage has the right polarity.
• the height of the voltage is at least 10 V and a maximum of 28 V.
www.janitza.de
UMG 605-PRO
30
8. 2 S0 pulse input
You can also connect S0 pulse transducers per DIN EN62053-31 to each UMG 605-PRO with inputs for 24 V.
You only require external auxiliary voltage of 20 to 28V DC and an external 1.5 kOhm resistor each.
+
-
1.5k
S0 pulse transducer
24V
DC
Fig. UMG 605-PRO with inputs for 24V. Example with
S0 pulse transducer.
Fig. UMG 605-PRO with inputs for 24V and an S0 pulse
transducer on digital input 2.
S0 pulse
transducer
1.5k
+
-
UMG 605-PRO
Digital inputs 1-2
4k
19
Digital
Input 1
3.9V
3.9V
4k
20
21
Digital
Input 2
24V
=
UMG 605-PRO
www.janitza.de
31
8. 3 Digital outputs
The device has 2 transistor switching outputs that are galvanically separated from the analysis electronics using opto couplers.
The digital outputs:
• can switch DC or AC loads.
• can switch loads depending on the supply voltage's polarity.
m
CAUTION!
Transmission errors
and damage to property
due to electrical faults
If the line is longer than 30 m, there is an increased probability of transmission errors and damage to the device due to atmospheric discharge.
Use a shielded cable for connection to the digital outputs.
24V
DC
+
-
Fig. Connection example of digital outputs.
Fig. Connection of a DC voltage relay to the digital
outputs.
16
17
Digital
Output 1
UMG 605-PRO
Digital outputs
K2 K1
+
-
24V
DC
18
Digital
Output 2
Fig. Connection of an AC voltage relay to the digital
outputs.
16
17
Digital
Output 1
UMG 605-PRO
Digital outputs
K2 K1
~
24V
AC
18
Digital
Output 2
~
m
CAUTION!
Damage to property due
to connection errors
The digital outputs are not short-circuit proof! Connection errors can therefore cause damage to the connections.
Ensure that the wiring is correct when connecting the outputs.
m
CAUTION!
Measurement errors when
using as a pulse output
When using the digital outputs as pulse outputs, measurement errors may arise due to the residual ripple.
Therefore, use a mains adapter for the supply voltage for the digital inputs and outputs, which has a residual ripple of less than 5% of the supply voltage.
www.janitza.de
UMG 605-PRO
32
UMG 605-PRO
www.janitza.de
33
9. Commissioning
Before commissioning, clear any content that may be present on the power meters, min./max. values or recordings due to the production process.
9. 1 Connecting the supply voltage
After connecting the supply voltage, the text “Start up” is shown on the display. Approximately two to six seconds later, the device switches to the fi rst measured value indication.
If no display appears, check whether the power supply voltage is within the rated voltage range.
Fig.23.1 Example connection for the supply voltage Uh.
Supply voltage
(see rating plate)
9. 2 Frequency measurement
In order to measure the frequency, at least one voltage measurement path (L-N) must have a measured voltage of greater than 10 V. Only detected frequencies in the range of 15 Hz to 440 Hz are used for measurement on the current and voltage measurement inputs.
9. 3 Connecting the measured voltage
After connecting the measured voltages, the measured values displayed by the device for the L-N and L-L voltages must correspond to those on the voltage measurement input.
If a voltage transformer factor is programmed, it must be taken into consideration for the comparison. At least one phase (L) and the neutral conductor (N) must be connected to the voltage measurement input for measurement.
A measured voltage of greater than 10 Veff must be present on at least one of the voltage measurement inputs so that the device can determine the mains frequency.
L N
9. 4 Phase sequence
Check the direction of the rotating fi eld voltage in the measured value indication of the device. A “right-hand” rotation fi eld usually exists.
www.janitza.de
UMG 605-PRO
34
9. 5 Applying the measured current
The device:
• is intended for connecting current transformers with secondary currents of ../1 A and ../5 A.
• does not measure DC.
• has current measurement inputs that are continuously loaded with 6 A or loaded with 100 A for 1 second.
Proceed as follows to connect measured current to the device:
1. Connect the currents to be measured to voltage measurement inputs I1 to I4.
2. Short circuit all current transformer outputs except for one.
3. Compare the currents displayed by the device with the applied current.
• Bearing in mind the current transformer conversion ratio, the current displayed by the device must correspond to the current input.
• The device must display approx. zero amperes in the short circuited current measurement inputs.
The current transformer ratio is factory-set to 5/5A and must be adapted to the current transformer used if necessary.
9. 6 Checking the power measurement
Short-circuit all current transformer outputs except for one and check the displayed power outputs.
The device may only display one power output in the phase with a non-short­circuited current transformer input. If this is not the case, check the connection of the measured voltage and the measuring­circuit current.
If the power figure is correct but the power sign is negative, connections S1(k) and S2(l) on the current transformer may be mixed up or they are supplying active energy back to the network.
UMG 605-PRO
www.janitza.de
35
10. Operation
In order to make it easier to install and commission the device without a PC, it has a display, as well as buttons 1, 2 and the Service button.
Important parameters such as the current transformer and the device address are listed in the parameter list in section “17. Parameter list” and can be programmed directly on the device.
When operating, the device differentiates between:
• Display mode and
• Programming mode
10. 1 Button functions
Press the button for a short time:
• scroll forwards
• digit/value +1
Press the button for a long time:
• scroll backwards
• digit/value -1
Press and hold both buttons simultaneously for around 1 second:
• Switch between display mode and programming mode.
The device is operated using buttons 1 and 2.
The service button is only for use by trained service employees.
Fig. Front view of UMG 605 -PRO control element
10. 2 Display mode
After the power returns, the device is in display mode.
In display mode, you can use buttons 1 and 2 to scroll through the measured value indications.
• Use button 1 to select the phase for the measured values.
• Use button 2 to scroll between the measured values for current, voltage, power, etc.
The factory default setting for the measured value indications is shown in section “17. Parameter list”.
N L1
RxD TxD
V
L1 L2 L3 L4
Input Output
Fig. Display example for "Display mode". Measured value
indication U
L1-N
= 230.0 V.
Fig. Display example for rotation fi eld and frequency.
RxD TxD
L1 L2 L3 L4
Input Output
Hz
C
NOTE!
You can reconfi gure the functions of the buttons and the selection of the values to be displayed using the GridVis® software as a Jasic program. (see www.janitza.de)
www.janitza.de
UMG 605-PRO
36
10. 3 Programming mode
You view and change the most important settings required to operate the device in programming mode.
The addresses for the most important settings are provided in section “17. Parameter list”.
You can make further settings in the GridVis® software supplied. Pressing and holding buttons 1 and 2 simultaneously for approx. 1 second takes you to programming mode after the password prompt.
If no display password has been set up, you are taken directly to the first programming menu.
