FOR YOUR SAFETY: This product must be installed and serviced by a contractor who is licensed and qualified in pool equipment by the jurisdiction in
which the product will be installed where such state or local requirements exists. In the event no such state or local requirement exists, the installer or
maintainer must be a professional with sufficient experience in pool equipment installation and maintenance so that all of the instructions in this manual
can be followed exactly. Before installing this product, read and follow all warning notices and instructions that accompany this product. Failure to follow
warning notices and instructions may result in property damage, personal injury, or death. Improper installation and/or operation can create carbon
monoxide gas and flue gases which can cause serious injury, property damage, or death. For indoor installations, as an additional measure of safety,
Zodiac Pool Systems, Inc. strongly recommends installation of suitable carbon monoxide detectors in the vicinity of this appliance and in any adjacent
occupied spaces. Improper installation and/or operation will void the warranty.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Immediately switch off main gas supply.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
H0205000_REVL
A FIRE OR EXPLOSION MAY RESULT, CAUSING PROPERTY
DAMAGE, PERSONAL INJURY, OR DEATH.
Page 2
Page 3
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
Table of Contents
ENGLISH
Page 3
Section 1. General Information ....................... 4
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
Section 1. General Information
1.1 Introduction
This manual contains information for the proper
installation and operation of the Hi-E
EHE pool/spa heater. Certain sections are specic to
United States or Canadian installations, and are labeled
United States or Canada. Procedures in this manual must
be followed exactly. To obtain a copy of this manual
contact Zodiac Pool Systems, Inc. ("Zodiac
address information. See back cover.
1.2 Description
The Hi-E2 Low NOx heater is a very efcient gas-red
pool and spa heater. Its combustion system includes a
heat exchanger which extracts 95% of the energy in the
gas fuel. It has no standing pilot burner. It exceeds the
requirements of energy conservation regulations such as
those in California, Hawaii, New York, Oregon and other
states which require that a pool heater have intermittent
ignition.
The heater is designed to operate in conventional
swimming pool and spa equipment arrangements. It
requires 115V 60 Hz electrical power. It has the versatile
dual-thermostat control system for pool/spa combinations.
The Hi-E2 is certied by CSA International to comply with
latest editions of applicable standards. In the United States,
the applicable standard is ANSI Standard Z21.56 for gasred pool heaters. In Canada, it is Standard CSA 4.7.
The Hi-E
to heat fresh water swimming pools and spas, and with
proper installation and care, it will provide years of
reliable service. Do not use it to maintain pool or spa
water temperature below 70°F. Do not use it as a heating
boiler or general service water heater or to heat true salt
water systems where salinity is in the 35,000 ppm range.
For special applications, consult your Jandy Pro Series
dealer.
2 Low NOx heater has been designed specically
2 and Hi-E2R Model
®
"). For
WARNING
Improper installation or maintenance can cause nausea
or asphyxiation from carbon monoxide in flue gases
which could result in severe injury, or death. For indoor
installations, as an additional measure of safety, Zodiac
Pool Systems, Inc. strongly recommends installation of
suitable Carbon Monoxide detectors in the vicinity of this
appliance and in any adjacent occupied spaces.
Section 2. Installation Instructions
2.1 General Requirements
All gas-red products require correct installation to assure
safe and satisfactory operation. The requirements for pool
heaters include the following:
1. Appropriate site location and clearances.
2. Sufcient supply of clean air for combustion and
ventilation.
3. Proper venting of products of combustion.
4. Properly sized gas pipe.
5. Properly sized gas meter.
6. Adequate water ow.
7. Provision for disposal of combustion condensate
water.
In the United States, installation must be in accordance
with local codes and the most recent edition of the
National Fuel Gas Code, ANSI Z223.1/NFPA-54. The
Code can be obtained from:
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169
www.nfpa.org
In Canada, install the heater in accordance with local
codes and the most recent edition of the Natural Gas and
Propane Installation Code, CAN/CSA B149.1.
1.3 Warranty
The Hi-E2 is sold with a limited factory warranty. A copy
of the warranty is included in a plastic bag inside the
heater. The warranty does not cover damage caused by
improper installation, operation, or eld modication; or
damage to the heat exchanger caused by corrosive water.
See Section 3.4 for guidelines on pool water chemistry.
Special Precautions
Liqueed petroleum (LP) gas is heavier than air.
Therefore, a pool heater using LP gas is subject to special
installation rules. Consult local codes and re protection
authorities about specic installation restrictions.
Fuel gas and its combustion products are known to cause
cancer or harm the reproductive process. Follow these
installation instructions and applicable codes exactly to
avoid this.
Page 5
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
WARNING
To Reduce the Risk of Fire, install pool equipment in an
area where leaves or other debris will not collect on or
around the equipment. Keep surrounding area clear of
all debris such as paper, leaves, pine-needles and other
combustible materials.
ENGLISH
Page 5
When pool equipment is located below the pool surface,
a leak from any component can cause large scale water
loss or ooding. Zodiac Pool Systems, Inc. cannot be
responsible for such water loss or ooding or resulting
damage. Location of the heater below or above the pool
deck affects operation of its water pressure switch. See
sections on water piping and heater start-up for more
information about this.
2.2 Heater Assembly and Preparation
The Hi-E2 can be installed in a variety of ways, some of them
requiring preparation or assembly in the eld. In all cases,
condensate tubing and ttings, which are provided with the
heater, must be connected and routed. Water connections are
provided on the right side of the heater but can be changed to
the left side by reversal of the water headers.
It is best to handle these preparations before the heater
is in its nal location. Instructions are provided in
subsequent sections of this document.
Installation at High Elevation
The Hi-E
2 has a venturi-type combustion system which
does not require modication for operation at high
elevation. In this type of system, air and fuel gas density
changes are automatically compensated for, assuring
proper air/fuel mixture. Heating capacity is reduced about
3 percent per 1000 feet (305 meters) above sea level. In
general, efciency at high elevation is equal to or better
than at sea level.
2.3 Heater Location
The Hi-E2 may be installed indoors or outdoors as outlined
in later sections. When installed indoors, combustion
air will often be piped to the heater and this requirement
may affect the choice of location, see later section on air
for combustion and ventilation. Both indoor and outdoor
installations require provision of means for disposal of
combustion condensate per section 2.8.
Install the heater at least 5 feet (1.52 meters) from the
inside wall of the pool or spa unless the heater is separated
from the pool or spa by a ve-foot (1.52 meter) high solid
fence, wall or other permanent barrier.
Equipment must be installed on a rm, solid, nonabsorbent level surface; and per the requirements of
local codes and Authority Having Jurisdiction (AHJ).
Equipment can weigh up to 300 lbs. Use suitably rated
mounting surface materials to avoid risk of settlement,
and never use sand to level the equipment as the sand
will wash away. Check local building codes for additional
requirements.
Locate the heater in an area where water leakage will
not result in damage to the area around the appliance or
to a structure. If forced to locate the heater where water
leakage may cause damage, provide a suitable pan with
drain under the heater. This pan must not restrict air ow
or heater functions.
In selection of a location, disposal of combustion
condensate must also be considered. The heater can
produce three gallons of condensate water per hour
under some operating conditions. Means to drain this
condensate must be available or special provisions, such
as a condensate pump must be provided. See later section
on condensate disposal.
2.4 Installation Clearances
Clearances between the heater and combustible material
must be per Table 1.
Table 1. Installation Clearance Requirements.
Surface/Component Minimum Clearance
Inches (mm)
Rear & Blank Side2 (55)
Piping Side12 (305)
Front18 (455)*
Top - Indoors6 (150)
Top - OutdoorsOpen (See Note)
FlooringCombustible
Vent0
* For Canada 24 inches (610 mm) clearance
NOTE See Section 2.5 for outdoor installation requirements.
These clearances are the minimum acceptable. Whenever
possible, larger clearances should be provided to assure
adequate room for service operations. Note that gas piping
must be provided through the left side of the unit and
that the combustion air duct, when provided, also enters
through the left side. See later section on combustion air,
and also the section on water piping.
Do not install the heater on carpeting or similar material.
2.5 Outdoor Installation
CAUTION
When pool equipment is located below the pool
surface, a leak from any component can cause large
scale water loss or flooding. Zodiac Pool Systems, Inc.
cannot be responsible for such water loss or flooding
or resulting damage.
Locate the heater in an open, unroofed area and maintain
the clearances shown in Table 1. Do not locate the heater
below or adjacent to any doors, windows, louvers or
grates, etc., which connect in any way with an inhabited
area of a building, even through another building such as
Page 6
Page 6
Figure 1. Outdoor heater location.
ENGLISH
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
1/4” X 2-1/4”
GALVANIZED OR PLATED
CONCRETE SCREWS
Figure 2. Anchor heater to equipment pad.
each of the holes and fasten the heater to the equipment
pad, see Figure 2. Do not over torque the screws.
a garage or utility room, see Figure 1. Do not locate the
heater below an outdoor deck, unless treated as an indoor
installation with adequate clearances and proper venting
to a location away from the deck.
If the heater is installed close to a structure, protect it from
rain water runoff by means of gutters, roof water diverters
or similar measures. Do not locate the heater close to
irrigation sprinklers. Water from sprinklers may damage
controls and electronic components.
Because the Hi-E
2 is very efcient, combustion system
exhaust gases are moist. Do not locate the heater such
that this exhaust will impinge on structures or vegetation
which may be damaged by combustion condensate.
WARNING
United States
Do not install the heater with the top of the vent
assembly within 4 feet (1.22 m) horizontally, 4 feet
(1.22 m) below or less than 1 ft (300 mm) above of any
opening into a building.
Canada
Do not install the heater with the top of the vent
assembly within 10 feet (3.05 m) of any opening into a
building.
In Florida it is required that the heater be securely
fastened to the equipment pad. Use a size 1/4” x 2-1/4”
long galvanized or plated concrete screws and washers
at each of the four (4) tabs located at the base of the
heater. Mounting the appliance in this manner meets the
applicable requirements of the Florida Building Code.
Mounting screws are not provided with this heater. After
placing the heater on the equipment pad, drill a hole in
the concrete at each of the four (4) tabs on the feet of the
heater. (The correct size drill bit is usually provided with
the concrete screws when purchased). Place a screw in
2.6 Outdoor Shelter Installation (Canada)
An outdoor shelter is an unoccupied enclosure which
does not communicate directly with occupied areas.
The Hi-E
2 may be installed in such a shelter only when
the installation is in accordance with local codes and
the most recent edition of the Natural Gas and Propane
Installation Code (CAN/CSA B-149.1). These codes and
®
standards and Zodiac
require that the heater be properly
vented as outlined in this manual. Other requirements also
apply, such as provision of ample uncontaminated air for
combustion and ventilation.
2.7 Indoor Installation
The Hi-E2 can be located indoors when provided with
“one-pipe” or “two-pipe” systems for combustion air
and combustion product venting. A one-pipe installation
has only a vent pipe, and air for combustion must be
provided to the room the heater is located in. A two-pipe
system (sometimes referred to as “direct vent” or “sealed
combustion”) has a vent pipe plus a pipe bringing air
directly to the heater's combustion system.
Section 2.7.2 species requirements for provision of
combustion and ventilation air for one-pipe installations.
Section 2.7.3 covers two-pipe installation.
An important consideration in selecting one (1) or two
(2) pipe installation is the quality of the combustion
air. Indoor air is sometimes contaminated with various
household or pool sanitation chemicals which can cause
corrosion in the heater combustion system. Unless the
indoor air is known to be free of these materials, two (2)
pipe installation is strongly recommended.
2.7.1 Preparation of Heater For Indoor Installation
If the Hi-E2 is to be installed indoors, its exhaust discharge
grille must be converted to an exhaust pipe conguration.
Page 7
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
ENGLISH
Page 7
The necessary vent collar, gasket and screws are shipped
packaged within the heater. The conversion can be done
quite simply as follows. See Figures 3 and 4:
1. Remove the vent exhaust grille by removing the
four (4) screws which retain it. The grille, its
gasket, and the screws may be discarded.
2. Place the vent collar gasket on the top of the
heater aligning its center hole and screw holes
with those in the top of the heater.
3. Place the vent collar over the gasket and fasten
it in place with the screws and lockwashers
provided. Be sure that all components are
properly aligned. Screws must be tightened
enough to assure a sealed joint without deforming
the vent collar.
2.7.2 Combustion Air Requirements for One-Pipe
Installation
One-pipe indoor installations must have specic
provisions for supply of combustion and ventilation air
to the room in which the heater is located. Two (2) air
openings must be provided — one (1) near the ceiling
and one (1) near the oor. When air is provided directly
through an outside wall, each opening must have at least
1 square inch (6.5 square cm) of area per 4000 BTU/h of
heater input. When air is provided indirectly through ducts
from the outside, the openings and passages must have
at least 1 square inch of area per 2000 BTU/h of heater
input. These requirements are interpreted in Table 2.
