janitza UMG 508 Operating Manual

Document no. 1.042.015.5n from firmware rel. 2.0 / hardware rel. 20
Power Analyser
UMG 508
Operating manual and technical data
Art. no. 33.03.121 (UL)
Janitza electronics GmbH Vor dem Polstück 1 D-35633 Lahnau Support Tel. 0049 6441 9642-22 Fax 0049 6441 9642-30 e-mail: info@janitza.com Internet: http://www.janitza.com
www.janitza.com
2
UMG 508
General 3 Goods-in Check 6 Description 8
Intended Use 8 Features 9 Measurement Method 10 GridVis network analysis software 11
Assembly 12
Place of Installation 12 Installation extradata 12 Front Board Cutout 12 Ethernet Connection 13 Fixing 13
Installation 14
Supply Voltage 14 Voltage Measurement 16 Current measurement 24 RS485 28 Ethernet 32 Digital outputs 34 Digital Inputs 36
Operation 38
Measurement value displays 39 "Home“ measurement value display 40 Select measurement value display 41 Call up additional information 42 Delete min/max values individually 43 List of transients 44 List of events 45
Configuration 46
Language 47 Communication 48 Measurement 50 Transients 56 Events 58 Display 60 System settings 62 Password 63 Delete minimum and maximum values 64 Delete power meters 65 Extensions 68
Initialization 71
Applying the supply voltage 71 Apply measurement voltage 72 Rotary field direction 72 Applying measurement current 73 Checking the power measurement 75 Checking communication 75
Service and Maintenance 81 Technical data 85
Dimensioned drawings 94 Measurement value displays overview 97 Connection example 100
3
UMG 508
General
Copyright
This handbook is subject to the legal regulati­ons of copyright law protection and may not be mechanically or electronically photocopied or reprinted in full in or parts and, without the legal, written permission of
Janitza electronics GmbH, Vor dem Polstück 1, D 35633 Lahnau, Germany,
may not be reproduced or further publication in any other way.
Protected trademarks
All trademarks and the resulting rights belong to the respective owners of the rights.
Disclaimer
Janitza electronics GmbH does not accept any liability for errors or deficits in this handbook and is not obliged to keep the contents of this handbook updated.
Comments on the handbook
We welcome your comments. If anything in this handbook seems unclear, please let us know and send us an EMAIL to:
info@janitza.de
4
UMG 508
Meaning of Symbols
The following pictograms are used in this hand­book:
Gefährliche Spannung!
Danger of death or risk of major injury. Disconnect the system and device be­fore beginning any work.
Protective ground connection.
Caution!
Please pay attention to the documenta­tion. This symbol should warn against possible dangers that can occur during assembly, initialization and use.
m
c
Inductive. The voltage lags the current
Capacitive. The voltage lags the current.
C
Note.
5
UMG 508
Application Information
Please read this operating manual and all other publications that have to be consulted to work with this product (particularly for installation, operation or maintenance).
Please pay attention to all safety regulations and warning information. If you fail to follow the in­formation, it can result in personal damage and/ or damages to the product.
Any unauthorized change or use of this device beyond the specified mechanical, electrical or other operating limits can cause personal da­mage and/or damage to the product.
Any such unauthorized change represents "mi­suse" and/or "negligence" in the sense of gua­rantee for the product and therefore makes the guarantee covering possible consequential da­mages void.
This device is to be exclusively operated and maintained by a specialist.
Specialists are persons who, due to their rele­vant training and experience, are capable of re­cognizing risks and avoiding possible hazards that can be caused when operating or servicing the device.
When using the device, the necessary legal and safety regulations should be considered additio­nally for the respective application case.
Caution! If the device is not operated according to the operating manual, protection is no longer ensured and the device may cause dangers.
c
Cables with single wires must be provi­ded with ferrules.
Only screw plugs with the same pole number and the same type of const­ruction can be plugged together.
m
m
6
UMG 508
The installation and initialization inst­ructions also describe options that do not belong to the scope of supply.
Goods-in Check
Correct and safe operation of this device is subject to appropriate transportation, correct warehousing, installation and assembly as well as careful operation and maintenance. If it can be assumed that safe operation without any danger is no longer possible, the device must be taken out of operation immediately and se­cured against unintentional initialization. Unpacking and packing must take place, with the usual care without applying force and using suitable tools. The devices must be checked for perfect condition with visual tests. It should be assumed that risk-free operation is not possible if, for example:
• There is visible damage,
• it no longer works due despite the main sup­ply being intact,
• has been subject to unfavorable conditions (e.g. storage outside of the authorized climate limits without adaptation to the room climate, thawing etc.) over a longer period of time or transport stresses (e.g. a fall from a height, in­cluding without any visisble external damage etc).
• Please check the delivered items for comple­teness before starting with the installation of the device.
All supplied options and design versi­ons are described on the delivery note.
All screw clamps that belong to the scope of supply are attached to the device.
C
C
C
7
UMG 508
Art.no. Description
13 10 539 Profibus plug, 9-pole DSUB, with integrated switchable terminating resistors.
1)
Refer to delivery note for article number.
Scope of Supply
Available accessories
Quantity Art.no. Description
1 52 21 xxx 1) UMG508 1 33 03 121 operating manual 1 51 00 116 CD with the following contents:
- "GridVis“ programming software,
- DEscription of functions, GridVis, UMG508,
- UMG508, GSD file "U5080C2C.GSD“ for Profibus DP V0 1 10 01 818 screw clamp, pluggable, 2-pole (auxiliary power) 1 10 01 847 screw clamp, pluggable, 5-pole (voltage measurement 1-4) 1 10 01 822 screw clamp, pluggable, 8-pole (current measurement 1-4) 1 10 01 810 screw clamp, pluggable, 6-pole (digital outputs) 2 10 01 809 screw clamp, pluggable, 5-pole (digital inputs) 1 08 01 505 2m patch cable, twisted, gray (connection UMG508-PC/Switch/Hub) 1 52 19 301 fixing clips
8
UMG 508
Description
Intended Use
The UMG508 is intended for measurements in the building installation, on distributors, power switches and bus bars. Measurement voltages and measurement cur­rents must come from the same network.
The UMG508 is suitable for installation in switch boards with a fixed, weather-protected extrada­ta.
The UMG508 can be used in 2, 3 and 4 supply networks and in TN and TT networks.
The current measurement inputs of the UMG508 are connected using external ../1A or ../5A cur­rent transformers.
The measurement in medium and high-voltage networks generally takes place using current and voltage transformers. The UMG508 can be used in residential and in­dustrial areas.
Measurement results can be displayed, saved and read-out using serial interfaces for further processing.
9
UMG 508
Features
• Front board installation, 144x144mm,
• Working temperature range -10°C .. +55°C,
• Colour graphic display 320x240, 256 colours, 6 keys,
• 8 digital inputs, 5 digital outputs,
• 16Bit A/transformer, data memory 256MByte Flash, SDRAM 32Mbyte,
• Continuous scanning of voltage and current measurement inputs with 20kHz,
• Frequency range of fundamental oscillation 40Hz .. 70Hz
• 4 voltage measurement inputs, 4 current measurement inputs,
• Measurement in TN and TT networks,
• RS485: Profibus DP/V0, Modbus RTU, Modbus-Master, BACnet (Option)
• Ethernet: Web-Server, EMAIL, BACnet (Option),TCP/IP, EMAIL (SMTP), DHCP-Client (BootP), Modbus/TCP, Modbus RTU over Ethernet, FTP, ICMP (Ping), NTP, TFTP. BACnet (Option), SNMP.
• Detection of transients >50µs and storage with up to 16000 scanning points,
• Detection of more than 800 measurement values,
• Measurement of harmonics 1 to 40, for
- Uln, I, P (ref/supply) and
- Q (ind/cap),
• Programming own applications in Jasic.
10
UMG 508
Measurement Method
The UMG508 measures without any gaps and calculates all effective values over a 200ms In­terval. The UMG508 measures the real effective value (TRMS) of the voltages and currents applied to the measurement inputs.
Operating Concept
You can program the UMG508 in several ways and call up measurement values.
• Direct- on the device using 6 keys and the display.
• Using the programming softwareGridVis.
• Using the UMG508 homepagefor devices with an Ethernet interface.
• Using the RS485 with theModbus-protocol. You can change and call up data with the help of the Modbus address list (stored on the en­closed data carrier).
Only operating the UMG508 using the integra­ted display and the 6 keys is described in this operating manual. The GridVis programming software and the homepage have their own "online assistance“.
11
UMG 508
GridVis network analysis software
The UMG508 can be programmed and read­out with the GridVis network analysis software
included in the scope of supply. A PC must be connected using a serial interface (RS485/ Ethernet) to the UMG508.
GridVis features
• Programming the UMG508.
• Configuration of recordings.
• Recordings read-out.
• Saving data in a database.
• Graphic presentation of measurement values.
• Programming specific applications for the cli­ent.
PC
UMG
508
Ethernet
Illu. Connection of a UMG508 to a PC using an interface converter.
PC
UMG
508
RS232
RS485
Interface
Converter
Illu. Connection of a UMG508 to a PC using Ethernet.
12
UMG 508
Assembly
Place of Installation
The UMG508 is suitable for installation in fixed, weather protected switch boards. Conducting switch boards have to be grounded.