Programming mode is indicated on screen by the text "PRG". The digit in the address flashes. If you are in programming mode and no button is pressed around 60 seconds or if buttons 1 and 2 are pressed simultaneously for around 1 second, the device returns to display mode.
Fig. Display example for "Programming mode", address
000 with a content of 5,000. Fig. Request window for the display password
Address Content
PRG
10. 4 Display password
To make it harder to accidentally modify the programming data on the device, you can program a 4-character display password. No display password is factory­set. No display password is requested in the factory default setting.
10. 5 Homepage password
You can password-protect access to the device’s homepage. No homepage password is factory-set.
The device differentiates between 3 password modes for the homepage password:
• 0 = The homepage password is not requested.
• 2 = Changes to the configuration and the measured values display require the password to be entered once.
• 128 = Each change to the configuration requires the password to be entered again
C
NOTE!
If you no longer remember your password, you can only change it using the GridVis® software. (see www.janitza.de)
Content
PRG
Addr. Contents
500 Display password
0 = The password is not requested.
501 Homepage,
password mode
502 Homepage password
Fig. Excerpt from the parameter list.
UMG 605-PRO
www.janitza.de
37
11. Configuration
11. 1 Measurement
The device has 4 measurement channels for voltage measurement (V1 - V4 against Vref) and 4 measurement channels for current measurement (I1 to I4). Measured voltage and measured current for the measurement channels 1-4 must derive from the same network.
11. 1. 1 Baseline measurement (measurement channels 1-3)
The baseline measurement uses measurement channels 1-3. Use measurement channels 1-3 for measurement in three-phase systems. You can choose one of 14 measurement switches for the baseline measurement. The relevant connection illustrations are provided in section “6. 6 Connection variants”. You can use parameter address “110” to set the selected measurement switch.
Selectable measurement switches:
• 0 = 4w3m (factory default setting)
• 1 = 4w2m
• 2 = 4w2u
• 3 = 4w2i
• 4 = 3w3m
• 5 = 3w2m
• 6 = 3w2u
• 7 = 3w2i
• 8 = 2w2m
• 9 = 2w1m
• 10 = 4w3m_hv
• 11 = 4w2u_hv
• 12 = 3w2u_hv
• 13 = 3w2m_hv
Address Content
PRG
Fig. Display example; measurement switch for the baseline
measurement, address 110 with a content of 0.
11. 1. 2 Supporting measurement (measurement channel 4)
The supporting measurement only uses measurement channel 4.
Use measurement channel 4 when measuring in single-phase systems or in three-phase systems with symmetrical loads.
The frequency setting and the setting for the relevant voltage are pulled automatically from the baseline measurement settings.
You can choose one of 3 measurement switches for the supporting measurement. The relevant connection illustrations are provided on page 23.
You can use parameter address “111” to set the selected measurement switch.
Address Content
PRG
Selectable measurement switches:
• 0 = 2w1n (factory default setting)
• 1 = 3w1m
• 2 = 4w1m
Fig. Display example; measurement switch for the supporting
measurement, address 111 with a content of 0.
www.janitza.de
UMG 605-PRO
38
11. 2 Current transformer ratio
You can set the current transformer ratio for the baseline measurement using addresses 000 and 001.
You can use addresses 010 and 011 to set the current transformer ratio for the supporting measurement.
A current transformer ratio of 5 A / 5 A is factory-set for all 4 current transformer inputs in the factory.
Address Current transformer
values
Baseline measurement 000 L1 L2 L3 (primary) 001 L1 L2 L3 (secondary) Supporting measurement 010 L4 (primary) 011 L4 (secondary)
Address
Content
PRG
Fig. Example; Current transformer (primary) for the baseline
measurement, address 000 with a content of “5“.
11. 3 Voltage transformer ratio
You can use addresses 002 and 003 to set the voltage transformer ratio for the baseline measurement.
You can use addresses 012 and 013 to set the voltage transformer ratio for the supporting measurement.
A voltage transformer ratio of 400 V / 400 V is factory-set for all 4 voltage transformer inputs in the factory.
Address Current transformer
values
Baseline measurement 002 L1 L2 L3 (primary) 003 L1 L2 L3 (secondary) Supporting measurement 012 L4 (primary) 013 L4 (secondary)
Fig. Example; voltage transformer (primary) for the baseline
measurement, address 002 with a content of “400“.
Address Content
PRG
UMG 605-PRO
www.janitza.de
39
11. 4 RS232 configuration
The following data must be programmed to operate the RS232 interface:
• baud rate,
• operating mode.
For information on the factory default setting and the setting ranges, see the parameter list in the appendix.
Address Settings
201 Baud rate, RS232
0 = 9600Bit/s 1 = 19200Bit/s 2 = 38400Bit/s 3 = 57600Bit/s 4 =115200Bit/s
204 RS232. mode
0 = Modbus RTU/slave 3 = Debug 6 = SLIP (for internal use only)
Address Settings
200 Device address (1 to 255)
applies to Modbus and Profibus 1 = factory default setting
202 Baud rate, RS485
0 = 9600Bit/s 1 = 19200Bit/s 2 = 38400Bit/s 3 = 57600Bit/s 4 =115200Bit/s 5 = 921600Bit/s
203 RS485, mode
0 = Modbus RTU/slave 1 = Modbus RTU/master 2 = Gateway transparent
11. 5 RS485 configuration
The following data must be programmed to operate the RS485 interface:
• device address,
• baud rate,
• operating mode.
For information on the factory default setting and the setting ranges, see the parameter list in the appendix.
www.janitza.de
UMG 605-PRO
40
11. 6 Ethernet configuration Static IP address
In simple networks with no DHCP serv­er, the network address must be set right on the device itself.
BootP
BootP enables the device to be integrated into an existing network fully automatically. However, BootP is an older protocol and does not provide the scope of functions provided by DHCP.
DHCP mode
DHCP makes it possible integrate a UMG 604-PRO into an existing network fully automatically without the need for any additional configuration. When started, the device automatically obtains the IP address, the subnet mask and the gateway from the DHCP server. The device is factory-set to the “DHCP client”.
Zeroconf
Zeroconf enables a UMG 605PRO to be automatically integrated (IP address assignment) into an existing network without a DHCP server.
m
CAUTION!
Damage to property due to
incorrect network settings
Incorrect network settings can cause faults in the IT network.
Obtain information from your network administrator about the correct settings for your device.
Fig. Connection example, the UMG 604PRO and PC
require a static IP address.
Switch
Patch cable Patch cable
PC UMG
605PRO
Fig. Connection example, the UMG 604PRO and PC are
automatically assigned an IP address by a DHCP server.