Table 2. Required Net Free Area of Openings for
Combustion and Ventilation Air.
Required net free area in square
inches (sq. cm) for each of 2 openings -
Model
35088 (570)175 (1130)
one (1) near ceiling and one (1) near floor
Directly
Through an
Exterior Wall
Through Horizontal
Ducts
Note that the numbers indicate the net free area —
after allowing for the blockage of grille bars, etc. See
applicable local codes and the previously-cited national
codes for details. Even though codes may permit it,
®
Zodiac
does not recommend installations with only
“inltration” as the means for provision of combustion air.
Figure 3. Removal of outdoor exhaust grille.
See Section 2.7.3.3 for vent pipe sizing.
WARNING
Do not store any chemicals, cleaners, or other corrosive
material near combustion air openings or in the
room. Avoid locating appliance vents in the vicinity of
combustion air openings. Failure to prevent corrosive
materials from mixing with combustion air can result in
reduced heater life and unsafe heater operation.
2.7.3 Two-Pipe Installation (Direct Vent)
This section species installation requirements
for combustion air and vent piping for “two pipe”
installations. A two-pipe system provides isolation of the
2 combustion system from the space in which the
Hi-E
heater is installed. It has not only a vent pipe, but also
a combustion air pipe to provide air directly from the
outdoors. Research studies have shown that contaminants
which may corrode internal heater parts are typically at
much lower levels in outdoor air than in air from indoors.
2.7.3.1 Connection of Combustion Air Pipe
A collar for combustion air pipe connection is provided in
the heater at the inlet of the lter box. As shown in Figure
5, the combustion air pipe is routed through the side of the
heater to the lter box connection. Remove the cover plate
from the left side panel to provide access for the air pipe.
Figure 4.
Vent collar assembly for indoor installation.
Page 8
Page 8
ENGLISH
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
4'
Figure 5.
Connection of combustion air pipe to heater.
2.7.3.2 Piping Materials
WARNING
To avoid risk of property damage, serious injury, or
death, use ONLY piping materials from the list below
which are certified or listed for the application per
the requirements of UL 1738 and/or ULC S636, by a
Nationally Recognized Testing Laboratory (NRTL).
Vent piping must be corrosion resistant because
combustion condensate is usually present on its internal
surfaces. The materials listed in Table 3. are acceptable
for vent piping:
Total Length: 42'
Total Elbows: 5
8'
18'
EHE350
10'
2'
Figure 6. “One-pipe” installation.
2.7.3.3 Size and Length of Combustion
Air and Vent Piping
Piping for combustion air and venting must be large
enough to avoid restriction of the heater combustion
system. Pipe diameter, number of elbows and length of
pipe determine how much it restricts ow to or from the
heater. Table 3 species the allowable length of piping for
various situations.
The following example illustrates use of table 3:
EXAMPLE: A model 350 heater is to be installed in a
one-pipe system with schedule 40 PVC or CPVC, see
Figure 6. The vent pipe run is 42 feet long and has
Table 3. Maximum Combined Length of Combustion Air and Vent Piping in Feet.
APPROVED VENTING MATERIALS*
PVC
®
29-4C
Pipe Size
Model
350
350
NOTES
Inches
4 (10.2)
5 (12.7)
6 (15.2)
4 (10.2)
5 (12.7)
6 (15.2)
1. Vent must be Class 100, 125 or Schedule 40 PVC or CPVC, Schedule 80 PVC or CPVC. Combustion air pipe may be PVC, CPVC or suitable metal pipe.
2. Heavy condensation occurs in long vent pipes. Provide a separate entrapped condensate drain from vent piping near heater when 5” vent pipe exceeds 100 feet or 6” vent pipe
*
• For saltwater version heaters (EHE350NS and EHE350PS) a 180°F vent limit switch is required and PVC venting is not allowed.
• Allmetalsectionsoftheventingsystemusedmustbestainlesssteelandlisted/certied/classiedbyaNationallyRecognizedTestingLaboratory(NRTL)as
being compliant with the applicable requirements of the Underwriters Laboratories (UL) standard for safety for “Venting Systems for Gas-Burning Appliances,
Categories II, III, and IV” (ANSI/UL 1738), and properly installed in accordance with any manufacturers’ instructions and in compliance with applicable local and
national installation codes.
• Thenon-metallicsectionsoftheventingsysteminstalledmustalsobelisted/certied/classiedbyaNationallyRecognizedTestingLaboratory(NRTL)as
being compliant with the applicable requirements of the applicable requirements of the Underwriters Laboratories (UL) standard for safety for “Venting Systems
being in compliance with the requirements of the UL standard for “Type BH Gas Venting Systems” (ULC S-636). When installed properly in accordance with any
manufacturers’ instructions and in compliance with applicable local and national installation codes.
Total Length of Pipe Schedule 40 PVC, Schedule 40 CPVC & 29-4C®- Feet (m)
61
50
39
(18.6)
225
(68.6)
573
(174.7)
(15.2)
211
(64.3)
556
(169.5)
27 (8.2) 16 (4.8)NANANANANANANANANANANA
(11.9)
184
170
157
143
465
130
(39.6)
446
(135.9)
(35.4)
197
(60)
538
(164)
(56)
521
(158.9)
(51.8)
503
(153.3)
(47.8)
484
(147.5)
(43.5)
(141.7)
Total Length of Pipe Schedule 80 PVC & Schedule 80 CPVC - Feet (m)
36
48
(14.6)
173
(52.7)
438
(134)
exceeds 50 feet.
(11.0)
161
(49.1)
426
(130)
24
(7.3)
(45.4)
(126)
NANANANANANANANANANANANANA
149
137
125
113
414
378
(115)
101
(30.8)
366
(112)
(41.8)
402
(123)
(38.1)
(34.4)
390
(119)
89
(27.1)
354
(108)
116
116
(35.4)
426
(130)
(130)
NANANANANANANANA
342
(104)
(101)
NANANANANANA
426
383
360
336
330
(116.7)
318
(96.9)
(110)
(102.4)
306
(93.3)
(89.6)
294
310
(94.5)
282
(86.0)
283
(86.3)
270
(82.3)
255
(77.7)
258
(78.6)
Page 9
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
PVC Adapter
when required
4" PVC Pipe
ENGLISH
Special insect screens installed
(see Figure 10)
Combustion
Air Pipe
7" min.
maximum snow level
Vent Exhaust
Pipe
18" min.
60" max
12" min.to
Page 9
6" min.
Grade level
or normal
snow
Clamping Connector
with Neoprene,
Nitrile or EPDM
Sleeve
(R0444900)
Hi-E2 Vent Collar
Figure 7. Indoor vent connection, Hi-E2 pool heater.
ve (5) elbows. Per Table 3, Only 16 feet of 4" vent
pipe would be allowable which would not allow for
completion of the run. Therefore the pipe size needs to
be increased. 140 feet of 5” piping would be sufcient
to complete the run.
2.7.3.4 Combustion Air and Vent Pipe
Installation
The Hi-E2 must be vented to the outdoors. Refer to Figure 7.
It must not be vented in common with any other appliance,
even if that appliance is of the condensing type. Common
venting can result in severe corrosion of the Hi-E
2 or of the
other appliances or their venting, or escape of combustion
product gases through such appliances or vents. Do not vent
the Hi-E
2 to a replace chimney or building chase.
Combustion air ducting, when provided, must not be
shared with any other appliance or with another Hi-E
2.
Doing so may result in ow of air through the other
appliances instead of directly from the outdoors.
The combustion air intake and vent outlet must be located
exterior to the building and in the same pressure zone - i.e.
both through the roof or both through a side wall. The vent
terminal must be located in accordance with local codes, as
applicable, and in accordance with the following:
1. Locate the vent terminal so that it will not be
damaged by pedestrians and other trafc, and so
that the discharge is not offensive. The National
Fuel Gas Code requires a through-wall vent
terminal be at least 7 feet (2.13 m) above grade if
Figure 8. Vent and combustion air terminals at
exterior wall.
Vent
Exhaust
Pipe
A
Plumbing vent
roof boot
Elbow
Combustion
Air Pipe
Insect Screens
Installed
(See Fig. 10)
18" min.
60" max
A
A=Maximum snow accumulation level plus 12"
Figure 9. Vent and combustion air terminals at roof.
located at a public walkway.
2. Locate the vent terminal so the vent exhaust does
not settle on building surfaces and other nearby
objects. Vent products may corrode such surfaces
or objects.
3.
Locate the vent terminal at a sufcient horizontal
distance from any gas or electric metering,
regulating or relief equipment. In the United States,
this distance must be at least 4 feet (1.22 m). In
Canada, it must be at least 10 feet (3.05 m).
4. Locate the vent terminal at a sufcient horizontal
distance from any building opening. Take special
care to assure that combustion products do
not enter a building through windows, doors,
ventilation inlets, etc. In the United States, this
distance must be at least 4 feet (1.21 m). In
Canada, it must be at least 10 feet (3.04 m).
Page 10
Page 10
Combustion
Air Pipe
ENGLISH
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
®
for such use. Joints in 29-4C
stainless steel pipe must
be sealed in accordance with its listing. Connection of
Vent
Exhaust
Pipe
combustion air and vent piping to the heater should be
serviceable — i.e. removable for heater service.
2.7.3.5 Room Ventilation
Elbow
Figure 10. Installation of insect screens.
Install special
insect screen
at end of pipe
inside coupling
or elbow. Cut
to size as necessary.
As shown in Figures 8 and 9, the combustion air intake
and the vent outlet must be installed no closer together
than 18" (45.7cm) and no farther apart than 60" (1.5m).
The combustion air inlet opening must face downward
to prevent entry of rain or snow. The vent outlet must
discharge away from the combustion air inlet - normally
in a horizontal direction when on a wall and vertically
upward when on a roof. Both should terminate at least
12" (30.5cm) above the snow accumulation level. In
locations with freezing climate, extension of the vent pipe
outside of the building should be minimized. The insect
screens provided with the heater must be installed at the
combustion air and vent pipe openings as shown in Figure
10. Insect screens are sized to t the inside of a 5" PVC
pipe tting. Trim them as necessary for smaller pipe sizes.
Connect the vent pipe to the heater vent collar with an air-
tight corrosion-resistant clamp. The connection must not
allow leakage of combustion products into the space but
should be removable for service. See Figure 7.
The room a Hi-E
2 is installed in must be provided with
adequate ventilation. Like other gas-red appliances, the
2 releases heat to its environment, and a room with no
Hi-E
ventilation may become too warm.
In one-pipe installations, the normal (code-required)
provisions for combustion air also assure reasonable
ventilation of the room. If a two-pipe system is installed,
ventilation must be provided by other means, such as
through grilles or openings or with a small fan.
2.7.3.6 Inspection and Replacement of
Existing Vent System with New
Components
If the Hi-E
2 is being installed to replace an existing pool
heater, it is recommended that a new appropriate venting
system be installed with the new heater. However, if
an existing venting system must be used, be sure to
carefully inspect the venting system to ensure that it is
in good condition and continues to be appropriate for the
2 heater. Replace any parts that are not in good and
Hi-E
serviceable condition with new parts before completing
the pool heater installation.
2.8 Condensate Disposal
In a high-efciency combustion process, combustion
product gases are cooled so much that liquid water is
condensed. Flow of this “condensate” can be quite high.
When pool water is very cold, as much as 2 or 3 gallons
Connect the combustion air pipe to collar of the air lter
box. For this combustion air pipe only, sheet metal pipe is
most convenient and can be screwed directly to the collar.
Seal the joint with silicone sealer or similar mastic material.
Install vent piping with a continuous rise of at least 1/4"
per foot (20 mm per meter) away from the heater. This will
assure that any condensate forming in the vent pipe will
ow back to the heater where it can be disposed of properly.
Support vent piping with suitable hangers so its weight
does not bear on the heater or building penetration and
so that piping joints are not strained. Support horizontal
runs at intervals no greater than 6 feet (1.82 meters), and
closer if necessary to avoid sagging. Sagging can trap
condensate water and block the vent.
Both combustion air and vent piping joints must be sealed.
Metal combustion air pipe joints should be fastened with
screws and sealed with permanent sealer or tape. Plastic
vent pipe joints must be made with solvent cement listed
Vent
Drain
To
Disposal
Collector
Drain
Blower
Drain
Trap/
Neutralizer
Figure 11. Condensate drainage components.
Page 11
®
Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
Jandy
ENGLISH
Page 11
of condensate can be produced in an hour. Condensate is
mildly acidic. Before treatment, its “pH” is typically in the
3.5 to 6.0 range.
Handling and disposal of condensate is not complicated,
but it must be done correctly to prevent problems or
complaints. A trap/neutralizer assembly is provided with
the heater to simplify installation. This assembly is easily
installed in the base of the heater. Figure 11 illustrates its
installation and the routing of drain tubes.
