James Rebarscope R-C-400, Rebarscope R-C-450, Rebarscope R-C-410 Operator's Manual

Page 1
R-C-400, R-C-450, R-C-410
Rebarscope®
Original Instructions: Revision July 2018
Page 2

Notice

The Rebarscope® System has been tested in accordance with the EU regulations governing Electro-Magnetic compliance and it meets required directives.
Rebarscope® System is a registered trademark of James® Instruments Inc. and is property of its respective owner.
© 2018 James® Instruments Inc. All rights reserved.
No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without prior written permission of James® Instruments.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because James® Instruments is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, James® Instruments assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
Page 3
ACI 318
Building Code Requirements for Structural
2008
Concrete and Commentary.
We: James® Instruments Inc. Of: Chicago, IL In accordance with the following Directive(s):
2006/95/EC
Low Voltage Directive
hereby declare that:
Equipment
Rebarscope® System
Model Number R-C-400, R-C-450, R-C-410
is in conformity with the applicable requirements of the following documents
Ref. No.
Title
Edition/date
DIN 1045 Concrete, reinforced and prestressed concrete
Structures.
EN 61000-6-3 Electromagnetic compatibility (EMC). Generic
standards. Emission standard for residential, commercial and light-industrial environments.
EN 61000-6-2 Electromagnetic Compatibility (EMC)
Part 6-2: Generic Standards—Immunity for Industrial Environments.
BS 1881-204 Testing concrete. Recommendations on the
use of electromagnetic covermeters.
2008
2007
1999
1988
I hereby declare that the equipment named above has been designed to comply with the relevant sections of the above referenced specifications. The unit complies with all applicable Essential Requirements of the Directives.
Signed:
Name: Michael Hoag Position: President, James® Instruments Inc. Location: Chicago, IL On: 7/2/2018
Page 4

Table of Contents

Introduction ....................................................................................... 1
Data Logger Unit .............................................................................. 2
Instrument Contents List .................................................................. 3
Contents List ............................................................................ 4
Control Panel .................................................................................... 5
Control Panel Buttons .............................................................. 6
Menu Layout ..................................................................................... 7
Using the Rebarscope® on Location .............................................. 8
Removing the Lid ..................................................................... 8
Attaching the Shoulder Support Straps ................................... 8
Sensor Probe ................................................................................. 10
Short / Deep Mode ......................................................................... 11
Locating Ferrous and Non-Ferrous Metals .................................... 13
Option 1 – Graphic Bar Display ............................................. 13
Option 2 – Number Display ................................................... 13
Determining Cover ......................................................................... 14
Determining Bar Size ..................................................................... 17
Rebar Sizing Guidelines ........................................................ 23
Pitch & Resolution ................................................................. 24
Utilizing Cover Map Function .........................................................
System Menu ................................................................................. 30
Display Cursor ....................................................................... 30
Language Options ................................................................. 31
Measuring Units ..................................................................... 32
Clock Menu ............................................................................ 32
Erase Memory ....................................................................... 34
Battery Operation .................................................................. 35
Scan Cart (R-C-410 Only) .............................................................. 38
Data Handler Introduction .............................................................. 42
Features ................................................................................. 42
Minimum System Requirements ............................................ 42
Data Handler Overview .................................................................. 45
Software Functions ................................................................ 45
Software Installation ....................................................................... 46
Uploading Cover Map (R-C-450 and R-C-410 only) ...................... 50
25
www.ndtJames.com iii
Page 5
Contents
Uploading Scan Map (R-C-410 only) ............................................. 54
Graphic representation of the Scan Map data................................ 55
Troubleshooting ............................................................................. 58
Maintenance ................................................................................... 61
Safety ............................................................................................. 61
Available Rebarscope® Accessories ............................................ 62
Specifications ................................................................................. 63
Warranty Information ...................................................................... 65
Repair Policy .................................................................................. 70
iv www.ndtJames.com
Page 6

Introduction

Introduction
The James® Instruments Rebarscope® utilizes the latest in eddy current sensing and micro-processor technology to accurately locate, determine the depth of, and estimate the size of metal objects in concrete. The eddy current sensor is specifically designed to react to the outer surface of the metal object only. It is uninfluenced by small particles in the concrete, whether the concrete is fresh or hardened, wet or dry.
The Rebarscope® has built-in test modes for rebar/post tension cable, conduit and copper pipe. The sensor allows the unit to locate both ferrous and nonferrous metals in concrete.
With an easy to view display, the Rebarscope® provides the user with an instantaneous structural analysis. The user is aided by using a graphic bar in the display, and an audio tone to quickly and accurately locate metal objects. Large numbers in the display show the estimate of cover. This information can then be used to display a map of the cover throughout the structure. Further options allow a 2-dimensional cross-section of the concrete under test.
The Rebarscope® was developed for real world application and everyday durability in mind. It’s rugged and splash resistant case allows the user to use the Rebarscope® in the field. It’s small but sturdy sensing probe can withstand test after test with little wear on the probe face. Additionally, the Rebarscope® is able to compensate the sensor signal for a wide temperature range; as may be seen during in-situ field testing.
The Rebarscope® enables the user to store field test data, and later upload it to a Personal Computer. Once downloaded, the software allows the user to analyze the data, while a graphing tool function allows the creation of a contour map.
www.ndtJames.com
1
Page 7

Data Logger Unit

The data logger unit is a standard with the James® Instruments Rebarscope®. It is a sophisticated, rugged field proven unit. The embedded microprocessor technology enables the user to easily locate, determine the amount of cover, record, and analyze ferrous and non- ferrous metals.
The large easy to read numbers on the data logger display make the Rebarscope® user friendly when estimating cover or bar size.
Plus, with a memory capacity of 8000 data points, the data
logger
allows for a large sum of data to be stored for later
analysis. The front panel of the data logger unit allows the user to interface
with the sensor probe, scan cart, headphones, charger and a personal computer via a USB port. The large viewing window protects the LCD display from possible damages that may occur during operation. Additionally, large control buttons on the front panel enable the user to easily scroll through menu options.
www.ndtJames.com
2
Page 8
e

Instrument Contents List

Each Rebarscope® comes with the following items included in the carrying case.
Figure 1: Rebarscop
®
System Contents
3
www.ndtJames.com
Page 9

Contents List

Item # Description
Case – Used for carrying the Rebarscope®
1
and
Rebarscope® Instrument – Rebar locator encased
2
a durable protective case.
in
accessories.
3
Instruction Manual – Operating instructions for
Rebarscope®.
4
Calibration Certificate – Certificate to confirm that the
instrument has been calibrated to meet or exceed published specifications.
5
USB Cable – Serial cord used to connect the
Rebarscope® to a PC to upload data.
AC Power Adapter – Used to power the Rebarscope®
6
and recharge the unit.
7 Headphones – Used in noisy environments.
8 Sensor Probe – Shows direction of rebar.
9 Phone Jack – For headset.
10 8’ Coiled Cable – Used with the Sensor Probe. 11 1 5/8” Spacer Block – Used to add space in lower
cover situations.
12 3/8” Spacer Block – Used for sizing feature. 13 Locating Template – Used for sizing feature. 14
Support Strap – Used to secure the Rebarscope®
the user during testing.
to
15 Scan Cart – (opt.) Comes with Complete system only. 16 Scan Cart Extension Poles – (opt.) Used to guide
Scan Cart
17 Scan Cart Cable – (opt.) Yellow cable used to connect
Scan Cart to main unit.
4
www.ndtJames.com
Page 10