Patch
Cable
Patch cable Patch cable
DHCP server
PC UMG
605PRO
Switch
Address Settings
205 DHCP mode
0 = static IP 1 = BootP 2 = DHCP client
3 = Zeroconf 300 IP address, xxx --- --- --­301 IP address, --- xxx --- --­302 IP address, --- --- xxx --­303 IP address, --- --- --- xxx 304 IP mask, xxx --- --- --­305 IP mask, --- xxx --- --­306 IP mask, --- --- xxx --- 307 IP mask, --- --- --- xxx 310 IP gateway, xxx --- --- --­311 IP gateway, --- xxx --- --­312 IP gateway, --- --- xxx --- 313 IP gateway, --- --- --- xxx
UMG 605-PRO
www.janitza.de
41
11. 7 Profibus configuration
11. 7. 1 Profiles
The device can manage 16 Profibus profiles, each with a maximum of 128 data bytes.
The first data byte of the PLC's output range always contains the profile number of the Profibus profile requested by the UMG.
To request a Profibus profile, write the profile number to the first byte of the PLC's output range.
All system variables and global variables
1)
can be individually scaled and converted into one of the following formats:
• 8, 16, 32 bit integer with and without sign.
• 32 or 64 bit float format.
• Big or little endian2).
1) Global variables are variables that the user defines in Jasic and are available to each interface in the UMG604 2 ) Big endian = high byte before low byte. Little endian = low byte before high byte.
11. 7. 2 Device master file
The device master file, abbreviated as the GSD file, describes the Profibus characteristics of the UMG. The GSD file is required by the configuration program of the PLC.
The device master file for your device is called “u6050c2d.GSD” and is available on the Janitza homepage.
PLC output box
1. Byte = profile number As of the 2nd byte, variables for the UMG 605PRO follow.
PLC
PLC input box
1. Byte = return signal from the profile number As of the 2nd byte, the variables requested by the UMG 605-PRO follow.
UMG 605-PRO
Fig. Block diagram for data exchange between PLC and
UMG 605-PRO.
Fig. Excerpt from the parameter list.
Address Settings
200 Device address (1 to 255)
applies to Modbus and Profibus 1 = factory default setting
www.janitza.de
UMG 605-PRO
42
11. 7. 3 Pre-set profiles
Profibus profile number 0
Byte index Value type Value format Scaling
1 1 Voltage L1-N Float 1
2 5 Voltage L2-N Float 1
3 9 Voltage L3-N Float 1
4 13 Voltage L4-N Float 1
5 17 Voltage L2-L1 Float 1
6 21 Voltage L3-L2 Float 1
7 25 Voltage L1-L3 Float 1
8 29 Current L1 Float 1
9 33 Current L2 Float 1
10 37 Current L3 Float 1
11 41 Current L4 Float 1
12 45 Active power L1 Float 1
13 49 Active power L2 Float 1
14 53 Active power L3 Float 1
15 57 Active power L4 Float 1
16 61 Cosphi (math.) L1 Float 1
17 65 Cosphi (math.) L2 Float 1
18 69 Cosphi (math.) L3 Float 1
19 73 Cosphi (math.) L4 Float 1
20 77 Frequency Float 1
21 81 Total active power L1-L4 Float 1
22 85 Total reactive power L1-L4 Float 1
23 89 Total apparent power L1-L4 Float 1
24 93 Total cosphi (math.) L1-L4 Float 1
25 97 Total effective current L1-L4 Float 1
26 101 Total active energy L1-L4 Float 1
27 105 Ind. Total reactive energy L1-L4 Float 1
28 109 THD voltage L1 Float 1
29 113 THD voltage L2 Float 1
30 117 THD voltage L3 Float 1
UMG 605-PRO
www.janitza.de
43
Profibus profile number 1
Byte index Value type Value format Scaling
1 1 Voltage L1-N Float 1
2 5 Voltage L2-N Float 1
3 9 Voltage L3-N Float 1
4 13 Voltage L2-L1 Float 1
5 17 Voltage L3-L2 Float 1
6 21 Voltage L1-L3 Float 1
7 25 Current L1 Float 1
8 29 Current L2 Float 1
9 33 Current L3 Float 1
10 37 Active power L1 Float 1
11 41 Active power L2 Float 1
12 45 Active power L3 Float 1
13 49 Cosphi (math.) L1 Float 1
14 53 Cosphi (math.) L2 Float 1
15 57 Cosphi (math.) L3 Float 1
16 61 Frequency Float 1
17 65 Total active power L1-L3 Float 1
18 69 Total reactive power L1-L3 Float 1
19 73 Total apparent power L1-L3 Float 1
20 77 Total cosphi (math.) L1-L3 Float 1
21 81 Total effective current L1-L3 Float 1
22 85 Total active energy L1-L3 Float 1
23 89 Ind. Total reactive energy L1-L3 Float 1
24 93 THD voltage L1 Float 1
25 97 THD voltage L2 Float 1
26 101 THD voltage L3 Float 1
27 105 THD current L1 Float 1
28 109 THD current L2 Float 1
29 113 THD current L3 Float 1
www.janitza.de
UMG 605-PRO
44
Profibus profile number 2
Profibus profile number 3
Byte index Value type Value format Scaling
1 1 Total active energy L1-L3 Float 1
2 5 Rel. Total active energy L1-L3 Float 1
3 9 Deliv. Total active energy L1-L3 Float 1
4 13 Total reactive energy L1-L3 Float 1
5 17 Ind. Total reactive energy L1-L3 Float 1
6 21 Total cap. reactive energy L1-L3 Float 1
7 25 Total apparent energy L1-L3 Float 1
8 29 Active energy L1 Float 1
9 33 Active energy L2 Float 1
10 37 Active energy L3 Float 1
11 41 Inductive reactive energy L1 Float 1
12 45 Inductive reactive energy L2 Float 1
13 49 Inductive reactive energy L3 Float 1
Byte index Value type Value format Scaling
1 1 Active power L1 Float 1
2 5 Active power L2 Float 1
3 9 Active power L3 Float 1
4 13 Total active power L1-L3 Float 1
5 17 Current L1 Float 1
6 21 Current L2 Float 1
7 25 Current L3 Float 1
8 29 Total current L1-L3 Float 1
9 33 Total active energy L1-L3 Float 1
10 37 CosPhi (math.) L1 Float 1
11 41 CosPhi (math.) L2 Float 1
12 45 CosPhi (math.) L3 Float 1
13 49 Total CosPhi (math.) L1-L3 Float 1
14 53 Reactive power L1 Float 1
15 53 Reactive power L2 Float 1
16 53 Reactive power L3 Float 1
17 53 Total reactive power L1-L3 Float 1
18 53 Apparent power L1 Float 1
19 53 Apparent power L2 Float 1
20 53 Apparent power L3 Float 1
21 53 Total apparent power L1-L3 Float 1
UMG 605-PRO
www.janitza.de
45
11. 8 Recording configuration
2 recordings are pre-configured in the device’s factory default setting.
