Jandy PRO Series JXI200, PRO Series JXI330, PRO Series JXI260, PRO Series JXI400 Quick Reference Manual

JXi™ Gas-Fired
Pool and Spa Heaters
Quick Reference Guide
Models JXI200, JXI260, JXI330, JXI400
2
WATER CHEMISTRY
• Proper chemical balances are necessary for sanitary bathing conditions, as well as ensuring your heater’s long life.
• For spas, it is necessary to perform water changes, in addition to chemical treatment. Change the spa water every 60 days for light usage and every 30 days if usage is heavy.
• Zodiac Pool Systems, Inc. does not warrant heat exchangers damaged by corrosive chemical levels or excess dissolved solids in pool or spa water. Refer to the recommended chemical levels, see table right. CORROSIVE WATER
CHEMISTRY VOIDS ALL WARRANTIES.
* For calcium hypochlorite, lithium hypochlorite, or sodium hypochlorite. ** For sodium dichlor, trichlor, chlorine, gas, BCDMH. *** Start-up includes the TDS contribution of salt found in chlorine generating systems. **** Dictated by state or local codes. Typically 100 ppm (mg/L). Some codes are higher, some are lower.
Parameter Min. Ideal Max. Pool Type
Free Chlorine (ppm or mg/L)
1.0 2.0 - 4.0 5.0 Pools, Waterparks
2.0 3.0 - 5.0 10.0 Spas
Combined Chlorine (ppm or mg/L)
0 0 0.2 Pools, Waterparks
0 0 0.5 Spas
Total Bromine (ppm or mg/L)
2.0 4.0 - 6.0 10.0 All Types
PHMB (ppm or mg/L)
30 30 - 50 50 All Types
pH
7.2 7.4 - 7.6 7.8 All Types
Total Alkalinity as CaCO
3
60 80 - 100*
100 - 120**
180 All Types
Total Dissolved Solids (ppm/ mg/L)
NA NA 1500 over
start-up***
All Types
Calcium Hardness as CaCO
3
(ppm or mg/L)
150 200-400 1000 Pools, Waterparks
100 150-250 800 Spas
Cyanuric Acid (ppm or mg/L)
0 30-50 **** All Types
3
MODEL & SERIAL NUMBER
Make sure you have the MODEL NUMBER and SERIAL NUMBER available before calling Zodiac Technical Support.
Model number and serial number on heater rating plate located on the front of the combustion chamber. (Remove heater front panel.) Model number and serial number on heater rating plate located on the front of the combustion chamber. (Remove heater front panel.)
4
For detailed information, refer to the complete installation and owner’s manual.
CLEARANCES General
Minimum Vertical Clearance:
36" (45 cm)
Minimum Clearance to At Least One Door Panel:
18" (22.5 cm) US 24" (30 cm) Canada
Minimum Service
Clearance
from Header:
12" (40.6 cm)
5
For detailed information, refer to the complete installation and owner’s manual.
Combustible Surfaces*
TOP:
6 inches (15 cm)
EXHAUST SIDE:
6 inches (15 cm) from surface of the exhaust vent
HEADER SIDE:
6 inches (15 cm)
SIDE PANELS:
6 inches (15 cm)
Service Access*
TOP:
36 inches (45 cm)
EXHAUST SIDE:
6 inches (15 cm) from surface of the exhaust vent
HEADER SIDE:
12 inches (30 cm)
SIDE PANELS (at least one):
18 inches (22.5 cm) US 24 inches (60 cm) CAN
CLEARANCES
Combustible Surfaces & Service Access
* Clearances are manufacturer’s tested values. These are given as minimum values. Where local and national codes apply, and if the clearance values specified in the applicable codes are different that those listed in this manual, use the greater value to ensure safest operation.
• Installation on a non-combustible surface is recommended.
• Do not install on carpet.
• This unit can be installed on combustible flooring.
6
For detailed information, refer to the complete installation and owner’s manual.
OUTDOOR CLEARANCES
A
Distance: Heater to Door
USA - at least 4 feet (1.2m) CAN - at least 10 feet (3.0m)
B
Distance: Top of Heater to Vented Opening (Forced Air Inlet)
If the top of the heater is less than 3 feet (0.9m) above a vented opening, the heater must be installed at least 10 feet (3.0m) away.
