Jaga Room Thermostat JRT-200 installation, setup & user manual
Features
• for 2- and 4-pipe fan coil systems
• heating and cooling mode (4-pipe)
• heating and cooling mode (2-pipe)
• automatic or manual fan speed control
• surface-mounting
• 0-10V output
• valves 24V AC/DC or 230VAC
• it is possible (at manual control) to allow the fan to run once “set point” is reached
Technical Data
Power Supply 24V AC/DC
Power Consumption 200 mA
Set Point Range +10 > +40°C
Ambient 0 > +40°C
Relative Humidity 85% max
Backlight Blue
Sensor NTC 10K
Accuracy + 1°C (step control by +0.5°C)
Protection Class IP30
Housing ABS to UL94-5 fire retardant plastic
Product-documentation:
• this manual is an integral part of the unit and must be handed over to the user after the installation of the device is completed in order to comply with applicable legal requirements.
• please read the manual carefully so that you understand the information in order to ensure safety during installation, use and maintenance.
• no liability is accepted for damage resulting from non-compliance with the guidelines in this installation manual.
Dimensions
M
M
4.25
6.5
3 2.8
9.3
14
9.7
13.4
1.21.4
0.4
CE-mark
The CE-mark symbolizes the compliance of the device with the following guide­lines:
• EN 61000-6-3:2007+A1:2011
• EN 61000-3-2:2006+A1:2009+A2:2009
• EN 61000-3-3:2008
• EN 61000-6-1:2007
IMPORTANT: This manual will guide you through the installation, setup and use of the Jaga Room Thermostat JRT-200. Keep this manual in a safe place for future reference.
JR T-2 00
ATTENTION !!
1.5 m
The room thermostat must be installed at approx.
1.5 m above floor and out of reach of external influ­ences such as direct sunlight, draught or other heat sources as they may impede the correct functioning of the thermostat. Nearby electric fires, televisions, wall or table lamps may prevent the thermostat from working properly. Ensure that there will be enough space to allow easy access to the two retaining screws, located at the bot­tom of the wall plate.
6
2.8
Mount the JRT-200 Room thermostat on a wall re­cessed box (60.3 mm fixing centers) or direct onto a flat
wall using wall plugs.
Deze handleiding in het NEDERL ANDS: Ce manuel en FRANÇAIS: Dieses Handbuch auf DEUTSCH: This manual in ENGLISH:
www.jaga.be/downloads/Briza/Manual_JRT200.pdf
Page 2
25 juni 2018, 8:45 - Jaga N.V.
Jaga Room Thermostat JRT-200 installation
Installation
WIRING: Warning: The installation of the thermostat should be performed by qualified personnel and must comply with the applicable
local and national electrical codes and utility requirements. All wire connections must be tightened and properly arranged to prevent a shortcircuit. Turn off the power at the electrical panel to prevent electrical shock or product damage.
To remove the wall plate, use a Phillips screwdriver to loosen the two screws from the bottom of the wall plate
Remove the front panel When not using a recessed conduit box:
• mark out and drill the holes
• screw the device to the wall. The type of wall, solid or cavity, determines
the type of screw or plug that is used.
24V AC/DC
M
1234567891011
M
M
• flush wiring can enter from the rear through the aperture in the wall plate
• connect the JRT-200 according the wiring diagrams** on this page
Reassemble the front panel Tighten the screws with a Phillips screwdriv-
er. (Do not over-tighten.)
Warning: Turn off the power at the electrical panel to prevent electrical shock or product damage.
** Wiring diagram
2-Pipe 4-Pipe
1234567891011
1234567891011
H/C VALVE
0...10V
COM
0...10V
COM
KEY CARD
-
+
L
N
24V / 220VAC
DC 24V
DC 24V
C VALVE
H VALVE
KEY CARD
-
+
++-
-
L
N
24V / 220VAC
1234567891011
0...10V
COM
DC 24V
C VALVE
H VALVE
KEY CARD
-
+
+
-
L
N
24V / 220VAC
H/C Heating / Cooling C Cooling
H Heating GND N
Page 3
25 juni 2018, 8:45 - Jaga N.V.