Recordings are adjusted and expanded using the GridVis® software.
Recording 1
The following measured values are recorded with the time base of 15 minutes:
• Voltage effective L1
• Voltage effective L2
• Voltage effective L3
• Voltage effective L4
• Voltage effective L1-L2
• Voltage effective L2-L3
• Voltage effective L3-L1
• Current effective L1
• Current effective L2
• Current effective L3
• Current effective L4
• Active power L1
• Active power L2
• Active power L3
• Active power L4
• Total active power L1-L3
• Total active power L1-L4
• Reactive power fundamental oscillation L1
• Reactive power fundamental oscillation L2
• Reactive power fundamental oscillation L3
• Reactive power fundamental oscillation L4
• Total reactive power fundamental oscillation L1-L3
• Total reactive power fundamental oscillation L1-L4
(The mean value, minimum value, and maximum value are also recorded for each measured value.)
Recording 2
The following measured values are recorded with the time base of 1 hour:
• Active energy drawn L1
• Active energy drawn L2
• Active energy drawn L3
• Active energy drawn L4
• Total active energy drawn L1-L3
• Total active energy drawn L1-L4
• Inductive reactive energy L1
• Inductive reactive energy L2
• Inductive reactive energy L3
• Inductive reactive energy L4
• Total inductive reactive energy L1-L3
• Total inductive reactive energy L1-L4
www.janitza.de
UMG 605-PRO
46
UMG 605-PRO
www.janitza.de
47
12. System information
12. 1 Measurement range exceeded
If the measurement range is exceeded, it is displayed as long as this persists and cannot be acknowledged. The measurement range is exceeded if at least one of the four voltage or current measurement inputs is outside its specified metering range.
If the measurement range is exceeded, this is shown on the display with “EEEE”.
Symbols L1, L2, L3 and L4 are used to show the input on which the measurement range was exceeded. The "V" and "A" symbols indicate whether the measurement range has been exceeded in the current or voltage circuit.
Fig. Measured value indication for the firmware release.
RxD TxD
L1 L2 L3 L4
Input Output
12. 2 Firmware release
Fig. Measured value indication with time.
RxD TxD
L1 L2 L3 L4
Input Output
12. 3 Time
L1 L2 L3 L4
RxD TxD
VA
L1 L2 L3 L4
Input Output
Fig. Measured value indication with measurement range
exceeded.
Fig. Measured value indication with serial number.
RxD TxD
L1 L2 L3 L4
Input Output
12. 4 Serial number
Fig. Measured value indication with date.
RxD TxD
L1 L2 L3 L4
Input Output
12. 5 Date
m
CAUTION!
Damage to property
due to not observing
the connection conditions
Failure to observe the connection conditions can damage or destroy your device.
Therefore, note the following:
Adhere to the specifications for voltage and frequency on the rating plate.
www.janitza.de
UMG 605-PRO
48
UMG 605-PRO
www.janitza.de
49
13. Device homepage
Your measurement device has an integrated web server, which has a separate homepage. You can use this device home page to access your measurement device from any end device via a standard web browser. You can access the homepage for your device by entering the device’s PI address in a web browser on your end device. Section “11. 6 Ethernet configuration” explains how to connect the device to the internet.
You can do the following here without first installing any software:
• call historical and current measured values.
• call the power quality status in an easy to understand illustration.
• control your device remotely.
• access installed apps.
Fig. Device homepage overview
www.janitza.de
UMG 605-PRO
50
13. 1 Measured values
You can use the measured values menu item to call simple and detailed views of the measured values, and to display individual measured values. The following menu items are available:
• Short overview
• Detailed measured values
• Diagrams
• Events
• Transients
13. 1. 1 Short overview
The short overview provides you with the most important measured values for each phase, such as the current voltage values, power values and current strength.
Fig. Short overview of measured values
UMG 605-PRO
www.janitza.de
51
13. 1. 2 Detailed measured values
In the overview, you can call extensive information on the following points:
• Voltage
• Current
• Power
• Harmonic oscillations
• Energy
• Peripheral devices (digital inputs/outputs, temperature measurements)
Fig. Detailed overview of measured values
www.janitza.de
UMG 605-PRO
52
13. 1. 3 Diagrams
You can use the “Diagrams” item to access the measured values monitor. The measured values monitor is a configurable display of current and historical measured values with automatic scaling. In order to display a graphic of the measured values, drag the required values from the list on the left edge of the screen into the field in the middle of the screen.
13. 1. 4 Events
You can use events item to display a graphical illustration of the recorded events such as overcurrent or undervoltage by clicking the relevant event in the list.
Fig. Event records
Fig. Device homepage event records
UMG 605-PRO
www.janitza.de
53
13. 1. 5 Transients
The “Transients” area provides a graphic illustration of transients within a date list. Transient voltages:
• are fast impulse transient effects in electrical networks.
• are unpredictable from a time perspective and have a limited duration.
• are caused by lightning strikes, switching operations or by tripped fuses.
Fig. Transients
www.janitza.de
UMG 605-PRO
54
13. 2 Power quality
The “Power quality” section (PQ) provides you with the option of calling the PQ status in a clear way according to common standards. Here, you have access to permanent power quality monitoring in accordance with:
• EN 50160 in energy supply networks.
• IEC 61000-2-4 in customer supply networks.
The display is based on the traffic light principle, which makes it easy to detect events that do not meet the relevant quality requirements without in-depth knowledge.
Fig. IEC 61000-2-4 parameters with traffic-light principle
UMG 605-PRO
www.janitza.de
55
13. 3 Apps
You have the option of extending the functions on your device retrospectively by installing additional apps.
13. 3. 1 Push Service
The push service is an example of an app installed in the factory. The push service sends measured values directly from the device to a cloud or portal solution chosen by you- such as the Janitza Energy Portal
Fig. Push Service
www.janitza.de
UMG 605-PRO
56
13. 4 Information
13. 4. 1 Device information
You can use the device information menu item to obtain all information and settings that you can change on the device.
13. 4. 2 Downloads
You can use the downloads item to access the download area on the Janitza homepage. You can download catalogues and user manuals from here.
13. 4. 3 Display
The display item provides you with the display of your device, which corresponds to the real display.
You can control the device remotely here by clicking the control buttons using the mouse.
Fig. Operating the UMG 605-PRO via the device homepage
UMG 605-PRO
www.janitza.de
57
14. Service and maintenance
The device underwent various safety checks before delivery and is marked with a seal. If a device is open, the safety checks must be repeated. Warranty claims will only be accepted if the device is unopened.
14. 1 Repair and calibration
Repair work and calibration can be carried out by the manufacturer only.
14. 2 Front film
The front film can be cleaned with a soft cloth and standard household cleaning agent. Do not use acids and products containing acid for cleaning.
