Janitza electronics GmbH
Vor dem Polstück 1
D-35633 Lahnau
Support tel. 0049 6441 9642-22
Fax 0049 6441 9642-30
E-mail: info@janitza.com
Doc no. 1.049.012.0.p
Internet: http://www.janitza.com
ProData 2
Operating instructions and technical data
www.janitza.com
ProData II
Table of contents
General 3
Inspection on receipt 6
Scope of delivery of ProData 2 7
Available accessories 7
Product description 8
Proper use 8
ProData 2 features 9
GridVis network analysis software 10
Connection variants 12
Installation 14
Position of installation 14
Installation 14
Supply voltage 14
RS485 interface 16
Ethernet interface 19
Digital outputs 20
Digital inputs 22
Temperature measurement input 25
Device address (RS485) 26
DIP switch S1 27
Service button S2 27
LED device status 27
Configuration and commissioning 28
Connecting the supply voltage 28
RS485 interface 28
Digital inputs 30
Service 42
Device calibration 42
Calibration 42
Battery 43
Replacing the battery 44
Firmware update 45
Procedure in the event of faults 46
Technical data 48
Dimension diagrams 52
Declaration of conformity 54
Connection example 56
General
ProData II
Copyright
This operating manual is subject to the legal requirements
for copyright protection and may not be, either in whole
or in part, photocopied, reprinted, or reproduced by
mechanical or electronic means, or in any other manner
be duplicated or redistributed without the legally binding,
written agreement of
Janitza electronics GmbH, Vor dem Polstück 1,
D 35633 Lahnau, Germany.
Trademarks
All trademarks and their resulting rights belong
to the respective holders of these rights.
Disclaimer
Janitza electronics GmbH takes no responsibility
for errors or defects within this operating manual and
takes no responsibility for keeping the contents of this
operating manual up to date.
Comments on the operating manual
We welcome your comments. In the event that anything
in this operating manual seems unclear, please let us
know and send us an EMAIL at: info@janitza.de
Meaning of the symbols
The following pictograms are used in this manual:
Dangerous voltage!
c
m
Danger to life or risk of serious injury.
Disconnect the system and device from
the power supply before beginning work.
Caution!
Please follow the documentation. This
symbol warns of possible dangers that can
arise during installation, commissioning
and use.
Note!
C
3
ProData II
Instructions for use
Please read the operating manual included in the delivery
as well as all other publications that must be referred
to for working with this product (in particular for
the installation, operation or maintenance).
Follow all safety regulations and warning information.
If you do not follow the information, it can result in bodily
injury and/or damage to the product.
Any unauthorised changes or use of this device, which
go beyond the mechanical, electrical or otherwise stated
operating limitations, can result in bodily injury or/and
damage to the product.
Any such unauthorised changes constitute "misuse"
and/or "negligence" in terms of the warranty for
the product and, therefore, invalidate the warranty for
covering any potential damage that result.
This device is to be operated and maintained exclusively
by specialised personnel.
Specialised personnel are persons who, based on their
respective training and experience, are qualified to
recognise risks and prevent potential dangers that can be
caused by the operation or maintenance of the device.
4
Additional legal and safety regulations required for
the respective application are to be followed when using
the device.
If the device is not operated according
c
m
m
to the operating manual, protection is
no longer ensured and hazards can
be presented by the device.
Conductors made from single wires must
be fitted with wire-end ferrules.
Only pluggable screw terminals with
the same number of poles and the same
type of construction are permitted to
be connected together.
Concerning these operating instructions
These operating instructions are part of the product.
• Read the operating instructions before using
the device.
• Keep the operating instructions throughout the entire
service life of the product and have them readily
available for reference.
• Pass the operating instructions on to each subsequent
owner or user of the product.
ProData II
C
All screw-type terminals included in
the scope of delivery are attached
to the device.
5
ProData II
Inspection on receipt
The prerequisites of faultless, safe operation of this
device are proper transport and proper storage, setup and assembly, as well as careful operation and
maintenance. If it can be assumed that risk-free operation
is no longer possible, the unit must be immediately put
out of operation and secured against being put back into
operation again.
Packing and unpacking must be carried out with
customary care without the use of force and only using
suitable tools. The devices should be visually checked
for flawless mechanical condition.
It can be assumed that risk-free operation is no longer
possible if the device, for example,
• has visible damage,
• no longer works despite being connected to the mains
power supply,
• has been exposed to prolonged adverse conditions
(e.g. storage outside the permissible climate
limits without being adapted to the room climate,
condensation, etc.) or rough handling during
transportation (e.g. falling from a height, even if there
is no visible external damage, etc.)
• Please check the delivered items for completeness
before you start installing the device.
108.01.505Patch cable 2 m, coiled, grey (ProData/switch connection)
Available accessories
Part no.Description
21.01.058Battery 3 V, TYPE CR2032 (approved in acc. with UL1642)
52.24.111S0 module for a group of S0 inputs, equipped with 1.3 kOhm resistors
ProData II
7
ProData II
Product description
Proper use
The ProData 2 is designed for fixed installation (mounting
rail assembly) in low voltage switchgear and is suitable
for recording and saving counter values and process
data.
