This document describes wiring, power up, basic
troubleshooting, and common installation issues for the
JADE™ Economizer Module (Model W7220). For further
information on mounting and operation, refer to Honeywell
document 63-2700.
BEFORE INSTALLATION
Review the following before installing the The W7220:
Economizer Module
INSTALLATION INSTRUCTIONS
DCV (CO2) Sensor (C7232): 2-10 Vdc control signal;
minimum impedance >50k ohm.
Outputs
Actuator signal: 2-10 Vdc; minimum actuator impedance is
2k ohm; Sylkbus two-wire output for Honeywell Sylkbus
communicating actuators.
Exhaust fan, Y1, Y2 and AUX1 O: Contact closure (24 Vac)
All Relay Outputs (at 30 Vac):
Running: 1.5A maximum
Inrush: 7.5A maximum
When Installing This Product
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous condition.
2. Check ratings given in instructions and on the product to
ensure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
5. For additional detailed information on this product go to
customer.honeywell.com and download the product
data sheet (lit no 63-2700) or scan QR code located on
the label above MAT terminals with your smart phone.
Electrical
Rated Voltage: 20 to 30 Vac RMS; 50/60 Hz
Transformer: 100 VA maximum system input
Relay Digital Output Rating: 30 Vac
IMPORTANT
All inputs and outputs must be Class 2 wiring.
Inputs
A Mixed air (MA) analog sensor is required on all W7220
units; either an OA (Outdoor Air) sensor for dry bulb change
over or an OA Sylkbus sensor for outdoor enthalpy change
over is required in addition to the MA sensor. An additional
Return Air (RA) Sylkbus sensor can be added to the system
for differential enthalpy changeover.
Accessories
50048926-001 2-pin edge connector for sensors
(20 pieces per bag)
50048926-002 6-pin edge connector for field wiring
(20 pieces per bag)
C7250 20k sensor for MA or OA (dry bulb changeover)
C7400S Sylkbus sensor for enthalpy control in OA and/or RA
and RA for differential dry bulb changeover
W7220 PCMOD interface tool for JADE controller and Per-
sonal Computer. Go to www.customer.honeywell.com/
economizertools for the software
50053060-001 Duct mounting kit for sensors
C7632 or C7232 CO
sensors
2
JADE™ ECONOMIZER MODULE
WARNING
CAUTION
INSTALLATION AND SETUP
The Economizer module may be mounted in any orientation.
However, mounting in the orientation shown above permits
proper viewing of the LCD display and use of the keypad.
NOTE: Jade will be in the “set up” mode for the first 60
minutes after powered. If a sensor for OA air or
Sylkbus device (sensor, actuator) is disconnected during the set up mode, the Jade will not
alarm that failure. The MA sensor is a system
“critical” sensor; if the MA sensor is removed
during the set up mode, the Jade will alarm. After
60 minutes the Jade controller will change to
operation mode and all components removed or
failed will alarm in the operation mode.
WIRING
All wiring must comply with applicable electrical codes and
ordinances, or as specified on installation wiring diagrams.
Module wiring in the field is terminated to the four screw
terminal blocks located on the left and right sides.
Module wiring at the OEM factory is terminated via the header
pin terminals located on the left and right sides. The header
terminal pins and the terminal blocks have common
terminations for the appropriate input or output. The part
number for the OEM female mating connector is 0039973997.
Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
Disconnect power supply before beginning wiring, or
making wiring connections, to prevent electrical shock
or equipment damage.
Equipment Damage Hazard.
Electrostatic discharge can short equipment
circuitry.
Ensure that you are properly grounded before
handling the unit.
Each terminal can accommodate the following gauges of wire:
• Single wire – from 18 AWG to 22 AWG solid or stranded
• Multiple wires – up to two 22 AWG stranded
• For the 24 Vac connections: single wire – from 14 to 18
AWG solid or stranded
For S-BUS wiring, the sensors may be mounted up to 200 ft.
(61 m) from the JADE controller. When the length of wire is
over 100 feet use twisted pair shielded wire.
NOTE: All wiring is polarity insensitive.
Refer to Fig. 1 through Fig. 6 for common wiring
configurations.
Actuator Wiring Options:
1. The JADE economizer controller can only have one (1)
communicating actuator connected to it.
2. Up to four (4) non-communicating and (2) 2-position
actuators (1 each on EXH1 and AUX1 O)
3. One (1) communicating and up to four (4) non-communicating and (2) 2-position actuators (1 each on EXH1
and AUX1 O)
When using a 2-position actuator on the AUX1 O the AUX1 O
must be programmed for Exh2 and the % open is the % open
of the outdoor damper when the 2-pos actuator opens.
Connect 24 V to Exh1 and/or AUX1 O and ground to the Jade
“C” terminal.
Note the W7220 economizer will not work with an old “black
motor” M7415; replace the M7415 with a M7215 or MS3103
DCA.
Table 1. Economizer Module - Left hand terminal blocks.