To install the condensate assembly, fi rst install the
short length of 5/8" I.D. tubing (Collector Drain) on
the barbed fi tting on the bottom of the condensate
collector. Then drop the condensate tray into the opening
in the base pan of the heater, bending the 5/8" tubing as
necessary to get the tube into the tray. Readjust the 5/8"
tubing so that its lower end is 1/4" - 3/8" above the bottom
of the tray. The tray can be positioned with the outlet tting
to the right, as shown in Figure 11, or with the tting to the
left, depending on the direction required for condensate
disposal. Connect the piece of 1/2" I.D. tubing to this
outlet tting and route it out of the heater through the hole
in the side of the base panel. This tube carries condensate
to the drain. If this disposal tube is routed to the left,
remove the plug button from the hole on the left side of the
base panel and push it into the hole on the right side.
Connect the remaining short piece of 3/8" I.D. tubing to
the barbed tee tting in the tubing immediately in front of
the blower. Position this tubing so that its bottom end is
1/4"-3/8" above the bottom of the condensate tray. This
tube provides drainage for the vent duct and blower.
A package of limestone gravel neutralizer is provided with
the condensate assembly. Remove the neutralizer from the
packing and spread evenly throughout the tray and around
the properly placed tubes. Be sure that a limestone pebble
does not plug any of the tubes.
IMPORTANT After placing the limestone neutralizer in
the tray add water until the water level is at the same
height as the overflow, see figure 12. Place the cover
on the tray when this is done.
It is important that there be no sagging sections of tubing
to trap water. Drainage to the trap and out of the trap
to the drain must be assured by continuous downward
routing of these tubes. It may be necessary to elevate
the heater to provide downward routing. The outlet of
the disposal tube must be open to the air. PVC pipe is
recommended for long drain tubes.
Condensate From
Vent/Blower Drains
Condensate
From
Collector
Drain
Water Level
Pushed Down
Water Level
Pulled Up
2"-3"
(50-75 mm)
Trap
Slightly
Overow
To
Disposal
1/4" - 3/8"
(6-10 mm)
Figure 12. Condensate drain and trap.
12 illustrates the water seal. Note that water is “pulled”
up toward the condensate collector pan and is pushed
down slightly by the vent/blower drain. If there is no water
seal, air rushes into the collector drain, preventing normal
drainage of condensate water, until vent drainage provides
the seal. See Section 2.12, Start-Up and Adjustment.
The installer must be sure to take whatever measures
are necessary to prevent property damage by condensate
over ow. If the heater location is such that this water
can directly or indirectly damage a building, furnishings
or other property, an over ow pan or other appropriate
preventative measure should be provided.
2.9 Gas Supply and Piping
Before installing gas piping, check the rating plate on the
heater to be sure that the heater is for use with the correct
(available) gas. Make sure that gas supply pressure is
adequate per the requirements in Table 4.
If a gravity drain is not available, a condensate pump
must be provided in the eld. Suitable condensate pumps
are available commercially at air conditioning equipment
distributors.
Incorrect installation of the condensate assembly or
tubing can result in over ow or waterlogging of the vent.
In normal operation, water accumulates in the tray at the
level of the outlet tting, and this provides a “water seal”
which accommodates combustion system pressures. Figure
PIPE
(
NIPPLE
SEDIMENT TRAP
3 in
(
Figure 13. Manual Shut-off Valve and Sediment Trap.
Page 12
Page 12
Table 4. Gas Supply Pressure Requirements.
Supply PressureMinimumMaximum
Natural Gas5 inches WC
LP Gas11 inches WC
ENGLISH
(125 mm WC)
(280 mm WC)
10.5 inches WC
(265 mm WC)
14 inches WC
(350 mm WC)
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
Gas piping must be large enough to provide the required
gas ow rate without excessive pressure drop. Table 5
species pipe sizes which will limit pressure drop to 0.5
inches WC (125 Pa), based on the National Fuel Gas
Code, ANSI Z223.1/NFPA-54.
Do not use exible appliance connectors on any gas
connections unless the connector is CSA approved for
outdoor installation and is marked with the BTUH capacity
(which must be equal to or greater than the heater rated
input) and the type of gas (Natural or LP). Also, any
exible connectors, such as CSST buried underground
must be certied for underground installation and meet all
applicable codes. Please note, use of exible connector still
requires the installation of a sediment trap per NFPA 54.
Table 5. Required Gas Pipe Size.
Natural GasLP Gas
Model
3501-1/4"1-1/4"1-1/2" 1"1-1/4"1-1/4"
0-50'
(0-15 m)
50-100'
(15-30 m)
100-200'
(30-60 m)
0-80'
(0-15 m)
50-100'
(15-30 m)
100-200'
(30-60 m)
Support gas piping properly so its weight does not bear on
the heater. Install a drip leg, a non-restrictive shutoff valve
and a union on the gas supply line outside of the heater.
See Figure 13.
Before operating the heater, test the gas supply system,
including all connections, for leaks using a soap solution.
Do not use a ame or any ignition source for leak
detection. Disconnect the heater and its individual gas
shutoff valve during pressure testing if the test pressure is
higher than 1/2 psig (3.34 kPa). If the pressure is 1/2 psig
(3.45 kPa) or lower, close the manual valve on the heater
gas control during testing.
When the heater is started, check the supply pressure
to verify that it is adequate during heater operation.
Undersize piping, a restrictive tting or an undersize gas
meter can cause low operating pressure.
High Elevation
To assure good combustion and general operation, gas
appliances may require manual de-rating when installed
at high elevation. This is not necessary with the Hi-E
2
because it has a special venturi-type combustion system
which self-compensates for changes in barometric
pressure. Air ow through the venturi pulls the correct
ow of gas into the burner regardless of air density.
Good quality combustion and high efciency are assured
without special adjustment or changes to the heater.
ATTACH GROUND-
ING WIRE TO
GREEN GROUND-
ING SCREW
(115 VAC ONLY)
Figure 14. Field wiring connections.
2.9.1 Special Precautions for LP Gas
LP Gas is heavier than air and can therefore more readily
collect or “pool” in enclosed areas if provision for proper
ventilation is not made. Installation of pool heaters in
enclosed areas such as pits is not recommended. However,
if such an installation is required be sure to pay special
attention to proper ventilation requirements for LP gas.
Locate heaters a safe distance from LP gas cylinders and
lling equipment. Consult the National Fuel Gas Code
(NFPA 54 / ANSI Z223.1, latest edition), the Natural
Gas and Propane Installation Code in Canada (CAN/
CSA B149.1, latest edition), and any other local codes
and re protection authorities about specic installation
restrictions in your area.
2.10 Electric Wiring
WARNING
ELECTRICAL SHOCK HAZARD. This heater contains
wiring that carries high voltage. Contact with these
wires may result in severe injury or death.
CAUTION
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous
operation. Verify proper operation after servicing.
2.10.1. Electrical Power
Electrical wiring must be in accordance with the latest
edition of the National Electrical Code® (NEC®), ANSI/
National Fire Protection Association® (NFPA) 70, unless
local code requirements indicate otherwise; and in Canada
with latest edition of CSA C22.1 Canadian Electrical
Code.
Page 13
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
H0205500F
ENGLISH
Page 13
SPA
Cuve Thermal
PV
24V
MV
Y
BURNER LIMIT
Limiteur du brûleur
BR
(SINGLE USE)
(Uniservice)
OFF
Arrét
POOL
Piscine
PSW
REMOTE CONNECTOR
Connecteur à distance
BK
PRESSURE SWITCH
(WATER)
Manostat (eau)
FIREMAN
Y/BK
GAS VALVE
Soupage de gaz
SWITCH
CONNECTION
Interrupteur
pompier
VENTURI. PRES. SWITCH
Interrupteur à pression
différentielle
VENT LIMIT
Limiteur de débit
BR
(MANUAL RESET)
(Remise à zéro)
TRTH
ELECTRONIC TEMP CONTROL
Régulation électronique de
température
WATER TEMP
SENSOR
Capteur de
température de l’eau
W
LIMIT
Limiteur
W
LIMIT
Limiteur
Hi-E2
W
Y
IGNITER
Allumeur
Y/BK
TRANSFORMER
Transformateur
R
Y
Y
W
BK
IGN240
W
IGN120
W
W
IGN/FS
IND
P
TH
VAL
BR
GND
Y
L1
L2
BK
W-R
W-BK
R
W
F1
F2
24V
FC
IGNITION
CONTROL
Commande
d’allumage
BK
BK
W
GY
BK
R
ELECTRICAL
FUSE
Fusible
R
Y/BK
IF ORIGINAL WIRE SUPPLIED WITH HEATER MUST BE REPLACED, APPLIANCE WIRING
Y
MATERIAL RATED FOR 105°C MUST BE USED.
Si le fil d’origine fourni avec le chauffee-eau doit être remplacé, utiliser un fil pour appareils
électriques à tolérance nominale de 105°C.
DIGITAL IGNITION CONTROL
L1
115V
G
60Hz
N
W
COMB.
FAN
Ventilateur
à
combustion
BK
BK-
Black
(Noir)
W-
White
(Blanc)
BR-
Brown
(Brun)
R-
Red
(Rouge)
Y-
Yellow
(Jaune)
G-
Green
(Vert)
P-
Purple
(Mauve)
GY- Gray (Gris)
FACTORY WIRED 24V
Cáblè en usine - 24V
FACTORY WIRED 115V
Cáblè en usine - 115V
FIELD WIRED 115V
Cáblè sur le terrain - 115V
Figure 15. Wiring diagram, Hi-E2 pool heater.
The Hi-E2 requires electrical power from a 115V, 60 Hz
source. Do not connect this heater to a 230VAC power
source. Wiring connections must be made exactly as
shown in the wiring diagram, see Figure 15. Grounding
must be provided as required by the prevailing electrical
code.
Connect wiring inside the junction box, which is on the
right side of the heater and is accessible through the door
opening. Line voltage connections must be made within
this box. A labeled green grounding screw is provided in
the junction box for a grounding wire. See Figure 14.
Wiring should include a means to prevent operation of
the heater when there is no water ow. This is typically
done with a time clock “Fireman’s Switch” as discussed
in Section 2.10.3.
2.10.2 Bonding
CAUTION
To prevent premature failure of the appliance resulting
from stray voltages and voltage differentials, the heater
must be bonded to other equipment which is part of
the pool plumbing system with a solid copper wire not
smaller in diameter than 8 AWG, 6 AWG in Canada.
Zodiac® requires that the appliance be connected to a
"bonding loop" that includes all electrical equipment in
the system and on the equipment pad. Bonding lugs must
be connected with a solid copper wire not smaller than
8 AWG (6 AWG in Canada). Failure to do so will void
warranty.
Page 14
Page 14
Figure 16. Typical time clock wiring.
ENGLISH
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
Additionally, in the United States the National Electrical
Code® and in Canada the Canadian Electrical Code,
require that all metallic components of a pool structure,
including reinforcing steel, metal ttings and above
ground components be bonded together (forming a
“bonding grid”) with a solid copper conductor not smaller
than a 8 AWG (6 AWG in Canada).
The NEC and the CEC also require that the equipment
and/or appliances associated with the pool water
circulating system, including, but not limited to, pump
motors and heaters be bonded together as part of the
®
equipotential bonding grid. Zodiac
provides a special
labeled bonding lug on the right side of the heater to
accommodate this requirement.
Figure 17. Terminal block for reman’s switch or
remote control wiring.
2.10.3 Auxiliary Time Clock Wiring
If a time clock is provided to control the pool lter pump,
it should have a separate low-voltage (Fireman’s) switch
for the heater. Route the heater’s 24 VAC control circuit
through this switch as shown in Figures 16 and 17. To do
this, remove the “jumper” from the terminal block in the
heater control compartment. Connect two (2) wires to this
terminal block and route them to the Fireman’s switch at
the time clock. Provide wiring of at least 18 gauge with
insulation at least 3/64" thick and having a temperature
rating of at least 90°C.
2.10.4 Remote Operation
The Hi-E2 pool/spa heater controls can be wired for
®
remote operation. The Jandy Pro Series AquaLink
RS
remote control permits switching from pool to spa, with
temperature set points for each, and turning the heater on
and off from a remote location. Contact your local Jandy
®
Pro Series distributor for information on the AquaLink
RS control system to t your back yard recreational needs.
Figure 18. Water connection as shipped.
An interrupt (on/off) type remote can be connected by
removing the jumper wire on the terminal block located
in the control compartment, see Figure 17 and connecting
the two (2) wires from the remote to the two (2) terminals
on the terminal block. This type of remote control will
turn the heater on or off, but will not switch between the
two (2) temperature controllers on the temperature control
panel or allow for temperature adjustments.
Figure 19. Water connection reversal.
Page 15
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
AQUAPURE
ENGLISH
Page 15
MANUAL BY-PASS DETAIL
MANUAL BY-PASS IS USED
WHEN FILTRATION RATE
EXCEEDS 125 GPM
Figure 20. Typical water piping.