Installation extradata
In order to achieve sufficient ventilation, the UMG508 has to be installed vertically. The clea­rance has to be at least 50mm at the top and bottom and 20mm at the side.
Front Board Cutout
Cutout size: 138
+0.8
x 138
+0.8
mm
Failure to maintain the minimum clea­rances can destroy the UMG508 at high environmental temperatures!
Wall
Airflow
Airflow
Ethernet Connection
Illu. UMG508 installation extradata; view from back.
m
13
UMG 508
Ethernet Connection
Patch Cable
Ethernet Connection
The UMG508's Ethernet connection is located on the underside of the housing. Depending on the bending radius of the Ether­net cable and plug type, you must provide a connection area beneath the UMG508.
The connection area beneath the UMG508 should not be less than 50 mm.
50 mm
Fixing
The UMG508 is fixed into the switch board with two fixing clips that are each mounted on the device at the top and bottom.
Fixing Clips
14
UMG 508
Installation
Protective Wire Connection
Use a ring cable lug for connecting the protecti­ve wire to the UMG508.
Supply Voltage
A supply voltage is required to operate the UMG508. The type and level of the necessary supply voltage is noted on the label.
Before applying the supply voltage, make sure that the voltage and the frequency match the details on the label!
The auxiliary voltage has to be connected via an UL/IEC approved fuse (1A Class CC) or a circuit breaker (1A C.Char.)
Illu. Connection example; connection of supply voltage to a UMG508.
Separator
Fuse
L1 N PEL3L2
Protective wire
c
Warning - danger of death!
It is necessary for the protective wire connection on the device to be con­nected with the system grounding.
Connection point for
protective wire
15
UMG 508
- An isolator or circuit breaker must be provided for the voltage supply in buil­ding installation.
- The isolator must be attached near to the device and must be easy for the user to access.
- The switch must be marked as a se­parator for this device.
-Voltages above the authorized voltage range can destroy the device.
m
Warning! The inputs for the supply voltage are dangerous to touch!
c
Warning! Please pay attention to the details on the supply voltage provided on the UMG508 label.
c
16
UMG 508
Illu. Basic circuit diagram, UMG508 in theTN- network.
Voltage Measurement Three-phase 4 conductor systems
The UMG508 can be used in three-phase 4 con­ductor systems (TN, TT network) with a groun­ded neutral wire. The bodies of the electrical system are grounded.
Three-phase 3 conductor systems
The UMG508 is only suitable for use in IT net­works with restrictions, because the measure­ment voltage is measured against the housing potential and the input impedance of the device causes a leakage current against ground. The leakage current can cause isolation monitoring in IT networks to respond. Connection variations with a voltage transfor­mer are suitable for IT networks without any re­strictions.
Illu. Basic circuit diagram, UMG508 in the IT net­work without N.
600V 50/60Hz
DC
AC/DC
L2
L3
Auxiliary
power
Voltage measurement
4M
4M
4M
4M
V1
V3V2
4M
V4
System grounding
Impedance
L1
UMG508
Vref
PE
347V/600V 50/60Hz
L2
L3
N
L1
N
L1
240V
50/60Hz
System grounding
DC
AC/DC
Auxiliary
power
Voltage measurement
4M
4M
4M
4M
V1 V3V2 Vref
4M
V4
UMG508
17
UMG 508
Maximum nominal voltage of
the network
Maximum nominal voltage of
the network according to UL
U
L-N
/ U
L-L
66V / 115V 120V / 208V 127V / 220V 220V / 380V 230V / 400V 240V / 415V 260V / 440V 277V / 480V 347V / 600V
Illu. Table of suitable network nominal voltages for the voltage measurement inputs according to EN60664-1:2003.
Three-phase 4 conductor systems with grounded neutral wire.
Nominal Voltages
Lists of the networks and their nominal network voltages in which the UMG508 can be used.
U
L-L
66V 115V 120V 127V 200V 220V 230V 240V 260V 277V 347V 380V 400V 415V 440V 480V 500V 577V 600V
Illu. Table of suitable network nominal voltages for the voltage measurement inputs according to EN60664-1:2003.
Ungrounded three-phase 3 conductor systems.
18
UMG 508
Voltage Measurement Inputs
The UMG508 has 4 voltage measurement in­puts (V1, V2, V3, V4).
Measurement category
The voltage measurement inputs are suitable for measurements in networks in which overvolta­ges in the measurement category 600V CATIII can occur.
Frequency
The UMG508 requires the rated frequency for measuring and calculating measurement values. The UMG508 is suitable for measurements in networks with a rated frequency in the range of 40Hz to 70Hz.
Illu. Connection example for voltage measure­ment.
A connection diagram does not have to be configured for the measurement inputs V4 and I4.
C
L1 N PEL3L2
10A
(UL/IEC listed)
19
UMG 508
The following has to be considered when con­necting the voltage measurement:
• A suitable separator is to be provided in order to disconnect the UMG508 from the current and voltage.
• The separator must be placed near to the UMG508, labelled for the user and must be easy to reach.
• Use for over current protection and circuit breaker an UL/IEC approved fuse 10A Class CC.
• The overcurrent protection device must have a nominal value calculated for the short-cir­cuit current at the connection point.
• Measurement voltages and measurement currents must come from the same network.
Warning!
The voltage measurement inputs on the UMG508 are dangerous to touch!
c
Warning!
The UMG508 is not suitable for measu­ring DC voltages.
Warning!
Voltages that exceed the authorized network nominal voltages must be connected using a voltage converter.
c
Warning! The voltage measurement inputs may not be used for voltage measurement in SELV circuits (Safety Extra Low Vol­tage).
c
c
20
UMG 508
Connection diagrams, voltage measurement
L1 L2 L3
N
V
1 V2 V3 V4 Vref
3p 4wu
L1 L2 L3
N
V1 V2 V3 V4 Vref
3p 4w
L1 L2 L3
N
V1 V2 V3 V4 Vref
3p 4wu
L1 L2 L3
N
3p 4w
I1 I2 I3 I4
S1 S2 S1 S2 S1 S2 S1 S2
L1 L2 L3
N
V
1 V2 V3 V4 Vref
3p 4wu
L1 L2 L3
N
V
1 V2 V3 V4 Vref
3p 4w
L1
L2
V
1 V2 V3 V4 Vref
1p 2w
L1 L2 L3
V1 V2 V3 V4 Vref
3p 3wu
L1 L2 L3
N
V
1 V2 V3 V4 Vref
3p 4wu
L1
L2
V1 V2 V3 V4 Vref
1p 2w
L1 L2 L3
3p 2i0
I1 I2 I3 I4
S1 S2 S1 S2 S1 S2 S1 S2
L1 L2 L3
N
3p 4w
I1 I2 I3 I4
S1 S2 S1 S2 S1 S2 S1 S2
21
UMG 508
L1 L2 L3
N
V
1 V2 V3 V4 Vref
3p 4wu
L1 L2 L3
N
V
1 V2 V3 V4 Vref
3p 4w
L1
L2
V
1 V2 V3 V4 Vref
1p 2w
L1 L2 L3
V
1 V2 V3 V4 Vref
3p 3wu
L1 L2 L3
V1 V2 V3 V4 Vref
3p 3w
L L L L
V
1 V2 V3 V4 Vref
3p 5w
N
L1 L2 L3
N
V
1 V2 V3 V4 Vref
3p 4wu
L1
L2
V
1 V2 V3 V4 Vref
1p 2w
L1 L2 L3
3p 2i0
I1 I2 I3 I4
S1 S2 S1 S2 S1 S2 S1 S2
L1 L2 L3
N
3p 4w
I1 I2 I3 I4
S1 S2 S1 S2 S1 S2 S1 S2
L L L L
N
3p 5w
I1 I2 I3 I4
S1 S2 S1 S2 S1 S2 S1 S2
L L L L
V1 V2 V3 V4 Vref
3p 5w
N
22
UMG 508
Connection diagrams, current measurement
L1 L2 L3
N
3p 2i
I1 I2 I3 I4
S1 S2 S1 S2 S1 S2 S1 S2
L1 L2 L3
N
3p 4w
I1 I2 I3 I4
S1 S2 S1 S2 S1 S2 S1 S2
L1 L2 L3
N
3p 2i
I1 I2 I3 I4
S1 S2 S1 S2 S1 S2 S1 S2
L1 L2 L3
N
3p 2i
L1 L2 L3
3p 2i0
L1
L2
1p 2i
I1 I2 I3 I4
S1 S2 S1 S2 S1 S2 S1 S2
I1 I2 I3 I4
S1 S2 S1 S2 S1 S2 S1 S2
I1 I2 I3 I4
S1 S2 S1 S2 S1 S2 S1 S2
L1 L2 L3
N
3p 4w
I1 I2 I3 I4
S1 S2 S1 S2 S1 S2 S1 S2
L1 L2 L3
N
3p 2i
L1
L2
1p 2i
I1 I2 I3 I4
S1 S2 S1 S2 S1 S2 S1 S2
I1 I2 I3 I4
S1 S2 S1 S2 S1 S2 S1 S2
23
UMG 508
L1 L2 L3
N
3p 2i
L1 L2 L3
3p 2i0
L1
L2
1p 2i
I1 I2 I3 I4
S1 S2 S1 S2 S1 S2 S1 S2
I1 I2 I3 I4
S1 S2 S1 S2 S1 S2 S1 S2
I1 I2 I3 I4
S1 S2 S1 S2 S1 S2 S1 S2
L1 L2 L3
N
3p 4w
I1 I2 I3 I4
S1 S2 S1 S2 S1 S2 S1 S2
L L L L
N
3p 5w
I1 I2 I3 I4
S1 S2 S1 S2 S1 S2 S1 S2
24
UMG 508
Current measurement
The UMG508 is designed for connecting current converters with secondary currents of ../1A and ../5A. Only alternating currents, and no direct currents, can be measured. Each current measurement input can be loaded with 120A for 1 second.
