janitza UMG505 Operating Instructions Manual

Page 1
Universal Measuring Device
UMG505
Operating Instructions
Brief instructions see last page
Doc. No.: 1.023.034.b HW: series 1
Janitza electronics GmbH
Vor dem Polstück 1 D-35633 Lahnau Support phone (0049-6441) 9642-22 Fax: (0049-6441) 9642-30 e-mail: info@janitza.de Internet: http://www.janitza.de
Mean value
Indicated phase,
- Phase against N,
- Phase against Phase,
- Sum measurement.
Peak values Lowest values Mark for the selected values for ring buffer
Consumption Supply
Key 1
Indication of mode
Key 3 Key 2
Current transformer Harmonic number / Energy meter Voltage transformer Device address
Page 2
2
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Table of contents
Generals 5
Receipt control 5 Meaning of symbols 5 Hints for maintenance 5
Product description 6
Intended use 6 Hints for usage 6 Support 6 Functional description 7
Measurement 7
Hints for installation 8
Supply voltage 8 Measuring voltage 8 Measuring current 9 Serial interfaces 12
RS485 (Option) 12 RS232 (Option) 12 LON-Bus (Option) 13
Digital inputs 14 Digital outputs 16 Analogue outputs 17
Putting into service 18
Check all phase power 19 Check sum power 19 Removal of errors 20
Usage and display 22
Measured value indications 23 SELECT Mode 23 Configuration menu CONF 23 Programming menu PRG 23
Mean values 24 Minimum and maximum values 25 Energy measurement 26
Time of deletion 26 Show running time 27
Harmonics 27
Total harmonic distortion THD(f) 27 Partial harmonic content 27
EMAX 28
Real power EMAX 28 Pulse input 28 Target values 28 Monthly EMAX peak values 28 Reset of the measuring period 29
Memory 30
Event memory 30 Ring buffer 31 Ring buffer data format 32 Changeover ring buffer 32 Read ring buffer 32
Programming menu PRG 34
Select menu PRG 34 Delete all min/max values 35 Delete max/min val. individually 35
Delete real and reactive energy 36 Program ring buffer 37
Mean values 37 Reset of measuring period EMAX 37
Averaging time 38
Set averaging times 38
Period of storage 38
Page 3
3
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Configuration 39
Current transformer 40 Voltage transformer 40 Aron circuit 41 Data logging 42 Serial interfaces 43
RS485 interface (Option) 43 Terminal resistors 43 RS232 interface (Option) 43 Modem 43 Modbus RTU 44 Transmission mode 44 Transmission parameters 44 Realized functions 44 LON interface (Option) 45
Device address 46 Measured value rotation 46
Program changing time 47 Program measured value selection 47
Set event memory 48 Net frequency 49 Limit supervision 50 Switching clock 55
Swich-on and switch-off time 56 Switching clock channel 56 Output channel 56
EMAX target value (Option) 58 EMAX digital outputs (Option) 58
Connection power and connection time 58 Disconnection time 59
EMAX analogue outputs 60 Digital Inputs 62
Digital input 4 62 Changeover of EMAX targ. val. (Option) 64 Activate energy meter 64 Synchronize internal clock 65 EMAX measuring period reset 65
Pulse valence 66 Pulse width 72 Analogue outputs 73
Source, destination and scale 73 Programming 74 Scale 75 Output range 76
LCD contrast 78 Clock 79
Summer-/Winter time changeover 79
Password 80
Clearance password 80 User password 81 Master password 81
Serial number 82 Software Release 82
PSW505 83
PC hardware 83 PC operating system 83 Functions 83
Configure the UMG505 83 Configure measured value indications 83 Read memory 83
Tables 84
Table 1a, Measured values 85 Table 1b, Messwerte 86 Table 2a, Time information 87 Table 2b, Time information 88 Table 3, Mean values 89 Table 4a, measured values 90 Table 4b, measured values 91 Table 4c, maximum values 92 Table 4d, Minimum values 93 Table 5, read energy 94 Table 6, delete energy 94 Table 7, energy 94 Table 8, EMAX-maximum values 94 Table 9, Scale 95 Table 10, Inputs and outputs 96 Table 11, LON variables 98 Measured value indications (Presettings) 100 Configuration data 104 Measured and calculated quantities 107 Indication range and accuracy 107
Technical Data 108
Design for panel mounting 110
Back side 110
Version for DIN rail mounting (Option) 110
Back side 110 Side view 110 Side view 110
Connection example 111
Brief instructions 112
Current transformers 112 Voltage transformer 112 EMAX-target 112
Page 4
4
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Issue note
04.06.02 First edition.
26.06.02 Ring buffer data format. Page 92; Table 7, double.
09.08.02 Total harmonic distortion.
27.09.02 LON-Table.
06.09.03 Page 55, principle diagram.
19.09.05 LON-Table.
All rights reserved. No part of this manual may be reproduced or duplicated without the written permission of the author. Any contraventions are punishable and will be prosecuted with all legal means.
No liability can be taken for the faultless condition of the manual or damage caused by the use of it. As failures cannot be avoided completely, we shall be very grateful for any advice. We will try to remove any failures as soon as possible. The mentioned software and hardware descriptions are registered trademarks in the most cases and are subjected to the regulations by law. All registered trademarks are property of the corresponding companies and are fully recognized by us.
Page 5
5
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Generals
Receipt control
In order to ensure a perfect and safe use of the device, a proper transport, expert storage, erection and mounting and careful usage and maintenance are required. When it may be supposed, that a safe operation is no longer possible, the device has to be put out of service and be protected against unintentional putting into service. A safe operation can no longer be assumed, when the device
• shows visible damage,
• does not work in spite of intact net supply,
• has been exposed to disadvantageous conditions for a longer time (e.g. storage out of the allowed climate without adaption to the room climate, dew etc.) or transport use (e.g. falling from great height, even without visible damage).
Please test the contents of delivery for completion, before starting the installation of the device. All deli­vered options are listed on the delivery papers.
Attention!
All plugs, which belong to the contents of delivery, are plugged on the device
The operating instructions also describe some Op- tions, which do not belong to the contents of delivery.
Warning of dangerous electrical tension.
This symbol shall warn you about possible dangers, which can occur while mounting, putting into service and use of this device.
Connection of protective wire
Meaning of symbols
The symbols, used in this manual have the following meaning:
Hints for maintenance
Before delivery the device is tested in various safety checks and marked with a seal. If the device is opened, these checks must be repeated. There is no guarantee for devices, which are opened out of the manufacturing works.
Repairing and calibration Repairing and calibration work can be carried out in the manufacturing works only.
Front foil The cleaning of the front foil must be done with a soft cloth using a common cleansing agent. Acid or acidic agents may not be used for cleaning.
Battery The life expectance of the battery is 5 years minimum for a storage temperature of +45°C. The typical life expectance of the battery is about 8 to 10 years. The battery is plumbed and should be exchanged in the manufacturing works only.
Waste management The UMG 503 can be disposed as electronical waste according to the legal regulations and recycled. Please note, that the input Lithium battery must be disposed separately.
Page 6
6
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Product description
Intended use
The UMG505 is designed for fix mounting in low and medium voltage switchgear and for measurement of voltage, current, power, energy and harmonics etc. Real and reactive energy can be given out via pulse signal at the digital outputs. The results of the measurement can be used for controlling consumers in energy distributions or energy generation.
The measurement with the UMG 505 can be carried out in TN-, TC- and IT-networks. Alternating voltage (50Hz/60Hz) up to 500VAC against ground and 870VAC outer conductor against outer conductor can be connected directly to the voltage measuring inputs. The voltage measuring inputs must be connected via external fuses 2A (medium time lag) to the UMG505. Voltage over 500VAC against ground must be connected via voltage transformers. The voltage measurement via voltage transformers can be carried out with two or three voltage transformers by choice. To the current measurement input, .../5A or .../1A current transformers can be connected by choice. In networks with voltage up to 150VAC against ground, currents up to 5.2A can be connected directly to the UMG 505 and be measured.
The connection of the auxiliary voltage, the measu­rement inputs etc. are on the rear side via all­insulated plug connectors. The auxiliary voltage must be connected to the building installation via a separation (switch or power switch) and a 2...10 A overload protection. A protective wire connection is necessary for operation of the UMG 505.
Attention!
Measurement in systems with pulse load is not possible, because no continuous scan­ning of the measuring signals is carried out.
Hints for usage
This device may be put into service and used by qualified personnel according to the safety regulati­ons and instructions only. Please mind the additio­nal legal and safety regulations for the respective application. Qualified personnel are persons, familiar with erection, mounting, putting into service and usage of the product and having the qualifications such as:
• education or instruction / entitlement to switch,
release, ground or characterize current circuits and devices according to the standards of safety techniques.
• education or instruction in the care and usage of
suitable safety equipment according to the standards of safety techniques.
Support
If questions should occur, which are not described within this manual, please call us directly. For the handling of your questions, we need the following information:
- Device description (see type plate),
- Serial number (see type plate),
- Software release,
- Measurement and auxiliary voltage and
- exact failure description.
We are opened for you:
Mo until Tu 07:00 until 15:00 Fr 07:00 until 12:00
Janitza electronics GmbH Vor dem Polstück 1 D-35633 Lahnau
Support:
Tel. (0049 6441) 9642-22 Fax (0049 6441) 9642-30 e-mail: info@janitza.de
Page 7
7
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Functional description
Measurement
The electronical three phase measurement system determines and digitalizes the effective values of voltages and currents in 50/60 Hz networks. Two random test measurements are carried out each second on all current and voltage measuring inputs. Signal interruptions, which are longer than 500ms are surely recognized. For each random test two periods are scanned. The scanning frequency for a 50Hz signal is 6400Hz. From those sampled values the microprocessor calculates the electrical magnitudes. These measured values are indicated within the programmable display. Highest values, lowest va­lues and programming data can be saved in a battery buffered storage. Selected measured values will be saved with date and time in a ring buffer.
Measurement in IT-networks The UMG505 can be used in IT-networks with outer conductor voltage up to 500V.
Measurement in networks without N In networks without N, the voltages are measured against an artificial neutral point (PE). From the voltage L-PE, the voltage L-L is calculated. The phase power in networks without N are used for the calculation of the sum power only, but have no further meaning.
Diagr. Drawing UMG505 in IT-networks with N.
2M 2M 2M
PE
UMG505
Voltage
measurement
Supply voltage
Impedance
Ground
2M
L2
L3
N
1n 1n
L1
Diagr. Drawing UMG505 in TN-networks.
2M 2M 2M
PE
UMG505
Voltage
measurement
Supply voltage
Ground
2M
L2
L3
N
1n 1n
L1
PE
500V 50/60Hz
230/400V 50/60Hz
Diagr. Drawing UMG505 in IT-networks without N.
2M 2M 2M
PE
UMG505
Voltage
measurement
Supply voltage
Impedance
Ground
2M
L1
L2
L3
1n 1n
500V 50/60Hz
Page 8
8
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Hints for installation
Supply voltage
A supply voltage is necessary for the operation of the UMG 505. The kind and dimension of the required supply voltage is noted on the type plate. The supply voltage is connected to the clamps 14 and 15. Between supply voltage (terminals 14, 15) and ground (PE) a maximum voltage of 300VAC may occur. Higher voltage between supply voltage and ground (PE) can destroy the UMG505. To avoid overvoltage, the supply voltage should be earthed.
Measuring voltage
The UMG505 is suitable for measurement of alternating voltage up to 500VAC against ground and 870VAC between the outer conductors. The wiring must be suitable for voltage up to 500VAC against ground and 870VAC between the outer conductors as well.
Attention!
The UMG505 is not suitable for measurement of direct current voltage.
Voltage over 500VAC against ground must be connected via voltage transformers.
For voltage measurement via two voltage transformers, the „Aron connection“ must be set in configuration mode of the UMG 505.
The wires for voltage measurement of the UMG 505 must be protected by an overcurrent fuse.
Attention!
- The connection wires of the supply voltage must be suitable for rated voltage up to 300VAC against ground.
- The supply voltage must be protected by a fuse. The fuse must be in the range of 4A up to 10A.
- A switch or power switch for the supply voltage must be provided within the building installation.
- The switch must be near the device and easy to reach by the user.
- The switch must be marked as a separation for the device.
- Please ensure before connecting the supply voltage, that voltage and frequency match the statements on type plate!
- The device may be operated with earthed housing only!
- Cables with sigle soldered wires cannot the connected via screw terminals!
- The screw terminals may be plugged in voltage free condition only.
- Only screw clamps with the same pole number and the same colour may be connected.
- The supply voltage for the UMG 505 may not be taken from voltage transformers. Switching procedures on medium voltage side can lead to short duration overvoltage, which can destroy the supply voltage input of the UMG 505.
Page 9
9
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Attention!
Current transformers can lead voltage, which is dangerous to touch and should be earthed.
Current transformers, not loaded at the secondary, can lead voltage dangerous to touch and should be short circuited.
Measuring current
The UMG505 is designed for the connection of current transformes with secondary currents of ../1A and ../5A. When the device is delivered, a current transformer of ../5A is set. Each currrent measurement input can be loaded with 5,2A over a long period or for 2 seconds with 180A. Via the current measurement inputs only alternating current can be measured but no direct current..
Page 10
10
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Diagr. 1 Medium voltage measurement with three voltage transformers and three current transformers.
L/L 80 .. 870V AC
L/PEN 50 .. 500V AC 0,005 .. 5A
27 26 25 24
23 22 21 20 19 18 14 15
L1 L2 L3 PE
2A
L1 N
Messung
Mesurement
Hilfs-
spannung
Auxiliary
Voltage
UMG505
k l
k l
k l
../5(1)A
../5(1)A
../5(1)A
10160400
Verbraucher
Consumer
4-
10A
L1 L2 L3
u u u
x x x
X X X
U U U
Diagr. 2 Medium voltage measurement with two voltage transformers and three current transformers.
L/L 80 .. 870V AC
L/PEN 50 .. 500V AC 0,005 .. 5A
27 26 25 24
23 22 21 20 19 18
14 15
u v PE
2A
L1 N
Messung
Mesurement
Hilfs-
spannung
Auxiliary
Voltage
UMG505
L1 L2
L3
k l
k l
k l
../5(1)A
../5(1)A
../5(1)A
10160410
Verbraucher
Consumer
4-
10A
u v u v
U V U V
Diagr. 4 Medium voltage measurement with two voltage transformers and two current transformers.
Messung
Measurement
Hilfs-
spannung
Auxiliary
Voltage
UMG505
27 26 25 24
23 22 21 20 19 18 14 15
u v PE
2A
L/L 80 .. 870V AC
L/PEN 50 .. 500V AC
0,005 .. 5A
10160430
u v u v
U V U V
k l
k l
../5(1)A
../5(1)A
Verbraucher
Consumer
4-
10A
Diagr. 3 Medium voltage measurement with three voltage transformers and two current transformers.
Messung
Measurement
Hilfs-
spannung
Auxiliary
Voltage
UMG505
27 26 25 24
23 22 21 20 19 18
14 15
u1 u2 u3 PE
2A
L1
L2 L3
k l
k l
../5(1)A
../5(1)A
L/L 80 .. 870V AC
L/PEN 50 .. 500V AC
0,005 .. 5A
Verbraucher
Consumer
u u u
x x x
U U U
X X X
10160420
4-
10A
Page 11
11
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Diagr. 5 Measurement in IT-networks
with N
.
L/L 80 .. 870V AC
L/PEN 50 .. 500V AC 0,005 .. 5A
27 26 25 24
23 22 21 20 19 18 14 15
L1 L2 L3 N
2A
L1 N
Messung
Mesurement
Hilfs-
spannung
Auxiliary
Voltage
UMG505
L1 L2
L3 N
k l
k l
k l
../5(1)A
../5(1)A
../5(1)A
230V/400V 50Hz
10160990
Verbraucher
Consumer
4-
10A
PE
Diagr. 6 Measurement in IT-Netz without N.
L/L 80 .. 870V AC
L/PEN 50 .. 500V AC 0,005 .. 5A
27 26 25 24 23 22 21 20 19 18 14 15
L1 L2 L3 N
2A
L1 N
Messung
Mesurement
Hilfs-
spannung
Auxiliary
Voltage
UMG505
L1 L2
L3
k l
k l
k l
../5(1)A
../5(1)A
../5(1)A
230V/400V 50Hz
101609100
Verbraucher
Consumer
4-
10A
PE
Diagr. 7 Measurement in TN-networks with three current transformers.
L/L 80 .. 870V AC
L/PEN 50 .. 500V AC 0,005 .. 5A
27 26 25 24
23 22 21 20 19 18 14 15
L1 L2 L3 N
2A
L1 N
Messung
Mesurement
Hilfs-
spannung
Auxiliary
Voltage
UMG505
L1 L2 L3
N
k l
k l
k l
../5(1)A
../5(1)A
../5(1)A
230V/400V 50Hz
10160440
Verbraucher
Consumer
4-
10A
PE
Page 12
12
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Serial interfaces
RS485 (Option)
Terminal resistors
All devices are connected in bus structure (line). In a segment, up to 32 participiants can be connected. At the beginning and at the end of a segment the cable is terminated with resistors. In the UMG505 these terminal resistors can be activated with pluggable bridges. For more than 32 participiants a repeater must be used (amplifier), to connect the single segments.
Protection
For connections via RS485 interface, a twisted and protected cable must be used. To reach the required protection, the shield must be connected to housing parts at both ends of the cable over a wide surface.
Cable type
Unitronic LI2YCYCTPJ2x2x0,22 (Lapp Kabel)
Cable length
1200m at baudrate 38,4k.
RS232 (Option)
The maximum distance between two devices with RS232 depends on the used cable and the baud­rate. The normal distance for a baudrate of 9600 Baud should not exceed 15 up to 30 meters. The allowed load must be bigger than 3kOhm, The capacitive load, caused by the transmission cable, is limited to 2500pF.
Diagr. Connection of two devices with RS232 interface
Terminal resistor Device with RS485 interface
Diagr. Bus structure with terminal resistors on both sides.
Converter
RS485/RS232
PSW505
Protocol 01 = MODBUS
UMG505 UMG505
RS232
RS485
RS232 RS485
RS232 RS232
Protocol 02 = Modem
Customer’s software
Modem
RxD TxD on
Modem
RxD TxD on
UMG505
Zero modem cable
Protocol 01 = MODBUS
PSW505
UMG505
RS232 RS232
Page 13
13
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
LON-Bus (Option)
For the connection of the UMG505 with other LON­bus devices a FTT10-transceiver is used within the UMG 505. Hence, the bus is safed against change of polarity and can be connected at one or two sides. Devices, that use a FTT10 -transceiver, can be connected to each other via line, star or ring structures. If the allowed transmission impedance is reached within a structure, the network can be enlarged by using repeaters or routers.
Free wiring
For free wiring and bus connection at one end, the maximum cable length may be 500m, and the maximum distance between two devices may be 400m.
Bus wiring
For bus wiring and connection at both sides, the to­tal cable length may be 2700m at maximum. The UMG 505 does not have a connectable terminal resistor for LON-bus.
Allowed cable length
Depending on the selected structure of the network and the chosen cable type, different transmission distances can be achieved.
Diagr. Free structure
Diagr. Bus structure with terminal resistors at both ends.
Termination or central feeding
Device with LON bus
Terminal resistor
Cable type Length
TIA 568A Category 5 < 900m Belden 85102, 16AWG < 2700m Belden 8471 < 2700m Level IV, 22AWG < 1400m JY (St) Y 2x2x0.8, 20AWG < 900m
Diagr. Maximum distance for bus wiring.
Diagr. Maximum length at free wiring.