If the top of heater is more than 3 feet (0.9m) above, then any distance is acceptable.
FORCED AIR INLET
A
B
7
For detailed information, refer to the complete installation and owner’s manual.
OUTDOOR INSTALLATIONS
5 ft (1.5 m)
Unless separated by a solid wall, the minimum distance to the inside wall of the pool must be at least 5 feet (1.5 m).
8
For detailed information, refer to the complete installation and owner’s manual.
INDOOR INSTALLATIONS
Category I, Category III Venting
• Vent the heater in accordance with the National Fuel Gas Code ANSI® Z223.1 (NFPA® 54).
• Category I: Install a 4" double-wall appliance adapter to meet vent size requirements for the heater model.
• Category III: Install vent connector or elbow to the flue collar according to specific installation instructions from the vent component manufacturer.
Model
Vent Size
(Category I)
Vent Size
(Category III)
JXI200
6" (15 cm) 4" (10 cm)
JXI260
7" (18 cm) 4" (10 cm)
JXI330
8" (20 cm) 4" (10 cm)
JXI400
8" (20 cm) 4" (10 cm)
9
For detailed information, refer to the complete installation and owner’s manual.
INDOOR CLEARANCES Venting for Category I (US) or Outdoor Shelter (CAN)
Required air supply to room top and bottom
1/4 in. (6.35 mm) minimum pitch per foot of horizontal pipe
LISTED VENT CAP
STORM COLLAR
ROOF JACK AND FLASHING
• NOTE: Use approved roof jack
Vent terminated at least 2 ft (0.6 m) above any object within 10 ft
10 ft
(3.5 m)
2 ft (0.6 m)
10
For detailed information, refer to the complete installation and owner’s manual.
• Side wall vent terminals for Category III (USA) illustrated.
• For Canadian installations, refer to CSA B149 for specific requirements.
• Suggested Z-vent part # 2SVSRTF.
VENT TERMINATION
FORCED AIR INLET
If less than 10 ft (3.0 m)
12 in (30 cm) min.
4 ft (1.2 m)
min.
3 ft (0.9 m)
min.
4 ft (1.2 m)
min.
INDOOR INSTALLATIONS
Side Wall Vent Termination
11
For detailed information, refer to the complete installation and owner’s manual.
INDOOR INSTALLATIONS
Combustion Air Supply
• All indoor installations must have openings to outside air for combustion and ventilation from the inside of the building.
• As outlined in ANSI® standard Z223.1 (NFPA® 54), the room in which the heater is installed should have two permanent air supply openings: (1) within 12 inches (305 mm) of the ceiling, and (2) within 12 inches (305 mm) of the floor.
• All air from outdoors should have a net free area, as shown in the table (right). If using screens or metal louvers, add additional area. Consult the specific louver manufacturer for restriction specifications as different louvers will have varying restrictions.
* Area indicated is for one of two openings: (1) 12ʺ from floor level, and (2) 12ʺ from ceiling level.
Minimum Required Area for Air Supply Openings
Model Direct from Outside* Duct from Outside*
JXI200
50 in2 (323 cm2) 100 in2 (645 cm2)
JXI260
65 in2 (419 cm2) 130 in2 (839 cm2)
JXI330
83 in2 (535 cm2) 165 in2 (1065 cm2)
JXI400
100 in2 (645 cm2) 200 in2 (1291 cm2)
12
For detailed information, refer to the complete installation and owner’s manual.
• Check supply pressure and local code requirements before proceeding with installation.
• Consider pipe fittings when determining gas pipe sizing.
• Larger pipe size can be used if required by local code.
• It is critical that the incoming gas supply pressure at the heater is within the maximum and minimum pressure requirements. If the range of acceptable supply pressure is not provided, the gas supply system to the heater must be modified to meet pressure requirements.
• The gas shut off valve must be installed in an accessible location within six (6) feet of the heater.
• Do not use CSST or any flexible gas piping.
GAS LINE SIZING
* Numbers are for natural gas (0.65 Sp. Gr.) based on 1/2 inch (3.45 kPa) water column pressure drop. Check
supply pressure with a manometer, and local code requirements for variations. For LP gas, reduce pipe diameter by one size, but maintain a minimum 3/4 inch diameter.
For specific requirements: (1) Natural gas heaters, refer to NFPA® 54. (2) Propane heaters, refer to NFPA 58.