14. 3 Disposal
Observe the national regulations! If necessary, dispose of individual parts according to their properties and existing country-specific regulations, e.g. as:
• Electronic waste
• Plastics
• Metals or commission a certified disposal company with scrapping.
14. 4 Service
Should questions arise, which are not described in this manual, please contact the manufacturer directly. We will need the following information from you to answer any questions:
• device name (see rating plate),
• serial number (see rating plate),
• software release (see measured value
indication),
• measured voltage and supply voltage,
• precise description of the error.
14. 5 Battery
The internal clock is fed from the supply voltage.
If the supply voltage fails then the clock is powered by the battery. The clock provides date and time information, for the records, min. and max. values and events, for example.
The life expectancy of the battery is at least 5 years with a storage temperature of +45°C. The typical life expectancy of the battery is 8 to 10 years. The device must be opened to change the battery.
C
NOTE!
If the device has been opened, a new safety inspection must be carried out to ensure safe operation. Warranty claims will only be accepted if the device is unopened.
14. 6 Firmware update
In order to carry out a firmware update, connect the device to a computer via Ethernet and access it using the GridVis® software.
Open the firmware update wizard by clicking “Update device” in the “Extras” menu.
Select the relevant update file and carry out the update.
C
NOTE!
Firmware may not be updated via the RS485 interface.
www.janitza.de
UMG 605-PRO
58
UMG 605-PRO
www.janitza.de
59
15. Procedure in the event of faults
Possible fault Cause Remedy
No display External fuse for the power
supply voltage has tripped.
Replace fuses.
Device defective. Send the device to the
manufacturer for repair.
No current display Measured voltage is
not connected.
Connect the measured voltage.
Measurement current is not connected.
Connect measuring-circuit current.
Displayed current is too high or too low
Current measurement in the wrong phase.
Check connection and correct if necessary.
Current transformer factor is incorrectly programmed.
Read out and program the CT ratio on the current transformer.
Displayed voltage is too low or too high.
Measurement in the wrong phase.
Check connection and correct if necessary.
Voltage transformer incorrectly programmed.
Read out and program the voltage transformer ratio at the voltage transformer.
Voltage displayed is too low.
Measurement range exceeded. Use voltage transformers. The peak voltage value
at the measurement input has been exceeded by the harmonics.
Attention! Ensure the measurement inputs are not overloaded.
“EEEE” and “V” on the display
The voltage measurement range has been exceeded.
Check the measured voltage and install a suitable voltage transformer if necessary.
“EEEE” and “A” on the display
The current measurement range has been exceeded.
Check the measured current and install a suitable current transformer if necessary.
Table Procedure in the event of faults, part 1
www.janitza.de
UMG 605-PRO
60
Table Procedure in the event of faults, part 2
Possible fault Cause Remedy
“Error CF” on the display
The calibration data could not be read.
Send the device to the manufacturer for inspection and testing along with an accurate fault description.
Active power, consumption/supply reversed.
At least one current transformer connection is mixed up/ reversed.
Check connection and correct if necessary.
A current circuit is assigned to the wrong voltage circuit.
Check connection and correct if necessary.
Active power too high or too low.
The programmed CT ratio is incorrect.
Read out and program the CT ratio on the current transformer
The current circuit is assigned to the wrong voltage circuit.
Check connection and correct if necessary.
The programmed voltage transformer ratio is incorrect.
Read out and program the voltage transformer ratio at the voltage transformer.
No connection to the device.
RS485:
- Incorrect device address.
- Wrong protocol.
- Termination missing.
Set the device address. Select the protocol. Terminate the bus with a termination resistor (120 ohm).
Ethernet:
- Incorrect IP address
- The hidden button (Service) was pressed.
Set the IP address on the device. Describe address 204 with 0 and set the IP address or activate DHCP.
Device still does not work despite the above measures.
Device defective. Send the device to
the manufacturer for inspection, along with an accurate fault description .
UMG 605-PRO
www.janitza.de
61
16. Technical data
16. 1 General
Net weight 350 g Device dimensions Approx. l=107.5 mm, w=90 mm, h=82 mm
(per DIN 43871:1992) Housing flammability rating UL 94V-0 Installation position any Fastening/assembly 35 mm DIN rail
(per IEC/EN60999-1, DIN EN 50022) Battery Type Lithium CR2032, 3 V
16. 2 Environmental conditions
The device is intended for weatherproof, fixed installation and meets the operational conditions in accordance with DIN IEC 60721-3-3.
Working temperature range -10 °C to +55 °C Relative humidity 5 to 95% RH, (at +25 °C) without condensation Pollution degree 2 Operating altitude 0 to 2000 m above sea level Installation position any Ventilation Forced ventilation is not required.
16. 3 Transport and storage
The following information applies to devices which are transported or stored in the original packaging.
Free fall 1 m Temperature -20 °C to +70 °C
www.janitza.de
UMG 605-PRO
62
16. 4 Supply voltage
The supply voltage must be connected through a UL/IEC approved fuse (6A char. B) to the device.
230 V option:
• Nominal range
• Operating range
• Power consumption
• Overvoltage category
95 V to 240 V (50/60Hz) / DC 135 V to 340 V +-10% of nominal range max. 3.2 W / 9 VA 300 V CATII
90 V option (without UL approval):
• Nominal range
• Operating range
• Power consumption
• Overvoltage category
50 V to 110 V (50/60 Hz) / DC 50 V to 155 V +-10% of nominal range max. 3.2 W / 9 VA 300 V CATII
24V option:
• Nominal range
• Operating range
• Power consumption
• Overvoltage category
20 V to 50 V (50/60 Hz) / DC 20 V to 70 V +-10% of nominal range max. 5 W / 8 VA 150 V CATII
Terminal connection capacity (supply voltage)
Connectable conductors. Only one conductor can be connected per terminal! Single core, multi-core, fine-stranded 0.08 - 2.5 mm
2
, AWG 28 - 12
Terminal pins, core end sheath 1.5 mm
2
, AWG 16
16. 5 Protection class
Protection class II in accordance with IEC 60536 (VDE 0106, part 1), i.e. a ground wire connection is not required!
