Jacuzzi LED, J-LX Series, J-375, J-365, J-355 Series Manual

...
Page 1
STANDARD TROUBLESHOOTING APPROACH
S.T.A. MANUAL 2011+ JLX/J200
2011-2013 J300
LED SERIES
Page 2
The following symbol is placed throughout this manual for your protection. Always use extreme cau­tion whenever performing repairs to electrical control system components of any kind!
DANGER: Electrical Shock Hazard Exists!
High Voltage Present on Circuit Board. Use Extreme Caution while Servicing Circuit Board.
Page 3

Table of Contents

1.0 Standard Troubleshooting Approach (S.T.A.) .......................................................................... 1
1.1 Why a Standard Troubleshooting Approach? .............................................................................................................. 1
1.2 How to Use the S.T.A................................................................................................................................................... 1
1.3 Professional Customer Service ...................................................................................................................................1
1.4 Before Leaving the Shop .............................................................................................................................................1
1.5 Fixing the Hot Tub........................................................................................................................................................1
1.6 Before Calling Technical Support .................................................................................................................................1
1.7 Before Leaving the Customer ...................................................................................................................................... 1
1.8 Satisfying the Customer...............................................................................................................................................2
2.0 Electro Static Discharge (E.S.D.) .............................................................................................. 3
2.1 E.S.D. - What is it? What does it do? ..........................................................................................................................3
2.2 Avoiding E.S.D. Damage .............................................................................................................................................3
2.3 What About Wrist Straps and Special Mats? ............................................................................................................... 3
2.4 Must Wrist Straps and Mats be Used When Replacing A Circuit Board? ....................................................................3
3.0 Main Control Panel Functions ................................................................................................... 4
3.1 J-LX Control Panel.......................................................................................................................................................4
3.2 J300 Control Panel ......................................................................................................................................................5
3.3 J200 Control Panel ......................................................................................................................................................6
4.0 Standard Programming Functions ........................................................................................... 7
4.1 Setting Filter Cycle Start Time (J200/ 2011-2013 J300/ JLX Collections) ................................................................... 7
4.2 Filtration Options..........................................................................................................................................................7
4.3 Programming Filter Cycles (J-LX/ 2011-2013 J300 Collection) ................................................................................... 8
4.4 Programming Filter Cycles (2011-2012 J200 models equipped with a circulation
pump)...........................................................................................................................................................................9
4.5 Programming Filter Cycles (2013+ J200 models not equipped with a circulation
pump)...........................................................................................................................................................................9
4.6 Programming the Circulation Pump Filtration Cycle (For models equipped with a circulation pump) ....................... 10
4.7 Programming the CLEARRAY® (Ultraviolet) Water Purification System (For models equipped
with a circulation pump) ............................................................................................................................................. 10
4.8 Programming the CLEARRAY (Ultraviolet) Water Purification System (For models NOT equipped
with a circulation pump) ............................................................................................................................................. 11
4.9 2011 Aftermarket Ozonator Facts ..............................................................................................................................12
4.10 2012+ CLEARRAY Facts ...........................................................................................................................................13
5.0 Additional Control Panel Functions ....................................................................................... 13
5.1 Setting Water Temperature and Overtemp Feature ................................................................................................... 13
5.2 Selecting Jets Speed ................................................................................................................................................. 14
5.3 Lock/Unlock Control Panel ........................................................................................................................................14
5.4 Summer Logic (Models equipped with the Circulation Pump Option) .......................................................................14
5.5 Multicolored Light System Operation (J-LX/J300 Models, except 2014 J300s) ........................................................14
5.6 Multicolored Light System Operation (Standard light for J-210 Models) ...................................................................15
5.7 Multi-Colored LED Light System Operation (J200 Collection) ................................................................................... 15
6.0 Understanding Circuit Board Pin Assignments .................................................................... 16
6.1 Circuit Board Jumpers (All North American 60 Hz 1-Pump Models) .........................................................................16
6.3 Circuit Board Jumpers (Domestic 60 Hz Models) ...................................................................................................... 17
6.4 Circuit Board Jumpers (All Export 50 Hz 1-Pump Models) ........................................................................................ 18
6.5 Circuit Board Jumpers (All Export 50 Hz 2-Pump Models) ........................................................................................ 18
Page 4
7.0 Troubleshooting Using The Control Panel ............................................................................. 19
7.1 Control Panel Displays ..............................................................................................................................................19
7.2 Control Panel Default Display .................................................................................................................................... 19
7.3 Control Panel Status and Error Messages ................................................................................................................19
7.4 Testing Flow/Pressure Switch .................................................................................................................................... 21
8.0 Troubleshooting without The Control Panel .......................................................................... 22
8.1A No Heat or Not Enough Heat (All Models) ................................................................................................................. 22
8.1B No Heat or Not Enough Heat (All Models) ................................................................................................................. 23
8.1C No Heat or Not Enough Heat (All Models) .................................................................................................................24
8.1D No Heat or Not Enough Heat (All Models) .................................................................................................................25
8.1E No Heat or Not Enough Heat (All Models) ................................................................................................................. 26
8.2 Intermittent Heating ...................................................................................................................................................27
8.3 Nothing Works ...........................................................................................................................................................27
8.4 Hot Tub Doesn’t Come On for Filter Cycle ................................................................................................................28
8.5 House Breaker Trips .................................................................................................................................................. 28
8.6A DCU Unit (J-LX Collection) ........................................................................................................................................ 29
8.6B DCU Unit (J300 Collection)........................................................................................................................................30
8.6C Hot Tub Light Will Not Come On (J-LX/2011-2013 J300 Models) ............................................................................. 31
8.6D Light does not come on (J200 Collection Standard light) ..........................................................................................32
8.6E 2013+ Light diagram of the DCU Unit (J200 Collection) ............................................................................................ 33
8.6F Hot Tub Light Will Not Come On (J200 Collection CL Lighting) ................................................................................34
8.7 No Jets.......................................................................................................................................................................35
8.8 2011 Ozonator Not Working ......................................................................................................................................36
8.9 2012+ CLEARRAY Not Working ..............................................................................................................................37
8.10 Weak or Surging Jets ................................................................................................................................................38
8.11 Jets Pump Runs and Quits During Jet Mode.............................................................................................................39
8.12 Circulation Pump Not Working (JLX, J300 and J200 with circ pump option only) ..................................................... 40
8.13 Troubleshooting A Thermal Pump Cutout .................................................................................................................. 41
8.14 Pump 1 Hums and Will Not Start ............................................................................................................................... 41
APPENDIX .......................................................................................................................................... 42
A1 Checking Voltage to Hot Tub .....................................................................................................................................43
A2 Checking Current Consumption of Devices ............................................................................................................... 45
A3 Checking Voltages to Devices ...................................................................................................................................46
A4 Testing Flow/Pressure Switch .................................................................................................................................... 47
A5 About Fuses...............................................................................................................................................................48
A6 The Watchdog “- - -” ..................................................................................................................................................48
A7 Understanding Sanitizers...........................................................................................................................................49
A8 Understanding pH ...................................................................................................................................................... 49
A9 North American 60 Hz 120V/240V Convertible 1-Pump Models ...............................................................................50
A10 North American 60 Hz 240V 1- or 2-Pumps Models .................................................................................................. 51
A11 Export 50 Hz 230V 1-Pump Models ..........................................................................................................................52
A12 Export 50 Hz 230V 1- or 2-Pump Models ..................................................................................................................53
A13 Load Box Connection Diagrams A - D (North American 60 Hz) ................................................................................54
A14 Temperature Sensor/Hi-Limit Sensor Resistance Chart ............................................................................................ 56
A15 Flow Switch Illustration (Models with a circulation pump)..........................................................................................57
A16 Pressure Switch Illustration (Models without a circulation pump) ..............................................................................57
A17 Sensor Harness Diagram ..........................................................................................................................................57
A18 Transformer Test ........................................................................................................................................................ 58
A19 Troubleshooting The Optional Stereo System ........................................................................................................... 59
A20 Glossary of Terms ...................................................................................................................................................... 62
A21 Troubleshooting Data Collection Form ...................................................................................................................... 63
Page 5

1.0 Standard Troubleshooting Approach (S.T.A.)

1.1 Why a Standard Troubleshooting Approach?

Service prices are basically set by local industry and geographic region. Stiff competition in the service indus-
try has made it difcult to raise the price of a service contract; or charge more for time and materials than the competitive shop down the street. If your service business is to be protable you must control the overall cost
of service. The total cost of service is made up of many individual cost factors, but three in particular are more important than the rest combined:
1. Time of Repair - How long it takes to nd and x a problem.
2. Time Between Failures - How often you are called to repair any one particular hot tub? How many times
are you called back to x the same problem on the same hot tub?
3. Parts Usage - Except in rare circumstances, only one part fails. How many parts do you replace before you
nd the bad one?
This S.T.A. manual has been designed to help you control the overall cost of service by focusing on the three
important aspects of your job outlined above. The S.T.A. will help you x your customer’s hot tub quickly, x it
well, and use fewer parts.

1.2 How to Use the S.T.A.

The S.T.A. was developed by the Technical Support Department and is designed to be the communications link between you and your customers. If you call for help on any symptom covered in this book, you will be told to do what the S.T.A. recommends, therefore, you will save time by calling technical support after you have done what the S.T.A. tells you to do.

1.3 Professional Customer Service

Doing your job in a way that keeps cost of service low and prot margin high also creates customer satisfac­tion. That’s being a professional!

1.4 Before Leaving the Shop

Phone the customer(s), personally if possible, and ask what problem(s) should be corrected. This may not tell
you what work must be done or what part(s) must be replaced, but it will tell you what you must x after you
arrive.

1.5 Fixing the Hot Tub

Use the S.T.A. to see how the Technical Support Department would approach the customer’s complaint. Try to
x the problem following the S.T.A. Use your experience and other information to help you answer any “Whys”
or “Hows.” The S.T.A. is designed to keep unnecessary part replacement to a minimum. Least expensive, most
likely, and easily changed parts are always swapped rst. Some parts, like control panels and temperature
sensors do not require complete installation to be temporarily swapped out for testing purposes. You should carry such spares as “Tools.”

1.6 Before Calling Technical Support

Make sure you have followed the S.T.A. and lled out a “Troubleshooting Data Collection Form”
(refer to example on page 63). Have the S.T.A. manual and the Troubleshooting Data Worksheet near the telephone. Technical Support can help you best if these two things become the communica­tions tools for the phone call.

1.7 Before Leaving the Customer

Even if you didn’t have to ll out a Troubleshooting Data Collection Form, please do so. If this is a warranty repair, the information will be needed when your ofce lls out the “Warranty reimbursement form.” In any case,
it will help you spot trouble before it happens. Pumps burn up if voltage at the hot tub is too low. Circuit break­ers trip if heaters and motors draw too much current (Amps). Wires overheat and connections burn if wire size is too small or push-on connectors are loose. Call backs cause cost of service to increase!
1
Page 6

1.8 Satisfying the Customer

Most customers do not care what work you have done or what parts you have replaced, but they always care whether or not their problem goes away. When you are done, show them that their problem is gone. If they ask how you did it, take a few minutes to explain. Show them the bad part(s) and explain or show why it is bad.
Develop the habit of examining the hot tub’s you service. Compliment customers on the
things they are doing right. Tell them how their care and attention can stop trouble before it starts.
Mention if you noticed any adverse conditions, especially in hot tub’s under warranty or contract, that could
lead to failure. Can the customer correct the problem? Would they like you to correct it? Can you recom­mend someone? Would they like an estimate?
Think of yourself and the customer as a “team” trying to keep the product up and running as cost-effective
and time-efcient as possible. That’s good for the customer, and it is good for your business.
2
Page 7

2.0 Electro Static Discharge (E.S.D.)

2.1 E.S.D. - What is it? What does it do?

Static electricity is always being generated around us, even at those times of the year when we no longer get zapped after walking across a rug and touching something.
Like all state-of-the-art circuit boards, the hot tubs circuit board can be damaged by unnoticed static electricity. Damaged is the key word. Sometimes a board which has been subjected to E.S.D. will fail immediately upon being put back into service.
If the hot tub runs only a few days, the customer thinks you provided poor service.
If the hot tub runs only a few months, the customer thinks the circuit board is a low quality product.
The customer loses use of the hot tub. You lose money because you must go back to make it right.
Jacuzzi loses its reputation for quality.

2.2 Avoiding E.S.D. Damage

We can’t prevent static charges from building up within our bodies as we go about our jobs, so we must do three things to protect circuit boards from getting zapped:
1. Never transport or ship circuit boards - Good boards or bad boards -
except in static protective bags.
2. Never remove the board from the static protective bag unless you are
ready to install it in the hot tub.
3. After removing the bad board from the hot tub, A) lay it on the ground,
B) remove the replacement board from the static protective bag, C) lay the replacement board on the ground, D) place the bad board in the bag from which you removed the replacement board, E) return bad board(s) in undamaged sealed static protective bags.

2.3 What About Wrist Straps and Special Mats?

The purpose of these devices is to keep the technician, the work surface, and the circuit board at the same electrical potential, and to drain into ground any static charges which might build up. Proper use of the wrist strap and special mat guarantees maximum protection against E.S.D. damage.

2.4 Must Wrist Straps and Mats be Used When Replacing A Circuit Board?

No, if you keep the spare board in the protective bag during transport and you observe a few simple tech­niques during replacement.
The possibility of E.S.D. damage to the circuit board during replacement will be minimal because of the hot tub’s design and the way you normally work on it. Touching the grounding lug or heater will drain all built-up static charges from your body much like a wrist strap would. Laying the bad board on the ground will tend to
keep it neutral. Touching a nger to the grounding lug or heater immediately before removing the good board
from the bag will drain any charges built up by the rustling of your clothes. Laying the good board on the ground after removing it from the bag will tend to keep it neutral. Another quick touch of the grounding lug or heater before picking up the bad board will again drain built up charges. Slipping the bad board into the protec­tive bag will allow it to be transported safely. Another quick touch of the grounding lug or heater before picking up the good board will again drain any charges built up by the rustling of your clothes. In the process of install­ing the replacement board, you and the board will be grounded to the load box, grounding lug, or heater, drain­ing off charges you may build up during installation.
3
Page 8

3.0 Main Control Panel Functions

3.1 J-LX Control Panel

A. 2013+ P/N 6600-506 SMT panel (replaced 6600-239 early in 2013) B. 2011-2012 P/N 6600-440
C
B
A
1
F
D
E
Display shown for example purposes only, actual water tem-
perature display will vary.
Button Function
LED Display: Can display current water temperature (default display), water temperature setpoint, selected
A
ltration/heating mode, and error messages.
B
Warmer Button: Increases water temperature setpoint.
C
Cooler Button: Decreases water temperature setpoint.
Light Button: Turns waterfall, footwell and accent lighting on in unison. Press once for high intensity, a sec-
D
ond time for medium intensity, a third time for low intensity, a fourth time to turn off. The displayed color is changed using the light mode button (E) below.
E
Light Mode Button: Selects one of 4 color modes for waterfall, footwell and accent lighting.
Jets 1 Button: Turns jets pump #1 on and off. Press once for low speed; a second time for high speed and a
F
third time to turn off.
H
2
G
G
Jets 2 Button: Turns high-speed jets pump #2 on and off. Press once to turn on; a second time to turn off.
H
Heat Indicator: Lit when heater is on.
OPERATION DETAILS
Temperature Adjustment: 65 to 104°F (18 to 40°C); temperature override not possible. Software default setting is
100°F (38°C).
Light System Operation: Light runs for 2 hours then shuts off.
Jets Button Operation: Jets run for 20 minutes after activated then turn off automatically to conserve energy. Simply press JETS Button to continue operation for an additional 20 minutes.
4
Page 9