Length
Cable type Total device - device
TIA 568A Category 5 500m < 250m Belden 85102, 16AWG 500m < 500m Belden 8471 500m < 400m UL Level IV, 22AWG 500m < 400m JY(St)Y 2x2x0.8, 20AWG 500m < 320m
Diagr. Connection LON-Bus
UMG505
LON-Bus
FTT-10A
GND
LON Bus
1
2
Page 14
14
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Digital inputs
The UMG 505 has four digital inputs, to which signal senders can be connected.
Digital Input 1 Digital Input 2 + 3
Digital Input 4 The inputs are separated by optical couplings and have different electrical properties. Only input 1 can operate with direct or alternating current voltage signals. Input 4 can be used as pulse input for real energy measurement as well.
Voltage version 2 For UMG's, which are driven with a supply voltage of "15 .. 55VAC, 20 .. 80VDC" (Option), the
Digital
Input 1
can be activated with an
alternating current voltage of 15 .. 55VAC or direct current voltage of 20 .. 80VDC .
Voltage version 3 For UMG's, which are driven with a supply voltage of "40 .. 115AC, 55 .. 165VDC" (Option), the
Digital
Input 1
can be activated with an
alternating current voltage of 40 .. 115VAC or direct current voltage of 55 .. 165VDC .
Diagr.: Digital Input 1 only for alternating current voltage.
17
16
Digital Input 1
AC
UMG505
Digital inputs
85..265VAC
Diagr.: Digital Input 1 for direct or alternating
current voltage.
17
16
Digital Input 1
UMG505
Digital inputs
15k
AC/
DC
40..115VAC
55..165VDC
Digital Input 1
The operating voltage for
Digital Input 1
depends on
the allowed supply voltage of the UMG 505.
Voltage version 1 In the standard version, the UMG 505 is driven with the supply voltage of "85 .. 265VAC, 120 .. 370VDC". In this case, the
Digital Input 1
is activated with alternating current voltage of 85 .. 265VAC .
17
16
Digital Input 1
UMG505
Digital inputs
6,8k
Diagr.: Digital Input 1 for direct or alternating
current voltage.
AC/
DC
15..55VAC
20..80VDC
Input 1-4
5
4
3
Digital
Input 3
Digital
Input 2
5,1 k
5,1 k
17
16
Digital
Input 1
7
7
Digital
Input 4
ZMM 3V9
1,5 k
4k
UMG505
Digital inputs
Diagr.: Internal circuit of the digital inputs.
Page 15
15
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Digital Input 4
Input 4 can be used as a pulse input according to DIN EN62053-31 or as digital input. For the operation, an external supply voltage of 20..30V DC is required.
Digital Input 2 and 3
Both inputs Digital Input 2 and 3 can be controlled by a direct current voltage signal. For the operation, an external supply voltage of 20..30V DC is required.
UMG505
Digital inputs
+
-
Diagr.: Connection proposal; Digital Input 4 as pul­se input.
7
6
Digital
Input 4
ZMM 3V9
1,5 k
4k
Pulse
generator
DC
24V
Diagr.: Connection proposal; Digital Input 2 and 3 with external supply voltage.
5
4
3
Digital
Input 3
Digital
Input 2
5,1 k
5,1 k
UMG505
Digital inputs
DC
+
-
S1
S2
24V
Page 16
16
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Digital outputs
The UMG505 has 5 transistor switching outputs. These outputs are separated from the evaluation electronics via optical couplings. The collectors of the transistors are connected together with plus po­tential (terminal 36).
+24V=
36
35
34
33
32
31
Digital
Output 5
Digital
Output 4
Digital
Output 3
Digital
Output 2
Digital
Output 1
UMG505
Digital outputs
K1
K2
Diagr Connection of two relays to the digital outputs.
+-
230V AC
24V DC
External
Supply
Page 17
17
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Analogue outputs
The UMG505 has 4 analogue outputs. Each analogue output can transmit a current of 0-20mA or 4-20mA. For the operation, an external net supply of 24VDC is required.
L+
M
Diagr. Connection of the analogue outputs to a PLC.
+
+
-
+24V=
0V
12
10
9
8
13
11
0/4 - 20mA
0/4 - 20mA
0/4 - 20mA
0/4 - 20mA
22 Ohm
Analogue output
4
Analogue output
3
Analogue output
2
Analogue output
1
UMG505
Analogue Outputs
PLC
Analogue inputs
M+
M+
M+
M+
M-
M-
M-
M-
+
+
+
-
-
230V AC
24V DC
External
supply
Diagr. Connection of an analogue output to an analogue printer.
+24V=
0V
12
10
9
8
13
11
0/4 - 20mA
0/4 - 20mA
0/4 - 20mA
0/4 - 20mA
22 Ohm
Analogue output
4
Analogue output
3
Analogue output
2
Analogue output
1
+
+
-
UMG505
Analogue outputs
Analogue
printer
+
-
External
supply
230V AC
24V DC
360 Ohm
Page 18
18
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Putting into service
The device should be put into service as follows:
1. Install the device.
The UMG505 is suitable for panel mounting in low
voltage switchgear, in which overvoltage in overvoltage class III can appear at maxi­mum.
Any mounting position is allowed. To ensure safety and functionality of the UMG 505, a protective wire connection is absolutely necessary.
2. Connect supply voltage Uh .
The size of the supply voltage Uh for the UMG505
must match the description on type plate. If
supply voltage for alternating current voltage
AC and for direct current voltage DC are
given on type plate, the UMG505 can be operated with one of these supply voltage by choice. Connected supply voltage, which do not match the type plate, can lead to malfunction or damage of the device. Between the inputs of the supply voltage Uh (terminals 14,15) and ground (PE), a maximum voltage of 300VAC may be attached. Higher voltage between supply voltage and ground (PE) can dama­ge the UMG 505. To avoid overvoltage at supply voltage input, the supply voltage should be earthed. The cables for the supply voltage must be suitable for rated voltage up to 300VAC against ground.
3. Program current and voltage
transformers
4. Connect measurement voltage.
The UMG505 is suitable for the measure­ment of voltage up to 500VAC against ground and 870VAC phase to phase.
The UMG505 is not suitable for the measu­rement of direct current voltage. Voltage over 500VAC against ground must be connected via voltage transformers. For voltage measurement with two voltage transfor­mers, „Aron Circuit“ must be entered within the con­figuration of the UMG 505. After the connection of the measurement voltage, the indicated values for voltage L-N and L-L must match the ones at measurement voltage input. If a voltage transformer ratio is programmed, it has to be respected during this comparison.
Page 19
19
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
5. Connect measurement current.
The UMG505 is designed for the connection of ../1A and ../5A current transformers. When the device is delivered, a current transformer of ../5A is set.
Each current measurement input can be loaded with
5.2A for long duration or 180A for two seconds. Over the current measuring inputs only alternating current, but no direct current can be measured. None earthed transformer clamps can be dangerous to touch. Current transformers, which are not loaded on the secondary can lead voltage dangerous to touch and should be short circuited.
The current measurement inputs should be con­nected one after the other. Please compare the current indicated by UMG 505 with the attached current. If the current transformer is short circuited, the UMG 505 must show zero A in the corresponding outer conductor. The current indicated by UMG505 must match the input current respecting the set current transformer.
6. Check measurement.
If all voltage and current inputs have been connected correctly, the phase and sum power is calculated and indicated correctly.
Check all phase power
If a current transformer is assigned to the wrong outer conductor, the corresponding phase power is indicated incorrectly. The assignment of the outer conductor to current transformer is correct, if no voltage between the outer conductor and the corresponding current transformer (primary) appears. To ensure, that an outer conductor at voltage measurement input is assigned to the right current transformer, the corresponding current transformer can be short circuited on the secondary. The apparent power, indicated by UMG 505 must be zero in this phase.
If the apparent power is displayed correctly, but the real power shows a „-“ sign, the current transformer clamps are exchanged or power is supplied to the energy supplier’ network.
Check sum power
If all voltage, current and power are displayed correctly for the corresponding outer conductors, the sum values must be correct as well. This can be confirmed by comparing the measured sum power with the energy, measured by the KW meter in the distribution.
Page 20
20
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Faults Possible reason Remedy
Indication dark External prefuse has released. Replace prefuse.
Internal prefuse has released. The fuse cannot be changed by the user. Please
send the device back to the manufacturing works. Contrast setting too dark. Change contrast settings in configuration menu. Device faulty. Please send the device to the manufacturer for
repair.
Bad legible display Contrast setting too dark Set contrast in configuration menu. No current indication Measurement voltage not Connect measurement voltage.
connected
Current too small Current measurement in the Check and correct connection.
wrong phase. Current transformer factor Read current transformer ratio on current transf. programmed incorrectly. and program correctly.
Wrong current Current measurement in the Check and correct connection.
wrong phase. Current transformer factor Read current transformer ratio on current transf. programmed incorrectly. and program correctly. Measuring range exceeded. Install bigger current transformer. The peak current value on Install bigger current transformer. meas. input was exceeded caused by harmonics. Attention: Please ensure, that the measuring
inputs are not overloaded. The current on measuring Install smaller current transformer. input was underscored.
Voltage L-N too small Measurement in wrong phase. Check and correct connection.
Voltage transformer factor Read current transformer ratio on current programmed incorrectly. transformer and program correctly.
If the voltage is not measured via voltage transf.
please program a voltage transf. ratio of 400/400. Voltage on measuring input Install smaller voltage transformer. out of measuring range.
Voltage L-N incorrect Measurement in wrong phase. Check and correct connection.
Voltage transformer factor Read current transformer ratio on current programmed incorrectly. transformer and program correctly.
If the voltage is not measured via voltage transf.
please program a voltage transformer ratio of
400/400. Measured range exceeded. Install bigger current transformer. The peak voltage value on Install bigger current transformer. meas. input was exceeded caused by harmonics. Attention: Please ensure, that the measuring
inputs are not overloaded.
Voltage L-L too small/ Outer conductors exchanged. Check and correct connection. too big N not connected. Check and correct connection.
Phase shift ind /cap too Current path is assigned to Check and correct connection. small or big the wrong voltage path. Program. data get lost Battery empty. Please send device to the manufacturer for
exchanging the battery. The device has been exposed External protection measure such as shielding, to electromagnetical interfer. filtering, earthing or spatial separation. bigger than the allowed by.
Removal of errors
Page 21
21
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Faults Possible reason Remedy
Programming data lost Battery empty Please send the device to the manufacturer for the replacement of the battery.
Real power too small / Current transformer factor Read current transformer ratio on current too big programmed incorrectly. transformer and program correctly.
Current path is assigned Check and correct connection. to the wrong voltage path. Current on measuring input Install bigger or smaller current transformer. out of measuring range.
Attention: Please ensure, that the measuring
inputs are not overloaded. Voltage transformer factor Read current transformer ratio on current programmed incorrectly. transformer and program correctly.
If the voltage is not measured via voltage
transformer
please program a voltage transformer ratio of
400/400. Current on measuring input Install bigger or smaller current transformer. out of measuring range.
Attention: Please ensure, that the measuring
inputs are not overloaded.
Real power consump./ One current transformer at Check and correct connection. supply exchanged. least exchanged.
Current path is assigned to Check and correct connection. the wrong voltage path.
The time is indicated The device has no automatical Correct time by hand. incorrectly. summer-/winter change over.
"EEEE A" in the display. The measuring range of Check measuring current and insert a suitable current current was exceeded. transformer.
"EEEE V" in the display The measuring range of Check measuring voltage and insert a suitable voltage voltage was exceeded. transformer.
Duration of mem. =38s. Not enough memory for all Select more equal averaging times for the measured selected values. values.
Relay output, analogue The outputs are not program. Program the outputs. output or pulse output do not react. The service protocol 04 is set Select another protocol.
The device does not Device out of order. Please send the device to the manufacturer with work correctly in spite an exact description of the failure. of the above
Page 22
22
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Usage and display
After net return, the UMG 505 shows always the first programmed measured value indication. The use of the UMG 505 is carried out via the three keys in the front.
=
Key 1
=
Key 2
=
Key 3
In the various indications, the keys have different mea­nings.
If you are in the measured value indication, you can change over to the below mentioned indication by using key 1.
the measured value indication, the SELECT mode, the configuration menu CONF and the programming menu PROG
SELECT
PRG CONF
Measured
values
Key 1 Key 2 Key 3
In configuration menu CONF and in programing menu PRG, the settings can be changed in edit mode EDIT. In edit mode EDIT the keys have the following meaning:
Key 1
Select digit/number and leave edit mode.
Key 3
Change numbers.
Key 2
Multiplication of a number with factor 10
Pressing key 1 for about 2 seconds, you return to the first measured value window of the measured value indication. Pressing
key 2
or
key 3
for about 2 seconds you
return to the previous measured value window.
Press Key 1
for 2 seconds.
Diagr. Menu overview
PRG
PRG
SELECT
PRG
Select averaging
times,
Read storage duration
of the ring buffer...
Voltage transformer,
Aron circuit,
Data logging,
Serial interfaces,
Device addresses,
....
CONF
CONF
A
A
SELECT CT
CONF
A
A
CT
SELECT
Measured values
SELECT
Show additional
information
SELECT
Measured values
Select phase
Measured values
Measured values
Measured values
Page 23
23
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
SELECT Mode
For various measured values, it is possible to call up additional information directly in the measured value indications. For this purpose, you change into the SELECT Mode in the corresponding measured value indication. Now the following additional indication for the measured values can be called up:
- Mean values and their averaging time.
- Minimum and maximum values with date and time.
- Time of deletion and running time of the energy measurement.
- The energy meters of the digital inputs.
Programming menu PRG
In programming menu PRG the minimum and maxi­mum values and energy can be deleted.
A
A
SELECT CT
CONF
Configuration menu CONF
In configuration menu CONF the settings, which are necessary for the operation of the UMG 505, are deposited. Besides others, it is the setting of the current transformer, device address and program­ming of the inputs and outputs. In delivery condition, these settings are not protected and can be changed. Unintentional change of the settings can be avoided by setting a password.
SELECT
PRG
Measured value indications
After a net return the device always starts with the first programmed measured value indication. In the indication of the UMG 505 up to three measured values can be indicated simultaneously. With the keys 2 and 3 one can scroll through those measu­red value indications. In order to keep the selection of measured values clear, only a part of the available measured values are programmed, when the device is delivered. If other measured values are desired for the display of UMG 505, They can be selected via the program­ming and evaluation software PSW505, which belongs to the contents of delivery, and a PC, and transmitted to PC via the serial interface of the UMG
505.
Example: Current transformer setting, primary 5000A and seconda­ry 5A.
Example: Delete minimum and maximum values.
Example: Voltage L1-N, L2-N, L3-N.
V
V
V
L3
L1
L2
Page 24
24
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Using
key 3
you scroll to the measu­red value indication of the real power.
Pressing
key 2
you
scroll to the mean
values of real power.
kW
kW
kW
L3
L1
L2
Select the SELECT mode using
key
1.
Confirm with
key 2
. The symbol SELECT is on.
kW
L3
SELECT
kW
kW
kW
L3
L1
L2
kW
L1
SELECT
Select the mean value of the real po­wer in L3 using
key
1
.
Call up the averaging time for the real power in phase L3 as an addi­tional information using
key 2
.
kW
M.S
L3
SELECT
Averaging time = 15 Minutes
Mean values
For the most measured values a mean value is build over the last passed period of time within the UMG 505 each second. This passed period of time is the programmable averaging time.
The calling up - in the example for the power maximum value in phase L3 - is carried out as follows:
Only mean values can be marked for storage in the ring buffer.
Press
key 1
for about 2 seconds and you return to the first measured value window of the measured value indication from each program part.
0123456 t/Sec.
Diagr.: Mean value for real power over 5 seconds.
Indication of a new mean value for the real power.
Mean value for the 5. minute
Mean value for the 6. minute
Mean value for the 7. minute
Page 25
25
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Move to the measu­red value indication of the current using
key
3
.
A
A
A
L3
L1
L2
Go to the maximum values of current using
key 2
.
Chose the Select mode with
key 1
. The symbol SELECT flashes.
Confirm with
key 2
. The symbol SELECT is on.
Call up additional in­formation date and time for the maximum value of current using
key 2
.
A
L3
L1
L2
A
A
Y.M
D.H
M.S
SELECT
Year=98 Month=10 Day=25 Hour=08
Minute=10 Second=31
A
L1
SELECT
Select the maximum current value in L2 using
key 1
.
Minimum and maximum values
For the most measured values (see table measured and calculated quantities) the minimum and maximum values are saved. The minimum value is the smallest measured value, which was detected since the last deletion. The maximum value is the biggest measured value, which was detected since the last deletion. Every measured value is compared to the saved minimum and maximum values, which are overwritten in case of exceeding. For each minimum and maximum value, the first existance is saved with date and time. After return of supply voltage, all minimum values are deleted automatically. Minimum values are marked with an arrow downwards and maximum values with an arrow upwards.
The maximum value of the current mean value, for example, is indicated as follows:
L2
A
SELECT
Example: Call up a maximum value The maximum value „current in L2“ shall be called up:
A
A
A
L3
L1
L2
Maximum value
Current
Mean value
The highest measu­red current mean value is:
I
L1
= 150A
I
L2
= 150A
I
L3
= 150A
When the device is delivered, most of the minimum and maximum values can be called up via the keys 1 and 2. If you are interested in date and time of the minimum and maximum values, this information can be called up by the SELECT function. All minimum and maximum values can be deleted all together or individually with the function PRG.
On 25.10.1998 at 08:10:31 appeared the maximum measured value of current in L2 since its last deletion.
Press
key 1
for about 2 seconds and you return to the first measured value window of the measured value indication from each program part.
Page 26
26
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Energy measurement
In the UMG505, all in all 30 energy meters are at your disposal. 24 meters can be cont­rolled by tariff chan­geover. When the device is delivered, 12 energy meters are displayed in the measured value indi­cation.
M VArh
kVArh
VArh
L1 L2 L3 ind
T
Press key 2 again. The time of deletion for real energy is indicated.
Year =01, Month =09 Day =06, Hour =08 Minute =15, Sec.=41
Time of deletion
For each energy meter, the running time is saved. If real energy or reactive energy is deleted, all corresponding tariffs are deleted as well. The time of deletion is saved and running time is started again. As all real and reactive energy can be deleted simultaneously, there is one time of deletion only for all real and reactive energy meters.
The time of deletion can be called up directly within the measured value indications as additional information for the energy meters, provided this energy meter is configured for measured value indication (see manufacturer settings).
Example: Call up deletion time for real energy The time of deletion can be called up in the measured value indication of real energy. To reach the first measured value indication from each programming part, press key 1 for about 2 seconds.
M Wh
kWh
Wh
L1 L2 L3
T
SELECT
Y.M
D.H
M.S
Chose select mode using key 1. The symbol SELECT flashes.
Confirm with key
2
. The symbol SELECT is on.
SELECT
M Wh
kWh
Wh
L1 L2 L3
T
When the device is delivered, only the grey meters can be called up within the measured value indicati­on.
Energy meter
Changeable
Real energy Without rev. run. stop T50 T51 T52 T53 T54 Consumption T00 T01 T02 T03 T04 Supply T30 T31 T32 T33 T34 Reactive energy Without rev. run. stop T40 T41 T42 T43 T44 inductive T10 T11 T12 T13 T14 capacitive T20 T21 T22 T23 T24
Diagr. Overview energy meters
Scroll to measured value indication of real power T00 by pressing key 3.
Press
key 1
for about 2 seconds and you return to the first measured value window of the measured value indication from each program part.
Page 27
27
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Chose select mode using key 1. The symbol SELECT flashes.