Minimum Required Gas Pipe Sizing
Model
(BTU)
0-50 ft (0-15m) from
gas meter*
50-100 ft (15-30m)
from gas meter*
100-200 ft (30-60m)
from gas meter*
JXI200
1ʺ (25 mm) 1-1/4ʺ (32 mm)
1-1/4ʺ (32 mm)
JXI260
1-1/4ʺ (32 mm) 1-1/4ʺ (32 mm)
1-1/4ʺ (32 mm)
JXI330
1-1/4ʺ (32 mm) 1-1/4ʺ (32 mm)
1-1/2ʺ (38 mm)
JXI400
1-1/4ʺ (32 mm) 1-1/2ʺ (38 mm)
1-1/2ʺ (38 mm)
13
For detailed information, refer to the complete installation and owner’s manual.
GAS PRESSURE TEST
• Check the gas supply pressure while the heater is operating.
• Any adjustments or readings made while the heater is off will result in poor performance and other problems.
• Connect a differential manometer to the supply pressure port on the
gas valve.
• If the gas supply pressure does not meet requirements (see table, right), check for a restrictive fitting, undersized gas meter, or undersized pipe between the meter and the heater.
• Minimum inlet supply pressure must be maintained during heater operation while there is a full demand on the gas delivery system.
Gas Supply Pressure NATURAL PROPANE
Max. Inlet
10.5" WC 14" WC
Min. Inlet
4" WC 4" WC
Gas Offset
–0.2" WC –0.2" WC
14
For detailed information, refer to the complete installation and owner’s manual.
ON OFF
UNITS
ZERO
ON OFF
UNITS
ZERO
NEGATIVE
(Low Pressure Port)
_
POSITIVE
(High Pressure Port)
+
DIGITAL
DIFFERENTIAL
MANOMETER
FAN INLET PORT
“T” JOINER
GAS VALVE VENT PORT
GAS VALVE MANIFOLD PORT
Target Offset Pressure
-0.2 inch wc
DIGITAL MANOMETER CONNECTION
15
For detailed information, refer to the complete installation and owner’s manual.
PRV SET-UP
• A pressure relief valve
(PRV) is recommended in all installations.
• A PRV is required in any
installation in which the water flow can be shut off between the heater outlet and the pool/ spa. Check any applicable installation codes in your area to determine whether a pressure relief valve is required.
• A pressure relief valve is not
supplied with the heater.
• Maximum working pressure of
this heater is 50 psi.
• Any PRV installed must comply
with provisions of the standard described in ANSI® Z21.22 for the United Sates or CSA 4.4 in Canada.
3/8” NPT Nipple
3/8” NPT Elbow
3/4” NPT Pressure Relief Valve (PRV)
3/4” to 3/8” NPT Reducing Bushing
1
2
3
4
PRV R-KIT - R0336101
Using the dimple in the center as a guide, drill a 1/4” hole in the threaded boss at the outlet.
1
2
6” min
Using the dimple in the center as a guide, drill a 1/4” hole in the threaded boss at the outlet.
Ground Level
1
2
3
4
6” min
MANUAL SHUT OFF VALVE
REMOVABLE CAP
T-FITTING
MINIMUM
3” (76 mm)
Incorrect
Correct
16
For detailed information, refer to the complete installation and owner’s manual.
MANUAL SHUT OFF VALVE
REMOVABLE CAP
T-FITTING
MINIMUM
3” (76 mm)
Incorrect
Correct
GAS LINE SEDIMENT TRAP
• Do not use flexible gas piping, it will restrict the gas flow to the heater.
• Do not use a restrictive gas cock.
• Install a sediment trap and union ahead of the gas controls and outside the heater panels.
• Sediment trap should be installed as close to the inlet as possible.
17
For detailed information, refer to the complete installation and owner’s manual.
POWER CONNECTIONS
• The heater comes factory-wired intended for use with 240 Volt, 60 Hz AC field electrical supply.
• Do NOT use with 208 Volt.
• To use 120 Volt, 60 Hz AC, change the position of the voltage selector board on the power distribution board (see procedure below right).
• Electrical wiring must be done in accordance with the latest edition of the National Electrical Code® (NEC®) NFPA® 70. In Canada, the Canadian Electrical Code (CEC), CSA C22.1, must be followed.