LabelTypeDescription
Top Left Terminal Block
MAT
MAT
OAT
OAT
S-BUS
S-BUS
IAQ 2-102-10 VdcAir Quality Sensor Input
IAQ COM COMAir Quality Sensor Common
IAQ 24V24 VacAir Quality Sensor 24 Vac Source
ACT 2-102-10 VdcDamper Actuator Output (2-10 Vdc)
ACT COM COMDamper Actuator Output Common
ACT 24V24 VacDamper Actuator 24 Vac Source
Table 2. Economizer Module - Right hand terminal blocks.
LabelTypeDescription
AUX2 I24 Vac INShut Down (SD) or Heat (W)
OCC24 Vac INOccupied / Unoccupied Input
E-GNDEGNDEarth Ground - System Required
EXH124 Vac OUT Exhaust Fan 1 Output
AUX1 O24 Vac OUT Programmable:
Y2-I24 Vac INY2 in - Cooling Stage 2 Input from
Y2-O24 Vac OUT Y2 out - Cooling Stage 2 Output to
Y1-I24 Vac INY1 in - Cooling Stage 1 Input from
Y1-O24 Vac OUT Y1 out - Cooling Stage 1 Output to
CCOM24 Vac Common
R24 Vac24 Vac Power (Hot)
20k NTC
and COM
20k NTC
and COM
SYLK Bus Sylk Bus sensor
Bottom Left Terminal Block
n/aThe first terminal is not used
Bottom Right Terminal Block
Mixed Air Temperature Sensor
(polarity insensitive connection)
Outdoor Air Temperature Sensor
(polarity insensitive connection)
(polarity insensitive connection)
(e.g. CO
Top Right Terminal Block
Conventional only or
Heat Pump Changeover (O/B) in
Heat Pump mode.
Exhaust fan 2 output or
ERV or System Alarm output.
space thermostat
stage 2 mechanical cooling
space thermostat
stage 1 mechanical cooling
sensor)
2
62-0331—112
JADE™ ECONOMIZER MODULE
ROOF TOP UNIT
Y1O
Y2O
Y1I
Y2I
OCC
24 VAC
1K1
1K1
E-GND
Y1
G
W2
W1
Y2
O/B
OCC
W7220 ECONOMIZER CONTROLLER MODULE
THERMOSTAT
CO2
SENSOR
2-10 VDC
(OPTIONAL)
MAT
MAT
OAT
OAT
C R
M28980D
IAQ (2-10V)
IAQ COM
IAQ 24V
ACT (2-10V)
ACT COM
ACT 24V
AUX1-0
AUX2-I
OAT TEMP
SENSOR
20K NTC
M7215
NOTE THAT THE C7250 20K NTC SENSOR CAN BE MOUNTED IN THE OAT ONLY IN THIS CONFIGURATION.
1
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O
OR B AND W2 MAY BE LABELED W.
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.
2
3
3
1
MA TEMP
SENSOR
20K NTC
+
-
TR1
TR
IN
IN
2
R(+)
C(-)
Fig. 1. Stand-alone dry bulb Economizer configuration with black motor M7215.
362-0331—11
JADE™ ECONOMIZER MODULE
ROOF TOP UNIT
Y1O
Y2O
Y1I
Y2I
OCC
24 VAC
E-GND
Y1
G
W2
W1
Y2
O/B
OCC
W7220 ECONOMIZER CONTROLLER MODULE
THERMOSTAT
CO2
SENSOR
2-10 VDC
(OPTIONAL)
MAT
MAT
OAT
OAT
C R
M32564D
IAQ (2-10V)
IAQ COM
IAQ 24V
ACT (2-10V)
ACT COM
ACT 24V
3
OAT TEMP
SENSOR
20K NTC
MS7503 OR MS7505
NOTE THAT THE 20K NTC SENSOR CAN BE MOUNTED IN THE OAT TERMINALS ONLY IN THIS CONFIGURATION.
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O
OR B AND W2 MAY BE LABELED W.
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.
1
1
MA TEMP
SENSOR
20K NTC
R(+)
C(-)
AUX1-0
AUX2-I
2
3
2
3
1K1
1K1
Fig. 2. Stand-alone dry-bulb Economizer configuration with Honeywell MS7403 Direct Coupled Actuator.
62-0331—114
JADE™ ECONOMIZER MODULE
ROOF TOP UNIT
Y1O
Y2O
Y1I
Y2I
OCC
24 VAC
E-GND
Y1
G
W2
W1
Y2
O/B
OCC
W7220 ECONOMIZER CONTROLLER MODULE
THERMOSTAT
CO2
SENSOR
2-10 VDC
(OPTIONAL)
MAT
MAT
OAT
OAT
C R
R(+)
C(-)
M32650D
IAQ (2-10V)
IAQ COM
IAQ 24V
ACT (2-10V)
ACT COM
ACT 24V
3
1
2
OAT TEMP
SENSOR
20K NTC
MS3103J
OR MS3105J
1
1
MA TEMP
SENSOR
20K NTC
S-BUS
4
5
S-BUS
AUX1-0
AUX2-I
NOTE THAT THE 20K NTC SENSOR CAN BE MOUNTED IN THE OAT TERMINALS ONLY IN THIS CONFIGURATION.
