Jaga JRT-100 Installation, Setup & User Manual

Page 1
Jaga Room Thermostat JRT-100 installation, setup & user manual
JR T-100
ATTENTION !!
1.5 m
The room thermostat must be installed at approx.
1.5 m above floor and out of reach of external influ­ences such as direct sunlight, draught or other heat sources as they may impede the correct functioning of the thermostat. Nearby electric fires, televisions, wall or table lamps may prevent the thermostat from working properly. Ensure that there will be enough space to allow easy access to the two release locks, located at the bottom of the wall plate.
1.43.4
6
Mount the JRT-100 Room thermostat on a suitable box (60.3 mm fixing centers). Minimum depth of 45mm. The internal size of the wall recess box must be at least Ø60mm or 50x50mm.
Features
• for 2- and 4-pipe fan coil systems
• (4-pipe): heating and cooling mode
• (2-pipe): heating and cooling mode
• automatic or manual fan speed control
• semi-recessed mounting
• 2 programmable time zones
• 0-10V output
• for valves 24V AC/DC only
• optional external room temperature sensor (order code: 24800.00053032)
• it is possible (at manual control) to allow the fan to run once “set point” is reached
Technical Data
Power Supply 24V AC/DC
Power Consumption 200 mA
Set Point Range +10 > +40°C
Ambient 0 > +40°C
Relative Humidity 85% max
Back-light
Sensor NTC 10K
Accuracy + 1°C (step control by +0.5°C)
Protection Class IP30
Housing ABS to UL94-5 fire retardant plastic
Product documentation:
• this manual is an integral part of the unit and must be handed over to the user after the installation of the device is completed in order to comply with applicable legal requirements.
• please read the manual carefully so that you understand the information in order to ensure safety during installation, use and maintenance.
• no liability is accepted for damage resulting from non-compliance with the guidelines in this installation manual.
Dimensions
M
8.6
8.6
6 1.4 3.4
CE-mark
The CE-mark symbolizes the compliance of the device with the following guide­lines:
• EN 61000-6-3:2007+A1:2011
• EN 61000-3-2:2006+A1:2009+A2:2009
• EN 61000-3-3:2008
• EN 61000-6-1:2007
IMPORTANT: This manual will guide you through the installation, setup and use of the Jaga Room Thermostat JRT-100. Keep this manual in a safe place for future reference.
Deze handleiding in het NEDERLANDS: Ce manuel en FRANÇAIS: Dieses Handbuch auf DEUTSCH: This manual in ENGLISH:
www.jaga.be/downloads/Briza/Manual_JRT100.pdf
Page 2
25 June 2018, 8:43 - Jaga N.V.
Jaga Room Thermostat JRT-100 installation
Installation
Warning: The installation of the thermostat should be performed by qualified personnel and must comply with the applicable local
and national electrical codes and utility requirements. All wire connections must be tightened and properly arranged to prevent a shortcircuit. Turn off the power at the electrical panel to prevent electrical shock or product damage;
1.43.4
6
Install appropriate mounting box (60.3 mm fixing centers).
Carefully remove the front plate:
• locate the (2) release locks on the bottom edge of the front plate assembly. Use a small flat head screwdriver to push each of the release locks up to disengage the lower clips of the front plate.
Swing the bottom of the front plate slightly away from the bottom of the back plate.
987654321
Connect the JRT-100 according the wiring diagrams* on this page.
Mount the thermostat base on the box and secure it using two mounting screws. Do not over-tighten.
Close the front plate:
• locate the upper clips into the slots at the top of the grid plate
• insert the lower clips on the front plate into the lower slots in the back plate. Press on the cover plate until it locks
Warning: Turn off the power at the electrical panel to prevent electrical shock or product damage.
* Wiring diagram
2-Pipe 4-Pipe
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
0...10V
SENSOR
COM
0...10V
SENSOR
COM
24V DC
24V DC
C VALVE
H VALVE
H/C VALVE
L
+ -
N
230 VAC L1 N
L
+ -
N
230 VAC L1 N
+
-
+
-
1 2 3 4 5 6 7 8 9
0...10V
SENSOR
COM
24V DC
C VALVE
H VALVE
L
+ -
N
230 VAC L1 N
+
-
H/C Heating / Cooling GND N
H Heating
Briza / Clima Canal / Quatro Canal ....
C Cooling
Optional external room temperature sensor
Page 3
25 June 2018, 8:43 - Jaga N.V.
Jaga Room Thermostat JRT-100 setup / user
Programmable Time settings:
• hold the “M” button for 5 seconds to enter “clock setting” ( ) and “day setting”
• enter 5+1+1 programmable mode
• press “+” and “-“ to set the thermostat “on/off time”
• next mode setting: toggle trough the menu with the “M” button. Activate the programmed time: press and hold the “ “ button for 5 seconds.
To deactivate the programmed time: press and hold the “ “ button for 5 seconds
Week
1st time zone 2nd time zone
Turn on Turn Off Turn on Turn Off
Icons
1
2 3 4
2
3 4
3
4
4
12345 (Monday~Friday) 8:30 12:00 14:00 18:00
6(Sat.) 9:00 12:00 15:00 18:00
7(Sun.) 9:00 12:00 15:00 18:00
Control panel:
Programming & week / day Clock
Room temperature
Set temperature
Room temperature Set temperature
Heating / Cooling Fan speed:
Low
Mid
High
Auto fan
Temperature / Parameter setting - / +
Fan speed Mode On / Off
Heating
Cooling
Sens or
Page 4
21/12/2018, 8:43 - Jaga N.V.
Parameter settings
• set Power Off, by pressing the “ ” button
• to access the MENU , press and hold “M” and “+” buttons simultaneously for 10 seconds until “ ” displays. Press “+” and “-“ to change the settings.
• toggle trough the menu with the “M” button
Menu Description Range
01 Temp. Of fset -8 °C > 8°C
04 Set Point High Limit +10 °C > +40°C
05 Set Point Low Limit +10 °C > +40°C
06 LCD temperature display Room/ Room Set / Set (default Room)
07 Temperature setting / Program +10 °C ~ +20°C
11 Dead Band 0°C~+3°C (default 0,5°C)
12 NTC select Room: internal sensor / Floor: optional external room temperature sensor
13 2-pipes / 4-pipes select 2/4 (default 2 pipes)
14 (0-10V) select dead band or not 0: with dead band 1: without dead band (default 0)
15 Repower memory OFF/LAS T
16 Heating / cooling / heating + cooling heating + cooling default
17 80% - 90% - 100% fan speed 100% default
19 Back to factory settings
Re > press short “
” button
20 Software version
Jaga Room Thermostat JRT-100 setup
Loading...