3.2 J300 Control Panel

2-pump J-375, J-365, J-355, J-345 and J-335
A
B
C
Display shown for example purposes only, actual water tem-
perature display will vary.
D
A. 2013 P/N 6600-504 SMT panel
H
G
F
E
A. 2013 P/N 6600-503 SMT panel
(replaced 6600-235 early in 2013)
B. 2008-2012 P/N 2600-328
B. 2008-2012 P/N 2600-331
Button Function
A
LED Display: Can display current water temperature (default display), water temperature setpoint, selected
ltration/heating mode, and error messages.
1-pump J-315 and J-325
HA
B
C
Display shown for example purposes only, actual water tem-
perature display will vary.
D
E
F
(replaced 6600-237 early in 2013)
B
C
Warmer Button: Increases water temperature setpoint.
Cooler Button: Decreases water temperature setpoint.
Light Button: Turns waterfall, footwell, pillows and cupholder lights on in unison. Press once for high intensity,
D
a second time for medium intensity, a third time for low intensity, a fourth time to turn off. The displayed color is changed using the light mode button (E) below.
E
F
G
H
Light Mode Button: Selects one of 4 color modes for waterfall, footwell, pillows and cupholder lights.
Jets 1 Button: Turns jets pump #1 on and off. Press once for low speed; a second time for high speed and a
third time to turn off.
Jets 2 Button: Turns high-speed jets pump #2 on and off. Press once to turn on; a second time to turn off (2-pump models only)
Heat Indicator: Lit when heater is on.
OPERATION DETAILS
Temperature Adjustment: 65 to 104°F (18 to 40°C); temperature override not possible. Software default setting is
100°F (38°C).
Light System Operation: Light runs for 2 hours then shuts off.
Jets Button Operation: Jets run for 20 minutes after activated then turn off automatically to conserve energy. Simply press JETS Button to continue operation for an additional 20 minutes.
5
Page 10

3.3 J200 Control Panel

Used on:
2012+ J-280, J-275, J-245, J-235
2011 2-pump J-280 and J-270
C
1
A
B
F
A. Mid 2013+ P/N 6600-501 SMT panel
B. 01/2013-Mid 2013 6600-329
D
2
E
G
Used on:
2013+ J-210
2011-2012 1-pump J-230 and J-210
A. Mid 2013+ P/N 6600-500 SMT panel
B. 2009-Mid 2013 P/N 2600-333
C. 2009-2012 P/N 2600-329
Button Function
C
1
A
B
F
E
G
A
B
C
D
LED Display: Can display current water temperature (default display), water temperature setpoint, selected
ltration/heating mode, and error messages.
Heat Indicator: Lit when heater is on.
Jets 1 Button: Turns jets pump #1 on and off. Press once for low speed; a second time for high speed and a
third time to turn off.
Jets 2 Button: Turns high-speed jets pump #2 on and off. Press once to turn on; a second time to turn off (2-pump models only)
Light Button:
E
With standard incandescent light: Turns underwater light on and off. With optional (2011-2012)/standard (2013+) LED lighting system: Turns underwater light and top rim accent lights on in one of three random modes or one of seven solid colors.
F
G
Warmer Button: Increases water temperature setpoint.
Cooler Button: Decreases water temperature setpoint.
OPERATION DETAILS
Temperature Adjustment: 65 to 104°F (18 to 40°C); temperature override not possible. Software default setting is
100°F (38°C).
Light System Operation: Light runs for 1 hour then shuts off.
Jets Button Operation: Jets run for 20 minutes after activated then turn off automatically to conserve energy. Simply press JETS Button to continue operation for an additional 20 minutes.
6
Page 11

4.0 Standard Programming Functions

4.1 Setting Filter Cycle Start Time (J200/ 2011-2013 J300/ JLX Collections)

Two methods for setting the lter cycle start time are possible:
1. Turn power on to the hot tub two minutes prior to the desired lter cycle start time, or
2. Press and hold both WARMER and COOLER buttons at the same time, then press the JETS 1
button once to reset the control panel and start the power-up sequence. During the power-up se-
quence, the factory default lter cycle (F1) and temperature setpoint 100°F (38°C) are automatically selected. To select another lter cycle at this time, refer to Section 4.2 below. The selected lter cycle will start approxi-
mately two minutes after the power-up sequence ends. Example: If you desire your rst lter cycle to begin at 10:00 AM, perform either of the above steps 1 or 2 at 9:58 AM. Filter cycle start time may vary slightly from
setpoint.

4.2 Filtration Options

The control system activates a programmable “standard” or “economy” ltration/heating cycle to remove larger debris missed by the circulation pump ltration system (when equipped). These cycles utilize pump 1 and the larger lter cartridge end to quickly clear “skim” the water of large debris and minimize their “bathtub ring” effect. Apart from their ltration benet, each mode also effects the op-
eration of your spa’s heater. Refer to Section 4.3 below for additional information.
A. F0-F3 Standard Skimming/Heating Modes (2011-2013 J300 Collection)
Standard ltration/heating modes are typically selected by customers that use their spa on a fre-
quent basis and desire a fully heated spa when lifting the cover. In these modes, the water tem­perature is regulated by the set temperature, the circulation pump, and heater which turns on as needed. After the programmed set temperature is reached, the heater turns off and the circulation
pump continues to operate for the remaining of the cycle to lter and clean your spa.
Note: In 2011-2012 the circulation pump had a default runtime of 24 hours. In 2013 the default time changed to 8 hours (except for the J-315 and J-325).
B. F4-F6 Economy Skimming/Heating Modes (2011-2013 J300 Collection)
Economy ltration/heating modes are typically selected by customers that use their spa on an infrequent
basis or to simply desire to minimize energy consumption levels. In these modes, the water temperature is
regulated by the set temperature, circulation pump, and heater only while a programmed lter cycle is run­ning (unless in summer logic; refer to Section 5.4, page 14).
Note:
Economy modes may consume less energy than standard modes above, in cold or freezing conditions.
In 2011-2012 the circulation pump had a default runtime of 24 hours. In 2013 the default time changed to 8 hours (except for the J-315 and J-325).
C. F0-F3 Standard Skimming/Heating Modes (J-LX Collection)
Standard ltration/heating modes are typically selected by customers that use their spa on a frequent basis
and desire a fully heated spa when lifting the cover. In these modes, the water temperature is regulated by the set temperature. The circulation pump, and heater turn on as needed. After the programmed set tem­perature is reached, the heater turns off and the spa continues normal operations.
Note: The circulation pump also supplies heated water to the spa when the heater turns on. Any time the circulation pump runs outside of a programmed cycle, that run time will reduce the length of the next cycle, started in 2014.
D. F4-F6 Economy Skimming/Heating Modes (J-LX Collection)
Economy ltration/heating modes are typically selected by customers in warm climates where heat up
times are minimized due to higher ambient temperatures. In these modes, the water temperature is regulat-
ed by the set temperature. The circulation pump, and heater only while a programmed lter cycle is running (unless in summer logic; refer to Section 5.4, page 14).
Note: Economy modes may consume less energy than standard modes above, in cold or freezing conditions.
7
Page 12
E. F0-F3 Standard Skimming/Heating Modes (J200 Cellection; F0 Mode used on 2011-2012 circulation
pump models)
Standard ltration/heating modes are typically selected by customers that use their spa on a frequent basis
and desire a fully heated spa when lifting the cover. In these modes, the water temperature is regulated by the set temperature, and heater which turns on as needed. After the programmed set temperature is
reached, the heater turns off followed by the jets pump 1 unless a programmed ltration cycle is running.
Note: Standard modes may consume more energy than Economy models below in cold or freezing climates.
F. F4-F6 Economy Skimming/Heating Modes (J200 Cellection)
Economy ltration/heating modes are typically selected by customers in warm climates where heat up
times are minimized due to higher ambient temperatures. In these modes, the water temperature is regu-
lated by the set temperature, and heater only while a programmed lter cycle is running (unless in summer logic; refer to Section 5.4, page 14).
Note: Economy modes may consume less energy than standard modes above in cold or freezing conditions.
G. Lock Modes L1-L3
These modes are designed for use during spa service or to prevent unauthorized use.
Note: Economy modes may consume less energy than standard modes above in cold or freezing conditions.

4.3 Programming Filter Cycles (J-LX/ 2011-2013 J300 Collection)

To select a pre-programmed lter cycle or lock mode, press and hold both control panel WARMER
and COOLER buttons at the same time, then release. Then press either WARMER or COOLER
buttons to select either lter mode F0-L2. During the ltration heating cycle the jets pump1 low speed
and circulation pump will activate.
Standard Mode F0 5 minutes of ltration per day (one 5 minute “Blow-Out” cycle every 24 hours to purge all plumbing lines. F1 1 hour of ltration per day (one 30-minute cycle every 12 hours); this is the factory default setting. F2 1.5 hours of ltration per day (one 30-minute cycle every 8 hours). F3 2 hours of ltration per day (one 30-minute cycle every 6 hours).
Economy Mode F4 1 hour of ltration/heating per day (one 30-minute cycle every 12 hours). F5 1.5 hours of ltration/heating per day (one 30-minute cycle every 8 hours). F6 2 hours of ltration/heating per day (one 30-minute cycle every 6 hours).
Lock Mode L1 Lock Out (disables all hot tub functions to permit lter cleaning). Note: The spa should not be left in this lock mode for an extended period of time. Especially in colder climates
or when freezing conditions exist.
L2 Lock Mode (disables the jets buttons to prevent unauthorized use of the hot tub) ltration/heating
cycles and heater will continue to operation as programmed in this mode. The temperature display
ashes when this function is enabled. Example: The “F3” lter cycle was enabled prior to choosing lock mode. The hot tub continues to perform lter cycle “F3” until lock mode is canceled, allowing another lter cycle to be selected.
L3* Lock Mode (disables the temperature up and down buttons to prevent unauthorized temperature
adjustments). Filtration/heating cycle will continue to operate as programmed in this mode. The jets and
lights buttons will still continue to operate as normal. The temperature display ashes when this function
is enabled. *Due to a difference in software this feature is not available for all models, started in 2014.
Note: To exit a Lock Mode you will need to re-enter the ltration/heating modes and select a cycle from F0-F6.
8
Page 13
4.4 Programming Filter Cycles (2011-2012 J200 models equipped with a circulation
pump)
To select a pre-programmed lter cycle or lockout mode, press and hold both control panel WARMER and COOLER buttons at the same time, then release. Then press either WARMER or
COOLER buttons to select either lter mode F0 through L2 below:
Standard Mode F0 5 minutes of ltration per day (one 5 minute “Blow-Out” cycle every 24 hours to purge all plumbing lines. F1 1 hour of ltration per day (one 30-minute cycle every 12 hours); this is the factory default setting. F2 1.5 hours of ltration per day (one 30-minute cycle every 8 hours). F3 2 hours of ltration per day (one 30-minute cycle every 6 hours).
Economy Mode F4 1 hour of ltration/heating per day (one 30-minute cycle every 12 hours). F5 1.5 hours of ltration/heating per day (one 30-minute cycle every 8 hours). F6 2 hours of ltration/heating per day (one 30-minute cycle every 6 hours).
Lock Mode L1 Lock Out (disables all hot tub functions to permit lter cleaning) - If hot tub is heating when the system is
put into lockout mode, the heater will immediately turn off and the pump will cycle water for 30 seconds to cool heater element, then turn off.
L2 Lock Mode (disables the jets and light buttons to prevent unauthorized use of the hot tub) - lter cycles and
heater will continue to operation as programmed in this mode. The temperature display ashes when this
function is enabled. Example: The “F3” lter cycle was enabled prior to choosing lock mode. The hot tub continues to perform lter cycle “F3” until lock mode is canceled, allowing another lter cycle to be selected.
4.5 Programming Filter Cycles (2013+ J200 models not equipped with a circulation
pump)
To select a pre-programmed lter cycle or lockout mode, press and hold both control panel WARMER and COOLER buttons at the same time, then release. Then press either WARMER or
COOLER buttons to select either lter mode F1 through L2 below:
Standard Mode F1 4 hours of ltration a day (2 hour cycle every 12 hours): this is the factory default setting. F2 6 hours of ltration a day (2 hour cycle every 8 hours)
F3 8 hours of ltration a day (2 hour cycle every 6 hours)
Economy Mode F4 4 hours of ltration a day (2 hour cycle every 12 hours) F5 6 hours of ltration a day (2 hour cycle every 8 hours) F6 8 hours of ltration a day (2 hour cycle every 6 hours)
Lock Mode L1 Lock Out (disables all hot tub functions to permit lter cleaning). Note: The spa should not be left in this lock mode for an extended period of time. Especially in colder climates
or when freezing conditions exist.
L2 Lock Mode (disables the jets buttons to prevent unauthorized use of the hot tub) ltration/heating cycles
and heater will continue to operation as programmed in this mode. The temperature display ashes
when this function is enabled. Example: The “F3” lter cycle was enabled prior to choosing lock mode. The hot tub continues to perform lter cycle “F3” until lock mode is canceled, allowing another lter cycle to be selected.
L3* Lock Mode (disables the temperature up and down buttons to prevent unauthorized temperature
adjustments). Filtration/heating cycle will continue to operate as programmed in this mode. The jets and
lights buttons will still continue to operate as normal. The temperature display ashes when this function
is enabled. *Due to a difference in software this feature is not available for all models, started in 2014.
Note: To exit a Lock Mode you will need to re-enter the ltration/heating modes and select a cycle from F0-F6.
9
Page 14
4.6 Programming the Circulation Pump Filtration Cycle (For models equipped with a circula-
tion pump)
Press and hold the Jets pump 1 ( 1 ) and Cooler ( ) button at the same time for 3 seconds to access the circulation pump programming. Continually press the Warmer (
1
below. Then select a cycle and press the Jets pump 1 (
) button to activate that cycle. Upon pressing the
jets pump 1 button the system will save your selection, exit the program menu and return to the main menu. Note:
2014+ Any time the circulation pump runs outside of a programmed cycle (except for C0 and C6), that run time will reduce the length of the next cycle.
After 10 seconds the programming screen will revert back to the temperature if no buttons are pressed. You cannot have more than one circulation pump cycle activated at a time.
0 hours of circulation per day
4 hours of circulation per day
8 hours of circulation per day (recommended factory default setting)
12 hours of circulation per day
16 hours of circulation per day
20 hours of circulation per day
) button to scroll up through the cycles
24 hours of circulation per day
Note: The recommended factory default setting for the Select Series is 8 hours. This setting should not be altered. Running the circulation pump less than the factory recommended time might result in issues with water quality maintenance.
In extreme bitter cold weather,
32°F (0°C), we recommend you program the circulation pump to run 24
hours.
4.7 Programming the CLEARRAY® (Ultraviolet) Water Purification System (For models
equipped with a circulation pump)
A. Programming the CLEARRAY System (U) or Corona Discharge Ozone (O3)
1
Press and hold the Jets pump 1 ( the circulation pump programming menus by pressing the Warmer button, Figure 1.
) and Cooler ( ) button at the same time for 3 seconds. Scroll pass
Press Press Press Press Press
Will select “O3” option and exit menu.
1
PressPress
Press
Press
Will take you back to “C0” option.
1. After the last cycle, “C6,” the LED screen will display “U” or “O3.” If the LED screen is displaying “U” then pressing the Jets pump 1 will change the sanitizing system from “U” to “O3” and exit the programming menu. If the LED screen is displaying “O3” then pressing the Jets pump 1 will change the sanitizing system
from “O3” to “U” and exit the programming menu. You will see one of the two congurations below:
A. C0, C1, C2, C3, C4, C5, C6, U, 365 (duration countdown timer) B. C0, C1, C2, C3, C4, C5, C6, O3, = Note: For the O3 option the “=” disables the duration countdown timer.
10
Page 15
2. If you do not wish to change the option do not press any buttons and after 10 seconds the display will return to the main menu.
Note: If the CLEARRAY System has been selected, when the time allotted has expired (365 days)
the display screen will ash between the water temperature and “blb.” At this time the UV bulb must
be replaced, the quartz tube must be cleaned and the duration countdown timer needs to be reset.
B. Resetting the duration countdown timer (CLEARRAY System only) Once the duration countdown timer for the CLEARRAY System has reached zero, you will need to reset it, replace the UV bulb and clean the quartz tube. To reset the duration countdown timer:
Press Press Press Press Press
Press
1
Will reset the timer to 365 days and exit the menu
Press
Press
Press
1. Press and hold the Jets pump 1 ( 1 ) and Cooler ( ) button at the same time for 3 seconds.
2. Press the Warmer (
3. If the counter has reached “0,” pressing the Jets pump 1 (
) button until the display shows “0.”
1
) button will reset the timer. If the timer is
not at “0” pressing the Jets pump 1 will not reset it.
Note: If the spa power is interrupted, the duration countdown timer is not affected. The number of days re-
maining is stored in the memory and will continue to countdown once power is regained.
4. If the duration countdown timer is not at “0” and you need to reset it: a. Press and hold the Jets pump 1 and Cooler buttons at the same time for 3 seconds. b. Press the Warmer button to scroll to “U.” c. Press the Jets pump 1 button to switch from “U” to “O3.” d. Press and hold the Jets pump 1 and Cooler buttons at the same time for 3 seconds. e. Press the Warmer button to scroll to “O3.” f. Press the Jets pump 1 button to switch from “O3” to “U.” The timer has been reset to 365 days.
4.8 Programming the CLEARRAY (Ultraviolet) Water Purification System (For models NOT
equipped with a circulation pump)
A. Programming the CLEARRAY System (U) or Corona Discharge Ozone (O3) Press and hold the Jets pump 1 ( sanitizing system program. The screen will display one of the two menus below:
) and Cooler ( ) button at the same time for 3 seconds to enter the
CLEARRAY menu O3 menu
Press
or
Press
or
1. If the LED screen is displaying “U” then pressing the Jets pump 1 will change the sanitizing system from “U” to “O3” and exit the programming menu. If the LED screen is displaying “O3” then pressing the Jets pump 1 will change the sanitizing system from “O3” to “U” and exit the programming menu.
Note: For the O3 option the “=” disables the duration countdown timer.
2. If you do not wish to change the option do not press any buttons and after 10 seconds the display will return to the main menu.
Note: If the CLEARRAY System has been selected, when the time allotted has expired (365 days)
the display screen will ash between the water temperature and “blb.” At this time the UV bulb must
be replaced, the quartz tube must be cleaned and the duration countdown timer needs to be reset.
11
Page 16
B. Resetting the duration countdown timer (CLEARRAY System only) Once the duration countdown timer for the CLEARRAY System has reached zero, you will need to reset it, replace the UV bulb and clean the quartz tube. To reset the duration countdown timer:
Press Press
1
1. Press and hold the Jets pump 1 (
2. Press the Warmer (
) button until the display shows “0.”
3. If the timer has reached “0,” pressing the Jets pump 1 (
) and Cooler ( ) button at the same time for 3 seconds.
) button will reset it. If the timer is not at “0”
pressing the Jets pump 1 button will not reset it.
Note: If the spa power is interrupted, the duration countdown timer is not affected. The number of days remain-
ing is stored in the memory and will continue to countdown once power is regained.
4. If the duration countdown timer is not at “0” and you need to reset it: a. Press and hold the Jets pump 1 and Cooler buttons at the same time for 3 seconds. b. Press the Warmer button to scroll to “U.” c. Press the Jets pump 1 button to switch from “U” to “O3.” d. Press and hold the Jets pump 1 and Cooler buttons at the same time for 3 seconds. e. Press the Warmer button to scroll to “O3.” f. Press the Jets pump 1 button to switch from “O3” to “U.” The timer has been reset to 365 days.