2.11 Water Piping
2.11.1 Reversal of Water Connections
The Hi-E2 is shipped with water connections on the right
side, but it can be modied in the eld to provide leftside water connections. This is done by removing the
water headers and re-installing them opposite to their
original location. Some of the heater wiring and control
components must be relocated, so this change must be
done only by a trained service technician.
Water connection reversal is illustrated in Figures 18 and
19. Proceed as follows:
1. Remove the vent exhaust grille by removing the
four (4) screws which retain it. Retain these and
all other parts for later reassembly.
2. Remove the top cover by removing the screws
around the edges, under the overhang.
3. Remove the header covers. Note that the return
header cover is retained by wing nut fasteners
inside the heater.
4. Disconnect the pressure switch wires and remove
the pressure switch tube from the inlet/outlet
header by unscrewing the brass tting.
5. Remove the temperature control sensor by
removing the retainer bracket and its cap screws.
6. Disconnect the limit switch wires from the limit
switches. The limit switches and the short wire
between them may be left in place.
7. Remove both headers by unscrewing eight (8) cap
screws retaining each header.
8. Install the inlet/outlet header on the left side of the
heater and the return header on the right. Position
gaskets carefully to avoid water leaks.
9. Re-route the limit switch wires in front of the
venturi tailpipe and attach them to the limit
switches.
10. Re-route the temperature sensor wires in front of
the venturi tailpipe and insert the sensor into the
header. When the inlet/outlet header is on the left
side, the sensor opening is at the rear. Re-install
the retainer bracket and screw.
11. Re-install the pressure switch tube and tting.
Relocate tting.
12. Adjust wiring and pressure switch tube routing
so that they don't rest on sharp edges or on
the hot surfaces of the combustion chamber.
The combustion chamber is the portion of the
assembly just above the heat headers.
13. Re-assemble all other components and fasteners.
2.11.2 Pool/Spa Piping Systems
Figure 20 illustrates typical piping for pool equipment
in pool/spa combination pools. With its Flex-Temp
temperature control, the Hi-E
2 is particularly suitable for
this type of pool installation.
Page 16
Page 16
ENGLISH
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
Method For Installing
Any Threaded Pipe
Use
Plastic
Sleeve
For Nonthreaded Pipe
or Tube, Discard
Plastic Sleeve
Figure 21. Piping to heater.
The heater must be protected from back-siphoning of
water, which can result in dry starts. If there is any chance
of back-siphoning, provide a check valve between the
pool and the lter pump inlet.
Arrangement of pool system components other than as
illustrated in these diagrams can affect the operation of
the heater’s water pressure switch. Location of the heater
above or below the pool water surface can also affect
operation of the switch. In general, the pressure switch
can be adjusted to accommodate this effect if the heater
water connections are no more than six feet below the
pool water surface and no more than 15 feet above it. See
instructions for pressure switch adjustment in the heater
start-up section of this manual for more information about
this. Note that when pool equipment is located below the
pool surface a leak can result in large scale water loss or
ooding. Zodiac cannot be responsible for such water loss
or ooding or the damage caused by it.
Do not install a shutoff valve or any kind of variable
restriction in the water piping between the heater outlet
and the pool/spa.
Pool systems with water ow rates higher than 100 GPM
require an adjustable external bypass at the heater. See the
section on start-up and adjustment for this information.
2.11.3 Connections at Heater
The Hi-E2 has a universal water header and ange design.
With this feature, a variety of piping materials and sizes
can be used at the heater. 1-1/2" PVC or 2" copper pipe
can be connected directly to the heater using the rubber
“donut” gaskets provided with the heater. 2" PVC or metal
pipe can be threaded directly to the anges and 1-1/2"
schedule 40 metal pipe can be used with the rubber donut
gaskets. See Figure 21.
2.11.4 Pressure Relief Valve and
Temperature Relief Valve
A pressure relief valve (PRV) is recommended in all
installations, and is mandatory in any installation in which
the water ow can be restricted between the heater outlet
and the pool/spa. A pressure relief valve may also be
required by local codes and a pressure relief valve must
be provided in Canada. Be sure to check any applicable
installation codes in your area to determine whether a
pressure relief valve is required.
A pressure relief valve is not supplied with the Hi-E
2. All
equipment installations need to be in accordance with the
manufacturers instructions.
To install a pressure relief valve:
Water In
Figure 22. Pressure relief valve installation.
Out
1. Remove the 3/4" brass plug from the top of the
inlet/outlet header, see Figure 22.
2. Install the pressure relief valve in the opening.
Make sure to get a sung t. Do not overtighten.
3. Provide a short length of brass or stainless steel
pipe as necessary to position the valve above the
sheet metal cover.
5. The nal orientation of the pressure relief valve
should be vertically aligned with the discharge
opening facing away from the heater.
6. Install a discharge pipe from the pressure relief
valve discharge opening to a safe area. This is a
precaution to prevent the possibility of personal
injury or property damage in the event scalding
water is discharged from the pressure relief valve.
7. Install the discharge pipe so that there is no
trapped or standing water in the piping. Discharge
piping must be facing down, terminating with a
threadless nipple, no less than 6” from oor.
Page 17
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
ENGLISH
Page 17
The maximum working pressure of this heater is 75
psig. Be sure to take into consideration the maximum
allowable pressure of the other components in the system
when installing a PRV. Any pressure relief valve installed
must comply with provisions of the standard described in
ANSI® Z21.22 for the United Sates or CSA 4.4 in Canada.
Some local codes may also require installation of a
temperature relief valve. Check with your local codes for
requirements in your area. The valve setting should be in
®
accordance with local codes. Zodiac
recommends that
the water delivered to the pool not exceed 104°F. All
temperature and/or pressure relief valves must be listed
by a Nationally Recognized Testing Lab (NRTL) such as
CSA, UL, or ETL.
2.11.5 Automatic Chlorinators (Chemical Feeders)
A high concentration of chlorine (and many similar
chemicals) in the pool heater can be very destructive.
Heater damage caused by chemical concentration is not
covered by the Warranty. See Table 7 for guidelines on
pool water chemistry.
IMPORTANT Always install a corrosion resistant check
valve when any sanitation equipment, including erosion
feeders and salt chlorination systems are installed.
Wire an electric chlorinator so that it cannot operate unless the
lter pump is running. If the chlorinator has an independent
clock control, synchronize it with the lter clock.
energizes a “hot surface” igniter.
5.
The igniter is allowed to reach ignition temperature,
at which it glows bright red-orange. This is visible
through the combustion chamber view port.
6. The gas valve is opened and gas ows into the
combustion air. The gas/air mixture ows through
the burner into the combustion chamber. It is
ignited by the igniter.
7. The ignition control electronically senses
successful ignition by “ame rectication”, and
the gas valve is allowed to stay on. The igniter is
de-energized.
8. The heater operates for as long as the control
demands heat, subject to continued water ow
and satisfactory operation of the system.
9. When the control stops calling for heat, the
ignition control shuts off the gas valve and the
ame goes out.
10. The ignition control continues to operate the
combustion blower for a “post-purge” period,
after which it is turned off.
The process is repeated upon the next call for heat. If ignition
is unsuccessful, or if the ame fails during normal operation,
the ignition shuts off the gas valve. It imposes a post purge
and two (2) more ignition cycles, and it shuts down the
system if ignition is not achieved in three (3) cycles.
If the chlorinator is equipped with its own pump, install it so
that it introduces the chlorine downstream from the heater,
and, if possible, below the level of the heater outlet tting.
2.12 Start-up and Adjustment
2.12.1 Normal Operation
The Hi-E2 pool heater operates automatically. It provides
heat in response to the selector switch and temperature
settings on the control panel on the front of the heater. The
heater has internal controls to sense adequate water ow
and to handle any abnormal condition.
Normal operation is as follows:
1. The pool/spa system lter pump provides water
ow. A pressure-ow switch in the heater detects
water ow and enables the control to operate the
heater. (If the recommended reman switch has
been provided, it must also enable operation.)
2. If the selector switch is set to "Pool" or "Spa", and
if the water temperature is not warm enough, the
control signals the combustion system to start.
3. The ignition control starts the combustion blower.
4. When the venturi pressure switch detects
combustion air ow and when a suitable “prepurge” time has been allowed, the ignition control
2.12.2 Start-up
Before operating the heater, pour water into the
condensate tray and verify that it drains properly. Conrm
that pool water is owing normally through the pool
system and equipment. Start the heater in accordance
with the Operating Instructions section of this manual,
with particular attention to the lighting and shutdown
instructions and temperature control operation.
The heater may not start on the rst try. Air in the gas line
or other start-up situations may cause it to recycle. It will
lock out if ignition is not achieved in three attempts. To
provide three (3) additional attempts, turn the pool/spa
selector switch off and then back on.
Figure 23. Step-down gas pressure regulator.
Page 18
Page 18
ENGLISH
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
When the heater starts, immediately feel the outlet header
of the heater to conrm that there is adequate water
ow. The header should not be hot. Normally, water
temperature will rise only a few degrees as it passes
through the heater, and a “hot” header or pipe indicates
low water ow.
WARNING
When the heater is fired for the first time, the
combustion chamber refractory binder material is
driven out by the heat of the flame. White smoke and/
or sharp odors may be emitted from the vent during
this period. Do not inhale combustion product fumes
at any time, and especially when these fumes are
being emitted. This “burn-in” period will last only a few
minutes.
2.12.3 Condensate
If there is no water in the condensate trap, the heater’s
combustion blower will pull air into the lower drain hose
and normal drainage of combustion condensate will
not occur. This water will accumulate to blower inlet
level and will (temporarily) be blown out of the vent.
Eventually it will drain back to the tray and will "prime"
the trap. To avoid this "wet" start-up, simply pour water
into the tray before starting the heater.
2.12.4.1 Step-down Gas Pressure Regulator
The step-down regulator does not change requirements
for gas supply piping or pressure as stated in Table 4 and
measurements must be taken before the step-down gas
pressure regulator. In addition, it will not change any
of the servicing procedures for the venturi/combination
ow system. Gas supply must be as stated in the
installation and operation manual and on the heater
rating plate. Servicing procedures for the venturi/
combustion ow system must be as specied in the
installation and operation manual. Incorrect adjustment
of the combination gas control can cause improper heater
operation and hazardous combustion emissions.
To order this regulator as a separate part, please order kit
number R0337300, shown in Figure 23.
2.12.5 Adjustment of Water Pressure Switch
The pressure switch is pre-set at the factory for normal
pool installations. Do not adjust it unless the heater water
connections are more than three feet above or below the
pool surface. If they are not in this range, the pressure
switch must be adjusted. This can be done in the eld if
the water connections are no more than six feet above the
pool surface and no more than ten feet below it. For other
situations, contact a Jandy Pro Series representative.
2.12.4 Gas Pressure
Model Hi-E2 pool heaters include a step-down regulator to
reduce the pressure of gas entering the combination gas valve.
This regulator is factory set between 1.25” and 3.0” WC
regardless of whether natural or LP gas is used by the heater.
Conrm that gas supply is of adequate size per Section
2.9 of this manual. Conrm that the step-down regulator
is properly set by verifying that the pressure at the port on
the inlet side of the gas valve is 1.25 - 3.0 inches WC with
the heater operating (red).
Checking of gas pressure at the outlet of the gas valve
requires knowledge of the venturi system of the Hi-E2
pool heater. Do not attempt to adjust this pressure without
thorough understanding of its operation and settings, as
outlined in the maintenance section of this manual.
CAUTION
The water pressure switch should be adjusted to turn
the heater off when the pump is off. Setting the switch
to close at too low of a flow can damage the appliance.
Adjust the switch to turn the heater off, not on.
To adjust the pressure switch, proceed as follows. See
Figure 24.
The pool lter must be clean before making this
adjustment. The heater does not have to be ring.
1. Turn the switch to OFF, and make sure the
pressure switch is at its lowest setting. This is
done by rotating the adjuster counterclockwise as
far as it will go.
2. Start the lter pump and conrm by means of
an ohmmeter that the pressure switch closes (if
the switch fails to close, replace it with a switch
which has a lower minimum setting).
3. Turn switch to ON. Heater should start.
4. With your ngers, turn the adjustment sprocket
very slowly clockwise until the heater goes off.
SLOWLY TURN ADJUSTMENT
SPROCKET CLOCKWISE
UNTIL HEATER GOES OFF.
Figure 24. Adjustment of pressure switch.
Page 19
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
Figure 25. Temperature rise measurement at return
header.
5. Slowly turn the pressure switch adjustment
sprocket counterclockwise one-quarter turn. The
heater should come back on.
6. Check the adjustment by turning the lter pump
OFF. The burners should shut off immediately.
If they do not, restart the lter pump and repeat
Steps 6 and 7. Check the adjustment again.
