janitza UMG 503 Operating Instructions Manual

Universal Measuring Device
UMG 503
Operating instructions
Doc. No.: 1.016.033.r Series IV SW. Rel.: 3.xxx
Janitza electronics GmbH
Vor dem Polstück 1 D-35633 Lahnau Support Tel. (0 64 41) 9642-22 Fax (0 64 41) 9642-30 e-mail: info@janitza.de Internet: http://www.janitza.de
Mean value
Displayed phase,
- Outer conductor against N,
- Phase to phase,
- Sum measurement.
Peak values Lowest values Mark for the selected ring buffer values
Consumption Delivery
Key 1
Indication of operation mode Key 3 Key 2
Current transformers Harmonic number/Tariff number Voltage transformer
Device address
Page 2 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
All rights reserved. No part of this manual may be reproduced or duplicated without the written permission of the author. Any contraventions are punishable and will be prosecuted with all legal means.
No liability can be taken for the faultless condition of the manual or damage caused by the use of it. As failures cannot be avoided completely, we shall be very grateful for any advice. We will try to remove any failures as soon as possible. The mentioned software and hardware descriptions are registered trademarks in the most cases and are subjected to the regulations by law. All registered trademarks are property of the corresponding companies and are fully recognized by us.
Page 3= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Page 4 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Table of contents
Meaning of the symbols 6
Generals 7
Receipt control 7 Hints for usage 7 Hints for maintenance 8
Repairing and calibration 8 Face plate 8 Battery 8 Waste management 8
Service 8
Product description 9
Intended use 9 Functional description 9
Putting into service 10
Auxiliary voltage 10 Measuring voltage 10 Testing current 10 RS485 Interface cable 10
Putting into service 14
Removal of errors 15
Usage 17
Keys 17
Edit 17 Special functions 17
Main menu 17
Measured value indication 18
Retrievable meas. and calculated quantities 18
Calling up additional information 22 Mean values 22 Minimum and maximum values 23 Energy determination 24 Real power EMAX 25 EMAX- monthly- peak values 25 Reset of the measuring period 26 Current meas. without measuring voltage 27
Harmonics 27
Total harmonic distortion factor THD(f) 27 Partial harmonics 27
Programming 28
Delete real and reactive energy 28
Delete via keyboard 28 Delete via serial interface 28
Delete highest and lowest values 29
Delete all minimum and max. values 29 Delete min. and max. values separately 30
Ring buffer 31
Select mean values 31 Averaging time 32 Duration of the measurement period 32 Memory 32 Period of storage 33 Ring buffer data format 34
Configuration 36
Configuration data 37 Konfigurationsdaten 38 Current transformer 39 Voltage transformer 39 RS485 interface (Option) 40
Transmission protocol RS485 40 Terminal resistance 40
RS232 interface (Option) 40
Transmission protocols RS232 40 Modem 40
Device address 41 Data recording 42 Limits 43
Internal relay outputs (Option) 43 External relay outputs 43 Assign limits 44 Example: Sum real power 44 Example: Real power EMAX 44 Example: Real power, sequence chart 44
Three wire measurement (Option) 45 Net frequency 46 Measured value rotation 47
Program changing times 47 Program measured value selection 48
Analogue output 49
Internal analogue output (Option) 49 External analogue outputs 51 Transmission protocol 51
Pulse output (Option) 54
Assign energy 54 Set pulse valency 55
Event memory 56
Table 3a 56
Internal auxiliary input (Option) 57
Table 3b 57 Reset of real power EMAX 57 Tariff change over 57 Synchronization of the internal clock 57 Programming 58
Tariff change over 59
External tariff change over (option) 59 Internal tariff changeover 60 Programming 60
Clock 61
Summer-/Wintertime changeover 61
Software Release 62 Serial number 62 LCD contrast 62 Password 63
Clearance password 63 User password 64 Master password 64
Page 5= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Transmission protocols 65
Service protocol 65 Modem 65 Modbus RTU 66
Transmission mode 66 Transmission parameters 66 Realized functions 66 Data formats 66
PROFIBUS DP (Option) 67
Configuration of UMG 503 67 Profibus DP V0 68 Profibus DP M1 68 Higher protocol 68 Create a GSD file 72 To bind in a GSD file 72 GSD file 72
Serial interfaces 73
UMG503 - RS485/RS232 - PC 73 UMG503 - Modem - PC 73 UMG503 - RS232- PC 73 UMG503 - RS485 - PLC 73 UMG503 - RS485 - WAGO I/O 73
Tables 74
Overview 74 Data formats 74
Table 1a 75 Table 1b 76 Table 2 77 Table 3a 78 Table 3b 79 Table 4 80 Table 5 80 Table 6a 81 Table 6b 81 Table 6c 82 Table 6d 82 Table 7 83 Table 8 84 Table 9 85 Table 10 86
PSWbasic 88
Required hard and software 88
Software 88 Hardware 88
Functions 88
Configure measured value indications 88 Memory 88 Configuration of UMG 503 89 Create GSD file 89
WAGO I/O SYSTEM 90
Installation instructions 90 Function clamps 90 Bus coupling 91
Indicating range and accuracy 92
Technical Data 93
Design for panel mounting 94
Back side 94
Design for DIN Rail Mounting (Option) 94
Back side 94 Side view 94 Side view 94
Connection example 95
Brief instructions 96
Current transformer 96 Votage transformer 96
Page 6 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Issue note
04.11.1998 First edition.
26.11.1998 Completions.
09.12.1998 Page 22 „password=3846“, page 31 „Gvarh“, page 35 „housing depth“
03.03.1999 Completions.
26.03.1999 Connection diagram.
03.05.1999 cos(phi), event memory.
30.09.1999 Expansion of functions.
02.02.2000 Higher protocol for PROFIBUS.
22.02.2000 Indication of outer conductor voltage.
29.02.2000 Reset of measuring period.
08.02.2000 Delete work via serial interface.
08.06.2000 Profibus DP V1.
15.01.2001 Summer and winter time changeover.
25.01.2001 Measured value rotation, data logging.
08.07.2002 IT-Netz, Profibus 500kbps, tables.
31.07.2002 Ringbuffer uncompressed by choice. Read limit outputs via Profibus.
22.10.2003 Additions.
11.08.2004 Page 70/71, table/address.
Warning of dangerous electrical voltage.
This symbol is supposed to warn you about possible dangers, which can occur during mounting, putting into service and usage.
Protective wire connection
Meaning of the symbols
Page 7= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Generals
Receipt control
In order to ensure a perfect and safe use of the device, a proper transport, expert storage, erection and mounting and careful usage and maintenance are required. When it may be supposed, that a safe operation is no longer possible, the device has to be put out of service and be protected against unintentional putting into service. A safe operation can no longer be assumed, when the device
• shows visible damage,
• does not work in spite of intact net supply,
• has been exposed to disadvantageous conditions for a longer time (e.g. storage out of the allowed climate without adaption to the room climate, dew etc.) or transport use (e.g. falling from great height, even without visible damage).
Please test the contents of delivery for completion, before starting the installation of the device. All delivered options are listed on the delivery papers.
Attention!
All plugs, which belong to the contents of delivery, are plugged on the device! The 9pole D-Sub plug for RS232 interface does not belong to the contents of delivery.
The operating instructions also describe those options, which are not delivered and therefore do not belong to the contents of delivery!
Hints for usage
This device may be put into service and used by qualified personnel according to the safety regulations and instructions only. Please mind the additional legal and safety regulations for the respective application. Qualified personnel are persons, familiar with erection, mounting, putting into service and usage of the product and having the qualifications such as:
• education or instruction / entitlement to switch, release, ground or characterize current circuits and devices according to the standards of safety techniques.
• education or instruction in the care and usage of suitable safety equipment according to the standards of safety techniques.
Page 8 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Hints for maintenance
Before delivery the device is tested in various safety checks and marked with a seal. If the device is opened, these checks must be repeated. There is no guarantee for devices, which are opened out of the manufacturing works.
Repairing and calibration
Repairing and calibration work can be carried out in the company of manufacture only.
Face plate
The cleaning of the front foil must be done with a soft cloth using a common cleansing agent. Acid or acidic agents may not be used for cleaning.
Battery
The life expectance of the battery is 5 years minimum for a storage temperature of +45°C. The typical life expectance of the battery is about 8 to 10 years. The battery is plumbed and should be exchanged in the ma­nufacturing works only.
Waste management
The UMG 503 can be disposed as electronical waste according to the legal regulations and recycled. Please note, that the input Lithium battery must be disposed separately.
Service
If you have problems, which are not described in this manual, please ask our technical support. For further handling of your questions, please have the following at hand:
- Device description (see type plate),
- Serial number (see type plate),
- Software Release,
- Measurement and auxiliary voltage and
- Exact description of the problem.
You can contact us: Monday to Thursday between 07:00 and 15:00
and Friday between 07:00 and 12:00
Janitza electronics GmbH Vor dem Polstück 1 D-35633 Lahnau Support: Tel. (0 64 41) 9642-22
Fax (0 64 41) 9642-30 e-mail: info@janitza.de
Page 9= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Product description
Intended use
The UMG 503 is suited for fix mounting and the measu­rement of voltage, current, harmonics (2nd to 20th), power etc. in low and medium voltage switchgear. For the operation of the UMG 503 a protective wire is required. The measurement is laid out for one phase and three phase systems with or without neutral conductor (three wire measurement). If the measurement should be carried out via two voltage transformers only, the option "three wire measurement" is required. Alternating voltages (50Hz/60Hz) up to 500VAC against ground and 870VAC between the outer conductors can be connected directly. The voltage measurement inputs are not separated galvanicly and must be connected to the UMG 503 via external prefuses M2A. The current measurement is carried out via a ../5A or ../ 1A current transformer. In networks with a voltage up to 150 VAC against ground currents up to 6 A can be connected to the UMG 503 directly and measured as well. The connection of the auxiliary voltage, the measure­ment inputs etc. are on the rear side via all-insulated plug connectors. The auxiliary voltage must be connected to the building installation via a separation (switch or power switch) and a 10 A overload protection.
Attention!
Measurement in systems with pulse load is not possible, because no continuous scanning of the measuring signals is carried out.
Functional description
The electronical three phase measurement system determines and digitalizes the effective values of voltages and currents in 50/60 Hz networks. Two random test measurements are carried out each second on all current and voltage measuring inputs. Signal interruptions, which are longer than 500ms are surely recognized. For each random test two periods are scanned. From those sampled values the microprocessor calculates the electrical magnitudes. These measured values are indicated within the programmable display. Highest values, lowest values and programming data can be saved in a battery buffered storage. Selected measu­red values will be saved with date and time in a ring buffer.
Diagr. Equivalent circuit diagram for voltage measurement
2 M
2 M
2 M
L1
L2
L3
PEN
Page 10 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Putting into service
Auxiliary voltage
The input of the auxiliary voltage (terminals 14, 15) of the UMG 503 is suitable for rated voltages up to 300VAC against ground (PE). Higher voltages between auxiliary voltage and ground can damage the UMG 503. To avoid overvoltage, auxiliary voltage should be earthed.
Please also note the following:
- The wiring for the auxiliary voltage must be suited for
operating voltage up to 300VAC against ground.
- The auxiliary voltage must be protected with a fuse,
which should be in the range of 2...10A.
- A switch or power breaker must be provided for the
auxiliary voltage within the installation.
- The switch must be installed near the device and must
have an easy access for the user.
- The switch must be marked as a breaker for this device.
- Please ensure, that voltage and frequency match the
type plate before connecting it to the auxiliary voltage!
- The device may be operated with earthed housing only!
- Conductors with single solded wires are not suited for
connection to screw clamps!
- The screw clamps may only be connected in dead
condition.
Measuring voltage
The wires for the measuring voltage must be suitable for up to 500VAC against ground and 870VAC phase to phase.
Attention! For the connection examples 5 and 6, the option "three wire measurement" is required. In mains without neu-
tral conductor, voltage transformes must be connected according to the respective connection example.
Testing current
Current transformers of .../5A or .../1A can be connected directly to the current inputs of the UMG 503.
Attention!
Current transformers can lead voltage, which can be live and should be earthed.
RS485 Interface cable
Bus structure All devices are connected in bus structure (line). In one segment up to 32 participants can be connected. At the beginning and the end of one segment, the cable is terminated with resistors. Within the UMG 503, these resistors can be activated with two plug bridges. For more than 32 participants, you must use a repeater (line amplifier) to connect the single segments.
Protection For the connection via RS485 interface, you must use a twisted pair and protected cable. To achieve a sufficient protection result, the protection must be connected to housing or cabinet parts at both ends of cable with large surface.
Baudrate (kbit/s)
Cable type 9.6 19.2 93.75 187.5 500 1500
Type A 1200 1200 1200 1000 400 200 Type B 1200 1200 1200 600 200 70
Cable length The following table shows the maximum cable length in meter (m) for different baudrates.
Cable specification: The maximum length depends on cable type and baud­rate. We recommend type A
Cable parameters Type A Type B
Impedance 135-165Ohm 100-130Ohm
(f = 3-20MHz) (f > 100kHz) Capacity < 30pF/m < 60pF/m Resistance < 110 Ohm/km ­Diameter >= 0,34mm2 >= 0,22mm2
(AWG22) (AWG24)
Page 11= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Connection example 2 Four wire measurement with three current transformers
Connection example 2a Four wire measurement with three current transformers
Connection example 3aConnection example 3
Four wire measurement with two current transformers
Page 12 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Connection example 5 Three wire measurement with three voltage transformers and three current transformers
Connection example 7 Three wire measurement with three voltage transformers and two current transformers
Connection example 8 Three wire measurement with two voltage transformers and two current transformers. (Option "Three wire measurement" required)
Connection example 6 Three wire measurement with two voltage transformers and three current transformers. (Option "three wire measurement" required)
Page 13= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Connection example 9 Measurement in IT-mains with N.
L/L 80 .. 870V AC
L/PEN 50 .. 500V AC 0,005 .. 5A
27 26 25 24 23 22 21 20 191814 15
L1 L2 L3 N
2A
L1 N
Messung
Mesurement
Hilfs-
spannung
Auxiliary
Voltage
UMG503
L1 L2
L3 N
k l
k l
k l
../5(1)A
../5(1)A
../5(1)A
230V/400V 50Hz
10160990
Verbraucher
Consumer
4-
10A
PE
Connection example 10 Measurement in IT-mains without N.
L/L 80 .. 870V AC
L/PEN 50 .. 500V AC 0,005 .. 5A
27 26 25 24 23 22 21 20 191814 15
L1 L2 L3 N
2A
L1 N
Messung
Mesurement
Hilfs-
spannung
Auxiliary
Voltage
UMG503
L1 L2
L3
k l
k l
k l
../5(1)A
../5(1)A
../5(1)A
230V/400V 50Hz
101609100
Verbraucher
Consumer
4-
10A
PE
Page 14 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Putting into service
The device should be put into service as follows:
- Install the device.
- Connect auxiliary voltage Uh. The size of the auxiliary voltage to be connected must be
according to the details on type plate. The input of the auxiliary voltage (terminal 14,
15) of UMG503 is suitable for rated voltage up
to 300VAC against ground (PE). Higher voltage between auxiliary voltage (terminal 14, 15) and ground (PE) can damage the UMG503. To avoid overvoltage at auxiliary voltage input, the auxiliary voltage should be earthed. The wiring for the auxiliary voltage must be suited for operating voltage up to 300VAC against ground.
- program current and voltage transformer.
Attention!
• A switch or power breaker must be provided for the auxiliary voltage within the installation.
• The switch must be installed near the device and must have an easy access for the user.
• The switch must be marked as a breaker for this device.
• Please ensure, that voltage and frequency match the type plate before connecting it to the auxiliary voltage!
• The device may be operated with earthed housing only!
• Conductors with single solded wires are not suited for connection to screw clamps!
• The screw clamps may only be connected in dead condition.
Connection example 1 Four wire measurement with three current transformers
- Connect measurement current (max. 6A). Check measurement current indication. Short-circuit current transformer and check, whether the measurement current indication is zero Ampere.
Attention!
None earthed current transformer clamps are
dangerous to be touched.
Current transformers, which are not loaded
secondarily, can lead live voltage and should be
short circuited.
- Check phase assignment. The assignment of outer conductor and current transformer is correct, if no voltage occurs between outer conductor and the respective current transformer (primary).
- Connect interface (RS485 2-wire). Please use an interface converter (RS485/RS232), when you connect it to the COM-interface of a PC.
- Connect measurement current (max. 500VAC against ground) and check measuring voltage indication.
Attention!
The wiring for the measurement voltage must
be suitable for a voltage up to 500VAC against
ground and 870VAC phase to phase.
Attention!
For connection examples 6 and 8 the option
"three wire measurement" is required. In
networks without neutral conductor, voltage
transformers are required and must be connected
according to the respective diagram.
Page 15= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Removal of errors
Faults Possible reason Remedy
Indication dark External prefuse has released. Replace prefuse.
Internal prefuse has released. The fuse cannot be changed by the user. Please send
the device back to the manufacturing works Contrast setting too dark. Change contrast settings in configuration menu. Device faulty. Please send the device to the manufacturer for repair.
No current indication Measurement voltage not Connect measurement voltage.
connected
Current too small Current measurement in the Check and correct connection.
wrong phase. Current transformer factor Read current transformer ratio on current transformer programmed incorrectly. and program correctly.
Wrong current Current measurement in the Check and correct connection.
wrong phase. Current transformer factor Read current transformer ratio on current transformer programmed incorrectly. and program correctly. Measuring range exceeded. Install bigger current transformer. The peak current value on Install bigger current transformer. measuring input was exceeded caused by harmonics. Attention: Please ensure, that the measuring
inputs are not overloaded. The current on measuring Install smaller current transformer. input was underscored.
Voltage L-N too small Measurement in wrong phase. Check and correct connection.
Voltage transformer factor Read current transformer ratio on current programmed incorrectly. transformer and program correctly.
If the voltage is not measured via voltage transformer
please program a voltage transformer ratio of
400/400. Voltage on measuring input Install smaller voltage transformer. out of measuring range.
Voltage L-N incorrect Measurement in wrong phase. Check and correct connection.
Voltage transformer factor Read current transformer ratio on current programmed incorrectly. transformer and program correctly.