Protection against ingress of solid foreign bodies and water
IP20 in accordance with EN60529 September 2014, IEC60529:2013
UMG 605-PRO
www.janitza.de
63
16. 6 Digital inputs and outputs
Digital outputs
2 digital outputs; semiconductor relays, not short-circuit proof Switching voltage max. 60 V DC, 30 V AC Switching current max. 50 mAeff AC/DC Response time (Jasic program) 200 ms Output of voltage dips 20 ms Output of voltage exceedance events 20 ms Switching frequency max. 20 Hz Cable length up to 30 m unshielded;
from 30 m shielded
Digital inputs
(Pulse input S0) Maximum counter frequency 20 Hz Switching input Input signal present 18 V to 28 V DC (typical 4 mA) Input signal not present 0 to 5 V DC, current less than 0.5 mA Response time (Jasic program) 200 ms Cable length up to 30 m unshielded, from 30 m shielded
Connectable conductors
Single core, multi-core, fine-stranded 0.08 - 1.5 mm
2
Terminal pins, core end sheath 1 mm2 Only one conductor can be connected
per terminal!
www.janitza.de
UMG 605-PRO
64
16. 7 Temperature measurement input
Temperature measurement input
Update time approx. 200 ms Connectable sensors PT100, PT1000, KTY83, KTY84 Total burden (sensor + cable) max. 4 kOhm Cable length up to 30 m unshielded, from 30 m shielded
Sensor type Temperature range Resistor range Measurement
uncertainty
KTY83 -55 °C to +175 °C 500 Ohm to 2.6 kOhm ± 1.5% rng
1)
KTY84 -40 °C to +300 °C 350 Ohm to 2.6 kOhm ± 1.5% rng
1)
PT100 -99 °C to +500 °C 60 Ohm to 180 Ohm ± 1.5% rng
1)
PT1000 -99 °C to +500 °C 600 Ohm to 1.8 kOhm ± 1.5% rng
1)
Connectable conductors
Single core, multi-core, fine-stranded 0.08 - 1.5mm
2
Terminal pins, core end sheath 1 mm2 Only one conductor can be connected
per terminal!
1)
rng = metering range
UMG 605-PRO
www.janitza.de
65
16. 8 Interfaces
RS232 interface
Connection 5-pin screw-type terminals Protocol Modbus RTU/slave Transmission rate 9.6 kbps, 19.2 kbps, 38.4 kbps, 57.6 kbps,
115.2 kbps
Profibus interface
Connection SUB D 9-pin Protocol Profibus DP/V0 per EN 50170 Transmission rate 9.6 kBaud to 12 MBaud
Ethernet interface
Connection RJ45 Function Modbus gateway, embedded web server
(HTTP)
Protocols TCP/IP, EMAIL (SMTP), DHCP client (BootP),
Modbus/TCP(port 502), ICMP (ping), NTP, TFTP, Modbus RTU over Ethernet (port
8000), FTP SNMP.
RS485 interface
Connection 2-pin screw-type terminals Protocol Modbus RTU/slave, Modbus RTU/master Transmission rate 9.6 kbps, 19.2 kbps, 38.4 kbps, 57.6 kbps,
115.2 kbps, 921.6 kbps
www.janitza.de
UMG 605-PRO
66
16. 9 Voltage measurement inputs
Three-phase 4-conductor systems (L-N/L-L) max. 277 V / 480 V Three-phase 3-conductor systems (L-L) max. 480 V Resolution 0.01 V Crest factor 2 (related to 480 Vrms) Overvoltage category 300 V CAT III Measurement surge voltage 4 kV Protection of voltage measurement 1 - 10 A Impedance 4 MOhm / phase Power consumption approx. 0.1 VA Sampling rate 20 kHz / phase Transients > 50 µs Frequency of the fundamental oscillation 15 Hz to 440 Hz
- Resolution 0.001 Hz
Rated current 5 A Rated current 6 A Protection when measuring directly
(without a current transformer)
6 A, char. B (approved i.a.w. UL/IEC)
Resolution on the display 10 mA Crest factor 2 (related to 6 Amps) Overvoltage category 300 V CAT III Measurement surge voltage 4 kV Power consumption approx. 0.2 VA (Ri = 5 mOhm) Overload for 1 sec. 100 A (sinusoidal) Sampling rate 20 kHz
16. 10 Current measurement inputs
Terminal connection capacity (current measurement and voltage measurement)
Connectable conductors. Only one conductor can be connected per terminal! Single core, multi-core, fine-stranded 0.08 - 4 mm
2
, AWG 28 - 12
Terminal pins, core end sheath 2.5 mm
2
, AWG 14
UMG 605-PRO
www.janitza.de
67
Function Symbol Precision class Metering range Display range
Total active power P 0.5
5)
(IEC61557-12) 0 to 15.3kW 0 W to 9999 GW
Total reactive power QA
6)
, Qv 6)0.55) (IEC61557-12) 0 to 15.3 kvar 0 varh .. 9999 Gvar
Total apparent power SA, Sv
6)
0.5
5)
(IEC61557-12) 0 to 15.3 kVA 0 VA to 9999 GVA
Total active energy Ea 0.5S
5) 7)
(IEC61557-12) 0 to 15.3 kWh 0 Wh to 9999 GWh
Total reactive energy ErA
6)
, ErV 6)15) (IEC61557-12) 0 to 15.3 kvarh 0 varh .. 9999 Gvarh
Total apparent energy EapA,EapV
6)
0.5
5)
(IEC61557-12) 0 to 15.3 kVAh 0 VAh to 9999 GVAh Frequency f 0.05 (IEC61557-12) 40 to 70 Hz 40 Hz to 70 Hz Phase current I 0.25
8)
(IEC61557-12) 0.001 to 8.5
Amps
