With water-temperature sensor
With 3-modes control panel
Basic settings
0
1
F
2
E
3
4
D
5
Basic settings JDPC.002: MODE 2
C
B
6
7
A
9
Configuration Code: see the product label on the device
Heating: JDPC.CC24
Setup and operation
The module is factory assembled and tested according to the
product configuration.
Basic settings water temperature set point:
Fan start when supply water T° > 28°C
Manually adjusting settings:Pag.
Adjusting
fan speed
Adjusting
water temperature
set point
Table 1: fan speed2
Table
2:
adjusting min. water
temperature heating
5
Connecting
Ι
Not connected
Ι
BLUE -24V
Ι
RED +24V
and Heating and cooling: JDPC.CC25
Setup and operation
The module is factory assembled and tested according to the
product configuration.
Basic settings water temperature set point:
Fan start when supply water T° > 28°C
Fan start when supply water T° < 18°C
Manually adjusting settings:Pag.
Adjusting
fan speed
Adjusting
water temperature
set point
Table 1: fan speed2
Table
2:
adjusting min. water
temperature heating
Table
3:
adjusting max. water
temperature cooling
5
1
Speed 1
Speed 2
Speed 3
Speed 1
Speed 2
Speed 3
Fan speed factory settings
Speed
Speed
With control panel: Adjusting Fan speed
20253035404550556065707580859095 100
20253035404550556065707580859095 100
%:
20253035404550556065707580859095 100
20253035404550556065707580859095 100
20253035404550556065707580859095 100
%:
20253035404550556065707580859095 100
I
-+
(MIN) The blue LED blinks fastThe red LED blinks fast (MAX)
Adjusting the Fan speed:
• short press “-” or “+” to adjust the speed of
the motor(s).
• after the adjustment of the speed, the fans
will run for 30” in order to control, irrespective of the water temperature. The water-temperature sensor will not respond during this
MODE
0
1
F
2
E
3
4
D
5
C
B
-+
6
7
A
9
8
-+
time. Any modification will be automatically
stored in the internal (EE PROM) memory.
!! The JDPC controller returns back into normal mode after 30“ and will automatically save all modified settings !!
Put the controller in the desired mode with the control panel
Mode /
Press button until the desired mode is reached (± 3 sec.)
• When AUTO CHANGE OVER mode the controller itself will
select the desired operation mode. The user can always choose
MANUALLY a different mode of operation.
How to use
Speed 1• • Speed 2• • • Speed 3
•
MODE
12
MODE
12
3
3
MODE/ BOOST
MODE / BOOST
MODE/ BOOST
� / 1 COMFORT / 2
BOOST / 3
verwarmen
chauffer
Heizung
heating
3”3”
� / 1 COMFORT / 2
BOOST / 3
koelen
rafrâichir
kühlen
cooling
3”
MODE
� / 1 COMFORT / 2
12
BOOST / 3
uit
éteinte
Aus
off
3
Water temperature < Adjusted temperature: Leds flashing every 3”
or
MODE
1
2
12
3
3
MODE
1
2
3
Leds flashing every 3”
How to use
Speed 1• •Speed 2• • •Speed 3
•
MODE
12
3
MODE
or
MODE
1
3
2
MODE
12
3
Water temperature > Adjusted temperature: Leds flashing every 3”
• short press “-” or “+” to adjust the speed of the
motor(s).
• after the adjustment of the speed, the fans will run
for 30” in order to control, irrespective of the water
temperature. The water-temperature sensor will
not respond during this time (position 2, 4, 6 or 7).
Any modification will be automatically stored in the
internal (EE PROM) memory.
Setting the water temperature
2
A
24°C26°C28°C30°C32°C34°C36°C38°C
- 2°C
I
Press and hold the (+) button until the red LED flashes 5 times.
B
Increasing temperature
Briefly press (+): the temperature increases by one step 2 ° C.
If the maximum temperature is reached, the red LED flashes
rapidly.
Decrease temperature
Briefly press (-): the temperature decreases by one step 2 ° C.
If the minimum temperature is reached, the blue LED will flash
rapidly. After 30”, the JDPC module returns to normal mode.
C
Exit setup mode by holding the “+” button
until the red LED blinks 5x.
Setting temperature ° C
Setting the minimum water temperature heating (default =>28 ° C)
(MIN) The blue LED blinks fastThe red LED blinks fast (MAX)
MODE
0
1
F
2
E
3
4
D
5
C
B
-+
6
7
A
9
8
-+
MODE
0
1
F
2
E
3
4
D
5
C
-+
B
6
7
A
9
8
I
Automatic control:
The green LED lights when the water temperature exceeds the set
temperature. This indicates that the supply water is hot.
Each adjustment is stored in the internal (EE PROM) memory.
-+
MODE
0
1
F
E
D
C
B
A
9
8
5x
2
3
4
5
6
7
5x
I
3
A
12°C14°C16°C18°C20°C22°C24°C26°C
- 2°C
I
Setting temperature ° C
Setting the maximum temperatureof cooling water (default = <18°C)
-+
+ 2°C
I
5x
Press and hold the (+) button until the blue LED flashes 5 times.
B
Increasing temperature
Briefly press (+): the temperature increases by one step 2 ° C.
If the maximum temperature is reached, the red LED flashes
rapidly.
Decrease temperature
Automatic control:
The green LED lights when the water temperature is lower than the
set temperature. This indicates that the supply water temperature
is colder.
Each adjustment is stored in the internal (EE PROM) memory.
Briefly press (-): the temperature decreases by one step 2 ° C.
If the minimum temperature is reached, the blue LED will flash
rapidly. After 30”, the JDPC module returns to normal mode.
C
Exit setup mode by holding the “+” button
until the blue LED blinks 5x.
-+
5x
!! The JDPC controller returns into normal mode after 30” and will automatically save all modified settings !!
0
1
F
2
E
3
4
D
5
C
B
6
7
A
9
8
0
1
F
2
E
3
4
D
5
C
B
6
7
A
9
8
default factory temperature setting
5
Clima Canal JDPC.002Dynamic Product Controller:
Reset to Factory Default
Reset to Factory Default
1. Turn off power
• press and hold both “-” and “+” buttons simultaneously.
2. Turn power on. Press and hold both “-” and “+” buttons simultaneously until the blue LED light is blinking. After 2“ the green LED will light
and then after 4”, the red LED.
3. The controller will return to Factory Default settings, all LEDs will flash for 8“
ATTENTION: Doing so will erase all of the data, settings, and applications and reset the controller to the original factory settings !!
Warning:
This product is not intended for use by persons (including children) with
reduced physical, sensory or mental capabilities, or lack of experience
and knowledge, unless they have been given supervision or instruction
concerning use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the
product.
Please follow these instructions carefully in order to allow for
an error-free installation and a carefree use.
6
Entitlement to warranty is cancelled in case of:
• errors or damage resulting from not following the assembly, cleaning
or user instructions supplied by the manufacturer,
• wrong, improper and/or irresponsible use or treatment of the device,
• wrong or incompetent repairs and defects due to external factors,
• self-applied changes to the device.
• equipment that is built in, in a way that it cannot be reached normally.
If you have any questions or complaints, please contact your supplier or
installer.
The copyright of these instructions is the property