If the voltage is not measured via voltage transformer
please program a voltage transf. ratio of 400/400. Measured range exceeded. Install bigger current transformer. The peak voltage value on Install bigger current transformer. measuring input was exceeded caused by harmonics. Attention: Please ensure, that the measuring inputs
are not overloaded.
Voltage L-L too small/ Outer conductors exchanged. Check and correct connection. too big N not connected. Check and correct connection.
Phase shift ind /cap too Current path is assigned to Check and correct connection. small or big the wrong voltage path.
Programmed data get lost Battery empty. Please send device to the manufacturer for
exchanging the battery. The device has been exposed to External protection measure such as shielding, electromagnetical interference filtering, earthing or spatial separation. bigger than the allowed by technical data.
Page 16 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Faults Possible reason Remedy
Real power too small / Current transformer factor Read current transformer ratio on current transformer too big programmed incorrectly. and program correctly.
Current path is assigned Check and correct connection. to the wrong voltage path. Current on measuring input Install bigger or smaller current transformer. out of measuring range.
Attention: Please ensure, that the measuring
inputs are not overloaded. Voltage transformer factor Read current transformer ratio on current programmed incorrectly. transformer and program correctly.
If the voltage is not measured via voltage transformer
please program a voltage transformer ratio of
400/400. Current on measuring input Install bigger or smaller current transformer. out of measuring range.
Attention: Please ensure, that the measuring
inputs are not overloaded.
Real power consumption / One current transformer at Check and correct connection. supply exchanged. least exchanged.
Current path is assigned to Check and correct connection. the wrong voltage path.
The time is indicated The device has no automatical Correct time by hand. incorrectly. summer-/winter change over.
"EEEE" in the display. The measuring range of Check measuring current and insert a suitable current
current was exceeded. transformer. The measuring range of Check measuring voltage and insert a suitable voltage voltage was exceeded. transformer.
Duration of memory =38 s. Not enough memory for all Select more equal averaging times for the measured
selected values. values.
Relay output, analogue The outputs are not programmed Program the outputs. output or pulse output do not react. The service protocol 04 is set Select another protocol.
The device does not work Device out of order. Please send the device to the manufacturer with correctly in spite of the an exact description of the failure. above
Page 17= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Usage
Keys
The UMG503 is operated using the three keys within the front plate.
= Key 1 = Key 2 = Key 3
In the different indications these keys have various mea­nings.
Edit
In configuration menu CONF and in programming menu PRG the settings in edit mode EDIT can be changed. In edit mode EDIT the keys have the following meaning:
Key 1 Select cipher/number or leave edit mode. Key 3 Change ciphers. Key 2 Multiply the number with factor 10.
Main menu
After a net return the device always starts with the first
programmed measured value indication. With key 1 you
change over between
the measured value indication, the SELECT mode, the configuration menu CONF and the programming menu PROG
Special functions
Press and hold key 1 for about 2 seconds to return to the first measured value window of the measured value indi­cation from each program part. Hold key 2 or key 3 for about 2 seconds to return to the previous measured value window.
Example: Delete all
highest and lowest va-
lues
Programming menu PRG
Example: Ratio current
transformer
Configuration menu CONF
SELECT Mode
Indication of date and
time information.
Year=98 Month=10
Day=25 Hour=08
Minute=10 Second=31
Example: Voltages L1-
N, L2-N, L3-N.
Measured value display
SELECT
PRG
V
V
V
L3
L1
L2
Y.M
D.H
M.S
SELECT
A
A
SELECT CT
CONF
Page 18 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Retrievable meas. and calculated quantities
Measured value Mean value Measured value Date and time
Measured quantity L1 L2 L3 Sum L1 L2 L3 Sum Peak value Lowest val.
Voltage L-N, L-L x x x x x x x x x Current x x x x1) x x x x
1
x x
2)
x Real power x x x x x x x x x x x Real power, 15min. mean value x x x x Apparent power x x x x x x x x x x x Reactive power x x x x x x x x ind cap x cos(phi) x x x x x x x x ind cap x Frequency of voltage x x x x x x x x x x Real work without reverse running stop x Start./run. time Consumption x Start./run. time Supply x Start./run. time Reactive work without reverse running stop x Start./run. time inductive x Start./run. time capacitive x Start./run. time Partial harm. content HDF, I/U x x x x x x x x x Total harmonic content THD, I/U x x x x x x x x x
1) Current in Neutral
2) Maximum value for current measurement and current mean value
Measured value indication
The display of UMG503 can indicate up to three measu­red values simultaneously.
V
V
V
L3
L1
L2
Example: Voltages L1­N, L2-N, L3-N
With the keys 2 and 3 one can scroll through those measured value indications.
Using key 3 you scroll to the next measured value indication. Example: Current in phase L1, L2 and L3
A
A
A
L3
L1
L2
To keep the selection of the indicated measured values clear, only a certain part of all possible measured values is programmed for the display in delivery condition. In the table "Retrievable measured and calculated quantities" all measured values, which can be called up, are listed. On the pages 32 to 33 the manufacturer's settings of the retrievable values are listed. If other measured values should be indicated on the display of UMG503, they can be selected in the software PSW basic, which belongs to the contents of delivery, and transmitted via serial interface to the UMG 503.
After a net return the device always starts with the first programmed measured value indication.
Page 19= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Min. value voltage L1-L2
Min. value voltage L2-L3
Min. value voltage L3-L1
Max. value voltage L1-L2
Max. value voltage L2-L3
Max. value voltage L3-L1
Mean val. voltage L1-L2
Mean val. voltage L2-L3
Mean val. voltage L3-L1
Meas. val. voltage L1-L2
Meas. val. voltage L2-L3
Meas. val. voltage L3-L1
Min. value current L1
Min. value current L2
Min. value current L3
Max. value current L1
Max. vaue current L2
Max. value current L3
Mean value current L1
Mean value current L2
Mean value current L3
Measured value current L1
Measured value current L2
Measured value current L3
Min. value real power L1
Min. value real power L2
Min. value real power L3
Max. value real power L1
Max. value real power L2
Max. value real power L3
Mean value real power L1
Mean value real power L2
Mean value real power L3
Meas. val. real power L1
Meas. val. real power L2
Meas. val. real power L3
Mean value app. power L1
Mean value app. power L2
Mean value app. power L3
Meas. val. app. power L1
Meas. val. app. power L2
Meas. val. app. power L3
Max. value app. power L1
Max. value app. power L2
Max. value app. power L3
Min. value app. power L1
Min. value app. power L2
Min. value app. power L3
Measured value display (Manufacturer's settings)
Mean val. react. power L1
Mean val. react. power L2
Mean val. react. power L3
Meas. val. react. power L1
Meas. val. react. power L2
Meas. val. react. power L3
Max. val. react. power L1
Max. val. react. power L2
Max. val. react. power L3
Min. val. react. power L1
Min. val. react. power L2
Min. val. react. power L3
Min. value voltage L1-N
Min. value voltage L2-N
Min. value voltage L3-N
Max. value voltage L1-N
Max. value voltage L2-N
Max. value voltage L3-N
Mean value voltage L1-N
Mean value voltage L2-N
Mean value voltage L3-N
Meas. val. voltage L1-N
Meas. val. voltage L2-N
Meas. val. voltage L3-N
Page 20 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Delivered real energy
Cons. real energy tariff 02
Cons. real energy tariff 01Cons. real energy tariff 00
Cap. react. energy tariff 20 Cap. react. energy tariff 22Cap. react. energy tariff 21
Ind. react. energy tariff 10 Ind. react. energy tariff 11
Ind. react. energy tariff 12
Mean value frequency L1
Mean value frequency L2
Mean value frequency L3
Meas. value frequency L1
Meas. value frequency L2
Meas. value frequency L3
Max. value frequency L1
Max. value frequency L2
Max. value frequency L3
Min. value frequency L1
Min. value frequency L2
Min. value frequency L3
Mean value cos(phi) L1
Mean value cos(phi) L2
Mean value cos(phi) L3
Meas. value cos(phi) L1
Meas. value cos(phi) L2
Meas. value cos(phi) L3
Max. value cos(phi) L1
Max. value cos(phi) L2
Max. value cos(phi) L3
Min. value cos(phi) L1
Min. value cos(phi) L2
Min. value cos(phi) L3
Page 21= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Meas. val. sum real power
Meas. val. sum react. power
Meas. val. sum cos(phi)
Mean val. sum real power
Mean val. sum react. power
Mean value sum cos(phi)
Min. value sum real power
Min. val. sum react. power
Min. value sum cos(phi)
Max. value sum real power
Max. value sum react. power
Max. value sum cos(phi)
Measured value current in N
Mean value current in N
Max. value current in N
Meas. val. sum power 15min Min. val. sum power 15 Max. val. sum power 15
Date / time Serial number Software Release
Mean value harmonic I L1
Mean value harmonic I L2
Mean value harmonic I L3
Max. value harmonic I L1
Max. value harmonic I L2
Max. value harmonic I L3
Mean value harmonic U L1
Mean value harmonic. U L2
Mean value harmonic. U L3
Max. value harmonic U L1
Max. value harmonic U L2
Max. value harmonic U L3
Page 22 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Calling up additional information
Additional information can be called up for the most indicated measured values:
Date and time for the highest and lowest values. Averaging times for the mean values. Duration of energy determination.
Using key 3 you scroll to the measured value indication of the real power.
Mean values
For each measured value, except work, a mean value is calculated. The averaging time is programmable. Only mean values can be marked for storage within the ring buffer. The calling up - in the example for the power maximum value in phase L3 - is carried out as follows:
Press key 1 for about 2 seconds and return to the first measured value window of the measured value indicati­on from each program part.
Pressing key 2 you scroll to the mean va- lues of real power.
kW
kW
kW
L3
L1
L2
Select the SELECT mode using key 1. The symbol SELECT is flashing.
Confirm with key 2. The symbol SELECT is on.
kW
L3
SELECT
kW
kW
kW
L3
L1
L2
kW
L1
SELECT
Select the mean value of the real power in L3 using key 1.
Call up the averaging time for the real power in phase L3 as an addi­tional information using key 2.
kW
M.S
L3
SELECT
Averaging time = 15 Minutes
Page 23= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Scroll to the display of current using key 3.
A
A
A
L3
L1
L2
Scroll to the maximum values of current using key 2.
Select mode with key
1. The symbol SELECT is flashing.
Confirm with key 2. The symbol SELECT is on.
With key 2 call up addi- tional information about date and time for the selected maximum value.
A
L3
L1
L2
A
A
Y.M
D.H
M.S
SELECT
Year=98 Month=10 Day=25 Hour=08
Minute=10 Second=31
A
L1
SELECT
Select maximum current value in L2 with key 1.
Minimum and maximum values
For each minimum and maximum value, the first time of existance is saved with date and time. To call up, for example, the maximum current value in L2, please proceed like mentioned on the right.
Keeping key 1 pressed for about 2 seconds, you return to the first measured value display from all programm parts.
L2
A
SELECT
Attention!
After return of the auxiliary voltage, all mini­mum values are deleted.
Page 24 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Energy determination
Starting time and running time are saved for the follo­wing real and reactive energy:
Real energy without reverse running stop Real energy supply Real energy consumption (T00) Reactive energy without reverse running stop Reactive energy ind., (T10)
Reactive energy cap., (T20) Starting and running time for energy meters, controlled by internal or external tariff changeovers, are not saved.
Move to the measured value indication of reactive energy using
key 3.
M VArh
kVArh
VArh
L1 L2 L3 ind
SELECT
T
Go to select mode using key 1. The symbol SELECT is flashing. Confirm with key 2. The symbol SELECT is on.
M VArh
kVArh
VArh
L1 L2 L3 ind
T
Call up the additional information starting time for reactive energy measurement using key
2.
Confirm again with key
2. The running time for reactive energy measu­rement is indicated.
Year=99 Month=09 Day=06 Hour=08 Minute=15 Seconds=41
SELECT
Y.M
D.H
M.S
SELECT
Y.M
D.H
M.S
Days=02 Hours=04 Minutes=15 Seconds=41
The interrogation, for reactive energy ind (T10) for instance, can be carried out as follows:
Press key 1 for about 2 seconds and you return to the first measured value window of the measured value indicati­on from each program part.
Page 25= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Real power EMAX
For the most measured values a mean value is build over the last passed period of time within the UMG 503 each second. This passed period of time is the programmable averaging time.
The real power is an exception. For the real power the mean value real power EMAX is build over a programmable measurement period additionally. The measuring period duration for real power EMAX can be 5, 10, 15, 30 or 60 minutes. The manufacturer's setting is 15 minutes. The real power EMAX is calculated from the work within a certain period of time divided by the passed time of the period. The calculation is done each second, in order to ensure the indication of real power EMAX within the measurement period. For the comparison and storage of the EMAX monthly peak value only the real power, measured at the end of a period, is used.
0123456 t/Sec.
Diagr.: Mean value for real power over 5 seconds.
Indication of a new mean value for the real power.
Mean value for the 5. seconds
Mean value for the 6. seconds
Mean value for the 7. seconds
The tariff changeover is not only valid for real and reactive energy meters but also for real power EMAX.
EMAX- monthly- peak values
All EMAX-monthly-peak values are saved for all tariffs each month. The old EMAX-monthly-peak values are overwritten at the beginning of a new year. If the real power EMAX is configurated for the display software PSWbasic, real power EMAX can be indicated in the display of the UMG 503 as well. The EMAX- monthly- peak values can be read out directly at the UMG503 and via the serial interface, with the software PSWbasic, for instance.
Diagr.: Calculation of mean value for real power EMAX over a measurement period of 15 minutes.
0 5 10 15 20 25 t/Min.
1.Measurement period 2.Measurement period
End of measurement period
Tariff
Month
Day . Hour Minute
W
D.H
M.
L1 L2 L3
Real power EMAX
Peak value
Energy meter Programmable via Time programs 1-4
Aux. input Energy work cons. T00 T01 T02 T03 T04 Reactive energy ind. T10 T11 T12 T13 T14 Reactive energy cap. T20 T21 T22 T23 T24 Real power EMAX 00 01 02 03 04
Attention!
The real power EMAX is not indicated in the standard indications.
Attention!
Real power EMAX is calculated from energy without reverse running stop.
Page 26 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
With key 3 you scroll to the indication of real power EMAX.
Real power EMAX (Example 100W). Rest time of period (Example. 8Min. 10Seconds). Measuring period (Example 15Minutes).
Reset of the measuring period
The reset of the measuring period deletes real power EMAX and starts a new period. If no external reset is carried out within the programmed period, the reset is carried out by the internal clock. If there are less than 30 seconds between two resets, the measuring period is reset and real power EMAX is deleted. The obsolete measured value is not saved in the maxi­mum and minimum memory and not be deposited within the event memory, if programmed.
The measuring period for real power EMAX can be reset by the following means:
- automatically, after measuring period,
- internally, via keyboard,
- internally, via auxiliary input (Option),
- externally, via connected WAGO- Modules,
- externally, via PROFIBUS DP Protocol,
- externally, via MODBUS Protocol. (Table 5)
Pressing key 1 for about 2 seconds, real work will be deleted and you return to the first programmed measured value window of the measured value indication!
W
M.S
L1 L2 L3
With key1 go to Select- Mode. The symbol SELECT flashes. Confirm with key 2 . The symbol SELECT is visible.
Press Key2 again. The rest time is deleted.
W
M.S
L1 L2 L3
SELECT
W
M.S
L1 L2 L3
The symbol SELECT disappears. The period for real po­wer EMAX is started again.
Reset of the measuring period by keyboard
Page 27= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Harmonics
Harmonics are the integer multiples of the fundamental. The UMG503 measures the fundamental of voltage in the range of 45 to 65 Hz. The calculated harmonics of voltage and current apply to this fundamental. For too distorted voltages, the fundamental cannot be detected accurate enough. Nevertheless it is possible to calculate the harmonics by selecting a stable fundamental of 50Hz or 60Hz. See also chapter "Net frequency". The UMG503 calculates up to the 20th harmonic.
Total harmonic distortion factor THD(f)
The calculated total harmonic distortion factor THD(f) is the effective ratio of the harmonics compared to the fundamental. The total harmonic distortion is given in %. As the total harmonic distortion corresponds to the fun­damental but not to the total value, it can exceed 100%.
THD(f) = Total Harmonic Distortion (fundamental)
Partial harmonics
In further descriptions, the single harmonics are described as partial harmonics. The partial harmonics of current are given in Ampere and the partial harmonics of voltage are given in Volt.
Current meas. without measuring voltage
The net frequency is detected from the measuring voltage within the UMG 503. From the net frequency, the scan­ning frequency for current and voltage inputs is calculated. If the measuring voltage is missing, net frequency and scanning frequency cannot be detected. Voltage, current and all resulting values cannot be calculated and are indicated with zero. If current should be measured without measuring voltage, the net frequency must be selected as a stable frequency at UMG 503. As stable frequency, 50Hz and 60Hz are available.
Page 28 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Programming
The following settings can be carried out in the menu
PRG:
Delete real and reactive energy, Delete all highest and lowest values "dEL" Select measured values for the ring buffer , Select averaging time for the measured values, Delete single highest and lowest values, Read out duration of storage of the ring buffer.
To reach the menu PRG, for example from the indicati­on of voltage, please proceed like this:
SELECT
PRG
V
V
V
L3
L1
L2
SELECTConfirm with key 1.
In the measured value indication the text SE- LECT appears flashing.
Confirm key 1 again. Now you are in the menu CONF.
A
A
SELECT CT
CONF
Confirm key 1 again. Now you are in the menu PRG.
Confirm the selection of the menu PRG using key 2. The text SELECT dis­appears from the dis­play.
PRG
Delete real and reactive energy
Real and reactive energy can be deleted separately via keyboard or serial interface. Starting time and running time will be actualized. If real energy is deleted, all corresponding tariffs are reset. If reactive energy is deleted, the meters for inductive and capacitive energy are reset.
Delete via keyboard
Please go to menu PRG (See chapter programming).
Confirm the selection of the menu PRG using
key 2. The text SE­LECT disappears.
PRG
Pressing key 2 again, the delete menu for
real and reactive energy appears.
The arrows for mini­mum and maximum values disappear.
Select the work to be deleted by pressing key 1, for example real energy. The text EDIT appears and "ALL" flashes. Confirming with key 3, a "0" flashes in the in­dication.