0 A to 9999 kA
Measured neutral conductor current
IN 0.25
8)
(IEC61557-12) 0.001 to 8.5
Amps
0 A to 9999 kA
Computed neutral conductor current
INc 1 (IEC61557-12) 0.001 to 25.5 A 0 A to 9999 kA
Voltage U L-N 0.2 (IEC61557-12) 10 to 600 Vrms 0 V to 9999 kV Voltage U L-L 0.2 (IEC61557-12) 18 to 1000 Vrms 0 V to 9999 kV Power factor PFA, PFV 0.5 (IEC61557-12) 0.00 to 1.00 0 to 1 Short-term flicker,
long-term flicker
Pst, Plt Cl. A (IEC61000-4-15) 0.4 Pst to 10.0 Pst 0 to 10
Voltage dips Udip 0.2 (IEC61557-12) 10 to 600 Vrms 0 V to 9999 kV Voltage increases Uswl 0.2 (IEC61557-12) 10 to 600 Vrms 0 V to 9999 kV Transient
overvoltages
Utr 0.2 (IEC61557-12) 10 to 600 Vrms 0 V to 9999 kV
Voltage interruptions Uint Duration +- 1 cycle - ­Voltage unbalance
1)
Unba 0.2 (IEC61557-12) 10 to 600 Vrms 0 V to 9999 kV
Voltage unbalance
2)
Unb 0.2 (IEC61557-12) 10 to 600 Vrms 0 V to 9999 kV Voltage harmonics Uh Cl. 1 (IEC61000-4-7) Up to 2.5 kHz 0 V to 9999 kV THD of the voltage
3)
THDu 1.0 (IEC61557-12) Up to 2.5 kHz 0% to 999 % THD of the voltage
4)
THD-Ru 1.0 (IEC61557-12) Up to 2.5 kHz 0% to 999 % Current harmonics Ih Cl. 1 (IEC61000-4-7) Up to 2.5 kHz 0 A to 9999 kA THD of the current
3)
THDi 1.0 (IEC61557-12) Up to 2.5 kHz 0% to 999 % THD of the current
4)
THD-Ri 1.0 (IEC61557-12) Up to 2.5 kHz 0% to 999 % Mains signal voltage
(interharmonics voltage)
MSV IEC 61000-4-7
Class 1
10% – 200% of IEC 61000-2-4 class 3
0 V to 9999 kV
16. 11 Function parameters
16. 11. 1 Measurement in the frequency range 50/60 Hz
Measurement via current transformer ../5 A
www.janitza.de
UMG 605-PRO
68
16. 11. 2 Measurement in the frequency range of 15 to 440 Hz
Measurement via current transformer ../5 A
Function Symbol Precision class Metering range Display range
Total active power P 1
5)
(IEC61557-12) 0 to 15.3kW 0 W to 9999 GW
Total reactive power QA
6)
, Qv
6)
15) (IEC61557-12) 0 to 15.3 kvar 0 varh .. 9999 Gvar
Total apparent power SA, Sv6) 15) (IEC61557-12) 0 to 15.3 kVA 0 VA to 9999 GVA
Total active energy Ea 1
5)
(IEC61557-12) 0 to 15.3 kWh 0 Wh to 9999 GWh
Total reactive energy ErA6), ErV
6)
25) (IEC61557-12) 0 to 15.3 kvarh 0 varh .. 9999 Gvarh
Total apparent energy EapA, EapV
6)15)
(IEC61557-12) 0 to 15.3 kVAh 0 VAh to 9999 GVAh
Frequency f 0.05 (IEC61557-12) 15 to 440 Hz 15 Hz to 440 Hz
Phase current I 0.5 (IEC61557-12) 0.001 to 8.5 Amps 0 A to 9999 kA
Measured neutral conductor current
IN 0.5 (IEC61557-12) 0.001 to 8.5
Amps
0 A to 9999 kA
Computed neutral conductor current
INc 1.5 (IEC61557-12) 0.001 to 25.5 A 0 A to 9999 kA
Voltage U L-N 0.5 (IEC61557-12) 10 to 600 Vrms 0 V to 9999 kV
Voltage U L-L 0.5 (IEC61557-12) 18 to 1000 Vrms 0 V to 9999 kV Power factor PFA, PFV 2 (IEC61557-12) 0.00 to 1.00 0 to 1
Short-term flicker, long­term flicker
Pst, Plt - - -
Voltage dips Udip 0.5 (IEC61557-12) 10 to 600 Vrms 0 V to 9999 kV
Voltage increases Uswl 0.5 (IEC61557-12) 10 to 600 Vrms 0 V to 9999 kV
Transient overvoltages Utr 0.5 (IEC61557-12) 10 to 600 Vrms 0 V to 9999 kV
Voltage interruptions Uint Duration +- 1 cycle - -
Voltage unbalance
1)
Unba 0.5 (IEC61557-12) 10 to 600 Vrms 0 V to 9999 kV
Voltage unbalance
2)
Unb 0.5 (IEC61557-12) 10 to 600 Vrms 0 V to 9999 kV
Voltage harmonics Uh Cl. 2
(IEC61000-4-7)
Up to 2.5 kHz 0 V to 9999 kV
THD of the voltage
3)
THDu 2.0 (IEC61557-12) Up to 2.5 kHz 0% to 999 %
Declarations
1) In relation to the amplitude.
2) In relation to phase and amplitude.
3) In relation to fundamental oscillation.
4) In relation to effective value.
5) The precision class deteriorates by one level for measurements using a ../1A converter.
6) Calculation from fundamental oscillation.
7) Precision class 0.5S per IEC62053-22
8) In accordance with standard IEC61557-12
UMG 605-PRO
www.janitza.de
69
16. 12 Specifications per IEC 61000-4-30 class S
Characteristic Uncertainty Metering range
5.1 Frequency ± 50 mHz 42.5 Hz – 57.5 Hz, 51 Hz – 69 Hz
5.2 Supply voltage level ± 0.5% of Udin 20% – 120% of Udin
5.3 Flicker ± 5% of measured value 0.4 – 4.0 Pst
5.4 Drops and excessive
increases
Amplitude: ± 1% of Udin Duration: ± 1 period
N/A
5.5 Voltage interruptions Duration: ± 1 period N/A
5.7 Unbalance ± 0,3% 1% – 5% u2 1% – 5% u0
5.8 Harmonics IEC 61000-4-7 class 2 10% – 100% of IEC 61000-2-4 class 3
5.9 Interharmonics IEC 61000-4-7 class 2 10% – 200% of IEC 61000-2-4 class 3
5.10 Mains signal voltage In the range 3%-15% of
Udin, ± 5% of Udin.