Control Panel

The following buttons appear on the James® Instruments Rebarscope® System.
www.ndtJames.com
Figure 2: Rebarscope® System Buttons
5
Page 11

Control Panel Buttons

Key Definition
The power button. Momentarily push this key to turn “on” the unit. Pressing it again turns off the unit. Upon power up, the unit will display the locate screen. Press the escape key to get to the Main Menu.
The up arrow button. This key is used to scroll through various settings and wave frames.
The down arrow button. This key is used to scroll through various settings.
The left arrow button. This key allows you to scroll through various settings.
The right arrow button. This key allows you to scroll through various settings.
The enter button. Pressing this key allows you to choose main menu selections. The enter key also allows you to prepare the Rebarscope® for operation.
The escape button. Pressing this key allows you to return to the main menu screen from any sub screen.
The back light button. Depressing this key the backlight of the display comes on. Depressing the key again turns the backlight off.
www.ndtJames.com
6
Page 12

Menu Layout

www.ndtJames.com
Figure 3: Rebarscope
7
®
Function Flow Chart
Page 13
For Quick Reference, in “LOCATE COVER” screen:
1.
For Automatic (RS), Short or Deep mode, go to line
and press the Left arrow button to change
between settings.
2.
For Audio Feature – go to and press the Right arrow button once for beeps, twice for continuous tone, and three times for audio off.
3.
Material Options – Rebar (Post Tension Cable) / Conduit / Copper.
System Menu

Using the Rebarscope® on Location

Removing the Lid

For ease of use in the field, the Rebarscope® lid can be removed the lid and
and the shoulder straps installed. To do so, fully open
the cover can be carefully pushed off of the case
hinge pins.

Attaching the Shoulder Support Straps

The Rebarscope® support straps can be used to hold the Rebarscope® once the Rebarscope® lid has been removed. When
using the Rebarscope® support straps, make sure that an
eyelet
hook is connected to each corner of the Rebarscope® . Two of the around the hinge
hooks clip to the O-rings, while the other two clip
pins.
Follow the step below:
1.
Attach the straight portion of the support strap to the
front metal O-rings of the Rebarscope®.
two
2.
Attach the other two straps (which are stitched to the straight portion of the harness) to the new exposed hinges
3.
Pull the supplied support strap over your head so that
rubber guard is resting on the back of the user’s
the neck.
www.ndtJames.com
of the case.
8
Page 14
4.
Now adjust the strap accordingly so that the Rebarscope® is within easy reach and readable. (see Figure 4)
Figure 4: Rebarscope® Support Strap
www.ndtJames.com
9
Page 15

Sensor Probe

The James® Instruments Rebarscope® utilizes the latest in eddy current sensing technology. The heart of this technology can be found in the sensor probe which has been specifically designed to react to the outer surface of metal objects. With this ability, the unit is able to accurately locate, determine the depth of, and estimate the size of metal objects within reinforced concrete structures. This makes the Rebarscope® sensor probe far superior to other commercially available rebar location systems.
The Rebarscope® sensing probe is compact, weighing only 1 lb
dimensioned at 5”x 2.4”x1.6” and still very tough and durable
and
field application. The sensing probe has been calibrated in our
for facility for operation with only the data logger unit it was purchased with. If a new sensor probe is needed it is recommended to send the complete unit in for proper calibration. Not calibrating the sensor unacceptable information office.
probe and the data logger unit together can cause
location, cover and bar size readings. For further
regarding repair and calibration please contact our
www.ndtJames.com
10
Page 16

Short / Deep Mode

The Rebarscope® facilitates the analysis of rebar location, cover and bar sizing; allowing the user to do measurements in short mode or deep mode. The Rebarscope® also provides the user the ability to automatically switch between deep and/or short mode.
Note: The single sensing probe operates efficiently in both modes. When the system is initially turned “on”, the Automatic (RS) mode is
the default setting. To change this, go to the Locate Cover screen.
Once in the Locate Cover screen, use the up or down arrow keys
on the front panel to highlight the graphic bar .
When the highlight is on the bar, press the left arrow key to change between modes. (Note: The letters RS in the upper left hand corner of the screen indicate auto ranging is “on”.)
Follow the procedure above to turn off Auto ranging, and to manually switch between Deep and Short modes as seen on line 1 of this screen.
www.ndtJames.com
Figure 5: Locate Cover Screen
11
Page 17
Short mode: Ideal when reinforcement cover ranges from .5” to
3.0”. Locating, determining cover and bar size can all be measured while in this mode. An error of ± .125” must be accounted for during measurement of metal bar or pipe location.
Deep mode: Ideal when reinforcement cover ranges from 2.75” to 8”. Locating, determining cover and bar size can all be measured while in this mode. An error of ± .125” must be accounted for during measurement of metal bar or pipe location.
Figure 6: Metric and Imperial Graphs for Rebar Ranges
www.ndtJames.com
12
Page 18

Locating Ferrous and Non-Ferrous Metals

The Rebarscope® uses eddy current sensing and micro-processing technology, and is ideal for locating ferrous and non-ferrous metals. Metals located with ease are the following:
Imperial and Metric reinforcement bars
Standard copper pipe
Standard conduit pipe
Post tension cable (use Rebar mode)
The Rebarscope® allows the user to locate metals by using two options on the LCD display.

Option 1 – Graphic Bar Display

The action bar displayed on the second line of the location screen enables the user to determine when the center of the metal bar/pipe has been detected. When the sensor probe is directly over the center of the metal bar/pipe, this bar display will have reached its highest point. When the sensor probe has passed the center of the metal bar/pipe, the bar display will decrease in size.