The data can be used to evaluate the energy consumption
and operating hours, or to monitor switching states and
faults in buildings, production facilities, etc.
The auxiliary voltage, the digital inputs, the interfaces,
etc. are connected via intrinsically safe plug-in terminals
and via an Ethernet plug.
8
ProData 2 features
• 15 digital/pulse inputs
• 3 digital outputs, switchable via Modbus, weekly timer,
boundary value and temperature monitoring
• Temperature measurement input
• Ethernet interface (Modbus TCP)
• RS485 (Modbus RTU, slave, up to 115 kbps)
• 32 MB flash memory (29 MB usable for recordings)
• Assembly on mounting rails (35 mm)
• Connection via pluggable screw terminals
• Clock and battery function
• Weekly timer
• Threshold value monitoring
• Modbus gateway functionality
*1
• Working temperature range -40 °C .. +55 °C
• Saving minimum and maximum values (with time stamp)
• Configurable records, can be read out via RS485 and Ethernet
*1
Use as a Modbus RTU slave is not possible in this mode. The ProData 2 can only forward queries to a Modbus slave device;
it cannot query Modbus slave devices independently.
ProData II
9
ProData II
Parameterisation
The parameterisation of all device functions takes place
via the RS485 serial interface or via Ethernet and with
the GridVis programming software.
The Modbus protocol can be used to change and
retrieve data using the Modbus address list (available on
the Internet or the enclosed CD).
Additional components that are not
C
included in the scope of deliverables will be
required for parametrisation via the RS485
interface.
10
GridVis network analysis software
The ProData 2 can be programmed and read out using
the GridVis network analysis software included in
the scope of delivery. For this, a PC must be connected
to the ProData 2 via a serial interface (RS485) or via
Ethernet (see the connection variants).
GridVis features
• Programming the ProData 2
• Graphical representation of measured values
ProData II
11
ProData II
(twisted patch cable)
Connection variants
Connection of a ProData 2 to a PC via an interface
converter:
ProData 2
UMG 96RM
Connection of a ProData 2 via a UMG 604 as a gateway.
UMG 604
ProData 2
UMG 96RM
12
Direct connection of a ProData 2 to a PC via Ethernet.
(twisted patch cable)
ProData 2
Connection of a ProData 2 to a PC via Ethernet.
ProData 2
Switch
ProData II
Connection of a ProData 2 with gateway function to
a PC via Ethernet.
ProData 2
(Gateway)
UMG 103
(Modbus slave)
UMG 104
(Modbus slave)
In this installation, the ProData 2 can forward queries
(e.g. from the GridVis software) to a Modbus slave
device. However, it CANNOT query Modbus slave
devices independently!
RS485 mode: Gateway; address 3=1
Connecting a ProData 2 as a Modbus slave device.
ProData 2
(Modbus slave)
UMG 103
(Modbus slave)
UMG 104
(Modbus slave)
UMG 604
(Modbus master)
The ProData 2 is configured as a Modbus slave.
Communication to the ProData 2 can take place directly
via Ethernet or via the Modbus master.
The ProData 2 cannot forward any Ethernet queries to
a Modbus slave device!
RS485 mode: Slave; address 3=0
13
ProData II
Installation
Position of installation
The ProData 2 is designed for fixed installation in low
voltage switching devices. It is assembled on a 35 mm
mounting rail in accordance with DIN EN 60715. Can be
installed in any mounting position.
14
Installation
Supply voltage
The ProData 2 requires a supply voltage to operate.
The supply voltage is connected to the front side
of the device via a 2-pin plug-in terminal.
Before connecting the supply voltage, make sure that
the voltage and frequency correspond to the details
on the ratings plate.
The supply voltage must be connected through a UL/
IEC approved fuse (6 A, type C) or a circuit breaker (6 A,
C.Char).
• If installed in a building, a disconnector
m
or circuit breaker must be provided for
the supply voltage.
• The disconnector must be installed
near the device and easily accessible
to the user.
• The switch must be marked as the circuit
breaker for this device.
• Voltages which are over the permitted
voltage range can destroy the device.
Circuit breaker
ProData II
+
-
DC
AC
Circuit breaker
Fuse
L
N
Fig. Connection example of the supply voltage
to a ProData 2 via an external mains supply.
Fuse
L
N
Fig. Connection example of the supply voltage
to a ProData 2.
15
ProData II
RS485 interface
In the ProData 2, the RS485 interface is designed as a 2pin plug contact, which communicates via the Modbus
RTU protocol (also see Parameter programming).
A
B
S1
Fig.: Placement in the middle of the segment;
termination via DIP switch S1 deactivated (OFF)
A
B
S1
Fig.: Placement at the end of the segment;
termination via DIP switch S1 activated (ON)
16
Termination resistors
The cable is terminated with resistors (120 Ohm, 1/4 W)
at the beginning and at the end of a segment.