4.9 2011 Aftermarket Ozonator Facts

Ozone System Specications are:
J-LX Ozone System Specications
• Circulation pump and ozone run 8 hours. Cycle starts approximately two minutes after power up.
• Ozonator shuts off when either JETS button is pressed. The Ozonator will resume operation approximately
5 minutes after jets are turned off intentionally or automatically. The ozonator also shuts off if the hot tub goes into “summer logic.” See Section 5.4 (page 14).
• Pressing a JETS button during an active lter cycle cancels the lter cycle until the next term.
Note: Pump may stay on if a heat call is present.
J300 Ozone System Specications (All 2011-2013 models) J200 Ozone System Specications (J-270, J-280, and J-230 models with a Circulation Pump)
• Circulation pump and ozone run 24 hrs.
• Ozonator shuts off when either JETS button is pressed. The Ozonator will resume operation approximately
5 minutes after jets are turned off intentionally or automatically. The ozonator also shuts if the hot tub goes into “summer logic.” See Section 5.4 (page 14).
• Pressing a JETS button during an active lter cycle cancels the lter cycle until the next term.
Note: Pump may stay on if a heat call is present.
J200 Ozone System Specications (Models without Circulation Pump)
• Ozonator runs during a programmed lter cycle.
• Ozonator turns off when either JETS button is pressed and will resume operation approximately 5 minutes
after jets are turned off intentionally or automatically.
• Pressing a JETS button during an active lter cycle cancels the lter cycle until the next term.
Note: Pump may stay on if a heat call is present.
12
Page 17

4.10 2012+ CLEARRAY Facts

Our water purication system will begin disinfecting your water instantly.
is exclusive technology utilizing natural ultraviolet technology to sanitize your water, disinfecting bacteria, viruses, and algae in portable hot tubs. The ultraviolet light otherwise known as UV-C or germicidal light inacti­vates the microorganisms by disrupting the DNA so that it cannot reproduce and is considered lifeless. The bal-
last is the power supply for the purication system; it has two LED indicator lights the green indicating incoming power ow and the red indicating the system is properly working. CLEARRAY is standard for all models.
Note:
• For JLX/2011-2013 J300 Models: The CLEARRAY System only runs when the circulation pump is running
and shuts off when either jets pump is manually activated during spa use. The system will remain off for 5 minutes after both jets pumps time out or are manually turned off, then resume operations if the circulation pump is programmed to run.
For J200 Models: The CLEARRAY System only runs when the jets pump 1 is running.
System Specications are:
2011+ J-LX/J-LXL/ 2011-2013 J-375/J-365/J-355/J-345/J-335 CLEARRAY
• Circulation pump and CLEARR AY run 8 hours (unless altered). Cycle starts approximately two minutes after
power up.
• CLEARRAY shuts off when either JETS button is pressed. It will resume operation approximately 5 minutes
after jets are turned off intentionally or automatically. The CLEARR AY also shuts off if the hot tub goes into “summer logic.” See Section 5.4 (page 14).
CLEARRAY Water Purication System
2011-2013 J-325/J-315 Ozone System Specications J200 Ozone System Specications (Models with a Circulation Pump)
• Circulation pump and CLEARR AY run 24 hrs. Cycle starts approximately two minutes after power up.
• CLEARRAY shuts off when either JETS button is pressed. It will resume operation approximately 5 minutes
after jets are turned off intentionally or automatically. The CLEARR AY also shuts if the hot tub goes into “summer logic.” See Section 5.4 (page 14).
J-200 CLEARRAY System Specications (Models without Circulation Pump)
• The CLEARR AY will run whenever jets pump 1 is running.

5.0 Additional Control Panel Functions

5.1 Setting Water Temperature and Overtemp Feature

1. Press WARMER or COOLER button once and release while the current water temperature is
displayed to view the current temperature setpoint, then;
2. Press WARMER or COOLER button within 3 seconds to increase or decrease set temperature setpoint in 1 degree increments as desired. Water temperature can set to any value within 65-
104°F (18-40°C);
3. After 3 seconds of keypad inactivity the LED display will return to actual water temperature and the new temperature setpoint will be maintained.
4. To access the overtemp feature that allows the spa to reach 106ºF (41ºC) follow the steps below:
A. Press and hold the WARMER button then;
B. Press and hold the JETS 1 button at the same time for 2 seconds. You will see the tempera-
ture rise to 106ºF (41ºC) on the LED display. To lower the temperature, press the COOLER button.
C. When the overtemp has been activated, the white decimal point after the last digit will ash on and off
every second as an indicator for being in the overtemp mode.
Note: Once the temperature goes below 104ºF (40ºC) and you would like to raise the temperature to 106ºF (41ºC) again, you will have to repeat step 4 above.
J-LX models
2011-2013 J300 models
J200 models
13
Page 18

5.2 Selecting Jets Speed

Press JETS 1 once for low speed; a second time for high speed; a third time to turn off.
Press JETS 2 (2 Pump Models Only) once for high speed; a second time to turn off.
Note: Anytime a pump has been manually turned on by selecting either jet button, it will automatically turn off after approximately 20 minutes. If at this time you desire more jet operation, simply turn the jet pump back on.

5.3 Lock/Unlock Control Panel

The control panel temperature display ashes when Lock Mode is active. Lock Mode disables the
jets and underwater light to prevent unauthorized use of the hot tub or disables all hot tub functions
to permit lter cleaning.

5.4 Summer Logic (Models equipped with the Circulation Pump Option)

When water temperature in the hot tub rises to 2°F (1°C) above the temperature setpoint, the hot tub goes into “summer logic.” When this happens, the circulation pump automatically turns off to prevent heat addition from the pump that would eventually create an overheat condition. The cir­culation pump, main pump, CLEARRAY and aftermarket ozone (if applicable) will remain off until the water temperature cools to the set temperature, then reactivate as programmed. This setting
Water Temp
too high
is not user-programmable. Note: Summer logic does not take effect until the hot tub’s water reaches 95°F (35°C) or higher.

5.5 Multicolored Light System Operation (J-LX/J300 Models, except 2014 J300s)

A. Pressing the LIGHT button activates the Footwell, Waterfall, Air Control LED Lights and
Accent lights (for the JLX Models) in sequence as follows: High - Medium - Low - Off.
J-LX
J300
Anytime the light system has been manually activated, it will automatically turn off after approximately 2 hours. If at this time you desire more light operation, simply turn the light back on.
B. This button offers four light modes for your enjoyment. Press the LIGHT MODE button to se-
lect your favorite lighting effect as follows:
Press
Once
Press
Again
Press
Again
Selects or “freezes” your low speed blending color of choice.
High-Speed Color Blend Mode
Low-Speed Color Blend Mode
Freeze Color Blend Mode:
J-LX
J300
14
Press Again
BLUE (X4) VIOLET (X5) RED (X6)
Selects one of 7 solid (high-intensity) colors of choice.
AMBER (X7) GREEN (X8) AQUA (X9) NEAR
Solid Color Mode:
WHITE (X10)
Page 19

5.6 Multicolored Light System Operation (Standard light for J-210 Models)

Press the LIGHT button once to turn the spa light on in “Random” mode, then repeatedly press the button to turn the light off or to select one of 6 constant colors illustrated below.
RANDOM
FADE
STROBE
OFF
NEAR
WHITE
RANDOM
SOLID
LIGHT
OFF
Spa Light Sequence
RED
BLUE
GREEN
VIOLET
OFF OFF
DARK
OFF OFFOFFOFF
LIME
GREEN
DARK
BLUE
You must press the LIGHT button within 5 seconds between each “off” or “color” step in the light sequence to prevent it from resetting. Note: Any time the spa light is manually turned on, it will automatically turn off after approximately 1 hour. If you desire more light at this time, simply turn the light back on.

5.7 Multi-Colored LED Light System Operation (J200 Collection)

Press LIGHT button once to turn on Random Fade and continue pressing to display one of seven
constant colors, Random Solid color or Strobe (lights ash in white color).
Note:
Anytime the light has been manually turned on, it will automatically turn off after approximately 1 hour to maximize bulb life. If at this time you desire more light operation, simply turn the light back on.
Light system was “optional” in 2011-2012. It became standard in 2013+.
Press
Once
= RANDOM FADE
= off
= NEAR WHITE
= off
= LIGHT BLUE
= off
= VIOLET
= off
= DARK BLUE
= off
= LIME GREEN
= off
= DARK GREEN
= off
= RED
= off
= RANDOM SOLID
= off
= STROBE
Any time the spa light is manually activated, it will remain on for 1 hour then automatically shut off.
Lights display different solid color every 5-6 seconds
= off
Lights flash “strobe” in white color
15
Page 20

6.0 Understanding Circuit Board Pin Assignments

6.1 Circuit Board Jumpers (All North American 60 Hz 1-Pump Models)

All North American 1-pump circuit boards can be congured for either 15/30A or 40A operation (40/50A for J230 models). Refer to jumper pin table and circuit board diagrams for specic system details.
MODEL
J-LX (2011+) Yes X X 3.60+
J-LX (2011+) Yes X X 3.60+
J-375 (2012-2013) Ye s X 3.60+
J-375 (2011) Yes X 3.57+
J-365 (2012-2013) Ye s X 3.60+
J-365 (2011) Yes X 3.57+
J-355 (2012-2013) Ye s X 3.60+
J-355 (2011) Yes X 3.57+
J-345 (2012-2013)
J-345 (2011) Yes X 3.57+
J-335 (2012-2013) Ye s X 3.60+
J-335 (2011) Yes X 3.57+
J-325 (2012-2013) Ye s X 3.60+
J-325 (2011) Yes X 3.57+
J-315 (2012-2013) Ye s X 3.60+
J-315 (2011) Yes X 3.57+
CIRCULATION
PUMP
Yes X 3.60+
6600-726 6000-167 6600-044 6600-286 6600-288
BOARD
LOGIC
6.2 Circuit Board Jumpers (All North American 60Hz 2-Pump Models)
All North American 2-pump circuit boards can be congured for either 40, 50A, or 60A operation. Refer to jumper pin table and circuit board diagram below for specic system details (factory jumper settings shown):
MODEL
J-280 (2013+) No X X 5.59+
J-280 (2012) No X 5.59+
J-280 (2012) Yes X 3.60+
J-280 (2011) No X 5.57+
J-280 (2011) Ye s X 3.57+
J-275 (2012+) No X X 5.59+
J-270 (2012) No X 5.59+
J-270 (2012) Yes X 3.60+
J-270 (2011) No X 5.57+
J-270 (2011) Ye s X 3.57+
J-245 (2012+) No X X 5.59+
J-235 (2012+) No X X 5.59+
J-230 (2012) No X 5.59+
J-230 (2012) Yes X 3.60+
J-230 (2011) No X 5.57+
J-230 (2011) Ye s X 3.57+
J-210 (2012+) No X X 5.57+
J-210 (2011) No X 5.57+
Circ
Pump
6600-042 6600-046 6000-167 6600-287 6600-288 6600-289 6600-720 6600-722
BOARD
LOG-
IC
16
Page 21