Option 2 – Number Display

This option consists of a numerical output value in brackets displayed on line 1 of the locate cover screen. The range of this number is 0 to 4095. As the probe moves toward the rebar/pipe the number will increase. Then when the probe is over the center of the rebar/pipe you will see the largest number displayed. As you move the probe away from the center of the rebar/pipe the number will begin to decrease.
This technique can also be useful in determining whether short or deep mode is necessary for proper location, cover, and sizing analysis.
www.ndtJames.com
13
Page 19

Determining Cover

The Rebarscope® allows the operator to easily determine the concrete cover of rebar. Since the Rebarscope® utilizes eddy current technology, cover is determined with even more accuracy than its predecessor. With this, only the bar/pipe is located and no small particles of metals (such as fly ash) in the concrete can influence the measurement. The following steps allow for proper cover measurements:
Step 1: Choose either Imperial or Metric units on the system menu screen.
Step 2: Decide whether short or deep mode is necessary for your testing. If needing to adjust this setting, go to the Locate Cover screen and follow the steps.
Figure 7: Locate Cover Screen
www.ndtJames.com
14
Page 20
Step 3: Using the down arrow key, scroll the highlighted section down to the bar diameter category. Once this line is highlighted, use the right or left arrow keys to choose the proper bar diameter.
Figure 8: Choosing Bar Diameter
Step 4: Now, pass the sensing probe on the surface of the test structure until the smallest cover is displayed on the right hand corner of the screen.
Step 5: The Rebarscope® allows the user to choose the minimum cover to analyze with. This feature is referred to as the S min. Using the up or down arrow key, scroll the highlighter down to the S min category and use the left or right arrow keys to choose an S min that ranges from 0.4 - 5.0.
www.ndtJames.com
Figure 9: Setting Minimum Cover
15
Page 21
Step 6: Now pass the sensing probe on the surface of the test structure until the smallest cover is displayed on the right hand corner of the screen. The audio/ headphone feature also allows
user to precisely locate the center of the rebar using the audio
the signal. This audio feature helps give even more cover precision. The steps below show how to properly choose the audio signal for your application.
Figure 10: Dynamic Bar Display
Step 6A: In the Locate Cover screen, use the up / down arrow
to scroll the cursor down to the action bar in the display.
keys Step 6B: Use the right arrow key to choose either a beeping type
audio signal, or a continuous tone audio signal. A small speaker icon will appear on the upper right hand corner of the display when the audio feature has been enabled. Headphones have also been supplied with the Rebarscope® to help the user hear a clearer audio
signal in noisy environments.
Step 6C: Pressing the right arrow key one more time after the continuous tone will turn off the audio feature, and the speaker
on the upper right hand corner will no longer appear on the
icon display
screen.
16
www.ndtJames.com
Page 22

Determining Bar Size

The bar diameter can be easily determined with the Rebarscope® without the prior knowledge of cover. This is possible by taking two readings, one at surface of the structure and another at the same location but 3/8 inches away. A 3/8 inch spacer block is provided with the system along with a locating template. This L shaped template helps keep the exact location of the first reading when taking the second reading with the 3/8 inch spacer block (see pictures below).
(Note: Bar sizing is done in Deep mode only, and at a maximum depth of approximately 4.5 inches.)
www.ndtJames.com
Figure 11: Locating Rebar
17
Page 23
Figure 12: 3/8” Spacer with L Shaped Template
Figure 13: Locating Rebar with Spacer
www.ndtJames.com
18
Page 24
www.ndtJames.com
Figure 14: Analyzing Data
19
Page 25
If the unit shows out of range in the BAR SIZE screen, and the display reading is 3000 or larger, this means the rebar is too close to the surface. The first reading should then be taken with the supplementary 1 5/8” spacer block, and the second with a 3/8” spacer block. See pictures below. (The supplement spacer block is used only to add space between the surface and the sensor probe. It’s size is not critical when performing the sizing function.)
www.ndtJames.com
Figure 15: 1 5/8” Block
Figure 16: 3/8” Block
20
Page 26
The following steps allow for proper bar sizing measurements:
Step 1: Press ESC to exit the Locate Cover screen. Step 2: In the Main menu screen use the up or down arrow keys to
navigate the highlight to the Locate category.
Figure 17: Bar Size Function
Step 3: Press the right arrow key on the front panel to choose Locate: Size and press Enter.
Step 4: In the BAR SIZE screen, use the sensor probe to locate the
center of the rebar either by using the bar display or the numerical output value in brackets [ ].
Figure 18: Bar Size Screen
www.ndtJames.com
21
Page 27
Step 5: Place the sensor on top of the surface where the rebar diameter is to be measured. If the reading on the first line is larger than 3000, use the 1 5/8 inches spacer block between the concrete surface and the sensor. If reading is still above 3000 it may be necessary to add an additional non-metallic block underneath the 1 5/8 block. (Note: The optimal cover range for sizing is between 1.7” and 4.2”. Also, the most accurate sizing of rebar occurs when the first measurement is about 1200.)
Step 6: Once the center has been determined, press Enter for a few seconds to store the result.
Step 7: The Rebarscope® will now read ADD BLOCK PRESS ENT on the top line.
Figure 19: Add Block is displayed
At this point the locating template needs to be placed alongside of the sensor probe; so the exact location of the first reading can be kept. Note: Taking the second reading at the exact location as the first is critical for precision. While holding the locating template, remove the sensor probe and place the 3/8 inch spacer block along the locating template.
Step 8: Now place the sensing probe over the 3/8 inch spacer block and press Enter. The Rebarscope® will now display the estimated diameter of the measured rebar. The Rebarscope® can accurately determine bar size up to a cover of 4.5" (115mm) in Deep mode.
22
www.ndtJames.com
Page 28
Figure 20: Estimated Diameter is Displayed
Rebar Sizing Guidelines
1. Sizing is done in Deep Mode only, and to a maximum depth of 4.5 inches (~114mm).
2. If the Rebar is too close to the surface (< 2.5 inches), use the 1_5/8” plastic spacer block (or some wood) to raise the sensor off the surface. (Rebar Size is best determined when the cover is between 2.5 - 4.5 inches.)
3. Sizing is also best determined when the rebar is isolated - no metal objects are near the sensor - including the main unit. This may require the user to move the main unit away from the sensor when testing for rebar size.
4. Sizing can be done when the rebar “on-center” spacing is equal to, or greater than 6 inches (~150mm) from any adjacent rebar, conduit pipe, copper pipe, post tension cable and wire mesh.
5. Sizing accuracy is +/- 1 Bar size for Imperial rebar, and ~ 3mm for Metric rebar sizes. This variance is due to the physical appearance of rebar, which has ribs (or ridges) along the length of the reinforcement bars. It is also due to the program settings of the unit itself. (Imperial sizes: 3, 4, 5, 6, 7, 9 & 11. Metric sizes: 6, 10, 13, 16, 19, 22, 25, 29, 32, 35, 38, 41 & 51mm.)
6. Due to the high concentration (and/or close proximity) of rebar within a Column, sizing (and location) is nearly impossible for a Column. It is not recommended to use the rebar locator for testing Columns.
www.ndtJames.com
23
Page 29

Pitch & Resolution

Measurements can often be influenced by neighboring parallel bar(s). The graph below shows the minimum spacing to a corresponding bar.
www.ndtJames.com
Figure 21: Minimum Bar Spacing
24
Page 30