Pressing key for about 2 seconds, real work will be deleted and you return to the first programmed measured value window of the measured value indication!
Wh
VArh
PRG
PRGEDIT
Wh
VArh
Delete via serial interface
In address 5000 a 17Byte large control word is deposited. A part of this control word is used for deletion of energy:
Byte 7 > 0, delete real energy
and
Byte 8 > 0, delete reactive energy.
In order to overwrite a Byte, first
read control word, overwrite Byte7/8 with e.g. 1
and rewrite the changed control word to address 5000.
Attention! Changing the control Byte incorrectly can lead to malfunctions of the UMG 503.
Page 29= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
PRG
EDIT
If you want to delete all maximum values with key 1, the indication "ALL" flashes.
Text flashing
Maximum value
Minimum value
SELECT
PRG
Delete highest and lowest values
Highest values are marked with an arrow upwards, the lowest with an arrow downwards.
Select menu PRG (see chapter programming). Using key 2 you con- firm the selection of menu PRG and the text SELECT disappears.
There are two possibilities of deleting the highest and lowest values:
- Delete all minimum and maximum values,
- Delete min. and maximum values separately.
The monthly peak values of the real power EMAX belong to the maximum values and are deleted together with them.
Using key 3, a "0" ap­pears within the indi­cation and all highest values are marked for deletion. Pressing key 1 again, you change to the indi­cation of minimum va­lues. Now the minimum values could be marked for deletion.
PRGEDIT
Pressing key for about 2 seconds, the highest value is deleted and you return to the first measured value window of the measured value indication!
Using key 2 you con- firm the selection of menu PRG and the text SELECT disappears.
PRG
Delete all minimum and max. values
Attention!
After return of auxiliary voltage, all minimum values are deleted.
Page 30 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Delete min. and max. values separately
If you are in the menu PRG and you would like to delete the highest voltage values only, please proceed as follows:
V
V
L3
L1
L2
V
PRG
V
L2
PRG
EDIT
V
L1
PRGEDIT
Pressing key 1, the highest value in phase L1 is indicated. The text EDIT appears.
Now scroll to the highest values of voltage using key 2.
Pressing key 1 again, the highest value in phase L2 is indicated. If this highest value should be deleted, ple­ase press key 3. The indicated value is set to 000.0 for a short duration and is over­written by the next measured value.
Pressing the key for about 2 seconds, you leave the PRG menu and return to the first measured value window of the measured value indication!
Change to the measu­red value indication using key 3. In this example the program­ming of the current in the three phases is shown. All three currents are programmed for the ring buffer.
Now scroll to the measured value indica­tion of the voltages by using key 3.
A
A
A
L3
L1
L2
PRG
V
V
V
L3
L1
L2
PRG
Averaging time =15 Minutes
Page 31= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Ring buffer
For the most measured values a mean value is calculated (please see table "Measured and calculated values"). These mean values can be selected for storage in the ring buffer. The mean values are marked with a horizontal bar on top of the measured value. The mean values, selected for storage in the ring buffer, can be called up in the menu PRG and are marked by the flashing of both of the arrow symbols. Additionally, the following energies can be selected for storage in the memory:
Real energy, Real energy consumption, Real energy supply, Reactive energy, Reactive energy inductive,
Reactive energy capacitive. Those energies with the various tariffs cannot be selected for storage in the ring buffer. For energies, the period between two savings is set to one hour.
The more mean values are selected for storage in the ring buffer, the earlier the ring buffer is complete and will be overwritten. The period of storage for the ring buffer can be read out in the measured value indication. The stored measured values can be read out of the ring buffer using the "programming- and reading out software PSWbasic" only.
Press key 3 to scroll to the mean value indica­tion of voltage.
Select mean values
If you are in menu PRG and would like to save the mean value of voltage L2 within the ring buffer, please proceed as follows:
Change over to mean value indication using key 3. In this example the programming of current in the three phases is indicated.
A
A
A
L3
L1
L2
PRG
With key 3 you select the voltage in phase L2.
V
V
V
L3
L1
L2
PRG
Switch on or off the arrow symbols using key 2.
If the arrow symbols are switched on, this mean value is stored every 15 minutes in the ring buf­fer.
V
L2
PRGEDIT
V
L2
PRGEDIT
Confirm selection of the menu PRG using key 2, the text SELECT dis- appears.
PRG
Averaging time=15Minutes..
All three currents are pro­grammed for storage in the ring buffer.
Voltage L2 is not pro­grammed for storage in the ring buffer.
Attention!
If the averaging time, the current transformer ratio, voltage transformer ratio, three wire or four wire measurement or the selection of the measured values stored in the ring buffer are changed, the contents of the ring buffer are deleted completely.
Page 32 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Averaging time
An averaging time can be assigned to each mean value. All averaging times are programmed to 15 minutes, when the device leaves the factory.
Attention!
If the averaging time, the current transformer, the voltage transformer, the three or four wire measu­rement or the measured value selection is chan­ged, the ring buffer is deleted.
V
L2
PRGEDIT
If the averaging time, for example, for voltage L2 should be changed to 5 seconds, please proceed as follows:
Select mean value as described in chapter "select mean value".
Select averaging time of 5 seconds using key 3.
The averaging time is selectable from 5, 10, 15, 30 seconds, 1, 5, 10, 15, 30 and 60 minutes.
V
L2
PRGEDIT
Duration of the measurement period
The averaging time for real power EMAX is called measu- ring period. Within the measuring period, the real work is measured and divided by the time passed by. As the result, the real power EMAX is indicated. When the measuring period is over, the added real work is deleted. The measuring period for real power EMAX can be set to 5, 10, 15, 30 and 60 minutes. The factory presetting is a measuring period of 15 minutes.
Memory
The memory of the UMG 503 is split into three areas: The event memory, the peak and lowest value storage and the ring buffer. The event memory and ring buffer can only be read out via PC using the programs PSWbasic or PSWprofessional. The read out data are available in ASCII-format, and the ring buffer data in binary format additionally. With PSWprofessional you can create graphics from those binary data.
In the peak and lowest value storage, the peak and lowest values of the measurement values are saved with date and time. All EMAX monthly peak values are saved for each months and all tariffs. The old EMAX monthly values are overwritten at the beginning of a new year.
In the ring buffer all measurement values, marked for storage, are saved. The configuration of the ring buffer is only possible with the option "Configuration UMG503".
In the event memory the following events can be saved with date and time:
- Deleting the event memory,
- Relay output 1 on/off,
- Relay output 2 on/off,
- Breakdown and return of the auxiliary voltage,
- Breakdown and return of the measurement voltage. The breakdown of the measurement voltage will be recognized, when:
- The measurement voltage is smaller than 50% of the set primary voltage of the current transformer,
- and the breakdown lasts longer but 500ms.
Pressing key for about 2 seconds, the highest value is deleted and you return to the first measured value window of the measured value indication!
Setting range
Description Setting range
Averaging time 5, 10, 15, 30Sec.,
1, 5, 10, 15, 30, 60Min.
Ring buffer All measured values (See table
"Measured and calculated quantities")
Presettings
Desription Presettings
Averaging time All measured values 15.00 m.s. Ring buffer U1, U2, U3, I1, I2, I3, P1, P2, P3
Page 33= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Period of storage
The more mean values are marked for storage in the ring buffer, the shorter becomes the period of storage. With the factory's presettings
Mean values: U1, U2, U3, I1, I2, I3, P1, P2, P3
Averaging time: 15 minutes . The mean values of about 1 year are saved in a device with 512kRAM. In devices with 128kRAM, this duration is about 3 months. If this period is over, the most ancient mean values are overwritten. If various averaging times are assigned to the mean values to be stored, more room for storage can be required, and the period of storage can get much shorter. If only 38 seconds are indicated for the period of storage, it cannot be granted any more, that the selected values are saved in the UMG 503. To enlarge the period of storage, you can remove some measured values with large periods or increase little periods of storage.
Attention!
After the selection of the measured values to be saved, the actual period of storage must be checked! If the period of storage is below 38 seconds, it cannot be
granted, that the selected values are saved in the UMG 503.
Selecting menu PRG (see chapter program­ming), the following in­dication appears first:
Text flashing Peak values
Lowest values
SELECT
PRG
Scroll to the indication besides using key 3 . Here, for example, the period of storage is estimated at more than one year.
With key 2 the selec­tion of the menu PRG is confirmed, and the text SELECT disap­pears.
PRG
Y.M
D.H
M.S
PRG
1year, 5months, 18days, 13hours, 45minutes, 0seconds
An estimate of the period of storage can be read out in menu PRG.
Page 34 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Ring buffer data format
Data sets can be saved in compressed or uncompressed form. With the presettings, the data are saved com­pressed. The programming and reading out software PSW503basic can read compressed data from ring buf­fer only. Other applications can read data sets in uncom­pressed form only. An uncompressed data set consists of the type of measu­red value, the date and the measured value. This value is always given in Float format.
1)
r/w = read/write
2)
Measured values {float: Actual value[L1, L2, L3], Mean value[L1, L2, L3], Minimum[L1, L2, L3], Maximum[L1, L2, L3]}
Changeover ring buffer
The changeover from compressed to uncompressed storage of data is carried out via the serial interface. If the Modbus RTU protocol is used, please use the addresses. If the Profibus DP protocol is used, please use the index. If data should be saved uncompressed within the ring buffer, address 19010dez (Index 11) must be overwritten by 2 Bytes of a content by choice. If data should be saved uncompressed within the ring buffer, address 19020dez (Index 12) must be overwritten by 2 Bytes of a content by choice.
Type of measured value
The type of the measured value can be determined by the addresses from the tables 1a and 1b. Example: If the type is marked by the decimal number „1004“, this corresponds to the current mean value in phase L2.
Date
In the part of the data set with the description „Date“, the date and time of the measurement are saved.
char: Year, Month, Day, Hour, Minute, Second
Diagr. Structure of „Date“
Meas. val. type Date Meas. value 2 Bytes 6 Byte 4 Byte (float)
Read ring buffer
If the data sets have been saved uncompressed, they can be read via the serial interface with Modbus protocol. To make this reading easy, there is a ring buffer pointer (4 Byte) available. This ring buffer pointer always points to the beginning of a data set. One data set consists of 12 Bytes.
Attention!
If another way of compression is selected, the total content of the ring buffer is deleted.
Table 1a, Measured value Meas. val. in floating point form.
Description Addr.(dez) r/w1)Type
Current 1000 r Meas. val2) A L1, L2, L3
1001 r Actual value in L2 1002 r Actual value in L3 1003 r Mean value in L1
1004 r Mean value in L2
.. .. ..
Voltage N-L 1012 r Meas. val.2) V L1, L2, Voltage L-L 1024 r Meas. val.2) V L1-L2, L2-L3, Real power 1036 r Meas. val.2) W Sign -=Supply.
.. .. .. .. .. ..
Extract from table 1a
Diagr. Assign measured value type.
Type Date Meas. value 2 Bytes 6 Byte 4 Byte (float)
Ring buffer
Data set 1 Data set 2 Data set 3 . . . Data set n Data set n+1 . .
Oldest data set in ring buffer
Ring buffer pointer = 0000. Last saved data set
Next data set, that will be saved
Diagr. Data sets in ring buffer.
Attention!
The inaccuracy of the compressed memory data is max. ±0,4% rng.
Page 35= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Read data sets
The reading of data sets is controlled by the following addresses:
Read address 19000dez (Index 231). The first 4 Bytes provide the contents of the ring buffer pointer. The next 12 Bytes provide the first data set, which the pointer points on. The ring buffer pointer is increased automatically by the number of read Bytes, but the first four Bytes are not included.
Write address 19000dez (Index 10). Set ring buffer pointer on a data set of the ring buffer. If the ring buffer pointer is overwritten by 0000, it points on the last read beginning of ring buffer with address 19008dez (Index 235).
Read address 19002dez (Index 232). Read a number (4 Bytes) of data sets from that address on, on which the pointer points. The ring buffer pointer is increased automatically by the number of read Bytes. The number of read Bytes must be divisible by 12.
Read address 19004dez (Index 233). Provides that address (4 Bytes), on which the actual pointer points.
Read address 19006dez (Index 234). Read a number of data sets, from that address on, on which the pointer points. The ring buffer pointer is not increased.
Read address 19008dez (Index 235). Delivers the number (4 Bytes) of the Bytes saved in ring buffer. If you divide this number by 12, the result is the number of the saved data sets. The ring buffer pointer is set to the last data set in ring buffer. The contents of this pointer is therefore zero. Overwrite address 19010dez (Index 11) with 2 Bytes with a content by choice New data sets are written into the ring buffer uncom­pressed. If data were saved before in a compressed form, the ring buffer will be deleted. Read address 19010dez (Index 236). Delivers the storage format of the ring buffer in 2 Bytes. 00=compressed ring buffer 01=uncompressed ring buffer
Overwrite address 19020dez (Index 12) with 2 Bytes with a content by choice. New data sets are written into the ring buffer compressed. If data were saved before in a uncompressed form, the ring buffer will be deleted. Overwrite address 19030dez (Index 13) with 2 Bytes with a content by choice. The ring buffer will be deleted.
Example 1: Read the last saved data set.
Read adress 19008dez (Index 235). The ring buffer pointer (0000) is set to the last data set in ring buffer. Read 12 Bytes from address 19006dez (Index 234). 12 Bytes correspond to one data set. The ring buffer pointer is not increased.
Example 2: Read all saved data sets.
1.) Read address 19008dez (Index 235). The number of saved Bytes is read. If you divide the result by 12, the number corresponds to the saved data sets. The pointer points to the last saved data set in ring buffer.
2.) Read the content of the Bytes in ring buffer by address 19002dez (Index 232). With the MODBUS-Protocol, at maximum 240 Bytes=20 data sets can be read per reading. The number of read Bytes must be divisible by
12. The ring buffer pointer is increased automatically by the number of read Bytes and points to the next data set, which has not been read yet.
3.) Repeat reading of address 19002dez (Index 232) as long as all data sets have been read.
Attention!
If a failure appeared during data transmission, the complete procedure must be repeated, starting with step 1.
Example 3: Read all saved data sets.
1.) Read address 19008dez (Index 235). Reads the num­ber of saved Bytes in ring buffer. Divided by 12, the num­ber of saved data sets is the result. The pointer points to the last saved data set.
2.) Read address 19000dez (Index 231). The first 4 Bytes refer to the actual address of the pointer. The next 12 Bytes provide the first data set of the ring buffer. With MODBUS-Protockol you can read 244Bytes (4Byte + 20 data sets) at maximum per reading.
3.) Repeat reading address 19000dez (Index 231) as long as all data sets have been read.
Attention!
If a failure occured during data transmission, the last actual address of the ring buffer pointer must be written on address 19000dez (Index 10) and the last reading procedure must be repeated.
Page 36 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Configuration
In configuration menu CONF the required settings are noted for operating the UMG503 (see also "Table of configuration data"). When the device is delivered, these settings are not protected and can be changed. An unintended change of the settings can be avoided using a password.
The following settings can be read out and changed:
Confirm the selection of the menu CONF using key 2. The text SELECT dis­appears. Now you are in the menu CONF, and the settings of the current transformer are indica­ted.
V
V
V
L3
L1
L2
SELECT
Press key 1. The flashing text SE- LECT appears in the indication.
Press key 1 again. Now you are in the menu CONF.
A
A
SELECT CT
CONF
A
A
CT
CONF
To jump from a measured value indication, in this example the indication of voltage, to the menu CONF, please proceed as follows:
Current transformer Voltage transformer Interfaces
RS485 interface (option) RS232 interface (option) Infrared interface (option)
Device address Data recording Limit group 1 (Option) Limit group 2 (Option) Three wire measurement (Option) Scanning frequency Measured value rotation Analogue output (Option) Pulse output (Option) Event memory Auxiliary input (Option) Tariff change over, real energy consumption Tariff change over, reactive energy inductive Tariff change over, reactive energy capacitive Clock
summer-/wintertime
Software Release Serial number
LCD contrast Password
Page 37= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Configuration data
Description Indication Setting range Settings
Current transformer, primary CT 1A .. 999,9MA "5000"A Current transformer, secondary CT 1A .. 5A " 5" A Voltage transformer, primary VT 100V.. 99,99kV " 400" V Voltage transformer, secondary VT 100V .. 500V " 400" V Serial interfaces RS485, RS232, Infrared
RS485 " 485"
Baud rate
MODBUS RTU 9.6, 19.2, 38.4, 57.6
1)
, 115.2kbps
1)
"38.4"
PROFIBUS DP
3)
9.6, 19.2, 93.75, 187.5, 500, 1500kbps
Protocol oFF, 1, 2, 3, 4 , 5, 6 "2"
RS232 " 232"
Baud rate 9600bps, 19.2kbps, 38.4kbps "38.4" Protocol oFF, 1, 2, 3, 4 , 5, 6 "oFF"
Infrarot "InFr"
Baud rate 9600bps, 19.2kbps, 38.4kbps2),
57.6kbps2), 115.2kbps
2)
"19.2"
Protocol oFF, 1 "oFF"
Relay outputs
Number "S. " 1, 2 " 1" Limit All measured values "L1 0.000 A" Minimum connection time " . M.S" 1 .. 59 Seconds "00.01 M.S"
Exceeding
Underscoring Three wire measurement (Option) " nEt" 3L, 4L "4 L" Net frequency "FrE " Auto, 50Hz, 60Hz "Auto" Measured value rotation "Pic "
Changing time 0 .. 9999 seconds "0000" Display selection All displays no rotation
Analogue output "AnLo" 0/4-20mA "4 20"
Measured value All values apart from energy Sum real power Minimum value "0000" Maximum value "0000"
Pulse output "PuLS"
Measured value All reactive and real works T"00"
Pulse valency 0.000(W/var)h .. 99.99k(W/var)h "0.000 Wh" Event memory "Prot"
Devices with 128k RAM 0-2000 Events 0 events Devices with 512k RAM 0-9999 Events 1000 events
Auxiliary input "rSEt" oFF = Auxiliary input not used "oFF"
1 = external reset of the 15 minutes power mean value. 2 = External tariff change over 3 = Sychronize internal clock
1) These baud rates are not available in the version UMG503LS.