7. Return the pool temperature control to the desired
temperature.
It may be necessary to repeat these steps to get a proper
setting. The switch must be set so that the heater will not
re unless the pump is running. If a proper setting cannot
be reached, contact the factory service department.
8. Reinstall the door.
2.12.6 Water Temperature Rise
The Hi-E2 pool heater has an internal bypass device which
accommodates a wide range of water ow. Its purpose
is to ensure that ow through the heat exchanger is
adequate to provide high efciency operation and prevent
overheating even though ow through the lter system
may vary.
Correct water ow should be conrmed upon start-up of
the heater and in most servicing situations. If ow is not
normal, corrections must be made to the pool system. If
the system has an external ow bypass (because of very
high lter system ow), it should be adjusted to provide
proper ow through the heater. Flow is evaluated by
determining the water temperature rise through the heat
exchanger.
ENGLISH
Page 19
inside the heater. Remove the brass plug on the top
surface of the header and install a Pete's Plug and pocket
thermometer. See Figure 25.
Proceed as follows:
1. If the piping system has a manual bypass valve,
close it.
2. Turn off the heater by moving the switch on the
temperature control panel to “Off”.
3. After three minutes, note and record the
thermometer reading. This is the pool
temperature.
4. Start the heater and let it operate for at least
ve minutes. Note and record the thermometer
reading. The difference between this reading and
the rst one is the temperature rise.
5. If the piping system has a manual bypass valve,
gradually adjust it until the temperature rise is in
the range required by Table 6.
6. Scribe a line on the bypass valve shaft and case
to mark the correct adjustment position. Wire the
handle to the pipe to prevent tampering.
Note that temperature rise is somewhat less when the
water is hot (spa application) and when heater is installed
at elevations signicantly above sea level. For high
elevation installations, reduce the numbers in Table 6 by
3% per 1000 feet above sea level.
Table 6. Water Temperature Rise and Flow Rates
(measured at return header).
Minimum
Model
35020 (11)29 (16)30
Temp Rise,
°F (C)
Maximum
Temp Rise,
°F (C)
Minimum
System
Flow
GPM
In a system without external bypass, it may be necessary
to make changes. If temperature rise is too low, a manual
bypass must be installed. If temperature rise is too high,
there is inadequate ow, possibly requiring a change to
the piping system or a larger pump. Before proceeding
with either remedy, verify proper heater operation. Low
gas input results in low temperature rise and vice-versa.
A problem with the heater internal bypass assembly also
affects measured temperature rise.
Before checking temperature rise, be sure the pool lter
is clean. If necessary, clean the lter. Temperature rise
is measured at the return header, which is on the side
opposite to the inlet/outlet header. For access, remove the
side cover, which is held in place by wing nut fasteners
Page 20
Page 20
ENGLISH
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
Section 3. Operating
Instructions
Lighting and shutdown instructions are posted inside the
heater.
WARNING
LP GAS: To avoid possible injury, fire and explosion,
read and follow these precautions and all instructions
on this appliance before starting the heater. LP
(propane) gas is heavier than air and will remain at
ground level if there is a leak. Before lighting, sniff at
ground level. If you smell gas, follow these rules:
1. DO NOT light matches. DO NOT turn electric
lights or switches on or off in area. DO NOT use
an electric fan to remove the gas from area.
2. Shut off gas at LP tank.
3. Telephone gas company and re department for
instructions. Give your name, address and phone
number.
If your LP tank runs out of fuel, turn off gas at the
appliance. After the tank is refilled, the appliance must
be re-started according to the instructions located on
the inside of the door.
3.1 Start-Up Procedure
WARNING
For your safety, when starting the heater, keep your
head and face well away from the burner area to
prevent any risk of personal injury.
WARNING
Vent pipes and heater tops get hot! These surfaces
can cause serious burns. Do not touch these surfaces
while the heater is in operation.
With any new pool or spa installation, run the lter pump
with the heater off long enough to completely clean the
water. This removes any installation residue from the
water. Clean the lter at the end of this operation before
starting the heater. Do not operate the heater unless the
pool is properly lled with water.
When raising the temperature of water in a cold pool,
remove all time clock settings. This lets the lter system
and heater operate continuously until the water reaches the
temperature setting on the thermostat. When that happens,
the heater will shut off automatically, but the lter pump
will keep running.
3.2 Temperature Controls
The Hi-E2 heater has a dual temperature control which
allows either of two (2) different temperature settings to
be selected with the rotary switch on the control panel.
The owner can set one control for normal use and the
other for standby, or one might be set for a pool and the
other for a spa. Setting the rotary switch to the middle
position turns the heater off. See Figure 26.
The temperature controls on the Hi-E
from approximately 70°F (21°C) to approximately 104°F
(40°C). Always use an accurate pool thermometer to
test the pool water temperature. To prevent users from
setting the water temperature higher than desired, use the
TEMP-LOK feature by positioning the tab next to the
knob and then tightening the screw. Note that the heater
should not be used to maintain pool or spa temperature
below 70°F (21°C).
IMPORTANT The temperature controls cannot be
calibrated in the field. If the temperature control
does not work, shut down the heater and replace the
temperature control. DO NOT use the temperature
control to shut the heater off. Remove the access door
and turn the main gas valve to OFF.
2 cover a range
CAUTION
Do not use this heater if any part has been under water.
Immediately call a qualified service technician to inspect
the heater and replace any part of the control system
and any gas control which has been under water.
CAUTION
Should overheating occur or the gas supply fail to shut
off, turn off the manual gas control valve to the heater.
CAUTION
Do not attempt repairs on the gas controls or appliance.
Tampering is dangerous and voids all warranties.
CAUTION
Keep all objects off the top of the heater. Blocking air flow
could damage the heater and might void the warranty.
3.3 Lighting and Shutdown
3.3.1 Lighting the Heater
Lighting and shutdown instructions are listed on the label
attached to the inside of the service door and also on the
inside of the control compartment door.
Lighting instructions are as follows:
1. Turn off all electrical power to the heater at the
main junction box.
2. Open the control compartment door and switch
the gas valve to OFF.
3. Turn the rotary switch on the temperature control
panel to OFF.
4. Wait 5 minutes before trying to start the heater.
5. Switch the gas valve toggle switch to ON. See
Figure 27.
Page 21
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
Jandy
Figure 26. Temperature control panel.
6. Replace the control compartment door.
7. Turn on electrical power to the heater.
8. Turn on the lter pump.
9. Turn the rotary switch to either SPA or POOL. Set
the temperature control to the desired setting. The
ignition control automatically lights the burner
when the thermostat calls for heat.
10. Set the time clock, if one is installed.
ENGLISH
Page 21
3.4 Water Chemistry
3.4.1 Pools
The mineral content of swimming pool water increases
daily, due to natural evaporation and the addition of
sanitizing chemicals. If the mineral concentration in the
pool gets too high, the excess minerals will deposit on the
walls of the pool, in the lter system, and in the heater
tubes. It is important to keep the pH factor of the pool
water between 7.4 and 7.6. See Table 7 for guidelines on
other chemical measurements.
3.4.2 Spas
The proper chemical balance in spa water is more critical
than in a swimming pool heater operation. Due to the spa's
size, high water temperature, and heavy usage, chemical
values in a spa can vary greatly. This chemical imbalance
can result in unsanitary water conditions, and affect the
life of the heater.
3.4.2.1 Spa Water Chemistry
3.3.2 Shutdown
Complete shutdown instructions are as follows:
1. Set both temperature controls to the lowest
setting.
2. Turn the rotary switch on the control panel to
OFF.
3. Turn off all electrical power to the heater at the
main junction box.
4. Open the control compartment door and switch
the gas valve to OFF.
5. Turn external gas valve off.
OF
F
ON
Figure 27. Gas valve.
GAS CONTROL TOGGLE
SWITCH SHOWN IN
“ON” POSITION
OFF
ON
Maintaining safe water conditions in a spa can only be
done by regular water changes and the proper addition of
sanitizing chemicals. Kits are available from your local
pool supply dealer for making the various tests for mineral
content. One of these kits will detect copper in the system.
This is usually a warning that corrosion is taking place,
possibly due to a low pH value combined with other
chemistry problems. The condition can be corrected by
changing the spa water and closely monitoring the pH
factor and chemical properties of the water. See Table 7.
Table 7. Chemical Concentration Levels.
TestRecommended
Level*
Free Chlorine or1.0 to 3.0 ppm (3.0 to 5.0 spa)
Bromine2.0 to 4.0 ppm (3.0 to 5.0 spa)
pH7.4 to 7.6
Total Alkalinity (TA)80 to 120 ppm
Calcium Hardness (CH)200 to 400 ppm
Cyanuric Acid30 to 50 ppm
Total Dissolved Solids (TDS) Less than 2000 ppm
Copper0 ppm
*Concentration levels taken from "Basic Pool and Spa Technology" published by APSP
(Association of Pool and Spa Professionals).
Page 22
Page 22
ENGLISH
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
3.4.2.2 Saturation Index
PH, Total Alkalinity (TA), temperature, Calcium Hardness
and Total Dissolved Solids (TDS) play a role in whether
the water is either corrosive or scale forming. These
factors are combined in the Langelier Saturation Index,
which is a method for determining whether or not water is
properly balanced.
Saturation Index = pH + AF + CF + TF -12.1*
A-Factor=(AF), C-Factor=(CF), T-Factor=(TF)
Total Alkalinity Calcium Hardness Temperature
A-FactorC-FactorT-Factor
PPM
5=0.75= 0.932=0.0
25= 1.425= 1.037=0.1
50= 1.750= 1.346=0.2
75= 1.975= 1.553=0.3
100=2.0100=1.660=0.4
150=2.2150=1.866=0.5
200=2.3200=1.976=0.6
300=2.5300=2.184=0.7
400=2.6400=2.294=0.8
800=2.9800=2.5105 =0.9
A saturation index of 0 is perfectly balanced
A negative saturation index has corrosive tendencies
A positive saturation index has scaling tendencies
A saturation index of +0.3 or -0.3 is ideal
*-12.1 should be changed to -12.2 if Total Dissolved Solids (TDS)
measure at 1,000 ppm or greater
Table 8. Water Saturation Index
Factor
Value
PPM
The practice of putting tablet-based sanitizer in the
skimmer basket can produce heavily chlorinated water
with very low pH. If this comes in contact with metal
parts of the heater it can cause serious damage. Practices
like this should be discontinued.
If acidic conditions are present, there could be signs of
metal in the pool water that could cause staining on the
oor of your pool. This might manifest itself in the form
of brown stains on the nish of your pool bottom or pool
water discoloration. Your local pool dealer can test for
metals in your water or can provide you with a test kit.
Every effort should be made to maintain the water balance
of your pool or spa in the proper range. Ignoring this very
important component of your pool’s water chemistry can
make the water less enjoyable to bathe in and result in
permanent damage to your heater and/or complete failure
of individual components.
Zodiac Pool Systems does not warrant heat exchangers
damaged by corrosive water issues or from the build-up
of calcium in the heater’s heat exchanger. Any questions
regarding proper water balance can be directed to our
product support line at Zodiac® or to your local pool dealer.
Factor
Value
°F
Factor
Value
3.4.2.3 Water Changing
Zodiac Pool Systems, Inc. recommends changing of
spa water every 60 days if usage is light and every 30
days during heavy usage. Be sure to stabilize the water
chemistry after every water change.
3.4.2.4 Corrosion
The corrosive action of pool/spa water is increased by the
following:
• Low pH - acidity
• Low Total Alkalinity - bicarbonates
• Low Calcium hardness - soft water
3.4.2.5 Testing
Zodiac recommends that spa owners purchase a test kit
and use it regularly. A minimum kit is one which will
measure chlorine and pH levels.
The pool/spa owner will nd it helpful to have a qualied
professional technician perform more extensive chemical
testing and water changing on a regular basis.
3.5 Spa/Hot Tub Safety Rules
The following "Safety Rules for Hot Tubs," recommended
by the U.S. Consumer Product Safety Commission should
be observed when using the spa:
1. Spa or hot tub water temperature should never
exceed 104°F (40°C). A temperature of 100°F
(38°C) is considered safe for a healthy adult.
Special caution is suggested for young children.
2. Drinking of alcoholic beverages before or during
spa or hot tub use can cause drowsiness which
could lead to unconsciousness and subsequently
result in drowning.
3. Pregnant women beware! Soaking in water above
102°F (39°C) can cause fetal damage during the
rst three (3) months of pregnancy (resulting in
the birth of a brain-damaged or deformed child).
Pregnant women should stick to the 100°F (38°C)
maximum rule.
4. Before entering the spa or hot tub, users should
check the water temperature with an accurate
thermometer; spa or hot tub thermostats may err
in regulating water temperatures by as much as
4°F (2°C).
5. Persons with medical history of heart disease,
circulatory problems, diabetes or blood pressure
problems should obtain their physician's advice
before using a spas or hot tubs.