Termination within the device is possible via the S1 DIP
switch of the ProData 2.
Correct
Incorrect
Terminal strip in the cabinet.
Device with RS485 interface
(without terminating resistor).
Device with RS485 interface
(with terminating resistor on the device).
ProData II
Screening
Twisted screened cable should be used for connections
via the RS485 interface.
• Earth the screens of all cables that lead to the cabinet
upon entering the cabinet.
• Connect the screens over a generous area and in
a manner that will conduct well to a low-noise earth.
• Gather the cables mechanically above the earthing
clamp in order to avoid damage due to cable
movements.
• Use suitable cable glands to feed the cables into
the cabinet - e.g. armoured conduit couplings.
Cable type
The cable used must be suitable for an environmental
temperature of at least 80 °C.
• All devices are connected in a bus structure (line) and
each device has its own address within the bus (see
also Parameter programming).
• Up to 32 subscribers can be connected together in
a single segment.
• The cable is terminated with resistors (bus termination
120Ohm, 1/4W) at the beginning and at the end of
a segment.
• With more that 32 subscribers, repeaters (amplifiers)
must be used to connect the individual segments.
• Devices for which the bus connection is switched
on must be under current.
Master
Power supply necessary
Bus terminator on
T
T
SlaveSlaveSlaveRepeater
T
SlaveSlaveSlaveSlave
SlaveSlaveSlave
18
• It is recommended that the master be placed at
the end of a segment.
• If the master is replaced with a bus connection,
the bus must be switched off.
• Replacing a slave with a bus connection that is either
switched on or de-energised can destabilise the bus.
• Devices that are not connected to the bus can
be replaced without destabilising the bus.
T
T
Fig. Bus structure
Ethernet interface
ProData II
The Ethernet network settings should be specified
by the network administrator and set accordingly
on the ProData 2 using the GridVis software.
If the network settings are not known, the ProData 2 may
not be integrated into the network via the patch cable.
PC / Switch
Ethernet
Connection
LEDs of the Ethernet interface
LEDFunction
YellowIlluminates when a connection (LINK)
GreenIlluminates sporadically when
m
m
is present.
a network activity occurs.
Caution!
Connection of the ProData 2 to the Ethernet
may only be carried out after discussion
with the network administrator.
Caution!
The ProData 2 is factory-set to the fixed
IP address 10.10.10.200 (subnet mask
255.0.0.0). The allocation of a dynamic IP
address is disabled.
The settings can be changed via a suitable
Ethernet connection using the GridVis
software.
19
ProData II
Digital outputs
The ProData 2 features three digital outputs that have
a joint reference. The status of each of the outputs is
shown by the corresponding LED. The corresponding
LED illuminates red when the output is set to active,
regardless of whether there is a continuing connection
to this interface.
Digital output 1 can also be configured to monitor
the temperature. This can be switched via the temperature
measurement input and using a comparator.
• The digital outputs can be controlled via Modbus and
the weekly timer.
• The digital outputs can display the results of
comparators.
• An external auxiliary voltage is required.
• The digital outputs can be used as pulse outputs.
• The digital outputs can switch AC and DC loads.
• The digital outputs are not short-circuit proof.
• Connected cables that are longer than 30 m must
be shielded when laid.
~
Fig. connection
Digital/pulse outputs
20
DC connection example
ProData II
Auxiliary voltage
ProData 2
Digital outputs 1-3
Digital outputs 1-3
21
Digital
Output 1
22
Digital
Output 2
23
Digital
Output 3
24
Fig. Example of two relays connected
to the digital outputs
External
DC
DC
24 V
AC/DC
K2K1
-+
Caution!
m
C
C
Digital outputs are not short-circuit proof.
Functions for the digital outputs can be
adjusted clearly in the GridVis software
provided in the scope of delivery.
A connection between the ProData 2 and
the PC via an interface is required to use
the GridVis software.
When using the digital outputs as pulse
outputs, the auxiliary voltage (DC) must
have a maximum residual ripple of 5%.
21
ProData II
Digital inputs
The ProData 2 features 15 digital inputs, which are
subdivided into three groups of 5 inputs, each with
a joint earth.
The status of each of the inputs is shown by
the corresponding LED. The corresponding LED
illuminates green if there is a signal on this interface.
An input signal is recognised (signal "1") if a voltage of at
least 18 V is flowing (typically 4 mA at 24 V). If the voltage
is lower than 5 V DC, no input signal exists (signal "0").
Wiring longer than 30 m must be screened.
Correct polarity of the supply voltage (20 ... 30 V DC)
must be ensured!
Caution!
m
Correct polarity of the supply voltage for
the digital inputs must be ensured.
Group 1
Group 2
+
-
Fig. Connection
example of digital
+
inputs of groups
-
1 and 2
22
ProData 2
Digital inputs 1-5
ProData II
External
Auxiliary voltage
6
3,9V
4k
4k
4k
4k
4k
3,9V
3,9V
3,9V
3,9V
Digital
Input 5
Digital
Input 4
Digital
Input 3
Digital
Input 2
Digital
Input 1
5
S5
4
S4
3
S3
2
S2
1
S1
24 V DC
-
+
Fig. Example of
the connection of
external switch
contacts S1 to S5
to digital inputs
1 to 5.