2) These baud rates are not available with any PC
3) The baud rates for PROFIBUS DP are mentioned within the GSD-file. These baud rates cannot be changed at UMG503!
Page 38 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Konfigurationsdaten
Description Indication Setting range Settings
Tariff times
Work Txx 0x = Real work, consumption "00"
1x = Reactive work, capacitive 2x = Reactive work, inductive
x = Tariff number 0 .. 4 Time number "P. 0" 0 .. 9 " 0" Week day "17.xx d.h."
Beginning 1 = Monday, .. 7 = Sunday 1 = Monday End 1 = Monday, .. 7 = Sunday 7 = Sunday
Starting time
Hours 00 h .. 24 h. "xx.24 d.h." Minutes/seconds 00.00 m.s .. 59.00 m.s. "00.00 m.s."
Date and time Date and time
Summertime "oFF" oFF, on, Eu oFF Wintertime "oFF" oFF, on, Eu oFF
Software release "rEL" 4-digits loaded software release Serial number "S. nr" 8-digits serial number LCD Contrast "cont" 170 .. 230 185
Inner temperature "88°" 2-digits -
User password "PASS" 0000 .. 9999 "0000"
Page 39= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Current transformer
The ratio of the current transformer is set in conf igurati­on menu CONF . The secondary current can either be set to ../1A or ../5A. If you are in configuration menu CONF , the current transformer ratio can be changed as follows:
A
A
SELECT CT
CONF
Select: Confirm the selection of the current transformer menu with
key 2.
The text SELECT dis­appears.
Set: Select the number to be changed using key 1. The selected number flashes. The text EDIT appears. Change the selected number using key 3. Multiply the number with a factor 10 with key 2.
When the ratio of the current transformer is set, press key 1 as often, as no number is flashing any longer. EDIT disappears. With key 3 you move to the next menu. The ratio of the current transformer is saved.
Voltage transformer
The ratio of the voltage transformer is set in configurati­on menu CONF. The secondary voltage can be set in the range of 100V up to 500V. If you are in configuration menu CONF, change the ratio of the current transformer as follows:
A
A
SELECT CT
CONF
Select Confirm selection of current transformer menu with key 3. The text SELECT dis­appears.
Select With key 3 you move to the voltage transformer menu.
Set Using key 1 the num­ber to be changed is se­lected. The selected number flashes. The text EDIT appears. With key 3 the selected number is changed. Key 2 multiplies the number with a factor
10.
If the ratio of the voltage transformer is set, press key 1 as often, as no number is flashing any longer. EDIT disappears. With key 3 you move to the next menu. The ratio of the voltage transformer will be saved.
A
A
CT
CONF
EDIT
Primary current
Secondary current
Primary voltage
Secondary voltage
kV
V
VT
CONF
EDIT
kV
V
VT
CONF
Page 40 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Modem
Via the RS232 interface, the UMG503 can be connected to an external analogue modem. The connection between UMG503 and the Modem is carried out via a "point to point" cable. For modem operation, the transmission protocol 5 (modem) must be selected for the RS232 interface.
Transmission protocol RS485
The following protocols can be selected: off no protocol, interface disconnected 1 Standard Protocol 2 Modbus Protocol 3­4 Service Protocol 5 PROFIBUS DP (Slave), (Option) 6 Modbus RTU (Master)
*1)
Terminal resistance
If the device is connected to the end of a bus cable, the bus cable must be terminated by terminal resistances. The required terminal resistances are integrated within the device and are activated in condition ON.
RS232 interface (Option)
The RS232 interface is suited for transmission of data over a distance of 15m. The UMG 503 can be connected directly via this interface to the COM-port of PC or an external analogue modem.
The connection to PC must be carried out via a
zero
modem cable.
Transmission protocols RS232
off no protocol, interface disconnected 1 Standard protocol 2 Modbus RTU protocol 3­4 Service protocol 5 Modem 6 Modbus RTU (Master)
*1)
CONF
Type of interface
Protocol number
Baud rate
RS485 interface (Option)
The RS485 interface is suited for transmission of data over a distance of 1200 m. Up to 31 UMG503 and a master (PC or SPS) can be connected. As PCs usually only have a RS232 interface, a suitable interface converter must be connected between UMG 503 and PC. The distance between interface converter and PC may be 4 m at maximum. The distance between UMG 503 and interface converter may be 1200 m at maximum.
Type of interface
Protocol number
Baud rate
CONF
*1)
The protocol 6 can run on one interface RS232 or RS485 only.
Diagr. Connection diagram RS485
Diagr. Connection diagram RS232
UMG503
UMG503
Page 41= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Device address
If several devices are connected via the RS485 interface, a master device (PC, PLC) can distinguish them by the device address only. Therefore each UMG 503 must have another device address. Device addresses can be given from 0 to 255.
Attention! With PROFIBUS DP protocol device addresses from 0 to 126 are managed.
ADDR
CONF
Select In menu CONF you move to indication of device address using key 3. In this example the factory's presetting is indicated as "1".
Change With key 1 a number of the device address can be selected and be changed using key 3. The selected number is flashing.
ADDR
EDIT CONF
The set device address can be called and changed in menu CONF. Please move to menu CONF (See chapter "configuration").
Save If you have set the desired device address, please use key 1 as often as no number is flashing any longer. Pressing key 2, the text EDITdisappears, and the indicated device address will be saved.
ADDR
CONF
Page 42 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Data recording
The memory of UMG 503 is devided into three areas: The event memory, the peak and lowest value storage and the ring buf­fer. In the peak and lowest value storage, all peak and lowest values are saved with date and time. In the ring buffer all measured values are deposited, as long as they are marked for storage. In the Event memory all switchings of relay outputs and breakdown of supply voltage are saved.
In delivery condition is
Data recording = on
and all memory areas can be written. If no data recording should be carried out, data recording must be oFF.
CONF
Select In menu CONF scroll to display of data recording "dAtA". Confirm selection with key 1. The text EDIT appears. The set data recording is displayed and flashing. In this example, data recording is on, which means, data are recorded.
Change The set data recording is flashing. Using key 1 you can change over between on and oFF. Confirming key 1, the text EDIT disappears. Confirming key 3, you change to the program­ming of limits.
Pressing key 1 long, the programming is saved and you change back to the first measured value display.
CONF
EDIT
CONF
EDIT
Page 43= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Internal relay outputs (Option)
The limits 1A up to 2C are assigned to the relay outputs K1 and K2. If one or more limits, which are assigned to an internal relay output, exceeded, the corresponding relay releases. To avoid too frequent switchings, a minimum connection time is programmable for each relay output.
Limits
6 limits of measured values can be programmed for supervision. Violations of these limits can be saved with date and time within the event buffer.
External relay outputs
Additional relay outputs can be controlled via a bus coupling and digital output clamps of the company WAG O . Each digital output clamp supervises one limit:
Digital output clamp DAK1 = Limit 1A Digital output clamp DAK2 = Limit 1B Digital output clamp DAK3 = Limit 1C Digital output clamp DAK4 = Limit 2A Digital output clamp DAK5 = Limit 2B Digital output clamp DAK6 = Limit 2C
The connection of the UMG 503 to the bus coupling can be carried out via the RS232 or RS485 interface. Both devices, UMG503 and bus coupling, must have the same interface.
Attention!
An event buffer must be reserved for the storage of limit violations.
Limits can be positive (+) or negative (-). For positive limits (+) , the sign is not indicated.
The limits are divided into the limit groups 1x and 2x and have the following descriptions:
1A, 1B, 1C,
2A, 2B, 2C The limits are assigned to two internal and 6 external relays.
kW
M.S
L1 L2 L3
EDIT CONF
Minimum connection time =10seconds
Violation at exceeding
Supervised measured value = Sum real power limit = 100kW
Limit group=2
Limit Symbol
Limit number = 2C
Diagr. Connection example for internal relay outputs
Relay outputs Limits inter. external 1A 1B 1C 2A 2B 2C
K1 x x x K2 x x x
DAK1 x
DAK2 x
DAK3 x
DAK4 x
DAK5 x
DAK6 x
Kx = Relay output(internal) DAKx = Digital output clamp (external)
Diagr. Assignment of the limits
Attention! On the relay contacts K1 and K2, no touchable low voltage and life voltages may be used at the same time. The wiring for the relay outputs must be suitable for voltage up to 300VAC against ground.
Page 44 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
t1 100kW were exceeded, relay K1 attracts. t2 200kW were exceeded, relay K2 attracts. t3 200kW were underscored. The programmed
minimum connection time for relay K2 is running.
t4 The minimum connection time is over and the
relay K2 releases.
t5 100kW were underscored. The programmed
minimum connection time for relay K1 is running.
t6 The minimum connection time is over, and relay
K1 releases.
Example: Real power, sequence chart
1234
1234
t1
Ein
K2
K1
Aus
t
Ein
Aus
t4t2 t3 t5 t6
P/kW
0
100
200
In menu CONF you leaf to the indication of the desired limit group using key 3. The limit number here is indicated as 1A. Now change over bet­ween the limit numbers 1A, 1B and 1C using key 2.
M.S
CONF
Assign measured value: Pressingkey 1, the middle indication is flashing, and a mea- sured value can be se­lected.
The text EDIT appears.
Pressing key 2 and then key 3 you leaf through the measured value indications.
A measured value can be selected using key 1. Please confirm with key
2.
M.S
CONF
EDIT
kW
M.S
L1 L2 L3
EDIT CONF
Attention!
To be able to distinguish between the measured values "Sum real power" and "Real power EMAX", the phases for "Real power EMAX" are shown in the first line.
Assign limits
With key 1 you can change between the ciphers of the limit, the
minimum connection time and the symbols for underscoring / ex­ceeding.
If you have confirmed the selected measured value with key 2, the first number of the middle indication flashes.
Minimum connection time
Underscoring/ Exceeding
Limit
The selected numbers or symbols can be changed with the keys 2 and 3 (see chapter Edit). If the limit is set, please press key 1 as often as no numbers flashing any longer. EDIT disappears. With key 3 you reach the next menu point. The limit is now saved.
Limit group
Example: Sum real power
limit number 2B
Assigned measured value= Sum real power.
Switched at exceeding.
Minimum connection time= 10 seconds
Limit=100kW
kW
M.S
L1 L2 L3
EDIT CONF
Example: Real power EMAX
Limit number1C Measured value= Sum "real power EMAX"
Switches, when ex­ceeded.
Minimum connection time= 10 seconds
Limit =100kW
kW
M.S
L1 L2 L3
CONF
kW
M.S
L1 L2 L3
CONF
Page 45= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Three wire measurement (Option)
The UMG503 is suited for measurement in networks with or without neutral conductor. Networks with a neu­tral conductor are called four wire networks, without neutral conductor are called three wire networks. The option "three wire measurement" is needed for the connection examples 5 and 6.
When option "three wire measurement" is released, you can select between three wire measurement "3L" and four wire measurement "4L" in menu CONF.
Select In menu CONF you move to the indication of three or four wire measurement using key
3.
In this example the four wire measurement "4L" is activated.
Change With key 1 can be switched between four wire (4 L) and three wire measurement (3 L).
CONF
EDIT CONF
Attention!
In networks without neutral conductor voltage transformers must be used!
Diagr: Three wire measurement with two voltage trans­formers and two current transformers.. (Option "Three
wire measurement" required)
Diagr: Three wire measurement with two voltage trans­formers and three current transformers. (Option "Three
wire measurement" required)
Page 46 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Net frequency
The net frequency is determined from the measuring voltage within the UMG 503. From this net frequency, the scanning frequency for current and voltage inputs are calculated. For measurements with very distorted voltages, the fre­quency of the voltage fundamental cannot exactly be determined any longer. Voltage distortion occurs in measurements at consumers, which are driven with phase changing controllings. For measuring voltage, which shows strong distortion, the corresponding stable net frequency should be set. Distortion of the current does not affect the determinati­on of the frequency.
If the measuring voltage is missing, no net frequency can be determined and no scanning frequency can be calculated. Voltage, Current and all resulting values are not calculated and indicated by zero. If the current should be measured without measuring voltage, the net frequency should be set at UMG 503.
The determination of the scanning frequency can either be done automatically or programmed.
The following settings for the determination of the fre­quency are at your disposal: "Auto" Automatical frequency "50"Hz Stable frequency "60"Hz Stable frequency
The proceeding for the determination of the frequency can be called up and changed in the menu CONF.
Select In menu CONF you can leaf to the indicati­on of the frequency deter-mination using key 3. In this example, the fre­quency is determined automatically.
Change Using key 1, the deter- mination of the fre­quency is selected, and the text "Auto" flashes. In the indication, the text EDIT appears.
Using key 3, you can change over between the two methods of fre­quency determination.
In this example a fix frequency of 50Hz is set.
Hz
SELECT
EDIT CONF
Hz
SELECT
CONF
Page 47= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Measured value rotation
All measured values are calculated two times per second and can be displayed. Normally the selection and displaying of measured values is carried out via the keys 2 and 3. Additionally, there is the possibility of measured value rota­tion, which means to show selected measured values one after the other without keypress. If no key is pressed for about 60 seconds, the measured value rotation becomes active, if programmed.
For the measured value rotation, all displays, which are retrievable by the key, are at your disposal. The changing time for the displays can be set in the range of
0 .. 9999 seconds
To activate the measured value rotation, at least one measured value must be selected and the changing time must be programmed for more than 0 seconds.
If a changing time is programmed with 0 seconds, there is no change of the display.
If the changing time is bigger than 0, but only one display has been selected, only this display is indicated.
CONF
CONFEDIT
CONFEDIT
Program changing times
Select Please scroll to display "changing time Pic" in menu CONF using key 3. Confirm selection with key 1. The text EDIT appears. The set changing time is indicated and flashes. In this example, a chan­ging time of 0 seconds is indicated, which means the measured value rotation is not active.
Change The set changing time is flashing. Confirm selection with key 1. The first digit of the changing time is flashing. Now select the number to be changed with key
1. If a number is flashing, it can be changed using key 3. If all numbers of the changing time are flashing, you can change to the measured value selection with key 2. If no number is flashing, you can change to the program­ming of the analogue output using key 3.
By a long press of key 1 you save programming and go back to the first measured value indication.
Page 48 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
V
V
V
L3
L1
L2
Program measured value selection
Select Please scroll to display "changing time Pic" in menu CONF using key
3. Confirm selection with key 1. The text EDIT appears. The set changing time is indicated and flashes. In this example, a chan­ging time of 0 seconds is indicated, which means the measured value rotation is not active.
Change to the measu­red value selection with key 2. In this example, the measured value indica­tion for voltage L against N appears. The measured value in­dication has not been programmed for the measured value rotation yet.
Pressing key 1 shortly, the measured value in­dication becomes active for the measured value rotation.
Pressing key 1 again shortly, the display becomes inactive again. Pressing key 1 longer, you change back to the programming of changing time. The number 1 of changing time is flashing.
By a long press of key 1 you save programming and go back to the first measured value indication.
CONFEDIT
V
V
V
L3
L1
L2
Page 49= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Analogue output
All measured values except real and reactive work, can be given out as a current via the analogue output. One internal and six external analogue outputs can be pro­grammed at maximum. The external analogue outputs are controlled via a bus coupling and analogue output clamps of the company WA G O . The connection of the UMG 503 to the bus coupling is carried out via the RS232 or RS485 interface. Both devices, UMG503 and bus coupling, must be con­nected to each other via the same interface. Each analogue output can be assigned to
one measured value, one scale starting value and
one scale end value Only the internal analogue output in the UMG 503 can be switched between
0-20mA and
4-20mA additionally. For the external analogue outputs analogue output clamps with the signal types
0-20mA,
4-20mA and
+-10V are available.
Internal analogue output (Option)
For the operation of the internal analogue output an external auxiliary voltage from 20V up to 30V DC is required. The connectable maximum load is 500Ohm. If the analogue output is loaded with a higher resistance, the output range (20mA) is limited.
internal analogue output
Attention!
The internal analogue output can be used only, if the option "analogue output" is released.
Diagr. Connection example, internal analogue output
CONF
UMG503
Hilfsspan­nung
0 .. 20mA
GND
Page 50 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Diagr.: Connection example for 2 UMG503 with analogue outputs to a PLC-analogue input module.
Grounding strip
Page 51= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Assign measured value
All measured values, which are configurated for the measured value indication, except real and reactive energy, can be given out of the analogue outputs. From the measured value tables, the desired measured value, "sum real power", for instance, are chosen and assigned to the analogue output.
Please scroll to the display analogue output in menu CONF. Text "AnLo" flashes. Now a measured value table can be selected with key 2. The measu­red value table for voltage appears. Now you can select a measured value table with key 3. Select a measured value key 1 from the measu­red value table and con­firm with key 2. The text "AnLo" does not flash anymore and the se­lected value is indicated.
W
L1 L2 L3
CONF
Sum real power
External analogue outputs
The external analogue outputs are controlled via a bus coupling and analogue output clamps of the company WA G O . The connection between UMG 503 and bus coupling can be carried out via RS232 or RS485 interface. Both devices, UMG 503 and bus coupling, must be connected with the same interface.
Indication in the configuration menu
External analogue outputs are indicated with the numbers 01 up to 06 in the UMG 503. The numbers correspond to the sequence of the analogue output clamps connected to the bus coupling. The menu "external analogue output" can only be called up, if the protocol number"06" (Modbus RTU Master) is set at the UMG 503.
Transmission protocol
The MODBUS RTU protocol is used as transmission protocol between the UMG 503 and the bus coupling of the company WAG O . The UMG 503 becomes the master and the bus coupling becomes the slave. In the UMG 503 the protocol "06" (Modbus RTU Ma­ster) must be set.
Attention!
For the transmission via RS232, only "point to point" connection with a maximum distance of 5m can be achieved. The RS485 allows a bus length of maximum 1200m.
External analogue output number = 01
CONF
If you are in the menu CONF, leaf to the indi- cation of the external analogue outputs using key 3. Analogue output num­ber 01 is indicated.
Please leaf to the analogue outputs 02 up to 06 using key 2 .
The following external analogue output clamps of the company WAGO can be controlled by the UMG 503:
Item code WAGO Number of outputs Signal type
750-550 2 0 .. 10V
750-552 2 0 .. 20mA
750-554 2 4 .. 20mA
750-556 2 +- 10V
UMG503 (Master)
Bus coupling (Slave)
Function clamps
Interface cable
Page 52 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
CONF
Scale starting value
Scale end value
The text "AnLo" flas­hes. Press key 1. The text EDIT appears and the first number of the scale starting value is flashing. By further pressing of the key 1, each cipher of the scale starting value or the scale end value can be selected.