Jaga Room Thermostat JRT-200 setup / user
Control panel
Clock
Programming & week / day On / Off
Room temperature
Set temperature
M
1 2 3 4 5 6 7
h
ROOM
SET
°C
1 2 3 4
Temperature / parameter setting
Fan Speed setting
Fan speed:
Temperature / parameter setting
Heating / cooling
Low
Mid
High
Auto fan
Heating
Cooling
Programmable Time setting
• press the “M” button for 5 seconds to enter clock setting ( ) and day setting
• enter 5+1+1 programmable mode
• press “+” and “-“ to set the thermostat on/off time
• next mode setting: toggle trough the menu with the “M” button. Activate the programmed time: press and hold the “ “ button for 5 seconds.
To deactivate the programmed time: press and hold the “ “ button for 5 seconds
Week
1st time zone 2nd time zone
Turn on Turn Off Turn on Turn Off
Icons
1
2 3 4
2
3 4
3
4
4
12345 (Monday~Friday) 8:30 12:00 14:00 18:00
6(Sat.) 9:00 12:00 15:00 18:00
7(Sun.) 9:00 12:00 15:00 18:00
Page 4
21/12/ 2018, 8:45 - Jaga N.V.
Wiring connections
Disconnect the power supply before making wiring connections, to prevent electrical shock and equipment damage.
Jaga Room Thermostat JRT-200 installation manual
2-Pipe system 4-Pipe system
Briza Clima Canal Quatro Canal
....
- 24 VDC
+ 24 VDC
0..10 V
L
+ -
N
230 VAC L1 N
+-
+-
1234567891011
H/C VALVE
COM
KEY CARD
L
N
24V / 220VAC
DCV24
0...10V
Briza Clima Canal Quatro Canal
....
- 24 VDC
+ 24 VDC
0..10 V
L
+ -
N
230 VAC L1 N
Briza Clima Canal Quatro Canal
....
- 24 VDC
+ 24 VDC
0..10 V
L
+ -
N
230 VAC L1 N
+-
+-
+-
+-
1234567891011
H/C VALVE
COM
KEY CARD
L
N
24V / 220VAC
24V DC
1234567891011
C VALVE
H VALVE
0...10V
KEY CARD
L
N
24V / 220VAC
DCV24
COM
0...10V
H/C Heating / Cooling C Cooling
H Heating GND Ground
Parameter settings
• set Power Off, bij pressing the “ ” button
• to access the MENU , press and hold “M” and “+” buttons simultaneously for 10 seconds until „ “ displays. Press “+” and “-“ to change the settings.
• toggle trough the menu with the “M” button
Menu Description Range
01 Temp. Offset -8 °C > +8°C, in steps of 0.5 ° C
03 Set Point High Limit +10 °C > +40°C, in steps of 0.5 ° C
04 Set Point Low Limit +10 °C > +40°C, in steps of 0.5 ° C
05 Display setting Room/Set (default Room)
06 Dead Band 0°C > +3°C (default 0,5°C)
07 Programmable Time setting: temperature +10 °C > +20°C, in steps of 0.5 ° C
09 Key-card select NO/NC (default NO)
10 Re-power status keep (default 1) 0:non keep 1:keep
11 2-pipes/4-pipes select 2/4 (default 4)
12 Fan output (0-10V) select dead band or not 0: with dead band 1: without dead band (default 0)
13 Heating / Cooling / Heating + Cooling Heating + Cooling default
14 80% - 90% - 100% fan speed 100% def ault
15 Back to factory settings
Select 0 or 1 (recovery) with the + and - buttons. After selecting “1”, press the “
” button to go to the startup screen. Recovery is success-
ful.
16 Software version 107D