janitza UMG 605 Operating Manual

Doc No. 1.038.006.y
Power Quality Analyser
UMG 605
Operating manual and technical data
Product No. 33.03.085
Janitza electronics GmbH Vor dem Polstück 1 D-35633 Lahnau Support Tel. 0049 6441 9642-22 Fax 0049 6441 9642-30 e-mail: info@janitza.com Internet: http://www.janitza.com
www.janitza.com
Profibus
Ethernet
Power supply voltage
Temperature measurement input
4 x current
measurement
4 x voltage
measurement
RS232 RS485 2 digital inputs
2 digital outputs
A B
2
UMG 605
General Information 4 Inspection on receipt 6
Scope of supply 7 Available accessories 7 Notes on Use 8
Product Description 10
Intended use 10 UMG605 features 11 Operating concept 12 GridVis programming software 13 Methods of measurement 14 Three-phase 4-wire systems 15 Three-phase 3-wire systems 16
Installation 18
Installed position 18 Power supply voltage 19 Voltage measurement 20 Frequency measurement 27 Current measurement 28 Direct measurement 32 Interfaces 34 RS485 36 RS485 profibus DP V0 slave 38 Digital inputs and outputs 40 Temperature measurement input 44
Operation 46
Key functions 46 Concealed key (service) 46 Display mode 47 Programming mode 48 Display password 49 Homepage password 49 Measurements 50 Voltage transformer ratio 52 Current transformer ratio 53 Interfaces 54 RS232 54 RS485 54 Ethernet 55 Profibus 56 Recordings 57
Putting into Service 58
Applying the power supply voltage 58 Frequency measurement 58 Applying the measuring-circuit voltage 59 Phase sequence 60 Applying the measuring-circuit current 60 Checking the energy measurement 61
3
UMG 605
System information 62
Overrange 62 Serial number 63 Date 63 Firmware release 63 Time 63
Service and maintenance 64
Repair and calibration 64 Front film 64 Battery 64 Firmware update 65 Service 65 Trouble shooting 66
Technical specifications 70
General information 70 Ambient conditions during operation 70 Transport and storage 70 Power supply voltage 71 Protection class 72 Inputs and outputs 73 Temperature measurement input 74 Interfaces 75 Function parameters 76 Measuring inputs 80 Voltage measurement 80
Appendix 82
Parameter list 82 Measured value displays 87 Declaration of conformity 88 Dimensioned drawings 90 UMG605 connection example 91
Quick Reference Instructions 92
4
UMG 605
General Information
Copyright
This manual is subject to the statutory co­pyright protection provisions and may not be photocopied, reprinted, reproduced as a whole or in parts, by mechanical or electronic means, nor copied or further published in any other way whatsoever without the legally bin­ding, written consent of Janitza electronics GmbH, Vor dem Polstück 1, D 35633 Lahnau, Germany.
Protected trademarks
All trademarks and their resulting rights be­long to the respective holders of these rights.
Liability disclaimer
Janitza electronics GmbH does not accept any responsibility whatsoever for errors or deficiencies within this manual and does not undertake any obligation to keep the content of this manual up to date.
Comments on the manual
We welcome your comments. If anything in this manual seems unclear to you, please let us know by sending an eMail to:
info@janitza.de
5
UMG 605
m
c
Meaning of the symbols used
The following pictograms are used in this ma­nual:
Dangerous voltage!
Danger or risk of severe injury. Disconnect the system and device from the power supply before starting the work.
Important!
Please note and follow the documentation. This symbol is intended to warn you of possib­le hazards that can occur during installation, starting up and use.
C
Note.
6
UMG 605
m
m
m
Inspection on receipt
Fault free and safe use of this device requires appropriate transport, proper storage, erection and assembly as well as careful operation and maintenance. If it can be assumed that safe operation is no longer possible, the device must be immediately taken out of service and secured against being accidentally started up. The device must be unpacked and packed with the usual care, without the use of force and only using suitable tools. The devices must be visually inspected for perfect mechanical condition. Please also note and follow the installation instructions enclosed with the device. It can be assumed that safe operation is no longer possible if the device, e.g.