Confirm with
key 2.
The symbol SELECT is on.
Press
key 2
twice. The running time for real energy T00 is indicated.
Days=02, Hours=04 Minutes=15, Sec.=41
Show running time
Each energy meter, besides of the 6 non controllable energy meters TX0, can be controlled via the digital inputs and internal swiching clock. For each energy meter, the duration of energy measurement with the corresponding running time is saved.
Example: Running time for real energy T00: The running time for real energy can be called up in the measured value indication. From each program part, you reach the first measured value indication by pressing key 1 for about two seconds.
M Wh
kWh
Wh
L1 L2 L3
T
SELECT
M Wh
kWh
Wh
L1 L2 L3
T
Pressing
key 3
you scroll to the measured value indication of energy T00.
SELECT
Y.M
D.H
M.S
Harmonics
Harmonic waves are the integer multiple of the fun­damental. The UMG505 measures the fundamental of voltage in the range of 45 up to 65Hz. The calculated harmonic current and voltage are related to this fundamental. For strongly distorted voltage, the fundamental cannot be detected with sufficient accuracy. In order to calculate the harmonics nevertheless, a fix fundamental can be assumed with either 50Hz or 60Hz. Please see chapter „Scanning frequency“. The UMG505 calculates harmonics up to the 20th.
Total harmonic distortion THD(f)
The calculated total harmonic content THD(f) represent the effective ratio of harmonics to the fun­damental. The total harmonic distortion is given in %.
Press
key 1
for about 2 seconds and you return to the first measured value window of the measured value indication from each program part.
I
212
THD
II
I
=
­ x
100%
U
212
THD
UU
U
=
­ x
100%
Partial harmonic content
In the further description, the single harmonics are called partial harmonics. The partial harmonics for current are given in Am­pere, the partial harmonics for voltage are given in Volt.
Page 28
28
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
EMAX
Real power EMAX
For the real power the mean value real power EMAX is build over a programmable measurement
period additionally. Here the measured value „sum real power“ is summarized each second and divided by the measuring period time. As a result, each se­cond a new mean value „real power Emax“ is at disposal. At the end of a measuring period, the sum is deleted, and the measuring period starts again. For the comparison and storage of the monthly Emax peak values, only that real power Emax is used, which was measured at the end of a period.
Monthly EMAX peak values
All monthly EMAX peak values are saved for all EMAX target numbers each month. The old monthly EMAX peak values are overwritten at the beginning of a new year. If the real power EMAX is configurated for the display software PSW505, real power EMAX can be indicated in the display of the UMG 505 as well. The monthly EMAX peak values can be read out directly at the UMG505 and via the serial interface, with the software PSW505, for instance.
EMAX target number
Attention!
The „Monthly EMAX peak values“ are not indicated in the standard display configura­tion, when the device is delivered. Those indications can be configured with the software PSW505, which belongs to the contents of delivery.
Pulse input
The measured value „Sum real power“ is calculated from the measured current and voltage, when the device is delivered. But if a pulse valence is assigned to „Digital Input 4“, „sum real power“ is calculated from pulse number and valence. The real power of the single phases will be calculated by the current and voltage, which the UMG 505 measures furthermore.
Target values
For the EMAX program in the UMG 505, 5 targets can be given. If no more settings were made, the target 1 is active. Via the input channels 1-16 and via the switching clock, one of the 5 target values can be selected and assigned to the Emax program. If a target value is activated via the input channels and at the same time another via the switching clock, the target with the highest number (priority) of Emax program is used. Please note:
Target number 1 = low Target number 2 = high
Diagr.: Calculation of mean value for real power EMAX over a measurement period of 15 minutes.
0 5 10 15 20 25 30 t/Min.
1. Measurement period 2. Measurement period
End of measurement periods
Month
Day . Hour Minute
W
D.H
M.
L1 L2 L3
Real power EMAX
Peak value
Page 29
29
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
With
key 3
you scroll to the indication of real power EMAX.
Real power EMAX (Example 100W). Rest time of period (Example. 8Min. 10Seconds). Measuring period (Example 15Minutes).
Reset of the measuring period
The averaging time for real power Emax is called measuring period. The measuring period for real power Emax can be 5, 10, 15, 30 and 60 minutes. The manufacturer’s setting is 15 minutes. To be synchronized with the measurement of the energy supplier, the reset of the measuring period should be carried out via an input of UMG 505. If no reset via an input of UMG 505 occurs within the pro­grammed measuring period, the reset is released automatically by the internal clock. The reset of the measuring period deletes real po­wer Emax and starts a new measuring period. The last measured real power Emax is used for the minimum and maximum storage and, if program­med, saved in the event memory. If there are less than 30 seconds between two resets, the measuring period is reset and real po­wer EMAX is deleted. The obsolete measured value is not saved in the maximum and minimum memory and not be deposited within the event memory, if programmed.
The measuring period for real power EMAX can be reset by the following means:
- automatically, after measuring period,
- internally, via keyboard,
- internally, via digital inputs,
- externally, with MODBUS Protocol,
- externally, with LON Bus. The automatical reset after measuring period can­not be suppressed.
Press
key 1
for about 2 seconds and you return to the first measured value window of the measured value indication from each program part.
W
M.S
L1 L2 L3
With
key1
go to Select-Mode. The symbol SELECT flashes. Confirm with
key 2
. The symbol SELECT is visible.
Press
Key2
again. The rest time is deleted.
The symbol SELECT disappears. The period for real power EMAX is started again.
W
M.S
L1 L2 L3
SELECT
W
M.S
L1 L2 L3
Reset of measuring period by keyboard
Attention !
A change of
- the averaging time,
- the measuring period,
- the current transformer ratio,
- the voltage transformer ratio,
- the measurement (Aron circuit) or
- the measured value selection for ring buffer delete the ring buffer.
Page 30
30
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Memory
The memory of the UMG 505 is deviced into three ranges. The event memory, the maximum and minimum memory and the ring buffer. The event and the ring buffer can be read out with the program PSW505 and PC only. The data which are read out by PC are available in ASCII format.
In the minimum and maximum memory, the minimum and maximum values are deposited with date and time. All monthly EMAX peak values are saved for all tariffs each month. The obsolete monthly Emax peak values are overwritten at the beginning of a new year.
Event memory
In the event memory, the following events can be saved with date and time:
- Deletion of event memory,
- Change of the digital inputs,
- Change of the digital Emax outputs,
- Breakdown and return of the supply voltage,
- Breakdown and return of the measurement
voltage,
- Threshold violations. The event memory can be read out with PC and the programming and reading out software PSW505 only. The breakdown of the measurement voltage will be recognized, when:
- the measurement voltage is smaller than
50% of the set primary of the voltage transformer,
- and the breakdown remains longer than
500ms without interruption.
In the device, a part of the memory is available, which are shared by the ring buffer and the event memory. Here, the size of the event buffer can be set in menu „Prot“ by programming the number of saved events. If the number is set to "0", the whole memory is available for the ring buffer.
If the number of events, that are saved, are changed, the event memory and ring buffer are deleted.
Page 31
31
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Ring buffer
For the most measured values a mean value is calculated (please see table "Measured and calculated values"). Mean values are marked with a horizontal bar above the measured values. The mean values, selected for storage in the ring buffer, are marked by both of the arrow symbols. For the storage in ring buffer, the following values can be selected in menu PRG of the UMG505
- the mean values of measured values,
- the EMAX reset of the measuring period and
- a part of the energy meters (Tx0)
The changeable energy meters (see table below) can be selected with the programming software PSW505 only for saving in the ring buffer. For energies, the period between two savings is set to one hour.
Storage duration
The more mean values are marked for saving in the ring buffer, the shorter becomes the storage duration. When the device is delivered, the setting Mean values: U1, U2, U3, I1, I2, I3, P1, P2, P3 Averaging time: 15 Minutes leads to a storage duration of about 1 year. If this time is exceeded, the most obsolete values are overwritten. If various averaging times are assigned to the mean values, more memory is required, and the storage duration becomes shorter. To enlarge the storage duration, the number of saved values can be decreased, or all values should be programmed for saving with the same averaging time.
Attention !
A change of
- the averaging time,
- the measuring period,
- the current transformer ratio,
- the voltage transformer ratio,
- the measurement (Aron circuit) or
- the measured value selection for ring buffer delete the ring buffer.
The more mean values are selected for storage in the ring buffer, the earlier the ring buffer is complete and will be overwritten. The period of storage for the ring buffer can be read out in the measured value indication. The stored measured values can be read out of the ring buffer using the "programming- and reading out software PSW505" only.
Energy meter
Fix Changeable
Real energy without rev. run. stop T50 T51 T52 T53 T54 Consumption T00 T01 T02 T03 T04 Supply T30 T31 T32 T33 T34 Reactive energy without rev. run. stop T40 T41 T42 T43 T44 inductive T10 T11 T12 T13 T14 capacitive T20 T21 T22 T23 T24
Diagr. Overview of energy meters.
Page 32
32
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Ring buffer data format
Data sets can be saved in compressed or uncom­pressed form. With the presettings, the data are saved compressed. The programming and reading out software PSW505 can read compressed data from ring buf­fer only. Other applications can read data sets in un­compressed form only. An uncompressed data set consists of the type of measured value, the date and the measured value. This value is always given in Float format.
1)
r/w = read/write
2)
Measured values {float: Actual value[L1, L2, L3], Mean value[L1, L2, L3], Minimum[L1, L2, L3], Maximum[L1, L2, L3]}
Changeover ring buffer
The changeover from compressed to uncom­pressed data is carried out via the serial interface and Modbus protocol. If data should be saved uncompressed within the ring buffer, address 19010dez must be overwritten by 2 Bytes of a content by choice. If data should be saved uncompressed within the ring buffer, address 19020dez must be overwritten by 2 Bytes of a content by choice.
Type of measured value
The type of the measured value can be determined by the addresses from the tables 1a and 1b. Example: If the type is marked by the decimal num­ber „1004“, this corresponds to the current mean value in phase L2.
Date
In the part of the data set with the description „Date“, the date and time of the measurement are saved.
char: Year, Month, Day, Hour, Minute, Second
Diagr. Structure of „Date“
Meas. val. type Date Meas. value 2 Bytes 6 Byte 4 Byte (float)
Read ring buffer
If the data sets have been saved uncompressed, they can be read via the serial interface with Modbus protocol. To make this reading easy, there is a ring buffer pointer available. This ring buffer pointer always points to the beginning of a data set. One data set consists of 12 Bytes.
Attention!
If another way of compression is selected, the total content of the ring buffer is deleted.
Table 1a, Measured value Meas. val. in floating point form.
Description Addr.(dez) r/w1)Type
Current 1000 r Meas. val
2)
A L1, L2, L3
1001 r Actual value in L2 1002 r Actual value in L3 1003 r Mean value in L1
1004 r Mean value in L2
.. .. ..
Voltage N-L 1012 r Meas. val.
2)
V L1, L2,
Voltage L-L 1024 r Meas. val.
2)
V L1-L2, L2-L3,
Real power 1036 r Meas. val.
2)
W Sign -=Supply.
.. .. .. .. .. ..
Extract from table 1a
Diagr. Assign measured value type.
Type Date Meas. value 2 Bytes 6 Byte 4 Byte (float)
Ring buffer
Data set 1 Data set 2 Data set 3 . . . Data set n Data set n+1 . .
Oldest data set in ring buffer
Ring buffer pointer = 0000. Last saved data set
Next data set, that will be saved
Diagr. Data sets in ring buffer.
Page 33
33
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Read data sets
The reading of data sets is controlled by the follo­wing addresses:
Read address 19000dez. The first 4 Bytes provide the contents of the ring buffer pointer. The next 12 Bytes provide the first data set, which the pointer points on. The ring buffer pointer is increased automatically by the number of read Bytes, but the first four Bytes are not included.
Write address 19000dez. Set ring buffer pointer on a data set of the ring buffer. If the ring buffer pointer is overwritten by 0000, it points on the last read beginning of ring buffer with address 19008
dez.
Read address 19002dez. Read a number (4 Bytes) of data sets from that address on, on which the pointer points. The ring buffer pointer is increased automatically by the number of read Bytes. The number of read Bytes must be divisible by 12.
Read address 19004dez. Provides that address (4 Bytes), on which the actual pointer points.
Read address 19006dez. Read a number of data sets, from that address on, on which the pointer points. The ring buffer pointer is not increased.
Read address 19008dez. Delivers the number (4 Bytes) of the Bytes saved in ring buffer. If you divide this number by 12, the result is the number of the saved data sets. The ring buffer pointer is set to the last data set in ring buffer. The contents of this pointer is therefore zero. Overwrite address 19010dez with 2 Bytes with a content by choice New data sets are written into the ring buffer uncom­pressed. If data were saved before in a compressed form, the ring buffer will be deleted. Read address 19010dez. Delivers the storage format of the ring buffer in 2 Bytes. 00=compressed ring buffer 01=uncompressed ring buffer
Overwrite address 19020dez with 2 Bytes with a content by choice. New data sets are written into the ring buffer compressed. If data were saved before in a uncom­pressed form, the ring buffer will be deleted. Overwrite address 19030dez with 2 Bytes with a content by choice. The ring buffer will be deleted.
Example 1: Read the last saved data set.
Read adress 19008
dez. The ring buffer pointer
(0000) is set to the last data set in ring buffer. Read 12 Bytes from address 19006
dez. 12 Bytes
correspond to one data set. The ring buffer pointer is not increased.
Example 2: Read all saved data sets.
1.) Read address 19008
dez. The number of saved
Bytes is read. If you divide the result by 12, the num­ber corresponds to the saved data sets. The pointer points to the last saved data set in ring buffer.
2.) Read the content of the Bytes in ring buffer by address 19002
dez. With the MODBUS-Protocol, at
maximum 240 Bytes=20 data sets can be read per reading. The number of read Bytes must be divisib­le by 12. The ring buffer pointer is increased automatically by the number of read Bytes and points to the next data set, which has not been read yet.
3.) Repeat reading of address 19002
dez as long as
all data sets have been read.
Attention!
If a failure appeared during data transmission, the complete procedure must be repeated, starting with step 1.
Example 3: Read all saved data sets.
1.) Read address 19008
dez. Reads the number of
saved Bytes in ring buffer. Divided by 12, the num­ber of saved data sets is the result. The pointer points to the last saved data set.
2.) Read address 19000
dez. The first 4 Bytes refer
to the actual address of the pointer. The next 12 Bytes provide the first data set of the ring buffer. With MODBUS-Protockol you can read 244Bytes (4Byte + 20 data sets) at maximum per reading.
3.) Repeat reading address 19000
dez as long as all
data sets have been read.
Attention!
If a failure occured during data transmission, the last actual address of the ring buffer pointer must be written on address 19000
dez
and the last reading procedure must be repeated.
Page 34
34
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
SELECT
PRG
V
V
V
L3
L1
L2
SELECT
Press
key 1
. The text SELECT flashes in the indica­tion.
Press
key 1
again.
Now you are in menu
CONF.
A
A
SELECT CT
CONF
Press
key 1
again. Now you are in menu PRG.
Confirm selection of the menu PRG pressing
key 2
. The text SELECT disappears.
PRG
Programming menu PRG
The following settings can be carried out in programming menu PRG :
delete all max. and minimum values "dEL", delete real and reactive energy, Select measured values for the ring buffer, Select averaging times for the measured values, Delete maximum and minimum values individually, Read storage duration for the ring buffer.
Select menu PRG
Only from a measured value indication of the UMG 505 can be changed over to the menu PRG. To reach the first measured value indication from each program part, press key 1 for about 2 seconds.
Page 35
35
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Max. values
Min. values
SELECT
PRG
Delete all min/max values
If you are in programming menu PRG, and you want to delete all maximum values, please proceed like this:
Confirm selection with
key 2
.
The symbol SELECT disappears.
Select maximum values with
key 1
.
The text „ ALL“ flas­hes.
The symbol EDIT appears.
Press
key 1
for about 2 seconds and you return to the first measured value window of the measured value indication from each program part.
Delete max/min val. individually
If you are in menu PRG and want to delete the voltage peak value in L2, please proceed like this:
SELECT
PRG
EDIT
Confirm selection with
key 3
. The text „ ALL“ dis­appears. The number „0“ appears in the indi­cation and flashes. All maximum values are marked for deletion and are deleted, when you change to the next indication.
PRGEDIT
Attention!
After return of the supply voltage, all minimum values are deleted.
Attention!
The monthly peak values of real power Emax belong to the maximum values and are deleted as well.
SELECT
PRG
Confirm selection with
key 2
.
The symbol SELECT disappears.
Change to the measured value indi­cation using
key
3. In this example the pro­gramming of the current in the three phases is shown. The averaging time of the currents is 15 minutes.
V
V
L3
L1
L2
V
PRG
Now scroll to the measured value indi­cation of the voltages by using
key 3
.
V
L2
PRG
EDIT
Select max. value of voltage in phase L2 with
key 1
. The symbol EDIT appears.
Confirm with
key 3
. The selected maxi­mum value is deleted.
A
A
A
L3
L1
L2
PRG
The indicated maximum value is set to 000.0 for a short time, and will be overwritten with the next measured value.
Press
key 1
for about 2 seconds and you return to the first measured value window of the measured value indication from each program part.
Page 36
36
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Delete real and reactive energy
Real and reactive energy can be deleted separately via keyboard or serial interface. The group of the reactive energy meters and the group of the real energy meters are reset separately. Starting time and running time will be actualized. If real energy is deleted, also the meters T50 - T54, T00-T04 and T30-T34 are deleted. If reactive energy is deleted, also the meters T40 ­T44, T10-T14 and T20-T24 are deleted.
Confirm selection of menu PRG with
key
2.
The symbol SELECT disappears.
Scroll to real and reactive energy meters using
key 2
.
The arrows for minimum and maxi­mum values disappear.
Press
key 1
for about 2 seconds and you return to the first measured value window of the measured value indication from each program part.
Wh
VArh
PRG
PRGEDIT
Wh
VArh
Energy meter
Changeable
Real energy without rev. run. stop T50 T51 T52 T53 T54 Consumption T00 T01 T02 T03 T04 Supply T30 T31 T32 T33 T34 Reactive energy without rev. run. stop T40 T41 T42 T43 T44 inductive T10 T11 T12 T13 T14 capacitive T20 T21 T22 T23 T24
Diagr. Overview of the energy meters.
If you are in menu PRG and would like to delete the real energy meter, please proceed as follows:
Select real energy meter with
key 1
. The text „ ALL“ flas­hes. The real energy meters are marked for deletion. The symbol EDIT appears.
Confirm selection with
key 3
. The text „ ALL“ dis­appears. The number „0“ appears and flashes. All real energy meters are marked for deletion and are deleted while chan­ging into the next in­dication.
SELECT
PRG
Wh
VArh
PRG
Page 37
37
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Press
key 1
for about 2 seconds and you return to the first measured value window of the measured value indication from each program part. The mean value of voltage in phase L2 is program­med for storage in ring buffer.
Program ring buffer
The following values can be chosen for storage in the ring buffer in menu PRG of the UMG505
- the mean values of the measured values,
- the reset of measuring period Emax
- a part of the energy meters (Tx0)
Mean values, which are selected for storage in the ring buffer are marked by both arrow symbols before the mean value.
Mean values
If you are in menu PRG and want to provide the mean value of voltage in phase L2 for storage in the ring buffer, please proceed as follows:
The mean value of voltage in L2 is not programmed for storage.
V
L2
PRGEDIT
V
V
V
L3
L1
L2
PRG
SELECT
PRG
Confirm selection with
key 2
.
The symbol SELECT disappears.