Grounding current converters! If a connection is provided for ground­ing the secondary winding, this must be connected with ground.
Illu. Connection example, current measurement using current converter.
Warning! The UMG508 is not suitable for the measurement of direct voltages.
Warning! The current measurement inputs are dangerous to touch.
m
c
c
A connection diagram does not have to be configured for meaurement in­puts V4 and I4.
C
S1
S2
L1 N PEL3L2
S1
S2
S1
S2
S1
S2
25
UMG 508
Current converter connections!
The secondary connections of the cur­rent converter must be short-circuited to these before the electricity cables are disconnected from the UMG508! If a test switch is available which auto­matically shorts the secondary current converter lines, it is sufficient to set them to the "test" extradata, as long as the short-circuiters have been checked beforehand.
Open current converters!
Extreme contact danger due to voltage peaks can occur on current converters that are operated open on the secon­dary side! For "anti-open current converters", the winding isolation is calculated so that the current converters can be operated open. However, these current conver­ters are also dangerous to touch if they are operated open.
cc
Current Direction
The current direction can corrected on the de­vice or individually using the available serial in­terfaces for each phase. In the case of incorrect connection, subsequent reconnection of the current converter is not ne­cessary.
26
UMG 508
Total current measurement
If the current is measured using two current converters, the total transfer ratio of the cur­rent converters must be programmed in the UMG508.
Illu. Example, current measurement using a total current converter.
Example The current measurement takes place using two current converters. Both current conver­ters have a transfer ratio of 1000/5A. The total measurement is carried out with a 5+5/5A total current converter. The UMG508 must then be set as follows:
Primary current: 1000A + 1000A = 2000A Secondary current: 5A
UMG
S2
I
S
1
P1
P2
Einspeisung 1 Supply 1
Einspeisung 2
Supply 2
1P1
1P2
(K)
(L)
(k) (l)
1S
2
1S1
1S1 1S2 2S1 2S2
2S1
2S2
(k)
(l)
(K) (L)
2P
1
2P2
Verbraucher A Consumer A
Verbraucher B
Consumer B
27
UMG 508
Illu. Example, current measurement with an ad­ditional ampere meter.
Ampere meter
If you do not want to measure the current with the UMG508 alone, but also with an additional ampere meter, the ampere meter must be swit­ched in series to the UMG508.
Illu. Example, direct current measurement.
Direct measurement
Nominal currents up to 5A can also be directly measured with the UMG508. Under consideration that the direct measure­ment will be carried out for the current only in three phase 4 wire systems with mains volt­age till
127V/220V (300V CAT III) according UL
and three phase 3 wire systems with mains voltage till
277V (300V CAT III) according UL
Due to the fact that the UMG508 does not have integrated protection for the current measurement, this protection must be fore­seen in the installation.
UMG
S2
I
S
1
Einspeisung Supply
Verbraucher
Consumer
A
(k)S
1 S2(l)
P
2(L)(K)P1
UMG
S2
I
S
1
Einspeisung
Supply
Verbraucher Consumer
5A Typ C
28
UMG 508
RS485
The RS485 interface is designed as a 9-pole DSUB socket on the UMG508. On this interface, the UMG508 supports the fol­lowing selection of protocols:
• Modbus RTU
• Profibus DP V0 Slave
For connection, we recommend a 9-pin profibus (modbus) plug e.g. the company Phoenix, type „SUBCON-Plus-ProfiB/AX/SC“ with the article number 2744380 (Janitza article no. 13.10.539).
Illu. UMG508 with DSUB socket for the RS485 interface.
DSUB socket
for Modbus or Profibus.
29
UMG 508
Connection of Bus Lines
The incoming bus line is connected to clamps 1A and 1B. The bus line for the next device in the line is connected to clamps 2A and 2B. If there is no further device in the line, the bus line has to be terminated with resistors (switch to ON). In switch extradata ON, clamps 2A and 2B are switched off for the continuing bus line.
Illu. Profibus plug with terminating resistors.
Profibus- (Modbus)-Stecker (extern)
Profibus (Modbus) connector (external)
Terminating resistors
Other
profibus
stations
Screw-type terminals
D-sub,
9 pin,
socket
D-sub,
9 pin,
connec-
tor
30
UMG 508
Shields
A twisted, shielded cable is foreseen for con­nections using the RS485 interface.
• Ground the shields of all cables leading to the cabinet at the cabinet entry point.
• Connect the shield extensively and with good conductivity with a low external voltage ground.
• Intercept the cable mechanically above the ground clip in order to avoid damages caused by cable movements.
• Use suitable cable insert guides, such as PG glands, to guide the cable into the switch ca­binet.
Cable type
The cables used must be suitable for an envi­ronmental temperature of at least 80°C. Recommended cable types: Unitronic Li2YCY(TP) 2x2x0.22 (Lapp cable) Unitronic BUS L2/FIP 1x2x0.64 (Lapp cable)
Maximum cable length
1200m at a Baud rate of 38.4k.
Illu. Shielding arrangement at cabinet entry point.
Cable
Strain relief
Cable shielding braid.
Grounding clip
Low external voltage ground.
Terminal resistors
The cable is terminated with resistors (120Ohm 1/4W) at the beginning and end of a segment.
The UMG508 does not have any terminal resis­tors.
C
For the wiring of the Modbus con­nection, CAT cables are not suitable. Please use the recommended cables.
31
UMG 508
Bus structure
• All devices are connected in a bus structure (line).
• In one segment, up to 32 participants can be switched together.
• The cable is terminated with resistors at the beginning and end of a segment.
• Repeaters (power boosters) must be used with more than 32 participants in order to connect the individual segments.
• Devices with terminated resistor have to be supplied.
• We recommend to install the master UMG at the end of the segment.
• In case that the master UMG with terminated bus resistor will be removed, the bus is not under operation.
• In case that slave UMG with terminated bus resistor will be removed or is not switched on, the bus is can be unstable.
• UMGs which have no termination can be re­placed without any interruption of the bus.
32
UMG 508
Ethernet
The network settings for the Ethernet are speci­fied by the network administrator and set accor­dingly on the UMG508. If the network settings are not known, the patch cable may not be plugged into the UMG508.
Ethernet connection
Patch cable
Warning! Incorrect nework settings can cause faults in the network!
m
33
UMG 508
Illu. Connection example; UMG508 and PC need a fixed IP address.
Illu. Connection example; UMG508 and PC are automatically allocated the IP address from a DHCP server.
DHCP
Server
Switch
PC UMG508
Patch cable
PC
UMG508
Patch cable
Switch
Illu. Connection example; direct connection between the UMG508 and PC using a twisted patch cable (art. no. 08.01.505)
PC
UMG508
Patch cable
(twisted)
34
UMG 508
Digital outputs
The UMG508 has 5 digital outputs. These out­puts are separated galvanically from the analy­sis electronics using optocouplers. The digital outputs have a common reference.
• The digital outputs can switch AC and DC loads.
• The digital outputs arenotshort-circuit proof.
• Connected lines that are longer than 30m must be laid with shields.
• External auxiliary power is necessary.
~
Illu. Digital outputs connection.
35
UMG 508
Illu. Connection of two relays to digital outputs 4 and 5.
16
K1 K2
24V
AC
External
auxiliary power
UMG508
Digital outputs 1-5 Digital Outputs 1-5
12
Digital
Output 5
13
Digital
Output 4
14
Digital
Output 3
15
Digital
Output 2
Digital
Output 1
~~
11
36
UMG 508
Digital Inputs
The UMG508 has 8 digital inputs. The digital in­puts are divided into two groups, each with 4 inputs. Each group has a common reference.
Illu. Example for the connection of external con­tacts S1 and S2 to the digital inputs 1 and 2.
24V
DC
-
+
External
auxiliary power
S1
S2
UMG508
Digital Inputs 1-4 Digital Inputs 1-4
3.9V
4k
10
Digital
Input 1
Digital
Input 3
Digital
Input 2
Digital
Input 4
3.9V
3,9V
3,9V
4k
4k
4k
9
8
7
6
-
+
-
+
Illu. Example for the connection of digital inputs.
37
UMG 508
S0 impulse input
You can connect an S0 impulse generator in ac­cordance with DIN EN62053-31 to each digital input. You require an external auxiliary voltage with an output voltage in the range of 20 .. 28V DC and a resistor with 1.5kOhm.
Illu. Example for the connection of an S0 impul­se generator to digital input 1.
24V
DC
-
+
External
auxiliary voltage
UMG508
Digitale Inputs 1-4 Digital Inputs 1-4
3.9V
4k
10
Digital
Input 1
Digital
Input 3
Digital
Input 2
Digital
Input 4
3.9V
3.9V
3.9V
4k
4k
4k
9
8
7
6
1.5k
S0
Impulse
generator
38
UMG 508
Operation
The UMG508 is operated using six function keys. The six keys are allocated different functions depending on the context:
• Selection of measurement value displays.