• has visible damage,
• no longer works, despite intact mains power supply,
• has been exposed to unfavourable conditions (e.g. storage outside the permissible climatic limits without adjustment to the ambient climate, condensation, or similar) for a lengthy period or was exposed to unfavourable effects or loads during transport (e.g. fall from a large height even if there is no visible external damage, or similar).
Please check the scope of supply for completeness before you start installing the device.
All supplied options and design versions are described on the delivery note.
The installation and start-up instruc­tions also describe options which do not belong to the scope of supply.
All screw-type terminals belonging to the scope of supply are plugged into the device.
7
UMG 605
Product No. Name
21 01 102 Battery, lithium CR2032, 3 V 08 02 427 RS232, Connection cable (UMG 605 – PC), 2m, 5 poles
1)
Refer to delivery note for product number.
2)
Design version.
Scope of supply
Number Product No. Name
1 52 16 xxx1) UMG605 XX
2)
1 33 03 085 Installation and start-up instructions. 1 51 00 116 CD with the following content:
- “GridVis” programming software,
- Functional descriptions, GridVis, UMG605 ..
- GSD file “u6050c2d.GSD” for profibus DP V0 1 10 01 807 Screw-type terminal, plug-in, 2 pin. 1 10 01 808 Screw-type terminal, plug-in, 3 pin. 1 10 01 809 Screw-type terminal, plug-in, 5 pin. 1 10 01 810 Screw-type terminal, plug-in, 6 pin. 1 89 10 051 Slot-head screwdriver (0.40x2 mm), ESD 1 08 01 505 Patch cable, 2m, twisted, grey (UMG605 - PC/switch connection). 1 52 00 008 RS485, external terminating resistor, 120 ohm
Available accessories
8
UMG 605
Notes on Use
Please read these operating instructions and all other publications which have to be used to work with this product (in particular for installation, operation or maintenance).
Note and follow all safety instructions as well as any warnings. If you do not follow the instructions, personal injuries and/or damage to the product could be the result.
Any unauthorised change or use of this device which extends beyond the given mechanical, electrical or other operating limits can cause personal injuries and/or damage to the product.
Any such unauthorised change is “misuse” and/or “negligence” under the product's warranty and therefore excludes the warranty for cover of possible resulting injuries or damage.
This device may be solely operated and maintained by skilled persons.
Skilled persons are people who, on the basis of their relevant training and experience, are capable of identifying risks and avoiding possible hazards which operation or maintenance of the device can cause.
When using the device, any additional legal and safety regulations required for the respective use must be observed.
9
UMG 605
m
c
m
Important! If the device is not operated according to the instruction manual, protection is no longer ensured and the device can cause hazards.
Conductors made of individual wires must be fitted with wire end ferrules.
Only pluggable screw terminals with the same number of poles (pins) and of the same type may be plugged together.
10
UMG 605
Intended use
The UMG605 is intended to be used for the measurement and calculation of electrical variables such as voltage, current, energy, work, harmonic components, etc. in building installations, at distribution boards, circuit­breakers and busbar trunking systems. Measuring-circuit voltages and currents must originate from the same system.
The UMG605 is permanently installed in control cabinets or small distribution boards. It can be installed in any position.
The measurement results can be displayed, stored and read out via serial interfaces and further processed.
The voltage measurement inputs are designed for measurements in low-voltage systems in which rated voltages up to 300 V conductor to earth and surge voltages of overvoltage category III can occur. The current measurement inputs of the UMG605 are connected via external ../1A or ../5A current transformers.
Mains failure detection
The mains failure detection takes place via the voltage measurement inputs. The selection of voltage measurement inputs can be configured using the GridVis software.