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O
OR B AND W2 MAY BE LABELED W.
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.
2
2
3
3
1K1
1K1
Fig. 3. Stand-alone dry-bulb Economizer configuration with Honeywell MS3103J or MS3105J communicating actuators.
562-0331—11
JADE™ ECONOMIZER MODULE
S-BUS
S-BUS
OUTSIDE AIR
TEMP/HUMIDITY (ENTHALPY)
SYLKBUS SENSOR
RETURN AIR
TEMP/HUMIDITY (ENTHALPY)
SYLKBUS SENSOR
ROOF TOP UNIT
Y1O
Y2O
Y1I
Y2I
OCC
E-GND
Y1
G
W2
W1
Y2
O/B
OCC
W7220 ECONOMIZER CONTROLLER MODULE
THERMOSTAT
MAT
MAT
C R
R(+)
C(-)
M32565D
IN THIS CONFIGURATION, AN OPTIONAL DISCHARGE AIR TEMP/HUMIDITY
(ENTHALPY) SYLKBUS SENSOR CAN BE ADDED FOR ADVANCED CONTROL
AS SHOWN IN THE LOWER LEFT OF THIS FIGURE.
DO NOT USE THE C7250 20K NTC SENSOR WITH THE OA TERMINAL IN THIS
CONFIGURATION.
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS
MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION
RELAY BETWEEN O AND C.
1
4
1
2
CO2
SENSOR
2-10 VDC
(OPTIONAL)
IAQ (2-10V)
IAQ COM
IAQ 24V
ACT (2-10V)
ACT COM
ACT 24V
+
-
TR1
TR
IN
IN
M7215
MA TEMP
SENSOR
20K NTC
AUX1-0
AUX2-I
3
2
4
3
1K1
1K1
24 VAC
Fig. 4. Economizer with Sylk Bus sensors for enthalpy configuration with Honeywell M7215 black motor.
62-0331—116
JADE™ ECONOMIZER MODULE
OUTSIDE AIR
TEMP/HUMIDITY (ENTHALPY)
SYLKBUS SENSOR
RETURN AIR
TEMP/HUMIDITY (ENTHALPY)
SYLKBUS SENSOR
ROOF TOP UNIT
Y1O
Y2O
Y1I
Y2I
OCC
E-GND
Y1
G
W2
W1
Y2
O/B
OCC
W7220 ECONOMIZER CONTROLLER MODULE
THERMOSTAT
C R
R(+)
C(-)
M32566D
IN THIS CONFIGURATION, AN OPTIONAL DISCHARGE AIR TEMP/HUMIDITY
(ENTHALPY) SYLKBUS SENSOR CAN BE ADDED FOR ADVANCED CONTROL AS
SHOWN IN THE LOWER LEFT OF THIS FIGURE.
DO NOT USE THE C7250 20K NTC SENSOR WITH THE OA TERMINAL IN THIS
CONFIGURATION.
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER:
W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION
RELAY BETWEEN O AND C.
1
1
2
MS7503 OR MS7505
3
S-BUS
S-BUS
MAT
MAT
CO2
SENSOR
2-10 VDC
(OPTIONAL)
IAQ (2-10V)
IAQ COM
IAQ 24V
ACT (2-10V)
ACT COM
ACT 24V
MA TEMP
SENSOR
20K NTC
AUX1-0
AUX2-I
2
3
4
3
4
1K1
1K1
24 VAC
Fig. 5. Economizer with Sylk Bus sensors for enthalpy configuration with a Honeywell MS7505 or MS7503 Direct
Coupled Actuator.
762-0331—11
JADE™ ECONOMIZER MODULE
C7400S
OUTSIDE AIR
TEMP/HUMIDITY (ENTHALPY)
SYLKBUS SENSOR
C7400S
RETURN AIR
TEMP/HUMIDITY (ENTHALPY)
SYLKBUS SENSOR
ROOF TOP UNIT
Y1O
Y2O
Y1I
Y2I
OCC
E-GND
Y1
G
W2
W1
Y2
O/B
OCC
W7220 ECONOMIZER CONTROLLER MODULE
THERMOSTAT
C R
C(-)
M32653D
IN THIS CONFIGURATION, AN OPTIONAL DISCHARGE AIR TEM/HUMIDITY
(ENTHALPY) SYLKBUS SENSOR CAN BE ADDED FOR ADVANCED
CONTROL AS SHOWN IN THE LOWER LEFT OF THIS FIGURE.
1
1
THE S-BUS COMPONENTS MAY BE DAISY CHAINED TO ANOTHER S-BUS
COMPONENT.
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS
MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN
ISOLATION RELAY BETWEEN O AND C.