23
ProData II
S0 pulse input
You can connect an S0 pulse transducer per
DIN EN62053-31 to any digital input.
This requires an auxiliary voltage with an output voltage in
the range 20 .. 27 V DC and a resistor of 1.3 kOhm/1 W.
S0 plug-in module
(optional, article number 52.24.111)
• Enables simple and fast connection of S0 pulse
transducers.
• Module for a group of 5 inputs with integrated
resistors.
Fig.: S0 plug-in module
to connect
S0 pulse transducers
24
ProData 2
Digital inputs 1-5
External
Auxiliary voltage
6
3,9V
4k
4k
4k
4k
4k
3,9V
3,9V
3,9V
3,9V
Digital
Input 5
Digital
Input 4
Digital
Input 3
Digital
Input 2
Digital
Input 1
5
4
1.3 k/1 W
3
2
1
24 V DC
-
S0
pulse
transducer
+
Temperature measurement input
Temperature sensors with a resistance region of
between 400 Ohm and 4 kOhm can be connected
to the temperature measurement input. Do not exceed
the total resistance load (sensor + cable) of 4 kOhm.
The temperature measurement value is determined
once per second. The sensor type and the desired
temperature offset can be set using the GridVis software
or a Modbus.
Fig.: PT1000 line
connection
ProData II
Example:
3-line connection PT100
Example:
2-line connection PT1000
a
k
Example:
2-line connection KTY83
When connecting the KTY83/84 sensor, correct polarity
must be ensured. The negative connection (indicated
with a black ring) must be connected to terminal 25.
25
26
27
25
26
27
25
26
27
25
ProData II
Device address (RS485)
If multiple devices are connected to each other via
the RS485 interface, a master device can only identify
the devices by their device address. Within a network,
each device must have its own device address.
The device address can be configured via the rotary
switch that is available on the ProData 2. In this way
addresses can be set in the range of 1 to 99.
X10X1
0
9
8
7
6
5
9
1
2
8
3
7
4
6
The device address 0 0 is
0
1
2
reserved and may not be assigned
3
4
for operation with Modbus
5
communication.
0
9
8
7
6
5
9
1
2
8
3
7
4
6
The device address 99 is reached
0
1
2
by setting the rotary switch X10 to
3
4
9 and X1 to 9. A device address
5
with a higher value cannot be set
for the ProData 2.
0
9
8
7
6
5
9
1
2
8
3
7
4
6
Example: Setting the device
0
1
2
address to 13.
3
4
5
26
0
9
8
7
6
5
9
1
2
8
3
7
4
6
Factory setting:
0
1
2
Device address 1.
3
4
5
Setting options for the device
address via the rotary switch
DIP switch S1
(device termination)
Service button S2
DIP switch S1
ProData II
If the ProData 2 is integrated into a bus via the RS485
interface, a termination resistor has to be set (see
the RS485 interface, termination resistors chapter)
depending on the placement of the ProData within
the segment.
Termination within the device is possible via the S1 DIP
switch of the ProData 2.
Service button S2
The service button is only to be used by instructed
service employees and must not be pressed by those
who are not acquainted with it.
LED device status
The status LEDs below the RS485 interface show
different states of the device. During the start process,
the red and the green LEDs illuminate at the same time.
Once the start process is complete (approximately
15 seconds), the red LED illuminates; the green LED
indicates flawless operation of the device.
LEDFunction
Red/Green Shows the initialisation process during
the start phase (approx. 15 seconds)
GreenDevice is operational
RedDevice error
Red/Green If the start process is complete
and both LEDs are still illuminated,
the initialisation process was
interrupted. Perform a device update
(firmware) via the software.
LED device status
27
ProData II
Configuration and commissioning
Connecting the supply voltage
The supply voltage must be connected to configure and
commission the ProData 2.
The supply voltage level for the ProData 2 is specified
on the rating plate.
RS485 interface
The following parameters must be set to operate
the RS485 interface:
- Device termination (termination resistor)
- Device address (see the device address chapter)
- Baud rate
- Stop bits
The factory settings and the setting area for the baud
rate are specified in the parameter list.
28
Device termination (termination resistor)
For fault-free operation of the devices within a bus
structure, termination resistors must be set at the start
and the end of a segment. If the ProData 2 is at the start
or the end of a segment, a termination can be switched
via the DIP switch S1.
S1
ON
ON: Device termination active (220 Ohm)
OFF
OFF: Device termination inactive
Device termination
Baud rate
A common baud rate can be adjusted for the RS485
interface. The baud rate must be selected consistently
in the grid and set via address 002.
Address 004 can be used to set the number of stop bits
where 0=1 bit (factory setting) and 1=2 bits. Data bits (8)
and parity (none) are fixed default values.