Mains failure stored energy time
The UMG605 bridges the following mains failures at the auxiliary voltage input:
Mains voltage Stored energy time 230V AC max 80ms
Measurement in medium and high-voltage systems takes place with current and voltage transformers. Special safety requirements must be complied, which are not dealt with in any greater detail here.
The UMG605 fulfils the test requirements for use in industrial areas.
Product Description
11
UMG 605
UMG605 features
- Measurement in IT, TT and TN systems,
- 4 voltage measurement inputs, - 4 current measurement inputs,
- Continuous scanning of the voltage and current measurement inputs,
- Measurement of power quality according to DIN EN61000-4-30:2009 class S,
- Flicker meter according to DIN EN61000-4-15:2011 class F3,
- Analysis and evaulation acoording to DIN EN50160 with software GridVis, which belongs to the contents of delivery,
- Measurement of harmonics and interharmonics (Uln, Ull, I) according to DIN EN61000-4-7,
- Measurement of audio remote frequence (U, I, P, Q),
- Detection of transients >50µs and storage with up to 16000 scanning points
- Detection of more than 2400 measurement values,
- Fourier analysis 1st to 63th harmonic component for U, I, P (cons./supply) and Q (ind./cap.),
- Detection of events such us overvoltage, voltage drop, power failure and overcurrent,
- Datalogger / event memory (128MB Flashdisk),
- Real energy; DIN EN62053-22, accuracy class 0,5S with ../5A converter.
- Reactive energy; DIN EN62053-23, accuracy class 2r.
- 2 digital inputs, 2 digital outputs, temperature measurement input,
- LC display, 2 keys,
- Operating temperature range -10°C .. +55°C,
- Mounting on top hat rails 35 mm. Suitable for installation in distribution systems.
- Serial interfaces Profibus DPV0, RS485; modbus RTU, modbus master, BACnet (option), RS232; modbus slave, Ethernet; web server, EMAIL, BACnet (option),
- Programming own applications in Jasic,
12
UMG 605
Operating concept
You can program the UMG605 and call up measured values in several ways.
• Directly at the device using 2 keys and the display. You can change the values in the parameter list (see Appendix) and call up the measured values from the measured value displays.
• Via the GridVis programming software.
• In devices with an ethernet interface, via the homepage of the UMG605.
• Via the RS485 with the modbus protocol. You can change and call up data with the help of the modbus address list (is filed on the enclosed data carrier).
Operation of the UMG605 via the integrated display and the two keys only is described in these operating instructions. The GridVis programming software and the homepage have their own “online help”.
Use the parameter list in the appendix to these instructions for programming at the UMG605 and the modbus address list on the data carrier included in the scope of supply for programming via a serial interface.
C
13
UMG 605
PC
UMG
605
Ethernet
PC
UMG
605
RS232
RS485
PC
UMG
605
RS232
GridVis programming software
The UMG605 can be programmed and read out using the GridVis® programming software included in the scope of supply. This requires a PC to be connected to the UMG605 via a serial interface/ethernet.
GridVis features
• Programming the UMG605.
• Configuring recordings.
• Analyse der ausgelesenen Daten nach EN 61000-2-4.
• Reading out recordings.
• Storing data in a database.
• Graphic display of measured values.
• Programming customer-specific applica­tions.
Fig. Connection of a UMG605 to a PC via an interface converter.
Interface
converter
Fig. Connection of a UMG605 to a PC via the ethernet.
Fig. Connection of a UMG605 to a PC via an RS232 cable.
14
UMG 605
Methods of measurement
The UMG605 measures continuously and calculates all effective values over a 200 ms interval. The UMG605 measures the real effective va­lue (TRMS) of the voltages and currents ap­plied to the measurement inputs.
15
UMG 605
Fig. Block diagram, UMG605 in TN system.
Three-phase 4-wire systems
The UMG605 can be used in three-phase 4 conductor systems (TN, TT system) (50 Hz, 60 Hz) with earthed PEN conductor. The bodies of the electrical system are earthed. The conductor to neutral conductor voltage may not exceed 300 V AC.