6. Persons taking medications which induce
drowsiness, such as tranquilizers, antihistamines,
or anticoagulants should not use spas or hot tubs.
Page 23
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
ENGLISH
Page 23
Prolonged immersion in hot water can induce
hyperthermia. Hyperthermia occurs when the internal
body temperature reaches a level several degrees above
the normal body temperature of 98.6°F (37°C). Symptoms
include dizziness, fainting, drowsiness, lethargy, and an
increase in the internal body temperature.
The effects of hyperthermia include:
• Unawareness of impending hazard
• Failure to perceive heat
• Failure to recognize need to leave spa
• Physical inability to leave spa
• Fetal damage in pregnant women
• Unconsciousness resulting in a danger of drowning
3.6 Swimming Pool Energy Savings Tips
Zodiac® suggests the following to help conserve fuel and
minimize the cost of operating your pool heater without
sacricing comfort.
1. Set the heater temperature control no higher
than 78°F (26°C). The American Red Cross
maintains that the healthiest water temperature
for swimming is 78°F (26°C). Be certain you are
using an accurate pool thermometer because a
variance of 4°, from 78 to 82°F (26 to 28°C), will
use as much as 40% more gas.
2. Carefully monitor the water temperature of your
pool in the summer time, because heater usage
can be reduced due to warmer air temperatures.
3. Find the proper setting on the pool heater
temperature control and use the TEMP-LOK to
discourage further adjustments.
4. Set the lter time clock to start the pump no
earlier than 6:00 AM during the pool heating
season. This is the time when nightly heat loss
stabilizes.
5. If the pool is only going to be used on weekends,
reduce the heater temperature control setting by 8
or 10 degrees during the week. It should be reset
to the 78°F (26°C) level before expected usage,
keeping in mind to allow enough lead time for the
water to reach the desired temperature.
6. During the winter shut down the heater by
following the lighting and shutdown instructions
in Section 3.1. When on vacation for longer than
a week, make sure the heater is shut off at the
temperature control panel.
7. Where possible, shelter the pool from prevailing
winds with well-trimmed hedges or other
landscaping, cabanas, or fencing.
8. Always use a pool cover when practical. Besides
providing a valuable safety feature, a pool cover
will reduce heat loss, conserve chemicals, and
reduce the load on lter systems.
3.7 Seasonal Care
3.7.1 Spring and Fall Operation
During periods when the pool is only going to be used
once in a while, turn the temperature control to the "MIN"
setting. This prevents the pool from becoming "chilled,"
yet still requires the least amount of time to raise the water
back up to swimming temperature.
If the heater is not going to be used for a long period of
time, shut it down completely, following the instructions
in Section 3.3.2, Shutdown, or the lighting and shutdown
instructions posted inside the heater.
3.7.2 Winterizing
If you don't plan to use the pool or spa over the winter
and your area is subject to freezing temperatures, have a
qualied professional technician perform the following
steps to protect the heater:
1. Shut off the heater's gas valve according to the
lighting and shutdown instructions.
2. Shut off the main supply gas cock outside the
heater jacket.
3. Completely drain the heater before the rst frost.
To drain the heater, remove the side panel, and
remove the drain plug. See Figure 28.
4. Grease the threads of the drain plug and return it
to the manifold, but do not tighten.
5. Disconnect the copper tubing from the pressure
switch tting. See Figure 28.
6. Cover the vent grille so that snow will not
accumulate in the combustion blower, where it
may freeze.
Right Side
Remove Plug
Figure 28. Water header draining.
Page 24
Page 24
ENGLISH
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
To reactivate the heater in the spring, have a qualied
professional technician reassemble the heater as follows:
1. Attach the pressure switch tting to the copper
tubing. See Figure 28.
2. Tighten the drain plugs in the headers.
3. Clean the condensate drainage system and
condensate trap.
4. Replace the combustion air lter.
5. Uncover the vent grille.
6. Turn on the main supply gas cock outside the
heater jacket.
7. Turn on the heater according to the lighting and
shutdown instructions inside the top cover.
3.8 Periodic Inspection
WARNING
Improper installation or maintenance can cause
nausea or asphyxiation from carbon monoxide in flue
gases which could result in severe injury, or death.
3.8.1 Owner Inspection
The Hi-E2 heater has been designed and constructed to
provide long performance life when installed and operated
properly under normal conditions. The following basic
guidelines should be maintained:
1. Keep the top of the heater clear of all debris, and
make sure there is no collecting of ammable
materials, leaves, paper, etc., around or beneath
the heater.
2. Keep the pool heater area clean and free of all
combustible materials, gasoline and other liquids,
and vapors.
3. Do not use the heater if any part has been under
water. Immediately call a qualied professional
technician to inspect the heater and replace any
part of the control system and any gas control
which has been under water.
4. Check for spider webs and other debris at the
combustion air inlet and vent outlet — especially
at spring start up.
neutralizer and enough water to create a water
trap in the condensate drain assembly.
2. Replace combustion air lter. Refer to Section
4.4.
3. For heaters installed with combustion air or vent
piping, inspect screens at the inlet or outlet of
these pipes. Clean screens as necessary to assure
free ow. See illustrations in combustion air and
vent pipe installation section.
4. Make sure that the pressure switch operates
properly by shutting the lter pump off and on a
few times. The burner should go off immediately
after the pump stops. An ignition sequence should
start shortly after the pump is turned back on.
5. Make a visual check of the main burner ame.
The ame can be seen in a mirror/viewport
arrangement in the upper part of the heater. The
ame should be light blue and the burner surface
should be dark, with only a few glowing bers.
See Figure 29.
6. Inspect the gas and electronic controls, including
the following:
• High temperature limit switch
• Water pressure switch
• Venturi differential pressure switch
• Automatic gas valve
• Burner temperature limit switch
• Vent limit switch
• Temperature control
• Control circuit fuse
7. Perform a temperature rise test in accordance with
Section 2.12.
8. If the heater is equipped with a pressure relief
valve, clean any accumulated corrosion and make
sure that water runs freely through it.
9. Inspect the outside of the combustion chamber
and burner for corrosion and indication of
improper operation.
10. Regularly inspect electrical controls for
deterioration. Repair and replace as necessary.
NOTE Keep this manual in a safe place for future reference
by you and your professional technician when
inspecting and servicing the heater.
3.8.2 Professional Inspection
Inspection by a qualied professional technician,
performed at least once a year by a qualied professional
technician, are required to keep the heater operating
efciently through the years. The following basic checks
should be performed.
1. Inspect the condensate disposal system to be
sure that condensate ows freely and verify
that the condensate tray has sufcient limestone
Figure 29.
Burner ame (visible near top of heater in mirror).
Page 25
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
ENGLISH
Page 25
Section 4. Maintenance and
Service
WARNING
Improper installation or maintenance can cause
nausea or asphyxiation from carbon monoxide in flue
gases which could result in severe injury, or death. For
indoor installations, as an additional measure of safety,
Zodiac Pool Systems, Inc. strongly recommends
installation of suitable Carbon Monoxide detectors
in the vicinity of this appliance and in any adjacent
occupied spaces.
WARNING
To avoid the risk of exposure to unsafe levels of
Carbon Monoxide, which can result in serious personal
injury or death, always ensure that the combustion
air filter is properly installed and secured in the tracks
provided in the air filter box.
WARNING
SERVICING SAFETY
Some of the servicing procedures for the HI-E2
heater are hazardous because they involve fuel gas,
electricity, moving parts and procedures which require
testing or temporary bypass of safety controls. For this
reason, the heater must be serviced only by a qualified
professional service technician.
IMPROPER SERVICE HAZARD
The HI-E2 heater incorporates unique design features.
Incorrect service of this heater can result in personal
injury or damage to property. To avoid such hazards,
the heater must be serviced only by a qualified
professional service technician.
4.1 General
A qualied professional technician must service the Hi-
2 pool heater using Zodiac
E
calling for service, however, the owner should check for
obvious problems. The other components in the pool
system, including pump, lters and strainers, water valves,
gas supply, electrical power and time clocks, have an
effect on heater operation.
®
service procedures. Before
4.2 Induced-Draft Combustion System
The Hi-E2 pool heater has an advanced combustion
system which makes it highly efcient and reliable. This
system is illustrated in Figure 30.
A special corrosion resistant high-speed blower pulls
ow through the system and exhausts it to the outdoors.
Air is pulled into the system through a combustion air
supply duct, when provided, and through an air lter into
a venturi. The venturi functions much like an automobile
carburetor venturi - i.e. when air is forced through it, a
“negative” pressure is created at the venturi throat. This
negative pressure pulls gas through a metering orice,
resulting in an optimal mixture of air and fuel gas. The air
and gas are thoroughly mixed in the venturi tailpipe, pulled
through a special burner and ignited in the combustion
chamber. Hot combustion products are then pulled
through a highly efcient downward-ow heat exchanger.
Combustion products are cooled below their dew point and
condensate water is formed and drained away. Flow then
enters the blower, where it is forced out of the heater at the
vent terminal or through a vent pipe to the outdoors.
4.3 Heater Components and Their
Operation
1. Gas valve / Regulator - The gas valve controls
gas ow into the venturi. It provides ow only
when the temperature control require heat and
only if all safety controls enable operation. It is
also a negative pressure regulator. It regulates the
gas pressure to 0.2” WC less than the air pressure
at the venturi inlet. This is necessary for proper
operation of the venturi system and cannot be
done with common (positive pressure) gas valves.
2. Combustion blower - The combustion blower is
a specially designed to handle moist combustion
products, having special plastic housing and
impeller. It is powered by a brushless DC motor.
Conrm that the heater control is set to “pool” or “spa”
and that the corresponding temperature knob is set high
enough to make the heater operate. Make sure the pump is
operating, that the lter and strainers aren’t clogged, that
there are no mis-positioned water valves, that the gas or
electric power supplies aren’t shut off and that time clocks
are properly adjusted. Also be sure that the combustion air
lter is clean and that there is no blockage of the vent or
combustion air inlet. See later section on combustion air
lter service.
Figure 30. Combustion system diagram.
Page 26
Page 26
ENGLISH
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
3. Temperature Control - The control is an electronic
control which senses water temperature by means
of a thermistor and controls heater operation to
bring the water to that selected. It has two (2)
temperature setting knobs which are typically
used to set pool and spa temperatures. A selector
switch determines which setting is chosen.
4. Ignition Control - The ignition control provides
energy for ignition of the air/gas mixture,
monitors the ame and controls the combustion
blower and gas valve. When the temperature
control requires heat, the ignition control
starts the blower, providing a pre-purge of the
combustion chamber. Then it applies electrical
power to a “hot surface” igniter. When the igniter
is hot enough, it opens the gas valve. It has
sophisticated means to sense ignition and ame
condition so that unburned gas will not escape.
After the burner is shut off, it continues blower
operation to provide a post-purge period.
5. Igniter - The hot surface igniter is a ceramic
element which becomes very hot when electrical
power is applied to it. It functions both as an
igniter and as ame sensor. As a sensor, it is the
electrode through which the ignition control
detects “rectication” of current passed through
the ame. Inadequate rectication indicates an
unsatisfactory ame condition. The ignition
control responds to the ame signal provided by
the ignitor.
6. Venturi Pressure Switch - This switch veries
that air is owing through the combustion system
by sensing pressure reduction at the venturi throat
(relative to pressure at the venturi inlet). It shuts
off the heater if air ow is inadequate.
7. Limit Switches -
Two (2) limit switches prevent
excessive water temperature - both are just outside
of the heat exchanger outlet (slightly before the
mixed water stream). If either senses excessive
temperature, burner operation is interrupted.
8.
Water Pressure Switch - This control senses whether
or not water is available to the heater by measuring
back pressure inside of the heat exchanger. If the
pool water pump fails or the water lter is blocked,
the pressure switch prevents operation of the burner.
It can be affected by the installation conditions as
discussed earlier in this manual.
9. Burner Temperature Limit Switch - This is a
single-use switch which detects abnormal burner
temperature. It is a disc-type switch which is
held against the burner plenum by a sheet metal
bracket. It is not able to be reset. The burner limit
switch prevents or interrupts burner operation if
the burner plenum becomes too hot.
10. Vent Limit Switch - The vent limit switch
protects the vent system from excessive exhaust
temperature. It is located on the vent diffuser
above the combustion blower. It interrupts burner
operation if temperature becomes too hot for the
plastic materials used to vent the heater.
See the earlier section entitled Start-up and Adjustment
for the normal sequence of operation.
4.4 Combustion Air Filter
WARNING
To avoid the risk of exposure to unsafe levels of
Carbon Monoxide, which can result in serious personal
injury or death, always ensure that the combustion
air filter is properly installed and secured in the tracks
provided in the air filter box.
The combustion air lter is a rectangular foam
lter located in a box near the bottom of the control
compartment. The lter removes lint and large scale dust
particles to prevent blockage of the burner media.