Scroll to mean values of voltage with
key 2
and
key 3
.
Select voltage in phase L2 with
key 1
. The symbol EDIT appears. Mark mean value of voltage in L2 for storage in ring buffer with
key 2
.
Attention !
A change of the measured value selection for the ring buffer deletes the ring buffer!
Reset of measuring period EMAX
If you are in menu PRG and would like to provide the reset the measuring period Emax for storage, please proceed as follows:
Press
key 1
for about 2 seconds and you return to the first measured value window of the measured value indication from each program part.
The reset of the measuring period Emax is not pro­grammed for storage.
SELECT
PRG
Confirm selection with
key 2
.
The symbol SELECT disappears.
Scroll to the indication beside with
key 3
.
Select measuring period with
key 1
. The symbol EDIT appears. Select reset of measuring period Emax for storage with
key 2
.
Mean value „Sum cosPhi“
Mean value „Current in N“
Reset measuring period Emax with 15 minutes period.
A
W
M.S
L1 L2 L3
L1 L2 L3
L1 L2 L3
PRG
cosϕ
W
M.S
L1 L2 L3
PRG
EDIT
Page 38
38
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Period of storage
The more mean values are marked for storage in the ring buffer, the shorter becomes the period of storage. If the ring buffer is completely full, the most obsolete values are overwritten. With the factory's presettings Mean values: U1, U2, U3, I1, I2, I3, P1, P2, P3 Averaging time: 15 minutes.
The mean values of about 1 year are saved in the device. If this period is over, the most obsolete values are overwritten. If various averaging times are assigned to the mean values to be stored, more room for storage can be required, and the period of storage can get much shorter.
To enlarge the period of storage, the number of saved mean values can be decreased or all mean values can be programmed with the same averaging time. An estimation of the period of storage can be called up in menu PRG.
1year, 5months, 18days, 13hours, 45minutes, 0seconds
Confirm menu PRG with
key 2
.
The symbol SELECT disappears.
SELECT
PRG
Scroll to indication of period of storage with
key 2
and
key 3
. In the example, the period is estimated to 1 year and 5 months.
Y.M
D.H
M.S
PRG
Press
key 1
for about 2 seconds and you return to the first measured value window of the measured value indication from each program part.
Averaging time
An averaging time can be assigned to each mean value. The following averaging times can be set:
1, 5, 10, 15, 30 seconds,
1, 5, 10, 15, 30, 60 minutes. All averaging times are programmed to 15 minutes, when the device leaves the factory.
Set averaging times
If the averaging time, for example, for voltage L2 should be changed to 5 seconds, please proceed as follows in menu PRG:
V
L2
PRGEDIT
Scroll to averaging time of 5 seconds with
key 3
.
00:05 = 5 seconds (15:00 = 15 minutes)
V
L2
PRGEDIT
Press
key 1
for about 2 seconds and you return to the first measured value window of the measured value indication from each program part.
The averaging time is saved.
A
A
A
L3
L1
L2
PRG
SELECT
PRG
Confirm selection with
key 2
.
The symbol SELECT disappears.
The averaging times are set to 15 minutes.
Scroll to mean values of voltage with
key 2
and
key 3
.
Select voltage in phase L2 with
key 1
. The symbol EDIT appears.
Attention !
A change of the averaging time deletes the ring buffer.
Page 39
39
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Configuration
In configuration menu CONF the required settings are noted for operating the UMG505 (see also "Table of configuration data"). When the device is delivered, these settings are not protected and can be changed. An unintended change of the settings can be avoided using a password.
The following settings can be read out and changed:
Confirm selection of the menu CONF with
key 2
. The text SELECT disappears. Now you are in menu CONF, and the current transformer ratio is indicated.
V
V
V
L3
L1
L2
SELECT
Press
key 1
. The text SELECT appears in the indi­cation and flashes.
Press
key 1
again.
Now you are in menu
CONF.
A
A
SELECT CT
CONF
A
A
CT
CONF
To reach menu CONF from a measured value indi­cation, please proceed as follows:
Current transformer Voltage transformer Aron circuit Data logging Serial interfaces
RS485 interface (Option) RS232 interface (Option) LON (Option)
Device address Measured value rotation Event memory Net frequency Switching outputs 1 to 5 Switching clock
Switch-on time Switch-off time Channels
EMAX target value (Option) EMAX digital outputs(Option) ,
Power min. connection time
EMAX digital outputs (Option),
min. disconnection time max. disconnection time
EMAX analogue outputs (Option)
max. power of consumer min. power of consumer
EMAX analogue outputs (Option)
max. disconnection power or min. connection time of the Generator Time between minP und maxP
Digital inputs Pulse valence Digital outputs Pulse width Analogue outputs, source and scale Analogue outputs, scale range 0/4mA LCD contrast Clock, summer/winterzeit Password
Serial number Software Release
Page 40
40
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Current transformer
The ratio of the current transformer is set in configu­ration menu CONF. The secondary current can either be set to ../1A or ../5A. If you are in configuration menu CONF, the current transformer ratio can be changed as follows:
A
A
SELECT CT
CONF
Select: Confirm the selection of the current transformer menu with
key 2.
The text SELECT disappears.
Set: Select the number to be changed using
key 1
. The selected number flashes. The text EDIT appears. Change the selected number using
key 3
. Multiply the number with a factor 10 with
key 2
.
When the ratio of the current transformer is set, press
key 1
as often, as no digit is flashing any longer. EDIT disappears. With
key 3
you move to the next menu. The ratio of
the current transformer is saved.
Voltage transformer
The ratio of the voltage transformer is set in confi­guration menu CONF. The secondary voltage can be set in the range of 1V up to 500V. If you are in configuration menu CONF, change the ratio of the current transformer as follows:
A
A
SELECT CT
CONF
Select Confirm selection of current transformer menu with
key 2
. The text SELECT disappears.
Select With
key 3
you move to the voltage transformer menu.
Set Using
key 1
the number to be changed is selected. The selected number flashes. The text EDIT appears. With
key 3
the se­lected number is changed.
Key 2
multiplies the
number with a factor
10.
When the ratio of the voltage transformer is set, press
key 1
as often, as no digit is flashing any longer. EDIT disappears. With
key 3
you move to the next menu. The ratio of
the voltage transformer is saved.
A
A
CT
CONF
EDIT
Secondary current
Primary voltage
Secondary voltage
kV
V
VT
CONF
EDIT
kV
V
VT
CONF
Primary current
Page 41
41
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Aron circuit
Voltage over 500VAC against ground must be con­nected via voltage transformers. The voltage measurement via voltage transformers can be carried out via two voltage transformers (Aron circuit) or three voltage transformers by choice. For direct measurement and measurement via three voltage transformers, „4L“ must be set at UMG 505 and for measurement with two voltage transformers, „3L“ must be set.
The manufacturer’s presetting is „4L“.
In menu CONF you can select between Aron circuit „3L“ or four wire measurement „4L“.
Select
In menu CONF scroll to indication of four wire measurement or Aron circuit with
key
3
. In this example, four wire measurement „4 L“ is activated.
Change
Press
key 1
. The digits „4 L“ flash. The symbol EDIT appears. With
key 3
you can changeover from four wire measurement „4
L“ and Aron circuit „3 L“ .
Confirm selection with
key 1
. The symbol EDIT disappears.
CONF
EDIT CONF
Diagr. Aron circuit with two voltage transformers and two current transformers.
Diagr. Aron circuit with two voltage transformers and three current transformers.
Messung
Measurement
Hilfs-
spannung
Auxiliary
Voltage
UMG505
27 26 25 24
23 22 21 20 19 18 14 15
u v PE
2A
L/L 80 .. 870V AC
L/PEN 50 .. 500V AC
0,005 .. 5A
10160410
u v u v
U V U V
k l
k l
k l
../5(1)A
../5(1)A
../5(1)A
Verbraucher
Consumer
4-
10A
Messung
Measurement
Hilfs-
spannung
Auxiliary
Voltage
UMG505
27 26 25 24
23 22 21 20 19 18 14 15
u v PE
2A
4-
10A
L/L 80 .. 870V AC
L/PEN 50 .. 500V AC
0,005 .. 5A
10160430
u v u v
U V U V
k l
k l
../5(1)A
../5(1)A
Verbraucher
Consumer
Press
key 1
for about 2 seconds and you return to the first measured value window of the measured value indication from each program part.
Page 42
42
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Data logging
The memory of the UMG505 is divided into three ranges:
- the event memory,
- the minimum and maximum storage and
- the ring buffer. When the device is deliverd, the data logging is on (on) and all three ranges can be written. If no data logging should be carried out, data logging must be switched oFF.
Select In menu CONF, you scroll to the indicati­on of data logging „dAtA“ with
key 3
. Confirm selection with
key 1
. The text EDIT appears. The set data logging is indicated and flashes. In this example is data logging = on, which means, the three ranges of memory can be written.
Change The set data logging is flashing. Change between on and off with
key 1
.
Pressing key
1
, the text EDIT disappears and the change is saved.
Pressing key 3, you change over to the program­ming of the measured value rotation.
Press
key 1
for about 2 seconds and you return to the first measured value window of the measured value indication from each program part.
CONF
EDIT
CONF
EDIT
Page 43
43
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Serial interfaces
In the UMG505, there is always a RS485 or RS232 interface included.
RS485 interface (Option)
The RS485 interface is suited for transmission of data over a distance of 1200 m. Up to 31 UMG505 and a master (PC or SPS) can be connected.
CONF
Type of interface
Transmission protocol
Baud rate
Modem
Via the RS232 interface, the UMG505 can be con­nected to an external analogue modem. The connection between UMG505 and the Modem is carried out via a "RS232" cable. For modem operation, the transmission protocol 2 (modem) must be selected for the RS232 interface.
RS232 interface (Option)
The RS232 interface is suited for transmission of data over a distance of 30m. The UMG 505 can be connected directly via this interface to the COM-port of PC or an external analogue modem. The connection to PC must be carried out via a
RS232 cable.
CONF
Interface type
Protocol number
Baud rate
Baud rate
The baudrates:
9600, 19.2k and 38.4k
can be set.
Transmission protocol RS485
The following protocols can be selected: oFF no protocol, interface is off. 01 Modbus RTU (Slave). 02 Modem.
Terminal resistors
If the device is connected to the end of a bus cable, the bus cable must be terminated by terminal resistors. The required terminal resistors are integrated within the device and are activated in condition ON.
Diagr: Connection diagram RS485
UMG505
RS485
30
29
28
A
B
GND
B
A
RS485
Driver
+5V=
GND
390R 390R220R
Abschlusswiderstände
Line Terminator
On
Off
Mit Abschlusswiderstand
With Line Terminator
Ohne Abschlusswiederstand
Without Line Terminator
Baud rate
The following baud rates can be set:
9600, 19.2k and 38.4k.
Transmission protocols RS232
oFF no protocol, interface is off 01 Modbus RTU (Slave). 02 Modem.
Interface converter
If a UMG 505, which is equipped with a RS485 interface, should be connected to a PC, which has got an RS232 interface, an interface converter is required.
k
Diagr. Connection diagram RS232 cable
Potential free
Diagr. Connection diagram RS232
UMG505
RS232
30
29
28
TXD
RXD
GND
RS232
Driver
Page 44
44
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Modbus RTU
Via Modbus RTU Protocol, the data of the following tables can be retrieved:
Example: Reading system time The system time is deposited in table 1 under the address 3000. The system time consists of 6 Bytes with year, month, day, hours, minutes and seconds in format "char" = 0..255. The device address of the UMG 505 is considered as address = 01.
The "Query Message" looks as follows: Description Hex Comment Device address 01 UMG505, Address = 1 Function 03 "Read Holding Register" Start address Hi 0B 3000dez = 0BB8hex Start address Lo B8 Number of val. Hi 00 6dez = 0006hex Number of val. Lo 06 Error Check -
The "Response" of the UMG505 can look as follows: Description Hex Comment Device address 01 UMG505, Address = 1 Function 03 Byte counter 06 Data 00 Year = 00hex = 00dez =
2000dez
Data 0A Month = 0Ahex = 10dez =
Okt. Data 0C Day = 0Chex = 12dez Data 0F Hour = 0Fhex = 15dez Data 1E Minute = 1Ehex = 30dez Data 0A Second =0Ahex = 10dez Error Check (CRC)-
Table 1a Measured values in floating point format Table 1b Measured values in floating point format Table 2a Time information for the minimum and
maximum values and system time
Table 2b Time information for the minimum and
maximum values and time of summer/
winter time changeover Table 3 Averaging times of mean values Table 4a Measured values, Integer format Table 4b Mean values, Integer format Table 4c Maximum values, Integer format Table 4d Minimum values, Integer format Table 5 Energy in Integer format Table 6 Delete energy Table 7 Energy in floating point format Table 8 EMAX peak values Table 9 Scale of meas. values in Integer format Table 10 Digital and analogue inputs and outputs
Transmission mode
RTU- Mode with CRC-Check.
Transmission parameters
Baud rate : 9600,19200 und 38400 (RS232 and RS485) Data bits : 8 Parity : none Stop bits : 2
Realized functions
Read Holding Register, function 03 Preset Single Register, function 06 Preset Multiple Registers, function 16
Page 45
45
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
LON interface (Option)
For the connection of UMG505 with other LON-Bus devices, a FTT10-Transceiver is used within the UMG 505. The bus is proof against change of polarity, and can be connected to one side or both sides. Devices which use a FTT10- Transceiver, can be linked to each other via line star or ring structures. If the allowed transmission resistance in a structure is reached, the network can be expanded by the use of repeaters or routers only. Service Pin The Service Pin is a special input of a node (UMG
505) for service purpose. In the UMG505, the service pin is activated via the keys in the front. If the service pin is activated, the UMG 505 sends a message over the LON-Bus. This message contains the Neuron-ID and the Program-ID of the neuron chip inside the UMG505. By this means, a node can be announced at a tool. Activate Service Pin The Service Pin can be activated in menu CONF. Please change into menu CONF (See chapter "Con­figuration").
CONF
Indication
In menu CONF, scroll to the indication of the serial interfaces (RS232/485) with key 3.
Call up Neuron-ID
The Neuron-ID can be called up in menu CONF. Please change to menu CONF (See chapter "Configuration").
RS232/ RS485
Baud rate
Protocol
LON
Service Pin
on/oFF
LON
Neuron-ID
RS232/ RS485
Baudrate
Protocol
LON
Service Pin
on/oFF
LON
Neuron-ID
Neuron-ID
The LON protocol runs on a Neuron-Chip, which is included in the UMG505. Each Neuron-Chip is assigned to a unique identification number during production, the Neuron-ID.
With
key 2
scroll to Neuron-ID. In this example, the Neuron-ID "356113901" is displayed.
CONF
Activate
In menu CONF, please scroll to the indication of the serial interfaces (RS232/485) using key 3.
With
key 2
scroll to
Service Pin.
Press
key 1
. The text EDIT appears. Press
key 3
. The Service Pin is activated, and the text „on“ appears for a short time in the display.
EDIT CONF
Page 46
46
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Measured value rotation
All measured values are calculated two times per second and can be called up in the display. Normally the selec­tion is carried out via the key 2 and 3. Additionally, there is the possibility of the measured value rota­tion, which means the indication of auto­matic changing of se­lected measured va­lues. if no key is pressed for about 60 seconds, the measured value rotation is activated, and the se­lected measured values are shown one after the other.
All measured values, which can be called up by the keys are also available for the measured value rotation. The time between two indication is called the chan­ging time, and can be set in the range of
0 .. 9999 seconds. To activate the measured value rotation, at least one value must be selected and the changing time must be programmed bigger than 0 seconds.
If zero seconds are set for the changing time, no changing is carried out.
If the changing time is bigger than 0, but only one measured value indication is selected, only this in­dication is shown.
CONF
Device address
If several devices are connected via the RS485 interface, a master device (PC, PLC) can distingu-
ish them by the device address only. Therefore each UMG 503 must have another device address. Device addresses can be given from 0 to 255.
ADDR
CONF
Select In menu CONF you move to indication of device address using
key 3
. In this example the factory's presetting is indicated as "1".
Change With
key 1
a number of the device address can be selected and be changed using
key 3
. The selected
number is flashing.
ADDR
EDIT CONF
Program
The set device address can be called and changed in menu CONF. Please move to menu CONF (See chapter "configuration").
Save If you have set the desired device address, please use
key 1
as often as no digit is flashing any longer. Pressing
key 2,
the text EDITdisappears, and the indicated device address will be saved.
ADDR
CONF
Press
key 1
for about 2 seconds and you return to the first measured value window of the measured value indication from each program part.
Page 47
47
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
CONFEDIT
CONFEDIT
Program changing time
Select In menu CONF you can scroll to the indication of the changing time „Pic“ with key 3. With key 1, you con­firm the selection of the menu. The text EDIT ap­pears. The set changing time is indicated and flashes. In this example, a changing time of 0 seconds is indicated, which means the measured value rotation is not activated.
Change The selected chan­ging time flashes. Confirm selection of changing time with
key
1. The first number of the changing time flashes. Now change to the selected number by pressing
key
1. If a number is flashing, it can be changed by pressing
key
3. If all numbers are flashing, you can change to the measured value selection with
key
2. If no digit is flashing, you can change to the pro­gramming of the analogue outputs with
key
3.
Press
key 1
for about 2 seconds and you return to the first measured value window of the measured value indication from each program part.
V
V
V
L3
L1
L2
Program measured value selection
Select In menu CONF you can scroll to the indication of the changing time „Pic“ with key 3. Confirm selection of the menu with
key 1
. The symbol EDIT ap- pears. The set changing time is indicated and flashes. In this example, a changing time of 0 seconds is indicated, which means the measured value rotation is not activated. Change to measured value selection with
key 2
. In this example, the display of voltage L against N appears. This indication is not yet programmed for measured value rota­tion.
By pressing
key 1
for a short time, the indication will be activated for measu­red value rotation.
By a second short pressing of
key 1,
the indication is deactivated again. Pressing
key 1
longer, you change back to the programming of the changing time. The number of the chan­ging time flashes.
Press
key 1
for about 2 seconds and you return to the first measured value window of the measured value indication from each program part.
CONFEDIT
V
V
V
L3
L1
L2
Page 48
48
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Set event memory
The UMG505 is delivered with a memory of 512kB RAM. A part of this memory is used for the ring buffer and the event memory. The division between ring buffer and event memory varies and is defined by the size of the event memory. The smaller the event memory is selected, the more memory is available for the ring buffer. The size of the event memory is determined by the number of saved events. At maximum 9999 events can be saved in the event memory. If more events are registered, the most obsolete events are overwritten.
The number of events, that should be saved, can be called up and changed in menu CONF.
Indicate: In menu CONF you scroll to the indication of event memory with
key 3
. Here the number of 1000 events is set.
Number of events = 1000
Change: Select the selected number with
key 1
. The symbol "EDIT" appears and the selected digit flashes. Change number with
key 3
.
EDIT CONF
CONF
Attention!
If the selection of saved events is changed, the ring buffer is deleted.
Press
key 1
for about 2 seconds and you return to the first measured value window of the measured value indication from each program part.
Page 49
49
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Net frequency
The net frequency is determined from the measure­ment voltage within the UMG 505. From the net fre­quency the scanning frequency for the current and voltage inputs is calculated. For measurements with very distorted voltages, the frequency of the voltage fundamental cannot exactly be determined any longer. Voltage distortion occurs in measurements at consumers, which are driven with phase changing controllings. For highly distorted measurement voltage, the corresponding net frequency should be program­med. Distortion of the current does not affect the determi­nation of the frequency.