The UMG605 is only suitable for environments in which the impulse voltage withstand level of 4 kV (overvoltage category III) is not exceeded.
Fig. Table of rated voltages of the grid suitable for the voltage inputs.
U
L-N
/ U
L-L
66 V / 115 V 120 V / 208 V 127 V / 220 V 220 V / 380 V 230 V / 400 V 240 V / 415 V 260 V / 440 V 277 V / 480 V
Maximum rated voltage
of the grid
UMG605
DC
AC/DC
PE
230/400V 50/60Hz
L2
L3
N
L1
4M
4M
4M
4M
L1 L3L2 N
4M
L4
Earthing the
system
Auxiliary power
Voltage measurement
16
UMG 605
Three-phase 3-wire systems
The UMG605 can be used in unearthed three-phase 3 wire systems (IT system). The conductor to conductor voltage may not exceed 480V AC (50 Hz, 60 Hz). The UMG605 is only suitable for environments in which the impulse voltage withstand level of 4 kV (overvoltage category III) is not exceeded.
In the IT system the neutral point (star point) of the voltage generator is not earthed. The bodies of the electrical system are earthed. Earthing via high-resistance impedance is allowed. IT systems are only allowed in certain systems with their own transformer or generator.
U
L-L
66 V 115 V 120 V 127 V 200 V 230 V 240 V 260 V 277 V 347 V 280 V 400 V 415 V 440 V 480 V
Fig. Table of rated voltages of the grid suitable for the voltage inputs.
Maximum rated voltage
of the grid
17
UMG 605
Fig. Block diagram, UMG605 in IT system without N.
Fig. Block diagram, UMG605 in IT system with N.
230/400V 50/60Hz
UMG605
DC
AC/DC
L2
L3
N
L1
4M
4M
4M
4M
L1
L3L2 N
4M
L4
Earthing the
system
Auxiliary power
Impedance
Voltage measurement
400V 50/60Hz
DC
AC/DC
L2
L3
Auxiliary power
Voltage measurement
4M
4M
4M
4M
L1
L3L2
4M
L4
Earthing the
system
Impedance
L1
UMG605
N
18
UMG 605
Installed position
The UMG605 can be installed in control cabinets or in small distribution boards according to DIN 43880. It is mounted on a 35 mm mounting v according to DIN EN 60715. It can be installed in any position.
Fig. UMG605 on mounting rail according to DIN EN 60715.
Installation
19
UMG 605
m
Power supply voltage
A power supply voltage is required for operation of the UMG605. The type and amount of power supply voltage required is noted on the rating plate.
Before applying the power supply voltage, ensure that the voltage and frequency match the information given on the rating plate!
The connection cables for the power supply voltage must be fused with a UL listed fuse (6A type C).
- A disconnector or circuit-breaker must be provided for the power supply voltage in the building installation.
- The disconnector must be installed near the device and must be easy for the user to reach.
- The switch must be labelled as a disconnecting device for this device.
- Voltages which are above the allowable voltage range can destroy the device.
Power supply
voltage Uh
Disconnecting device
Fuse
Fig. Connection example for the power supply voltage Uh.
Important!
The inputs for the supply voltage are dangerous to touch!
c
Devices driven with direct currrent are protected against polarity reversal.
m
20
UMG 605
m
c
Important! The voltage measurement inputs are hazardous live!
The UMG605 can only determine measured values if a measurement­current voltage greater than 10 Veff is applied to at least one voltage measurement input.
Voltage measurement
The UMG605 is designed for the measurement of alternating voltages in 300 V systems in which category III overvoltages can occur. The UMG605 can only determine measured values if a measurement-current voltage greater than 10 Veff is applied to at least one voltage measurement input.
The following must be noted when selecting the instrument leads for the voltage measurement:
• The instrument leads required for the voltage measurement must be suitable for voltages up to 300 VAC to earth and 520 VAC conductor to conductor.