The lter should be replaced annually in normal
service. Heavy use of the heater or operation in adverse
environments may dictate more frequent replacement,
however. It can be removed through the front of the lter
box as illustrated in Figure 31.
Remove the wing nuts retaining the front panel and slide
the panel out. Replace it only with the specied part
available from a Jandy Pro Series representative. Push the
replacement lter into the tracks and slide the panel back in.
Filter
Figure 31. Air lter replacement.
Page 27
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
ENGLISH
Page 27
4.5 Electrical Trouble Shooting
WARNING
ELECTRICAL SHOCK HAZARD. This heater contains
wiring that carries high voltage. Contact with these
wires may result in severe injury or death.
CAUTION
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and
dangerous operation. Verify proper operation after
servicing.
This section describes procedures for checking the electrical power and control components of the heater one at a
time and in the order they appear in the control circuit.
These procedures require a Volt-Ohm meter with 0-150
VAC range, and 0-1000 Ohm resistance range. Figure 32
shows the power and control circuits, and where to take
Hi-E2
measurements. Location numbers in circles have been
added, and will be referenced in the following sections.
As stated at the beginning of this manual, some of these
procedures are hazardous. Only a qualied service
technician should service the heater.
4.5.1 115V Electrical Power Supply
The electrical components of the Hi-E2 pool heater are
designed to operate with supply voltage ranging from
103V to 126V at 60 Hz. Measure supply voltage at the
“hot” and “neutral” wirenut connections in the heater
electrical junction box (identied as points A and B on
the wiring diagram). If no voltage is present, correct
this external to the heater. Circuit breakers, time clock
settings or similar devices may be the problem. Voltage
outside of the above range may be due to poor wiring,
poor connections, other loads such as air conditioning
compressors or to an electric utility company problem.
Arrange for correction of the voltage as appropriate.
4.5.2 Control Circuit Trouble Shooting
The heater controls are in a 24V 60 Hz circuit
with operating and safety controls basically
arranged in a series circuit. Trouble shooting is
done by probing for voltage at various points
in the circuit to determine which component
is preventing operation. Check points are
indicated on Figure 32. The recommended
procedure steps through the circuit in a
sequential way, but verifying voltage at any
of the numbered points conrms that all prior
components are OK. Experienced technicians
may be able to shorten the process by going
directly to one of the intermediate test points.
Figure 32. Wiring diagram with test points.
4.5.2.1 Transformer
Attach one lead of the voltmeter to the
transformer terminal with a yellow wire
attached to it, which is point 11 on Figure 32.
(This lead can be left in place for most of the
testing.) Touch the free lead of the meter to the
transformer terminal with a red wire, point 1.
The meter should show 20-28 volts. If there is
no voltage, replace the transformer.
4.5.2.2 Fuse
Leaving the “common” voltmeter lead in place
at point 11, touch the free probe to point 2.
This is the terminal block screw attached to
the red wire from the in-line fuse, and absence
of voltage indicates a defective fuse. If there
is no voltage, inspect the rest of the wiring to
be sure that there is no “short” such as contact
of a terminal with the heater chassis or another
F
terminal. Correct any such condition and
replace the fuse.
Page 28
Page 28
ENGLISH
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
4.5.2.3 Fireman Switch and External
Interlocks
Probe for voltage at point 3, the other connection of the
terminal block, which has a white wire connected to
it. If there is no voltage, the time clock switch or other
external interlock may be mis-adjusted, mis-connected or
defective. Correct this external problem.
4.5.2.4 Limit Switches
Probe for voltage at point 4, which is the water pressure
switch terminal with the white wire connected to it. This
switch is mounted on the end of a copper tube and is
about 2” in diameter. Absence of voltage at this point
indicates that one of the limit switches is open. This is
normally due to excessive water temperature, which should
be thoroughly investigated before replacement of limit
switches. Water ow deciency may be due to obvious
problems such as a defective pump or blocked water lter.
Alternatively, it may be due to overring, or to a problem
with the water piping or the heater's internal bypass control.
Overring might be a result of an incorrect gas orice or
supply of propane gas to a heater intended for natural gas.
If there are no such fundamental problems, identify which
of the switches is open by temporarily connecting a jumper
wire across its terminals. Replace a defective limit switch.
Limit switch access is through the side cover panel on the
side of the heater to which water pipes are connected.
NOTE The limit switches have different trip points, and it is
important that replacements are correct. The 150°F
switch has a red dot on the side of the brass fitting, and
must be installed closest to the combustion chamber.
The 135°F switch has no dot and must be installed in
the tapping closest to the water piping connections.
4.5.2.5 Water Pressure Switch
Touch the voltage probe to point 5, which is the other
terminal of the water pressure switch having a black wire
is connected to it.
If there is no voltage, the pressure switch contacts
are open. This is almost always due to a water ow
deciency, the most common one being a blocked water
lter. It may be due to causes cited in the previous
paragraph, however, and sometimes is due to blockage
of the copper tube or mis-adjustment of the switch.
Investigate thoroughly, referring to the earlier section on
“Adjustment of Pressure Switch”. If there is no problem
with the pool system or pressure switch adjustment,
replace the pressure switch.
4.5.2.6 Temperature Control
Absence of voltage at point 6 indicates that the control is
not calling for heat. Be sure that knobs are set to call for
heat as indicated earlier and as described in the Operating
Instructions section of this manual. Verify that the
thermistor sensor wires are not severed or shorted. Check
wiring connections by removing the temperature control
through the front of the bezel. If the control is properly
set and all wiring and connections are correct, replace the
control.
4.5.2.7 Venturi Pressure Switch
Touch the voltmeter probe to point 7, which is the
terminal of the venturi pressure switch having a purple
wire connected to it. If there is no voltage at point 7, the
venturi pressure switch is open, indicating inadequate
ow through the combustion system. The venturi pressure
switch is a differential type switch which is activated by
the pressure difference created when air ows through the
venturi. When the combustion blower is not operating,
the venturi pressure switch must be open and voltage will
not be present. See following sections on ignition control
"lockout" and combustion blower operation for possible
remedies.
Check for blockage at the combustion air inlet, a dirty
air lter or blockage at the vent exhaust or in the vent. In
improperly installed vent may trap condensate water, for
example, restricting ow. If there is no obvious problem,
analyze venturi operation as outlined in a later section of
this manual. If ow is normal, replace the venturi pressure
switch.
4.5.2.8 Ignition Control
There will be voltage at point 8, which is the “MVP”
terminal of the ignition control, only when there is an
attempt to ignite the burner or when the ignition control’s
ame sensing system has determined that it is OK to allow
burner operation. Even if voltage has been conrmed at
point 7, the “trial for ignition” sequence is imposed by the
ignition control. This sequence consists of a 15 second
period of pre-purge blower operation, a 40 second period
for heatup of the igniter and a 7 second trial for ignition,
during which there is voltage at point 8. If satisfactory
ignition is not achieved, the igniter is turned off and the
blower is operated for a 45 second post-purge. The system
may go through this cycle as many as three (3) times,
but thereafter it is “locked out” by the ignition control.
Additional attempts will be made only if the call for heat
is interrupted by turning off electrical power or setting the
control to “Off”.
Probe for voltage at point 6, which is the terminal of the
venturi pressure switch having a yellow & black wire
connected to it. This is the switch mounted on the frame
above the blower between the vent diffuser and the
venturi tailpipe. It is about 4” in diameter.
Page 29
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
ENGLISH
Page 29
To trouble shoot the ignition control, connect the voltmeter
probe at point 8 and set the control to call for heat. Observe
that the normal sequence takes place by noting blower
operation, the glow of the igniter through the combustion
chamber sight glass and then voltage at point 8. If the
blower does not operate or the igniter doesn’t glow,
investigate as outlined in a later sections. If both of these
components operate normally but voltage doesn’t appear
at point 8 during the trial for ignition, replace the ignition
control. If voltage appears at point 8 but there is no
ignition, proceed to analysis of other components.
4.5.2.9 Burner Limit Switch
The burner limit switch is located on the front surface of
the burner plenum near the top of the heater. Servicing this
switch normally requires removal of the top of the heater,
but it can be checked by probing for voltage at point 9 on
the vent limit switch. Point 9 is the terminal of the vent
limit switch to which is connected a brown wire coming
down from above. The vent limit switch is mounted on the
vent outlet diffuser above the combustion blower.
Voltage will be present at point 9 only during normal
operation or during a trial for ignition. If necessary
restart the heater using the control to obtain one of these
conditions. If voltage does not appear at point 9, the
burner limit switch is open. This may be due to burner
mis-adjustment, incorrect gas orice size or similar
problems which should be investigated as outlined in
later sections. If there are no such problems and there is
no evidence of excessive burner temperature, replace the
burner limit switch.
4.5.2.10 Vent Limit Switch
4.5.2.11 Combustion Blower
The combustion blower operates when it is provided with
115V, 60 Hz power. Conrm this by connecting the voltmeter
between the “neutral” wirenut and point C, which is the
terminal marked F2 on the ignition control. Unless the system
is in lockout, 115V should be present at point C whenever a
call for heat reaches the venturi pressure switch (i.e. 24V at
point 6). To be sure that a lockout condition is not in effect,
turn the heater off and then back on at the control.
If 24V is present at point 6 but 115V does not appear at
point C (and there is no lockout) the ignition control is
defective. If 115V power is available at point C and the
combustion blower does not run, the blower is defective
and should be replaced. Note, however, that the blower
has an internal overtemperature limit and before replacing
it conrm that the environment of the heater is not
excessively hot. If so, ventilation of the heater room may
be necessary.
4.5.2.12 Igniter
The igniter should glow during ignition attempts as outlined
in the earlier section on ignition control. If it does not,
connect the voltmeter between terminals marked D and E
on the ignition control. If 115V is present during the igniteron portion of the ignition sequence but there is no glow,
the igniter is probably defective. If voltage is not found, the
ignition control is defective and should be replaced.
An igniter which will not glow should be checked by
disconnecting the wires from the ignition control and
measuring the igniter resistance. A cold igniter should
have resistance in the range of 40 to 75 ohms. Replace the
igniter if resistance is outside of this range.
Probe for voltage at point 10, which is the gas valve
terminal having a brown wire connected to it. As in the
preceding case, this terminal will have voltage present
only during a trial for ignition or during normal operation.
If voltage is not found, the vent limit switch is open,
indicating that the exhaust temperature has been too high.
Normal vent temperature is between 100oF and 140oF.
Excessive temperature might be due to excessive water
temperature or overring of the system. Investigate
water temperature and possible water ow deciency.
Conrm that the heater is equipped for the correct fuel
gas - especially that propane gas is not being provided to a
heater congured for natural gas. To conrm correction of
the problem, re-set the switch by pushing the red button. If
vent temperature is normal and the switch will not allow
operation, replace it.
WARNING
The combustion blower, the igniter and some terminals
of the ignition control utilize 115V power and require
appropriate servicing precautions. Note that wires and
terminals of these components may be “hot” even
when the component is not operating.
4.6 Venturi Combustion Flow System
Verifying proper operation of the comustion ow system
has two (2) aspects - air ow and gas ow. Air ow
is checked by measuring pressures at service ports on
the venturi. Gas ow is checked by evaluating venturi
pressures plus the regulator offset pressure and the gas
orice size.
In a venturi ow system the difference between various
pressures is far more important than their “gauge” value
relative to the room. The gas pressure offset and the gas orice pressure differential are especially important
concepts. The following sections illustrate these and
related information.
Page 30
Page 30
ENGLISH
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
4.6.1 Pressure Measurement Ports
Figure 33 shows venturi and gas control components
and service port locations. Air ow enters the venturi
from below through the lter box. It is pulled through
a converging section to the throat, where pressure is
reduced substantially. Gas ow is pulled into the throat
through an orice inside the pipe between the throat and
the elbow. Air and gas are combined in the throat and mix
thoroughly as they proceed through the venturi tailpipe to
the burner.
Service ports are provided at three (3) places. On the right
side of the venturi an inlet service port is provided just
above the air lter box. Also on the right side, a throat
service port is provided - at the narrowest section of the
venturi casting. A gas valve service port is provided on the
outlet face (right side) of the gas valve.
To evaluate system operation requires accurate
measurement at these ports. A digital manometer, known
to be accurately calibrated, is ideal. Other instruments
may be used, but the “positive/negative” nature of the
readings must be very clear. Also, gas pressure offset
measurements are at very low levels (0.2” WC) and
the instrumentation must be capable of determining it
accurately.
Connect the positive side of the manometer to the venturi
inlet service port, which is at the bottom on the right
side. Connect the negative side of the manometer to the
gas valve service port, see Figure 35. Turn the heater on.
Until the heater res, the manometer will indicate several
inches of water pressure, but after the gas valve opens, it
will indicate the gas pressure offset, which should be 0.2”
± 0.1” WC - i.e. the gas pressure should be 0.2” WC less
than the pressure at the venturi inlet service port.