Utilizing Cover Map Function

The James® Instruments Rebarscope® has incorporated a user friendly cover map to further assist in field analysis. The cover map mode allows the user to mark the cover and location of a rebar on a grid. The grid lines are numerically numbered with the Y axis starting at 1 from left to right. The X axis is also numerically numbered with number 1 starting at the top of the grid.
The Three symbols below have been selected to allow the user to distinguish the status of the current reading. A full shaded box represents that the cover is less than the selected S min. The S min is the selected minimum cover you have told the Rebarscope® to detect. A box with 3 thick shaded lines means that the cover is within range of the selected S min. A box with 3 thin inner lines means that the Rebarscope® has not detected a bar/tube.
Figure 22: Cover Map Symbols
Please follow this procedure to correctly prepare the Rebarscope® for Cover Map operations:
25
www.ndtJames.com
Page 31
Step 1: Press the escape key on the front panel to get to the Main Menu screen.
Figure 23: Cover Function
Step 2: Navigate the highlighted cursor using the up or down arrow keys to COVER MAP MENU option and press Enter.
Figure 24: Cover Map Menu
www.ndtJames.com
26
Page 32
Step 3: Choose whether you would like to INSTALL NEW MAP or VIEW OLD MAP by highlighting one and pressing Enter.
Figure 25: Install New Map or View Old Map
Step 4: If View Old Map is chosen please proceed to step 4B, if not please follow the instruction directly below for installation of a new map.
Figure 26: Map Display
Step 4A: 1
The Rebarscope® automatically generates a map number.
2
Under the Material category line, choose the material under
investigation. (rebar, conduit, copper)
3.
Choose the diameter of the material under investigation.
4.
Choose the S min (minimum cover)
27
www.ndtJames.com
Page 33
5.
Choose the detection range DEEP or SHORT, that the cover
analysis will be done in.
6.
Press Enter.
7.
The screen now displays the cover map grid.

Step 4B:

1.
After choosing to view old map a REVIEW COVER MAP menu
screen will appear.
2.
The system does not allow adjustment of previous set
Figure 27: Review Cover Map Screen
parameters.
3.
The only function that can be changed is that of which map to
view.
4.
Choose the map number to view and press Enter.
5.
The screen now displays the cover map grid with previously saved data. New data can be saved into the gridded map along with the older data.
28
www.ndtJames.com
Page 34
Step 5: Utilizing the Up or Down arrow keys on the front panel chose the location for your first mark.
Step 6: Pass the sensor probe over the area being investigated; the blinking cursor will turn into one of the three cover symbols.
Step 7: Pressing the Enter key will save that symbol onto the screen and store into memory the location information seen on the bottom of the screen. This information will also appear for this particular point on the upload screen of the PC software.
www.ndtJames.com
29
Page 35

System Menu

The system setup option on the main menu screen allows you to make modifications to system configurations. Once in the system setup sub menu modification can be made to the following
Display
Language
Units
Clock menu
Erase Memory
Battery operation
Pressing the escape key takes you back to the main menu screen

Display Cursor

To change the visibility of the display cursor, follow these steps:
Press the up or down key until you get to the system setup menu
option. Press Enter. The Setup Menu sub screen should appear.
Scroll through the Setup menu using the up or down arrow key. Select the Display option by pressing Enter. The display should read the following.
DISPLAY= Black Lines
Pressing the left or right arrow keys will give the user the option to choose Black (highlighted) Lines or White (highlighted) Lines, as well as the background color.
www.ndtJames.com
30
Page 36
Pressing the Escape key will return you to the Main Menu Screen.
Figure 28: Display with Black or White Lines

Language Options

To choose which Language the Rebarscope® will be operating in, follow these steps:
Press the up or down key until you get to the system setup menu
option. Press Enter. The Setup Menu sub screen should appear.
Scroll through the Setup menu using the up or down arrow key. Select the Language menu option by pressing Enter. The display should read the following.
LANGUAGE=
Use the left or right arrow keys to choose English or Spanish as the language that your Rebarscope® operates in.
Figure 29: Setting the Language
Pressing the Escape key will return you to the Main Menu Screen.
31
www.ndtJames.com
Page 37

Measuring Units

English and Metric units are available for the user to choose from. The following steps allow the user to choose the measuring units viewed:
Step 1: In the main menu screen use the up or down arrow keys on the front panel to navigate down to the system set up category.
Step 2: Press Enter. Step 3: In the system setup screen use the up or down arrow keys
on the front panel to navigate down to the UNITS category. Step 4: Use the right arrow key to choose either Imperial (English)
or metric measuring units.
Figure 30: Setting the Units
Step 5: Press the ESC key to go back to the main menu screen and continue measurements.

Clock Menu

To change date and time, please follow these steps:
Press the up or down key until you get to the setup menu option.
Press Enter. The Setup Menu sub screen should appear.
32
www.ndtJames.com
Page 38
Figure 31: Clock Menu is Highlighted
Scroll through the Setup menu using the up or down arrow keys. Select the Clock Menu option by pressing Enter. The display should be similar to the following.
Pressing the left or right arrow key will increment the digits on the
Figure 32: Setting the Date and Time
display.
Use the up and down key to select each hour and date options.
Scroll to the save changes option using the up or down arrow key.
www.ndtJames.com
33
Page 39
Pressing the Enter key will store the date and time and return you
Figure 33: Save Changes When Finished
to the Main menu screen.
Erase Memory
To erase stored memory from the Rebarscope®, follow these steps:
Press the up or down keys until you get to the system setup menu
option. Press Enter. The Setup Menu sub screen should appear.
SETUP MENU
Scroll through the Setup menu using the up or down arrow key. Select the Erase Memory option by pressing Enter. The display should read the following.

ERASE MEMORY

Press Enter once and a message telling you to press Enter again to verify this action should appear.
PRESS ENTER AGAIN
Pressing Enter a second time will erase ALL stored memory in the Rebarscope® system. When complete, the phrase “Ø errors” should be seen on the display screen.
Pressing the Escape key will return you to the Main Menu Screen.
www.ndtJames.com
34
Page 40

Battery Operation

The Rebarscope® uses a 14.4V Lithium-Ion battery with a built-in thermo-sensing circuit. This circuit allows for a suitable charge, and maintains the voltage to the cells (< 4.1V). Additionally, this circuit provides the proper charge current to lengthen the battery’s life.
At full charge, the bottom of the display will show BATTERY=100%. (Note: This value may be inaccurate, if the battery counters were reset without properly charging the unit.)
-
The battery status can be viewed in the “System Menu”, under the “Battery Operation” mode. (Fig.34 & 35)
-
When the charger is supplying power to the unit, the battery is charging, and the charge counter (“Charge CTR”) will increase.
-
When the unit is ON, and the charger is disconnected from the unit, the discharge counter (“Discharge CTR”) will increase.
-
The battery will continue to charge even after the microcontroller times out - display and unit turn OFF automatically.
-
When the mode is set to any of the following settings: Locate­Cover, Size, Statistic, or Cover Map (or Scan Cart for R-C-410) the charge operation is disabled.
www.ndtJames.com
Figure 34: Battery Operation Menu is Highlighted
35
Page 41
-- BATTERY STATUS-­DISCHARGE CTR = xxxx CHARGE CTR = xxxx DCR EXT = 0 CCR EXT = 0 Hit ENT to Clear Reg BATTERY = 100%
Figure 35: Clearing Charger Register

Battery Charge:

1.
Connect the charger to a working outlet, and then to the charger input on the unit’s front panel. Although, it is recommended for the unit to be OFF during a charge, the user can monitor the charging process in the screen above.
2.
If the Charge counter slows to a stop (and does not increase), this is an indication the charge is complete. The battery now has a full charge, and needs to be reset. To do this, go to: Main Menu / System Menu / Battery Operation - press “Enter” to zero the counters. This action also resets the battery circuit mentioned above, and will correct any miscounts. (If charging is still an issue, review the Troubleshooting section on p.57.)