• Normal instrument leads must be fused by an overcurrent protective device and routed via disconnectors.
• Short-circuit proof instrument leads must be routed via disconnectors only.
Overcurrent protective devices and disconnectors must be positioned near the device and must be easy for the user to reach.
Fig. Connection example: Voltage measurement via short-circuit proof instrument leads.
Disconnector
L3
N
L1
L2
10A
(UL listed)
21
UMG 605
When connecting the voltage measurement, the following must be observed:
• In order to disconnect the voltage and cur­rent, a suitable circuit breaker is to be pro­vided.
• The circuit breaker must be positioned near to the UMG605, identified for the user and easy to reach.
• Only use authorised UL/IEC excess current protection devices and circuit breakers.
• Please use a 6A (UL-listed) cable circuit breaker.
• The excess current protection device must have a nominal value which is measured for the short circuit current at the connection point.
• Measurement voltages and measurement currents must come from the same network.
Caution!
Contact with the voltage measure­ment inputs on the UMG605 is dan­gerous!
c
Caution!
The UMG605 is not suitable for meas­uring DC voltages.
c
Caution!
Voltages that exceed the permitted nominal network voltages must be connected using a voltage converter.
c
Caution! The voltage measurement inputs may not be used for voltage mea­surement in SELV circuits (low volt­age protector).
c
22
UMG 605
Main measurement, inputs 1-3
4-conductor connection
Fig. measurement using 3 voltage converters in a three-phase 4 conductor network with asymmetrical load.
Fig. measurement in a three-phase 4 conduc­tor network with asymmetrical load.
Fig. measurement using 2 voltage converters in a three-phase 4 conductor network with asymmetrical load.
Fig. measurement using a three-phase 4 con­ductor network with symmetrical load.
L1 L2 L3
N
L1 L2 L3 N
4w 3m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L
1 L2 L3 N
4w 3m
hv
I
1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L
1 L2 L3 N
4w 2i
L1 L2 L3
N
L1 L2 L3 N
4w 3m
hv
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L
1 L2 L3 N
4w 2i
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L
1 L2 L3 N
4w 3m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L
1 L2 L3 N
4w 3m
hv
I
1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L
1 L2 L3 N
4w 2i
L1 L2 L3
N
L1 L2 L3 N
4w 2m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L
1 L2 L3 N
4w 2u
hv
I
1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L
1 L2 L3 N
4w 2u
L1 L2 L3
N
L
1 L2 L3 N
4w 3m
hv
I
1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L
1 L2 L3 N
4w 2i
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L1 L2 L3 N
4w 2u
hv
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L
1 L2 L3 N
4w 2u
I1 I2 I3
S1 S2 S1 S2 S1 S2
23
UMG 605
Fig. measurement in a three-phase 4 conduc­tor network with asymmetrical load.
Fig. measurement using 2 current converters in a three-phase 3 conductor network with symmetrical load.
L1 L2 L3
N
L1 L2 L3 N
4w 2i
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L
1 L2 L3 N
4w 2i
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
N
L1 L2 L3 N
4w 2u
I1 I2 I3
S1 S2 S1 S2 S1 S2
24
UMG 605
Fig. measurement in a three-phase 3 conduc­tor network with asymmetrical load.
Fig. measurement in a three-phase 3 conduc­tor network with asymmetrical load.
Fig. measurement in a three-phase 3 conduc­tor network with asymmetrical load.
Fig. measurement in a three-phase 3 conduc­tor network with asymmetrical load.