• Take care not to abrade or damage any wiring or other components.
The voltage selector board is keyed so that it will fit in only one (1) direction for the selected voltage (either side of the board).
1. Cut the plastic wire tie fastening the voltage selector board in place
2. Unplug the voltage selector board from the receptacle.
3. Rotate the voltage selector board 180 degrees and reinsert it into the receptacle so that the hole in the board is not visible.
4. Verify that the board is securely seated in the receptacle.
NOTE
POWER DISTRIBUTION BOARD WIRE TIE VOLTAGE SELECTOR BOARD
18
For detailed information, refer to the complete installation and owner’s manual.
WIRE TO 120V OR 240V/60 HZ
1. Remove the front panel of the heater.
2. Connect the wires from the power source to the leads on the heater.
• Electrical wiring must be done in accordance with the latest edition of the National Electrical Code® (NEC®) NFPA® 70. In Canada, the Canadian Electrical Code (CEC), CSA C22.1, must be followed.
• Take care not to abrade or damage any wiring or other components.
• The “hot” wire of the 120V power supply has to be connected to the black wire (ACH1) on the power distribution board and the “neutral” wire of the 120V power supply has to be connected to the red wire (ACN1).
WARNING
RISK OF ELECTRIC SHOCK WHICH CAN RESULT IN SERIOUS INJURY OR DEATH. Before attempting installation or service, ensure that all power to the device is disconnected/turned off at the circuit breaker. For detailed information to correctly and safely complete the connection to the power source, refer to the complete installation and owner’s manual.
Connect Power Source to Heater Leads
Connect Conduit at Port in Side Panel
Heater Interior
(access from front panel)
19
For detailed information, refer to the complete installation and owner’s manual.
ELECTRICAL SYSTEM SERVICE ACCESS
Use a screwdriver or other tool to insert and release latch
Lift raceway until latch engages to lock in raised position
Press to release latch and lower raceway
Raceway will swing outward and up
Remove front panel (four screws)
1
2
3
4
5
4
1
2
3
5
20
For detailed information, refer to the complete installation and owner’s manual.
SEQUENCE OF OPERATIONS
WARNING
This heater does not have a pilot light. It is equipped with an ignition device which automatically lights the burner. DO NOT try to light the burners by hand.
1. The control system reads the temperature of the water.
2. Start-up process begins if the temperature is below the set point.
3. Blower starts, then adequate airflow is confirmed by the air pressure switch.
4. After airflow is confirmed, the ignition sequence begins.
5. After a 15-second purge, the igniter gets power.
6. After approximately 40 seconds of igniter heat up, power is sent to the gas valve.
7. The gas valve remains open for 5 seconds while the Ignition Control is looking
for flame rectification.
8. As long as flame is sensed at the burner, operation continues until the
temperature of the water entering the heater reaches the temperature control setting.
21
For detailed information, refer to the complete installation and owner’s manual.
HEATER CONTROL PANEL
The display reverts to OFF after one minute of inactivity.
Press POOL button to activate the pool thermostat.
Press MENU button to access setup functions and programming for pool and spa.
Press SPA button to activate the spa thermostat.
Use UP and DOWN buttons to select pool and spa functions.
NOTE
22
For detailed information, refer to the complete installation and owner’s manual.
USER INTERFACE SET UP Display Language
Control must be OFF to begin.
OR
SELECT USER SETUP LANGUAGE
to Change Language
OR
SELECT LANGUAGE ENGLISH
MENU
SPA
to Exit
MENU
SPA
POOL
MENU
SPA
SPA
OR
to Save
MENU
SPA
Hold for 5 seconds
23
For detailed information, refer to the complete installation and owner’s manual.
USER INTERFACE SET UP Display Temperature Units
Control must be OFF to begin.
Hold for 5 seconds
MENU
SPA
OR
SELECT USER SETUP TEMPERATURE SCALE
to Toggle °F and °C
OR
SELECT TEMP SCALE °F
MENU
SPA
to Exit
MENU
SPA
POOL
MENU
SPA
SPA
OR
to Save
24
For detailed information, refer to the complete installation and owner’s manual.
Hold for 5 seconds
MENU
SPA
Control must be OFF to begin.