Without measurement voltage, no net frequency can be determined, and no scanning frequency can be calculated. Voltage, current and all resulting values are not calculated and indicated with zero. If the current should be measured without measure­ment voltage, the net frequency must be program­med at UMG 505.
The determination of the net frequency can be carried out automatically or as a fix frequency. The following settings for the determination of the frequency are at your disposal: "Auto" Automatical frequency "50"Hz Fix frequency "60"Hz Fix frequency
The proceeding for the determination of the frequen­cy can be called up and changed in the menu CONF.
Select In menu CONF you can scroll to the indi­cation of the frequen­cy determination using
key 3
.
In this example, the frequency is determi­ned automatically.
Change Using
key 1,
the de­termination of the frequency is se­lected, and the text "Auto" flashes. In the indication, the text EDIT appears.
Using
key 3,
you can change over between the two methods of frequency determina­tion.
In this example a fix frequency of 50Hz is set.
Hz
SELECT
EDIT CONF
Hz
SELECT
CONF
Page 50
50
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Limit supervision
For the supervision of limits of measured values 5 threshold outputs can be programmed. Each threshold output can be assigned to up to three comparators (A, B, C). For each comparator,
2 limits and two measured values or 2 limits and 1 measured value or
1 limit and the minimum connection time can be programmed. The function of the corresponding combination can be seen in the following diagrams.
UMG505
Digital Outputs
UMG505
Limit supervision
Diagr. Principle diagram limit supervision
If a limit violation is detected in one of the compara­tors "A", "B" or "C", the threshold output is activated. The violation is registered within the event memory with date and time and can be given out via a „Digi­tal Output“. The assignment of a threshold output to a „Digital Output“ is carried out while programming the digital outputs. Limits may be positive or negative. Negative limits are marked with a "-" before the limit.
OR
Threshold out-
put 1
Event me-
mory
Event me-
mory
Event me-
mory
Digital Outputs
1 - 5
Digital
Output
Comparator
A
Min. connection time
Meas. value Limit 1
Meas. value Limit 2
or
Exceeding- /Underscore
Comparator
B
Min. connection time
Meas. value Limit 1
Meas. value Limit 2
or
Exceeding- /Underscore
Comparator
C
Min. connection time
Meas. value Limit 1
Meas. value Limit 2
or
Exceeding- /Underscore
OR
Threshold out-
put 5
Event me-
mory
Event me-
mory
Event me-
mory
Digital Outputs
1 - 5
Digital
Output
Comparator
A
Min. connection time
Meas. value Limit 1
Meas. value Limit 2
or
Exceeding- /Underscore
Comparator
B
Min. connection time
Meas. value Limit 1
Meas. value Limit 2
or
Exceeding- /Underscore
Comparator
C
Min. connection time
Meas. value Limit 1
Meas. value Limit 2
or
Exceeding- /Underscore
EDIT CONF
L1
A
M.S
A
Page 51
51
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Diagr. Limit supervision with one limit and one measured value.
Limit supervision with one limit and one measured value.
Minimum connection
time
t
Limit 1
Measured
value1
Exceeding
t
Threshold output
t
1Second
t
Minimum connection
time
t
Limit 1
Measured
value 1
Exceeding
t
Threshold output
t
2 seconds
t
Minimum connection
time
t
Limit 1
Measured
value1
Underscoring
t
Threshold output
t
2 seconds
t
Minimum connection
time
t
Limit 1
Measured
value 1
Underscoring
t
Threshold output
t
1 second
t
Min. connection time = 1second (example)
Min. connection time = 2seconds (example)
Case 1.1
Case 1.2
Case 1.3 Case 1.4
Exceeding
Underscroring
Page 52
52
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Programming of case 1.1
When voltage in L1 exceeds the limit of 240V, the treshold output 4 should be activated. The comparison is carried out by comparator „A“. The comparators „B“ and „C“ are not used. Please note, that the UMG 505 carries out the measurement twice a second, but the shortest minimum connection time is 1second.
Threshold output
In menu CONF scroll to threshold output 4 with
key 3
.
Measured value
Confirm selection with
key
1. The middle indication flashes. The text EDIT appears. Now the measured value can be selected, or deleted, if one was programmed before, using
key 3
.
Scroll to indication of voltage with
key 2
and
key 3
.
V
L3
L1
L2
V
V
Select voltage L1 with
key 1
. The text EDIT appears. Confirm selection with
key 2
.
V
L1
EDIT
Limit
The first number of the limit is flashing and can be changed with
key 3
.
Select other digit with
key 1
and change
with
key 3
. As long as a digit of the limit is flashing, you can move the decimal point with
key 2
.
The selected measured value appears in the threshold indication.
The first digit is flashing.
Minimum connection time
If the last digit of the limit is flashing, and you press
key 1
again, the lowest programming block is selected and flashes. In this example, a minimum connection time of 1 second is indicated.
Press
key 1
again. The first digit of the minimum connection time is flashing and can be changed with
key 3
. Select the other digits with
key 1
and
change with
key 3
.
Exceeding or underscoring
If the last digit of the minimum connection time is flashing, and you press
key 1
again, the arrow for exceeding is flashing. With
key 3
you can change between ex­ceeding and un­derscoring.
Confirm programming with key
1
. The text EDIT disappears. The comparator „A“ is programmed for threshold output 4. With
key 3
you can change to the next
threshold output, or pressing
key 1
for about 2 seconds, you return to the first measured value indication.
If a measured value is programmed to the compara­tors „B“ and „C“ as well, this assignment must be deleted.
M.S
CONF
M.S
EDIT CONF
V
M.S
L1
EDIT CONF
V
M.S
L1
EDIT CONF
V
M.S
L1
EDIT CONF
V
M.S
L1
EDIT CONF
V
M.S
L1
EDIT CONF
Page 53
53
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
With one measured value With two measured values
Diagr. Supervision of limits with two limits
Limit 1
Limit 2
Measured
value
Threshold output
t
t
Threshold output
t
t
Limit 2
Measured
value 2
Limit 1
Measured
value 1
Limit 1
Limit 2
Measured
value
Threshold output
t
t
Threshold output
t
t
Limit 2
Measured
value 2
Limit 1
Measured
value 1
Limit 1
Limit 2
Measured
value
Threshold output
t
t
Threshold output
t
t
Limit 2
Measured
value2
Limit 1
Measured
value 1
Limit 1
Limit 2
Measured
value
Threshold output
t
t
Threshold output
t
t
Limit 2
Measured
value 2
Limit 1
Measured
value 1
Limit supervision of two limits
Case 2.1
Case 2.2
Case 2.3
Case 2.4
t
t
t
Case 2.5
Case 2.6
Case 2.7
Case 2.8
AND
Hysteresis
HysteresisWithinOut of
AND AND
AND
ExceedingUnderscoring
Page 54
54
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Programming example case 2.1
When the current in L1 exceeds the limit 1 (120A), the threshold output 3 must be activated, and when the current underscores the limit 2 (80A), the threshold output 3 should be deactivated. The comparison is carried out with comparator „A“. The comparators „B“ and „C“ are not used. Please note, that the UMG 505 measured twice a second.
Threshold output
In menu CONF scroll to threshold output 3 with
key 3
.
Measured value
Confirm selection with
key
1. The middle indication flashes. The text EDIT appears. Now the measured value can be selected, or deleted, if one was programmed before, using
key 3
.
Scroll to indication of current with
key 2
and
key 3
.
A
L3
L1
L2
A
A
Select current L1 with
key 1
. The text EDIT appears. Confirm selection with
key 2
.
A
L1
EDIT
Limit 1
The first number of the limit is flashing and can be changed with
key 3
.
Select other digit with
key 1
and change
with
key 3
. As long as a digit of the limit is flashing, you can move the decimal point with
key 2
.
A
M.S
L1
EDIT CONF
The selected measured value appears in the threshold indication.
The first digit is flashing.
Limit 2
If the last digit of the first limit is flashing, and you press
key 1
again, the lowest pro­gram block is se­lected and flashes. Now select the measured value for limit 2 as described for limit 1.
Exceeding or underscoring
With
key 1
move to the arrows for excee­ding or underscoring. With
key 3
you can select. Please press
key 1
so often, unless the text EDIT disappears. The comparator „A“ is now programmed for threshold output 3. With
key 3
you can change to the next threshold
output, or pressing
key 1
for about 2 seconds, you
return to the first measured value indication.
Attention!
If a measured value is assigned to the comparators „B“ and „C“, this assignement must be deleted.
Limit 2
The first number of the limit is flashing and can be changed with
key 3
.
Select other digit with
key 1
and change
with
key 3
. As long as a digit of the limit is flashing, you can move the decimal point with
key 2
.
A
M.S
L1
EDIT CONF
A
M.S
L1
EDIT CONF
M.S
EDIT CONF
M.S
CONF
A
L1
EDIT CONF
L1
A
A
L1
EDIT CONF
L1
A
Page 55
55
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Switching clock
The switching clock of the UMG505 has 100 switching clock channels. Each switching clock channel describes a certain period. The period is described by a switch-on time and switch-off time. The switch-on and -off time is determined by the day, hour and minute. Each switching clock channel can control a switching clock output, and select an Emax target value and an energy meter. In the programming of the digital outputs, a „Digital Output“ can be assigned to the switching clock outputs.
Setting range: Switching clock channels 00 - 99 Switching clock outputs 0
1)
- 5
EMAX target number 0
1)
- 5
Energy meter see table, TX0
1)
1)
No assignment
Energy meter
Changeable
Real energy without rev. run. stop T50 T51 T52 T53 T54 Consumption (EMAX) T00 T01 T02 T03 T04 Supply T30 T31 T32 T33 T34 Reactive energy without rev. run. stop T40 T41 T42 T43 T44 inductive T10 T11 T12 T13 T14 capacitive T20 T21 T22 T23 T24
Diagr. Energy meters of UMG505.
Diagr. Principle diagram of the switching clock
D.H
M.S
CONF
D.H
M.S
CONF
Switch-on time
Switch-off time
CONF
Output channel
UMG505
Switching clock
Switching
clock channel
00
Switch-off time
First week day Last week day Minute, hour
Switch-on time
First week day Last week day Minute, hour
Switch-off time
First week day Last week day Minute, hour
Switch-on time
First week day Last week day Minute, hour
Digital
Output
Digital Output
1 - 5
Digital
Output
Digital Output
1 - 5
UMG505
Digital Outputs
Switching clock output
0 - 5
EMAX target value
0 - 5
Change energy meter
Output channel
Switching clock output
0 - 5
EMAX target value
0 - 5
Change energy meter
Switching clock
channel 99
Page 56
56
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Attention!
If several targets are used by the switching clock, the target with the highest number is used by Emax program.
Output channel
Several switching clock channels can be assigned to an output channel. If a switching clock channel is active, also the output channel is active. Possible output channels: Switching clock output 0
1)
- 5
EMAX target number 0
1)
- 5
Energy meter see table, TX0
1)
1)
No assignment
Each switching clock channel of the switching clock can be assigned to a „Digital Output“.
Swich-on and switch-off time
Each switching clock channel is described by its switch-on and switch-off time, which is determined by one or more week days and the time. The time is given in hours and minutes. If the time is valid for one week day only, the first week day is identical to the last week day. The switching clock channel is not active, when the switch-on time is programmed to 24:00h. Assignment of the week days:
1 - Monday 2 - Tuesday 3 - Wednesday 4 - Thursday 5 - Friday 6 - Saturday 7 - Sunday
Switching clock channel
Each channel consists of a switch-on time and a switch-off time. Each switching clock channel can be assigned to several output channels.
Switching clock channel
D.H
M.S
CONF
CONF
Programming of a switching clock channel for switch-on and -off time.
Indication of the switching clock channel while programming the output channels.
CONF
Switching clock output
EMAX target number
Energy meter
D.H
M.S
CONF
Time =
Hour Minute
First week day Last week day
D.H
M.S
CONF
D.H
M.S
CONF
Switch-off time
Switch-on time
D.H
M.S
CONF
Switching clock channel
Switch-on time Switch-off time
Page 57
57
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Programming example
The EMAX target „01“ was assigned to a value of 200kW by the Emax programming. This EMAX target shall be active from Monday to Friday from 08:00 until 20:00h. The switching clock channel 1 is programmed for the period from Monday to Friday.
The set switch-on and -off times can be called up and changed in menu CONF. Please change to menu CONF (See chapter "Configuration").
Switch-on time In menu CONF, scroll to the indication of switch-on time with
key 3
.
Confirm selection with
key 1
. The symbol EDIT appears. The first number of the switching clock channel flashes and can be changed with
key 3
. Select the numbers for the switching clock channel, week days and switch-on time with
key 1
and
change with
key 3
.
Switch-off time
Scroll to switch-off time with
key 2
.
Confirm with
key 1
. The symbol EDIT appears. The first digit of the first week day is flashing and can be changed with
key 3
.
Select last week day and switch-on time with
key 1
and
change with
key 3
.
Output channel
Scroll to output channel with
key 2
. Confirm selection with
key 1
. The symbol EDIT appears. The first number of the switching clock channel is flashing.
Select Emax target number with
key 1
and change with
key
3
.
CONF
EDIT
Save
Press
key 1
until no digit is flashing.
Confirm with
key 2
. The symbol EDIT disappears, and the indicated switch-on time is saved.
CONF
EDIT
Save
Press
key 1
until no digit is flashing.
Confirm with
key 2
. The symbol EDIT disappears, and the indicated switch-on time is saved. The next window (switch-off time) appears.
Save
Press
key 1
until no digit is flashing.
Confirm with
key 2
. The symbol EDIT disappears, and the indicated switch-on time is saved. The next window (switch-off time) appears.
D.H
M.S
CONF
EDIT CONF
D.H
M.S
D.H
M.S
EDIT CONF
Switching clock
channel = 1
Monday to Friday
Switch-on time = 08:00
EDIT CONF
D.H
M.S
Switch-off time = 20:00
Page 58
58
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
EMAX target value (Option)
For the EMAX-Program, up to 5 EMAX target values can be programmed. To each target, a target number is assigned (1-5). The changeover of the target is effected via the EMAX target numbers. The changeover can be selected via the internal clock or the digital inputs of the UMG 505.
EMAX digital outputs (Option)
Connection power and connection time
The EMAX program can control up to 5 Emax digi­tal outputs. Each Emax digital output can have a priority 0 ... 9. EMAX outputs with priority 0 are not considered in the trand calculation of the Emax pro­gram. EMAX outputs with low priority, example 1, are disconnected at first and reconnected at last. EMAX outputs with the same priority have equal rights. Only if all Emax outputs of the same priority have been disconnected, the next priority will be considered for disconnection. To determine the time of switching more accurate, each Emax output must be programmed with its connection power, which means the power of the connected consumers. The assigned switching times are held in any case. The minimum connection time describes, for how long a consumer must be connected between two disconnections.
Priority
EMAX digital output
Connection power
Minimum connection time in seconds.
The programmable parameters are: Priority : 0 .. 9 (0 = off) EMAX digital outputs : 1 .. 5 Connection power : 0W .. 9999MW Min. connection time : 20 .. 999seconds Min. disconnection time : 20 .. 999seconds Max. disconnection time : 20 .. 999seconds
W
CONF
W
CONF
T
EMAX Target number
EMAX target
Page 59
59
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Priority
EMAX digital output Minimum disconnection time Maximum disconnection time
The programmable parameters are: Priority : 0 .. 9 (0 = off) EMAX digital outputs : 1 .. 5 Connection power : 0W .. 9999MW Min. connection time : 20 .. 999seconds Min. disconnection time : 20 .. 999seconds Max. disconnection time : 20 .. 999seconds
Disconnection time
The minimum disconnection time describes, how long a consumer, which is connected to an Emax output, must be disconnected before reconnection. The maximum disconnection time describes, how long a consumer may be disconnected at maximum.
Diagr. Priciple diagram for the digital outputs
UMG505
Digital Outputs
Pulse
width
L1 L2 L3
T
LON-Bus
Index 53, Bit 3-7
MODBUS
Adr. 30
hex, Bit 1-5
Energy meters
T00-T34
Threshold outputs
1-5
Switching clock outputs
1-5
EMAX digital outputs
1-5
EMAX analogue outputs
1-4
No source assigned
+24V=
36
35
34
33
32
31
Digital
Output 5
Digital
Output 4
Digital
Output 3
Digital
Output 2
Digital
Output 1
M Wh
Attention!
The EMAX digital outputs must be assigned to the „Digital Outputs“ in the programming.
CONF
Page 60
60
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
EMAX analogue outputs
The UMG505 has 5 digital and 4 analogue Emax­outputs internally. Each internal Emax analogue output can be assigned to an „analogue output“. If a generator should be controlled by an Emax analogue output, the internal Emax analogue output cannot only be assigned to an „Analogue Output“, but also to a „Digital Output“. The „Digital Output“ is active, when the calculated current of the Emax analogue output is bigger than 0mA. Therefore, this „Digital Output“ can be used as a starting signal for generator control.
MODBUS
Diagr. Priciple diagram for the analogue outputs. Selection of source.
Measured values
EMAX analogue
outputs 1-4
UMG505
Analogue Outputs
0/4 -
20mA
0/4 -
20mA
0/4 -
20mA
+24V=
0V
12
10
9
8
13
11
0/4 - 20mA
0/4 - 20mA
0/4 - 20mA
0/4 - 20mA
22 Ohm
analogue output 4
analogue output 3
analogue output 2
analogue output 1
0/4 -
20mA
Scale start. value
Scale end value
L1
V
01
Attention!
The EMAX analogue outputs must be assigned to an „Analogue Output“ in the programming.
EMAX­analogue output
Maximum connection power
Consumer/ (Generator)
Minimum connection power
Priority
W
W
CONF
EMAX­analogue output
Max. spare power (Min. running time)
Run up time/ (Run up time)
Priority
CONF
W
For the EMAX analogue outputs, the following parameters can be set:
Description Setting range
Priority : 0 .. 9 (0 = off) EMAX analogue output : 1 .. 4 Max. connection power : 0W .. 9999MW Min. connection power : 0W .. 9999MW Consumer
Max. spare power : 0W .. 9999MW Run up time : 10 .. 9999sec.
Generator
Min. running time : 0 .. 9999minutes Run up time : 0 .. 99seconds
Page 61
61
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Generator control
The Run up time is here the time, which the generator needs to supply its power after switching on. The minimum running time is the time, which the generator must run, before it can be disconnected again by the UMG 505. The speed, with what the analogue signal is chan­ging, is 2% of the difference from maximum connection power less minimum connection power per second. The speed cannot be changed directly.
Consumer control
The run up time sets a limit to the starting speed of the consumer’s power. To reach maximum connection power from minimum connection power takes the run up time. The maximum spare power represents the power, that may be spared within one measuring period.
EMAX analogue output
Maximum connection power
Generator
Minimum connection power
Priority
EMAX analogue outputs
Maximum connection power
Consumer
Minimum connection power
Priority
EMAX analogue output
Max. spare power
Run up time
Priority
Max. connection po­wer
Min. connection power
Run up time Run up time
Consumer power
t
P
EMAX analogue po­wer
Minimum running time
Run up time
Priority
W
W
CONF
CONF
CONF
W
W
W
CONF
Description Setting range
Priority : 0 .. 9 (0 = off) EMAX analogue output : 1 .. 4 Max. connection power : 0W .. 9999MW Min. connection power : 0W .. 9999MW Max. spare power : 0W .. 9999MW Run up time : 10 .. 9999sec.
Description Setting range
Priority : 0 .. 9 (0 = off) EMAX analogue output : 1 .. 4 Max. connection power : 0W .. 9999MW Min. connection power : 0W .. 9999MW Minimum running time : 0 .. 9999minutes Run up time : 0 .. 99sec.