6.3 Circuit Board Jumpers (Domestic 60 Hz Models)

J20
Circuit Board #6600-726, 6000-167 and 6600-288; Micro Chip 3.57+)
Pins 1-2: Jumper ON Enables 40A logic; forces heater off when either pump is
on high speed (Pump 2 only runs in high speed)
Pins 1-2: Jumper OFF Enables 50A logic; forces heater off when both pumps are
on high speed
Pins 3-4: Jumper ON Enables 2 Pump Operation Pins 3-4: Jumper OFF Not Used. (Enables 1 Pumps Operation) Pins 5-6: Jumper ON Enables 60A logic; (Remove JP1 1-2 Jumper). Allows the
heater to operate when both pumps are on high speed. Pins 5-6: Jumper OFF Leave off for 40A or 50A Logic Pins 7-8: Jumper ON Enables Celsius (°C) temperature display Pins 7-8: Jumper OFF Enables Fahrenheit (°F) temperature display
Circuit Board #6600-724, 6600-044 and 6600-286; Micro Chip 3.57+)
Pins 1-2: Jumper ON Enables 15A logic; forces heater off when pump is on high
speed (3-wire 120 VAC operation only) Pins 1-2: Jumper ON Enables 30A logic; forces heater off when pump is on high
speed (4- +wire 120/240 VAC operation only) Pins 1-2: Jumper OFF Enables 40A logic; allows the heater to operate when
pump is on high speed (4-wire 120/240 VAC operation
only) Pins 3-4: Jumper ON Not Used Pins 3-4: Jumper OFF Enables 1 Pump Operation Pins 7-8: Jumper ON Enables Celsius (°C) temperature display
Pins 7-8: Jumper OFF Enables Fahrenheit (°F) temperature display
J20
K1
J21
J11
K2
J12
J13
K3
J14
K4
J15
J16
K5
J17
J18
J19
REDJ6BLK
J21
J12
J14
J16
J11
J13
J6
J4
K6 K7 K8
F1
J5
J20
K1
K2
JP1
K3
8 7 6 5
K4
BK Y
423
W
F1*
J15
K5 K7 K8
J5
WHT
J1
JP1
8 7
JP1
8 7 6 5 423
J4
Y
1
J17 J7 J8 J9 J10
6 5 423
J2
J3
1
J7 J8J9J10
7 6 2 4
J1
JP1
8 7 6 5 423
1
Heater IN Heater OUT
1
J2
J3
Circuit Board #6600-720, 6600-046 and 6600-287; Micro Chip 5.57+
Pins 1-2: Jumper ON Enables 40A logic; forces heater off when either pump is
on high speed (Pump 2 only runs in high speed) Pins 1-2: Jumper OFF Enables 50A logic; forces heater off when both pumps are
on high speed
Pins 3-4: Jumper ON Enables 2 Pump Operation Pins 3-4: Jumper OFF Enables 1 Pump Operation Pins 5-6: Jumper ON Enables 60A logic; (Remove JP1 1-2 Jumper). Allows the
heater to operate when both pumps are on high speed Pins 5-6: Jumper OFF Leave off for 40A or 50A Logic Pins 7-8: Jumper ON Enables Celsius (°C) temperature display Pins 7-8: Jumper OFF Enables Fahrenheit (°F) temperature display
Circuit Board #6600-722, 6600-042 and 6600-289; Micro Chip 5.57+
Pins 1-2: Jumper ON Enables 15A logic; forces heater off when pump is on high
speed (3-wire 120 VAC operation only) Pins 1-2: Jumper ON Enables 30A logic; forces heater off when pump is on high
speed (4-wire 240 VAC operation only) Pins 1-2: Jumper OFF Enables 40A logic; allows the heater to operate when
pump is on high speed (4-wire 120/240 VAC operation
only) Pins 3-4: Jumper ON Not Used Pins 3-4: Jumper OFF Enables 1 Pump Operation Pins 7-8: Jumper ON Enables Celsius (°C) temperature display
Pins 7-8: Jumper OFF Enables Fahrenheit (°F) temperature display
J20
K1
J21
J11
K2
J12
J13
K3
J14
K4
J15
J16
K5
J17
J18
J19
REDJ6BLK
J21
J12
J14
J16
J11
J15
J13
J6
J4
K6 K7 K8
F1
J5
K1
K2
JP1
K3
8 7 6 5
K4
BK Y
423
W
F1*
K5 K7 K8
J5
WHT
J17 J7 J8 J9 J10
JP1
8 7 6 5 423
1
J7 J8J9J10
7 6 2 4
JP1
8 7 6 5 423
J4
Y
1
Heater IN Heater OUT
J1
JP1
8 7 6 5 423
1
J2
J3
J1
1
J2
J3
17
Page 22

6.4 Circuit Board Jumpers (All Export 50 Hz 1-Pump Models)

These circuit boards can be congured for 20A or 30A logic. Each mode affects overall energy consumption
and heater performance.
Pins 1-2: Jumper ON Enables 20A logic; forces heater off when jets pump 1 is running in high speed Pins 1-2: Jumper OFF Enables 30A logic; allows heater to operate when jets pump 1 is running in high
speed
Pins 3-4: Jumper ON Enables 2 Pump Operation (2-pump models only) Pins 3-4: Jumper OFF Enables 1 Pump Operation Pins 5-6: Jumper ON Not Used Pins 5-6: Jumper OFF Not Used Pins 7-8: Jumper ON Enables Celsius (°C) temperature display Pins 7-8: Jumper OFF Enables Fahrenheit (°F) temperature display

6.5 Circuit Board Jumpers (All Export 50 Hz 2-Pump Models)

These circuit boards can be congured for 20A, 30A or 40A logic modes. Each mode affects overall energy
consumption and heater performance.
Pins 1-2: Jumper ON Enables 20A logic; forces heater off when either jets pump is on high speed (Pump
2 only runs in high speed)
Pins 1-2: Jumper OFF Enables 30A logic; allows heater to operate with one jets pump running in high
speed
Pins 3-4: Jumper ON Enables 2 Pump Operation Pins 3-4: Jumper OFF Enables 1 Pump Operation Pins 5-6: Jumper ON 40A logic (Remove JP1 1-2 Jumper); allow heater to operate with both jets pumps
running in high speed
Pins 5-6: Jumper OFF Leave off for 20A or 30A logic setting Pins 7-8: Jumper ON Enables Celsius (°C) temperature display Pins 7-8: Jumper OFF Enables Fahrenheit (°F) temperature display
1 Pump (LX 10) Non-Circulation Pump Board
6600-289 → 6600-042 → 6600-722 (5.60 LOGIC)
1 Pump (LX 10) Circulation Pump Board
6600-286 → 6600-044 → 6600-724 (3.61 LOGIC)
2 Pump (LX 15) Non-Circulation Pump Board
6600-287 → 6600-046 → 6600-720 (5.60 LOGIC)
2 Pump (LX 15) Circulation Pump Board
6600-288 → 6000-167 → 6600-726 (3.61 LOGIC)
18
Page 23

7.0 Troubleshooting Using The Control Panel

7.1 Control Panel Displays

Complete operating instructions for the control panel can be found in the owner’s manual. The hot tubs self­diagnostic control system constantly monitors the hot tub for proper operation. When anything goes wrong, the control panel displays a message for the user which may result in a service call. Refer to Section 7.3 below for a listing of error messages and probable causes.

7.2 Control Panel Default Display

The control panel displays the following information during initial start-up:
1. Control panel displays current software microchip revision, then
2. Control panel displays “888” and all indicator LED’s are lit, permitting visual inspection of all
display segments and indicator lights for proper operation.
3. After the initial start-up sequence ends actual water temperature is displayed. If the water
temperature at this time is less than the factory default temperature setting of 100°F (38°C):
J-LX and J-LXL Models: The low speed pump, circulation pump and heater will turn on
and run until the water temperature rises to the factory default temperature setting. Then the low speed pump and heater turn off. The circulation pump will continue to run for the remainder of the 8 hrs.
2011-2013 J300 and J200 (2011-2012 with Circulation Pump) Models: The circulation pump and heater
will turn on and run until the water temperature rises to the factory default temperature setting. Then the heater turns off and the circulation pump remains on for the remainder of the programmed cycle.
J200 (2011+ without Circulation Pump) Models: The low speed pump and heater will turn on and oper-
ate until the water temperature rises to the factory default temperature setting, then both turn off.
Example sequence shown. Actual sequence can vary depending on model.
Approximately two minutes after initial start-up, the rst ltration cycle begins to operate. The ltration cycle can be modied any time after the start-up sequence ends. You will be able to select a pre-programmed lter cycle and reset your temperature setpoint at this time. Press either COOLER or WARMER button once at
this time to display the current temperature setpoint. You can change the setpoint by pressing either COOLER or WARMER button within 3 seconds. Each button press increases or decreases the temperature setpoint by one degree. Three seconds after the setpoint is set, the display defaults back to actual water temperature.

7.3 Control Panel Status and Error Messages

SN1 Nonfunctional Hi-limit Sensor (All Models)
Open or shorted hi-limit sensor. Heater is deactivated. Refer to test steps 1-2 below:
1. Turn off main breaker to hot tub. Refer to appendix, page 56, for expected hi-limit sensor
resistance/water temperature values.
2. Remove hi-limit sensor connector from circuit board test point 21. Refer to pages 50-53 for your circuit
board conguration. Set ohmmeter to 100 kΩ - 200 kΩ range, then measure resistance across hi-limit sen­sor wires (refer to page 56). If sensor resistance tests OK (± 200 Ω), check sensor connections. If con-
nections are OK, replace circuit board. If sensor resistance is incorrect, replace hi-limit sensor.
SN2 Nonfunctional Temperature Sensor (All Models)
Open or shorted temperature sensor. Heater is deactivated. Refer to test steps 1-2 below:
1. Turn off main breaker to hot tub. Refer to appendix, page 56, for expected hi-limit sensor
resistance/water temperature values.
2. Remove temperature sensor connector from circuit board test point 21. Refer to pages
50-53 for your circuit board conguration. Set ohmmeter to 100 kΩ - 200 kΩ range, then
measure resistance across temperature sensor wires (refer to page 56). If sensor resistance tests OK
(± 200 Ω), check sensor connections. If connections are OK, replace circuit board. If sensor resistance is
incorrect, replace temperature sensor.
19
Page 24
FL1 & FL2 Water Flow Problem (All Models)
• FL1: ow or pressure switch not closed when circulation pump is running. Heater is deacti-
vated. Proper water ow is inhibited or ow/pressure switch may be obstructed, misaligned,
or defective. Refer to troubleshooting steps 1-5 below:
1. Remove lter and allow air to bleed out of cartridge. Check lter for trapped air.
2. Check for proper water level.
3. Check for clogged lter cartridge.
4. Check for sticking or damaged oating skimmer.
5. If problem persists, refer to Section 7.4 (page 21) for ow/pressure switch testing instructions.
• FL2: ow switch or pressure switch closed when pump is not running. Heater is deactivated
and pump may or may not turn on. Flow/pressure switch is defective. Refer to Section 7.4 (page 21) for switch testing instructions.
COL Cool Condition (All Models)
If the water temperature drops 20°F (11°C) below the set temperature, the low speed pump and heater will activate to raise the water temperature within 15°F (8°C) of the set temperature. No
corrective action is necessary. This condition is common during water changes and/or rst time ll
ups.
ICE Freeze Condition (All Models)
A potential water freeze condition of 55°F (13°C) has been detected. No action is required. The low speed pump and heater will activate and raise water temperature to approximately 65°F (18°C), canceling the “ICE” error message. After the error message is canceled, the low speed pump will turn off (circulation pump models only) and the heater will remain on until the set tem­perature is reached.
OH Overheat Condition (All Models)
Water temperature is above acceptable limits. DO NOT ENTER HOT TUB WATER! Water tem­perature has reached 116°F (47°C) and the low speed pump has activated to circulate water through the heater to cool it down for approximately 6 minutes. Refer to test steps 1-4 below:
1. Verify actual water temperature with an accurate thermometer. If actual water temperature is
less than 110°F (44°C), proceed to steps 2-4.
2. Turn off main breaker to hot tub. Refer to appendix page 56 for expected hi-limit/temperature sensor
resistance/water temperature values.
3. Remove hi-limit sensor connector from circuit board points 22. Verify that the heater is not excessively hot.
Refer to pages 50-53 for your circuit board conguration. Set ohmmeter to 100-200 kΩ range, then measure resistance across sensor wires (refer to page 56). If resistance tests OK (± 200Ω), check wiring
harness connections. If wiring harness connections test OK, replace circuit board. If sensor resistance is incorrect, replace hi-limit sensor.
4. Set ohmmeter to 100-200 kΩ range, then measure resistance across temperature sensor wires (refer to
page 56). If resistance tests OK (± 200Ω), replace circuit board. If temperature sensor resistance is
incorrect, replace sensor.
20
Page 25
“- - -” Watchdog (All Models)
Water temperature has reached 118°F (48°C). DO NOT ENTER HOT TUB WATER! The entire system is disabled. Refer to test steps 1-4 below:
1. Check hi-limit and temperature sensor resistance values. Both sensors should measure
close in resistance to each other (e.g. one may be defective and way out of range). Refer to appendix page 56 for expected hi-limit/temperature sensor resistance/water tempera­ture values. If either sensor is faulty, replace it and recheck system. If problem persists, proceed to steps 2.
2. Plug in new control panel. If problem persists, proceed to step 3. If problem corrects, replace panel.
3. Check voltage at transformer secondary. Refer to Section A29, page 58 for transformer testing instruc-
tions. If voltage is bad, replace transformer. If voltage is good, perform step 4.
4. Check circuit board transformer connections. If connections are loose or oxidized, repair connections and
retest system. If problem persists, replace circuit board.

7.4 Testing Flow/Pressure Switch

Testing The Flow Switch
•All J-LX Models
•All 2011-2013 J300 Models
•All J200 Models (with the Circulation Pump Option)
A. Verify ow switch directional arrow is pointing in the direction of ow away
from the heater output. If switch orientation is incorrect, loosen or tighten
switch no more than 1/2 turn, being careful not to bottom out switch in tting. The switch’s ow arrow must be parallel to tee tting as shown (Fig. 1). Test
system operation. If condition corrects, skip steps B-C.
B. Remove switch from tting making note of the number of turns (revolutions)
it takes to do so. Visually inspect switch for debris interference or damage. If debris is present, remove debris, then install switch with the same number of turns as originally installed. Test system. If switch is damaged, replace switch and retest system. If condition corrects, skip step C.
C. Test switch operation with an ohmmeter (set to 1000-
2000 Ω range) for continuity across switch terminals. Measure resistance
across switch terminals for innite resistance with the magnet arm not touching the switch body (Fig. 2), and for continuity (0 Ω) with the magnet arm touching the switch body (Fig. 2). If ow switch tests OK, check switch
wiring harness. If wiring harness tests OK, replace circuit board.
D. Verify that low ow is not preventing the ow switch from closing.
Testing The Pressure Switch
•All J200 Models (without the Circulation Pump)
FLOW
Incorrect
Orientation
Open
Infinite
Pump off
Infinite
Arrows
not
aligned
DCV ACV
200
20
2000m
200m
2000k
200k
20k
DCV ACV
2000m
200m
2000k
1000
2000
200
1000
200
20
200k
20k
2000
OFF
750
200
DCA
200µ
2000µ
20m
200m
10A
+
OFF
750
200
200
+
Fig. 1
Correct
Orientation
Fig. 2
Fig. 3
DCA
200µ
2000µ
20m
200m
10A
Arrows aligned
FLOW
Continuity 0
Pump on
Continuity 0
DCV ACV
2000m
200m
2000k
Closed
DCV ACV
1000
200
20
2000m
200m
2000k
200k
20k
2000
correct
incorrect
Pipe
End View
OFF
750
1000
200
DCA
200
200µ
20
2000µ
20m
200m
10A
200k
20k
2000
200
+
OFF
750
200
DCA
200µ
2000µ
20m
200m
10A
200
+
DCV ACV
OFF
750
1000
200
20
2000m
200m
2000k
200k
20k
2000
200
+
200
DCA
200µ
2000µ
20m
200m
10A
A. Remove switch. Visually inspect switch for debris blockage. If debris is present, remove debris, install
switch and test system. If condition corrects, skip step B.
B. Disconnect wires from switch terminals. Set ohmmeter to 1000-2000 Ω range. Measure resistance across
switch terminals for innite resistance with pump off (Fig. 3). If continuity (0 Ω) is measured with pump off, the switch is defective, replace switch. If switch measures innite Ω (no continuity) with pump off, switch is OK. Turn on main pump and measure across switch terminals for continuity (0 Ω). If continuity (0 Ω) is
measured, switch is OK. Check wiring harness. If wiring harness tests OK, replace circuit board.
If the switch tests ok in the steps above, check the wiring harness connections between switch and circuit board. Scrape the switch’s contact pin surfaces to remove any oxidation or conformal coating.
21
Page 26

8.0 Troubleshooting without The Control Panel

• Diagnostic Tools for Sections 8.1A-8.1E: Clamp-on ammeter, voltmeter, and ohmmeter
• Suggested Spare Parts for Sections 8.1A-8.1E: Circuit board, control panel, temperature sensor, pres-
sure switch, ow switch, heater assembly.