Scale starting value and scale end value
The scale starting value and the scale end value can be set in the indication range of the corresponding measu­red value
With key 3, the flashing cipher can be changed. With key 2 the decimal point is moved.
In the first digit of the scale starting and scale end value, the sign "-" can be set. The sign appears after the number "9".
Set output range
The output range for the external analogue outputs can­not be programmed, as it is fixed for the used type of the function clamps. The output range of the internal analogue output of the UMG 503 can programmed to 0 .. 20mA or 4 .. 20mA. In delivery condition, the analogue output is preset to 4 .. 20mA.
The text "AnLo" is flashing. Pressing key2, the output range is in­dicated in "mA". Output range (4..20mA / 0..20mA)
Select the output range with key 1. The text EDIT appears.
Pressing key 3 you select the output range from 0 to 20mA.
After selecting the last cipher of the scale end value the text EDIT disappears. Now change to the next menu using key 3.
Sign
Scale starting value = - 0.100MW = - 100kW
Scale end value = 400kW
L1 L2 L3
W
EDIT
L1 L2 L3
W
M
k
CONFEDIT
CONF
EDIT
Page 53= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Example: Sum real power
On the internal analogue output of the UMG 503 the sum of real power shall be given out as a current. As a generator shall be switched on sometimes, the delivered real power shall be retrieved as well. Real power supplied is indicated by a "-" before the real power value. The following settings are required: Output range = 0 .. 20mA Measured value = Sum real power Scale start value = -100kW (Delivery to energy
supplier)
Scale end value = 400kW (Consumption)
With the selected settings, a power range of 100kW + 400kW = 500kW is covered. So is 500kW = 20mA. 1mA corresponds to 500kW/20 = 25kW. If no real power is supplied or consumed, a current of 4mA is flowing. If real power is supplied, a current smaller but 4mA is flowing.
Example: cos(phi)
output range = 4 .. 20mA Scale start value = 0.700inductive Scale end value = 0.900capacitive So the scale range is devided from 0, 400 to 16mA, and cos(phi)1.000 corresponds to 16mA.
0mA 4mA 20mA10mA
0,700ind.
0,900kap.
1,000
16mA
CONF
Programming
The external analogue outputs can only be indicated and programmed, when the protocol "06" (Modbus RTU Ma­ster) is set at the UMG 503. The programming of the internal and external analogue output is very similar except some small exceptions.
If the protocol "06" (Modbus RTU Master) is selected, the first external analogue output "01" is indicated besides the internal analogue output. Otherwise the indication of the menu for the pulse output appears.
To display the other external analogue out­puts "02" up to "06", please press key 2. Con­firm the selected analogue output with key 1 and program it. The text" AnLo" flas­hes.
0mA 4mA 20mA10mA
-100kW 400kW0kW
15mA
300kW150kW
ConsumptionSupply
If you are in the menu CONF, you leaf to the indication of the internal analogue output using key 3. With key 1, the selected analogue output is confirmed and can be programmed. The text "AnLo" is flashing.
CONF
Page 54 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Pulse output (Option)
Corresponding to the mechanical energy meters, the UMG 503 has a pulse output as well. At the pulse output, the energy of real and reactive energy meters can be given out. The minimum pulse duration is 50 ms and the maxi­mum frequency is 10Hz. If more than one pulse per second is given out by the pulse output, the pulse gap is not proportional to the power anymore. If less than one pulse per second is given out by the pulse output, the pulse gap is proportio­nal to the power. The inaccuracy of the pulse gap is +­10ms.
Assign energy
Various measured values can be assigned to the pulse output of the UMG 503
Without reverse running stop Consumption T00, T01, T02, T03, T04 Supply T00, T01, T02, T03, T04
Reactive energy
Without reverse running stop inductive (ind) T00, T01, T02, T03, T04 capacitive (cap) T00, T01, T02, T03, T04
Pulse valency Iw=0,000Wh/Pulse
Real energySum Consumption
Scroll to the indication of the pulse output in menu CONF with key
3.
Wh
L1 L2 L3
CONF
T
Confirm the selection using key 1. The middle indication is flashing and the text EDIT appears.
Wh
L1 L2 L3
EDIT CONF
T
Switch to the measured value selection pressing key 2 . The picture in the margin appears. With key 2 and key 3 the desired energy can be assigned to the pul- se output.
M Wh
kWh
Wh
L1 L2 L3
T
Confirm selection with key 1.
The text EDIT appears. With key 2 change into the edit mode. The first number is flashing.
Wh
L1 L2 L3
EDIT CONF
T
To leave the menu, press key 1 so often until the text EDIT disappears. Pressing key 3 you switch to the next menu.
Attention! When the pulse output is assigned to real energy meter without reverse running stop, pulses are
given out for consumption and supply. If the pulse output is assigned to the reactive energy meter without reverse running stop, pulses are given out for inductive and capacitive load.
If the measured work exceeds the set pulse valency, so that the maximum for the pulse output is exceeded, the rest of the pulses are saved and given out later. Up to 32000 pulses are saved in the pulse memory.
Display example for the pulse output:
Wh
L1 L2 L3
CONF
T
Diagr.: Connection example for pulse output
UMG503
Page 55= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
kWh
L1 L2 L3
EDIT CONF
T
Set pulse valency
The pulses from the UMG 503 can be assigned to certain work. The energy per pulse is given as pulse valency Iw in Wh/puls.
Iw =energy/pulse
The pulse valency must not be confused with a meter constant. The meter constant is given in revolutions per kWh. The connection between pulse valency and meter constant can be seen in the following correlations:
meter constant = 1/pulse valency
pulse valency = 1/meter constant
Example: Pulse valency
The pulse valency Iw should be destined for a three phase network with connected consumers of maximum P=400kW. In one hour, a maximum work A of:
A = P * t (t = 1Stunde) A = 400kW *1h A = 400kWh can be consumed.
This means a pulse valency Iw of
Iw = A/pulse Iw = 400kWh/pulse
Iw = 400kW This means, that the pulse valency Iw must be set equal or higher than 400kW at the UMG 503.
Example: Maximum power
A pulse collecting device can only manage a pulse valency of 9999Wh/pulse. What power can be transmitted at maximum?
Iw = A/pulse The work A can be calculated with:
A = Iw * pulse
A = 9999Wh/pulss * pulse
A = 9999Wh
This means a pulse valency Iw of
Iw = A/pulse
Iw = 9999Wh/pulse, which must be set at the UMG 503.
Pulse valency Iw=0,000Wh/pulse
Real energy
Sum Consumption
In the menu CONF scroll to indication of the pulse output with key 3.
Wh
L1 L2 L3
CONF
T
Confirm selection with key 1. The middle indication flashes and the text EDIT appears.
Press key 1 again, and the first digit flashes.
Wh
L1 L2 L3
EDIT CONF
T
Using key 1, you switch to the next digit.
With key 3 the number will be changed. With key 2, the decimal point is moved.
Change with key 2 .
To leave the menu, press key 1 so often until the text EDIT disappears. Pressing key 3 you switch to the next menu.
Page 56 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Event memory
The following events can be saved in the event memory with date and time:
- Deletion of the event memory,
- Relay outputs 1A, 1B, 1C on/off,
- Relay outputs 2A, 2B, 2C on/off,
- Auxiliary input on/off,
- Breakdown and return of the auxiliary voltage,
- Breakdown and return of the measurement voltage,
- Reset of real power EMAX,
- Synchronization of the internal clock,
- Tariff change over 1/2. The event memory can be read out with PC and the programming and reading out software PSWbasic. A breakdown of the measurement voltage is recognized, if:
- the measurement voltage is smaller than 50% of the set primary voltage of the voltage transformer
- and the breakdown lasts longer but 500ms without interruption.
In the device a memory is available, which is divided into the ring buffer and the event memory. The dimension of the event memory can be programmed to determine the number of events, that can be saved in the memory. If the number is set to "0", the whole memory is available for the ring buffer.
If the number of events is changed, the contents of the event memory and ring buffer are deleted.
The dimension of the memory for event memory and ring buffer is depending on the RAM of the UMG 503.
Memory
Event memory 128k RAM 512k RAM
Setting range 0 - 2000 0 - 9999 Presettings 0 1000
The number of events, that should be saved, can be displayed and changed in the menu CONF.
Display Scroll to the indication of the event memory in menu CONF using key
3. In the example, the num­ber is set to 1000.
Number of events = 1000
Change The digit to be changed can now be selected with key 1 and be changed with key 3. The symbol "EDIT" appears and the selected number is flashing.
EDIT CONF
128kRAM
up to 2000
events
512kRAM
up to 9999
events
CONF
Page 57= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Internal auxiliary input (Option)
The functions
- Reset real power EMAX,
- Tariff change over and
- Synchronizing the internal clock can be controlled by the internal auxiliary input (option) and external digital inputs of the WAGO I/O System. Changes of condition of each auxiliary input are saved in the event memors with date and time. The storage of the changes of condition cannot be given up!
The assignment of the functions to the inputs is laid out by the ciphers 1 to 6. If the internal auxiliary input (option) and the external digital inputs are not used, "oFF" appears in the indication. The producer's presetting is "oFF".
The following assignment is possible:
Reset of real power EMAX
If an external reset occurs within the 15 minutes period, the EMAX real power is deleted and a new period is started. If no external reset occurs within the programmed measu­ring period, the reset is done by the internal clock. If there are less than 30 seconds between two resets, the measurement period is reset and the EMAX real power is deleted. The former measured value is not used for high­est nor lowest value storage and not saved in the ring buffer although programmed.
Tariff change over
The tariff change over can be carried out externally via the auxiliary input or internally via programmed swit­ching times. If the tariff change over is carried out via the auxiliary input, the change over is carried out by the tariff meters Tx1 and Tx2. If there is no voltage at the auxiliary input, tariff meter Tx1 is active. If there is voltage at the auxiliary input, tariff meter Tx2 is active.
Synchronization of the internal clock
Inaccuracies of the internal clock can be corrected via the keys on UMG 503 or via the auxiliary input. If a voltage is connected to the auxiliary input, the clock within the UMG 503 will be set to the next full hour.
Example 1 If the UMG 503 shows a time of 15:05, and a synchroni­zation is carried out, the time will be corrected to 15:00.
Example 2 If the UMG 503 shows a time of 15:35, and a synchroni­zation is carried out, the time will be corrected to 16:00.
Attention!
The assignment 5 and 6 cannot be program­med not before the assignment of a serial interface of the UMG 503 to protocol "06" (Modbus RTU Master) .
- = Locked z = Via internal time program i = Internal auxiliary input e1 = external "digital input 1" e2 = external "digital input 2" e3 = external "digital input 3"
Table: Assignment of auxiliary inputs
Auxiliary inputs
internal extern.
Function oFF 1 2 3 4 5 6
Reset real power EMAX - - - i i e1 e1 Tariff change over z i z z z e2 e2 Synchron. of the int. clock - - i - i i e3
Page 58 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Set function = oFF The tariff changeover is carried out by the internal time program "z".
For devices with the auxiliary voltage of "85 .. 265VAC, 120 .. 370VDC" the auxiliary input is activated with an alternating voltage of 85 .. 265VAC .
CONF
For devices with an auxiliary voltage of "15 .. 55VAC, 20 .. 80VDC" the auxiliary input is activated with an alter-
nating voltage of 15 .. 55VAC or a direct current voltage of 20 .. 80VDC.
For devices with an auxiliary voltage of "40.. 115VAC,
55.. 165VDC" the auxiliary input is activated with an
alternating voltage of 40.. 115VAC or a direct current voltage of 55.. 165VDC.
Symbol text for the au­xiliary input
Diagr.: Auxiliary for direct current and alternating volta­ge
Diagr.: Auxiliary voltage for alternating voltage only
Select In menu CONF move to the indication of au­xiliary input using key
3
EDIT CONF
Change Confirm with key 1. The set function appears and can be changed with key 3.
The text EDIT appears.
If the function for the auxiliary input is set, press key 1 as often as no digit is flashing any longer. EDIT disappears. . With key 3 you move to the next menu point. The function is stored.
Programming
The external digital inputs can only be indicated and programmed, if the protocol "06" (Modbus RTU Master) is set at the UMG503. The functions
- Reset real power EMAX,
- Tariff changeover and
- Synchronization of internal clock can be programmed according to the table "assignment of auxiliary inputs" on page 50.
Attention!
The wiring for the auxiliary input must be suitable for voltages up to 300VAC against ground.
On the internal auxiliary input, only the tariff changeover is ac­tive.
UMG503
AC/DC
Page 59= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Tariff change over
For energy measurement, which should be carried out in certain periods, four tariffs are available: T01 .. T04 Real energy consumption and real power
EMAX, T11 .. T14 Reactive energy, inductive and T21 .. T24 Reactive energy, capacitive.
The tariff changeover is carried out internally via a time program or externally via the auxiliary input. To each of the three tariff groups T0x, T1x and T2x 10 changeover times can be assigned. Work meter Tx0 is not programmable.
External tariff change over (option)
The first two work meters can be changed over via the auxiliary input. When the contact is open, work meter Tx2 is active. When there is voltage on the auxiliary input, work meter Tx1 is active. When the auxiliary input is programmed for tariff change over, only the work meters Tx3 and Tx4 can be cont­rolled via the time program.
Attention!
The energy meters (Tariffs) cannot be deleted individually. If reactive or real energy is deleted, all corresponding energy meters (tariffs) are de­leted.
Energy meter
Controlled via Internal time program Auxiliary input
Real energy
Without reverse running stop T50 Consumption, real power EMAX T00 T01 T02 T03 T04 Supply T30
Reactive energy
Without reverse running stop T40 inductive T10 T11 T12 T13 T14 capacitive T20 T21 T22 T23 T24
Wh
D.H
M.S
L1 L2 L3
CONF
T
Changeover time
Symbol Number
Starting time:
-Hour
-Second
-Minute
Sum
Energy meter
Symbol Energy type Number
Real energy
Consump­tion
Week day
- beginning
- end
Page 60 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Internal tariff changeover
The internal tariff changeover is carried out via time programs. When the auxiliary input is programmed for tariff changeover, only the work meters Tx3 und Tx4 can be controlled via time program. The time program can be programmed by PC or directly at UMG 503.
Assignment of the week days:
1 - Monday 2 - Tuesday 3 - Wednesday 4 - Thurday 5 - Friday 6 - Saturday 7 - Sunday
For each three selectable work up to 10 changeover times can be programmed. In the changeover time the starting time is determined for the corresponding work meter in
Week day, beginning/end and
Hours/Minute If energy measurement (P3) does not follow energy mea­surement (P1), the changeover time for the end of energy measurement must be laid out to tariff zone Tx0, which is not programmable. In the example, this is changeover time "P2".
If the starting time is set to "24h 00:00", the correspon- ding energy meter is not activated.
In menu CONF move to the indication of work meters using key
3. Here consumed real work was selected.
With key 2 you can sel- ect the number (0-9) of the changeover time.
Pressing key 1, you can select the number and the text EDIT appears. Changeable Values: Week day beginning Week day end Start time - Hour Start time - Minute Start time - Second The selected numbers can be changed using the keys 2 and 3 (see chapter Edit).
If the changeover times are set, press key 1 as often as no number is flashing any longer. EDIT disappears. With key 3 you move to the next menu point. The time program is saved.
Programming
Wh
D.H
M.S
L1 L2 L3
EDIT CONF
T
12:00
P3
P2
P1
T00
T01
T04
T03
T02
09:0000:00
P0
06:00 24:00
Diagr. Energy meter T0x, real energy consumption
Wh
D.H
M.S
L1 L2 L3
CONF
T
Page 61= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Clock
Date and time are needed as time information for highest and lowest value and storage of measured values in the ring buffer. Date and time are set to the Middle European summer time.
Select In menu CONF move to the indication of date and time with key 3. In this example the date is 10.08.1998 and the time is 14:27:15.
Change With key 1 a digit can be selected and chan­ged with key 3. The selected number is flashing. The text "EDIT" ap­pears. Date and time stop.
Date and time can be called up and changed in menu CONF. Therefore please change to menu CONF (See chapter "configuration").
Y.M
D.H
M.S
CONF
Day Year
Month
Minute Second Hour
Y.M
D.H
M.S
EDIT CONF
Save When you have set the actual date and time, please press key 1 as of­ten as no number is flashing any longer. Pressing key 2, the text EDITdisappears and date and time run with their new settings.
Y.M
D.H
M.S
CONF
Comment: The device is Year 2000 concurring according to DP2000­1:1998 of BSI (British Standards Institution).
Summer-/Wintertime changeover
The UMG503 can carry out an automatical summer and wintertime changeover. The following possibilities are available:
oFF - No summer and winter time changeover. on - Your own changeover times
Eu - Listed changeover times At the date, which is marked by an arrow downwards, time leaps back from 03:00 to 02:00. At the date, which is marked by an arrow upwards, time leaps forward from 02:00 to 03:00.
Your own changeover times If summer-/winter changeover is "on", both changeover times can be entered individually. The changeover times within the list are not valid.
Listed changeover times In UMG503 a list of changeover times up to year 2020 is deposited. In this list, the last weekend in March and the last weekend in October of each year has been respected. If summer-/wintertime is set to "Eu", the changeover times of this list are used.
Y.M
D.H
M.S
CONF
Y.M
D.H
M.S
CONF
Select In menu CONF you can scroll to the display of date and time using key 3 and then with key 2 to the summer time chan­geover. In this example, the date
25.03.2001 is indicated.
Pressing key 2 again, the time for winter changeover is indicated.
Winter time changeover
Summer time changeover
Page 62 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
LCD contrast
The best view for the LCD display is "from below". The contrast of the LCD display can be adapted by the user. The contrast setting is possible in the range of 170 to 230 in 5 point steps.
230 = very light
170 = very dark In order to reach the optimum contrast for the whole operating temperature range, the inner temperature is measured within the device, and the contrast setting is corrected automatically. This correction will not be indi­cated in the contrast settings indication.