3% – 15% of Udin
5.12 Downward/upward
deviation
± 0.5% of Udin 10% – 150% of Udin
The UMG 605-PRO meets the requirements according to IEC 61000-4-30 class S for:
• compensation
• time uncertainty
• marking concept
• transient influence quantities
www.janitza.de
UMG 605-PRO
70
UMG 605-PRO
www.janitza.de
71
17. Parameter list
Address Designation Setting range Unit Default
000
Current transformer, primary, L1 to L4
0 to 1000000 A 5
001 Current transformer, secondary,
L1 to L4
1 to 5 A 5
002
Voltage transformer, primary, L1 to L4
0 to 1000000 V 400
003 Voltage transformer, secondary,
L1 to L4
1 to 480 V 400
010 Current transformer, primary, L1 0 to 1000000 A 5 011 Current transformer, secondary, L1 1 to 5 A 5 012 Voltage transformer, primary, L1 0 to 1000000 V 400 013 Voltage transformer, secondary, L4 1 to 480 V 400
Table Parameter list for measurement settings
www.janitza.de
UMG 605-PRO
72
Address Designation Setting range Unit Default
100 Collect TFTP configuration file
automatically 0 = deactivated x = file number
0 to 9999 - 0
101 TFTP error handling
0 = in the event of an error, the configuration menu is shown on the display. 1 = TFTP error handling in the device is deactivated
0 to 1 - 0
110 Measurement switch for baseline
measurement (L1 to L3) 0=4w3m, 1=4w2m, 2=4w2u, 3=4w2i, 4=3w3m, 5=3w2m, 6=3w2u, 7=3w2i, 8=2w2m, 9=2w1m, 10=4w3mhv, 11=4w2uhv,12=3w2uhv, 13=3w2mhv
0 to 13 - 0
111 Measurement switch for
supporting measurement (L4) 0=2w1n, 1=3w1m, 2=4w1m
0 to 2 - 0
112 Relevant voltage
0 = L-N, 1 = L-L
0 to 9 - 0
113 Deletes all active energy
counters and S0 counters (1 = delete)
0 to 1 - 0
114 Deletes all reactive energy
counters (1 = reset)
0 to 1 - 0
115 Resets all min. and max. values
(1=delete)
0 to 1 - 0
116 Flicker filters
0 - 50 Hz / 230 V, 1 - 120 V / 50 Hz 2 - 230 V 60 Hz, 3 - 120 V/ 60 Hz
0 to 3 - 0
Table Parameter list for measurement settings
UMG 605-PRO
www.janitza.de
73
Address Designation Setting range Unit Default
200 Device address, Modbus/Profibus 1 to 255 - 1 201 Baud rate, RS232
0 = 9600Bit/s 1 = 19200Bit/s 2 = 38400Bit/s 3 = 57600Bit/s 4 =115200Bit/s
0 to 4 - 4
202 Baud rate, RS485
0 = 9600Bit/s 1 = 19200Bit/s 2 = 38400Bit/s 3 = 57600Bit/s 4 =115200Bit/s 5 = 921600Bit/s
0 to 5 - 4
203 RS485, mode
0 = Modbus RTU/slave 1 = Modbus RTU/master 2 = Gateway transparent 3,4 = internal use
0 to 6 - 0
204 RS232, mode 0 to 6 0
0 = Modbus RTU/slave 3 = Debug 6 = SLIP (for internal use only)
0 to 6 - 0
Address Designation Setting range Unit Default
205 DHCP mode
0 = static IP 1 = BootP 2 = DHCP client 3 = Zeroconf
0 to 3 - 2
300 IP address, xxx --- --- --- 0 to 255 - 000 301 IP address, --- xxx --- --- 0 to 255 - 000 302 IP address, --- --- xxx --- 0 to 255 - 000 303 IP address, --- --- --- xxx 0 to 255 - 000 304 IP mask, xxx --- --- --- 0 to 255 - 000 305 IP mask, --- xxx --- --- 0 to 255 - 000 306 IP mask, --- --- xxx --- 0 to 255 - 000
307 IP mask, --- --- --- xxx 0 to 255 - 000
310 IP gateway, xxx --- --- --- 0 to 255 - 000
311 IP gateway, --- xxx --- --- 0 to 255 - 000
312 IP gateway, --- --- xxx --- 0 to 255 - 000
313 IP gateway, --- --- --- xxx 0 to 255 - 000
Table Parameter list for bus settings
Table Parameter list for Ethernet settings
www.janitza.de
UMG 605-PRO
74
Address Designation Setting range Unit Default
400 Day 1 to 31 - xx 401 Month 1 to 12 - xx 402 Year 1 to 9999 - xxxx 403 Hour 0 to 23 - xx 404 Minute 0 to 59 - xx 405 Second 0 to 59 - xx 406 Copy date and time
1 = copy set data
0, 1 - 0
500 Device password 0 to 9999 - xxxx
501 Homepage, password mode 0, 2, 128, 130 - 0
502 Homepage, password 0 to 9999 - xxxx
510 Enabling “EMAX” option, licence
part 1
0 to 9999 - xxxx
511 Enabling “EMAX” option, licence
part 2
0 to 9999 - xxxx
520 Enabling “BACnet” option,
licence part 1
0 to 9999 - xxxx
521 Enabling “BACnet” option,
licence part 2
0 to 9999 - xxxx
600 LCD, contrast 0 to 99 - 50 601 LCD, backlight, max. brightness 0 to 16 - 10 602 LCD, backlight, min. brightness 0 to 8 - 3 603 LCD, backlight, time until
switching from maximum to minimum brightness.
0 to 9999 s 60
Table Parameter list for other settings
UMG 605-PRO
www.janitza.de
75
18. Measured value indications
You can use buttons 1 and 2 on the display to display the following measured values in the factory default setting. The measured value designations used are abbreviated and have the following meanings:
• Active power = active power, consumption
• Reactive power= reactive power, inductive
• Active energy = active energy, consumption with backstop
Active energy
L1
Active energy
L4
Active energy
L3
Active energy
L2
Active energy
L1 to L4
Active energy
L1 to L3
cos(phi)
L4
cos(phi)
L1
cos(phi)
L3
cos(phi)
L2
cos(phi)
L1 to L3
Voltage
L1-N
Voltage
L2-N
Voltage
L4-N
Voltage
L3-N
Current
L2
Current
L1
Current
L4
Current
L3
Voltage
L1-L2
Voltage
L3-L1
Voltage
L2-L3
Active power
L1 to L3
Active powerL1Active powerL2Active powerL3Active power
L4
Active power
L1 to L4
Reactive power
L1
Reactive power
L4
Reactive power
L3
Reactive power
L2
Reactive power
L1 to L3
Reactive power
L1 to L4
Frequency
Rotation field
Serial
number
Date Time
Thermistor
input
Firmware
release
www.janitza.de
UMG 605-PRO
76
UMG 605-PRO
www.janitza.de
77
19. Dimension diagrams
19. 1 Front view
Fig. Front view of UMG 605-PRO with installation dimensions
www.janitza.de
UMG 605-PRO
78
19. 2 Side view
Fig. Schematic side view of UMG 605-PRO with installation dimensions
UMG 605-PRO
www.janitza.de
79
20. Connection example
L1
L2
L3
N
PE
S1
S2
S1
S2
S1 S2
S1
S2
Strommessung
Current measurement
I
1
1 2 3 4 5 6 7 8
I2 I3 I4
9 10 11 12
Spannungsmessung
Voltage measurement L
1 L2 L3 L4
N
13
Versorgungs-
spannung
Auxiliary Supply
Dig. I/ORS485RS232An. In
Option Option
RS485 Ethernet
Verbraucher
Consumer
Power Analyser
UMG 605-PRO
Fig. Connection example for UMG 605-PRO
www.janitza.de
UMG 605-PRO
80
UMG 605-PRO
www.janitza.de
81
21. Short introduction (setting primary current)
You have three identical current transformers with a current transformer ratio of 200 A / 5 A. You want to program the primary current of 200 A. To do this, you must enter the value 200 for the primary current in address 000. The secondary current is factory-set to 5 A in address 001.
1. Switch to programming mode by pressing buttons 1 and 2 simultaneously for approximately one second.
• The symbol for programming mode PRG appears.
• The contents of address 000 are displayed.
2. Enter the primary current by using button 1 to select the number to be changed and button 2 to change the selected number.
3. Exit programming mode by pressing buttons 1 and 2 simultaneously again for approximately one second.
• The current transformer setting is saved.
• The device returns to display mode.
Address Content
PRG
Address Content
PRG
Fig. UMG 605-PRO display in programming mode
Fig. UMG 605-PRO display in programming mode
www.janitza.de
UMG 605-PRO
82
Loading...