Resetting the battery counters should be done both before and after (at least) a 4hr charge.

When done so, the battery status % on the display will be accurate.
3.
When the Battery percentage reaches ~ 40-50%, be sure to charge the unit again. (Go to step 1)
4.
A charged battery allows for 4-6 hours of continuous field testing.
5.
To extend the battery’s run time in the field, to turn “OFF” the background light.
www.ndtJames.com
36
Page 42

Simple Guidelines for Battery Maintenance.

1.
When allowed to discharge and charge regularly, the end user
will experience a better Battery life span (or cycle).
2.
Lithium-ion batteries do not need to be fully charged; as the
charger can aid its performance.
3.
Shallow discharges provide more cycles than deep discharges.
4.
It is recommended to fully charge the unit (4-6hrs) before a
lengthy field test is performed.
5.
As a general rule, it is best to charge the battery both before and after each use. There is no memory effect, so it is a good practice to recharge the unit after each use, or at the end of the day - if used daily.
6.
Charge the battery at a moderate temperature. Do not charge below 0deg C (or < 32deg F).
7.
Lithium-Ion batteries suffer from stress when exposed to heat. Therefore, to lengthen the life of the battery, avoid elevated temperatures > 30deg C (or > 86deg F).
8.
Lithium-Ion batteries may fail when stored for long periods of time in a discharged state. Thus, before a prolonged storage period, be sure to apply a charge to the battery. It's recommended once every 2 months to recharge the battery to keep it fresh. You should store the Unit (and battery) during this period at room temperature.
9.
Replacing or repair of the battery should be done by a trained James® Instruments technician. Please follow the repair procedure
found on page 68.
www.ndtJames.com
37
Page 43

Scan Cart (R-C-410 Only)

The Rebarscope® Scan cart feature allows the end user to quickly and easily determine the location and cover of reinforcement in a concrete structure. The scan cart can be used in a vertical or horizontal position. The B-Scan diagram generated by the Rebarscope® facilitates cover readings of a specified rebar.
The following steps allow for proper scan cart application: Step 1: Insert Rebarscope® probe in scan cart unit with company
logo facing up. Step 2: Connect scan cart cable (yellow) to front panel of
Rebarscope® unit and scan cart back cover.
Step 3: Turn Rebarscope® and allow unit to initialize. Step 4: Upon initialization unit defaults to Locate cover screen. Step 5: Press Esc key.
Step 6: Rebarscope® will now go to the main menu screen. Using
the up or down arrow to highlight the Scan Map Menu.
Step 7: Press Enter
www.ndtJames.com
Figure 36: Highlighted Scan Map Menu
38
Page 44
Step 8: The Scan Map Menu screen will now appear
Figure 37: Scan Map Menu
Step 9: Using the up or down arrow keys navigate the highlighted line to one of the three sections on the scan map menu screen.
Step 10: Press Enter. Step 11: The next screen allows you to enter your parameters.
After choosing desired parameters press Enter.
Figure 38: Scan Map Parameters
Step 12: The Rebarscope® now displays the scan cart diagram screen.
www.ndtJames.com
39
Page 45
Figure 39: Scan Cart Diagram
Step 13: Position scan cart at beginning of area to be analyzed. Step 14: Press Enter on Rebarscope® Front Panel. The display will
read “Scanner is ON”, and the user is ready to start testing.
now Step 15: Measuring from the front of the scan cart, begin pushing
the cart at a very slow pace from the starting point; using the extended handle. (See picture below.)
Step 16: Remain at this same pace until Rebarscope® notifies the end of scan by producing an end beep noise.
Step 17: The Rebarscope® does not present real time data of a scan, it is necessary to back the cursor toward the start point to view data. The results will be displayed in a B-Scan diagram.
www.ndtJames.com
40
Page 46
Figure 40: Scan Map Graph
The scan cart B-Scan diagram can be translated as follows:
Cover is represented on the left axis.
Distance measured is represented on the top axis.
The two dotted lines represent the predetermined setting for Smin.
The waveform will start at distance zero and it will be at its lowest
cover reading.
As the electro- magnetic decay of the reinforcement bar is detected by the probe, the built in B-scan analyzer starts to graph every point of detected cover by its built correlation.
Once the scan cart with inserted probe is above the center of a section of rebar the wave form will be displayed at its top peak.
After the scan cart has moved past the center of the rebar a very noticeable downward decay will begin to display. The wave form will remain at its lowest possible cover until another rebar’s electromagnetic decay can be detected by the scan cart.
41
www.ndtJames.com
Page 47
Operating System

Data Handler Introduction

The Data Handler allows you to accept uploaded data from
Rebarscope® to the PC
the

Features

Easy to Use
Quick
Convenient
Traceability
Data Backup

Minimum System Requirements Rebarscope® Data Handler

Windows Vista or Windows 7
Memory Processor Capacity
www.ndtJames.com
1 GB RAM 1 GHz Pentium class processor 1 MB hard drive space
42
Page 48

Upload Data (R-C-450 and R-C-410 only)

Connect the unit to the appropriate port of the P.C. using the
supplied serial cable.
Press the up or down key to advance to the upload menu option.
Figure 41: Upload Menu is Highlighted
Press Enter. The following upload sub screen should appear.
Figure 42: Upload Sub Screen
Scroll through the upload sub menu using the up or down arrow key. Select which upload menu function you would like to perform by pressing Enter. The display should read the following:

UPLOAD SCAN MAP (R-C-410 only) UPLOAD ALL SCAN MAPS (R-C-410 only)

www.ndtJames.com
43
Page 49
Pressing the left or right arrow key allows the user to select which
number of test data they want uploaded.
Open the Rebarscope® software (“Rebarscope” will appear on the
upper left corner) on the P.C.
Press the Lightning Bolt (Upload) icon. The P.C. software will
display “waiting for data”.
Go to the Rebarscope® and press the Enter key. Rebarscope® software waits 50 seconds for the upload information. If no data is received after 50 seconds a “No data received“ sub screen will appear.
During Test upload the displays reads “Upload In Progress”
Once the upload has been completed the display will read “Upload complete” and data will appear on the screen. Save the data in a desired folder.
Pressing the Escape key will return you to the Main Menu screen.
After upload, graphing of data should be done with PC software.
Press the graph icon to graph the B-Scan diagram on the PC.
www.ndtJames.com
44
Page 50

Data Handler Overview

The following is an overview of all of the features of the Data Handler software.
Figure 43: Data Handler Overview

Software Functions

Key Definition
The “Open” command (Ctrl+O) – Opens a previously uploaded text file.
The “Save” command (Ctrl+S) – Saves uploaded data to a text file.
The “Upload” command (Ctrl+U) – Uploads data from the Rebarscope to the Data Handler program.
The “Graph Time” command (Ctrl+T) – Graphs the stored data.
The “3D” command (Ctrl+D) – Graphs the stored data as 3D.
www.ndtJames.com
45
Page 51

Software Installation

The PC software that has been developed for the Rebarscope is for data upload purposes. To install the software on your PC follow these instructions.