• Navigation within the menu.
• Processing the device settings.
Function key labeling
Display titles
Measurement values
Function keys
39
UMG 508
Measurement value displays
Main values
You can use keys 2 and 5 to browse between the main values of the measurement value dis­plays.
Display
Configuration
Display
Pointer dia-
gram
Display
"Home“
Display
Voltages L-N
Auxiliary values
You can use keys 3 and 4 to browse between the auxiliary values of a measurement value dis­play.
Display
Voltage L-N
Display
Voltages L-L
Main values
Auxiliary values
40
UMG 508
"Home“ measurement value display
Once the network returns, the UMG508 starts with the "Home“ measurement value display. This measurement value display contains the device names and an overview of important measurement values. The device name consists of the device type and serial number upon de­livery.
Using the "Home - Key 1“, you come out of the measurement value dis­plays for the main values directly to the first "Home" measurement value display.
41
UMG 508
Select measurement value display
You want to change to a measurement value display with main values.
• Use the function keys 2 and 5 to browse bet­ween the measurement value displays of the main values.
• With function key 1 (Home), you always ac­cess the first measurement value display.
Display
Voltage L-N
Display
Voltages L-L
You want to change to a measurement value display with auxiliary values.
• Select the measurement value display with the main values.
• Select the measurement value display with function keys 3 and 4 for the auxiliary values.
Example: selection of auxiliary value voltage.
42
UMG 508
Call up additional information
• Browse with keys 2 to 5 to the required mea­surement value display.
• Activate the measurement value selection with key 6 (selection).
• Select the required measurement value with keys 2 to 5.
• The background colour for the measurement value changes from grey to green. The addi­tional information is shown in a blue window.
• End the process with key 1 (ESC) or select another measurement value with keys 2 to 5.
43
UMG 508
Delete min/max values individually
• Use keys 2 to 5 to browse to the required measurement value display.
• Activate the measurement value selection with key 6 (selection).
• Select the required minimum and maximum value with keys 2 to 5.
• The background colour for the measurement value changes from grey to green. The point with the date and time of occurence is shown in an additional blue window.
• You can now delete the selected min or max value with key 6 (reset).
• End the process with key 1 (ESC) or select another min/max value with keys 2 to 5.
C
The date and time for the min/max va­lues are shown in UTC time (coordina­ted world time).
44
UMG 508
List of transients
Recognized transients are listed in the transi­ents list.
• The transients list consists of 2 pages.
• Transients 1 to 8 are listed on page 1 and 9 to 16 on page 2.
Display transients
• Go to the transients list with key 6 „selec­tion“.
• Select a transient with keys 3 and 4.
• Allow to the transients to be presented gra­phically with key 6.
• Show or hide the legends with key 6 „Le­gends“.
• You can exit the graphic presentation of the transients with key 1.
Transient voltages are quick, impulsive transient oscillation processes in elec­trical networks. Transient voltages are not predictable with respect to time and have a limited period. Transient voltages are caused by the effects of lighting, by switching opera­tions or by triggered fuses.
C
45
UMG 508
List of events
Recognized events are listed in the events list.
• The events list consists of 2 pages.
• Events 1 to 8 are listed on page 1 and events 9 to 18 on page 2.
Display incident
• Go to the events list with key 6 „Selection“.
• Select an incident with keys 3 and 4.
• Allow the incident to be graphically presen­ted with key 6.
• Show or hide the legends with key 6 „Le­gends“.
• You can leave the graphic presentation of the incident with key 1.
Events are limit value violations of ef­fective current and voltage values.
C
46
UMG 508
Configuration
The supply voltage must be connected for con­figuration of the UMG508.
Apply supply voltage
• The level of supply voltage for the UMG508 can be taken from the label.
• After applying the supply voltage, a startup screen appears on the display. Approximate­ly ten seconds later, the UMG508 changes to the first „Home“ measurement value display.
• If a display does not appear, check whether the applied supply voltage is within the nomi­nal voltage range.
Warning!
Supply voltages that do not corres­pond with the label details can lead to incorrect functions and damage to the device.
c
Illu. Example of "Home“ measurement value.
47
UMG 508
Configuration menu
Once the network returns, the „Home“ measu­rement value display is found on the start page.
• Browse to the menu configuration with key 1.
If you are in a measurement value display for main values, you use
• key 1 - „Home“ to directly access the first „Home“ measurement display.
• Use key 1 to browse to the menu configu­ration.
Language
You can set the language for the measurement value displays and menus directly in the "confi­guration" menu. There are different languages to select between. The preset language in the factory is "English".
Display
Configuration
Display
"home“
Main values
Illu. Example configuration of "languages".
48
UMG 508
Communication
The UMG508 has an Ethernet and a RS485 in­terface.
Ethernet (TCP/IP)
Select the type of address allocation for the Ethernet interface here.
DHCP mode
• Off- IP address, Netmask and Gateway are specified by the user and set directly on the UMG508. Select this mode for simple net­works without a DHCP server.
• BOOTP - BootP permits the fully automatic integration of a UMG508 in an existing net­work. BootP is an older protocol and does not have DHCP's extent of functions.
• DHCP- Upon starting, the UMG508 automa­tically collects the IP address, the Netmask and the Gateway from a DHCP server.
Factory pre-setting:DHCP
The UMG508 may only be connected to the Ethernet after coordinating with the network administrator!
m
49
UMG 508
RS485
You can specify the protocol, the device address and the Baud rate for operating the RS485 inter­face.
Protocol
Selection options:
• Modbus Slave
• Modbus Master/Gateway
• Profibus DP V0
• BACnet (Option)
Factory pre-setting: Modbus Master/Gateway
Device address
Setting range: 0 - 255 Factory pre-setting: 1
Baud rate
Setting range: 9.600, 19.200, 38.400, 57.600,
115.200, 921.600 kbps
Factory pre-setting: 115.200 kbps
50
UMG 508
Measurement
Configure here:
• The measurement converters for the current and voltage measurement.
• The record of transients.
• The recording of events.
• The rated frequency.
51
UMG 508
Rated frequency
For measuring and calculating the meaurement values, the UMG508 requires the Rated fre­quency of a.c. systems. The UMG508 is suitable for measurements in networks with a rated frequency in the range of 40Hz to 70Hz.
The rated frequency can be specified by the user or automatically detected by the device.
• Auto- Factory pre-setting. The rated fre­quency is measured.
• 50Hz- The rated frequency is set to 50Hz. The rated frequency is not measured.
• 60Hz- The rated frequency is set to 60Hz. The rated frequency is not measured.
Automatic frequency detection
A voltage (V-Vref) larger than 10Veff must be applied on at least one of the voltage measure­ment inputs for the automatic detection of fre­quency by the UMG508. If a sufficient measurement voltage is not ap­plied, the UMG508 can not detect the rated fre­quency and a measurement can therefore not be carried out.
52
UMG 508
Nominal voltage
The nominal voltage specifies the value which
• transients,
• events and automatic graphic scaling refer to.
Setting range: 0 .. 1,000,000 V Factory pre-setting: 230 V
For example, you can also select the primary voltage as nominal voltage.
Voltage converter
You can allocate the main meaurement and the auxiliary measurement voltage converter rela­tions. You select the setting 400 V / 400 V for measu­rements without a voltage converter.
Setting range: Primary 1 .. 999,999 V Secondary 1 .. 400 V
Factory pre-setting: Primary 400 V Secondary 400 V
53
UMG 508
Illu. Example for voltage measurement in a 3 phase 4 conductor network.
A connection diagram has to be con­figured for the measurement inputs V4 and I4.
C
Connection diagram for voltage measurement
For the voltage measurement, you can select between the following connection diagrams:
3p4w - 3 phase 4 conductor 3p4wu - 3 phase 4 conductor 3p3w - 3 phase 4 conductor For networks without a neutral conductor under symmetric load. 3p3wu - 3 Phasen 3 Leiter For networks without a neutral conductor under symmetric load. 3p5w - 3 Phasen 4 Leiter Measurement of an additional measuring point. 1p2w - 1 phase 2 conductor (180°)
Factory pre-setting: 3p4w
54
UMG 508
Current converter
You can allocate both the main measurement and auxiliary measurement current converter relations. Select setting 5/5A for direct measurement of currents.
Setting range: Primary 1 .. 999,999 A Secondary 1 .. 5 A Factory pre-setting: Primary 5 A Secondary 5 A
Nominal current
The nominal current specifies which value
• overcurrent,
• current transients,
• and automatic graphics scaling
refer to.
Setting range: 0 .. 1,000,000 A
You can only set the nominal values for measurement of the K-Factor and TDD using GridVis.
C
55
UMG 508
Illu. Example for current measurement using 3 current converters in a 3 phase 4 conductor net­work.
A connection diagram does not have to be configured for measurement in­puts V4 and I4.