8.1A No Heat or Not Enough Heat (All Models)

• Symptoms: Low speed pump or circulation pump is moving water, panel heat indicator is lit, water is not
getting hot.
• Conguration: 1-pump system heaters will not operate with the jets pump running in high speed unless the
circuit board is congured for 40A operation. 2-pump system heaters will not operate with both jets pumps running in high speed, unless congured for 60A operation, or with either pump in high speed if circuit board is congured for 30A operation. Refer to Sections 6.1-6.5, pages 16-18.
Note: Jets pump 2 only runs in high speed. This applies to 2011-2013 J300 Models not 2014+
Turn up temperature setpoint to initiate a heat call (verify “Standard Mode” F0-F3 is selected (see page 7). Is voltage present at the heater output? Test points 12 and 13. See pages 50-53.
Yes
Is voltage present at heater element? Test points 25 and
26. See pages 50-53.
Yes
Is there current draw? Refer to Section A2 (page 45) for expected heater current consumption values.
Check heater element with clamp-on ammeter around one of the heater element wires.
No
No
No
Is voltage present at heater input? Test points 10 and 11. See pages 50-53.
Yes
Replace circuit board.
Locate thermal switch inside, the J-LX/J300 heater box, or J200 load box. Set voltage meter to 500-1000 VAC range. Test thermal switch by connecting voltage meter across the terminals with a heat call present (Fig. 4). If 120 VAC* or 240 VAC exists, the switch is open. If no voltage exists, the switch is closed. Is the switch open?
*Convertible J-315/J-325, and J-210 models only.
Replace or reconnect wires
No
between heater input relay and TB1 (main power terminal block).
Replace or reconnect wires
No
between heater output and heater element.
Replace Thermal Switch and retest spa.
Thermal Switch
Bad
Fig. 4
Thermal Switch
Good
Is the heater’s current draw within ±10% of the listed value?
Yes
Current draw is proof that heater element is working. Make sure customer knows how to use control panel and heater. Ask about any possible error messages.
DANGER: Electrical Shock Hazard Exists!
High Voltage Present on Circuit Board. Use Extreme Caution while Servicing Circuit Board.
22
Yes
Place thermometer against heater housing and verify temperature. Is temperature above 130ºF?
Yes
**Call Technical Support
Replace heater.
VAC
VAC
No
Optional Test Method: you can also remove one wire from either side of switch and test across its terminals for continuity. Infinite =bad switch; 0 =good switch
**WARNING: heater temperature may have ex­ceeded 130°F (54°C). Inspect heater. Call technical support if visible damage is apparent.
Page 27

8.1B No Heat or Not Enough Heat (All Models)

• Symptoms: low speed pump or circulation pump (heating pump) not turning, panel heat
indicator not lit, panel is ashing FL2.
Standard Troubleshooting Approach
This applies to 2011-2013 J300 Models not 2014+
Turn power off. Disconnect
ow or pressure switch wire
from board (Fig. 5). Turn power on. Does the FL2 er­ror message go away?
Yes
1. All Models: Remove wires at board.
2. Test ow or pressure
switch with ohmmeter for continuity across switch wires (Fig. 6-7). Does meter read continuity (0 ohms)?
Yes
Remove ow or pressure
switch and inspect for debris interference. Remove debris if present. Test switch for
continuity (0Ω) when closed and for innite Ω when open
(Fig. 6-7). Does switch oper­ate correctly?
No No
Is wire shorted?
Yes
Replace wire.
No
Make sure wire is not shorted when installed on switch. For models where the wire is removable.
No
Replace ow or
pressure switch.
Replace circuit board.
DCV ACV
1000
200
20
2000m
200m
2000k
200k
20k
2000
Infinite
Open
Infinite
DCV ACV
1000
200
20
2000m
200m
2000k
200k
20k
2000
Pump off
Fig. 5
Flow Cable
Fig. 6
DCV ACV
OFF
OFF
750
200
DCA
200µ
2000µ
20m
200m
10A
200
+
Pump on
750
1000
200
DCA
200
200µ
20
2000µ
2000m
20m
200m
200m
2000k
10A
200k
20k
2000
200
+
Continuity 0
Fig. 7
DCV ACV
OFF
750
1000
OFF
750
200
DCA
200µ
2000µ
20m
200m
10A
200
+
200
DCA
200
200µ
20
2000µ
2000m
20m
200m
200m
2000k
10A
200k
20k
2000
200
+
Closed
Continuity 0
Yes
J-LX/J300/J200 Models with circulation pump:
Install switch making sure
ow arrow points in direction of ow and switch doesn’t bottom out in tting (Fig. 8).
Retest system.
Yes
J200 Models (without the circulation pump):
Replace pressure switch. Retest system.
aligned
FLOW
Incorrect
Orientation
Arrows
not
Fig. 8
FLOW
Correct
Orientation
Arrows aligned
Correct
Orientation
DCV ACV
OFF
1000
200
20
2000m
200m
2000k
200k
20k
2000
200
+
correct
incorrect
End View
750
200
Pipe
DCA
200µ
2000µ
20m
200m
10A
23
Page 28

8.1C No Heat or Not Enough Heat (All Models)

• Symptoms: Low speed pump 1 or circulation pump (heating pump) not turning, panel heat
indicator not lit, panel is ashing FL1.
Standard Troubleshooting Approach
This applies to 2011-2013 J300 Models not 2014+
Is there correct voltage coming to the hot tub at TB1? Test point 1 and 2. See page 50-53
240 VAC, ± 10%, or (120 VAC, ± 10% for convertible models).
Yes
Put hot tub in standard ltration mode
(page 7). Set temperature high enough to initiate a heat call.
J-LX, J300, J200 (with Circ Pump): Is voltage from circuit board to circulation pump ok? Test point 14 and 15. (See page 50-53).
J200 (without Circ Pump): Is voltage from circuit board to low speed pump 1 ok? Test point 5 and 6. (See page 50-53)
No
No
Call an electrician.
Replace circuit board.
Note: Refer to voltage and current charts on appendix pages 43-45 for expected voltage/current readings.
Yes
Is connection ok from circuit board to pump?
Yes
Replace pump.
DANGER: Electrical Shock Hazard Exists!
High Voltage Present on Circuit Board. Use Extreme Caution while Servicing Circuit Board.
No
Repair connection.
24
Page 29

8.1D No Heat or Not Enough Heat (All Models)

• Symptoms: Low speed pump 1 or circulation pump (heating pump) is turning, panel heat
indicator not lit, panel is ashing FL1.
Standard Troubleshooting Approach
Is the low speed pump or circulation pump (Heat Pump) moving water?
Yes
Verify hot tub is in
standard ltration mode
(page 7) then perform step below.
Remove switch wires from board. Increase set temperature to initiate a
heat call, then jumper ow
switch wires together (Fig. 9-10). Does heat indicator appear and FL1 error message disappear?
Yes
Test ow or pressure
switch with ohmmeter for
continuity (0Ω) across
switch terminals (Fig. 11) Does meter read continuity
(0Ω) with pump on?
Yes
Clean connectors between
ow cable and switch.
No
1. Remove lter and
allow air to bleed out of cartridge.
2. Check for proper water level.
3. Check for clogged/ excessively dirty
lter.
4. Check for blockage
at lter wall tting.
5. Check for sticking weir.
6. Is pump moving water?
Remove ow or pressure
switch connector from circuit board test point 23 (Fig. 10). Place
No
jumper across exposed connector pins*. Does heat indicator appear and FL1 error message disappear?
Repair or replace ow or
pressure sensor cable.
Remove ow or pressure
No
switch and inspect for debris blockage. Remove blockage or replace switch.
Re-install ow or
pressure switch. Install
ow switch with arrow
pointing in direction of
ow. Make sure magnet
arm doesn’t bottom out
in tting (Fig. 12).
Yes
Yes
No
Models with a circulation pump: See Section 8.12 (pg.
40)
Models without a circulation pump: See Section 8.7 (pg. 35)
Replace circuit board.
No
*Lightly scrape contact pins at point 23 with a razor blade or sandpaper to re­move conformal coating or oxida­tion form contact surface.
Jumper
Temporarily Short Pins with Jumper #6560-864
Open
Pump off
Infinite Ω
FLOW
Incorrect
Orientation
Fig. 9
Temporarily Jumper
Flow or Pressure Switch Cable Wires Together as Shown.
Fig. 10
Fig. 11
DCV ACV
OFF
750
1000
200
DCA
200
200µ
20
2000µ
2000m
20m
200m
200m
2000k
10A
200k
20k
2000
200
+
Fig. 12
Arrows
not
aligned
Correct
Orientation
22
23
Closed
Pump on
Continuity 0 Ω
DCV ACV
OFF
750
1000
200
200
20
2000m
200m
2000k
200k
20k
2000
200
+
Arrows
aligned
FLOW
Jumper
Flow Cable
DCV ACV
OFF
1000
200
20
2000m
200m
2000k
200k
20k
2000
200
+
DCA
200µ
2000µ
20m
200m
10A
correct
incorrect
Pipe
End View
750
200
DCA
200µ
2000µ
20m
200m
10A
DANGER: Electrical Shock Hazard Exists!
High Voltage Present on Circuit Board. Use Extreme Caution while Servicing Circuit Board.
Correct
Orientation
25
Page 30

8.1E No Heat or Not Enough Heat (All Models)

• Symptoms: Low Speed Pump or circulation pump (heating pump) is turning, panel heat
indicator not lit, panel is NOT ashing FL1.
Standard Troubleshooting Approach
Put hot tub in standard
ltration mode (pg. 7).
Set temperature high enough to initiated a heat call. Remove power to hot tub then plug in a spare control panel. Turn power on. Does indicator work now?
Yes
Replace control panel.
No
Jump out ow switch pins at
board. Does heat indicator come on?
Yes
Verify that ow switch
padde is not bouncing and address possible restriction problems.
No
Replace circuit board.
26
Page 31

8.2 Intermittent Heating

As with all intermittent problems, routine measurements and display panel error messages are not trustworthy. The following procedure will eliminate the most probable causes.
It is important to explain to the customer how difcult intermittent problems are to locate. You will be doing a se­ries of things to eliminate the problem. Ask the customer to be patient and please cooperate by calling you back to inform you of the hot tubs status until the problem is corrected. It might be a good idea to review this S.T.A. with the customer. It may help he or she understand why it might take several service calls to effect a repair.
Suspects: circuit board, temperature sensor, control panel, wiring connections, and partial water ow obstruc­tions.
Diagnostic Tools
Voltmeter, Ohmmeter
Suggested Spare Parts
Heater element, circuit board, temperature sensors, pressure switch, control panel
Standard Troubleshooting Approach
1. Check crimped wire connections to heater element. If burned, replace heater element wires. Verify heater element connections are good on circuit board. Check heater resistance, see current chart on page 45 for expected heater resistance values.
2. Check connections labeled “heater out” on circuit board (test points 12 and 13). Refer to pages 50-53 for your circuit board. If possible, clean and renew connections. If relay is physically burned at connections, replace circuit board.
3. Check ow switch or pressure switch for proper and consistent mechanical operation. Observe mechanical
action of switch. Refer to page 21 for ow switch testing procedure.
4. Clean connections where panel plugs into board.
5. If all above items check out, ask the customer if the SN2 error has ever displayed. If the SN2 error mes­sage has displayed, replace temperature sensor.
6. Tell the customer what you have done, that you are not sure the problem has been xed, and that you want
to be called immediately if the problem returns. Explain what you will do if the problem returns. Check back with the customer in a few days if you haven’t been contacted.
7. If the customer calls back, call Technical Support.
Note: J-LX/2011-2013 J300/J200 (with circ pump) Models use a “magnetic reed switch”
type ow switch that can remain closed from debris interference. Removal of the ow
switch for cleaning and inspection will correct most problems. Record the number of turns
it takes to remove the switch from the tting. After cleaning, use the same number of
turns to reinstall the switch. DO NOT thread the switch farther than originally installed, or
the paddle may stick on the bottom of the tting. Also, make sure ow arrow is pointing in direction of ow away from heater output.
correct
incorrect

8.3 Nothing Works

Things to remember: when a system fails, there is probably one, and only one problem. Verify power to the hot tub by observing the control panels LED display. The control panel will usually display something as long as there is power to the hot tub. Check for error messages. Displayed error messages usually indicate the problem.
Diagnostic Tools: Voltmeter
Suggested Spare Parts: Fuses, control panel, circuit board Nothing Works (Panel Indicators lit)
1. Plug in spare control panel. If it works, change panel.
2. Remove power from hot tub. Check connections on sensor harness and verify proper resistance of temper­ature and hi-limit sensors (page 57). Replace defective temperature or hi-limit sensor then test system.
3. Check transformer. See Section A24, page 58.
4 . Still no operation? Replace circuit board.
27
Page 32
Nothing Works (Panel Dead)
1. All Models - Check for proper power to the hot tub on the main TB1 terminal block (page 43) as follows:
120V Convertible North American Models: 120 VAC ±10% (3-wire).
240V North American Models: 240 VAC ± 10%.
2. Check for power at transformer secondary. Refer to appendix page 58. If power exists on transformer secondary, plug in spare control panel. Still nothing? Replace board.
3. If no power exists at transformer secondary, check for voltage at transformer primary. Refer to appendix page 58. If voltage exists on the primary but is missing on the secondary, replace transformer.
4. No power at the transformer primary indicates either an open 1.25 Amp fuse, 20/30 Amp main fuse, or a loose or disconnected wire. If voltage exists on the primary but is missing on the secondary, replace trans-
former. See Section A5 (page 48) for specic fuse details.

8.4 Hot Tub Doesn’t Come On for Filter Cycle

Turn power to hot tub off and on to restart lter cycle program. Does lter cycle start approximately two minutes
after power is applied?
If yes: the hot tub is functioning properly. Refer to Sections 4.3-4.7 (page 7) for lter cycle setup details. Take time to explain lter cycle selection and operation to your customer. Make sure your customer under­stands lter cycles are selectable, not programmable.
If no: Select appropriate lter cycle mode within two minutes after applying power. Refer to Sections 4.3-
4.7 (page 7). If lter cycle starts approximately two minutes after setting, no corrective action is re­quired. If lter cycle does not start two minutes after setting, replace circuit board.