The ProData 2 features 15 digital inputs, which are
subdivided into three groups of 5 inputs:
• The status of each of the inputs is shown by
the corresponding LED. The corresponding
LED illuminates green if there is a signal on this
interface.
• The GridVis software can be used to assign a
name, unit and description to each digital input.
• The states of the digital inputs are each located on
their own Modbus address.
• The last 16 switches (events) are logged with a
time stamp for each digital input.
• Digital inputs 1-10 can be configured as functional
inputs. Operating these inputs as pulse counters is
not possible in this configuration.
• A tariff selection can be assigned to each digital
input where only the highest activated tariff runs.
30
Functional attributes
Specific functions can be assigned to digital inputs 1 - 10.
In this function mode, operating these inputs as pulse
counters is not possible.
Digital input 1 to 8:
Configuration as tariff converter
Digital input 9:
Synchronisation of the internal clock; choosing between
minute or hour synchronisation is possible. However,
synchronisation is also possible via a Modbus address.
Digital input 10:
Reset for the synchronisation values (see notes).
You also have the option of resetting the mean values via
a Modbus address.
Pulse counters
ProData II
All digital inputs can be operated with a frequency of
25 Hz. Here, the pulse duration and the pulse interval
must be greater than 20 ms. The typical pulse duration
for S0 pulses is 30 ms.
Pulse duration
> 20 ms
Pulse interval
> 20 ms
The maximum number of pulses per hour is based on
the minimum pulse duration and the minimum pulse
interval:
Pulse lengthPulse intervalMax. pulse/h
20 ms20 ms90 000 pulse/h
30 ms30 ms60 000 pulse/h
50 ms50 ms36 000 pulse/h
100 ms100 ms18 000 pulse/h
500 ms500 ms3600 pulse/h
1 s1 s1800 pulse/h
10 s10 s180 pulse/h
Examples of the maximum possible number of pulses
per hour.
The pulse counters can be configured with
a simultaneous measurement value or power calculation.
The pulses are counted as 64-bit numbers and overflow
after approximately 1.17 x 1010 years of continuous
operation (25 Hz).
Pulse value:
A pulse value can be assigned to each digital input.
Use the impulse value to specify the measurement value
or power value (e.g. energy) to which a pulse should
correspond.
Measurement value calculation:
Measurement value = pulse x pulse value
Power value calculation:
Power value =
pulse x pulse value
Time [sec]
31
ProData II
S0 power values
Since the pulse interval may be very large, continual
calculation of the measurement or power values is not
possible. For this reason, only the mean values are
calculated. For measurement value calculation, the mean
values are calculated from the number of pulses per
period multiplied by the pulse value. For power value
calculation, this value must be divided by the amount of
time that can be set.
The period is assigned to the digital input and can be
set in a region of 1 to 60 minutes. After the period ends,
the value can be called via the Modbus.
For each digital input, an external synchronisation
can be triggered; in this case, a synchronisation pulse
completes one period and starts a new period. A fixed
capture period of 30 seconds is preset for external
synchronisation. If no synchronisation pulse exists after
the period expires, a maximum of 30 seconds is waited
and the software then carries out the synchronisation.
All further periods are synchronised by the software.
A period of 15 min is the factory setting.
32
C
The calculation result for the S0-power
value is not until the end of the cycle available.
Events
Events are status changes of the relevant digital inputs
that are logged in a ring buffer.
Status changes (events):
Time
Event:15 14 13 12 11 109 8 7 654 3 2 10
ProData II
The ring buffer saves
the last 16 events for each
digital input and specifies
the time stamp and
the current status. Within
the ring buffer, the event
field with the index 0 always
describes the current
status of the relevant digital
input.
Current valueOldest value
0
0
15
14
13
12
11
10
9
1
2
6
7
8
Fig.: Ring buffer for
16 field elements
3
4
5
33
ProData II
Clock
The internal device clock is recorded in UTC (Universal
Time Coordinated) format with a resolution of 1 second
and converted into the local time via a possible
configuration of the time zone and the switch between
daylight saving time and standard time.
The time can be read and set via a Modbus address.
The GridVis software can be used as a user-friendly way
to set the clock.
A minute or hour synchronisation of the time takes place
via digital input 9.
Example:
Current device timeTime after minute pulse
15:05:5115:06:00
15:05:1115:05:00
Current device timeTime after hour pulse
15:05:1115:00:00
When synchronising the time via Ethernet (NTP),
the external clock is only set and is read during a restart.
The NTP service can receive broadcasts (passive) or
send queries to an NTP server (active). In active mode,
an NTP server with the IP address must be set. A name
resolution is not possible.
34
Timer
In the ProData 2, 64 independent weekly timers can be
set; here, the resolution is 1 minute. The weekly timer
defines an active period within a day; the active day
must be released within a week.
Example of an active period:
From 9:25 to 11:45 am Sunday, Monday and Friday
The weekly timers can be configured as tariff converters
(1..8), setting digital outputs 1-3, but also as "inoperable".
The status can always be queried via the Modbus.
The states of the timer are linked via an OR operator to
the digital output.