If the offset is incorrect, adjust the gas pressure regulator
to the correct pressure. This can usually be done while
the heater is ring, but the burner may go off when the
regulator seal cap is removed. In any case, the offset
pressure measurement must be read when the heater is operating and the seal cap is rmly in place. Note that a
special tool is required to remove the regulator cap.
Figure 36 shows the gas pressure offset reading when a
U-Tube manometer is used.
4.6.2 Venturi System Checkout
WARNING
When servicing is complete be sure to replace
pressure service port plugs and assure that pressure
switch and equalizer tube connections are unaltered
and firmly in place.
4.6.2.1 Gas Orice Differential
This measurement indicates how much “pull” is available
to move gas through the orice. Turn off the heater
and connect the manometer tubes with the positive side
connected to the gas valve service port and the negative
side to the venturi throat service port as shown in Figure
34. Turn on heater. The manometer will read zero until
the gas valve opens, and then it will indicate the gas
orice differential. The gas orice differential should
be 4.0” ± 0.3” WC for a unit at sea level. See section on
High Elevation Operation for other elevations.
Note the reading and turn off the heater at the control.
Then go on to the next measurement - gas pressure offset.
4.6.2.2 Gas Pressure Offset
Note that an equalizer tube is connected from a port on
the front of the venturi inlet to the vent of the gas valve
regulator. This is a very important component which
allows the regulator to track air pressure even when
abnormal things occur, such as blockage of the combustion
air. Before ring, conrm that this tube and the venturi
pressure switch tubes are in place and rmly connected.
VENTURI
THROAT
SERVICE
PORT
VENTURI
INLET
SERVICE
PORT
GAS VALVE
SERVICE
PORT
Figure 33. Venturi ow system components.
WARNING
In order to discourage incorrect adjustment by
unqualified persons, the gas valve regulator cap
requires a special tool for removal. Contact your
representative about a special tool for this cap.
WARNING
When servicing is complete be sure to replace
pressure service port plugs and assure that pressure
switch and equalizer tube connections are unaltered
and firmly in place.
Page 31
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
4.6.3 Air Flow Investigation
If gas pressure offset is correctly set but gas orice
differential is abnormal, check air ow through the system
per the following sections.
4.6.3.1. Unred Venturi Differential
Pressure.
Determine if air ow through the system is in a normal
range by operating the system with the gas valve turned
off. Connect the positive side of the manometer to the
venturi inlet service port, which is at the bottom on the
right side. Connect the negative side of the manometer
to the gas valve service port of the gas valve, see Figure
37. Turn the gas valve knob to "Off". Turn the heater
on by selecting "Pool" or "Spa" at the control and
adjusting the temperature setting high. The blower will
start immediately and the manometer will indicate the
"unred venturi differential" pressure. This is the pressure
difference created by airow through the venturi. It should
be approximately 4.7" ± 0.3" at sea level. See Section
4.6.5 for other elevations.
ENGLISH
-
+
Figure 34. Gas orice differential measurement.
-
+
Page 31
Note that when the heater is operated with the gas valve
off, it will eventually “lock out” because the ignition
control does not sense ame. Normally there will be
enough time to obtain the measurement, but if necessary,
additional blower operation can be induced by turning the
Flex-Temp control off and then back on again.
If the reading is not normal, attempt to correct it by
blower speed adjustment. Blower speed is adjusted by
turning a special screw on the right side of the motor - at
about 4 o’clock, see Figure 38. A small countersunk hole
is provided there for access to the screw, but is covered by
a thin silver-colored label. Remove or puncture the label.
A small at-blade screw driver is required. It must have
a 3/32” or 2.5 mm (.098”) blade and must be about
4-1/2” long. A jeweler’s screw driver or an electronics
pot adjustment screw driver (with handle cut short if
necessary) can be used. Insert the screw driver through
the hole on the motor housing. Turn it clockwise to
increase the ow and counter-clockwise to decrease.
If blower speed adjustment results in acceptable venturi
differential, shut off the system at the Flex-Temp control
and return to “Gas orice differential” measurement
per Section 4.6.2.2. Make a nal speed adjustment as
necessary to obtain correct gas orice differential.
If the system cannot be made to operate normally by
blower speed adjustment, investigate possible ow
problems per the following sections.
Figure 35. Gas pressure offset measurement.
To Venturi
Inlet Service
Port
To Gas Valve
Service Port
0.2" WC
Figure 36. Gas pressure offset measurement with
U-tube manometer.
Page 32
Page 32
ENGLISH
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
4.6.3.2 Combustion Air Flow
Begin by connecting the negative side of the manometer
to the venturi inlet and leaving the positive side open to
ambient, as shown in Figure 39. In a normally operating
heater, the pressure will be 0.2 to 0.6" WC less than
the ambient pressure. For a model 350 with clean lter
and no combustion air duct, the reading will be near
the middle. If combustion air is ducted to the heater,
the reading will be near the high end. If an excessive
reading is observed (i.e. more negative), ow is probably
restricted by a dirty lter or blockage in the combustion
air supply system. Correct any such problems and verify
normal operation by returning to the venturi system
checkout procedures.
Pressure readings will be less if the heater is located at an
elevation signicantly above sea level.
4.6.3.3 Flow in Heater and Vent
If the venturi inlet pressure reading is normal (or less
than normal), ow may be blocked within the heater or
in the exhaust venting, or the combustion blower may be
operating below standard. To evaluate this, connect the
negative side of the manometer to the collector pressure
tap, as shown in Figure 40, leaving the positive side open
to ambient (this requires a pressure tap with a 1/4" NPT
thread). When the heater is operating, the pressure at this
location should be about 2.8 ± 0.5" WC less than ambient
for a model 350. If a greater reading is observed (i.e.
more negative), ow is restricted within the heater, most
likely at the burner or the heat exchanger. If the reading
is substantially less (i.e. less negative), the combustion
blower is not operating properly or ow is blocked
after the blower, possibly in the vent. Correct any such
problems and verify normal operation by returning to the
venturi system checkout procedures.
Pressure readings will be less if the heater is located at an
elevation signicantly above sea level.
4.6.4 Fuel Gas Type and Gas Orice Size
Zodiac® congures its heaters for natural gas with 0.60
specic gravity and 1035 BTU/Ft3 or for propane gas
with 1.52 specic gravity and 2500 BTU/Ft3. Required
gas orices are listed in the replacement parts list. Consult
your Jandy Pro Series representative if the available gas is
substantially different.
4.6.5 High Elevation Operation
The venturi combustion ow system completely
compensates for installation at elevations other than
sea level. Gas orice changes are not necessary. Unlike
conventional systems with open type burners and positive
pressure regulators, the gas orice differential pressure
is created by the air ow, and it is automatically reduced
when air density decreased. A Hi-E
2 heater commissioned
at sea level will operate at nearly the same air/gas mixture
when operated at higher elevation. Its ring rate will
decrease about 3% per 1000 feet due to the barometric
pressure change.
that the input will be naturally reduced by this amount
and that the differential pressures, as discussed in prior
sections, will also be reduced. Pressure readings at various
elevations will be approximately as follows:
Elevation
Ft (m)
Sea Level
4000 (1220)3.4 (86)4.0 (102)
6000 (18303.2 (81)3.7 (94)
8000 (2440)2.9 (74)3.5 (89)
10000 (3050) 2.7 (69)3.2 (81)
The gas pressure offset is determined by the regulator spring adjustment, not air
density. It is not affected by elevation change.
Gas Orifice
Differential
4.0" (102 mm) WC
Unfired Venturi
Differential
4.7" (119 mm) WC
Page 33
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
ENGLISH
Page 33
4.7 Combustion Condensate
The condensate disposal system of the Hi-E2 pool
heater is quite simple, but must be properly installed
and maintained. See the installation instructions for
information on correct tubing installation. Condensate
drainage should be observed routinely and if necessary,
the ow-ways should be cleaned.
In normal operation, condensate drains from the
condensate collector behind the combustion fan. A 5/8"
I.D. drain tube conducts this water into the condensate
trap/neutralizer, where a “water seal” prevents room
air from being pulled into the system. The water seal of
the trap prevents vent gases from being discharged into
the room. A smaller amount of condensate may drain
from the vent duct and blower. See Figures 12 and 13
in the Condensate Disposal section of the installation
instructions.
During start-up, condensate from the collector cannot
reach the trap unless the water seal is established. This
can be done by pouring water into the trap. The heater
will self-prime by driving water into the vent outlet, from
which it will eventually drain into the trap. However, it is
better to avoid this by manually priming the trap.
If condensate is not draining from the system, check
for improper routing of the drainage tubes or blockage
in the drainage system. Tubing must be installed with a
continuous fall in the direction of condensate ow. Sags
may trap water, defeating the intended operation. Check
for blockage by disconnecting drainage tubes at the
collector and the vent diffuser. Probe these openings with
a tool or wire hook to dislodge any debris.
Limestone gravel neutralizer is required in the condensate
tray to prevent corrosion. This material should be replaced
once a year to assure its continuous benet. Replacement
®
packages are available from Zodiac
or its representatives.
It is normal that a blue/green deposit forms in the
neutralizer. This is caused by very small concentrations of
copper ions present in the condensate. By increasing the
pH of the condensate, the limestone causes this material to
precipitate and be retained in the gravel.
Figure 39. Venturi inlet pressure measurement.
4.8 Major Component Service
The venturi assembly, the burner assembly and the heat
exchanger tube assembly can be replaced if necessary,
but correct procedures and use of only factory-provided
parts are essential to assure satisfactory service and safe
operation. Sealing the system with the specied sealers
®
and gaskets is especially important. Contact Zodiac
Technical Support for information.
Section 5. Capacities and
Dimensions
5.1 General Information
• The Hi-E2 is design certied by CSA International as a
swimming pool heater under ANSI Standard Z21.56 for
use in the United States and Standard CSA-4.7 for use in
Canada.
• The Hi-E2 pool heater is certied for use indoors or
outdoors in the United States.
• The Hi-E2 pool heater is for use with natural or liqueed
petroleum gas. Ratings apply to either fuel.
• De-rating for elevation is not necessary because of the
Hi-E2 heater's special combustion system. Reduced
barometric pressure at high elevations naturally
decreases input and output by approximately 3 percent
per 1000 feet above sea level.
• Heaters require 115V, 60Hz electrical power.
• Working pressure 75 psig.
Figure 40. Collector pressure measurement.
Page 34
Page 34
Model
No
ENGLISH
With
W
11/16"
341/16"
InputShipping
Weight
35031 7/8350,000252 lbs.
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
231/2"
63/8"
W
5"
41/
165/8"
10"
16
"
21/8"
35/8"
Vent Collar
35/8"
215/16"
13"
Figure 41. Capacities and Dimensions.
Section 6. Replacement Parts
6.1 Ordering Information
To order or purchase parts for the Jandy Pro Series Hi-E2 pool and spa heater, contact your nearest Zodiac dealer or
distributor. Access the Zodiac web site at www.zodiacpoolsystems.com for the nearest service center. If it cannot supply
you with what you need, contact Zodiac Pool Systems, Inc. Technical Support Department at 800.822.7933.
NOTE To order the correct part, it is important that you state the model number, serial number and type of gas when applicable.
6.2 Parts List
Key Model ORDER
No. Description No. PART NO:
Limestone Gravel 350 R0306200
(condensate neutralizer)
Combustion Air Filter 350 R0308000
1 Base Panel 350 R0347105
2 Frame Support Assembly 350 R0301505
3 Back Panel 350 R0347205
4 Left Side Panel 350 R0347300
5 Right Side Panel 350 R0347400
6 Temperature Control Panel Assy 350 R0347505
7 Door 350 R0347605
8 Inlet/Outlet Header Panel 350 R0347700
9 Right Top Side Panel 350 R0347800
10 Return Header Panel 350 R0347900
11 Front Kick Panel 350 R0348005
12 Top Panel 350 R0348105
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
12
56
55
41
40
86
83-84
42
43
46
30A
32,33
35
30
34
10
38
13
16
48
39
37
36
14
17
68-70
44
65,66
45
3
4
6
29
9
54
53
51,52
50
18-23
15
24-28
49
85
87
1
75-81
7
64
61
2
8
5
67
58-60
11
62
72-74
63
Page 37
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
NOTES
ENGLISH
Page 37
Page 38
Page 38
ENGLISH
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
NOTES
Page 39
Jandy® Pro Series, Hi-E2® and Hi-E2R Gas-Fired Heater | Installation & Operation Manual
NOTES
ENGLISH
Page 39
Page 40
Zodiac Pool Systems, Inc.
2620 Commerce Way, Vista, CA 92081
1.800.822.7933 | www.jandy.com
ZODIAC® is a registered trademark of Zodiac International, S.A.S.U., used under license.
All other trademarks referenced herein are the property of their respective owners.