Min. running time
Maximum connection po­wer
Minimum connection po­wer
Generator power
t
„analogue
output“
„digital output“
On
Of
Run up time
t
20mA
Page 62
62
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Digital Inputs
The UMG505 has 20 internal inputs. On the internal inputs 1 to 4, the 4 optical inputs (
digital inputs 1-4
) are handled. On the internal inputs 5 to 12 the 8 inputs of the LON-Bus interface (Option), and on the internal inputs 13 to 20 the 8 inputs of the MODBUS interface (Option) are handled. The condition of the digital inputs
digital input 1-4
can be called up via the serial interfaces (Option).
Each of the 20 internal inputs can be assigned to one of the 16 input channels. Each input channel can simultaneously
Changeover an energy meter, Effect the Emax reset, Synchronize the internal clock and Select another target value for Emax pro-
gram.
Two digital inputs (
digital inputs
) can be combined by AND and the result can be assigned to an input channel. In this case, both digital inputs must be active to activate the assigned input channel.
Each of the
digital Inputs 1-4
is assigned to an event counter. The deletion of the event counters is done together with the real energy meters. If a function except pulse valence is assigned to a
digital input 1-4
, all changes of the input are saved
with date and time.
Internal input Comment Indication in third line
0 No input selected No input selected 01 .. 04 Internal inputs of UMG505 Combination with a second internal input 05 .. 12 External input via LON-Bus Just indication "Lon" 13 .. 20 External input via MODBUS Just indication "bus"
CONF
Input channel 0 - 15
Internal input 1 - 20
Digital input (by choice) 1- 4
Digital input 4
Digital input 4
can be used as pulse input for real energy measurement. For this purpose, a pulse valence must be assigned to the
digital input 4
in menu „S0 input“. If the pulse valence was assigned to the
digital input 4
, the changes of the input are
not registered in the event memory.
Call up event counter
Press
key 2
again. The contents of the event counter of Digi- tal input 1 is indica­ted.
Event counter = 3
Go to select mode with
key 1
. The symbol SELECT flashes.
Confirm with
key 2
. The symbol SELECT remains.
Scroll to Digital input 1 with
key 3
.
oFF= no signal. on = signal at input
Press
key 1
for about 2 seconds and you return to the first measured value window of the measured value indication from each program part.
SELECT
SELECT
Page 63
63
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
CONF
W
0
CONFCONFCONF
Principle diagram , digital inputs
Input channel
Diagr. Principle diagram digital inputs
UMG505
Digital Inputs
EMAX target
number
Synchronize
internal clock
EMAX
measuring period
reset
EMAX target num-
ber
Synchronize
internal clock
Activate energy
meter
Activate energy
meter
Input
channel 0
Input
channel
15
28
29
30
2
1
RS485
RS232
A / TXD
B / RXD
GND
Input 13-20
Input 5-12
Index 53
Bit 8 - 15
Addr. 30hex
Bit 0 - 7
7
6
Digital
Input 4
ZMM 3V9
1,5 k
4k
5
4
3
Digital
Input 3
Digital
Input 2
17
16
Digital
Input 1
Event
counter/
memory
5,1 k
5,1 k
Input 1-4
AND
Input 1-4
Meas. value
Psum
Pulse
valence
EMAX measuring
period reset
Event
counter/
memory
Event
counter/
memory
Event
counter/
memory
Page 64
64
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Activate energy meter
In UMG505 up to 30 energy meters are at your disposal. The 6 energy meters Tx0 can only be deleted, but not deactivated. The other 24 energy meters can be deactivated. Only active energy meters count the occurred energy. The changeable energy meters are marked grey in the following dia­gram. The changeover of the energy meters is carried out via the input channels 1-16 or via the switching clock. An energy meter is active, when it is activated via an input channel or the switching clock.
Changeover of EMAX targ. val. (Option)
For the EMAX program, up to 5 targets can be va­lid. If not otherwise programmed, target 1 is active. Via the input channels 1-16 and via the switching clock, one of the 5 targets can be selected and assigned to the EMAX program. If the target is activated via the input channels, and another target simultaneously by the switching clock, the target with the highest target number is used by the EMAX program.
Energy meter
Fix Changeable
Real energy without rev. run. stop T50 T51 T52 T53 T54 Consumption T00 T01 T02 T03 T04 Supply T30 T31 T32 T33 T34 Reactive energy Without rev. run. stop T40 T41 T42 T43 T44 inductive T10 T11 T12 T13 T14 capacitive T20 T21 T22 T23 T24
Diagr. The energy meters of UMG 505.
EMAX target number 1 - 5
Activate energy meter
CONF
Input channel 0 - 15
EMAX target number
Activate energy meter
CONF
Input channel 1 - 16.
Page 65
65
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
EMAX measuring period reset
The reset of the measuring period should be carried out via an input of the UMG 505 to run synchronized to the energy suplliers measurement. If no reset is carried out at the input of the UMG 505 within the programmed measuring period, the reset is done automatically, effected by the internal clock. The reset of the measuring period deletes the EMAX real power and starts a new measuring period. The last measured EMAX real power is used for minimum and maximum storage and, if program­med, saved in event memory.
Synchronize internal clock
Inaccuracies of the internal clock can be corrected by synchronization via one of the internal inputs. If the internal input, which is assigned for synchronicity, is active, the clock in UMG 505 will be set to the nearest full hour.
Example 1 If the UMG 505 shows a time of 15:05h, the clock will be corrected to 15:00h..
Example 2 If the UMG 505 shows a time of 15:35h, the clock will be corrected to 16:00h..
CONF
Input channel 0 - 15
Synchronize clock
EMAX measuring period reset
CONF
Input channel 0 - 15
Synchronize clock
EMAX measuring period reset
Page 66
66
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Pulse valence
With the manufacturer’s settings, the measured value „sum real power“ is calculated by the real po­wer of the single phases. If a pulse valence is assigned to „digital input 4“, the measured value „sum real power“ is calculated by the incoming pulses of „digital input 4“, and changes at the input are no longer registered in event memory. The EMAX program (Option) in UMG505 uses the measured value „sum real power“ for the control of disconnection and connection of the consumers and generators.
Diagr. Principle diagram digital inputs
UMG505
Digital Inputs
Changeover
energy meters
Synchronize
internal clock
Change target
value EMAX
Changeover
energy meters
Synchronize
internal clock
Change target
value EMAX
Reset
EMAX
Reset
EMAX
Input
channel 0
Eingangs-
kanal 15
28
29
30
2
1
RS485
RS232
A / TXD
B / RXD
GND
Input 13-20
Input 5-12
Index 53
Bit 8 - 15
Addr. 30hex
Bit 0 - 7
7
6
Digital
Input 4
ZMM 3V9
1,5 k
4k
5
4
3
Digital
Input 3
Digital
Input 2
17
16
Digital
Input 1
Event
counter/
memory
5,1 k
5,1 k
Input 1-4
AND
Input 1-4
Meas. value
„sum real po-
wer“
Pulse
valence
CONF
Wh
Event
counter/
memory
Event
counter/
memory
Event
counter/
memory
Pulse
valence
Page 67
67
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Digital Outputs
The UMG505 has 5 digital transistor outputs. These outputs are depicted with out1 to out5 in display. Each output can be assigned to different data sources. There are 7 different data sources at disposal:
Threshold outputs, Switching clock outputs, EMAX digital outputs, EMAX analogue outputs, LON-Bus (Option), MODBUS, Energy meters T00 - T04, T30 - T34,
T10-T24, T20 - T24. Each data source can be assigned to one output only. If the output is assigned to an energy meter, the output works as pulse output. The signals from all data sources except the energy meter, can be inverted.
Signal is inverted Signal is not inverted
CONF
Signal inverted. (Not for energy)
Number
threshold
output
Symbol
threshold
output
Diagr. Principle diagram digital outputs
UMG505
Digital Outputs
Pulse
width
L1 L2 L3
T
LON-Bus
Index 53, Bit 3-7
MODBUS
Adr. 30
hex, Bit 1-5
Energy meter
T00-T34
Threshold outputs
1-5
Switching clock outputs
1-5
EMAX digital outputs
1-5
EMAX analogue outputs
1-4
No source assigned
+24V=
36
35
34
33
32
31
Digital
Output 5
Digital
Output 4
Digital
Output 3
Digital
Output 2
Digital
Output 1
M Wh
CONF
Pulse valence = 1Wh pro Impuls
Wh
L1 L2 L3
EDIT CONF
T
Energy meter T00 for real energy consump­tion.
digital output 3
digital output 1
Page 68
68
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Threshold output
In the following programming example, the inverted signal of threshold output 3 is assigned to „digital output 1“.
In menu CONF scroll to the digital outputs using
key 3
.
Scroll to the desired output number with
key 2
.
Confirm selection with
key 1
. The text EDIT ap- pears. The actual data source is flashing.
Change data source with
key 2
. Select data source with the
keys 2
and
3
. Confirm selection with
key 1
. The symbol EDIT appears.
Confirm with
key 2
. The arrow for inverting flashes. The inverting can be changed with
key 3
.
Press
key 1
. Threshold output 3 has been assigned to „digital output 1“ . The symbol EDIT disappears. Scroll through configuration menu with key
3
.
No source
In the following programming example, no source (off) is assigned to „digital output 3“.
In configuration menu CONF scroll to the di­gital outputs with
key
3
.
Scroll to output num­ber 3 with
key 2
.
CONF
Confirm selection with
key 1
. The symbol EDIT appears. Use
key 3
to switch off data source. The indication „oFF“ appears. Confirm selection with
key 2
. The symbol EDIT disappears.
EDIT CONF
CONFEDIT
CONF
EDIT
CONF
EDIT
Threshold output 3
Page 69
69
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
EMAX digital outputs
In the following programming example, the signal of Emax output 1 shall be assigned to digital output 3.
CONF
In menu CONF scroll to the digital outputs using
key 3
.
Scroll to the desired output number with
key 2
.
Confirm selection with
key 1
. The text EDIT ap- pears. The actual data source is flashing. Here no data source has been selected.
Change data source with
key 2
. Select data source with the
keys 2
and
3
. Confirm selection with
key 1
.
Confirm with
key 2
. The arrow for inverting flashes. The inverting can be changed with
key 3
.
EDIT
Press
key 1
. EMAX output 1 has been assigned to „digital output 3“ . The symbol EDIT disappears. Scroll through configuration menu with key
3
.
EDIT CONF
Switching clock outputs
In the following programming example, the signal of a switching clock output 1 should be assigned to digital output 2.
In menu CONF scroll to the digital outputs using
key 3
.
Scroll to the desired output number with
key 2
.
Confirm selection with
key 1
. The text EDIT ap- pears. The actual data source is flashing.
Change data source with
key 2
. Select data source with the
keys 2
and 3. Confirm selection with
key 1
.
EDIT
CONF
Confirm with
key 2
. The arrow for inverting flashes. The inverting can be changed with
key 3
.
EDIT
Press
key 1
. Switching clock output 1 has been assigned to „digital output 2“ . The symbol EDIT disappears. Scroll through configuration menu with key
3
.
Switching clock output
CONF
EDIT
CONF
CONFEDIT
Page 70
70
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
EDIT CONF
CONF
CONF
EDIT
LON-Bus
In the following programming example, Bit 3 with index 53from the LON network variables is assigned to digital output 5.
In menu CONF scroll to the digital outputs using
key 3
.
Scroll to the desired output number with
key 2
.
Confirm selection with
key 1
. The text EDIT ap- pears. The actual data source is flashing.
Change data source with
key 2
. Select data source with the
keys 2
and 3. Confirm selection with
key 1
. The symbol EDIT appears.
Confirm with
key 2
. The arrow for inverting is flashing. Using
key 3
the inverting, here of Bit 7, can be changed.
Press
key 1
. Bit 3 of the LON network variable with index 53 was assigned to digital output 5. The text EDIT disappears. Scroll through configuration menu with key
3
.
MODBUS
In the following programming example, Bit 11 from Hex-address 0x30 (see table 10) is assigned via MODBUS protocol to digital output 4.
In menu CONF scroll to the digital outputs using
key 3
.
Scroll to the desired output number with
key 2
.
Confirm selection with
key 1
. The text EDIT ap- pears. The actual data source is flashing.
Change data source with
key 2
. Select data source with the
keys 2
and 3. Confirm selection with
key 1
. The symbol EDIT appears.
Confirm with
key 2
. The arrow for inverting is flashing. Using
key 3
the inverting, here of Bit 7, can be changed.
CONF
CONF
EDIT
EDIT CONF
Diagr. Data transmission from LON-bus to UMG 505.
31 32 33 34 35 Input 5-12 Dig. Output 1-5 5 6 7 8 9 10 11 12 1 2 3 4 5
15 14 13 12 11 10 9 8 7 6 5 4 3
Index 53
Terminal
UMG505
LON-Bus
Bit
Bit
Press
key 1
. Bit 11 of the MODBUS, HEX-address 0x30 was assigned to digital output 4. The text EDIT disappears. Scroll through configuration menu with key
3
.
Page 71
71
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Set pulse valence
To the pulses of UMG 505, energy can be assigned. The energy per pulse is called pulse valence Iw in Wh/pulse.
Iw = energy/pulse
The pulse valence may not be confused with the meter constant. The meter constant is given in rota­tion per kWh. The correlation between pulse valence and meter constant is:
Meter constant = 1/pulse valence Pulse valence = 1/meter constant
M Wh
kWh
Wh
L1 L2 L3
T
Wh
L1 L2 L3
EDIT CONF
T
Energy meter
Changeable
Real energy without rev. run. stop T50 T51 T52 T53 T54 Consumption T00 T01 T02 T03 T04 Supply T30 T31 T32 T33 T34 Reactive energy without rev. run. stop T40 T41 T42 T43 T44 inductive T10 T11 T12 T13 T14 capacitive T20 T21 T22 T23 T24
Diagr. Overview of the energy meters.
Energy meter
In the following programming example, the consumed real energy is assigned to „digital output 3“.
In menu CONF scroll to the digital outputs using
key 3
.
Scroll to the desired output number with
key 2
.
Confirm selection with
key 1
. The text EDIT ap- pears. The actual data source is flashing.
Change data source with
key 2
. Select data source with the
keys 2
and 3. Confirm selection with
key 1
. The symbol EDIT appears.
The first number of the pulse valence is flashing. Select the digit to be changed with
key 1
and change with
key
3
.
Press
key 1
. Consumed real power was assigned to digital output 3. The text EDIT disappears. Scroll through configuration menu with key
3
.
CONF
CONF
EDIT
Example 1.: The pulse frequency for a total power of 500kW should be calculated, when the pulse valence should be 250Wh/pulse.
Ptot [kW]
Pulse-Freq. [Hz] = ----------------------------------
Pulse valence [Wh] • 3,6
500 kW
Pulse-Freq. = ------------------- =
0,55 Hz
250 Wh • 3,6
Example 2.: The pulse valence for a total power of 100kW should be calculated, if the pulse frequency should be 2Hz.
Ptot [kW]
Pulse valence [Wh] = -----------------------------
Pulse-Freq. [Hz] • 3,6
100 kW
Pulse valence = -------------- =
13,88 Wh
2 Hz • 3,6
Page 72
72
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Pulse width
To each „digital output“, that was assigned to energy, a pulse width and valence can be assigned. In the manufacturers presettings, the pulse width is set to 50ms. The pulse width can be set in the raneg of
50ms to 99,99 seconds. At pulse width of 50ms, pulses with a maximum frequeny of 10 Hz can be given out. Pulses, that cannot be sent, are saved in pulse memory. The pulse memory can save up to 32000 pulses.
Diagr. Principle diagram for digital outputs
UMG505
Digital Outputs
L1 L2 L3
T
M Wh
LON-Bus
Index 53, Bit 3-7
MODBUS
Adr. 30hex, Bit 1-5
Energy meter
T00-T34
Threshold outputs
1-5
Switching clock outputs
1-5
EMAX digital outputs
1-5
EMAX analogue outputs
1-4
No source assigned
+24V=
36
35
34
33
32
31
Digital
Output 5
Digital
Output 4
Digital
Output 3
Digital
Output 2
Digital
Output 1
Pulse width
Pulse width
CONF
Page 73
73
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Analogue outputs
Source, destination and scale
The UMG505 has 4 analogue outputs. The analogue outputs have a common earth and are separated galvanically against the other inputs and outputs of the UMG 505. For the operation of the analogue outputs, an external auxiliary voltage of 20V to 30V DC is required. The maximum burden may not exceed 360 Ohm. If the analogue output is loaded by a bigger resistance, the output range (20mA) is limited. To each analogue output, a range of 4-20mA or 0­20mA can be assigned.
The following sources can be used for the analogue outputs:
- Measured values,
- The internal EMAX analogue outputs 1-4 and
- Values, which are transmitted to UMG 505 via Modbus.
Only measured values, which are configured for the measured values indication, can be given out by the analogue outputs. The measured values of real energy and reactive energy cannot be given out by the analogue outputs.
Select indication
In menu CONF scroll to indication „analogue output (source)“ with
key 3
. Carry on scrolling to the desired analogue output (01-04) pressing
key 2
.
CONF
Source
Number of analogue output
MODBUS
Diagr. Principle diagram analogue outputs. Selection of source.
Measured values
EMAX analogue
outputs 1-4
UMG505
Analogue Outputs
0/4 -
20mA
0/4 -
20mA
0/4 -
20mA
+24V=
0V
12
10
9
8
13
11
0/4 - 20mA
0/4 - 20mA
0/4 - 20mA
0/4 - 20mA
22 Ohm
Analogue output 4
Analogue output 3
Analogue output
2
Analogue output 1
0/4 -
20mA
Scale start value
Scale end value
L1
V
01
CONF
CONF
01
CONF
02
Pulse width
Analogue output, 0/4-20mA
Analogue output (Source and scale)
01
CONF
Page 74
74
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Select analogue output with
key 2
. Confirm selection with
key 1
. The text „AnLo“ flas­hes and the symbol EDIT appears.
Analogue output 01
Example: Measured values Select measured va­lues as source with
key 2
.
V
V
V
L3
L1
L2
CONF
EDIT
V
L1
EDIT
Select a measured value from the indica­tion using
key 1
. The symbol EDIT ap- pears.
V
L1
EDIT CONF
Confirm selection with
key 2
. The first number of the scale start value flashes.
Select digit with
key 1
and change with
key
3
.
Voltage in L1
Scale start
value
Changeover between the source with
key 3
:
- oFF (no source),
- EMAX analogue outputs and
- MODBUS or select measured values with
key 2
.
EDIT CONF
EDIT CONF
Example: EMAX analogue output Select „EMAX analogue output as source with
key 3
. Confirm selection with
key 2
. The programmed EMAX analogue output appears. Select other EMAX analogue outputs with
key 2
and
key 3
.
Example: MODBUS Select MODBUS as source with
key 3
. Confirm selection with
key 2
.
Programming
We are in the indication „analogue output (source)“ with the respective output number. Here, for example analogue output 01. No source oFF has been assigned.
EDIT CONF
The first measured value indication ap­pears. The text „AnLo“ and the symbol EDIT disappear. Select measured value indication with
key 3
.
EMAX analogue output
Only if an EMAX analogue output is programmed, it appears as a source. If an EMAX analogue output is programmed, it is assigned to the analogue output with the same number automatically. An EMAX analogue output cannot be assigned to an analogue output at will.
MODBUS
Scale end
value
Measured value
Page 75
75
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Scale
The text "AnLo" flas­hes. Press
key 1
. The text EDIT ap- pears and the first digit of the scale start value flashes. Pressing
key 1
again, every other digit of the scale start value or scale end value can be selected.