The weekly timer must be set using the GridVis software.
ProData II
Recordings
Recordings with static access (SCADA systems):
• Differential monthly values (without tariff) and
the maximum power values are saved for each
digital input for the current and previous year.
• Static recordings such as work values of the pulse
inputs (pulse number x factor) and the minimum/
maximum values of the temperature input are
stored in the flash memory every 3 minutes.
Recordings in the data flash (for GridVis software):
• Up to 8 recordings with up to 29 values can
be stored in the ProData 2.
• The smallest time basis for recordings is 1 minute
and the largest time basis is 60 min.
• Recordings and the names of the power values
can be adjusted and extended via the GridVis
software.
Data memory
The size of the ProData 2's flash memory is 32 MB;
24 MB is available for recordings and 5 MB is available
for the cyclical drawings of the work values.
Recording all 15 channels at a recording interval of
15 minutes results in a recording depth of approximately
1024 days.
The memory is read or deleted via a Modbus or via
the GridVis software.
35
ProData II
Rate conversion
A tariff selection of 1 to 8 can be assigned to each digital
input; the tariffs can be activated via digital inputs 1-8,
via a Modbus and via the timer. Each input can be reset
individually via the GridVis software.
The tariff conversion via Modbus takes place via
addresses 1940 (for digital input 1) to 1954 (digital
input 16). The relevant tariff is to be selected by setting
or deleting bits 0 to 7. Only the highest-value tariff is
evaluated.
Bit:
0 1 2 3 4 5 6 7
0
000001
00
Tariff 8 (0 = not set)
Tariff 7 (0 = not set)
Tariff 6 (0 = not set)
Tariff 5 (0 = not set)
Tariff 4 (0 = not set)
Tariff 3 (0 = not set)
Tariff 2 (1 = tariff set)
Tariff 1 (0 = not set)
Example of tariff 2 set: If the value is set to address 1940,
the tariff conversion for digital input 1 applies.
36
Bit-by-bit representation of the tariff conversion
TariffT1 T2 T3 T4 T5 T6 T7 T8
Bit01234567
InputAddress
1194001000000
2194100000000
......
15195400100000
Example: For digital input 1, tariff 2 is set, for input 15,
tariff 3 is set.
In addition to the tariff conversion, the individual tariffs
are to be activated via Modbus addresses 1700 (tariff 1)
to 1707 (tariff 8).
AddressTariff
170010 = tariff deactivated, 1 = tariff activated
170120 = tariff deactivated, 1 = tariff activated
170230 = tariff deactivated, 1 = tariff activated
.........
170780 = tariff deactivated, 1 = tariff activated
ProData II
37
ProData II
Temperature measurement input
The temperature measurement value is determined
once per second. The sensor type and the desired
temperature offset can be set using the GridVis software
or a Modbus.
Threshold value monitoring of the temperature
measurement input is possible using a comparator.
The results of the comparator can be combined with
the OR operator.
The combination result of the comparator group can
be assigned to digital output 1.
Sensor types:
- PT100 / PT1000
- KTY83 / KTY84
Fig.: GridVis software, configuration menu
38
C
Threshold value monitoring can be
adjusted clearly in the GridVis software
provided in the scope of delivery.
A connection between the ProData 2 and
the PC via an interface is required to use
the GridVis software.
Ethernet
ProData II
Within an Ethernet, each device has a unique TCP/IP
address that can be assigned manually or from a DHCP
server.
Fixed IP address:
In simple networks without a DHCP server, the network
address of the ProData 2 must be set via a Modbus or
via the GridVis software.
BootP:
BootP allows for fully-automatic integration of
the ProData 2 into an existing network. However,
BootP is an older protocol and does not provide
the scope of functions provided by DHCP.
DHCP mode:
DHCP allows for fully-automatic integration of a ProData
2 into an existing network with a DHCP server without
additional configuration. When started, the ProData 2
automatically obtains the IP address, the network mask
and the gateway from the DHCP server.
Factory default settings: Fixed IP address
IP address 10.10.10.200
Subnet mask 255.0.0.0
DHCP deactivated
m
m
Caution!
Connection of the ProData 2 to the Ethernet
may only be carried out after discussion
with the network administrator.
Caution!
The device is factory-set to the fixed
IP address 10.10.10.200 (subnet mask
255.0.0.0). The allocation of a dynamic IP
address is disabled.
The settings can be changed via a suitable
Ethernet connection using the GridVis
software.
39
ProData II
Modbus gateway
The ProData 2 can be set as a Modbus gateway with
the following limitations:
• In this mode, the ProData 2 cannot be used as a
Modbus RTU slave device.
• In this mode, the ProData 2 converts Modbus TCP
packages from port 502 (only TCP) to Modbus
RTU and sends these via the RS485 interface.
If a response is received via the RS485 interface
within a timeout period that can be set, this is
converted to Modbus TCP again and sent via
the IP connection.
• The ProData 2 can only forward queries (e.g.
from the GridVis software) to a Modbus slave
device. It CANNOT query Modbus slave devices
independently.