C
Connection diagram for current measurement
You can select between the following connec­tion diagrams for current measurement:
3p4w - 3 phase 4 conductor, 3 current conv. 3p5w - 3 phase 4 conductor, 4 current conv. The fourth current transformer can be used for measuring the neutral conductor e.g. 3p2i - 3 phase 4 conductor, 2 current conv. For networks under symmetric load. 3p2i0 - 3 phase 3 conductor, 2 current conv. Aron connection for networks without a neutral conductor. The third current will be calculated. 1p2i - 1 Phasen 2 Leiter, 2 Stromwandler
Factory pre-setting: 3p4w
56
UMG 508
Transients
Transient voltages are rapid, impulsive transi­ent oscillation processes in electrical networks. Transient voltages are not predictable with res­pect to time and last for a limited period. Transient voltages are caused by the effects of lighting, due to switching operations or the trig­gering of fuses.
• The UMG508 recognizes transients that are longer than 50µs.
• The UMG508 monitors the voltage measure­ment inputs on transients.
• Transient monitoring can be set per phase.
• There are two independent criteria for recog­nizing transients.
• If a transient has been recognized, the wave shape is saved in a transient recording.
• If a transient has been recognized, the limit value is automatically increased by 20V, both in automatic and manual modes. This auto­matic increase of the limit value fades within 10 minutes.
• If another transient is recognized within the next 60 seconds, this transient is recorded with 512 points.
• You can display recorded transients with the GridVis incident browser.
57
UMG 508
Mode (delta)
If the difference of two neighbouring scanning points exceeds the set limit value, a transient is recognized.
• Off- Transient monitoring is switched off.
• Automatic- Factoring pre-setting. The limit
value is calculated automatically and is 0.2175 times the current 200ms effective value.
• Manual- Transient monitoring uses the adjus­table limit value under "Trns U“.
Accept L2-L4
Transient monitoring can be set per phase. You can accept settings from phase L1 into phases L2, L3 and L4.
• No - The L1 phase settings are not transferred to the stages L2, L3 and L4.
• Yes- The settings from phase L1 are taken over into phases L2, L3 and L4.
Mode (absolute)
If a scanning value exceeds the set limit value, a transient is recognized.
• Off- Transient monitoring is switched off
• Automatic- Factory pre-setting. The limit va-
lue is automatically calculated and is 110% of the current 200 ms effective value.
• Manual- Transient monitoring uses the adjus­table limit value under "Peak U“.
58
UMG 508
Events
Events are threshold value violations of set threshold values for current and voltage. Here, threshold values are compared with the full wave effective values for current and volta­ge from the measurement channels. The event record consists of a mean value, a minimum or maximum value, a start time and an end time.
• Monitoring of the threshold values can be switched off (Off/Manual).
• Threshold values must be set as a percentage of the nominal value.
• Threshold values can be set for excess volta­ge, undervoltage and overcurrent.
• An event is triggered if in the course of the pre­run period there is an uninterrupted threshold value violation. An event is ended if there are no threshold value violations in the course of the after-run period.
• If an event has occurred, the corresponding measurement value is recorded with the set pre-run and after-run periods (respectively
0..1000 full waves).
• Event records are configured with the GridVis and displayed with the event browser.
Limit value
Measured value
Vollwellen­effektivwert
Limit value
violations
before the
lead time
End time
Limit value violations before the follow-up time
Event
Follow-up timeLead time
Start time event
(Trigger time)
Event record
Pre-run
After-run
Fig. Shows the full wave effective values for an event.
59
UMG 508
Voltage
Drop
A drop in voltage is set in % of the nominal vol­tage.
Overvoltage
The overvoltage is set in % of the nominal vol­tage.
Current
Overcurrent
The rapid increase of current is set in % of the nominal current.
Accept L2-L4
Monitoring of events can be set per phase. You can accept settings from phase L1 into phases L2, L3 and L4.
• No- Settings from phase L1 are not taken over into phases L2, L3 and L4.
• Yes- The settings from phase L1 are taken over into phases L2, L3 and L4.
Follow-up time
The follow-up time can only be set with GridVis. Factory pre-setting: 0
C
Preparation time
The preparation time can only be set with GridVis. Factory pre-setting: 0
C
60
UMG 508
Display
Brightness
The brightness level of the background illumi­nation can be adjusted. The brightness level set here is used during operation of the UMG508. Setting range: 0 .. 100% Factory pre-setting: 70% (0% = dark, 100% = very bright)
Standby
This refers to the time before the brightness changes to "standby brightness". Setting range: 60 .. 9999 seconds Factory pre-setting: 900 seconds
Standby brightness
This refers to the brightness level changed to after the end of the standby time. The standby time is restarted by using keys 1-6. Setting range: 0 .. 60% Factory pre-setting: 40%
Screensaver
The screensaver prevents a screen on the LCD from "sticking" if the screen does not change for a longer period of time. Setting range: yes, no Factory pre-setting: yes
Presentation
You can specify the speed at which new measu­rement values should appear on the measure­ment value displays. Setting range: fast (200ms), slow (1s) Factory pre-setting: fast
Rotate
The measurement value displays are automati­cally displayed in sequence. The configuration displays are not affected by this. Setting range: yes, no Factory pre-setting: no
61
UMG 508
The service life of the background il­lumination extends if the brightness of the background illumination is kept lower.
Transition time
You can set the time between automatic transiti­on to the next measurement value display. Setting range: 0 .. 255 seconds Factory pre-setting: 2 seconds
C
62
UMG 508
System settings
Display of system settings specific to the de­vice.
Firmware version
Device serial number
Fixed device MAC address
Set IP address
Set Gateway address
Date and time
Set password
Reset settings
Illu. Example for the display of system settings.
C
You cannot configure the date and time directly on the device. Settings for time synchronization and the date and time can only be made using GridVis.
63
UMG 508
Forgotten password
If you have forgotten the password, you can only delete the password using the "GridVis“ software. In order to do this, connect the UMG508 with the PC using a suitable interface. Further infor­mation can be found in the GridVis assistant.
Password
The user can block access to the configuration with a password. Changing the configuration di­rectly on the device is then only possible after entering the password. The password consists of a 6 digit combination of numbers.
Setting range: 1-999999 = with password 000000 = without password
A password (000000) is not programmed in the factory.
• In order to change a set password, you must know the current password.
• Note any changed password.
• If you do not want a password request any­more, enter "000000" as a password.
64
UMG 508
Delete minimum and maximum va­lues
You can delete all minimum and maximum valu­es in the UMG508 simultaneously.
How to delete the individual minimum and maxi­mum values is described in the chapter "indivi­dually deleting min. and max. values".
Delete all minimum and maximum values.
• Select "yes" with key 3
• Confirm with key 6.
• The message "executed" appears in the line ­all minimum and maximum values have been deleted.
65
UMG 508
Delete power meters
You can delete all power meters in the UMG508 at the same time. A selection of certain power meters is not pos­sible.
• Select with key 3 "yes“
• Confirm with key 6.
• The message "executed" appears in the line ­all power meters have been deleted.
Prior to commissioning potential pro­duction dependant contents of the energy counter, min/max values and records have to be deleted.
C
66
UMG 508
Delivered condition
All settings such as the configuration and recor­ded data are reset to the factory pre-settings or deleted. Entered release codes are not deleted.
• Select with key 3 "yes“
• Confirm with key 6.
• The message "executed" appears in the line ­the delivered condition is reinstored.
Restart
The UMG508 restarts all programs.
• Select with the key 3 "yes“.
• Confirm with key 6.
• The message "executed" appears in the line
- all programs have been restarted.
67
UMG 508
Colors
Selection of colors for the presentation of cur­rent and voltage in the graphic presentations.
68
UMG 508
Extensions
Under "Extensions“ you can subsequently re­lease charged functions and show the status of Jasic programs.
69
UMG 508
Release
The UMG508 contains chargeable functions that can be subsequently released. List of release functions:
• BACnet
• EMAX
You receive the release code from the manufac­turer. The manufacturer needs the device serial number and the name of function to be released. In order to release the function, you enter the 6 digit release code in the respective line. Please note that the release code is only valid for one device.
70
UMG 508
Jasic status
Up to 7 specific customer Jasic programs (1-7) and one recording can run in the UMG508. The Jasic programs can adopt the following sta­tuses:
• Stopped
• Running
You cannot change the status of Jasic programs on the device.
71
UMG 508
Initialization
Applying the supply voltage
• The level of supply voltage for the UMG508 can be taken from the label.
• After applying the supply voltage, a startup screen appears on the display. Around ten seconds later, the UMG508 changes to the first measurement value display.
• If no display appears, you must check whe­ther the supply voltage is within the nominal voltage range.
Warning!
Supply voltages that do not corres­pond with the details on the type label can lead to malfunctions and damage to the device.
m
72
UMG 508
Rotary field direction
Check the direction of the voltage rotary field on the measurement value display of the UMG508. A "right" rotary field is usually available.
Presentation of the phase sequence according to the rotary field direction.
UL1-UL2-UL3 = right rotary field UL1-UL3-UL2 = left rotary field
Apply measurement voltage
• Voltage measurements in networks with nominal voltages above 346VAC against ground must be connected using a voltage converter.
• After connection of the measurement volta­ges, the measurement values displayed by the UMG508 for voltages L-N and L-L must match those at the voltage measurement in­put.
• If a voltage converter factor is programmed, this must considered upon comparison.
Warning!
The UMG508 is not suitable for measu­ring DC voltages.
m
73
UMG 508
Applying measurement current
The UMG508 is designed for the connection of ../1A and ../5A current converters. Only AC currents, and not DC currents, can be measured using the current measurement in­puts.