Scale start value and scale end value
Scale start and end value can be set within the setting range of the corresponding measured value.
With
key 3
you can change the flashing number. with
key 2
the decimal
point can be moved:
In the first digit of the scale start value and the scale end value. the sign „-“ can be entered. The sign appears after the number „9“. After selection of the last number of the scale end value, the text EDIT disappears, and you can change to the next menu with
key 3
.
At a selected output range of 4-20mA, a current of 4mA is effected for -100kW and 20mA for 400kW.
L1 L2 L3
W
EDIT
Scale start value at 0/4mA
Scale end value at 20mA
Sign
Scale start value = - 0.100MW = - 100kW Scale end value = 400kW
L1 L2 L3
W
M
k
CONF
EDIT
Scale start value (0/4mA)
Scale end value (20mA )
L1 L2 L3
W
EDIT
MODBUS
Diagr. Principle diagram analogue output, selection of scale start value and scale end value.
Measured values
EMAX analogue
outputs 1-4
UMG505
Analogue Outputs
0/4 -
20mA
0/4 -
20mA
0/4 -
20mA
+24V=
0V
12
10
9
8
13
11
0/4 - 20mA
0/4 - 20mA
0/4 - 20mA
0/4 - 20mA
22 Ohm
Analogue output 4
Analogue output
3
Analogue output 2
Analogue output 1
0/4 -
20mA
Scale start value
Scale end value
L1
V
01
Page 76
76
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Output range
The output range of the analogue outputs of the UMG 505 can be programmed to 0-20mA or 4­20mA. The presettings are 4-20mA.
The text "AnLo" is flashing. Pressing
key 2
, the output range is shown in "mA".
Output range
0..20mA (4..20mA)
Select output range with
key 1
. the text
EDIT appears.
With
key 3
you can select the output range.
CONF
EDIT
CONF
Contrast
Analogue output (output range)
Select indication
In menu CONF scroll to indication „analogue output“ (output range) with
key 3
. Carry on scrolling to the desired analogue output (01-04) with
key 2
.
CONF
01
CONF
02
CONF
CONF
01
CONF
Output range
MODBUS
Diagr. Principle diagram analogue output. Set output range.
Measured values
EMAX analogue
outputs 1-4
UMG505
Analogue Outputs
0/4 -
20mA
0/4 -
20mA
0/4 -
20mA
+24V=
0V
12
10
9
8
13
11
0/4 - 20mA
0/4 - 20mA
0/4 - 20mA
0/4 - 20mA
22 Ohm
Analogue output 4
Analogue output 3
Analogue output 2
Analogue output 1
0/4 -
20mA
Scale start value
Scale end value
L1
V
01
Page 77
77
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Example: Sum real power
The sum real power must be given out via analogue output of UMG 505. As sometimes a generator is connected, also that power shall be transmitted, which is delivered to the energy supplier. Real po­wer supply is marked be a „-“ before the measured value. The following settings are required: Output range = 0 .. 20mA Measured value = Sum real power Scale start value = -100kW (supply) Scale end value = 400kW (consumption)
With the selected settings, a range of 100kW + 400kW = 500kW is covered. Therefore: 500kW = 20mA. 1mA means 500kW/20 = 25kW. If no real power is consumed or supplied, a current of 4mA flows. If real power is supplied, the current is smaller but 4mA.
Example: cos(phi)
Output range = 4 .. 20mA Scale start value = 0.700inductive Scale end value = 0.900capacitive The scale range of 0.400 is divided into 16mA, cos(phi)=1 lies at 16mA.
0mA 4mA 20mA10mA
0,700ind.
0,900cap.
1,000
16mA
0mA 4mA 20mA10mA
-100kW 400kW0kW
15mA
300kW150kW
ConsumptionSupply
Page 78
78
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
LCD contrast
The best direction for the LCD display is „from below“. The contrast of the LCD display can be adapted by the user. The contrast setting is possible in the range of 170 230 in 5 wide steps.
230 = Very light
170 = Very dark To reach the optimum contrast over the whole raneg of temperature, the inner temperature of the device is measured and the contrast setting is corrected automatically. This correction is not indicated in the contrast indication.
Change
Select contrast setting with
key 1,
the number flashes. The text EDIT ap­pears. Increase the contrast setting by 5 with
key
3
. If 230 is exceeded, the value jumps to
170.
EDIT CONF
Select
In menu CONF scroll to the indication of LCD contrast with
key
3
. In this example, the inner temperature is indicated with 28°C and the contrast setting is 185.
Inner temperature
Contrast setting
CONF
Page 79
79
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Clock
Date and time are set to the Middle European summer time. There is no automatical changeover from summer to winter time. Date and time are needed as time information for highest and lowest value and storage of measured values in the ring buffer.
Select In menu CONF move to the indication of date and time with
key 3
. In this example the date is 10.08.1998 and the time is 14:27:15.
Change With
key 1
a number can be selected and changed with
key 3
. The selected digit is flashing. The text "EDIT" ap­pears. Date and time stop.
Date and time can be called up and changed in menu CONF. Therefore please change to menu
CONF (See chapter "configuration").
Y.M
D.H
M.S
EDIT CONF
Save When you have set the actual date and time, please press
key 1
as often as no number is flashing any longer. Pressing
key 2,
the text EDITdisappears and date and time run with their new set­tings.
Y.M
D.H
M.S
CONF
Summer-/Winter time changeover
The UMG505 can carry out an automatical change­over of the summer/winter time. The following possibilities are available: oFF - No summer/winter time changeover. on - Specific changeover. Eu - Listed changeover times.
At the date, marked with the arrow downwards, the time jumps back from 03:00 to 02:00. At the date marked with the arrow upwards, the time jumps from 02:00 to 03:00.
Specific changeover If the summer wintertime changeover is activated „on“, both changeover times can be entered individually. The changeover times from the list are not used.
Listed changeover times In the UMG505, a list of changeover times is deposited until year 2020. In this list, the changeo­ver times are always set to the last weekend in March and the last weekend in October of each year. If the summer/winter changeover is set to "Eu", the changeover times of this list are used.
Y.M
D.H
M.S
CONF
Select In menu CONF you scroll to the indication of date and time with
key 3
and use
key 2
to reach the summer time changeover. In this example, the date 25.03.2001 is in­dicated.
Pressing
key 2
again, the winter time chan­geover is indicated.
Summer time changeover
Y.M
D.H
M.S
CONF
Day Year
Month
Minute
Second
Hour
Y.M
D.H
M.S
CONF
Winter time changeover
Page 80
80
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Password
Special functions of the device are protected by passwords. There are three types of passwords:
Clearance password (8-digit) User password (4-digit) Master password (4-digit)
CONF
Select In menu CONF you move to the indication of the password with
key 3
. In the basic setting a 0000 0000 is indica­ted.
EDIT CONF
Input With
key 1
you select the cipher to be chan­ged. The text EDIT appears within the in­dication With
key 3
you change the selected number.
Clearance password
In the various device variants functions are available as an option. These function expansions can be released in the manufacturing works, when ordering. When later a functional expansion shall be released by the user, a clearance password is needed with 8 digits. This password is deposited in the manufac­turing works.
Functional expansions (options), that can be released:
EMAX
To release a functional expansion via the clearance password, please proceed as follows:
Function
User or master password
CONF
Clearance password
CONF
Clearance password "0000 0000"
Save When the password is put in, please confirm
key 1
as often as no digit is flashing any longer and con­firm with
key 2
. When the password is accepted, the password is deleted and 0000 0000 appears in the indication. Now the released functional expansion can be called up in the programming or configuration menu.
Page 81
81
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Master password
The four digit master password is needed for service purpose only and it is not announced to the user.
Function Comment
0004 Delete user password. 7645 Restore delivery conditions.
After calling up the function „0004“, the user pass­word is set back to the condition of delivery:
User password = "0000".
Now programming and configuration is possible with user password "0000" again with function „0002“.
The input of the master password is done in the same way like the user password.
User password
With the four digit user password the user can protect the programmed data and configuration against unintentional change. The programming and configuration will just be indicated but cannot be changed. In delivery condition, the user password is "0000". If the user cannot remember the user password, it can be changed with the master password only.
There are four functions for the user password at your disposal:
Function Description
0001 Lock programming and configuration. 0002 Admit programming and configuration. 0003 Input user password. 0004 Delete user password.
To activate a function, the user password and the desired function must be put in the password menu. A new user password can be put in, when it was deleted with function 4 by putting in the old user password. A deleted password is indicated with "0000".
EDIT CONF
Input Select the number to be changed using
key
1
. The text EDIT is flashing in the indi­cation. The selected number is flashing. Change the selected number using
key 3
.
Save When you have put in the password and function, press
key 1
as often as no number is flashing any
longer and confirm with
key 2
. If the password was accepted, the password is deleted and 0000 0000 appears in the indication.
Function
User or master pass­word
CONF
Page 82
82
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Serial number
Each device has its 8 digit serial number, which can­not be changed by the user. For several devices, even after delivery a release of certain functions is possible. In this case, the serial number of the device is needed in the manufactu­ring works. For each device there are passwords deposited in the producing works for releasing the functions (options).
Software Release
The software within the device is ammended and expanded continously. The software issue of the devices are therefore marked with a software release. The software release cannot be overwritten by the customer.
Select Scroll to indication of the software release in menu CONF with
key 3
. In this example, the software release is indicated with 2.010.
The software release can be called up in menu CONF. Please change into menu CONF (see chapter "Configuration").
Example: Serial number = 5400 0003
CONF
CONF
Page 83
83
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
PSW505
The programming and evaluation software PSW505 belongs to the contents of delivery of the UMG505. With this software, you can
- Configure the display,
- Read out event memory and ring buffer and save it to PC and
- Read, change and save configuration by PC.
For the operation, a PC with COM interface and Windows® operating system is required. The connection between UMG 505 and PC can be carried out via RS232 or RS485 interface, depen­ding on the version of UMG 505. If the UMG 505 has a RS232 interface, the connec­tion to PC is carried out via zero modem cable. If the UMG 505 has a RS485 interface, the connec­tion to PC must be carried out via an interface con­verter.
Functions
Configure the UMG505
A simple configuration of the UMG 505 can be done directly via the three function keys and display. But the more comfortable way of programming the UMG 505 is possible with the function "Configuration of UMG505" with PSW505 and PC. Configurations can be saved on PC. Only the measured value indications can be printed.
Configure measured value indications
With the manufacturer’s presettings, only a part of the possible measured values is indicated by UMG
505. This program part allows:
- To read the actual configuration of the measured value indications.
- To load a configuration of the measured value indications from PC.
- Determine the sequence of the indicated measured values.
- Load the configuration of the measured value indications into UMG 505.
- Save the configuration of the measured value indications to PC.
Read memory
The memory of the UMG 505 is divided into three ranges:
the event memory, the ring buffer and
the storage for minimum and maximum values. The event memory and ring buffer can be read out by PC only. The minimum and maximum values can be called up at UMG 505 directly via the keys.
Protocol
01 = MODBUS
PSW505
RS232
RS485
UMG505
Converter
RS232
RS485
Diagr. UMG505 with RS485 interface.
PC hardware
The hardware, on which the PSW505 can be installed, should fullfill the following minimum requirements:
- CPU, AMD®/Intel® from 200MHz,
- 32 MByte main memory,
- ca. 5MB harddisk for the program,
- Colour monitor, 800x600, 265 colours,
- 8MByte Graphical board,
- CD-ROM drive,
- Serial interfaces (COM1/2 ..)
PC operating system
The software PSW505 can run with the following operating systems:
- WIN98SE® or
- NT4.0® with SP3 or
- WIN2000® with SP2.
Zero modem cable
Protocol
01 = MODBUS
PSW505
RS232 RS232
UMG505
Diagr. UMG505 with RS232 interface.
Page 84
84
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Tables
Overview
Table 1a Measured values in floating point format Table 1b Measured values in floating point format Table 2a Time information for minimum and maximum values and time information Table 2b Time information for min. and max. values and time of summer /winter changeover Table 3 Averaging times of measured values Table 4a Measured values, integer format Table 4b Mean values, integer format Table 4c Maximum values, integer format Table 4d Minimum values, integer format Table 5 Energy, integer format Table 6 Delete energy Table 7 Energy, floating point format Table 8 EMAX peak values Table 9 Scale of the measured values, which are called up in integer format Table 10 Digital and analogue inputs and outputs Table 11 List of LON network variables
Data formats
For the data, the following formats are used:
char : 1 Byte (0 .. 255) word : 2 Byte (- 32 768 .. + 32 767) unsign. long : 2 Byte (0 .. 4 294 967 296) long : 4 Byte (- 2 147 483 648 .. + 2 147 483 647) float : 4 Byte (IEEE754) double : 8 Byte (IEEE754)
The sequence of bytes is high before low byte.
Page 85
85
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Table 1a, Measured values
Measured values in floating point format
Description Address
(dez) r/w
1)
Type Unit Comment
Current 1000 r Meas. val. A L1, L2, L3 Voltage N-L 1012 r Meas. val. V L1, L2, L3 Voltage L-L 1024 r Meas. val. V L1-L2, L2-L3, L1-L3 Real power 1036 r Meas. val. W Sign. -=supply, +=consumption Apparebt power 1048 r Meas. val. VA L1, L2, L3 Reactive power 1060 r Meas. val. var Sign -=cap, +=ind Cos(phi) 1072 r Meas. val. Sign -=cap, +=ind Frequency 1084 r Meas. val. Hz L1, L2, L3 Real power, Sum 1096 r Sum W Sign -=supply, +=Consumption Apparent power, Sum 1100 r Sum VA Reactive power, Sum 1104 r Sum var Sign -=cap, +=ind Cos(phi), Sum 1108 r Sum Sign -=cap, +=ind Total harmonic distortion _U Measured value 1112 r float % Maximum value 1115 r float % Total harmonic distortion _I Measured value 1118 r float %
1120 Maximum value 1121 r float % Partial harmonic content _U Maximum value 1124 r float[20][3] V Partial harmonic 1-20; L1, L2, L3
1132
..
1180 Partial harmonic content _U Measured value 1184 r float[20][3] V Partial harmonic 1-20; L1, L2, L3
1192
..
1240 Partial harmonic content _I Maximum value 1244 r float[20][3] A Partial harmonic 1-20; L1, L2, L3
1252
..
1300 Partial harmonic content _I Measured value 1304 r float[20][3] A Partial harmonic 1-20; L1, L2, L3
1312
..
1360 Real power EMAX 1365 r Emax W Sign. -=Supply, +=Consumption
1372
1384
Measured values {float: Actual value [L1, L2, L3], Mean value[L1, L2, L3], Minimun value[L1, L2, L3], Maximum value[L1, L2, L3]} Sum {float: Actual value[Sum], Mean value[Sum], Minimum value[Sum], Maximum value[Sum]} Emax {float: Actual value[Sum], Minimum[Sum], Maximum value[Sum]}
1) r/w = read/write
Page 86
86
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Table 1b, Messwerte
Measured values in floating point format
Description Address
(dez) r/w
1)
Type Unit Comment
Total harmonic distortion _U Mean value 1390 r float[3] % L1, L2, L3 Total harmonic distortion _I Mean value 1393 r float[3] % L1, L2, L3
1396 Partial harmonic content _U Minimum value 1400 r float[20][3] V Partial harmonic 1-20; L1, L2, L3
1408
..
1456 Partial harmonic content_I Minimum value 1460 r float[20][3] A Partial harmonic 1-20; L1, L2, L3
1468
..
1516 Partial harmonic content _U Mean value 1520 r float[20][3] V Partial harmonic 1-20; L1, L2, L3
1528
..
1576 Partial harmonic content _I Mean value 1580 r float[20][3] A Partial harmonic 1-20; L1, L2, L3
1588
..
1636 Total harmonic distortion _U Minimum value 1640 r float[3] % L1, L2, L3
Total harmonic distortion _I Minimum value 1643 r float[3] % L1, L2, L3
Current, N 1646 r float A
1648
1660 Maximum value of
current mean value 1663 r float[3] A L1, L2, L3
Page 87
87
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Table 2a, Time information
Time information for the minimum and maximum values and system time
Description Address
(dez) r/w
1)
Type Comment
System time 3000 r date System time Current L1, L2, L3 3001 r date[2][3] Min.-, max.- val.; L1, L2, L3 Voltage N-L 3007 r date[2][3] Min.-, max.- val.; L1, L2, L3 Voltage L-L 3013 r date[2][3] Min.-, max.- val.; L1, L2, L3 Real power 3019 r date[2][3] Min.-, max.- val.; L1, L2, L3 Apparent power 3025 r date[2][3] Min.-, max.- val.; L1, L2, L3 Reactive power 3031 r date[2][3] Min.-, max.- val.; L1, L2, L3 Cos(phi) 3037 r date[2][3] Min.-, max.- val.; L1, L2, L3 Frequency 3043 r date[2][3] Min.-, max.- val.; L1, L2, L3 Real power, Sum 3049 r date[2] Min.-, max.- val.; Apparent power, Sum 3051 r date[2] Min.-, max.- val.; Reactive power, Sum 3053 r date[2] Min.-, max.- val.; Cos(phi), Sum 3055 r date[2] Min.-, max.- val.; Total harmonic distortion_U Maximum value 3057 r date[3] L1, L2, L3 Total harmonic distortion_I Maximum value 3060 r date[3] L1, L2, L3
3061 Partial harmonic distortion_U Maximum value 3063 r date[20][3] Partial harmonic 1-20; L1, L2, L3
3067
..
3121 Partial harmonic content_I Maximum value 3123 r date[20][3] Partial harmonic 1-20; L1, L2, L3
3127
..
3181 free 3187 free 3188 free 3189 Real energy consumption T00 3190 r date Deletion time React. energy inductive T10 3191 r date Deletion time React. energy capacitive T20 3192 r date Deletion time Real energy supply T30 3193 r date Deletion time Reactive energy Without rev. run. stop T40 3194 r date Deletion time Real energy Without rev. run. stop T50 3195 r date Deletion time free 3196
.. ..
free 3198 free 3199
Format of time information: date {char: Year, Month, Day, Hour, Minute, Second}Year: 00 .. 99 = 2000 .. 2099
Page 88
88
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Table 2b, Time information
Time information for the minimum and maximum values and system time
Description Address
(dez) r/w
1)
Type Comment
free 3205 Partial harmonic content_U Minimum value 3210 r date[20][3] Partial harmonic 1-20; L1, L2, L3
3211 .. 3265
Partial harmonic content_U Minimum value 3270 r date[20][3] Partial harmonic 1-20; L1, L2, L3
3271 ..
3325 free 3331 free 3332 Total harmonic distortion_I Minimum value 3333 r date[3] L1, L2, L3 Current, N 3336 r date[2] Minimum and maximum value, Maximum value 3337 Real power EMAX 3338 r date[2] Minimum and maximum value, Current mean val. (L1, L2, L3) 3340 r date[2][3] Min.- and max.- value; L1, L2, L3 Time changeover 3343 r date2[2] Summer/wintertime in seconds
0 = oFF - No summer/winter changeover. 1 = on - Individual changeover. 2 = Eu - Listed changeover.
Format of time information:
date {char: year, month, day, hour, minute, second} year: 00 .. 99 = 2000 .. 2099
Format of time information:
date2 {char: year, month, day, hour, minute, second} year: 00 .. 99 = 2000 .. 2099
0 = oFF - No summer/winter changeover 1 = on - Individual changeover. 2 = Eu - Listed changeover.