OR
SELECT USER SETUP DISPLAY LIGHT
MENU
SPA
SELECT DISPLAY LIGHT 2 MIN TIMEOUT
to Toggle:
OR
2 MIN TIMEOUT LIGHT OFF LIGHT ON
USER INTERFACE SET UP Display Backlight Auto OFF
to Exit
MENU
SPA
POOL
MENU
SPA
SPA
OR
to Save
25
For detailed information, refer to the complete installation and owner’s manual.
OR
SET: 80°F
current temp displayed
To Change Temperature Set Point
POOL
MENU
SPA
SPA
OR
After 5 seconds of inactivity, new temp is stored as the set point.
USER INTERFACE OPERATION
Turn ON Pool/Spa Heat
26
For detailed information, refer to the complete installation and owner’s manual.
POOL
MENU
SPA
SPA
OR
MENU
SPA
After 5 seconds of inactivity, new temp is stored as the maintain temp set point.
OR
To Change Maintain Temp Set Point
MENU
SPA
SET: 80°F
current temp displayed
MAINTAIN POOL HEAT OR MAINTAIN SPA HEAT
USER INTERFACE OPERATION
Maintain Pool/Spa Heat
27
For detailed information, refer to the complete installation and owner’s manual.
POOL
MENU
SPA
SPA
OR
SET POINT LOCKED OR SET POINT UNLOCKED
Press both Keys at same time. Hold for 7 seconds
Lock or unlock depending on current setting.
USER INTERFACE OPERATION
Lock/Unlock Temperature Set Point
28
For detailed information, refer to the complete installation and owner’s manual.
REMOTE WIRING
Connections and Setup
1. Remove the heater front panel and run the wires from the control system through the opening on the lower right or left side of the heater.
2. Connect the wiring from the pool/spa control system to the heater remote control terminal.
3. Connect two wires to Pool and Common terminals of the J6 terminal bar.
WARNING
RISK OF ELECTRIC SHOCK WHICH CAN RESULT IN SERIOUS INJURY OR DEATH. Before attempting installation or service, ensure that all power to the device is disconnected/turned off at the circuit breaker.
• Electrical wiring must be done in accordance with the latest edition of the National Electrical Code® (NEC®) NFPA® 70. In Canada, the Canadian Electrical Code (CEC), CSA C22.1, must be followed.
• Take care not to abrade or damage any wiring or other components.
• When using a remote TSAT 2-Wire connection, set the heater control to SPA and the thermostat control to maximum.
47 HHA. L13
220 VHA. 1Q4
1
HFC.
1JN
1
HFC.
1JN
1
HFC.
1JN
1 2 3 4
UNIVERSAL CONTROLLER
WATER
TEMP
POWER INTERFACE
ASSY:
PCB: E0256800C
CONFIG 0
COIL/AIR
TEMP
GAS
VALVE
Aqualink RS
J14
J12 J11
J5
J8
J7
R BK
Y
GR
J9 J10
J18
R30
R31
R32
R33
R34
C21
C23
C20
C22
C19
C24
C2
X1
C1
33
17
1
1
2
1
C13
C12
TVS4
TVS3
1 2 3 4
1
J4
OUT
Chiller Enable
Chiller Disable
IN
R20
R19
49
C7
R9
U5
U2
C8
C16
C17
C18
C9
C6
U4
C33
C11
C30
C4
C5
U3
L1
R14
R13
PTC1
D14
D9
U6
J13
J17 J16
C22 C23 C24
J15
J6
Q1Q2Q3Q4Q5
TV57
TV56
C15
C14
R16R17
D15
C3
+
User Interface1
BK O BL R BK O BL R
User Interface2
HiPres/
HiLimit
LoPres/
Fuselink
Water
Press
REV
VALVE
24VAC
COMP/
IGN
SPA POOL COM
24VAC LOOP
REMOTE
R21
R28
D16
R3
R4
R1
R12
D5
D1
D6
D7
D19
D18
D17
R11
R10
R5
R26
D13
J7
J3
K5 K4 K3 K2
K1
NO
NO
COM
COM
NC
NC
J1
1 1
J2
D12 D11 D10
D8
R25 R18 R7 R8
R6
R27
R2
R29
TVS2
TVS1
1
JP1
PUMP
FAN/
LOUVER
JVA
INTAKE
JVA
RETURN
YS-2 94V-0
E226490 RoHS
U1
+
+
+
+
NTC1
MOV1
For heater remote controls please use 2 or 3 wire connections at the J6 Terminal Bar.