2
S-BUS
S-BUS
MAT
MAT
CO2
SENSOR
2-10 VDC
(OPTIONAL)
IAQ (2-10V)
IAQ COM
IAQ 24V
ACT (2-10V)
ACT COM
ACT 24V
MA TEMP
SENSOR
20K NTC
AUX1-0
AUX2-I
3
1
2
MS3103J
OR MS3105J
S-BUS
4
5
S-BUS
2
R(+)
24 VAC
3
3
4
1K1
1K1
4
1
2
ACTUATOR
EXH1 OR AUX1 O
NOTE: ON/OFF ACTUATORS CAN BE USED ON THE EXH1 OR AUX1
O TERMINAL WITH GROUND TO THE C TERMINAL. WHEN
PROGRAMMING THE EXH1 OR AUX1 O, THE % IS THE PERCENT
OPEN POSITION OF THE OUTDOOR AIR DAMPER WHEN THE
EXH1 OR AUX1 O TERMINAL IS ENERGIZED AND THE 2-POS
DAMPER GOES OPEN. IF USING THE AUX1 O TERMINAL
PROGRAM AUX1 O FOR EXH2.
C
M33409
V
Fig. 6. Economizer with Sylk bus sensor for enthalpy configuration with Honeywell MS3103 or MS3105 communicating
62-0331—118
actuators.
Fig. 7. 2-position actuator.
JADE™ ECONOMIZER MODULE
ECONOMIZING
AVAILABLE
NOT AVAILABLE
TEMPERATURE
ENTHALPY
A
R
RA TEMP
)
H
R
%
(
M
U
H
ABSOLUTE HUMIDITY
DUAL ENTHALPY
SINGLE ENTHALPY
P2 (T,RH)
ES4ES3ES2ES1HL
ES5
HIGH LIMIT
P1
(T,RH)
Fig. 8. Single Enthalpy curves and boundaries.
Table 3. Single Enthalpy and Dual Enthalpy High Limit Curves.
Enthalpy
Curve
Tem p.
Dry-Bulb (°F)
Temp.
Dewpoint (°F)
Enthalpy
(btu/lb/da)
Temp. °FHumidity %RHTemp. °FHumidity %RH
Point P1Point P2
ES180.060.028.080.036.866.380.1
ES275.057.026.075.039.663.380.0
ES370.054.024.070.042.359.781.4
ES465.051.022.065.044.855.784.2
ES560.048.020.060.046.951.388.5
HL86.066.032.486.038.972.480.3
M32286
Power Up
After the module is mounted and wired, apply power.
Power Up Delay
Upon power up (or after a power outage or brownout), the
W7220 controller module begins a 5 minute power up delay
before enabling mechanical cooling.
Initial Menu Display
On initial start up, Honeywell displays on the first line and
Economizer W7220 on the second line. After a brief pause,
the revision of the software appears on the first line and the
second line will be blank. After another brief moment the
screen will display W7220 on the first line and STATUS on the
second line. Refer to table 3 for menu structure.
Power Loss (Outage or Brownout)
All setpoints and advanced settings are restoreda after any
power loss or interruption.
NOTE: If power goes below 18 Vac, the W7220 controller
module assumes a power loss and the 5 minute
power up delay will become functional when
power returns above 18 Vac.
Using the Keypad with Menus
To use the keypad when working with menus:
• Press the
• Press the
• Press the button (Enter) to display the first item in the
currently displayed menu.
• Press the button (Menu up) to exit a menu’s item and
return to the list of menus.
a
All settings are stored in non-volatile flash memory.
button to move to the previous menu.
button to move to the next menu.
962-0331—11
JADE™ ECONOMIZER MODULE
Using the Keypad with Settings and
Parameters
To use the keypad when working with Setpoints, System and
Advanced Settings, Checkout tests, and Alarms:
• Navigate to the desired menu.
• Press the button (Enter) to display the first item in the
currently displayed menu.
•Use the
parameter.
• Press the button (Enter) to display the value of the
currently displayed item.
• Press the
parameter value.
• Press the button to decrease (change) the displayed
parameter value.
• Press the button to accept the displayed value and store
it in non-volatile RAM.
• CHANGE STORED displays.
• Press the button (Enter) to return to the current menu
parameter.
• Press the button (MenuUp/Exit) to return to the
previous menu.
a
When values are displayed, pressing and holding the
or button causes the display to automatically
increment.
and buttons to scroll to the desired
button to increase (change) the displayed
a
a
Menu Structure
Table 4 on page 10 illustrates the complete hierarchy of
menus and parameters for the JADE™ Economizer system.
The Menus in display order are:
•STATUS
• SETPOINTS
• SYSTEM SETUP
• ADVANCED SETUP
• CHECKOUT
•ALARMS
IMPORTANT
Table 4 on page 10 illustrates the complete hierarchy.
Your menu parameters will be different depending on
your configuration.
For example if you do not have a DCV (CO
then none of the DCV parameters appear and only
MIN POS will display. If you have a CO2 sensor, the
DCV MIN and DCV MAX will appear AND if you have
2 speed fan DCV MIN (high and low speed) and DCV
MAX (high and low speed will appear).
) sensor,
2
SETUP AND CONFIGURATION
Before being placed into service, the JADE™ Economizer
module must be setup and configured for the installed system.
IMPORTANT
During setup, the Economizer module is live at all
times.
The setup process uses a hierarchical menu structure that is
easy to use. You press the
forward and backward through the menus and press the
button to select and confirm setup item changes.