8.5 House Breaker Trips

The hot tubs current draw will vary depending on how the circuit board is jumpered. Jumper options determine whether multiple functions can operate together.
If the house breaker trips, check the hot tubs current draw. If jumpers are properly set and current draw is within expected limits, the house breaker or wiring is defective and must be repaired/replaced. The hot tubs current draw at the breaker represents the sum of all enabled devices. Refer to appendix page 46.
If the hot tub’s current draw is high, individual device current measurements must be made to determine which device is pulling excessive current. Refer to appendix page 46. Repair or replace the device which is draw­ing excessive current.
If the GFCI trips, try removing the heater, pump, ozonator (if installed), stereo power supply and circulation
pump or pump 2 wires from the circuit board one at a time to nd which device may be causing the GFCI to
trip. For chronic GFCI tripping, call Technical Support.
North American 60Hz Installations: As of January 1, 1994 the National Electric Code (NEC) requires a Ground Fault Circuit In­terrupter on all hot tub installations in the U.S. A GFCI must be wired correctly or it will trip. Make sure the electrician has wired the GFCI according to the diagram on pages 54.
28
Page 33

8.6A DCU Unit (J-LX Collection)

2013+ DCU Diagram
8 7 6 5 423
1
To location A on the DCU Unit
To location J1 on the Board
DCU wires splice into the yellow transformer wires.
2011-2012 DCU Diagram
J20
K1
J21
J11
K2
J12
J13
K3
J14
K4
J15
J16
J17
J18
J19
K5
K6 K7 K8
3.58
J4
F1
J1
JP1
8 7 6 5 423
1
J2
J3
TRANSFORMER
T1
Mini-Din Cable provides constant 12 VAC from yellow transformer wires
Light DCU
EXP BAR EXP BAR
POWER
Red Wire 12vAC Constant Voltage
To location J1 on the Board
To location A on the DCU Unit
J20
K1
J21
J11
K2
J12
J13
K3
J14
K4
J15
J16
J17
J18
J19
K5
K6 K7 K8
3.58
J4
J1
JP1
8 7 6 5 423
1
J2
J3
Waterfall lights connection
TRANSFORMER
T1
DCU Unit
A
Control Panel
A
connection
Blue Wire 12vAC Constant Voltage
F1
RED
J6
BLK J5
J9
J8
J10J7
29
Page 34

8.6B DCU Unit (J300 Collection)

2013 DCU Diagram
8 7 6 5 423
1
To location A on the DCU Unit
To location J1 on the Board
DCU wires splice into the yellow transformer wires.
2011-2012 DCU Diagram
J20
K1
J21
J11
K2
J12
J13
K3
J14
K4
J15
J16
J17
J18
J19
K5
K6 K7 K8
3.57
J4
J1
JP1
8 7 6 5 423
1
J2
J3
TRANSFORMER
T1
Mini-Din Cable provides constant 12 VAC from yellow transformer wires
Light DCU
EXP BAR EXP BAR
POWER
Red Wire 12vAC Constant Voltage
F1
RED
J6
BLK J5
J9
J8
J10J7
30
To location J1 on the Board
To location A on the DCU Unit
DCU Unit
J20
K1
J21
J11
K2
J12
J13
K3
J14
K4
J15
J16
J17
K5
3.57
J1
JP1
8 7 6 5 423
1
J2
J3
TRANSFORMER
T1
A
Control Panel
A
connection
J4
J18
J19
K6 K7 K8
Blue Wire 12vAC Constant Voltage
F1
RED
J6
BLK J5
J9
J8
J10J7
Page 35

8.6C Hot Tub Light Will Not Come On (J-LX/2011-2013 J300 Models)

Diagnostic Tools: Voltmeter
Suggested Spare Parts: Circuit board, DCU, Lights
Standard Troubleshooting Approach (Light has a two hour time out)
Do any of the lights work?
Yes
Is connection be­tween DCU and light ok?
Yes
If one light works and the other does not, try switching their connections on the DCU unit. Does the light work?
Yes
No
Plug in spare con­trol panel. Does the light work now?
Replace control panel.
No
Correct connec­tion.
No
Replace light. Plug known work­ing light into each DCU port to verify DCU ports are unaffected.
Yes
No
Is there correct voltage at the transformer yel­low wires? Refer Section A24 page 58 for voltage readings.
Is connection between the transformer and DCU ok?
Replace DCU
Yes
Yes
No
Replace trans­former
No
Correct connec­tion
Replace DCU if light won’t turn on or functions incor­rectly. See notes below*.
*Note: Before replacing DCU, perform the tasks described below in order to prevent shorting out the new DCU.
Step 1: Unplug all lights except footwell light.
Step 2: Verify footwell light works an goes through all color functions correctly.
Step 3: Plug in one light next to footwell light connection. Verify that all color functions work correctly and light does not
icker or have missing color LED’s. Unplug light and plug in another light in the same place and perform the same
test as with the previous light. Continue to follow this procedure until all lights have been tested.
Step 4: Now replace DCU and any lights that were determined to perform incorrectly.
31
Page 36

8.6D Light does not come on (J200 Collection Standard light)

A. 2011+ J210 Models B. 2011-2012 J-230, J-270 and J-280 Diagnostic Tools: Voltmeter
Suggested Spare Parts: Circuit board, Transformer, Lights
Standard Troubleshooting Approach (Light has a one hour time out)
Refer to pages 50-53 for testing points.
J210 Models
To location J1 on the Board
2011-2012: J230, J270 2011+ J280 Models
Plug in spare con­trol panel. Does the light work now?
Yes
Replace control panel.
J20
K1
J21
J11
K2
J12
J13
K3
J14
K4
J15
J16
K5
J17
J18
K6 K7 K8
J19
RED
No No
Check for voltage
BLK
J6
J5
at points 18 and
19. Is voltage pres­ent?
Yes
Replace light.
J1
JP1
8 7 6 5 423
J2
J3
J4
F1
J9
J8
J10J7
Is there correct voltage at the transformer? Refer Section A24 page 58 for voltage readings.
Yes
Replace circuit board.
1
TRANSFORMER
T1
No
Replace transformer.
32
Page 37

8.6E 2013+ Light diagram of the DCU Unit (J200 Collection)

(actual number of lights may vary by model)
3
16587
To location J1
on the Board
JP1
4
2
J2
J1
J3
T1
TRANSFORMER
J4
K1
K2
K3
K4
K5
J21
J20
J11
J12
J13
J14
J15
J16
J17
J10J7
J9
J8
F1
BLK
J5
K6 K7 K8
J6
RED
J18
J19
To Sloan
waterfall
connection
To waterfall
connection
To Sloan DCU
connector
To connector
on the board
33
Page 38

8.6F Hot Tub Light Will Not Come On (J200 Collection CL Lighting)

Diagnostic Tools: Voltmeter
Suggested Spare Parts: Circuit board, DCU, Lights
Standard Troubleshooting Approach (Light has a two hour time out)
All the LEDs are controlled by a central control box (protected by a inline fuse), the topside control panel func­tions and color cycles. The LED cables are daisy chained together with locking Molex connectors, they are run clockwise, starting at the front right corner of the spa.
One or two LEDs are out.
Many LEDs are off.
LEDs are out of sync.
Remove cabinet where problem LEDs are located.
Remove cabinet
where the rst
LED daisy chain is located. LEDs run clockwise, start point is at the front right corner of the spa.
Remove cabinet
where the rst
LED daisy chain is located. LEDs run clockwise, start point is at the front right corner of the spa.
Check the daisy chain connection for the light harness.
Check the daisy chain connection for the light harness.
Check the daisy chain connection for the light harness.
Replace bad LEDs with a new daisy chain cable.
Replace with a new daisy chain cable. Continue to the next daisy chain cable.
Replace with a new daisy chain cable. Continue to the next daisy chain cable.
None of the LEDs turn on.
All LEDs turn on but one color doesn’t light.
34
Check voltage across points 18 and 19.
Disconnect the cables one at a time starting at the open end of the daisy chain.
Check light controller fuse. Located on the red power wire of the controller.
Check LEDs after disconnecting each cable.
Plug new daisy chain into light controller to determine if it is the controller or an LED cable issue.
If LEDs start to work properly, then the last cable removed needs to be replaced.
Page 39

8.7 No Jets

This is a condition of constant zero water pressure. The rst step in diagnosing the problem is to
determine if the pump is actually turning. Once this determination is made, follow the appropriate portion of the S.T.A.
Diagnostic Tools: Voltmeter
Suggested Spare Parts: Control Panel, Circuit Board, Jets Pump 1
Pump Is Turning (Checking for A Flow Problem)
1. Make sure jets are open. (Jets can be individually turned off, in some cases.)
2. Is the lter clogged?
3. Is there an obstruction in the plumbing line?
4. Check for air lock (clear air lock by opening union on pump discharge).
Standard Troubleshooting Approach
Refer to pages 50-53 for testing points.
No
Press JETS Button to turn on jets pump.
Do you hear a relay click on the circuit board?
Plug in spare control panel then press JETS Button.
Do you hear a relay click on the circuit board?
Yes
Is voltage from circuit board to main pump test point correct?
Check for 240 VAC (120 VAC for convertible J-210, J-315, J-325 models) at recommended test points. See table at right for a listing of recommended test points.
No
Replace circuit board.
Yes
This applies to 2011-2013 J300 Models not 2014+
No
Replace circuit board.
Yes
Replace control panel.
Recommended Test Points
All 1-Pump (2-speed) models
• Low Speed Pump 1 - test point 5 and 6.
• High Speed Pump 1 - test point 5 and 7.
All two pump models
• Low Speed Pump 1 - test point 5 and 6.
• High Speed Pump 1 - test point 5 and 7.
• High Speed Pump 2 - test point 8 and 9.
Is connection between circuit board and pump OK?
Yes
Replace pump.
DANGER: Electrical Shock Hazard Exists!
High Voltage Present on Circuit Board. Use Extreme Caution while Servicing Circuit Board.
No
Repair wiring.
35
Page 40

8.8 2011 Ozonator Not Working

Diagnostic Tools: Clamp-on Ammeter, Voltmeter
Suggested Spare Parts: Ozonator, Circuit Board, Control Panel
Standard Troubleshooting Approach
Refer to pages 50-53 for testing points.
Turn power to hot tub off and on. Wait approximately two minutes
for lter cycle to begin and turn
on the circulation pump and ozonator (J-LX, J300 and J200 with circ pump Models) or Pump 1 and ozonator (J200 without a circulation pump.
DO NOT press either JETS button at this time or ozonator
will shut off! Is lter cycle 1
running?
No
This applies to 2011-2013 J300 Models not 2014+
Turn power off, plug in spare control panel, then turn power on. Wait approximately 2 minutes
for lter cycle to begin. Is lter cycle running?
Yes
Replace control panel.
Yes
No
Replace circuit board
O
3
Is 120 VAC* or 240 VAC present at circuit board ozone outputs? Test points 16 and 17, See pages 50-53.
*Convertible J-210, J-315, J-325 models only.
Yes
Is there a faint buzzing sound coming from the ozonator’s internal high voltage arching chamber? Or is there current
draw from the ozonator (≈ 0.1
Amp)? Check with clamp-on ammeter.
Yes
A faint buzzing sound and/or current draw is proof that the ozonator is working.
No
Replace circuit board.
No
Replace ozonator.
Read steps outlined above to ensure customer understands ozone logic.
36
DANGER: Electrical Shock Hazard Exists!
High Voltage Present on Circuit Board. Use Extreme Caution while Servicing Circuit Board.
Page 41

8.9 2012+ CLEARRAY Not Working

Verify that the CLEARRAY system should be running before proceeding (no error message, not in summer logic. CLEARRAY turns off when either jets button is pressed and will remain off for 5 minutes after function ends.
Diagnostic Tools: Clamp-on Ammeter, Voltmeter
Suggested Spare Parts: CLEARRAY ballast, UV bulb, circuit board, control panel
Standard Troubleshooting Approach. Refer to pages 50-53 for testing points.
This applies to 2011-2013 J300 Models not 2014+
Turn power to hot tub off and on. Wait approximately two minutes for
lter cycle to begin and turn on the
circulation pump and CLEARRAY (J-LX, J300 and J200 with circ pump Models) or Pump 1 and CLEARRAY (J200 Models).
DO NOT press either JETS button at this time or the CLEARRAY will shut off!
Is lter cycle 1 running?
Yes
Is 120 VAC* or 240 VAC present at circuit board CLEARRAY outputs?
Test points 16 and 17, See pages 50-53.
*Convertible J-210, J-315, J-325 models only.
Yes
No
Turn power off, plug in spare control panel, then turn power on. Wait approximately 2
minutes for lter cycle to begin. Is lter cycle running?
Replace control panel.
No
Replace circuit board.
Yes
No
Replace circuit board.
Is there current draw (0.4 Amp) on the CLEARRAY? Check with clamp-on ampmeter.
Yes
Current draw is proof that CLEARRAY is working. Read steps outlined above to ensure customer understands the logic.
1 2
0
­230
V
UV bulb
Ballast
No
Is the green light lit on the ballast?
Yes
Is the red light lit on the ballast?
Yes
Turn power off, plug in spare panel, then turn power on. Is CLEARRAY indicator lit?
Yes
Replace control panel.
DANGER: Electrical Shock Hazard Exists!
High Voltage Present on Circuit Board. Use Extreme Caution while Servicing Circuit Board.
No
Replace ballast.
No
Replace UV bulb.
No
Replace circuit board.
37
Page 42

8.10 Weak or Surging Jets

Weak or surging jets are usually caused by an insufcient water supply to the pump or a
clogged or broken pump impeller. The water level may simply be low, or there may be an ob-
struction in the water ow path to the pump or in the pump’s impeller. Before making a service call, ask customer to verify all jets are open.
Suggested Spare Parts: Filter cartridge, Pump
Standard Troubleshooting Approach
Is the water level OK?
Yes
Is the lter cartridge
clogged or dirty?
Yes
Clean or replace lter
cartridge.
No
No
Adjust the water level and retest.
Is the lter cartridge
installed correctly? Is the weir gate or skimmer operating correctly?
Yes
Take pump housing apart. Is debris present in pump impeller? Is the impeller broken?
Yes Yes
No
Fix lter installation
problem.
No No
Is there debris or a loose foreign object
between the lter and
pump input?
If pump suction line is clear, check for blockage in plumbing on the return side of pump. Call Technical Support for assistance in performing this
verication step.
38
Remove debris or replace broken impeller and retest system.
Remove debris or loose foreign object.
Page 43

8.11 Jets Pump Runs and Quits During Jet Mode

This is usually a problem of pump overheating. The pump motor incorporates a thermal cutout switch that triggers when the motor gets too hot. There is no reset for this condition. When the motor cools, the thermal switch resets automatically. In some cases, a faulty circuit can also cause this problem.
Diagnostic Tools: Clamp-on Ammeter, Voltmeter
Suggested Spare Parts: Circuit Board, Jets Pump
Standard Troubleshooting Approach
Refer to pages 50-53 for testing points.
Press JETS button. Does motor make a “laboring” sound?
Yes
Is there sufcient
voltage connected to hot tub. Check for 240 VAC ±10% (or 120 VAC ±10% for convertible J-210, J-315, J-325 models) at TB1 test points 1 and 2.
No
No
Is voltage from circuit board to pump correct after pump quits? Check for 240 VAC (120 VAC for convertible J-210, J-315, J-325 models) at recommended test points. See table at right for a listing of recommended test points.
Pump has thermally shut down. See page 41.
Call an electrician to
x problem.
This applies to 2011-2013 J300 Models not 2014+
No
Replace circuit board
Yes
Recommended Test Points
All 1-Pump (2-speed) models
• Low Speed Pump 1 - test point 5 and 6.
• High Speed Pump 1 - test point 5 and 7.
Yes
Check voltage with pump running. Is the voltage 240 VAC ±10% (or 120 VAC ±10% for convertible models) at test points 1 and 2.
Yes
Replace pump
No
This is caused by
insufcient wiring
or the pump motor drawing too much current. Contact Technical Support.
All two pump models
• Low Speed Pump 1 - test point 5 and 6.
• High Speed Pump 1 - test point 5 and 7.
• High Speed Pump 2 - test point 8 and 9.
DANGER: Electrical Shock Hazard Exists!
High Voltage Present on Circuit Board. Use Extreme Caution while Servicing Circuit Board.
39
Page 44