Change With key 1 the contrast setting is selected, and the number is flashing. In the indication the text EDIT appears. Increase the contrast setting in 5 point steps using key 3. If 230 is exceeded, the value jumps back to
170.
EDIT CONF
Selection In menu CONF move to indication of LCD contrast using key 3. In this case the inner temperature is 28°C and the contrast setting is 185.
Inner temperature
Contrast setting
CONF
Serial number
Each device has its own 8 digit serial number, which cannot be changed by user. For certain device variants the user can release functions (options) later on. In that case the serial number is needed in the manufacturing works. For each device passwords are deposited in the manufac­turing company for releasing certain functions (options).
Software Release
The software within the device is improved and expan­ded continuously. Therefore the condition of software is marked by the software release. The software release cannot be changed.
Select In menu CONF move to the indication of the software release using key 3. In this case the software release is indicated
1.210.
CONF
The software release can be called up in menu CONF. Please move to the menu CONF (See chapter "conf i­guration").
CONF
Example: Serial number = 5300 0003
Page 63= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Password
Certain functions are protected by a user password. There are three types of passwords:
Clearance password (8-digits) User password (4-digits) Master password (4-digits)
CONF
Select In menu CONF you move to the indication of the password with key
3. In the basic setting a 0000 0000 is indicated.
EDIT CONF
Input With key 1 you select the digit to be changed. The text EDIT appears within the display. With key 3 you change the selected digit.
Clearance password
In the various device variants functions are available as an option. These function expansions can be released in the manufacturing works, when ordering. When later a functional expansion shall be released by the user, a clearance password is needed with 8 digits. This password is deposited in the manufacturing works.
Functional expansions (options), that can be released, are:
Relay outputs Impuls output Analogue output RS232 interface Auxiliary input Infra red interface Three wire measurement PROFIBUS DP (Slave)
To release a functional expansion via the clearance pass­word, please proceed as follows:
Function
User password or Ma­ster password
CONF
Clearance password
CONF
Clearance password "0000 0000"
Save When the password is put in, please confirm key 1 as often as no digit is flashing any longer and confirm with key 2. When the password is accepted, the password is deleted and 0000 0000 appears in the indication. Now the released functional expansion can be called up in the programming or configuration menu.
Page 64 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Master password
The four digit master password is needed for service purpose only and it is not announced to the user.
Function Description
0004 Delete user password 3846 software update 7645 Restore delivery conditions of the device.
After calling function "0004" the user password is reset to delivery condition:
User password = "0000". Now programming can be allowed with user password "0000" and configuration with function "0002".
The input of the master password is done just like the input of the user password.
User password
With the four digit user password the user can protect the programmed data and configuration against unintentio­nal change. The programming and configuration will nevertheless be displayed. In delivery condition the user password is "0000". If the user cannot remember the user password, it can be changed with the master password only. The protection of the user password is not available for access to data within the UMG503 via the serial inter­faces.
There are four functions for the user password at your disposal:
Function Description
1 Lock programming and configuration 2 Admit programming and configuration. 3 Input user password 4 Delete user password.
To activate a function, the user password and the desired function must be put in the password menu. A new user password can be put in, when it was deleted with function 4 by putting in the old user password. A deleted password is indicated with "0000".
EDIT CONF
Input Select the digit to be changed using key 1. The text EDIT is flashing in the indi-ca­tion. The selected digit is flashing. Change the selected number using key 3.
Save When you have put in the password and function, press key 1 as often as no digit is flashing any longer and confirm with key 2.
Function
User password or ma­ster password
CONF
Page 65= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Transmission protocols
For the connection of the UMG 503 to existing field bus systems, two transmission protocols are at your disposal:
- PROFIBUS DP (Slave)
- Modbus RTU (Master and Slave)
The following protocols can be operate via RS485 inter­face: off no protocol, interface is not active. 1 Reserved 2 Modbus RTU (Slave) 3­4 Service protocol 5 PROFIBUS DP (Slave), (Option) 6 Modbus RTU (Master)
*1)
The following protocols can be operate via RS232 inter­face: off no protocol, interface is not active. 1 Reserved 2 Modbus RTU (Slave) 3­4 Service protocol 5 Modem 6 Modbus RTU (Master)
*1)
*1)
Protocol 6 can run only on one interface, RS232 or RS485, at the
same time.
Service protocol
The service protocol is used for calibration and testing purpose in the manufacturing works only.
Modem
For the connection of the UMG 503 to a modem, the protocol "modem" must be set at the UMG 503. Operation of the UMG 503 via modem is only safe with modems tested by the producer.
Page 66 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Modbus RTU
With Modbus RTU protocol all addresses of the follo­wing tables can be retrieved. Table 1a Measured values (floating point format) Table 1b Measured values (floating point format) Table 2 Energy (floating point format) Table 3a Time information for min. and maximum
values and system time
Table 3b Time information for min. and maximum
values and time of summer/ winter
changeover Table 4 Avaraging times of mean values Table 5 Internal control word Table 6a Measured values, integer format Table 6b Mean values, integer format Table 6c Maximum values, integer format Table 6d Minimum values, integer format Table 7 Energy, integer format Table 8 Scale of measured values, which are called
up in integer format Table 9 In- and outputs Table 10 EMAX-peak values
Transmission mode
RTU- Mode with CRC-Check.
Transmission parameters
Baud rate RS232 : 9.6,19.2 and 38.4 RS485 : 9.6,19.2, 38.4, 57.6 and 115.2
Data bits : 8 Parity : none Stop bits (UMG503) : 2 Stop bits (extern) : 1 or 2
Realized functions
Read Holding Register, function 03 Preset Single Register, function 06 Preset Multiple Registers, function 16
Data formats
The data are in the following formats at your disposal: char: 1 Byte (0 .. 255) word: 2 Byte (- 32 768 .. + 32 767) long: 4 Byte (- 2 147 483 648 .. + 2 147 483 647)
The sequence of the bytes is high before low byte.
Example: Reading of system time The system time is deposited under address 3000 in table
1. The system time is deposited in 6 bytes with year, months, day, hours, minutes and second in the format "char" = 0..255. The device address of the UMG 503 is determined as address = 01.
The "Query Message" looks as follows: Description Hex Comment Device address 01 UMG503, Address = 1 Function 03 "Read Holding Register" Start address Hi 0B 3000dez = 0BB8hex Start address Lo B8 No. of values Hi 00 6dez = 0006hex no. of values Lo 06 Error Check -
The "Response" of UMG503 can look as follows: Description Hex Comment Device address 01 UMG503, Address = 1 Function 03 Byte Counter 06 Data 00 Year = 00hex = 00dez = 2000dez Data 0A Month = 0Ahex = 10dez = Oct. Data 0C Day = 0Chex = 12dez Data 0F Hour = 0Fhex = 15dez Data 1E Minute = 1Ehex = 30dez Data 0A Second = 0Ahex = 10dez Error Check (CRC) -
Page 67= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
PROFIBUS DP (Option)
The UMG 503 corresponds to the field bus norm PROFI­BUS DP, DIN E 19245 part 3 as a slave device. The device is listed by the PROFIBUS user organisation e.V. with the following entries: Device description : UMG 503 Ident-Number : 044C HEX GSD : U503044C.GSD
For transmission of measured values with the PROFI­BUS DP protocol integer formats are used by the UMG 503 such as char, int and word.
The UMG503 is suitable for the connection to controls of the type DP-Master Class 1 (DP M1). The maximum baud rate is 1500kbps.
Configuration of UMG 503
The following requirements and settings are necessary for the operation of UMG 503 at Profibus DP:
- A RS485 interface,
- A device address,
- Protocol "05" = PROFIBUS DP
The baud rate is determined automatically between the master (SPS) and slave (UMG503). The setting of the device address is described in chapter "device address".
In menu CONF scroll to the indication of RS485 interface with key 3.
Manufacturer's set­tings:
Baud rate = 38,4kbps Protocol = 02
CONF
Confirming key 1 twice, the lower indica­tion is flashing.
The text EDIT appears.
The protocol can now be changed.
CONFEDIT
CONF
EDIT
Using key 3 you select Protocol "05". If protocol "05" is en­tered, the baudrate is set to "Auto" automatical­ly and cannot be chan­ged.
Pressing key 1 again, the text EDIT disap- pears.
CONF
Protocol
Hints and examples for DP can be found on our homepage.
Page 68 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Higher protocol
Dependant on the format of the measured values to be transmitted, up to 21 measured values can be transmitted from UMG 503 to PLC by PROFIBUS DP protocol cyclically. To transmit more measured values from UMG 503 than determined in the GSD file, you must use a GSD file, which determines the values to be transmitted during operation. With the program PSWbasic, which belongs to the con­tents of delivery, a GSD f ile is created.In this GSD-file a 32 words large output range and a 28 words large input range is determined. In the output range, the PLC can save the desired measu­red value addresses in the control words 4 to 32 and in the input range, the corresponding measured values can be retrieved in the control words 2 to 28. A control word consists of 2 Byte. For controlling purpose, a number is sent by each request for new measured values. The requested measured va­lues are written to the input range, when the PLC replies the request number. Please note, that the request number must be written to the measured value addresses into the output range befo­re, as thereby it is ensured, that the read measured values correspond to the new measured value addresses.
With the "higher protocol" you can call up data from the following tables: Table 1a - Measured values, floating point format Table 1b - Measured values, floating point format Table 2 - Energy, floating point format Table 3a - Time information (Min. and max. values) Table 3b - Time information (Min. and max. values) Table 6a - Measured values, integer format Table 6b - Mean values, integer format Table 6c - Maximun values, integer format Table 6d - Minimum values, integer format Table 8 - Scale of measured values
The measured values from table 4 are scaled by the addresses in table 3. The scaling of the measured values depends on the ratios for current and voltage transformer set at UMG 503 and must be read by changing the ratios only.
The output and input range can be read out and overwrit­ten by the control words 1 and 2 from PLC. With the "Remote bits" an output is selected for con­trolling by the PLC.
Profibus DP V0
In Profibus version "DP V0" only a cyclic data transmis­sion is possible between master PLC and slave UMG503. The transmission data have been determined in the GSD file and the PLC has to request this data set from UMG503 (Slave).
Profibus DP M1
In Profibus version (DP M1) even none cyclical data can be retrieved additionally to the cyclic data. Please note, that calling none cyclical data (DP M1) takes a longer time than using cyclical communication services (DP V0). The functional expansion for none cyclical data trans­mission is specified according to the technical directive
2.082.
Page 69= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Control word1 In- and outputs
bit 0..1 Tariffs 0-3,real work, consumption bit 2..3 Tariffs 0-3, reactive work, inductive bit 4..5 Tariffs 0-3, reactive work, capacitive bit 6 Remote tariff change over bit 7 Synchronization of internal clock, 0 1 bit 8 Reset real power EMAX, 0 1 bit 9 Remote reset of real power EMAX bit 10 Change over winter / summer time,
0 = winter time, 1 = summer time bit 11 Remote change over winter / summer time bit 12 Relay output 2, 0=Off, 1=On bit 13 Remote relay output 2 bit 14 Relay output 1, 0=Off, 1=On bit 15 Remote relay output 1
Control word 2 In- and outputs
bit 0..11 Analogue output bit 12..13 free bit 14 Remote analogue output bit 15 cur rent range, 0 = 0..20mA, 1 = 4..20mA
Control word 3
byte 1 Request number, 0-255 byte 2 free
Control word 4 Address of f irst measured value Control word 5 Address of second measured value Control word 6 Address of third measured value
.. ..
Control word 32
Output range of PLC (32 words=64 Byte)
Input range of PLC (28 Worte = 56 Byte)
Control word 1
byte 1 Called back request number byte 2 Condition of limits (see page 39)
Bit 0 = 1A, 1=Limit output active.
Bit 1 = 1B
..
Bit 5 = 2C
Control word 2 1. Measured value Control word x 2. Measured value Control word x 3. Measured value
.. ..
Control word 28
Diagr. Data transmission with higher protocol
UMG503
SPS
Page 70 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Example: Measured values in integer format
The UMG503 and PLC are set for "Higher protocol". There is a current transformer of 500A/5A and a voltage transformer of 400V/400V. The currents in L1, L2, L3 and the sum of real power should be transmitted in integer format.
Read out scale The scale of the measured values depends on the set current and voltage transformer ratios, which are set at UMG 503, and must only be read after a change of those ratios
The scales of the measured values can be found in table
8. Scale Address
Currents 9100 Power 9102
Within the PLC the output range with control words (4-
5) must be overwritten for the scale and afterwards with the control word (3) for the request number. Control word 1 = In- and outputs "0000" (Example) Control word 2 = In- and outputs "0000" (Example) Control word 4 = Scale "9100" (Currents) Control word 5 = Scale "9102" (Power) Control word 3 = Request number "1" (Example) Control word 6..32 free
After that, the following scales are available in the input range of PLC:
Control word Measured value Contents
1 Request number 1 2 Scale, Currents 0 (*1) 3 Scale, Powers 3 (*1000)
4..28 not defined
Read measured values The measured values in integer format can be found in table 6. The following addresses can be found in table 6.
Measured value Address
Current L1 8000 A Current L2 8001 A Current L3 8002 A Real power, Sum 8024 W
Control word 1 = In- and outputs "0000" (Example) Control word 2 = In- and outputs "0000" (Example) Control word 4 = Measured value address "8000"
(Current in L1)
Control word 5 = Measured value address "8001"
(Current in L2)
Control word 6 = Measured value address "8002"
(Current in L3)
Control word 7 = Measured value address "8024"
(Real power sum.) Control word 3 = Request number "2" (Example) Control words 8..32 free
After that the following measured values are available in the input range of the PLC:
Control word Measured value Contents (Example)
1 Request number 2 2 Current L1 100 (A) 3 Current L2 120 (A) 4 Current L3 140 (A) 5 Real power, Sum. 82800 (W)
6..28 not defined
Page 71= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Example: Measured values in foating point format
The UMG 503 and the PLC are suited for "higher proto­col". A current transformer of 200A/5A and a voltage transformer of 400V/400V have been set. Real energy consumption and reactive power inductive should be transmitted in floating point format and volta­ge in L1, L2 and L3 against earth in integer format.
Read scale The scale of the measured values depends on the set current and voltage transformer ratios only und must only be read after changing those ratios. The scale for voltage measured values can be found in table 8.
Scale Address
Voltage 9101
Within the PLC, the output range must be overwritten with control word 4 for the scales of voltage and with control word (3) for the request number. Control word 1 = In- and outputs "0000" (Example) Control word 2 = In- and outputs "0000" (Example) Control word 4 = Scale "9101" (Voltage) Control word 3 = Request number "3" (Example) Control words 5..32 free
After that, the following scales are available for voltage in the input range of PLC:
Control word Measured value Contents
1 Request number 3 2 Scale, voltage0 (*1)
3..28 not defined
Read measured values The measured values in floating point format can be found in table 1. The following addresses can be read in table 1:
Measured value Address Contents (Example)
Voltage L1-N 1012 230 (V) Voltage L2-N 1017 225 (V) Voltage L3-N 1014 235 (V) Real energy cons. 2000 60444 (Wh) React. energy ind. 2020 23501 (varh)
In the PLC the output range must be overwritten with the control words (4-7) for the measured value addresses and afterwards with control word (3) for the request number. Control word 1 = In- and outputs "0000" (Example) Control word 2 = In- and outputs "0000" (Example) Control word 4 = Measured value address "1012"
(Voltage L1-N)
Control word 5 = Measured value address "1013"
(Voltage L2-N)
Control word 6 = Measured value address "1014"
(Voltage L3-N)
Control word 7 = Measured value address "2000"
(Real energy, consumption) Control word 8..10 = free Control word 11 = Measured value address"2020"
(Reactive energy ind.) Control word 12..14 = free Control word 3 = request number "4" (Example) Control words 15..32 = free
After that the following measured values are available in the input range of the PLC:
Control word Measured value Contents (Example)
1 Request number 4 2 Voltage L1-N 230 (V) 3 Voltage L2-N 225 (V) 4 Voltage L3-N 235 (V)
5..8 Real energy cons. 604,44(Wh)
9..12 Reac. energy ind. 235,01(varh)
13..28 not defined
The voltages each are transmitted in one word (2 Byte) and real and reactive energy each in 4 words (8Byte). Therefore real and reactive energy need 4 control words each and the measured value of reactive energy is depo­sited from control word 9.
Page 72 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Create a GSD file
The program PSW 503 belongs to the contents of delive­ry for the device and includes the module "PROFIBUS configuration". Measured values and in- and outputs can be selected for transmission to PLC with that module. As a result of the configuration, a GSD f ile for the PLC is created.
To bind in a GSD file
The binding of the GSD file in a program is carried out by the customer. It is very different from application to application. Instructions for binding in a UMG 503 in a Siemens SPS S7 (CPU 315-2DP) can be downloaded from the internet page "http://www.janitza.de".
GSD file
The GSD file is a f ile specific for the device, in which the transmission parameters and the kind of measuring data between PROFIBUS Master and the PROFIBUS Slave are laid. The PROFIBUS Slave here is the UMG 503 and the PROFIBUS Master is a PLC, for instance. Depending on the format of the values to be transmitted, at minimum 7 measured values and at maximum 21 measured values can be transmitted. If more measured values are required, a GSD file must be created, that determines a 32 word large output range and a 28 words large input range. In the output range, the PLC can deposit the desired measured value addresses and retrieve the corresponding measured values within the input range. If the addresses in the output range are not changed further, the UMG 503 deliveres new measu­red values continuosly to the input range of PLC. This method of retrieving measuring data is depicted as "higher protocol" in the description.
Diagr. Two UMG 503 and one PLC at PROFIBUS DP
Protokolle
Standard-Protokoll
Protokollablauf
Der Protokollablauf unterscheidet sich in den Betriebsarten
 Daten an ein Gerät senden,  Daten von einem Gerät empfangen.