Table 4. Menu Structurea.
Parameter
Default
n/a
Val ue
c
MenuParameter
STATUSECON AVAILNOYES/NOYES = economizing available; the system can use Outdoor Air for
ECONOMIZINGNOYES/NO
OCCUPIEDNOYES/NOYES = OCC signal received from space thermostat or unitary
HEAT PUMP
COOL Y1-INOFFON/OFFY1-I signal from space thermostat or unitary controller for
COOL Y1-OUTOFFON/OFFCool Stage 1 Relay Output to mechanical cooling (Y1-OUT
Parameter
Range and
Increment
COOL
HEAT
b
free cooling when required.
YES = Outdoor Air being used for 1
controller.
YES = 24 Vac on terminal OCC
No = 0 Vac on terminal OCC.
Displays COOL or HEAT when system is set to heat pump (nonconventional)
cooling stage 1.
ON = 24 Vac on term Y1-I
OFF = 0 Vac on term Y1-I
terminal).
and arrow buttons to move
Notes
st
stage cooling.
62-0331—1110
JADE™ ECONOMIZER MODULE
MenuParameter
STATUS
COOL Y2-INOFFON/OFFY2-I signal from space thermostat or unitary controller for
CONTINUED
COOL Y2-OUTOFFON/OFFCool Stage 2 Relay Output to mechanical cooling (Y2-OUT
MA TEMP_ _._ ºF-40 to 150 ºFDisplays value of measured mixed air from MAT sensor.
DA TEMP_ _._ ºF-40 to 150 ºFDisplays when Discharge Air Sylk Bus sensor is connected and
OA TEMP_ _._ ºF-40 to 140 ºFDisplays measured value of outdoor air temperature.
OA HUM_ _ %0 to 100%Displays measured value of outdoor humidity from QA Sylkbus
RA TEMP_ _._ ºF0 to 140 ºFDisplays measured value of return air temperature from RA
RA HUM_ _ %0 to 100%Displays measured value of return air humidity from RA Sylkbus
IN CO2_ _ _ ppm 0 to 2000 ppmDisplays value of measured CO2 from CO2 sensor. Invalid if not
DCV STATUSn/aON/OFFDisplays ON if above setpoint and OFF if below setpoint, and
DAMPER OUT2.0V2.0 to 10.0 V
ACT POSn/a0 to 100%Displays actual position of actuator.
ACT COUNTn/a1 to 65,535Displays number of times actuator has cycled. 1 Cycle equals
ACTUATORn/aOK/Alarm (on
EXH1 OUTOFFON/OFFOutput of EXH1 terminal.
EXH2 OUTOFFON/OFFOutput of AUX1 O terminal Displays ON when damper position
ERVOFFON/OFFOutput of AUX1 O terminal, ON = 24 Vac Output, OFF = No
MECH COOL ON00, 1, or 2Displays number of mechanical cooling stages that are active.
FAN SPEEDn/aLOW or HIGHDisplays speed of fan on a 2-speed fan unit
W (HEAT IN)n/aON/OFFDisplays status of heat on a 2-speed fan unit.
Table 4. Menu Structure
Parameter
Default
Val ue
Parameter
Range and
Increment
Alarm menu)
a
. (Continued)
b
Notes
second stage cooling.
ON = 24 Vac on term Y2-I
OFF = 0 Vac on term Y2-I
terminal).
Displays --.- if not connected, short, or out- of-range.
displays measured discharge air temperature.
Displays --.-°F if sensor sends invalid value, if not connected,
short or out-of-range.
Displays --°F if sensor sends invalid value, if not connected,
short or out-of-range.
sensor. Displays --% if not connected, short, or out- of-range.
sensor. Displays --°F if sensor sends invalid value, if not
connected, short or out-of-range.
sensor. Displays --% if sensor sends invalid value, if not
connected, short or out-of-range.
connected, short or out-of-range. May be adjusted in Advanced
menu by Zero offset and Span
ONLY if a CO2 sensor is connected.
Displays output voltage or position to the damper actuator.
the sum of 180° of movement in any direction.
Displays Error if voltage or torque is below actuator range
ON = 24 Vac Output; OFF = No Output.
reaches programmed percentage setpoint
ON = 24 Vac Output, OFF = No Output; displays only if AUX1 O =
EXH2
Output; displays only if AUX1 O = ERV
e
1162-0331—11
JADE™ ECONOMIZER MODULE
Table 4. Menu Structure
Parameter
Range and
Increment
MenuParameter
Parameter
Default
Val ue
SETPOINTS MAT SET53ºF38 to 70 ºF;
increment by 1
LOW T LOCK32ºF-45 to 80 ºF;
increment by 1
DRYBLB SET63ºF48 to 80 ºF;
increment by 1
ENTH CURVEES3ES1, ES2, ES3,
ES4, or ES5
DCV SET1100ppm500 to 2000
ppm
increment by
100
MIN POS2.8 V2 to 10 VdcDisplays ONLY if a CO2 sensor is NOT connected. With 2-speed
VENTMAX2.8 V2 to 10 Vdc
or
100 to 9990 cfm
increment by 10
VENTMIN2.25 V2 to 10 Vdc
or
100 to 9990 cfm
increment by 10
ERV OAT SP
d
32ºF0 to 50 ºF;
increment by 1
EXH1 SET50%0 to 100%;
increment by 1
EXH2 SET75%0 to 100%;
increment by 1
a
. (Continued)
b
Notes
The economizer will modulate the OA damper to maintain the
mixed air temperature at the setpoint.