To install the software:

1.
Insert the Rebarscope PC Software CD into the CD-ROM drive.
2.
If the CD does not load the setup automatically, go to My Computer, double click on the CD under devices and double click on setup.exe.
3.
The Install Shield Wizard checks for the operating system
Figure 44: Installation File Location
you are using.
www.ndtJames.com
Figure 45: Install Shield Wizard
46
Page 52
4.
The Install Shield Wizard dialog appears. Click Next to proceed.
5.
Accept the terms in the license agreement and click Next.
Figure 46: Install Shield Wizard
Figure 47: License Agreement Screen
www.ndtJames.com
47
Page 53
6.
Complete the customer information fields and click Next.
Figure 48: Customer Information Screen
www.ndtJames.com
48
Page 54
7.
The Install Shield Wizard confirms your installation. Click Install to continue.
8.
The installation progress screen appears.
Figure 49: Install Shield Wizard Confirmation
9.
When the installation has completed the following message will appear. Click Finish to close the dialog.
www.ndtJames.com
Figure 50: Installation Progress Screen
49
Page 55
Figure 51: Install Shield Wizard Completed
The Data Handler shortcut appears on the desktop as well
10. as the Start Menu.
www.ndtJames.com
Figure 52: Data Handler Shortcut
50
Page 56
Uploading Cover Map (R-C-450 and R-C-410 only)
Uploading a single Cover Map.
a.
On the Rebarscope® display, go to “Upload Menu”.
i.
Figure 53: Main Menu Screen
On the Data Handler Software press the Upload
ii.
Button.
iii.
iv.
On the Rebarscope® display, choose “Upload Cover
Map”.
Now save the results into the PC.
www.ndtJames.com
51
Page 57
Fig. 54: Rebarscope Data Handler Screen
The display should show the Cover Map as a text.
Fig.55: Data Handler Screen with Text Data
www.ndtJames.com
52
Page 58
b.
Uploading multiple Cover Maps.
On the Rebarscope® display, go to “Upload Menu”.
i.
Fig. 56: Main Menu Screen
ii. On the Data Handler Software press the Upload
Button.
iii.
On the Rebarscope® display, choose “Upload Cover
Maps”.
iv.
Now save the results into the PC.
Note: The Data Handler Software doesn’t provide graphical presentation of the Cover Map, as this only done inside the
Rebarscope® software. To view the cover map data:
-
From open menu or simply press the open button
or press “Ctrl + O”
Then open the required file in the Data Handle Software.
-
Also it is possible to open the Cover Map file as text file it.
simple by double clicking
Fig. 56
www.ndtJames.com
53
Page 59
Uploading Scan Map (R-C-410 only)
c.
Uploading a single Scan Map.
On the Rebarscope® display, go to “Upload Menu”.
i.
Fig. 58: Main Menu Screen
On the Data Handler Software press the Upload
ii.
Button.
On the Rebarscope® display, choose
iii.
“Upload Scan
Now save the results into the PC.
iv.
d.
Uploading multiple Scan Maps.
On the Rebarscope® display, go to “Upload Menu”.
i.
On the Data Handler Software
ii.
press the Upload On the Rebarscope® display, choose “Upload Scan
iii.
Maps”. Now save the results into the PC.
iv.
Note: It is essential to move the scan cart at a slow rate: bad readings.
(1 inch/sec maximum) to avoid
Map”.
Button.
www.ndtJames.com
54
Page 60

Graphic representation of the Scan Map data

1.
2D representation:
a.
Open a saved Scan Map data.
b.
Press the Graph Time command symbol.
c.
The software will show a 2D representation of Cover vs. Distance in inches, and it represents
cross section of the location that was crossed
a
the scan cart.
by
www.ndtJames.com
Fig. 59: Graph Window Screen
As shown in the example above (3 foot map), it shows the existence of a rebar at a distance of 11” (1.7”cover), 22.7” (1.7” cover) and 36” (0.9” cover).
55
Page 61
2.
3D representation: The 3D representation helps to show multiple Scan Maps
one graph, to use this feature; first it requires storing
in several Scan Maps (minimum two).
As shown in the figure to the
by taking several scan
left, readings, Scan Maps to the 3D option will these maps to generate a graph showing the peaks that represents the existence of a rebar and valleys that correspond rebar, also a color implemented that shows a rebar in the dark blue area of the are in
and upload all the
the computer,
arrange
3D
to absence of
code is
graph and the empty areas
green or orange color.
Fig.60
www.ndtJames.com
56
Page 62
Using the 3D graph option:
a.
Press the 3D command symbol.
b.
Set the Slice number to 1
c.
Browse for the first Scan Map, select it and click open, graph space.
d.
Set the Slice number to 2.
e.
Browse for the second Scan Map (usually all Scan Maps are save in the same location), select it and
open.
click
f.
The graph starts to form, and by adding more slices
graph will expand in the Z-direction.
the
g.
To export the graph, click “Export”.
h.
Choose s suitable format and click Save.
Fig. 61: Graph Window
at this stage nothing will appear on the
www.ndtJames.com
Fig. 62: Graph Window with Export Dialog Screen
57
Page 63