Page 89
89
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Table 3, Mean values
Averaging times and mean values
Description Address
(dez) r/w
1)
Type Description
Current 4000 r date[3] L1, L2, L3 Voltage N-L 4003 r date[3] L1, L2, L3 Voltage L-L 4006 r date[3] L1-L2, L2-L3, L1-L3 Real power 4009 r date[3] L1, L2, L3 Apparent power 4012 r date[3] L1, L2, L3 Reactive power 4015 r date[3] L1, L2, L3 Cos(phi) 4018 r date[3] L1, L2, L3 Frequency 4021 r date[3] L1, L2, L3 Real power, Sum 4024 r date Real power EMAX 4156 r date 5=5, 6=10, 7=15, 8=30, 9=60 Minutes Apparent power, Sum 4025 r date Reactive power, Sum 4026 r date Cos(phi), Sum 4027 r date Current, N 4028 r date Total harmonic distortion _U 4150 r date[3] L1, L2, L3 Total harmonic distortion _I 4153 r date[3] L1, L2, L3 Partial harmonic content_U 4030 r date[20][3] Partial harmonic 1-20; L1, L2, L3 Partial harmonic content _I 4090 r date[20][3] Partial harmonic 1-20; L1, L2, L3
1)
r/w = read/write
Format of time information: date {char: year, month, day, hour, minute, second} year: 00 .. 99 = 2000 .. 2099
Page 90
90
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Table 4a, measured values
Measured values in integer format
Measured values Address
(dez) r/w
1)
Format Unit Comment
Current 8000 r word[3] A L1, L2, L3 Voltage 8003 r word[3] V N-L1, N-L2, N-L3 Voltage 8006 r word[3] V L1-L2, L2-L3, L1-L3 Real power
2)
8009 r word[3] W L1, L2, L3 Apparent power 8012 r word[3] VA L1, L2, L3 Reactive power
3)
8015 r word[3] var L1, L2, L3 Cos(phi)
3)
8018 r word[3] L1, L2, L3 Frequency 8021 r word[3] Hz L1, L2, L3 Real power, Sum
2)
8024 r word W Apparent power, Sum 8025 r word VA Reactive power, Sum
3)
8026 r word var Cos(phi), Sum
3)
8027 r word Current, N 8028 r word A Current in Neutral Partial harmonic content _U 8030 r word[20][3] V Part. harm.1-20; L1, L2, L3
8036
..
8084 Partial harmonic content _I 8090 r word[20][3] A Part. harm.1-20; L1, L2, L3
8096
..
8144 Total harmonic distortion _U 8150 r word[3]
0
/00 L1, L2, L3
Total harmonic distortion _I 8153 r word[3]
0
/00 L1, L2, L3
Real power EMAX, Sum
2)
8156 r word W
1) r/w = read/write
2) Sign - = supply, + = consumption
3) sign - = cap, + = ind
Page 91
91
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Table 4b, measured values
Mean values in integer format
Mean values Address
(dez) r/w
1)
Format Unit Comment
Current 8157 r word[3] A L1, L2, L3 Voltage 8160 r word[3] V N-L1, N-L2, N-L3 Voltage 8163 r word[3] V L1-L2, L2-L3, L1-L3 Real power
2)
8166 r word[3] W L1, L2, L3
8168 Apparent power 8169 r word[3] VA L1, L2, L3 Reactive power
3)
8172 r word[3] var L1, L2, L3 Cos(phi)
3)
8175 r word[3] L1, L2, L3 Frequency 8178 r word[3] Hz L1, L2, L3
8180 Real power, Sum
2)
8181 r word W Apparent power, Sum 8182 r word VA Reactive power, Sum
3)
8183 r word var Cos(phi), Sum
3)
8184 r word Current, N 8185 r word A Current in Neutral Partial harmonic content _U 8187 r word[20][3] V Part. harm. 1-20; L1, L2, L3
8192
..
8240 Partial harmonic content _I 8247 r word[20][3] A Part. harm. 1-20; L1, L2, L3
8252
..
8300 Total harmonic distortion _U 8307 r word[3]
0
/00 L1, L2, L3
Total harmonic distortion _I 8310 r word[3]
0
/00 L1, L2, L3
Page 92
92
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Table 4c, maximum values
Maximum values in iteger format
Maximum values Address
(dez) r/w
1)
Format Unit Comment
Current 8314 r word[3] A L1, L2, L3 Voltage 8317 r word[3] V N-L1, N-L2, N-L3 Voltage 8320 r word[3] V L1-L2, L2-L3, L1-L3 Real power
2)
8323 r word[3] W L1, L2, L3 Apparent power 8326 r word[3] VA L1, L2, L3 Reactive power
3)
8329 r word[3] var L1, L2, L3 Cos(phi)
3)
8332 r word[3] L1, L2, L3 Frequency 8335 r word[3] Hz L1, L2, L3 Real power, Sum
2)
8338 r word W Apparent power, Sum 8339 r word VA Reactive power, Sum
3)
8340 r word var Cos(phi), Sum
3)
8341 r word Current, N 8342 r word A Current in Neutral Partial harmonic content _U 8344 r word[20][3] V Part. harm. 1-20; L1, L2, L3 Partial harmonic content _I 8404 r word[20][3] A Part. harm. 1-20; L1, L2, L3 Total harmonic distortion _U 8464 r word[3]
0
/00 L1, L2, L3
Total harmonic distortion _I 8467 r word[3]
0
/00 L1, L2, L3
Real power EMAX, Sum
2)
8470 r word W Current mean value 8663 r word[3] A L1, L2, L3
1) r/w = read/write
2) Sign - = Supply, + = Consumption
3) Sign - = cap, + = ind
Page 93
93
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Table 4d, Minimum values
Mean values in integer format
Minimum values Address
(dez) r/w
1)
Format Unit Comment
Current 8471 r word[3] A L1, L2, L3 Voltage 8474 r word[3] V N-L1, N-L2, N-L3 Voltage 8477 r word[3] V L1-L2, L2-L3, L1-L3 Real power
2)
8480 r word[3] W L1, L2, L3 Apparent power 8483 r word[3] VA L1, L2, L3 Reactive power
3)
8486 r word[3] var L1, L2, L3 Cos(phi)
3)
8489 r word[3] L1, L2, L3 Frequency 8492 r word[3] Hz L1, L2, L3 Real power, Sum
2)
8495 r word W Apparent power, Sum 8496 r word VA Reactive power, Sum
3)
8497 r word var Cos(phi), Sum
3)
8498 r word Current, N 8499 r word A Current in neutral Partial harmonic content _U 8501 r word[20][3] V Part. harm.1-20; L1, L2, L3 Partial harmonic content _I 8561 r word[20][3] A Part. harm.1-20; L1, L2, L3 Total harmonic distortion _U 8621 r word[3]
0
/00 L1, L2, L3
Total harmonic distortion _I 8624 r word[3]
0
/00 L1, L2, L3
Real power EMAX, Sum
2)
8627 r word W
Page 94
94
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
1) r/w = read/write
Table 5, read energy
Energy in integer format
Energy Address
(dez) r/w
1)
Format Unit Comment
Real energy consumption, T10 9000 r long Wh scale see address 9102 Real energy supply, T30 9001 r long Wh scale see address 9102 Real energy without rev. run. stop, T50 9002 r long Wh scale see address 9102 Reactive energy capacitive, T20 9003 r long varh scale see address 9102 Reactive energy inductive, T10 9004 r long varh scale see address 9102 React. energy without rev. run. stop T40 9005 r long varh scale see address 9102 Running time of energy meters 7600 r date[6][5] sec. Running time in seconds
Format of time information: date {unsign. long}
Table 6, delete energy
Description Address(dez) r/w1)Format Unit Comment
Delete real energy 576 w word 1=delete Delete reactive energy 578 w word 1=delete Delete maximum values 580 w word 1=delete Delete minimum values 582 w word 1=delete
Table 8, EMAX-maximum values
EMAX-maximum values
Description Address
(dez) r/w
1)
Format Comment
Real power EMAX
Peak value 16000 r float [Tariff] [Month] Measured value in Watt.
Date
Year 16500 r char [Month] In which year the month was. Day 16600 r char [Tariff] [Month] On which day of the month the
peak value ocurred.
Time
Hour 16700 r char [Tariff] [Month] Minute 16800 r char [Tariff] [Monat]
For each month, one peak value is saved per tariff. After one year, the peak value is overwritten.
Year = 0 .. 99 00 .. 99 = 2000 .. 2099 Tariff = 0 .. 4 0 = T00, 1 = T01, .. Month = 0 .. 11 0 = January, 1 = February, ..
Table 7, energy
Energy in floating point format
Description Address
(dez) r/w
1)
Type Unit Comment
Real energy consumption 2000 r double[5] Wh Energy, T00 .. T04 Reactive energy inductive 2010 r double[5] varh Energy, T10 .. T14 Reactive energy capacitive 2020 r double[5] varh Energy, T20 .. T24 Real energy supply 2030 r double[5] Wh Energy, T30 .. T34 React. energy without rev. run. stop 2040 r double[5] varh Energy, T40 .. T44 Real energy without rev. run. stop 2050 r double[5] Wh Energy, T50 .. T54
Page 95
95
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Within the UMG 505 almost all measured values are available in floating point format (Table 2). For the transmission of measured values the floating point values are recalculated in integer format by the UMG 505, such as char, int and word (Table 4). To lose no digits after decimal point, the value, that should be transmitted, is scaled. The opening value from UMG 505 is calculated as follows:
Measured value = Transmitted value * Factor
The scales of the measured values are calculated from UMG 505 out of current and voltage transformer ratio. Here the minimum definition of the transmitted value of 0,1% is strived for.
The scales of the UMG 505 can be retrieved under the following addresses:
Example
Transmitted value UMG 505 = 2301 Programmed scale = -1 Which voltage is measured by the UMG 505?
From the scale table, you can read the factor =/10 for scale=-1:
Measured value = Transmitted value * Factor Measured value = 2301 * 1/10 Measured value = 230,1V
The measured voltage is 230,1V.
Measured values Address
(dez) r/w
1)
Format Possible scale
Currents 9100 r word -3 .. 6 Voltage 9101 r word -3 .. 6 Power 9102 r word -3 .. 6 Cos(phi) 9103 r word -3 Frequency 9104 r word -2 THD 9105 r word -3
10 scale factors are at your disposal: Scale Factor
-3 /1000
-2 /100
-1 /10 0 1 1* 10 2 * 100 3 * 1 000 4 * 10 000 5 * 100 000 6 * 1000 000
The scale of energy is determined by the scale of power
1) r/w = read/write
Table 9, Scale
Scale of measured values, which are called in integer format.
Page 96
96
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
1) r/w = read/write
Table 10, Inputs and outputs
Description Address r/w1)Format Unit Comment
Digital Input 1-4, Energy meter 272
dez r/w long[4] -
Analogue output 1-4 544
dez r/w word[4] - Range 0 -10000
0 = 0/4mA, 10000=20mA
Description Address r/w1)Format Unit Comment
Digital Inputs 20
hex r word - Assignment see diagr.
17 4 5 6 3534333231 Input 1-4 Digital Output 1234 5 4 3 2 1
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
0 1 2 3 4 5 6 ....
Terminal
Bit
UMG505
MODBUS
Word 1
Bit
MODBUS
Word 0
Bit
31 32 33 34 35 Input 13-20 Digital Output 13 14 15 16 17 18 19 20 1 2 3 4 5
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
0 1 2 3 4 5 6 ....
MODBUS
Word 1
Bit
MODBUS
Word 0
Bit
Terminal
Bit
UMG505
Description Address r/w1)Format Unit Comment
Digital Outputs 30
hex r/w word - Assignment see Diagr.
Page 97
97
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Page 98
98
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Table 11, LON variables
Description SNVT-Typ Indic. Direction Unit Presett. Type Comment
nvi00Request SNVT_obj_request 0 Output nvi00Request nvo00Status SNVT_obj_status 1 Output nvo00Status volt_NL1 SNVT_volt_f 2 Output V float voltage L1-N volt_NL2 SNVT_volt_f 3 Output V float voltage L2-N volt_NL3 SNVT_volt_f 4 Output V float voltage L3-N volt_LL12 SNVT_volt_f 5 Output V float voltage L1-L2 volt_LL23 SNVT_volt_f 6 Output V float voltage L2-L3 volt_LL31 SNVT_volt_f 7 Output V float voltage L3-L1 amp_L1 SNVT_amp_f 8 Output A float current L1 amp_L2 SNVT_amp_f 9 Output float current L2 amp_L3 SNVT_amp_f 10 Output A float current L3 power_L1 SNVT_power _f 11 Output W float real power L1 power_L2 SNVT_power _f 12 Output W float real power L2 power_L3 SNVT_power _f 13 Output W float real power L3 frq_L1 SNVT_freq _f 14 Output Hz float frequency L1 frq_L2 SNVT_freq _f 15 Output Hz float frequency L2 frq_L3 SNVT_freq _f 16 Output Hz float frequency L3 amp_L1_avg SNVT_amp_f 17 Output A float Strommittelwert L1 amp_L2_avg SNVT_amp_f 18 Output A float Strommittelwert L2 amp_L2_avg SNVT_amp_f 19 Output A float Strommittelwert L3 amp_L1_avg_max SNVT_amp_f 20 Output A float Maximaler Strommittelwert L1 amp_L2_avg_max SNVT_amp_f 21 Output A float Maximaler Strommittelwert L2 amp_L3_avg_max SNVT_amp_f 22 Output A float Maximaler Strommittelwert L3 cos_phi_L1 SNVT_pwr_fact_f 23 Output float Cos-phi L1 cos_phi_L2 SNVT_pwr_fact_f 24 Output float Cos-phi L2 cos_phi_L3 SNVT_pwr_fact_f 25 Output float Cos-phi L3 r_power_L1 SNVT_power_f 26 Output var float reactive power L1 r_power_L2 SNVT_power_f 27 Output var float reactive power L2 r_power_L3 SNVT_power_f 28 Output var float reactive power L3 va_power_L1 SNVT_power_f 29 Output VA float Scheinleistung L1 va_power_L1 SNVT_power_f 30 Output VA float Scheinleistung L2 va_power_L1 SNVT_power_f 31 Output VA float Scheinleistung L3 energie SNVT_elec_whr_f 32 Output Wh float real energy, sum t1_energie SNVT_elec_whr_f 33 Output Wh float real energy, T1 t2_energie SNVT_elec_whr_f 34 Output Wh float real energy, T2 r_energie SNVT_elec_whr_f 35 Output varh float reactive energy, ind. t1_r_energie SNVT_elec_whr_f 36 Output varh float reactive energy, ind T1 t2_r_energie SNVT_elec_whr_f 37 Output varh float reactive energy, ind T2 power_tot SNVT_power_f 38 Output W float real energy, sum va_power_tot SNVT_power_f 39 Output VA float Scheinleistung, sum r_power_tot SNVT_power_f 40 Output var float reactive energy, sum cos_phi_tot SNVT_pwr_fact_f 41 Output float Cos-phi, sum power_tot_max SNVT_power_f 42 Output W float Wirkleistung, Summe Maximum va_power_tot_max SNVT_power_f 43 Output VA float Scheinleistung, Summe Max. system_time SNVT_time_stamp 44 Output Systemzeit UMG505 (nur lesen) input_state SNVT_state 45 Input Status der Ein-/Ausgänge
Configuration properties
amp_deltaI SNVT_amp_f 46 Input A 0 float DELTA I
1)
amp_deltaU SNVT_amp_f 47 Input V 0 float DELTA U
1)
power_delta SNVT_power_f 48 Input W 0 float DELTA P
1)
frq_delta SNVT_freq_f 49 Input Hz 0 float DELTA F
1)
cos_phi_delta SNVT_pwr_fact_f 50 Input 0 float DELTA cos-phi
1)
energie_delta SNVT_elec_whr_f 51 Input 0 float DELTA Energie
1)
maxsendtime NONE 52 Input sec 0 unsig. MaxSendTime
long outputState SNVT_state 53 Input Setzen der intern. Ein-/Ausgänge rset_energie SNVT_lev_disc 54 Input Energiezähler löschen
Page 99
99
= Key1
= Key 2 = Key 3
= Max. value or consumption = Min. value or supply
BIT Belegung: nvoInputState = Bit 0 nicht benutzt
Bit 1 nicht benutzt Bit 2 nicht benutzt Bit 3 nicht benutzt Bit 4 Status Digital Eingang 4 Bit 5 Status Digital Eingang 3 Bit 6 Status Digital Eingang 2 Bit 7 Status Digital Eingang 1 Bit 8 nicht benutzt Bit 9 nicht benutzt Bit 10 nicht benutzt Bit 11 Status Digital Ausgang 1 Bit 12 Status Digital Ausgang 2 Bit 13 Status Digital Ausgang 3 Bit 14 Status Digital Ausgang 4 Bit 15 Status Digital Ausgang 5
nvoOutputState = Bit 0 nicht benutzt
Bit 1 nicht benutzt Bit 2 nicht benutzt Bit 3 setzt Digital Ausgang 3
2)
Bit 4 setzt Digital Ausgang 4
2)
Bit 5 setzt Digital Ausgang 3
2)
Bit 6 setzt Digital Ausgang 2
2)
Bit 7 setzt Digital Ausgang 1
2)
Bit 8 interner Eingang 12 Bit 9 interner Eingang 11 Bit 10 interner Eingang 10 Bit 11 interner Eingang 9 Bit 12 interner Eingang 8 Bit 13 interner Eingang 7 Bit 14 interner Eingang 6 Bit 15 interner Eingang 5
Page 100
100
= Key1 = Key 2 = Key 3
= Max. value or consumption = Min. value or supply
Min. val. voltage L1-L2
Min. val. voltage L2-L3
Min. val. voltage L3-L1
Max. val. voltage L1-L2
Max. val. voltage L2-L3
Max. val. voltage L3-L1
Mean val. voltage L1-L2
Mean val. voltage L2-L3
Mean val. voltage L3-L1
Meas.val. voltage L1-L2
Meas. val. voltage L2-L3
Meas. val. voltage L3-L1
Min. val. current L1
Min. val. current L2
Min. val. current L3
Max. val. current L1
Max. val. current L2
Max. val. current L3
Mean val. current L1
Mean val. current L2
Mean val. current L3
Meas. val. current L1
Meas. val. current L2
Meas. val. current L3
Min. val. real power L1
Min. val. real power L2
Min. val. real power L3
Max. val. real power L1
Max. val. real power L2
Max. val. real power L3
Mean val. real power L1
Mean val. real power L2
Mean val. real power L3
Meas. val. real power L1
Meas. val. real power L2
Meas. val. real power L3
Mean val. app. power L1
Mean val. app. power L2
Mean val. app. power L3
Meas. val. app. power L1
Meas. val. app. power L2
Meas. val. app. power L3
Max. val. app. power L1
Max. val. app. power L2
Max. val. app. power L3
Min. val. app. power L1
Min. val. app. power L2
Min. val. app. power L3
Measured value indications (Presettings)
Mean val. react. power
L1
Mean val. react. power
L2
Mean val. react. power
L3
Meas. val. react. power
L1
Meas. val. react. power
L2
Meas. val. react. power
L3
Max. val. react. power L1
Max. val. react. power L2
Max. val. react. power L3
Min. val. react. power L1
Min. val. react. power L2
Min. val. react. power L3
Min. val. voltage L1-N
Min. val. voltage L2-N
Min. val. voltage L3-N
Max. val. voltage L1-N
Max. val. voltage L2-N
Max. val. voltage L3-N
Mean val. voltage L1-N
Mean val. voltage L2-N
Mean val. voltage L3-N
Meas. val. voltage L1-N
Meas. val. voltage L2-N
Meas. val. voltage L3-N
Loading...