Setpoint determines outdoor temperature when the mechanical
cooling cannot be turned on. Commonly referred to as the
Compressor lockout. At or below the setpoint the Y1-O and
Y2-O will not be energized on the controller.
Setpoint determines where the economizer will assume outdoor
air temperature is good for free cooling; e.g.; at 63 ºF setpoint
unit will economizer at 62 ºF and below and not economize at
64 ºF and above. There is a a 2 ºF deadband.
Enthalpy boundary “curves” for economizing using single
enthalpy.
See page 22 for description of enthalpy curves.
Displays ONLY if a CO2 sensor is connected.
Setpoint for Demand Control Ventilation of space. Above the
setpoint, the OA dampers will modulate open to bring in
additional OA to maintain a space ppm level below the setpoint.
fan units MIN POS L (low speed fan) and MIN POS H (high
speed fan) settings are required. Default for MIN POS L is 3.2V
and MIN POS H is 2.8V.
Displays only if a CO2 sensor is connected.
Used for Vbz (ventilation max cfm) setpoint. VENTMAX is the
same setting as MIN POS would be if you did not have the CO2
sensor.
Displays 2 to 10 V if <3 sensors (RA,OA and MA).
In DCV CAL ENABLE AUTO mode dampers controlled by CFM
With 2-speed fan units VENTMAX L (low speed fan) and
VENTMAX H (high speed fan) settings are required. Default for
VENTMAX L is 3.2V and VENTMAX H is 2.8V.
Displays only if CO2 sensor is connected.
Used for Va (ventilation min cfm) setpoint. This is the ventilation
for less than maximum occupancy of the space.
Displays 2 to 10 V if <3 sensors (RA,OA and MA). Va is only set
if DCV is used.
In DCV CAL ENABLE AUTO mode dampers controlled by CFM
With 2-speed fan units VENTMIN L (low speed fan) and
VENTMIN H (high speed fan) settings are required. Default for
VENTMIN L is 2.5V and VENTMIN H is 2.25V.
Only when AUX1 O = ERV
Setpoint for OA damper position when exhaust fan 1 is powered
by the economizer.
With 2-speed fan units Exh1 L (low speed fan) and Exh1 H (high
speed fan) settings are required. Default for Exh1 L is 65% and
Exh1 H is 50%
Setpoint for OA damper position when exhaust fan 2 is powered
by the economizer. Only used when AUX1 O is set to EHX2.
With 2-speed fan units Exh2 L (low speed fan) and Exh2 H (high
speed fan) settings are required. Default for Exh2 L is 80% and
Exh2 H is 75%
62-0331—1112
JADE™ ECONOMIZER MODULE
MenuParameter
SYSTEM
INSTALL01/01/11Display order = MM/DD/YY
SETUP
UNITS DEGºFºF or ºCSets economizer controller in degrees Fahrenheit or Celsius.
EQUIPMENTCONVCONV
AUX2 In/aShutdown (SD)
FAN SPEED1 speed1 speed/
FAN CFM5000cfm100 to 15000
AUX1 OUTNONENONE
OCCINPUTINPUT or
FACTORY DEFAULTNONO or YESResets all set points to factory defaults when set to YES. LCD
Table 4. Menu Structure
Parameter
Default
Val ue
Parameter
Range and
Increment
HP
Heat (W1)
HP(O)
HP(B)
2 speed
cfm;
increment by
100
ERV
EXH2
SYS
ALWAYS
a
. (Continued)
b
Notes
Setting order = DD, MM, then YY.
CONV = conventional.
HP O/B = Enables Heat Pump mode. Use AUX2 I for Heat Pump
input from thermostat or controller.
In CONV mode:
SD = Enables configuration of shutdown (default);
W = Informs controller that system is in heating mode.
NOTE: If using 2-speed fan mode, you must pro-
gram CONV mode for W. Shutdown is not
available in the two-speed fan mode.
In HP O/B mode:
HP(O) = energize heat pump on Cool (default);
HP(B) = energize heat pump on Heat.
Sets economizer controller for operation of 1 speed or 2 speed
supply fan. The controller does not control the fan but positions
the OA and RA dampers to the heating or cooling mode. See
page 23 for modes and position.
NOTE: 2-speed fan option also needs Heat (W1) pro-
grammed in AUX 2 In.
This is the capacity of the RTU. The value is found on the label
from the RTU manufacturer.
• NONE = not configured (output is not used)
• ERV= Energy Recovery Ventilator
d
• EXH2 = second damper position 24 Vac out for second
exhaust fan.