Troubleshooting

The James® Instruments Rebarscope® built in troubleshooting diagnostics helps the user identify problems with the system. This is a beneficial tool for the user which may help to resolve the problem without the need of sending the system “in” for repair. The troubleshooting diagnostics are the following: (a) Sensor Cable
Problem, (b) Sensor board Problem, (c) White Display, (d) Battery Charging problems, (e) Uploading Data issues. Follow
the steps below to properly diagnose the 5 problems listed:
(a)
Sensor Cable Problem Step 1: Check cable connections between sensor and front panel. Step 2: Check cable connectors for bent or pushed “in” pins. If yes,
the sensor cable problem will appear. Step 3: Check sensor and front panel connectors. If a pin(s) has
been bent or pushed “in”, the sensor connector cable problem will appear.
If steps 1 thru 3 do not correct the problem please contact our office for assistance and possible repair options.
(b)
Sensor Board Problem
Please Contact our Office for repair options.
(c)
White (or blank) Display
This error condition may occur when using the White Line setting of the Display mode (under System Menu).
In this condition, the Black background becomes White, along with the letters; thus making the entire screen White. To correct this issue, try the following steps… (Note: This is a blind operation; until the end.)
1.
Press the Escape button (x1)
2.
Press the Down button (x2) for Basic systems, and (x3) for
www.ndtJames.com
58
Page 64
Complete systems.
3.
Press the Enter button (x1)
4.
Press the Right (or Left) Arrow button (x1)
When completed, the display should become visible – with Black letters and a White background. If this does not reset the display condition, the user should Power cycle the unit “OFF”, and then back “ON”.
In the event this White Out condition remains, contact James® Instruments for further repair instructions. (or see Page 70)
(d)
Battery Charging Problems
This condition can happen when the Charge Counters have not been reset for some time, or… if there is a problem with the battery itself. (Note: The main battery usually lasts ~ 3-5 years.)
Before sending the unit to James®, try to Reset (or zero) the battery
System
Charge and be reset properly. Also, status value to
counters in the Battery Status screen. Go to: Main Menu /
Menu / Battery Operations - press “Enter” to reset the
Discharge counters to zero. These counters need to
periodically for the battery monitoring circuit to work
Zeroing these counters will change the battery
100%. This will happen whether or not the unit was charged. Therefore, after resetting the counters, charge the unit for at least 4 hours, and reset the counters again. Doing so will provide the most accurate % status of the battery.
If this does not correct the charging problem, the system will need to be evaluated further at James® Instruments. (See Repair Services
in the Calibration & Repair section.)
(e)
Uploading Data Problems
This condition can happen when first attempting to use the James® not being
Instruments software on a PC. It is due to the Comports
set to the same setting within the software.
www.ndtJames.com
59
Page 65
To find the correct Comport to use, follow the steps below…
1.
Go to the PC’s Device Manager… Start button / Control Panel /
Device Manager / Ports.
2.
Connect the USB cable to the unit. Then, while viewing the ‘Ports’ directory, connect the USB cable to one of the PC’s USB ports. The correct Comport setting will become visible in the ‘Ports” directory.
3.
When the correct Comport is found, go to the James® software, the correct
and click on ‘Tools’ in the task bar (at the top). Select
Comport (1-20) from the drop down list.
4.
Go back to the unit and select the Test Data to upload.
5.
Go back again to the software, and click on the Lightning Bolt icon in the task bar…
6.
Now press ‘Enter’ on the unit to start the upload process. The PC should say the computer is “Receiving Data”.
If these steps do not work, it is possible the correct Drivers need to be installed on the PC. Go to the following website for more help…
http://www.ftdichip.com/Drivers/D2XX.htm
(Note: Although James® does not support Windows XP (any longer),
the data handler should still work with XP.)
60
www.ndtJames.com
Page 66

Maintenance

If the Main 14.4V Battery does not hold a charge, the
system should come back to James® Instruments for battery before
replacement. (Review Troubleshooting section (d)
sending the unit back to James® Instruments.)
Calibration is recommended to be done annually, or
when
display readings are suspected to be inaccurate.
Keep the unit clean. If dust builds up in the unit, clean it
out
with compressed air.

Safety

Do not submerge unit in water. This can cause electrical
The sensor generates a magnetic field. Do not point the fields.
shock.
sensor on products that are sensitive to magnetic
www.ndtJames.com
61
Page 67

Available Rebarscope Accessories

Part # Description R-C-3015 R-C-3020 R-C-3030 R-C-3031 R-C-3035 R-C-3040 R-C-3051 R-C-3052 R-C-3056 R-C-475 S-31800
Probe Scan Cart Coiled Cable Scan Cart Cable Headphones Locating Template Basic Software Scanning Software USB Cable Scan Cart Upgrade Charger
www.ndtJames.com
62
Page 68
Specifications

Rebarscope® System R-C-400, R-C-450, R-C-410

Sensor Dimensions 5”L x 2.4” W x 1.6” H Sensor Weight 1lb Instrument Dimensions 10.625” L x 9.68” W x 4.875” H Instrument Weight 5.4
lbs
Complete System Weight 10 lbs Basic System Weight 8 lbs LCD Dimension 3.5”L x 4.65“H LCD Size 320 x 240 pixels Operating Temperature -10 - 50 C Covered Rebar Sizes (#) 3, 4, 5, 6, 7, 9, 11
Standard Copper Pipe Sizes .375, .500, .750, 1.00, .1.250 Standard Conduit Sizes .750, 1.00, 1.250
(mm) 6, 10, 13, 16, 19, 25, 29, 32, 35, 38, 41, 51
Power Source 14.4V, 4hr continuous use
63
www.ndtJames.com
Page 69