L1 L2 L3
L1 L2 L3 N
3w 3m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L
1 L2 L3 N
3w 2i
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L
1 L2 L3 N
3w 2m
L1 L2 L3
L1 L2 L3 N
3w 2i
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L
1 L2 L3 N
3w 2m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L
1 L2 L3 N
3w 2m
hv
L1
N
L
1 L2 L3 N
2w 1m
L1 L2 L3
L
1 L2 L3 N
3w 3m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L
1 L2 L3 N
3w 2i
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L
1 L2 L3 N
3w 2m
L1 L2 L3
L1 L2 L3 N
3w 2u
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L
1 L2 L3 N
3w 2u
hv
I
1 I2 I3
S1 S2 S1 S2 S1 S2
L1
N
L
1 L2 L3 N
2w 1m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L
1 L2 L3 N
3w 2i
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L
1 L2 L3 N
3w 2m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L
1 L2 L3 N
3w 2m
hv
L1 L2 L3
L1 L2 L3 N
3w 2u
hv
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3 N
2w 2m
L1
L2
25
UMG 605
Fig. measurement in a single-phase 3 conduc­tor network. I3 and U3 are not calculated and set to zero.
Fig. measurement in a three-phase 3 conduc­tor network with asymmetrical load.
Fig. measurement in a three-phase 3 conduc­tor network with asymmetrical load.
Fig. measurement of a phase in a three-phase 4 conductor network.
L1 L2 L3
L1 L2 L3 N
3w 2m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L
1 L2 L3 N
3w 2m
hv
I
1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L1 L2 L3 N
3w 2m
hv
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1
N
L1 L2 L3 N
2w 1m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L
1 L2 L3 N
3w 2m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3
L
1 L2 L3 N
3w 2m
hv
I
1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3 N
2w 2m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1
L2
L1 L2 L3
L
1 L2 L3 N
3w 2m
hv
I
1 I2 I3
S1 S2 S1 S2 S1 S2
L1 L2 L3 N
2w 2m
I1 I2 I3
S1 S2 S1 S2 S1 S2
L1
L2
26
UMG 605
Auxiliary measurement, input V4
3-conductor connection
Fig. measurement with one current transform­er in a three-phase 4 conductor network with symmetrical load
Fig. measurement with one current transform­er in a three-phase 3 conductor network with symmetrical load.
Fig. measurement with one current transformer
m
In case of a three wire main mea­surement (input V1-V3), the auxiliary measurement (input V4) cannot be used as measuring input.
Be connected for the measurement of the auxiliary measurement (V4) for frequency estimation needs a voltage to the main measurement.
m
L1 L2 L3
N
L4 N
4w 1m
I4
S1 S2
L1 L2 L3
L
4 N
4w 1m
I4
S1 S2
L1 L2 L3
L4 N
4w 1m
I4
S1 S2
L1 L2 L3
N
L
4 N
4w 1m
I4
S1 S2
L1 L2 L3
L
4 N
4w 1m
I4
S1 S2
L
L4 N
2w 1n
I4
S1 S2
N
27
UMG 605
Be connected for the measurement of the auxiliary measurement (V4) for frequency estimation needs a voltage to the main measurement.
m
C
C
Frequency measurement
The UMG605 needs the network frequency to measure and calculate measurement values. The network frequency must be in a range be­tween 15Hz and 440Hz.
For automatic ascertainment (wide range) of the frequency, an L1-N voltage larger than 10Veff must be applied to the voltage meas­urement input V1.
The measurement of power frequency hap­pens only at the measuring inputs of the main measurement (V1, V2, V3).
Measurement voltages and measure­ment currents must come from the same network.
In case of a three wire main mea­surement (input V1-V3), the auxiliary measurement (input V4) cannot be used as measuring input.
28
UMG 605
m
c
c
Current measurement
The UMG605 is designed for the connection of current transformers with secondary currents of ../1A and ../5A. Only alternating currents, not direct currents, can be measured. Each current measurement input can be permanently loaded with 6A or for 1 second with 100 A.
Earthing current transformers If a connection is provided for earthing the secondary winding, this must be connected with earth.
Fig. Connection example, current mea­surement via current transformers.
Important! The UMG605 is not suitable for the measurement of direct voltages.
Attention! The current inputs are live.
Loads
L3
L1
L2
N
S1
S2
S1
S2
S1
S2
S1
S2
Loading...
+ 64 hidden pages