• SYS = use output as an alarm signal
When using a setback thermostat with occupancy out (24 Vac),
the 24 Vac is input “INPUT” to the OCC terminal. If no
occupancy output from the thermostat then change program to
“ALWAYS” OR add a jumper from terminal R to OCC terminal.
will briefly flash YES and change to NO but all parameters will
change to factory default values.
1362-0331—11
JADE™ ECONOMIZER MODULE
MenuParameter
ADVANCED
MA LO SET45ºF35 to 55 ºF;
SETUP
FREEZE POSCLOCLO
CO2 ZERO0ppm0 to 500 ppm;
CO2 SPAN2000ppm1000 to 3000
STG3 DLY2.0h0 min, 5 min, 15
SD DMPR POSCLOCLO
DCVCAL ENAMANMAN (manual)
MAT T CAL0.0 F°+/-2.5F°Allows for the operator to adjust for an out of calibration
OA T CAL0.0F°+/-2.5F°Allows for the operator to adjust for an out of calibration
OA H CAL0% RH+/-10% RHAllows for the operator to adjust for an out of calibration
RA T CAL0.0F°+/-2.5F°Allows for the operator to adjust for an out of calibration
RA H CAL0% RH+/-10% RHAllows for the operator to adjust for an out of calibration
DA T CAL0.0 F°+/-2.5F°Allows for the operator to adjust for an out of calibration
2SP FAN DELAY5 Minutes 0 to 20 minutes
Table 4. Menu Structure
Parameter
Default
Val ue
Parameter
Range and
Increment
increment by 1º
MIN
increment by 10
ppm;
increment by 50
min, then 15
min intervals.
Up to 4h or OFF
OPN
AUTO
in 1 minute
increments.
a
. (Continued)
b
Notes
Temp to activate Freeze Protection (close damper or modulate to
MIN POS if temp falls below set value)
Damper position when freeze protection is active (closed or MIN
POS).
CO2 ppm level to match CO2 sensor start level.
CO2 ppm span to match CO2 sensor; e.g.; 500-1500 sensor
output would be 500 CO2 zero and 1000 CO2 span.
Delay after stage 2 for cool has been active. Turns on 2nd stage
of mechanical cooling when economizer is 1st stage call and
mechanical cooling is 2nd stage call. Allows three stages of
cooling, 1 economizer and 2 mechanical.
OFF = no Stage 3 cooling.
Indicates shutdown signal from space thermostat or unitary
controller. When controller receives 24 Vac input on the SD
terminal in conventional mode, the OA damper will open if
programmed for OPN and OA damper will close if programmed
for CLO. All other controls, e.g., Y1-O, Y2-O, EXH1, etc. will shut
off.
Turns on the DCV automatic control of the dampers. Resets
ventilation based on the RA, OA and MA sensor conditions.
Requires all sensors (RA, OA, MA and CO2).
This operation is not operable with a 2-speed fan unit.
temperature sensor
temperature sensor
humidity sensor
temperature sensor
humidity sensor
temperature sensor
When in economizing mode this is the delay for the high speed
fan to try to satisfy the call for second stage cooling before the
first stage mechanical cooling is enabled.
62-0331—1114
JADE™ ECONOMIZER MODULE
Table 4. Menu Structurea. (Continued)
Parameter
Range and
Increment
b
Notes
MenuParameter
f
CHECKOUT
DAMPER VMIN-HSn/an/aPositions damper to VMIN position.
Parameter
Default
Val ue
DAMPER VMAX-HS (LS) n/an/aPositions damper to VMAX position. With 2-speed fan units the
damper will position to VMAX low speed fan.
DAMPER OPENn/an/aPositions damper to the full open position.
Exhaust fan contacts enable during the DAMPER OPEN test.
Make sure you pause in this mode to allow for exhaust contacts
to energize due to the delay in the system.
DAMPER CLOSEn/an/aPositions damper to the fully closed position.
CONNECT Y1-On/an/aCloses the Y1-O relay (Y1-O).
See CAUTION on page 20
CONNECT Y2-On/an/aCloses the Y2-O relay (Y2-O).
See CAUTION on page 20
CONNECT AUX1-On/an/aEnergizes the AUX1-O output. If AUX1-O setting is:
• NONE – no action taken
• ERV – 24 Vac out. Turns on or signals an ERV that the
conditions are not good for economizing but are good for
ERV operation.
d
• SYS – 24 Vac out. Issues a system alarm.
CONNECT EXH1n/an/aCloses the power exhaust fan 1 relay (EXH1)
ALARMS(_) MA T SENS ERRn/an/aAlarms display only when they are active. The menu title
CO2 SENS ERRn/an/a
OA T SENS ERRn/an/a
“ALARMS (_)” includes the number of active alarms in
parenthesis ().
DA ENTHL ERRn/an/a
SYS ALARMn/an/aWhen AUX1-O is set to SYS and there is any alarm (e.g., failed
sensors, etc.), the AUX1-O terminal has 24 Vac out.