Daten an ein Gerät senden
Zeichenbedeutung Hex-Wert Datenrichtung
PC Gerät Protokollanfang (76) ---> Geräteadresse (00..FF) ---> Steuerbyte (45) ---> (Echo) <--­Anzahl der Datenbytes einschließlich Startadr. (03..0F) ---> (Echo) <--­Startadresse lsb (00..FF) ---> (Echo) <--­Startadresse msb (00..FF) ---> (Echo) <---
1. Datenbyte (00..FF) ---> (Echo) <---
2. Datenbyte (00..FF) ---> (Echo) <--­... ... n. Datenbyte (00..FF) ---> (Echo) <--­Falls alle Echos korrekt waren:
Echo o.k. (78) --->
wenn nicht:
Echofehler (7A) --->
Protokollende (79) <---
Daten von einem Gerät empfangen
Zeichenbedeutung Hex-Wert Datenrichtung
PC Gerät
GSD-Datei
PROFIBUS DP Master
PROFIBUS
DP Slave
PROFIBUS
DP Slave
SPS
UMG503UMG503
Page 73= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Serial interfaces
The UMG503 is available with the serial interfaces RS232, RS485 and Infrared. In the basical edition, at least one interface RS485 or RS232 is at your disposal. The interfaces can be used at the same time, even with different protocols. Please note, that not all combinations of interfaces and protocols are allowed.
UMG503 - RS485 - WAGO I/O
UMG503
RS232/RS485
Protocol 6 = Modbus RTU (Master)
Bus coupling (Slave)
WAGO I/O SYSTEM
UMG503 - RS485 - PLC
Protocol 5 = Profibus DP (Slave)
RS485
SPS
UMG503
UMG503
UMG503 - RS232- PC
Direct connection to PC via zero mo­dem cable.
The maximum distance between PC and UMG503 can be 5m at maximum.
Zero modem cable
RS232
RS232
UMG503
Protocol 2 = Modbus RTU (Slave)
PSWbasic or custo-
mer software
UMG503 - RS485/RS232 - PC
For the connection to PC an interface converter from RS485 to RS232 must be used. The maximum distance for RS485 is 1200m and for RS232 about 5m.
Interface converter
RS485/RS232
RS485
RS232
UMG503
RS232
RS485
PSWbasic or customer
software
Protocol 2 = Modbus RTU (Slave)
UMG503
UMG503 - Modem - PC
RS232
RS232
UMG503
Modem
RxD TxD on
PSWbasic
Protocol 5 = Modem
Modem
RxD TxD on
Page 74 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Tables
Overview
Table 1a Measured values, floating point format Table 1b Measured values, floating point format Table 2 Energy, floating point format Table 3a Time information for minimum and maximum values and system time Table 3b Time information for minimum and maximum values and summer/winter changeover Table 4 Averaging time of mean values Table 5 Internal control word Table 6a Measured values, integer format Table 6b Mean values, integer format Table 6c Maximum values, integer format Table 6d Minimum values, integer format Table 7 Energy, integer format Table 8 Scale of measured values, which are retrieved in integer format. Table 9 Inputs and outputs Table 10 EMAX peak values
Data formats
The data are available in the following formats:
char : 1 Byte (0 .. 255) word : 2 Byte (- 32 768 .. + 32 767) long : 4 Byte (- 2 147 483 648 .. + 2 147 483 647) float : 4 Byte (IEEE754) double: 8 Byte (IEEE754)
The sequence of the bytes is high before low byte.
Page 75= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Table 1a
Measured values in floating point format
Description Index Address(dez) r/w1)Type Unit Comment
DPV1 DPV0/MODB.
Current 64 1000 r meas. val.2)A L1, L2, L3 Voltage N-L 65 1012 r meas. val.2)V L1, L2, L3 Voltage L-L 66 1024 r meas. val.2)V L1-L2, L2-L3, L1-L3 Real power 67 1036 r meas. val.2)W Sign -=Supply, +=Consumption Apparent power 68 1048 r meas. val.2)VA L1, L2, L3 Reactive power 69 1060 r meas. val.2)var Sign -=cap, +=ind cos(phi) 70 1072 r meas. val.
2)
Sign -=cap, +=ind Frequency 71 1084 r meas. val.2)Hz L1, L2, L3 Real power, sum 72 1096 r sum
3)
W Sign -=Supply, +=Consumption
Apparent power, sum 1100 r sum
3)
VA
Reactive power, sum 1104 r sum
3)
var Sign -=cap, +=ind
cos(phi), sum 73 1108 r sum
3)
Sign -=cap, +=ind Total harmonic distortion _U Measured value 1112 r float[3] % L1, L2, L3 Maximum value 1115 r float[3] % L1, L2, L3 Total harmonic distortion _I Measured value 1118 r float[3] % L1, L2, L3
74 1120 Maximum value 1121 r float[3] % L1, L2, L3 Partial harmonics _U Maximum value 1124 r float[20][3] V Partial harmonics 1-20; L1, L2, L3
75 1132
.. ..
79 1180 Partial harmonics _U Measured value 1184 r float[20][3] V Partial harmonics 1-20; L1, L2, L3
80 1192
.. ..
84 1240 Partial harmonic _I Maximum value 1244 r float[20][3] A Partial harmonics 1-20; L1, L2, L3
85 1252
.. ..
89 1300 Partial harmonic _I Measured value 1304 r float[20][3] A Partial harmonic 1-20; L1, L2, L3
90 1312
.. ..
94 1360 Real power EMAX 1365 r float W Sign -=Supply, +=Consumption
95 1372
96 1384
1)
r/w = read/write
2)
measured value {float: measured value[L1-L3], mean value[L1-L3], lowest value[L1-L3], peak value[L1-L3]}
3)
sum {float: measured value, mean value, lowest value, peak value}
Page 76 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Table 1b
Measured values in floating point format
Description Index Address(dez) r/w1)Type Unit Comment
DPV1 DPV0/MODB.
Total harmonic distortion _U Mean value 1390 r float[3] % L1, L2, L3 Total harmonic distortion _I Mean value 1393 r float[3] % L1, L2, L3
97 1396 Partial harmonics _U Minimum value 1400 r float[20][3] V Partial harmonic 1-20; L1, L2, L3
98 1408
.. ..
102 1456 Partial harmonics _I Minimum value 1460 r float[20][3] A Partial harmonic 1-20; L1, L2, L3
103 1468
.. ..
107 1516 Partial harmonics _U Mean value 1520 r float[20][3] V Partial harmonic 1-20; L1, L2, L3
108 1528
.. ..
112 1576 Partial harmonics _I Mean value 1580 r float[20][3] A Partial harmonic 1-20; L1, L2, L3
113 1588
.. ..
117 1636 Total harmonic distortion _U Minimum value 1640 r float[3] % L1, L2, L3
Total harmonic distortion _I Minimum value 1643 r float[3] % L1, L2, L3 Current, N 1646 r float A
118 1648
119 1660 Maximum of current mean value 1663 r float[3] A L1, L2, L3
Page 77= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Table 2
Energy in floating point format
Description Index Address(dez) r/w1)Type Unit Comment
DPV1 DPV0/MODB.
Real energy, Consumption 220 2000 r double[4] Wh Energy, Tariff1, Tariff2, Tariff3, Tariff4
Reactive energy, inductive 221 2010 r double[4] varh Energy, Tariff1, Tariff2, Tariff3, Tariff4
Reactive energy, capacitive 222 2020 r double[4] varh Energy, Tariff1, Tariff2, Tariff3, Tariff4
Real energy, supply 223 2030 r double[4] Wh Energy, Tariff1, Tariff2, Tariff3, Tariff4 Reactive energy without rev. running stop 224 2040 r double[4] varh Energy, Tariff1, Tariff2, Tariff3, Tariff4 Real energy without rev. running stop 225 2050 r double[4] Wh Energy, Tariff1, Tariff2, Tariff3, Tariff4
Page 78 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Table 3a
Time information for minimum and maximum values and system time
Description Index Address(dez) Type Comment
DPV1 DPV0/MODB.
System time 230 3000 char System time Current L1, L2, L3 128 3001 char[2][3] Min. value, Max. value; L1, L2, L3 Voltage N-L 129 3007 char[2][3] Min. value, Max. value; L1, L2, L3 Voltage L-L 130 3013 char[2][3] Min. value, Max. value; L1, L2, L3 Real power 131 3019 char[2][3] Min. value, Max. value; L1, L2, L3 Apparent power 132 3025 char[2][3] Min. value, Max. value; L1, L2, L3 Reactive power 133 3031 char[2][3] Min. value, Max. value; L1, L2, L3 cos(phi) 134 3037 char[2][3] Min. value, Max. value; L1, L2, L3 Frequency 135 3043 char[2][3] Min. value, Max. value; L1, L2, L3 Real power, sum 136 3049 char[2] Min. value, Max. value; Apparent power, sum 3051 char[2] Min. value, Max. value; Reactive power, sum 3053 char[2] Min. value, Max. value; cos(phi), sum 137 3055 char[2] Min. value, Max. value; Total harmonic distortion _U Maximum value 3057 char[3] L1, L2, L3 Total harmonic distortion _I Maximum value 3060 char[3] L1, L2, L3
138 3061 Partial harmonics _U Maximum value 3063 char[20][3] Partial harmonics 1-20; L1, L2, L3
139 3067
.. ..
148 3121 Partial harmonics _I Maximum value 3123 char[20][3] Partial harmonics 1-20; L1, L2, L3
149 3127
.. ..
158 3181 free 159 3187 free 3188 free 3189 Real energy, starting time consumption 3190 char Starting time of energy measurement Reactive energy, starting time inductive 3191 char Starting time of energy measurement Reactive energy, starting time capacitive 3192 char Starting time of energy measurement Real energy, starting time supply 160 3193 char Starting time of energy measurement Reactive energy, starting time without reverse running stop 3194 char Starting time of energy measurement Real energy, starting time without reverse running stop 3195 char Starting time of energy measurement free 3196
.. ..
free 3198 free 161 3199
Format of time information: {char: year, month, day, hour, minute, second} Year: 00 .. 99 = 2000 .. 2099
Page 79= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Table 3b
Time information for minimum and maximum values and system time
Description Index Address
(dez)
Type Comment
DPV1 DPV0/MODB.
free 162 3205 Partial harmonics _U Minimum value 3210 char[20][3] Partial harmonics 1-20; L1, L2, L3
163 3211
.. ..
172 3265
Partial harmonics _U Minimum value 3270 char[20][3] Partial harmonic 1-20; L1, L2, L3
173 3271
.. ..
182 3325 free 183 3331 free 3332 Total harmonic distortion _I Minimum value 3333 char[3] L1, L2, L3 Current, N 3336 char[2] Minimum value, Maximum value
184 3337 Real power EMAX 3338 char[2] Minimum value, maximum value Current mean value (L1, L2, L3) 3340 char[2][3] Min. and maximum value; L1, L2, L3 Time changeover 3343 char[2] Summer time, winter time
Format of time information: {char: Year, month, day, hours, minute, second} Year: 00 .. 99 = 2000 .. 2099
Page 80 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Table 4
Averaging times of the mean values.
The averaging times cannot be retrieved via Profibus DP V1.
Description Index Address(dez) Type Comment
DPV1 DPV0/MODB.
Current 4000 char[3] L1, L2, L3 Voltage N-L 4003 char[3] L1, L2, L3 Voltage L-L 4006 char[3] L1-L2, L2-L3, L1-L3 Real power 4009 char[3] L1, L2, L3 Apparent power 4012 char[3] L1, L2, L3 Reactive power 4015 char[3] L1, L2, L3 cos(phi) 4018 char[3] L1, L2, L3 Frequency 4021 char[3] L1, L2, L3 Real power, sum 4024 char Real power EMAX 4156 char 5=5, 6=10, 7=15, 8=30, 9=60Minutes Apparent power, sum 4025 char Reactive power, sum 4026 char cos(phi), sum 4027 char Current, N 4028 char Total harmonic distortion _U 4150 char[3] L1, L2, L3 Total harmonic distortion _I 4153 char[3] L1, L2, L3 Partial harmonics _U 4030 char[20][3] Partial harmonics 1-20; L1, L2, L3 Partial harmonics _I 4090 char[20][3] Partial harmonics 1-20; L1, L2, L3
1)
r/w = read/write
Table 5
Internal control word
Description Address(dez) r/w1)Format Comment
Internal control word 5000 r/w char[17] Byte 0 Only internal use.
Byte 1 Only internal use.
Byte 2 Delete minimum value. (Byte > 0) Byte 3 Delete maximum value. (Byte > 0)
Byte 4 Only internal use. Byte 5 Only internal use.
Byte 6 Delete real energy. (Byte > 0) Byte 7 Delete reactive energy. (Byte > 0)
Byte 8 Only internal use. Byte 9 Only internal use. Byte 10 Only internal use. Byte 11 Only internal use. Byte 12 Only internal use. Byte 13 Only internal use. Byte 14 Only internal use. Byte 15 Only internal use. Byte 16 Only internal use.
To change a byte of the "internal control word", the "internal control word" must be read, and the changed word must be written back to address 5000.
Attention!
If the bytes with the comment "Only internal use" are changed, this may lead to a faulty operation of UMG 503!
Format of time information: {char: Year, month, day, hour, minute, second} Year: 00 .. 99 = 2000 .. 2099
Page 81= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Table 6a
Measured values in integer format
Measured values Index Address(dez) r/w1) Format Unit Comment
DPV1 DPV0/MODB.
Current 4 8000 r word[3] A L1, L2, L3 Voltage 8003 r word[3] V N-L1, N-L2, N-L3 Voltage 8006 r word[3] V L1-L2, L2-L3, L1-L3 Real power
2)
8009 r word[3] W L1, L2, L3 Apparent power 5 8012 r word[3] VA L1, L2, L3 Reactive power
3)
8015 r word[3] var L1, L2, L3 cos(phi)
3)
8018 r word[3] L1, L2, L3 Frequency 8021 r word[3] Hz L1, L2, L3 Real power, sum
2)
6 8024 r word W Apparent power, sum 8025 r word VA Reactive power, sum
3)
8026 r word var
cos(phi), sum
3)
8027 r word Current, N 8028 r word A Current in neutral conductor Partial harmonics _U 8030 r word[20][3] V Partial harm. 1-20; L1, L2, L3
7 8036
.. ..
11 8084
Partial harmonics _I 8090 r word[20][3] A Partial harm. 1-20; L1, L2, L3
12 8096
.. ..
16 8144
Total harmonic distortion_U 8150 r word[3]
0
/00 L1, L2, L3
Total harmonic distortion _I 8153 r word[3]
0
/00 L1, L2, L3
Real power EMAX, sum
2)
17 8156 r word W
Table 6b
Mean values in integer format
Mean values Index Address(dez) r/w1)Format Unit Comment Current 8157 r word[3] A L1, L2, L3 Voltage 8160 r word[3] V N-L1, N-L2, N-L3 Voltage 8163 r word[3] V L1-L2, L2-L3, L1-L3 Real power
2)
8166 r word[3] W L1, L2, L3
18 8168 Apparent power 8169 r word[3] VA L1, L2, L3 Reactive power
3)
8172 r word[3] var L1, L2, L3
cos(phi)
3)
8175 r word[3] L1, L2, L3
Frequency 8178 r word[3] Hz L1, L2, L3
19 8180 Real power, sum
2)
8181 r word W Apparent power, sum 8182 r word VA Reactive power, sum
3)
8183 r word var cos(phi), sum
3)
8184 r word Current, N 8185 r word A Current in neutral conductor Partial harmonics _U 8187 r word[20][3] V Partial harm. -20; L1, L2, L3
20 8192
.. ..
24 8240
Partial harmonics _I 8247 r word[20][3] A Partial harm. 1-20; L1, L2, L3
25 8252
.. ..
29 8300
Total harmonic distortion _U 8307 r word[3]
0
/00 L1, L2, L3
Total harmonic distortion _I 8310 r word[3]
0
/00 L1, L2, L3
1)
r/w = read/write
2)
Sign - = Supply, + = Consumption
3)
Sign - = cap, + = ind
Page 82 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Table 6c
Maximum values in integer format
Maximum values Index Address(dez) r/w1) Format Unit Comment
Current 8314 r word[3] A L1, L2, L3 Voltage 8317 r word[3] V N-L1, N-L2, N-L3 Voltage 8320 r word[3] V L1-L2, L2-L3, L1-L3 Real power
2)
8323 r word[3] W L1, L2, L3 Apparent power 8326 r word[3] VA L1, L2, L3 Reactive power
3)
8329 r word[3] var L1, L2, L3 cos(phi)
3)
8332 r word[3] L1, L2, L3 Frequency 8335 r word[3] Hz L1, L2, L3 Real power, sum
2)
8338 r word W Apparent power, sum 8339 r word VA Reactive power, sum
3)
8340 r word var cos(phi), sum
3)
8341 r word Current, N 8342 r word A Current in neutral conductor Partial harmonics _U 8344 r word[20][3] V Partial harm. 1-20; L1, L2, L3 Partial harmonics _I 8404 r word[20][3] A Partial harm. 1-20; L1, L2, L3 Total harmonic distortion _U 8464 r word[3]
0
/00 L1, L2, L3
Total harmonic distortion _I 8467 r word[3]
0
/00 L1, L2, L3
Real power EMAX, sum
2)
8470 r word W Current mean value 8663 r word[3] A L1, L2, L3
Table 6d
Minimum values in integer format
Minimum values Index Address(dez) r/w1) Format Unit Comment
Current 8471 r word[3] A L1, L2, L3 Voltage 8474 r word[3] V N-L1, N-L2, N-L3 Voltage 8477 r word[3] V L1-L2, L2-L3, L1-L3 Real power
2)
8480 r word[3] W L1, L2, L3 Apparent power 8483 r word[3] VA L1, L2, L3 Reactive power
3)
8486 r word[3] var L1, L2, L3 cos(phi)
3)
8489 r word[3] L1, L2, L3 Frequency 8492 r word[3] Hz L1, L2, L3 Real power, sum
2)
8495 r word W Apparent power, sum 8496 r word VA Reactive power, sum
3)
8497 r word var cos(phi), sum
3)
8498 r word Current, N 8499 r word A Current in neutral conductor Partial harmonics _U 8501 r word[20][3] V Partial harm. 1-20; L1, L2, L3 Partial harmonics _I 8561 r word[20][3] A Partial harm. 1-20; L1, L2, L3 Total harmonic distortion _U 8621 r word[3]
0
/00 L1, L2, L3
Total harmonic distortion _I 8624 r word[3]
0
/00 L1, L2, L3
Real power EMAX, sum
2)
8627 r word W
1)
r/w = read/write
2)
Sign - = Supply, + = Consumption
3)
Sign - = cap, + = ind
Page 83= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Table 7
Energy in integer format
Energy Index Address(dez) r/w1)Format Unit Comment
Real energy, consumption 9000 r long Wh Scale see address 9102
Real energy, supply 9001 r long Wh Scale see address 9102
Real energy without rev. running stop 9002 r long Wh Scale see address 9102
Reactive energy, capacitive 9003 r long varh Scale see address 9102
Reactive energy, inductive 9004 r long varh Scale see address 9102 React. energy without rev. running stop 9005 r long varh Scale see address 9102
1) r/w = read/write
Page 84 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
In UMG503 almost all measured values are available in floating point format (Table 2). For the transmission of measured values, the floating format values are changed into integer formats by UMG 503, such as char, int and word (Table 4). In order not to lose a digit after decimal point, the transmitted value is scaled. The transmission value is calculated as follows:
Measured value = Transmission value * Factor
The scales of the measured values are calculated from UMG 503 out of current and voltage transformer ratio. Here the minimum definition of the transmitted value of 0,1% is strived for.