Warranty Information

1. Contract Unless otherwise stated all sales transactions are expressly subject to these terms and conditions. Modification or additions will be recognized only if accepted in writing by an authorized Officer of James® Instruments Inc. (hereinafter referred to as “James®” or the “Company”), or an officially designated representative. PROVISIONS OF BUYER'S PURCHASE ORDER OR OTHER DOCUMENTS THAT ADD TO OR DIFFER FROM THESE TERMS AND CONDITIONS ARE EXPRESSLY REJECTED. NO WAIVER OF THESE TERMS AND CONDITIONS OR ACCEPTANCE OF OTHERS SHALL BE CONSTRUED AS FAILURE OF THE COMPANY TO RAISE OBJECTIONS.
2. Warranties The Company only warrants the equipment manufactured or supplied by the Company as set forth herein. James® makes no other warranties, either expressed or implied (including without limitation, warranties as to merchantability or fitness for a particular purpose). In no event shall James® be liable for any type of special, consequential, incidental, or penal damages, whether such damages arise out of or are a result of breach of contract, warranty, negligence, strict liability or otherwise. Warranty shall not apply where the equipment manufactured or supplied has been subject to accident, alteration, misuse, abuse, improper storage, packing, force majeure, improper operation, installation, or servicing. In addition, the following shall constitute the sole and exclusive remedies of Buyer for any breach by James® of its warranty hereunder.
a. New Products James® warrants the equipment manufactured or supplied by James® as set forth herein. This limited warranty can only be exercised by the original purchaser of the equipment from James® or authorized James® Agent and is not transferable to any subsequent owner or party. This l imited warranty gives you specific legal rights, and you may also have other rights which vary from case to case.
i. For James® Equipment James® warrants that James's equipment will be free from defects in materials and workmanship for a period of twenty- four (24) months on the electronic portion and six (6) months on the mechanical portion from the date of shipment of equipment from James® to Buyer. Should any defects be found and reported by the Buyer during the applicable limited warranty period, the defect will be corrected upon return of the item to James®. James® will, during the applicable new equipment warranty period, provide the necessary replacement parts and labor to correct the defect.
Excluded from the new equipment warranty are all
www.ndtJames.com
64
Page 70
www.ndtJames.com
consumable and wear and tear items suc h as impact bodies, penetrators, connection cables, etc. These items are subject to usual wear and tear during usage. Refer to the Consumable, Wear and Tear Items section of this warranty document.
Option For Extended Limited Warranty Coverage The original purchaser of any new equipment of James® which have been identified or labeled by James® from time to time in James's sole discretion as being eligible for extended warranty coverage shall have the option to purchase certain extensions of the applicable limited warranty provided hereunder to the electronic portion of any such items for either a twelve (12), twenty-four (24) or thirty-six (36) month period (up to a possible maximum limited warranty coverage period for the electronic portions of such new James® equipment of sixty (60) months) by purchasing any such twelve (12), twenty-four (24) or thirty-six (36) month limited warranty extension period either all the time of the purchase of any such item(s) or within ninety (90) days from the date of delivery of the subject item(s) of the original purchaser of such item(s). The price for each such extended limited warranty coverage period shall be as determined by the Company from time to time and all such purchases of any extended warranty coverage periods shall only be effective upon a completed purchase order and payment directly between James® and the original purchaser of any such item(s). The extended warranty coverage periods
only valid with respect to the original purchaser of
are such item(s) from the Company and such extended warranty coverage is not transferable to subsequent owners of the subject item(s) or any other parties. Upon the purchase of any extended limited warranty coverage period, the Company will issue a certificate to Buyer evidencing the details of the applicable extended warranty coverage period purchased by the Buyer.
ii. For Other Manufacturer's Products Supplied by James® Products of other manufacturers supplied as such by James® are warranted by James® only to the extent of any warranty provided by the original manufacturer, if any.
iii. For Parts and Sub-Assemblies Parts or sub-assemblies purchased by the Buyer to perform its own repair work etc. are warranted as provided hereunder by James® for six (6) months from date of shipment of material from James® to Buyer.
65
Page 71
iv. For Consumables, Wear and Tear Items
James® supplies consumable items and items subject to wear and tear during normal usage of James® supplied products. These items are not covered under warranty. Buyer is to check for proper fit, form and function of such items upon receipt of such items. In case of a defect condition, Buyer can return the item to James® for evaluation within thirty (30) days of the date of shipment to the Buyer. James® reserves the exclusive right to issue full, partial, or no credit to the Buyer based on the condition of the returned item and circumstances related to the return. Examples of items in this category: connection cables, test blocks, impact bodies, penetrators, probes, extraction liquids, calibration liquids, pins, recording paper,
b. Calibration and Repair
test plugs, etc.
i. For Calibration Services James® does not warrant the calibration of any equipment. James® does however warrant the equipment manufactured by it, in proper working condition, to be capable of being adjusted to meet James® printed specifications, if any, for accuracy and performance as to the particular model type during the period of warranty applicable as stated above.
ii. For Repair Services James® warrants repair work performed under the direct control and supervision of James® personnel for a period of three (3) months from the date repairs are completed either at James® or at the customer site. Should the def ect for which the repair work was performed reoccur within this period, James® will supply the necessary parts and labor (repair at James® facility) or parts (repair at Buyer facility) required to repair the original equipment defect for which the repair parts and labor were required. Additional repair charges that may be incurred in conjunction with any repair service warranty event will be invoiced at the James® customer s ervice rates and policies in effect at the time of the event.
Excluded are all consumable and wear and tear items such as impact bodies, probes, connection cables, etc. These
www.ndtJames.com
66
Page 72
items are subject to usual wear and tear during usage. Refer to the Consumable Wear and Tear Item section of this warranty document.
www.ndtJames.com
67
Page 73
c. Warranty Claims
i. For Warranty Claim Processing James® has established James® organizations in the Americas, and Europe. Please visit the James® web site
www.ndtJames.com for latest address and contact
3. Regulatory Laws a nd/or Standards The performance of the parties hereto is subject to the applicable laws of the United States. The Company takes reasonable steps to keep its products in conformity with various nationally recognized standards and such regulations, which may affect its products. However, the Company recognizes that its products are utilized in many regulated applications and that from time to time standards and regulations are in conflict with each other. The Company makes no promise or representation that its product will conform to any federal, provincial, state or local laws, ordinances, regulations, codes or standards except as particularly specified and agreed upon for compliance in writing as a part of the contract between Buyer and the Company. The Company prices can not i nclude the cost of any related inspections or permits or inspection fees.
information for the James® organization nearest you.
4. Notices Notice by either the Company or Buyer will be made only by facsimile or similar electronic transmission, effective on the first business day after confirmed receipt, or by letter addressed to the) other party at its address as provided in this Agreement, effective three (3) business days after deposit with the U.S. Postal Services, postage prepaid, or one (1) business day after deposit with a recognized overnight express service.
5. Interpretation Should any term or provision contained In the contract contravene or be invalid under applicable law, the contract shall not fail by reason thereof but shall be construed in the same manner as if such term or provision had not appeared therein.
6. Assignability Neither this contract nor any claim arising directly or indirectly out of or in connection herewith shall be assignable by Buyer or by operation of law, without the prior written consent of Company. This document shall be binding upon and inure to the benefit of each party hereto and their respective permitted successors and assigns.
68
www.ndtJames.com
Page 74
7. Governing Law This Agreement shall be governed by and construed in accordance with the internal laws of the State of Illinois, without regard to its conflict of laws provisions. Buyer and the Company expressly agree to submit to the personal jurisdiction of the federal and/or stale courts silting in Chicago, Illinois, U.S.A. and agree that such courts may be utilized if necessary to obtain injunctive or any other relief. The Hague Convention and the United Nations Convention on Contracts for the International Sale of Goods shall not apply to the construction or interpretation of these Standard Terms and Conditions or affect any of its provisions.
END.
www.ndtJames.com
69
Page 75

Repair Policy

United States | Canada | International Ship the instrument in a box that meets UPS, Fed Ex, and standard
shipping regulations. Enclose a note describing the problem(s) you are having. Include the name and phone number of the contact person in your organization.
The instrument will be evaluated within one week of receipt. The contact person will be notified with an estimate of the cost of the repair.
Upon receipt of your authorization of repair and payment terms, delivery time will be 2 weeks from that day.
If you need the repair back sooner than this, you have the option of paying an express service fee of 10 percent of the purchase price of said instrument, plus the repair cost. With this service, you can receive the instrument back within 3 working days in the USA (5 working days for Europe).
International repair shipments must contain a commercial invoice listing the instrument being returned and must contain the words:
Country of manufacture: USA Instrument being returned to manufacturer for repair – no value for
customs, value for carriage only.
Ship the complete system to: Attn: Repair Department
Attn: Repair Department
James Instruments, Inc. - USA 3727 North Kedzie Avenue Chicago, IL 60618-4503 USA
Home page: www.ndtJames.com E-mail: info@ndtJames.com
europe@ndtJames.eu
www.ndtJames.com
James Instruments, Inc. Windmolen 22 7609 NN Almelo The Netherlands
70
Europe
Page 76

James Instruments Inc. 3727 N. Kedzie Ave. Chicago, IL 60618-4503 USA Tel: (773) 463-6565 Fax: (773) 463-0009

James Instruments Inc. - Europe Windmolen 22 7609 NN Almelo The Netherlands Tel: +31 (0)548 659032 Fax: +31 (0)548 659010

Purchase Date: ___________________
Serial Number: ___________________
www.ndtJames.com
71
Loading...