Aqualink
®
RS, Aqualink PDA and Aqualink Z4™ controllers can use “smart” communication by utilizing the RS 485 connector at the J8 Terminal Bar.
29
For detailed information, refer to the complete installation and owner’s manual.
REMOTE SETUP (2-Wire)
Control must be OFF to begin.
Hold for 7 seconds
REMOTE
to Exit
OR
MENU
SPA
REMOTE OFF
MENU
SPA
+
POOL
MENU
SPA
SPA
+
OR
REMOTE TSTAT
POOL
MENU
SPA
SPA
OR
SPA
SET: °F
set to maximum temp
OR
30
For detailed information, refer to the complete installation and owner’s manual.
Control Panel Message Fault
PUMP
• Filter pump remains turned OFF when heater programmed for Maintain Temp mode.
NO FLOW
• Pump is not running.
• Low pump pressure.
• Pressure switch fault.
• Variable speed pump set too low.
HIGH LIMIT
• Water temperature in heater exceeds the internal limit.
• Limit switch fault.
• Temperature control thermostat failure.
FUSELINK/FIELD
• Vent temp limit fault.
CHECK IGNITION STEPS
• Broken, split, pinched or disconnected air pressure switch.
• Fan not operating.
• Fan running slow or premature fan failure.
• Air flow restricted at intake or discharge.
• Broken igniter.
• Low gas supply pressure.
• No flame at burners.
SHORTED H2O SENSOR OPEN WATER SENSOR
• Faulty wiring or connection.
• Failed water temperature sensor.
SERVICE ERROR MESSAGES
31
For detailed information, refer to the complete installation and owner’s manual.
TEMPERATURE SENSOR RESPONSE
Temperature °F (°C) Resistance (Ohms)
40°F (5°C) 25,274
50°F (10°C) 19,906
60°F (16°C) 15,314
70°F (21°C) 11,884
80°F (27°C) 9,299
90°F (32°C) 7,333
100°F (38°C) 5,827
110°F (43°C) 4,663
120°F (49°C) 3,758
130°F (54°C) 3,048
140°F (60°C) 2,488
32
For detailed information, refer to the complete installation and owner’s manual.
SAFETY CONTROLS
High Limit Switches (2)
(1) At heat exchanger (135°F/57°C) (2) At heat exchanger outlet (150°F/65°C)
Water Pressure Switch
Prevents burner from firing if water flow to the heater is restricted.
Air Flow Switch
Prevents igniter from firing if there is not adequate vacuum in the blower.
Temperature Sensor
Controls heater operation to attain and maintain selected water temperature.
Ignition Control
Provides pre-purge of the combustion chamber. Opens the gas valve when the igniter is hot enough. Monitors flame condition so that unburned gas does not escape.
33
For detailed information, refer to the complete installation and owner’s manual.
HEADER ASSEMBLY
FLOW PLATE
BACKPLATE
GASKETS
BYPASS
THERMAL REGULATOR VALVE (TRV)
TEMPERATURE SENSOR
HIGH LIMIT SWITCH
HIGH LIMIT SWITCH
DRAIN PLUG
ACCESS DOOR
ACCESS DOOR GASKET
BACKPLATE GASKET
3 PORT MANIFOLD
34
For detailed information, refer to the complete installation and owner’s manual.
THERMAL REGULATOR VALVE REPLACEMENT
Loosen Screw and Rotate Bracket to Release
Pull Out Thermal Regulator Valve
Remove Screws
1
2
3
1
2
3
35
For detailed information, refer to the complete installation and owner’s manual.
JXi 400
JXi 260
BURNER DEPTH
4 HEAT EXCHANGE
TUBES
COMBUSTION CHAMBER SHELF
BURNER DEPTH
6 HEAT EXCHANGE
TUBES
HEAT EXCHANGER (by Model)
JXI400 JXI260
36
OPTIONAL WATER INLET PIPING
• Heater comes with Zodiac® Sweep Elbow.
• Installation provides increased hydraulic performance.
• Exclusive interface with Zodiac AquaLink® RS temperature sensor.
Versa Plumb® Ready
37
For detailed information, refer to the complete installation and owner’s manual.