40
PC with GridVis software
ProData 2
as gateway
Ethernet
UMG 104
Slave 1
Ethernet
UMG 103
Slave 2
ModbusModbusModbus
UMG 604
Slave 3
Fig.: Connection variant with ProData 2 as a gateway.
The ProData 2 converts the queries of the GridVis
software (TCP packages via Ethernet) for the Modbus
slave devices (Modbus RTU) and forwards these via
the RS485 interface (RS485 mode: Gateway; Addr. 3=1).
PC with GridVis software
Ethernet
ProData II
ProData 2
as slave 1
UMG 104
Slave 2
ModbusModbusModbus
UMG 103
Slave 3
UMG 604
Master
Fig.: Connection variant with ProData 2 as a Modbus
RTU slave device.
The ProData 2 can be addressed directly via Ethernet
but it cannot send any Ethernet queries to a Modbus
slave device. The ProData 2 contains a slave function in
the RS485 bus and can be read from the master device
(UMG 604). (RS485 mode: Slave; Addr. 3=0).
41
ProData II
Service and maintenance
The device underwent various safety checks before
delivery and is marked with a seal. If a device is open,
then the safety checks must be repeated. Warranty
claims will only be accepted if the device is unopened.
Repairs
Repair work can be carried out by the manufacturer only.
Front film
The front film can be cleaned with a soft cloth and
standard household cleaning agent. Do not use acids
and products containing acid for cleaning.
Disposal
The ProData 2 can be reused or recycled as electronic
scrap in accordance with the legal provisions.
The permanently installed lithium battery must be
disposed of separately.
42
Service
Should questions arise, which are not described in this
manual, please contact the manufacturer directly.
We will need the following information from you
to answer any questions:
- Device name (see rating plate),
- Serial number (see rating plate),
- Software release,
- Supply voltage,
- Precise description of the error.
Device calibration
The devices are calibrated by the manufacturer at
the factory - it is not necessary to recalibrate the device
providing that the environmental conditions are complied
with.
Calibration
We recommend having a re-calibration carried out
by the manufacturer or an accredited laboratory
approximately every 5 years.
Battery
ProData II
The internal clock is fed from the supply voltage.
If the supply voltage fails then the clock is powered by
the battery.
The clock provides date and time information, e.g. for
the records and events.
The life expectancy of the battery is at least 5 years
with a storage temperature of +45 °C. The typical life
expectancy of the battery is 8 to 10 years.
The battery status (full capacity, undervoltage, no
can be read via the Modbus (address 4942) / Ethernet using
the GridVis software. If the battery
time synchronisation (NTP) is set, the software takes
the last valid time stamp from the memory and resumes
from there.
The following chapter provides information about
changing the battery.
is exhausted and no
capacity)
Modbus
Address
4942
(short,
16-bit)
Table: Battery status
(can be read via Modbus in address 4942).
BitStatus description
0• Battery capacity exhausted
• Clock has stopped and must
be set if necessary
• Battery should be replaced
1• Battery capacity nearly
exhausted
• Battery should be replaced
2• Battery capacity low
• Battery should be replaced
43
ProData II
Replacing the battery
If the battery capacity that is displayed by the GridVis
software is in the "Undervoltage" range, we recommend
changing the battery.
If the capacity of the battery is too low and a time
synchronisation via NTP is not set, the device software
takes the last valid time stamp and resumes it.
The battery is replaced via the battery insert provided on
the front of the device. Ensure that the correct type of
battery is used here and observe correct polarity when
changing it. Information about polarity is provided on
the battery insert cover.
Procedure
1. To change the battery, the device must be switched off.
2. Discharge any electrostatic charge in your body, e.g.
by touching an earthed cabinet or metal part (radiator)
connected to the earth of the building.
3. Open the battery compartment on the front of
the device.
4. Remove the battery from the battery compartment,
e.g. using long-nose pliers.
44
5. Ensure that the polarity is as shown on the battery
compartment and slide the replacement battery into
the battery compartment. Use a battery compliant
with the description in the technical data for this.
The battery must fulfil the safety requirements of
UL1642. Otherwise, there is a risk of combustion or
explosion.
6. Close the battery compartment with the relevant
cover.
7. Dispose of the old battery according to the legal
regulations.
Grease or dirt on the contact surfaces
m
m
form a transfer resistance that will
shorten the life of the battery. Only touch
the battery at the edges.
Make sure that the correct type of battery
is used and observe correct polarity when
changing it.
Fig. Battery insertion compartment
on the front
ProData II
Firmware update
If the device is connected to a computer via Ethernet
(Modbus TCP) or the RS485 interface (Modbus RTU),
the device firmware can be updated via the GridVis
software.
The new firmware is transferred by selecting a suitable
update menu (Tools/Upgrade Devices menu) and
the device.