ACT UNDER Vn/an/aVoltage received by Actuator is above expected range
ACT OVER Vn/an/aVoltage received by Actuator is below expected range
ACT STALLEDn/an/aActuator stopped before achieving commanded position
NOTE: The alarms listed are examples. Additional alarms display depending on the parameter settings
and configuration.
a
Table 4 illustrates the complete hierarchy. Your menu parameters may be different depending on your configuration.
For example if you do not have a DCV (CO
b
When values are displayed, pressing and holding the or button causes the display to automatically increment.
c
n/a = not applicable
d
ERV Operation: When in Cooling mode AND the conditions are NOT OK for economizing - the ERV terminal will be energized. In
) sensor, then none of the DCV parameters appear.
2
the Heating mode the ERV terminal will be energized when the OA is below the ERV OAT setpoint in the setpoint menu.
e
When used with Honeywell communicating actuator the damper out is reported in XX.X% open versus XX.X Vdc.
f
After 10 minutes without a command or mode change, the controller will change to normal operation.
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if
the call for Y1-I and Y2-I have not been satisfied.
DCV
Below CO2
set
Above CO2
set
a
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if
the call for Y1-I and Y2-I have not been satisfied.
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if
0-v/Off
a
MIN POS H to FullOpen
Closed to Full-Open
the call for Y1-I and Y2-I have not been satisfied.
b
With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to
satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage
mechanical cooling is enabled.
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if
0-v/Off
a
VENTMIN H to FullOpen
Closed to Full-Open
the call for Y1-I and Y2-I have not been satisfied.
b
With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to
satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage
mechanical cooling is enabled.
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if
0-v/Off
a
MIN POS H to FullOpen
Closed to Full-Open
the call for Y1-I and Y2-I have not been satisfied.
b
With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to
satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage
mechanical cooling is enabled.
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if
0-v/Off
a
VENTMIN H to FullOpen
Closed to Full-Open
the call for Y1-I and Y2-I have not been satisfied.
b
With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to
satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage
mechanical cooling is enabled.
TROUBLESHOOTING
Alarms
The Economizer module provides alarm messages that
display on the 2-line LCD.
NOTE: Upon power up, the module waits 60 minutes
before checking for alarms. This allows time for
all the configured devices (e.g. sensors, actuator) to become operational. The exception is the
MA sensor which will alarm immediately. If one or
more alarms are present and there has been no
keypad activity for at least 5 minutes, the Alarms
menu displays and cycles through the active
alarms.
You can also navigate to the Alarms menu at any time.
Table 13. Alarms Menu.
MenuAlarm
ALARMS(_)MA T SENS ERR
CO2 SENS ERR
OA T SENS ERR
DA ENTHL ERR
SYS ALARM
ACT Over Voltage
ACT Under Voltage
ACT Stalled
a
b
b
b
NOTES:
1.The Alarms menu displays only when alarm(s)
are active and includes the number of active
alarms in parenthesis ().
2.The alarms listed are a few examples. Additional
alarms display depending on the parameter settings and configuration.
a
When AUX1 O is set to SYS and there is any alarm (e.g.,
failed sensors, etc.), the AUX1 O terminal has 24 Vac out
and the LCD displays the ALARM.
b
This alarm is only displayed when a communicating actuator
is used. (ex: MS3105AJ)
1962-0331—11
JADE™ ECONOMIZER MODULE
CAUTION
Clearing Alarms
Once the alarm has been identified and the cause has been
removed (e.g. replaced faulty sensor), the alarm can be
cleared from the display.
To clear an alarm, perform the following:
1. Navigate to the desired alarm.
2. Press the button.
3. ERASE? displays.
4. Press the button.
5. ALARM ERASED displays.
6. Press the button (MenuUp/Exit) to complete the
action and return to the previous menu.
NOTE: If an alarm still exists after you clear it, it re-dis-
plays within 5 seconds.
NOTE: Jade will be in the “set up” mode for the first 60
minutes after powered. If a sensor for OA air or
Sylkbus device (sensor, actuator) is disconnected during the set up mode, the Jade will not
alarm that failure. The MA sensor is a system
“critical” sensor; if the MA sensor is removed
during the set up mode, the Jade will alarm. After
60 minutes the Jade controller will change to
operation mode and all components removed or
failed will alarm in the operation mode.
Checkout Tests
Use the Checkout menu (Table 4) to test the damper operation
and any configured outputs. Only items that are configured
are shown in the Checkout menu.
NOTE: See “Interface Overview” on page 13 of 63-2700 for
To perform a Checkout test:
The checkout tests can all be performed at the time of
installation or any time during the operation of the system as a
test that the system is operable.
information about menu navigation and use of the
keypad.
1. Scroll to the desired test in the Checkout menu using
the
2. Press the button to select the item.
3. RUN? displays.
4. Press the button to start the test.
5. The unit pauses and then displays IN PROGRESS.
6. When the test is complete, DONE appears.
7. When all parameters have been tested, press the
and buttons.
button (Menu up) to end the test (e.g. turn off the relay).
Equipment damage may result.
Be sure to allow enough time for compressor startup
and shutdown between checkout tests so that you do
not short-cycle the compressors