Inlet
Outlet
®
MasterTemp
®
DIRECT DROP-IN REPLACEMENT FOR PENTAIR® MASTERTEMP
®
38
For detailed information, refer to the complete installation and owner’s manual.
INSTALLATION OF ANCHOR BRACKETS
CONCRETE EQUIPMENT PAD ANCHOR BRACKET
Pre Drill Holes
Prior to Screw Installation
1/4" X 2-1/4” Concrete Screws
In areas where there is high risk of extreme weather conditions, such as in Florida (and other states where there is risk as applicable), the heater is required to be securely fastened to the equipment pad to meet applicable local building code requirements.
(Order Anchor Brackets Kit: Part Number R0593400).
39
WIRING DIAGRAM
L1
F1
ACN1
ACH1
L2
F2
G
R
BK
240 VAC HEATER POWER SUPPLY
BLOWER MOTOR
BK R Y BL W
IGNITION CONTROL
F1
F2
24 VAC
FV+
FV-
IGN 120
L1 L2
IGN FS
W
GNDVAL
BK
W
BK
BL
R
GY BK
24 VAC
R
Y
HOT SURFACE IGNITER
W
GY
W
TRANSFORMER
WATER TEMP
GAS VALVE
USER INTERFACE1
BK O BL
R
HIPRESS/ HILIMIT
LOPRESS/ FUSELINK
WATER PRESS
REMOTE
SPA POOL COM
REV VALVE
24VAC
PUMP
COMP/ IGN
FAN/ LOUVER
UNIVERSAL CONTROLLER POWER INTERFACE
UNIVERSAL CONTROLLER USER INTERFACE
BYPASS
CONTROLLER
POWER INTERFACE
BK O BL R
AIR FLOW SWITCH
GAS VALVE
WATER TEMP SENSOR
BL
W
BK
TO PUMP STARTER CONTACTS (IF USED)
TO COMBUSTION AIR
LOUVER STARTER
(IF
USED)
W
FUSE
R
R
Y
Y
O
BK/Y
BK/Y
O
Y/BK
O
BR Y
BR Y
R
BL
BK BK BK
W BK BL
BR
Y
W WWBL
BK
BLGR
W
O VGY
BK
BK
PSW
Y/BK
C
NO
NC
Y/BK
COIL/AIR TEMP
J3 CONNECTOR
Factory Wired 24V Factory Wired 120V/240V
BK - BLACK BK/Y - BLACK WITH YELLOW TRACE BL - BLUE BR - BROWN G - GREEN GY - GRAY O - ORANGE R - RED V - VIOLET W - WHITE Y - YELLOW Y/BK - YELLOW WITH BLACK TRACE
LIMIT
SWITCH
57˚C
(135˚F)
LIMIT
SWITCH
66˚C
(150˚F)
WATER PRESS SWITCH
VENT
TEMPERATURE
LIMIT
240˚C
(464˚F)
OPTIONAL
BYPASS
ACTUATOR
BK/Y
CIRCUIT BOARD FOR OPTIONAL BYPASS
120 VAC HEATER POWER SUPPLY
G
R
BK
NEUTRAL
HOT
Voltage Selector Card Must Be Rotated.
Alternate 120V Wiring*
WARNING
RISK OF ELECTRIC SHOCK WHICH CAN RESULT IN SERIOUS INJURY OR DEATH. To avoid risk of fire or electrocution, which can cause property damage and/or serious injury, including loss of life, if any of the orginal wire as supplied with the heater must be replaced, appliance wiring material rated for 105°C must be used. Where marked thus -----, appliance wiring material rated for 200°C must be used.
40
NOTES
41
©2014 ZODIAC® is a registered trademark of Zodiac International, S.A.S.U., used under license All other trademarks referenced herein are the property of their respective owners.
Zodiac Pool Systems, Inc.
2620 Commerce Way Vista, CA 92081-8438 USA 1-800-822-7933
www.zodiacpoolsystems.com
Zodiac Pool Systems Canada, Inc.
2115 South Service Road West Unit 3 Oakville ON L6L 5W2 CANADA 1-888-647-4004
www.zodiacpoolsystems.ca
H0454800 REV A
TECHNICAL SUPPORT
USA 1-800-822-7933, enter regional extension CAN 1-888-647-4004
Loading...