Short-circuit all current converter outputs ex­cept one. Compare the currents displayed by the UMG508 with the applied current. The current displayed by the UMG508 must match the input current under consideration of the current converter transfer relation. The UMG508 must display approx. zero am­peres in the short-circuited current measure­ment inputs.
The current converter ratio is set to 5/5A in the factory and may have to be adapted to the cur­rent converter used.
Warning! Voltages and currents outside of the authorized measurement range can destroy the device.
m
Voltages are shown with long pointers in the pointer diagram, and currents with shorter pointers.
Current
Voltage
Sign
Reactive power
• positive (+) with inductive load,
• negative (-) with capacitive load.
Phase angle (U/I)
• positive (+) with capacitive load,
• negative (-) with inductive load.
74
UMG 508
Voltage and current only have
a minor difference in the pha­se.
Voltage and current have a
difference of approximately 180° in the phase.
Pointer diagram, examplel 1
Primarily ohmic load.
Pointer diagram, example 2
Primarily ohmic load.
• The current measurement input is allocated to the right voltage measurement input.
• In this current measurement, the connections k and l are swapped over or there is a return feed into the supplier network.
• The current measurement input is allocated to the right voltage measurement input.
75
UMG 508
Checking communication
The UMG508 counts all received (RX), all sent (TX) and all faulty data packages. In the ideal case, the number of errors shown in the error column is zero.
Reset
You can delete the counters for the data pa­ckages with key 6. The start time for the recount is reset.
Checking the power measurement
Short-circuit all current converter outputs ex­cept one and check the displayed power out­puts. The UMG508 may only display one power out­put in the phase with the current converter input that is not short-circuited. If this does not apply, please check the connection of the measure­ment voltage and measurement current.
If the amount of effective power is correct but the sign of effective power is negative, this may have two causes:
• Connections S1(k) and S2(l) are mixed up on the current converter.
• Effective power is returned to the network.
In the pointer diagram, voltages are shown with the longer pointers and currents with shorter pointers.
76
UMG 508
Metering range exceedance (overload)
Metering range exceedances are displayed for as long as they are present and cannot be ac­knowledged. A metering range is exceeded if at least one of the four voltage or current mea­suring inputs is outside of its specified meter­ing range.
Limit values for metering range exceedance: (200 ms rms values):
I = 7.4 Arms UL-N = 600 Vrms
Display of the metering range exceedance in the voltage circuit L2 and in the current circuit of the 4th phase (I4).
77
UMG 508
Device master file
The device master file, abbreviated with GSD file, describes the Profibus characteristics of the UMG508. The GSD file is required by the PLC configuration program. The device master file for the UMG508 has the file name "U5080C2C.GSD“ and is contained on the data carrier supplied with the delivery.
1) Global variables are variables that are defined by
the user in Jasic and are provided to each interface in the UMG508.
Profibus profile
A Profibus profile contains data to be exchanged between a UMG and an SPS. Four Profibus pro­files are pre-configured in the factory.
With a Profibus profile, you can:
• call-up measurement values from the UMG,
• set the digital outputs in the UMG,
• request the status of the digital inputs in the UMG.
Each Profibus profile can contain a maximum of 127Bytes. You can apply further Profibus profi­les if more data has to be transferred.
• Each Profibus profile has a profile number. The profile number is sent by the PLC to the UMG.
• You can directly process 16 Profibus profiles with GridVis (profile numbers 0..15).
• Additional Profibus profiles (profile numbers
16..255) can be applied using Jasic pro­grams.
• Factory pre-configured Profibus profiles can be subsequently changed.
Variable definition
All system variables and global variables
1)
can be scaled individually and converted into one of the following formats:
• 8, 16, 32Bit integer with and without sign.
• 32 or 64Bit float format.
• Big or Little Endian.
Big-Endian = High Byte before Low Byte. Little-Endian = Low Byte before High Byte.
78
UMG 508
Illu. Block switch diagram for data exchange between PLC and UMG508.
Example Collect measurement values using Profibus
You must transfer at least one Profibus profile with GridVis and transfer it to the UMG508. A Jasic program is not necessary.
79
UMG 508
Profibus profile number 1
Byte- Values- Scaling Index Value type format
1 1 Voltage L1-N Float 1 2 5 Voltage L2-N Float 1 3 9 Voltage L3-N Float 1 4 13 Voltage L2-L1 Float 1 5 17 Voltage L3-L2 Float 1 6 21 Voltage L1-L3 Float 1 7 25 Current L1 Float 1 8 29 Current L2 Float 1 9 33 Current L3 Float 1 10 37 Effective power L1 Float 1 11 41 Effective power L2 Float 1 12 45 Effective power L3 Float 1 13 49 Cosphi (math.) L1 Float 1 14 53 Cosphi (math.) L2 Float 1 15 57 Cosphi (math.) L3 Float 1 16 61 Frequency Float 1 17 65 Effective power total L1-L3 Float 1 18 69 Reactive power total L1-L3 Float 1 19 73 Apparent power total L1-L3 Float 1 20 77 Cosphi (math.) total L1-L3 Float 1 21 81 Effective current total L1-L3 Float 1 22 85 Effective consumption total L1-L3 Float 1 23 89 Ind. Reactive consum. total L1-L3 Float 1 24 93 THD voltage L1 Float 1 25 97 THD voltage L2 Float 1 26 101 THD voltage L3 Float 1 27 105 THD current L1 Float 1 28 109 THD current L2 Float 1 29 113 THD current L3 Float 1
Profibus profile number 0
Byte Value Scaling Index Value type format
1 1 Voltage L1-N float 1 2 5 Voltage L2-N float 1 3 9 Voltage L3-N float 1 4 13 Voltage L4-N float 1 5 17 Voltage L2-L1 float 1 6 21 Voltage L3-L2 float 1 7 25 Voltage L1-L3 float 1 8 29 Current L1 float 1 9 33 Current L2 float 1 10 37 Current L3 float 1 11 41 Current L4 float 1 12 45 Effective power L1 float 1 13 49 Effective power L2 float 1 14 53 Effective power L3 float 1 15 57 Effective power L4 float 1 16 61 Cosphi (math.) L1 float 1 17 65 Cosphi (math.) L2 float 1 18 69 Cosphi (math.) L3 float 1 19 73 Cosphi (math.) L4 float 1 20 77 Frequency float 1 21 81 Effective power total L1-L4 float 1 22 85 Reactive power L1-L4 float 1 23 89 Apparent power total L1-L4 float 1 24 93 Cosphi (math.) total L1-L4 float 1 25 97 Effective current total L1-L4 float 1 26 101 Effective consumption total L1-L4 float 1 27 105 Ind. reactive consum. total L1-L4 float 1 28 109 THD voltage L1 float 1 29 113 THD voltage L2 float 1 30 117 THD voltage L3 float 1
80
UMG 508
Profibus profile number 2 Profibus profile number 3
Byte- Values- Scaling Index Value type Format
1 1 Effective power L1 Float 1 2 5 Effective power L2 Float 1 3 9 Effective power L3 Float 1 4 13 Effective power total L1-L3 Float 1 5 17 Current L1 Float 1 6 21 Current L2 Float 1 7 25 Current L3 Float 1 8 29 Current total L1-L3 Float 1 9 33 Effective consumption total L1-L3 Float 1 10 37 CosPhi (math.) L1 Float 1 11 41 CosPhi (math.) L2 Float 1 12 45 CosPhi (math.) L3 Float 1 13 49 CosPhi (math.) total L1-L3 Float 1 14 53 Reactive power L1 Float 1 15 53 Reactive power L2 Float 1 16 53 Reactive power L3 Float 1 17 53 Reactive power total L1-L3 Float 1 18 53 Apparent power L1 Float 1 19 53 Apparent power L2 Float 1 20 53 Apparent power L3 Float 1 21 53 Apparent power total L1-L3 Float 1
Byte- Values- Scaling Index Value type Format
1 1 Effective consumption total L1-L3 Float 1 2 5 Drawn eff. consum. total L1-L3 Float 1 3 9 Supplied eff. consum. total L1-L3 Float 1 4 13 Reactive consumption total L1-L3 Float 1 5 17 Ind. reactive consum. total L1-L3 Float 1 6 21 Cap. reactive consum. total L1-L3 Float 1 7 25 Apparent consumption total L1-L3 Float 1 8 29 Effective consumption L1 Float 1 9 33 Effective consumption L2 Float 1 10 37 Effective consumption L3 Float 1 11 41 Inductive reactive consumption L1 Float 1 12 45 Inductive reactive consumption L2 Float 1 13 49 Inductive reactive consumption L3 Float 1
81
UMG 508
Service and Maintenance
The device is subjected to different safety tests before delivery and marked with a seal. If a de­vice is opened, the safety tests have to be re­peated. A guarantee is only provided for unope­ned devices.
Repair and Calibration
Repair work and calibration can only be under­taken by the manufacturer.
Front film
Cleaning the front film can be done with a soft cloth and domestic detergent. Acids and pro­ducts containing acids may not be used for cleaning.
Battery
The internal clock is fed from the supply voltage. If the supply voltage fails, the clock is supplied by the battery. The clock provides the date and time information, e.g. for recordings, minimum and maximum values and events. The expected battery life is at least 5 years at a storage temperature of +45°C. The typical bat­tery life is 8 to 10 years. The device must be opened to exchange the battery. If the device has been opened, a new safety test is required for safe operation. A gu­arantee is only provided for unopened devices.