Fig. GridVis firmware update assistant
45
ProData II
Procedure in the event of faults
Possible faultCauseRemedy
The device does not functionExternal fusing for the power
Status LEDs illuminate RED and
GREEN after the start process
Status LED illuminates REDDevice defectiveSend the device for inspection
No connection to the device
(RS485)
No connection to the device
(Ethernet)
Device still does not work
despite the above measures.
supply voltage has tripped
Initialisation of the device
terminated (see the chapter on
LED device
status)
Incorrect device addressCorrect the device address
Different bus speeds (baud rate)Correct the speed (baud rate)
Incorrect protocolCorrect the protocol
Termination missingClose bus with termination resistor
Defective or faulty connection
paths
Incorrect addressing mode
selected
Incorrect device addressCorrect the device address
Defective or faulty connection
paths
Device defective.Send the device to the manufacturer
Replace the fuse
Send the device to the
manufacturer for inspection
and testing along with an accurate
fault description.
Check connection paths
Check addressing mode and
correct if necessary
Check connection paths and
correct if necessary
for inspection and testing along with
an accurate fault description.
46
ProData II
47
ProData II
Technical data
General information
Net weight (with attached connectors)approx. 200 g
Packaging weight (including accessories)approx. 440 g
BatteryLithium battery CR2032, 3V (approval i.a.w. UL 1642)
Transport and storage
The following information applies to devices which are transported or stored in the original packaging.
Free fall1 m
TemperatureK55 (-40 °C to +70 °C)
Relative humidity 0 to 90 % RH
Ambient conditions during operation
The ProData 2 is intended for weather-protected, stationary use.
Protection class II in acc. with IEC 60536 (VDE 0106, Part 1).
Flammability rating of housingUL 94V-0
Working temperature rangeK55 (-40 °C to +70 °C)
Relative humidity5 to 95 % RH (at +25 °C without condensation)
Operating altitude0 .. 2000 m above sea level
Degree of pollution2
Mounting / assemblyMounting rails 35 mm
Mounting positionany
VentilationForced ventilation is not required.
Protection against ingress of solid foreign bodies and waterIP20 in acc. with EN60529
(in acc. with IEC/EN60999-1, DIN EN 50022)
48
ProData II
Supply voltage
Installation overvoltage category300 V CAT II
Protection of the supply voltageFuse: 6 A, type CC (approved in acc. with UL/IEC) or
Nominal range20 V - 250 V (45..65 Hz) or DC 20 V - 300 V
Power consumptionmax. 4 VA / 2 W
Terminal connection capacity (supply voltage)
Conductors to be connected. Only one conductor can be connected per terminal!
Precision+/- 5 ppm in temperature range -40 °C to 70 °C
(corresponding to approx. 3 minutes p.a.)
51
ProData II
Dimension diagrams
All dimensions provided in mm
ProData 2 front viewProData 2 side view
with Ethernet connector inserted
107.5
90
46
52
32.2
35.5
46
ProData II
53
ProData II
Declaration of conformity
The product fulfils the following EC Directives:
2004/108/EG Electromagnetic compatibility of electrical equipment.
2006/95/EG Electrical equipment for use within certain voltage limits.
Considered standards:
Noise immunity
IEC/EN 61326-1:2013 Class A: Industrial environment
IEC/EN 61000-4-2:2009 Electrostatic discharge
IEC/EN 61000-4-3:2011, EMV-ILA V01-03 Electromagnetic RF Field 80-1000MHz
IEC/EN 61000-4-3:2011, EMV-ILA V01-03 Electromagnetic RF Field 1000-2700MHz
IEC/EN 61000-4-4:2013, EMV-ILA V01-03 Burst
IEC/EN 61000-4-5:2007, EMV-ILA V01-03 Surge
IEC/EN 61000-4-6:2009, EMV-ILA V01-03 Conducted disturbances 0.15-80MHz
IEC/EN 61000-4-11:2005, EMV-ILA V01-03 Voltage dips, short interrupts, voltage variations and
frequency changes
Noise emission
IEC/EN 61326-1:2013 Class B: Residental environment
IEC/CISPR11/EN 55011:2011 Radio disturbance field strength 30-1000MHz
IEC/CISPR11/EN 55011:2011 Radio disturbance voltage 0.15-30MHz
EMV-ILA V01-03 Radio disturbance voltage 9-150kHz
Equipment safety
IEC/EN 61010-1:2011 Safety requirements for electrical equipment for Measurement, control and laboratory use – Part 1: General requirements
IEC/EN 61010-2-030:2011 Particular requirements for testing and measuring circuits
54
ProData II
55
ProData II
Connection example
56
+
24 V
=
DC
DI1 DI2 DI3 DI4 DI5DI6 DI7 DI8 DI9 D10
-
123456789 10 11 12
Digital inputs
Digital inputs
15 16 17 18 19 20
-
DI11 DI12 DI13 DI14 DI15
=
24 V
DC
+
Digital outputs
21 22 23 2425 26 27
DO3
DO1
DO2
+
=
24 V
DC
-
L
N
+
24 V
=
DC
-
1314
BA
RS485
ProData 2
Temperature inputsSupply
PT1000
voltage
L/+ N/-
Circuit breaker
Fuse
B
A
PC
Ethernet
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.