The scales of the UMG 503 can be retrieved under the following addresses:
Example: Scale
Transmitted value UMG 503 = 2301 Programmed scale = -1 Which voltage is measured by the UMG 503?
From the scale table, you can read the factor =/10 for scale=-1:
Measured value = Transmitted value * Factor Measured value = 2301 * 1/10 Measured value = 230,1V
The measured voltage is 230,1V.
Measured values Index Address
dez
r/w
1)
Format Possible scale
Current 200 9100 r word -3 .. 6 Voltage 201 9101 r word -3 .. 6 Power 202 9102 r word -3 .. 6 cos(phi) 203 9103 r word -3 Frequency 204 9104 r word -2 THD 205 9105 r word -3
10 scale factors are at your disposal: Scale Factor
-3 /1000
-2 /100
-1 /10 0* 1 1* 10 2 * 100 3 * 1 000 4 * 10 000 5 * 100 000 6 * 1000 000
The scale of energy is fixed by the scale of power
1)
r/w = read/write
Table 8
Scale of measured values, which can be retrieved in integer format.
Page 85= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Table 9
In and outputs
A remote Bit is assigned to each in- or output, that can be controlled externally. If this remote Bit=0, the in- or output is controlled by the UMG 503 only. If the remote Bit=1, the in- or output is controlled externally.
Description Address Format r/w
1)
Comment
Inputs 0048 word[3]
r/w Bit 0 Change over summer time (Winter=0, Summer=1) r/w Bit 1 Remote, change over summer time r/w Bit 2 Relay output 2 r/w Bit 3 Remote Bit, Relay output 2 r/w Bit 4 Relay output 1 r/w Bit 5 Remote Bit, Relay output 1
Bit 6..15 Free
r/w Bit 0 Remote Bit, Tariffs r Bit 1 Synchronize of the internal clock
Bit 2..3 Free r/w Bit 4 Reset of real power EMAX r/w Bit 5 Remote Bit, Reset of real power EMAX
Bit 6..15 Free
r Bit 0..1 Tariff real energy consumption r Bit 2..3 Tariff reactive energy Ind. r Bit 4..5 Tariff reactive energy cap.
Bit 6..15 Free
Outputs 0032 word[3]
r Bit 0 Measuring range of voltage in L1 exceeded r Bit 1 Measuring range of voltage in L2 exceeded r Bit 2 Measuring range of voltage in L3 exceeded r Bit 3 Measuring range of voltage in L1 underscored r Bit 4 Measuring range of voltage in L2 underscored r Bit 5 Measuring range of voltage in L3 underscored
Bit 6..15 Free
r Bit 0 Measuring range of current in L1 exceeded r Bit 1 Measuring range of current in L2 exceeded r Bit 2 Measuring range of current in L3 exceeded r Bit 3 Measuring range of current in L1 underscored r Bit 4 Measuring range of current in L2 underscored r Bit 5 Measuring range of current in L3 underscored
Bit 6..15 Free
r Bit 0..2 Watchdogcounter r Bit 3 Auxiliary input
Bit 4..15 Free
1)
r/w = read/write
Page 86 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Table 10
EMAX-Peak values
Description Address(dez) r/w1)Type Comment
Real power EMAX
Peak value 16000 r float [Tariff] [Month] Measured value in Watt
Date
Year 16500 r char [Month] The month of the year, in which... Day 16600 r char [Tariff] [Monat] The day of the month, in which the
peak value appeared
Time
Hour 16700 r char [Tariff] [Month] Minute 16800 r char [Tariff] [Month]
Year = 0 .. 99 00 .. 99 = 2000 .. 2099 Tariff = 0 .. 4 0 = T00, 1 = T01, .. Month = 0 .. 11 0 = January, 1 = February, ..
For each month, a peak value is saved for each tariff. After one year, this peak value will be overwritten.
1)
r/w = read/write
Page 87= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Page 88 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
PSWbasic
The programming and reading out software PSWbasic always belongs to the extent of delivery of the UMG 503. The software can be installed on PCs with the operating systems WIN98,WIN98ME, NT4.0 or WIN2000, and offers the following possibilities:
- Configuration of the measured value indications,
- Read out the ring buffer,
- Create a GSD file,
- Configure the UMG503.
Functions
Configure measured value indications
Only a part of all possible measured values is indicated in the producers presettings. This part of the program makes possible:
- Read out the actual configuration of the measured value indications of the UMG 503.
- Load the configuration of the measured value indications from PC.
- Destine the kind and sequence of the measured values.
- Transmit the configuration of the measured value indications to the UMG 503.
- Save the configuration of the measured value indications on PC.
Memory
The memory of the UMG 503 is divided into three areas:
the event memory, the minimum and maximum memory and
the ring buffer. Only the contents of the minimum and maximum memo­ry can be read out directly at the UMG 503. The event memory and the ring buffer must be read out by PC.
Required hard and software
Software
A PC with Windows® 98/2000/NT4 is required for running the Software PSWbasic. Please note, that the used Windows version should be the latest issue. When this manual was printed, the following issues were actual:
- Windows® 98
- Windows® 98ME
- Windows® NT4.0 mit Service-Pack3
- Windows® 2000 The service packs contain corrections of Windows faults. They can be obtained from Microsoft or downloaded from Microsoft™-Side in the internet.
Hardware
- PC Pentium 100MHz or higher
- 16 MByte RAM(for Windos® NT 32MByte)
- About 5MB free memory on harddisk for the program
PSWbasic
- Color monitor with a solution of 640x480 or 800x600 dots and 265 colours.
- 1MB PCI graphic board.
- The PSWbasic must be installed on harddisk.
- CD-ROM drive.
- Parallel printer interface.
- Modem and/or serial interface (Com1/2..).
Page 89= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Create GSD file
Devices with PROFIBUS protocol need a GSD file. The GSD file is a f ile which is specific for the device, in which the transmission parameters, the kind of measure­ment data are agreed between the PROFIBUS master and the PROFIBUS Slave. With this module, measured values and inputs and out­puts can be selected for transmission to the PLC. As a result of the configuration, a GSD f ile is created for the PLC and programming data are generated for the UMG 503. The programming data for the UMG 503 are deposited as a text at the beginning of the GSD file. The programming data must be entered in the UMG 503 under "input buffer", "output buffer" und "User-Parame­ter-buffer".
Configuration of UMG 503
A simple configuration of the UMG 503 can be carried out directly at the device via the three keys and display. A configuration of the UMG 503 from PC is possible with the option "Configuration of UMG 503". Configurations can be saved and printed out at PC. Additionally, an expanded configuration of the ring buf­fer is possible. The selection of six memory areas makes possible a better usage of the ring buffer. Each memory area can be assigned to one mean value. The recording is done either within or out of the destined area, which is limited by two selectable limits. Only those mean values are saved in the ring buffer, which are within the memory area.
Page 90 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
WAGO I/O SYSTEM
A simple expansion of the inputs and outputs of the UMG 503 is possible with the WAGO I/O SYSTEM. The UMG 503 is connected to the bus coupling via an interface cable. The Modbus RTU protocol is used for transmission of data. Function clamps such as analogue outputs, and digital inputs and outputs can be connected to the bus coupling.
Function clamps
Function clamps, which can be used with the WAGO Modbus coupling: Digital inputs
750-400 2-chanel digital input 24V; 3,0ms
750-405 2-chanel digital input 230V AC
750-415 4-chanel digital input 24V AC/DC Digital outputs
750-501 2 outputs, 24V, 0,5A
750-502 2 outputs, 24V, 2A
750-504 4 outputs,
750-516 4 outputs, 24V
750-519 4 outputs, 5V
750-509 2 outputs, 230V, Solid State
750-512 2 NO, Relay, potential bound.
750-513 2 NO, Relay, potential free
750-514 2 Change over switch, Relay, po­tential free
750-517 2 Change over switch, Relay,
potential free
Analogue outputs
750-550 2-chanel analogue output 0-10V
750-552 2-chanel analogue output 0-20mA
750-554 2-chanel analogue output 4-20mA
750-556 2-chanel analogue output +-10V
As the Siemens data format is not supported by the UMG 503, the function clamps
750-580 0-10V and
750-584 4-20mA cannot be used.
Attention!
Please not the corresponding installation instructions for the WAGO I/O SYSTEM.
Installation instructions
The connection of the UMG 503 to the bus coupling can be carried out via RS232 or RS485 interface. The WAGO Bus coupling has always the address 1. For operation with the WAGO bus coupling, protocol number "06" must be set at the UMG 503 (Modbus RTU Master). Please note, that protocol "06" cannot be operated on both interfaces of the UMG 503 at the same time. All existing analogue function modules must be pro­grammed at the UMG 503. Only the last clamp of the analogue module does not have to be programmed. The analogue clamps must be plugged to the bus coupling at first, and the digital clamps afterwards.
UMG503 (Master)
Bus coupling (Slave)
Function terminals
Interface cable
WAGO I/O SYSTEM
Page 91= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Description Transmission Possible
mode Baud rates
750-312 RS485 9600, 19200 750-315 RS485 9600, 19200, 38400, 115200 750-314 RS232 9600, 19200 750-316 RS232 9600, 19200, 38400
If the UMG 503 is connected to the bus coupling via RS232 interface, a "1 to 1 cable" must be used. Connections via RS485 interface are carried out according to the diagram below.
Bus coupling
The UMG503 can communicate with maximal
6 analogue outputs, 6 digital outputs and
3 digital inputs via WAGO Bus coupling at maximum. The following bus couplings can operate with UMG503 with the same transmission mode and Modbus RTU protocol.
WAGO-Bus coupling
RS485 interface (2-wire)
UMG503 RS485 Interface (2-wire)
Diagr: Connection between UMG 503 and WAGO-Bus coupling via RS485 (2-wire)
1 2 3 TXD/RXD 4 5 GND
6 7
8 TXD/RXD inverted 9
Schnittstellen­kabel
UMG 503
Page 92 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Indicating range and accuracy
Quantity Indicating range Measuring range for Measuring
Scale factor=1 accuracy
Voltage
L-N 0,0V .. 999,9 MV 50 .. 500 V ±0,2% rng
L-L 0,0V .. 999,9 MV 80 .. 870 V ±0,2% rng Current 0,000 .. 9999 A 0,005 .. 5 A ±0,2% rng Current in N 0,000 .. 9999 A 0,060 .. 15 A ±0,6% rng Frequency (of voltage) 45,00 .. 65,00 Hz 45,00 .. 65,00 Hz ±0,1% rng Power
Real power, consump. 0,00W .. 9999 MW 0,05 W .. 2,5 kW ±0,5% rng
Real power, supply -0,00W .. -999 MW 0,05 W .. 2,5 kW ±0,5% rng
Apparent power 0,00VA .. 9999 MVA 0,05 VA .. 2,5 kVA ±0,5% rng
Reactive power 0,00VAr.. 9999 MVAr 0,05 kvar .. 2,5 kvar ±0,5% rng Energy (max. 10 digits)
Real energy,
without rev. running stop 0,0 Wh .. 9999 GWh 0,05 Ws .. 9999 MWh
1)
Real energy, consump. 0,0 Wh .. 9999 GWh 0,05 Ws .. 9999 MWh
1)
Real energy, supply 0,0 Wh .. 9999 GWh 0,05 Ws .. 9999 MWh
1)
Reactive energy 0,0 vars .. 9999 Gvarh 0,05 vars .. 9999 Mvarh
1)
Total harmonic content THD(f)
Current 0,0 .. 100 % 0,0 .. 100 % ±0,5% rng
Voltage 0,0 .. 100 % 0,0 .. 100 % ±0,5% rng Partial harmonic content
Current (1. - 20.) 0,000 .. 9999 A 0,005 A .. 5A (1A) ±0,5% rng
Voltage (1. - 20.) 0,0V .. 99,99 kV 0,000 V .. 9999 V ±0,5% rng cos(Phi) 0,00ind .. 1,00 .. 0,00cap. 0,00ind .. 1,00 .. 0,00cap.
2)
The specifications presuppose the following conditions:
Yearly calibration
Warm up 10 minutes
Ambient temperature of 18 .. 28°C. In the range of -10..18°C and 28..55°C an additional error of ±0,2% Mv per K must be considered.
Used abbreviations: rng = of measuring range rdg = of measured value ind = inductive kap = capacitive
1)
The measuring accuracy corresponds to the measuring accuracy of power.
2)
If the measured apparent power in the range of 1% .. 100% of measuring range, cos(phi) is displayed with an
accuracy of ±1% of 1.000.
Attention!
The inaccuracy of the compressed memory data
is max. ±0,4% rng.
Page 93= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Technical Data
Ambient conditions
Overvoltage class : CATIII Pollution degree : 2 Operating temperature : -10°C .. +50°C Storage temperature : -20°C .. +60°C humidity class : 15% to 95%
(without dew)
Operating altitude : 0 .. 2000m over NN
Auxiliary voltage Uh : see type plate
Range 1 (Standard) : 85 .. 265V AC
80 .. 370V DC
Range 2 (Option) : 40 .. 115V AC
55 .. 165V DC
Range 3 (Option) : 15 .. 55V AC
20 .. 80V DC Fuse : 4A up to 10 A Power consumption : max. 9VA
Measuring inputs
Rated pulse voltage : 6kV Signal frequency : 45Hz .. 1200Hz
Current measurement
Power consumption : ca. 0,2 VA Rated current for ../5A(1A) : 5A(1A)
Min. working current : 5mA Limiting current : 5,3A (sinus shape) Overload : 180A for 2 sec.
Voltage measurement
max. 500VAC against ground Power consumption : ca. 0,1 VA Maximum prefuse : M2A Measuring range L-N : 50 .. 500V AC
2,3 .. 23V AC (option)
Measuring range L-L : 90 .. 870V AC
4 .. 40V AC (option)
Frequency of fundamental : 45Hz .. 65Hz
Protection class
Front :IP50 acc. IEC60529 Front with seal (Option) :IP65 acc. IEC60529 Back side :IP20 acc. IEC60529 Plug screw connection :IP20 acc. IEC60529
Measurement
Mode : True (RMS) Measuring rate : 2 measurements/sec. Actualization
Display : 1 time per second Analogue output : < 500ms Relay outputs : < 500ms
Auxiliary input (Option)
Current consumption : ca. 2,5mA .. 10mA
Analogue output (Option)
Definition : 12Bit Load : max. 500Ohm External auxiliary voltage :20V.. 27VDC/50mA Reaction time : 1,5 seconds
Pulse output (Option)
S0 interface according to DIN 43864 Switching frequency : max. 10Hz Switching current : max. 30mA External auxiliary voltage : 20V .. 30VDC
Relay outputs (Option)
Switching voltage : max. 250VAC Switching power : max. 1000W Reaction time : 500ms
Weight : 1kg Location : any Operating height : 0 .. 2000m over NN Accuracy of the internal clock : +- 1 minute/month
Interference resistance (industrial areas)
: EN55082-2:1995 : IEC61000-4-3,10V/m : IEC61000-4-4, 2kV : IEC61000-4-2, 8kV
Spurious radiation (residential areas)
: EN55011 10.1997
Safety guidelines : EN61010-1:2001
: IEC61010-1:2001
Protection class : I (device with protective wire)
Testing voltages Voltage measuring inputs against Housing, RS232 and RS485 : 3250V AC Relay outputs, auxiliary input and current measuring inputs against Housing, RS232 and RS485 : 2200V AC
Page 94 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
The grey marked connections are available as options. All dimensions are given in mm.
Design for panel mounting
Back side
Side view
Design for DIN Rail Mounting (Option)
Back side
Diagr. Feeding wires for a DIN Rail mounted UMG 503
Side view
Page 95= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Connection example
The grey marked terminals are not available for all types of UMG 503.
RS485
RS232
Relaisausgänge
Relay Outputs
K1 K2
Hilfsein-
gang
Auxiliary
Input
Hilfsspan-
nung
Auxiliary
Voltage
Messung
Measurement
L-L 90 .. 870VAC
L-N 50..500VAC
0,005A .. 5A
4 - DTR
3 - TXD
7 - RTS
2 - RXD
8 - CTS
5 - GND
27 26 25 24 23 22 21 20 19 18 14 15 16 17 10 11 12 13
max. 5m
Aus
Off
1 2 3 4
L1
PE
N
L3
L2
230/400V
50Hz
../5(1)A
../5(1)A
../5(1)A
k l
k l
k l
4-
10A
2A
L1 L2 L3 N
L1 N
PE
Verbraucher
Consumer
Ohne Abschlusswiderstand
Without Line Terminator
Mit Abschlusswiderstand
With Line Terminator
max.
1000m
RS485
RS232
Com
PC
Aus
Off
Ein
On
Ein
On
A B
Impuls-
ausgang
Pulse
Output
Ausgang
Output
0/4 .. 20mA
5 6 7
8 9
10160205
1,5k
24V
20..30VDC
+5V GND
UMG503
Page 96 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Brief instructions
Select programming menu. Select current transformer. Select number. Change number. Move decimal point. Save and measured value indication.
Primary current Secondary current
Primary voltage Secondary voltage
Select programming menu Confirm selection. Select voltage transformer. Select number. Change number. Move decimal point. Save and measured value indication.
2 x 1 x
2 Sek.
2 x 1 x 1 x
2 Sek.
Current transformer
Votage transformer
V
V
VT
CONF
A
A
CT
CONF
Loading...