Disposal
The UMG508 can be recycled as electronic scrap in accordance with the legal regulations. The fixed, integrated lithium battery must be disposed of separately.
Firmware update
If a firmware update has to be carried out for your UMG508, you can do this with the GridVis software included in the delivery.
Service
Should any questions arise that are not descri­bed in this handbook please contact the manu­facturer directly. We will require the following compulsory details from you for processing:
-Device name (refer to label),
-Serial number (refer to label),
-Software release (refer to measurement value display),
-Measurement voltage and supply voltage,
-Precise error description.
82
UMG 508
Possible error
None Display.
None Current dis- play.
Displayed current is too high or low.
Displayed voltage is too low or high
Displayed voltage is too light.
Cause
External fuse for the supply vol­tage has triggered.
The measurement voltage is not connected. The measurement current is not connected.
Current measurement is in the wrong phase. Current converter factor is in­correctly programmed.
Measurement in the wrong pha­se. Voltage converter is incorrectly programmed.
Measurement range exceeded. The voltage peak at the measu­rement input has been excee­ded due to harmonics.
Remedy
Replace fuse.
Connect measurement voltage.
Connect measurement current.
Check connection and correct if necessary. Read current converter transfer ratio on the current converter and program it.
Check connection and correct if necessary. Read voltage converter transfer ratio on the voltage converter and program it.
Use a voltage converter.
Warning!It is necessary to make sure that the measurement inputs are not overloaded.
Procedure in case of errors
83
UMG 508
Possible errors
Metering range ex­ceedance (overload)
Effective power is too high or low.
Effective power-
receipt/supply are mixed up.
Cause
Voltage or current input out of range (see chapter mete­ring range exceedance)
The programmed current converter transfer ratio is wrong. The current path is allocated to the wrong voltage path. The programmed voltage converter transfer ratio is wrong.
At least one current conver­ter connection is mixed up.
A current path is allocated to the wrong voltage path.
Remedy
Check and correct the connection if necessary. Use suitable voltage or current trans­formers.
Read and program the current or voltage transformer ratio on the transformer.
Read and program the current conver­ter transfer ratio on the current conver­ter. Check the connection and correct if necessary.
Read and program the current conver­ter transfer ratio on the current conver­ter.
Check and correct the connection if necessary.
Check and correct the connection if necessary.
84
UMG 508
Possible errors
No connection to device.
The device does not work despite taking the above measures.
Cause
RS485:
- Wrong device address.
- Different bus speeds
- Wrong protocol.
- Termination is missing.
Ethernet:
- IP address is wrong
Device is defective.
Remedy
Set device address. Check and correct the speed (baudrate) Select protocol. Connect bus with terminating resistor (120 Ohm).
Set IP address on the device.
Send the device to the manufacturer to check with an exact description of the error.
85
UMG 508
Technical data
The UMG508 is intended for use in a weather-protected, fixed extradata. The UMG508 must be connected to the protective wire connection! Protection class I according to IEC 60536 (VDE 0106, part 1). Calculation temperature range : K55 (-10°C .. +55°C) Relative air humidity : 0 to 75 % RH Operating height : 0 .. 2000m above sea level Impurity level : 2 Installation extradata : any Ventilation : external ventilation is not required. Foreign matter and water protection, Front : IP40 according to EN60529 Reverse side : IP20 according to EN60529
The following details apply to devices transported or stored in the original packaging. Free fall : 1m Temperature : K55 (-25°C to +70°C) Relative air humidity : 0 to 90 % RH
Net weight : 1080g Device dimensions : approx. l=144mm, w=144mm, h=75mm Battery : Type VARTA CR1/2AA, 3 V, Li-Mn Service life of background illumination : 40000h (50% of initial brightness)
General
Transport and storage
Environmental conditions in operation
86
UMG 508
Supply voltage
Connection capacity of terminal points
Connectable conductors. Only one conductor per terminal point may be connected! Single wire, multi-wire, fine wire : 0.2 - 2.5mm
2, AWG 24 - 12
Pin terminals, ferrules : 0.25 - 2.5mm
2
Tightening torque : 0.5 - 0.6 Nm, Insulation length : 7mm
Installation overvoltage category : II Safeguarding of supply voltage Circuit breaker : 1A Class CC or circuit breaker 1A Char. C (UL/IEC approved) Option 240V (Art. no. 52.21.011) Nominal range : 95V - 240V (50 - 60Hz) or DC 80 - 280V Working range : +/- 10% of nominal range Power consumption : max. 6W Option 130V (Art.no. 52.21.012) Nominal range : 44V - 130V (50 - 60Hz) or DC 48 - 180V Working range : +/- 10% of nominal range Power consumption : max. 6W
87
UMG 508
8 digital inputs Maximum counting frequency : 20Hz Reaction time (Jasic program) : 200ms Input signal applied : 18V .. 28V DC (typical 4mA) Input signal not applied : 0 .. 5V DC, current lower than 0.5mA
5 digital outputs, semi-conductor relay, not short-circuit proof. Switch voltage : max. 54V DC, 27V AC Switch current : max. 50mAeff AC/DC Reaction time (Jasic program) : 200ms Output of voltage drops : 20ms Output of voltage excesses : 20ms Impulse output (power impulse) : max. 20Hz
Line length : up to 30m - not shielded : larger than 30m - shielded
Inputs and outputs
Connection capacity of terminal points
Rigid/flexible : 0.14 - 1.5mm
2, AWG 28-16
Flexible with ferrules without plastic sleeve : 0.25 - 1.5mm
2
Flexible with ferrules with plastic sleeve : 0.25 - 0.5mm
2
Tightening torque : 0.22 - 0.25Nm Insulation length : 7mm
88
UMG 508
1)
The UMG508 can only detect measurement values if a voltage L-N larger than 10Veff or a voltage
L-L larger than 18Veff is applied to at least one voltage measurement input.
Measurement inputs
The voltage measuring inputs are suitable for the following grids of power supply: Three-phase 4 conductor systems L-N/L-L
: 347V/600V
Three-phase 3 conductor systems L-L : 600V
The voltage measuring inputs regarding safety and reliability reasons are dimensioned as follows: Measurement category : 600V CAT III Measurement surge voltage : 6kV
Measuring range L-N : 01) .. 600Vrms Measuring range L-L : 01) .. 1000Vrms Resolution : 0.01V Crest factor : 1,6 (relating to 600Vrms) Impedance : 4MOhm/Phase Power consumption : ca. 0.1 VA Scanning frequency : 20kHz/phase Transients : >50µs Frequency of fundamental oscillation : 40Hz .. 70Hz Resolution : 0.001Hz
Voltage measurement
89
UMG 508
Current measurement
Connection capacity of terminal points
Connectable conductor (current measurement and voltage measurement). Only one conductor per terminal point may be connected! Single wire, multi-wire, fine wire : 0.2 - 2.5mm
2, AWG 24 - 12
Pin terminals, ferrules : 0.25 - 2.5mm
2
Tightening torque : 0.5 - 0.6Nm Insulation length : 7mm
Rated current : 5A Resolution : 0.1mA Measuring range : 0.001 .. 7.4Arms Crest factor : 2.4 Measurement category : 300V CAT III Measurement surge voltage : 4kV Power consumption : ca. 0.2 VA, (Ri=5mOhm) Overload for 1 second : 120A (sinusoidal) Scanning frequency : 20kHz
90
UMG 508
RS485 : plug, SUB D 9-pole Protocol, Modbus RTU : Modbus RTU/Slave, Modbus RTU/Master Transfer rate : 9.6kbps, 19.2kbps, 38.4kbps, 57.6kbps,
115.2kbps, 921.6kbps Protocol, Profibus : Profibus DP/V0 according to EN 50170 Transfer rate : 9.6kBaud to 12MBaud Protocol, BACnet (option)
Ethernet 10/100Base-TX Connection : RJ-45 Functions :
Modbus Gateway, Embedded Webserver (HTTP) Protocols : TCP/IP, EMAIL (SMTP), DHCP-Client (BootP), Modbus/TCP, Modbus RTU over Ethernet, FTP, ICMP (Ping), NTP, TFTP. BACnet (Option), SNMP.
Serial interfaces
91
UMG 508
Network quality parameters
Specifications
(Measurement using current converters ../5A)
Function Symbol Accuracy class Measur. range Display range
Frequency f 0.05 (IEC61557-12) 40 .. 70 Hz 40 Hz .. 70 Hz Phase current I 0.2 (IEC61557-12) 0.001 .. 7.4 Arms 0 A .. 9999 kA Neutral cond. current measured IN 0.2 (IEC61557-12) 0.001 .. 7.4 Arms 0 A .. 9999 kA Neutral cond. current calculated INc 0.5 (IEC61557-12) 0.001 .. 22.2 A 0 A .. 9999 kA Voltage U L-N 0.1 (IEC61557-12) 10 .. 600 Vrms 0 V .. 9999 kV Voltage U L-L 0.1 (IEC61557-12) 18 .. 1000 Vrms 0 V .. 9999 kV Short-time flicker, long-time fli. Pst, Plt - - ­Voltage drops (L-N) Udip 0.2 (IEC61557-12) 10 .. 600 Vrms 0 V .. 9999 kV Voltage rises (L-N) Uswl 0.2 (IEC61557-12) 10 .. 600 Vrms 0 V .. 9999 kV Voltage interruptions Uint - - ­Voltage unbalance (L-N)
1)
Unba 0.2 (IEC61557-12) 10 .. 600Vrms 0 V .. 9999 kV
Voltage inbalance (L-N)
2)
Unb 0.2 (IEC61557-12) 10 .. 600 Vrms 0 V .. 9999 kV Voltage harmonics Uh cl. 1 (IEC61000-4-7) to 2.5 kHz 0 % .. 100 % Current harmonics Ih cl. 1 (IEC61000-4-7) to 2.5 kHz 0 % .. 100 % Network signal voltage MSV - - -
1) Reference to amplitude.