8.12 Circulation Pump Not Working (JLX, J300 and J200 with circ pump option only)

The circulation pump works as follows:
2011+ JLX Models circ pump runs 8 hrs (default)
2012-2013 J335/J345/J355/J365/J375 8 hrs (default)
2011 J335/J345/J355/J365/J375 8 hrs (default)
2011-2013 J315/J325 24 hrs (default)
2011-2012 J280/J270/J230 circ pump was an option, 24 hrs (default)
The circulation pump should be running unless “summer logic” is activated. Verify “summer logic” is not acti­vated before starting. Refer to Section 5.4 (page 14) for details.
The circulation pump is preset to run for a specic lter cycle, two minutes after power up. If the circulation
pump is not running, turn power off to the spa then back on and wait two minutes for the cycle to begin. Or raise the temperature to initiate a heat call.
Diagnostic Tools: Clamp-on Ammeter, Voltmeter
Suggested Spare Parts: Circuit Board, Circulation Pump
Standard Troubleshooting Approach
Refer to pages 50-53 for testing points.
No
Is 240 VAC (120 VAC for J-210, J-315, J-325) present at pump output? Test Points 14 and 15.
Make sure circulation pump should be on. If pump should be on and there is no voltage at test points change circuit board.
Yes
Check connection
Is there current draw (0.5 Amp)? Check with clamp­on ammeter.
No
between circuit board and circulation pump. If connection is OK, replace pump.
Yes
This applies to 2011-2013 J300 Models not 2014+
Current draw is proof that circulation pump is working. Read steps above to make sure circulation pump should be on*.
*Note: If circulation pump is running but there is no ow, check for an excessively dirty lter, an air lock, block- age in the plumbing, debris in the pump, or a broken pump impeller.
DANGER: Electrical Shock Hazard Exists!
High Voltage Present on Circuit Board. Use Extreme Caution while Servicing Circuit Board.
40
Page 45

8.13 Troubleshooting A Thermal Pump Cutout

mmm...
1. Verify voltage to hot tub is 240 VAC ±10% (or 120 VAC ±10% for convertible models). An
insufcient voltage supply can cause the motor to pull too much current and overheat. The
situation must be corrected.
2. Check voltage to hot tub.
3. If voltage is OK, examine the environment in which the hot tub is installed. Hot sun, hot weather, and lack of breeze can cause heat build up in the equipment bay in addition to the normal heat produced by the pump. This can raise the temperature high enough to cause the pumps thermal cutout to trip. There are two possible solutions to thermal pump cutout problems which are not due to low line voltage. One is to change the lter cycle period so that it does not coincide with the hottest time of day and peak power con­sumption hours. Another is to ventilate the equipment bay. Call technical support for advice on this matter.
4. If there seems to be no overheating problem yet the motor keeps cutting out, the motor’s thermal switch may be bad. In this case the pump should be replaced.

8.14 Pump 1 Hums and Will Not Start

If the pump impeller is not “frozen”, this condition usually indicates a bad start capacitor. This component is inside the pump motor housing.
Diagnostic Tools: Voltmeter
Suggested Spare Parts: Pump, Capacitor, Circuit Board
Standard Troubleshooting Approach
Press JETS 1 button. Check voltage at the following circuit board test points 5 and 6.
North American 60 Hz Models:
All models (except J-315/J-325/J-210): 240 VAC ±10% J-315/J-325/J-210: 120 VAC ±10%
Export 50 Hz Models:
All models; 230 VAC ±10%
All Models
If there is no voltage present at the recommended test points, replace circuit board. If voltage is present, the pump needs to be repaired or replaced. Try replacing the pump’s start capacitor. If the pump still doesn’t work, replace pump.
If pump 1 runs in low speed but hums in high speed, make sure circuit board is not sending voltage to both pump windings at the same time. Disconnect pump wires from the circuit board before performing this test. Test for voltage at test points 5 and 6. When voltage exists at test points 5 and 6 there should be no volt­age at test points 5 and 7. Conversely, when voltage exists at test points 5 and 7, there should be no voltage at test points 5 and 6. If voltage is present across both sets of test points at the same time, replace circuit board.
Refer to pages 50-53 for your specic circuit board layout.
DANGER: Electrical Shock Hazard Exists!
High Voltage Present on Circuit Board. Use Extreme Caution while Servicing Circuit Board.
41
Page 46

APPENDIX

42
Page 47

A1 Checking Voltage to Hot Tub

Correct supply voltage wiring to the hot tub is essential for safe/proper operation. The rst step in troubleshoot­ing a new installation should be to take voltage readings at the terminal block TB1. Do not trust wire colors. Electricians make mistakes and electrons are color-blind. A low line voltage or incorrectly wired hot tub will result in either of the following symptoms: A) Strange or intermittent symptoms, B) Displays with indications that simply cannot be correct
Many of the most perplexing problems in the past have been wiring errors and voltage drop problems. Human
safety depends on proper hot tub grounding. It is essential that the voltage readings described below are as indicated. The ground connection must be heavy duty wiring.
J-210, 2011-2013 J-315, 2011-2013 J-325 North American 60 Hz are convertible for either 120 VAC 3-wire
operation or 240 VAC 4-wire operation. The 4-wire power conguration powers the heater with 240 VAC for
increased performance while powering all other components with 120 VAC.
All other models are North American 60 Hz are exclusively powered by 240 VAC.
All Models Export 50 Hz are exclusively powered by 230 VAC ±10%, see Figure C below.
Verify All Convertible Models Power Connections as Follows:
North American Models (120 VAC/60 Hz, Fig. A)
Hot to Neutral: Measure across test points 1 and 2 with voltmeter for 120 VAC.
Hot to Ground Test: Measure across test points 2 to 23 for 120 VAC.
North American Models (240 VAC/60 Hz, Fig. B)
Hot to Neutral: Measure across test points 1 and 2 with voltmeter for 120 VAC; then across test points 1
and 24 for 120 VAC.
Hot to Ground: Measure across test points 2 and 23 for 120 VAC; then across test points 24 and 23 for 120
VAC.
Hot to Hot: Measure across test points 2 and 24 for 240 VAC.
TB1 TB1
WHT
1
BLK
2
Power In
3
23
GRN
North American (60 Hz)
120 VAC 3-Wire
J-210, J-315, J-325
DANGER: Electrical Shock Hazard Exists!
High Voltage Present on Circuit Board. Use Extreme Caution while Servicing Circuit Board.
Fig. BFig. A
1
2
24
WHT
RED
BLK
BLK
to Circuit Board
WHT WHT
1
BLK
2
RED
Power In
3
23
GRN
North American (60 Hz)
240 VAC 4-Wire
J-210, J-315, J-325
1
2
24
BLK
BLK
RED
to Circuit Board
For Heater
Power In
230 VAC 3-Wire
J-210, J-315, J-325
1
2
GRN
Export (50 Hz)
Fig. C
TB2
TB1
23
1
2
BLUE
BLUE
BROWN
BROWN
to Circuit Board
43
Page 48
Verify All 240 VAC Models power connections are as follows:
GRN
1
2
Export (50 Hz) 230 VAC Models
Fig. E
TB1
BLK
RED
GRN
1
2
North American (60 Hz) 240 VAC 3-Wire
1- and 2-pump models.
Fig. D
TB1
1
2
23
BLUE
BLUE
BROWN
HOT
HOT
HOT
HOT
BROWN
to Circuit Board to Circuit Board
Power In
Power In
1
2
TB2
For Heater
North American 240 VAC/60 Hz, Fig. D:
Hot to Hot: Measure across test points 1 and 2 for 240 VAC.
Hot to Ground: Measure across test points 1 and 23 for 120 VAC; then across 2 and 23 for 120 VAC.
DANGER: Electrical Shock Hazard Exists!
High Voltage Present on Circuit Board. Use Extreme Caution while Servicing Circuit Board.
44
Page 49

A2 Checking Current Consumption of Devices

This table lists current draw for most major hot tub components:
2011-2013 J300 Collection
(North American 60 Hz)
Device
Pump 1 (2-speed) High/ Low 9.5A-12.0A/2.6A-3.6A
Pump 1 (2-speed) High/ Low (J-315/J-325 only) 10.6A-13.6A/2.6A-3.9A
Pump 2 (High speed only) 9.0A-11.0A
Heater 1 kW/4 kW (Con-
vertible Models Only)
Heater 5.5 kW 19.5A-23.5A (240 VAC)
Circulation Pump 0.5A-1.0A
CLEARRAY (Standard) 0.4A
Ozone Generator (Opt) 0.1A
Current
Consumption ±10%
7.0A-9.0A (120 VAC)
16.7A (240 VAC)
J-LX Collection
(North American 60 Hz)
Device
Pump 1 (2-speed) High/ Low 9.5A-12.0A/2.6A-3.6A
Pump 2 (High speed only) 9.0A-11.0A
Heater 5.5 kW 19.5A-23.5A (240 VAC)
Circulation Pump 0.5A-1.0A
CLEARRAY (Standard) 0.4A
Ozone Generator (Opt) 0.1A
Current
Consumption ±10%
J-200 Collection
(North American 60 Hz)
Device
Pump 1 (2-speed) High/ Low 9.5A-12.0A/2.6A-3.6A
Pump 1 (2-speed) High/ Low (J-210 only) 10.6A-13.6A/2.6A-3.9A
Pump 2 (High speed only) 9.0A-11.0A
Heater 1 kW/4 kW (Con-
vertible Models Only)
Heater 5.5 kW 19.5A-23.5A (240 VAC)
Circulation Pump (Optional for J-230, J-270 J-280) 0.5A-1.0A
CLEARRAY (Standard) 0.4A
Ozone Generator (Optional) 0.1A
Current
Consumption ±10%
7.0A-9.0A (120 VAC)
16.7A (240 VAC)
J-LX/2011-2013 J300/J200 Models
(Export 50 Hz)
Device
Pump 1 (2-speed) High/ Low 6.3A-8.7A/2.2A-2.8A
Pump 2 (High speed only ­for 2-pump models) 6.3A-8.7A
Heater 2.7 kW 9.5A-12.5A (230 VAC)
Circulation Pump 0.3A-0.7A
CLEARRAY (Standard) 0.4A
Ozone Generator (stan­dard) 0.1A
Current
Consumption ±10%
45
Page 50

A3 Checking Voltages to Devices

Device voltages are often measured at the circuit board to determine whether the board or device is bad. If the circuit board delivers voltage when device operation is called, the circuit board is probably good and the prob­lem lies with the device or the wiring to the device. The following voltage chart shows operating voltages for all major hot tub components. Voltage is considered good if within ±10% of the listed value. Refer to appendix
pages 50-53 for your specic circuit boards test point locations.
For all North American 60 Hz
J-LX/J-LXL
2011-2013 J-335/J-345/J-355/J-365/J-375 Models
Device Test Points Voltage ±10%
Pump 1 (Low Speed) 5 and 6 240 VAC
Pump 1 (High Speed) 5 and 7 240 VAC
Pump 2 (High Speed) 8 and 9 240 VAC
Circulation pump 14 and 15 240 VAC
Water heater 12 and 13 240 VAC
CLEARRAY or Ozone generator (optional) 16 and 17 240 VAC
2011-2013 J-315/J-325 Models
Device Test Points Voltage ±10%
Pump 1 (Low Speed) 5 and 6 240 VAC
Pump 1 (High Speed) 5 and 7 240 VAC
Circulation pump 14 and 15 240 VAC
Water heater 12 and 13 240 VAC
CLEARRAY or Ozone generator (optional) 16 and 17 240 VAC
2011-2012 J-230/J-270/J-280 Models with Circulation Pump
Device Test Points Voltage ±10%
Pump 1 (Low Speed) 5 and 6 240 VAC
Pump 1 (High Speed) 5 and 7 240 VAC
Pump 2 (N/A on J-230) 8 and 9 240 VAC
Circulation pump 14 and 15 240 VAC
Water heater 12 and 13 240 VAC
CLEARRAY or Ozone generator (optional) 16 and 17 240 VAC
J-210 Models
2011-2013 J-315/J-325 Models
Device Test Points Voltage ±10%
Pump 1 (Low Speed) 5 and 6 120 VAC
Pump 1 (High Speed) 5 and 7 120 VAC
Water heater 12 and 13 120 VAC or 240 VAC*
CLEARRAY or Ozone generator (optional) 16 and 17 120 VAC
*Depends whether hot tub is connected to 120 VAC or 240 VAC supply
J-230/J-235/J-245/J-270/J-275/J-280 Models without Circulation Pump Models
Device Test Points Voltage ±10%
Pump 1 (Low Speed) 5 and 6 240 VAC
Pump 1 (High Speed) 5 and 7 240 VAC
Pump 2 (N/A on J-230) 8 and 9 240 VAC
Water heater 12 and 13 240 VAC
CLEARRAY or Ozone generator (optional) 16 and 17 240 VAC
46
Page 51
J-230/J-235/J-245/J-270/J-275/J-280
2011-2013 J-335/J-345/J-355/J-365/J-375
J-LX/J-LXL 2-pump Models
Models (Export 50 Hz)
Device Test Points Voltage ±10%
Pump 1 (Low Speed) 5 and 6 230 VAC
Pump 1 (High Speed) 5 and 7 230 VAC
Pump 2 8 and 9 230 VAC
Circulation pump 14 and 15 230 VAC
Water heater 12 and 13 230 VAC
CLEARRAY or Ozone generator 16 and 17 230 VAC
J-210/2011-2013 J-315/2011-2013 J-325 1-pump Models (Export 50 Hz)
Device Test Points Voltage ±10%
Pump 1 (Low Speed) 5 and 6 230 VAC
Pump 1 (High Speed) 5 and 7 230 VAC
Circulation pump (if equipped) 14 and 15 230 VAC
Water heater 12 and 13 230 VAC
CLEARRAY or Ozone generator 16 and 17 230 VAC

A4 Testing Flow/Pressure Switch

When the “FL1 or FL2” message appears, it means the ow switch or pressure contacts have failed to close when the pump was turned on, or failed to open when the
pump was turned off. This could be caused by an excessively dirty lter, an obstruction in the ow path or by a bad switch. The rst thing to look for is an excessively dirty lter or an obvious obstruc-
tion, remembering (while not likely) that it is possible for a small object to work its way into the plumbing where
it will not be obvious. After verifying no obvious blockage exists, the ow or pressure switch can be tested.
Refer to page 21 for switch testing instructions.
47
Page 52

A5 About Fuses

When current passes through a conductor the conductor heats up. If the conductor is a heavy piece of wire or
a strip of metal, it will pass large currents and generate very little heat. If a wire is ne, or a strip of metal is thin, it will heat up at lower current levels. Fuses rely on this principle to protect circuits from massive current ows
by simply melting if their current rating is exceeded. By selecting different alloys for the fuse element, fuses can be made to have their current rating exceeded for a short period of time. Such slow-blow fuses are excellent for protecting motor circuits where start-up currents (surge currents) are higher than running currents.
For 2014+ J300s see the 2014 J300 S.T.A.
Fuse Part Number
1-Pump J-210,
J-315/J-325,
Models
1-Pump J-230
Models
2-Pump Models
1-Pump
Export
Models
2-Pump
Export
Models
Main Power, 20A 6660-106 X X X Main Power, 30A 6660-105 X X Transformer, 1.5A 6760-120 X X X X X
Testing Fuses
A good fuse should read continuity (0 Ω); a blown fuse will read no continuity (innite ohms). See Figures 6
and 7 for testing methods.
CAUTION: Make sure replacement fuses are exactly those listed above. Never test a fuse for continuity while installed in the fuse holder.
Figure 6
on board test
(power on voltage reading)
DCV ACV
OFF
750
1000
200
DCA
200
200µ
20
2000µ
2000m
20m
200m
200m
2000k
10A
200k
20k
2000
200
+
DCV ACV
OFF
1000
200
20
2000m
200m
2000k
200k
20k
2000
200
DCV ACV
OFF
750
1000
200
DCA
200
200µ
20
2000µ
2000m
20m
200m
200m
750
200
DCA
200µ
2000µ
20m
200m
10A
+
2000k
10A
200k
20k
2000
200
+
Figure 7
off board test
(resistance reading)
DCV ACV
1000
200
20
2000m
200m
2000k
200k
20k
2000
200
OFF
750
200
DCA
200µ
2000µ
20m
200m
10A
+