2) Reference to phase and amplitude.
92
UMG 508
Function parameters
Function Symbol Accuracy class Measurem. range Display range
Total effective power P 0.2
5)
(IEC61557-12) 0 .. 15.3kW 0 W .. 9999 GW Total reactive power QA, Qv 1 (IEC61557-12) 0 .. 15.3 kvar 0 varh .. 9999 Gvar Total apparent power SA, Sv 0.25 (IEC61557-12) 0 .. 15.3 kVA 0 VA .. 9999 GVA Total effective energy Ea 0.2
5)
(IEC61557-12) 0 .. 15.3 kWh 0 Wh .. 9999 GWh Total reactive energy ErA, ErV 1 (IEC61557-12) 0 .. 15.3 kvarh 0 varh .. 9999 Gvarh Total apparent energy EapA, EapV 0.25 (IEC61557-12) 0 .. 15.3 kVAh 0 VAh .. 9999 GVAh Frequency f 0.05 (IEC61557-12) 40 .. 70 Hz 40 Hz .. 70 Hz Phase current I 0.2 (IEC61557-12) 0.001 .. 7.4 Arms 0 A .. 9999 kA Neutral cond. current measured IN 0.2 (IEC61557-12) 0,001 .. 7.4 Arms 0 A .. 9999 kA Neutral cond. current calculated INc 0.5 (IEC61557-12) 0.001 .. 22.2 A 0 A .. 9999 kA Voltage U L-N 0.1 (IEC61557-12) 10 .. 600 Vrms 0 V .. 9999 kV Voltage U L-L 0.1 (IEC61557-12) 18 .. 1000 Vrms 0 V .. 9999 kV Power factor PFA, PFV 0.5 (IEC61557-12) 0.00 .. 1.00 0 .. 1 Short-time flicker, long-time fl. Pst, Plt - - ­Voltage drops Udip 0.2 (IEC61557-12) 10 .. 600 Vrms 0 V .. 9999 kV Voltage rises Uswl 0.2 (IEC61557-12) 10 .. 600 Vrms 0 V .. 9999 kV Transient overvoltages Utr 0.2 (IEC61557-12) 10 .. 600 Vrms 0 V .. 9999 kV Voltage interruptions Uint - - ­Voltage inbalance
1)
Unba 0.2 (IEC61557-12) 10 .. 600 Vrms 0 V .. 9999 kV
Voltage inbalance
2)
Unb 0.2 (IEC61557-12) 10 .. 600 Vrms 0 V .. 9999 kV Voltage harmonics Uh cl. 1 (IEC61000-4-7) to 2.5 kHz 0 V .. 9999 kV THD of voltage
3)
THDu 1.0 (IEC61557-12) to 2.5 kHz 0 % .. 999 % THD of voltage
4)
THD-Ru 1.0 (IEC61557-12) to 2.5 kHz 0 % .. 999 % Current harmonics Ih cl. 1 (IEC61000-4-7) to 2.5 kHz 0 A .. 9999 kA THD of current
3)
THDi 1.0 (IEC61557-12) to 2.5 kHz 0 % .. 999 % THD des Stromes
4)
THD-Ri 1.0 (IEC61557-12) to 2.5 kHz 0 % .. 999 % Mains signal voltage MSV - - -
1) Reference to amplitude.
2) Reference to phase and amplitude.
3) Reference to basic oscillation.
4) Reference to effective value.
5) Accuracy class 0.2 with ../5A converter. Accuracy class 0.5 with ../1A converter.
93
UMG 508
Declaration of Conformity
The product fulfils the following EC Directives:
2004/108/EG Electromagnetic compatibility of electrical equipment.
2006/95/EG Electrical equipment for use within certain voltage limits.
Considered standards:
Noise immunity
IEC/EN 61326-1:2013 Class A: Industrial environment IEC/EN 61000-4-2:2009 Electrostatic discharge IEC/EN 61000-4-3:2011 Electromagnetic RF Field 80-1000MHz IEC/EN 61000-4-3:2011, EMV-ILA V01-03 Electromagnetic RF Field 1000-2700MHz IEC/EN 61000-4-4:2013, EMV-ILA V01-03 Burst IEC/EN 61000-4-5:2007, EMV-ILA V01-03 Surge IEC/EN 61000-4-6:2009, EMV-ILA V01-03 Conducted disturbances 0.15-80MHz IEC/EN 61000-4-8:2010 Power frequency magnetic field IEC/EN 61000-4-11:2005, EMV-ILA V01-03 Voltage dips, short interrupts, voltage variations and frequency changes
Noise emission
IEC/EN 61326-1:2013 Class B: Residental environment IEC/CISPR11/EN 55011:2011 Radio disturbance field strength 30-1000MHz IEC/CISPR11/EN 55011:2011 Radio disturbance voltage 0.15-30MHz EMV-ILA V01-03 Radio disturbance voltage 9-150kHz EMV-ILA V01-03 Flicker
Equipment safety IEC/EN 61010-1:2011 Safety requirements for electrical equipment for Measurement, UL61010-1:2005 2nd Edition control and laboratory use – Part 1: General requirements CAN/CSA-C22.2 No. 61010-1:2004 2nd Edition IEC/EN 61010-2-030:2011 Particular requirements for testing and measuring circuits
94
UMG 508
Dimensioned drawings
Cutout size: 138
+0,8
x 138
+0,8
mm
Reverse side
Patch cable
95
UMG 508
View from belowSide view
96
UMG 508
Configuration
Language, Communication, Measurement, System
Display, Colors, Extensions
...
Other main values
Display
Communication
State
Display
Home
Measurement values
overview)
Display
Voltage L-N
...
(config)
Communication
Ethernet
Feldbus
Measurement
Transformer
Transients
Events
Rated Frequency
System
Information
Password
Re-initialization
Display Colors
U, I
L1...L4
Extensions
Activation
Jasic state
Transformer
Phase L1, L2,
L3, L4
U prim./sec.
I prim./sec.
I rated
U rated
Connection
Transients
Phase L1, L2,
L3, L4
Events
Phase L1, L2,
L3, L4
Re-initialization
Energy
Min/Max values
Delivery state
Reset
Activation
BACnet
EMAX
Jasic state
Modus (abs)
Peak U
Modus (delta)
Trns U
Drop U
Overvoltage
Rapid increase I
Other main values
97
UMG 508
Configuration
(config)
Device name
Overview
Measurement
values
Voltage
L-N
Current
L1..L4
Voltage
L-L
Current
Sum
Auxiliary values
Sum Real
Power L1..L4
(Real Power
L1..L3)
Reactive
Power
(Sum Real Power
L1..L3)
Apparent
Power
(Sum Real Power
L1..L3)
Main values
Apparent Energy
Overview
Active Energy
Overview
(Tariff 1, Tariff 2)
Reactive Energy
Overview
(Tariff 1, Tariff 2)
Measurement value displays overview
98
UMG 508
Main values
Auxiliary values
Reactive Energy
Monthly values
Bar diagram
Apparent Energy
Monthly values
Bar diagram
Active Energy
Monthly values
Bar diagram
Active Power
Curve L1
(L2, L3, L4,
L1..L3, L1..L4)
Reactive Power
Curve L1
(L2, L3, L4,
L1..L3, L1..L4)
Current
Curve
(L2, L3, L4)
Voltage
Curve L1
(L2, L3, L4)
Voltage
Harmonics L1
(L2, L3, L4)
Current
Harmonics L1
(L2, L3, L4)
Transients
1..8
(9..16)
Events
1..8
(9..16)
99
UMG 508
Phasor
Diagram
Main values
Auxiliary values
Communication
State
Oscilloscope
L1
Oscilloscope
L2 L3 L4
Oscilloscope
ULN1..3 ULN1..4
Oscilloscope
IL1..3 IL1..4
100
UMG 508
Connection example
Digital Outputs 1-5 Digital Inputs 5-8
RS485
Modbus/Profibus
Digital Inputs 1-4
DSUB-911 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10
5 4 3 2 1 8 7 6 5 4 3 2 1
UMG 508
Ethernet
10/100Base-TX
RJ45
Auxiliary Supply
N/- L/+
18 17
PE
Current Input 1-4
I
1
19 20 21 22 23 24 25 26
I2 I3 I4
27 28 29 30
Voltage Input 1-4
V
1 V2 V3 V4
Vref
31
L1
N
PE
L1
L2
L3
N
PE
S1
S2
S1
S2
S1
S2
S1
S2
SPS SPS
Switch
PC PC
Loading...