A6 The Watchdog “- - -”

Three horizontal dashes with no other control panel indicators illuminated is a result of the watchdog circuitry detecting a potential destructive condition within the hot tub.
There are many conditions that can cause a watchdog error message. Except for a runaway heat condition, most are caused by a faulty circuit board, bad hi-limit sensor, or temperature sensor. On rare
occasions a control panel or a bad transformer will cause Watchdog. Conrm this by using a test panel and
testing transformer connections on the circuit board, refer to appendix page 58.
1. Turn power to hot tub off. Verify proper resistance of hi-limit and temperature sensor (page 56). Replace defective temperature or hi-limit sensor then retest system. If watchdog error goes away, skip steps 2-4.
2. If the heater is not overly hot to touch and the watchdog displays an immediate dashed line error, the circuit board is probably bad. Check transformer primary and secondary voltages (page 58) before changing the circuit board.
3. See if the temperature in the heater has reached 118°F (48°C). If the heater got too hot, check for ow
restrictions or a sticking weir gate and correct the problem.
4. If you cannot produce the watchdog error and the hi-limit and temperature sensors check out OK, tell the customer to call you if watchdog display reappears.
48
Page 53

A7 Understanding Sanitizers

A. CLEARRAY
Our water purication system will begin disinfecting your water instantly.
is exclusive technology utilizing natural ultraviolet technology to sanitize your water, disinfecting bacteria, viruses, and algae in portable hot tubs. The ultraviolet light otherwise known as UV-C or germicidal light inacti­vates the microorganisms by disrupting the DNA so that it cannot reproduce and is considered lifeless. The bal-
last is the power supply for the purication system; it has two LED indicator lights the green indicating incoming power ow and the red indicating the system is properly working. CLEARRAY is standard for all models.
As the water is ltered, it passes through the CLEARRAY unit, and is exposed to UV light that sanitizes the water.
The combination of the CLEARRAY system and a residual sanitizer work in conjuction to keep your water clear and clean.
B. Ozone Oxygen is an element, and like other gaseous elements, normally exists as a pair of atoms bonded together to make a whole molecule. Chemists therefore use the symbol O
2
oxygen atoms.
CLEARRAY Water Purication System
to speak of “oxygen molecules” rather than
In the presence of an electric discharge like lightning, three molecules of O
can combine to form O
2
known
3
as ozone. While oxygen has no smell, ozone has a very pronounced smell in large concentrations. In small quantities, it causes the pleasant “fresh air” smell that laundry has when dried on a outdoor clothesline. Some clothing dryer manufacturers have installed an ultraviolet lamp inside their machines to give clothes that “fresh­as-all-outdoors” smell.
The technician must understand three things about ozone:
1. Ozone (O
) breaks down quickly into plain oxygen (O2).
3
2. Ozone kills germs.
3. Ozone is a strong oxidizer.
Because ozone breaks down quickly into oxygen (O
), a residual sanitizer must be used. There are two
2
choices, chlorine or bromine. While chlorine is oxidized by ozone just as quickly as bromine, residual bromine compounds are a much better disinfectant than residual chlorine compounds. Hence ozone and bromine team up much better to do the overall job than ozone and chlorine.

A8 Understanding pH

Keeping hot tub water clean and clear involves a very complex set of chemical reactions. Most importantly,
the hot tub must be sanitized. Bacteria, algae, and other single-cell life forms that may nd their way into the
hot tub must be killed. Three chemical elements, chlorine, bromine, and ozone are all good sanitizing agents. When any of these elements come into contact with bacteria or algae, these single-cell organisms die. There­fore, to keep the water germ free, we must simply keep a residual of the sanitizing agent in the water.
Making germs dead is only half the objective, however. The dead cells of the bacteria and algae we have killed, and the organic “stuff” (dandruff, perspiration, dead skin cells, etc.) that our bodies deposit in the hot tub, will make the water cloudy and uninviting as they decompose. These microscopic contaminants must be “burned out” or oxidized. These oxidation reactions occur simultaneously with reactions known as reduction reactions. The balance of these chemical reactions is quite critical and can occur properly only if pH levels are maintained from 7.2 to 7.8 pH (Ideal 7.4 to 7.6). If the pH is out of range, the sanitizing agent itself will be oxidized or re­duced and in effect be “used up” before it has a chance to do it’s job.
pH is critical for maximum disinfection, sanitizing, and cleaning results with the least amount of chemical addi­tion. Make sure your customer understands the importance of regular water test intervals and the proper use of chemicals. Both are necessary to ensure maximum water quality and to maintain a healthy and fun hot tub environment.
49
Page 54

A9 North American 60 Hz 120V/240V Convertible 1-Pump Models

Board is shown with 2013+ DCU with minidin connectors.
2011-2013 J300s only
2011-2012 Models used the ribbon style DCU.
This is a generic diagram actual connections and components may vary.
Light DCU
1
6
2
7
3
8
4
9
5
10
EXP BAR EXP BAR
POWER
Ozonator
OR
Optional
Circ.
(not offered
on all models)
Pump
Plug-in GFCI Cord (US Models Only) OR Hard Wire
Ports 1-10 power spa lights, waterfall lights and step lights on applicable models
Mini-Din Control Panel Cable
Mini-Din Cable provides constant 12 VAC from yellow transformer wires
OR
LED Lighting System DCU
CLEARRAY
C
F1
20A
250V
20
SC-20
BLK
GROUND
23
GRN
TB1
1
WHT
1
BLK
2
BLK
2
24
3
BLK
BLK
WHT
WHT
17
15
J6
WHT
RED
J1 Logic Jumper Settings
JP1 1-2 ON = 30A Logic (4-wire 120/240 VAC
J21
J12
J14
J16
5
J11
6
14
16
J15
J13
3
WHT
BLK
Transformer 120 VAC
J20
F1
K5 K7 K8
J5
4
7
J17 J7 J8
Main Pump
WHT
HILO
JP1
8 6 4 2
Heater IN Heater OUT
11
10
BLK
RED
RED
RED
7 5 3 1
Control
Control
12
J9
BLK
Panel
Panel
J2
21
22
J3
13
J10
THERM
THERM
SWITCH
SWITCH
JP1 1-2 OFF = 40A Logic (4-wire 120/240 VAC
JP1 7-8 ON = °C Temperature Display JP1 7-8 OFF = °F Temperature Display
Temperature Sensor
Hi-limit/Freeze Sensor
Pressure Switch
This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference.
2. This device must accept any inteference received including interference that may cause undesired operation.
(Located inside the heater for certain models)
25
26
*
Standard 120 VAC 3-Wire Connection (60 Hz, 1 Phase, 15A Service),
operation only)
operation only)
Heater
1.0 kW @ 120 VAC (3-wire connection)
4.0 kW @ 240 VAC (4-wire connection)
USE COPPER CONDUCTORS ONLY. WIRE SIZE MUST MEET NEC RECOMENDATIONS AND/OR LOCAL CODES AND IS DETERMINED BY MAXIMUM CURRENT DRAW AND LENGTH OF RUN.
50
Hard Wire Only
WARNING, ELECTRICAL SHOCK HAZARD EXISTS! Always remove power to spa before wiring and/or configuring the circuit board
Optional 4-Wire 240/120 VAC Convertible Heater Connection
1. Remove and discard the factory installed GFCI Cord.
2. Move RED* wire from TB1 position #1 to TB1 position #3 as shown below.
3. Permanently connect to the power supply. Use copper conductors ONLY. Wire size must be appropriate per NEC and/or local codes.
4. If hot tub is to be operated on 30A service, make sure the jumper provided at location JP1 #1 & 2 on the circuit board is installed. If hot tub is to be operated on 40A service, remove the jumper JP1 #1 & 2 on the circuit board.
EXTERNAL SERVICE PANEL BOX DISCONNECT MEANS MUST BE LOCATED NO CLOSER THAN 5 FT. (1.52m) FROM THE INSIDE WALLS OF THE SPA AND WITHIN SIGHT OF SPA
MAIN POWER
ON//OFF SHUTOFF
SWITCH
WHT
BLK
RED
GRN
TB1
GROUND
WHT
1
2
3
To circuit board
RED
*
BLK
RED
*
Page 55
Ozonator
(optional)
Light DCU
EXTERNAL SERVICE PANEL
MUST BE LOCATED NO CLOSER
THAN 5 FT. (1.52m) FROM THE
INSIDE WALLS OF THE SPA AND

A10 North American 60 Hz 240V 1- or 2-Pumps Models

Board is shown with 2013+ DCU with minidin connectors.
2011-2013 J300s only
2011-2012 Models used the ribbon style DCU.
This is a generic diagram actual connections and components may vary.
Flow sensor
Temperature sensor
Hi - limit / freeze sensor
This device complies with Part 15 of the
FCC rules. Operation is subject to the
following two conditions:
1. This device may not cause harmful
interference.
2. This device must accept any inteference
received including interference that may
Logic Jumper Settings
JP1 1-2 ON = 40A Logic
JP1 1-2 OFF = 50A Logic (Factory Default Setting)
JP1 3-4 ON = 2 Pump Operation
JP1 3-4 OFF = 1 Pump Operation
JP1 5-6 ON = 60A Logic (Remove JP1 1-2 Jumper)
JP1 5-6 OFF = Leave Off for 40A or 50A Logic
JP1 7-8 ON = Celsius Temperature Display
JP1 7-8 OFF = Fahrenheit Temperature Display
JP1
8 7
Control Panel
J1
3
1
21
4
2
6 5
22
J2
J3
cause undesired operation.
13
J10
J9
12
Heater
5.5 kW
25
240 VAC
26
Ports 1-10
power spa
lights, waterfall
lights and step
678
123
OR
lights on
applicable
models
9
4
240 VAC
Transformer
LED Lighting
System DCU
Mini-Din Control
10
5
POWER
EXP BAR EXP BAR
K1
J20
J21
J11
17
BLK
WHT
CLEARRAY
Panel Cable
Mini-Din Cable provides
OR
constant 12 VAC from
yellow transformer wires
J12
16
11
BLK BLK
J7 J8
10
J4
RED RED
F1
F1
30A, 250V
BLK
4
K2
K3
K4
K5
K6 K7 K8
3
J13
J14
15
14
J15
5
J16
6
J17
7
J18
8
J19
9
RED
SC-30
J5
20
J6
Stereo
(Not offered on all models)
Power Supply
2
2
1
1
TB1
Standard 240 VAC, 3-Wire Connection (60 Hz, 1-Phase Service)
USE COPPER CONDUCTORS ONLY. WIRE SIZE MUST BE APPROPRIATE
PER NEC AND/OR LOCAL CODES. THE MAX SUPPLY CONNECTOR
AMPACITY IS 60A. THE AMPERE RATING OF SUPPLY CONDUCTOR
OVERCURRENT PROTECTIVE DEVICE IS 60A.
BLK
RED
GRN
23
BLK
RED
BLK
WHT
Circ
BLK
C
Pump
(Not offered
on all models)
WHT
LO
Pump 1
WHT
HI
HI
Pump 2
(Not offered on
all models)
SWITCH
MAIN POWER
ON//OFF SHUTOFF
BOX DISCONNECT MEANS
WITHIN SIGHT OF SPA
51
Page 56

A11 Export 50 Hz 230V 1-Pump Models

Standard
Ozonator
LED Lighting
230 VAC 3-Wire Connection (50 Hz, 1-Phase Service),
OR LOCAL CODES AND IS DETERMINED BY MAXIMUM CURRENT DRAW AND LENGTH OF RUN.
Board is shown with 2013+ DCU with minidin connectors.
2011-2013 J300s only
2011-2012 Models used the ribbon style DCU.
This is a generic diagram actual connections and components may vary.
(Factory Setting)
J1 Logic Jumper Settings
JP1 1-2 ON = 20A Logic (Factory Setting)
JP1 1-2 OFF = 30A Logic
JP1 7-8 ON = °C Temperature Display
JP1 7-8 OFF = °F Temperature Display
Control Panel
J1
J20
Transformer
230 VAC
19
JP1
J21
8 7
K1
18
Pressure Switch
Temperature Sensor
Hi-limit/Freeze Sensor
21
22
J2
J3
3
1
4
2
6 5
K2
K3
J12
J14
27
17
Circ.
BRN
BRN
J16
Pump
Heater Specifications
Export Model:
2.7kW @ 230 VAC
(Thermo Switch - located inside
the heater for certain models)
26
25
13
THERM
SWITCH
K5 K7 K8
6
BLU
Heater IN Heater OUT
J5
3
J13
BRN
J17 J7 J8 J9 J10
4
7 10 11 12
BLK BLU BRN BLU BRN
HILO
Main
Pump
J6
BRN
F1
20A
20
250V
TB1
SC-20
2
1
USE COPPER CONDUCTORS ONLY. WIRE SIZE MUST MEET NEC RECOMMENDATIONS AND/
21
BRN
BLU
J4
K4
5
F1
J15
J11
28
16
BLU
BLU
Light DCU
52
Ports 1-10 power
spa lights, waterfall
lights and step lights
on applicable models
6
7
8
9
1
2
3
4
(not offered
on all models)
Mini-Din Cable provides
constant 12 VAC from
Mini-Din Control
Panel Cable
10
5
POWER
EXP BAR EXP BAR
yellow transformer wires
CLEARRAY
OR
OR
23
GRN
System DCU
Page 57

A12 Export 50 Hz 230V 1- or 2-Pump Models

Light DCU
LED Lighting
System DCU
Board is shown with 2013+ DCU with minidin connectors.
2011-2013 J300s only
2011-2012 Models used the ribbon style DCU.
This is a generic diagram actual connections and components may vary.
Flow Sensor
Temperature sensor
Hi - limit / freeze sensor
Logic Jumper Settings
JP1 1-2 ON = 20A Logic
JP1 1-2 OFF = 30A Logic
JP1 3-4 ON = 2 Pump Operation
JP1 3-4 OFF = 1 Pump Operation
JP1 5-6 ON = 40A Logic (Remove JP1 1-2 Jumper)
JP1 5-6 OFF = Leave Off for 20A or 30A Logic
JP1 7-8 ON = Celsius Temperature Display
JP1 7-8 OFF = Fahrenheit Temperature Display
3
Control Panel
1
JP1
4
2
6 5
8 7
J1
21
J2
22
J3
J10
J9
13
Heater
2.7 kW @
25
230 VAC
26
Ports 1-10
power spa
lights, waterfall
lights and step
lights on
applicable
models
230 VAC
Transformer
J20
BLK
Mini-Din Cable provides
constant 12 VAC from
Mini-Din Control
Panel Cable
yellow transformer wires
K1
J21
WHT
BLU
CLEARRAY
J11
17
OR
K2
J12
16
BRN
K3
J13
15
BLU
BRN
C
Circ.
all models)
(not offered on
J14
14
Pump
K4
5
BLU
J15
LO
BRN
J16
6
K5
BLK
J17
7
Pump 1
Stereo
BRN BRN
J7 J8
10 11 12
BLU BLU
J4
(not offered on all models)
Power Supply
F1
230 VAC 3-Wire Connection (50 Hz, 1-Phase Service), 1 Pump=15A/21A, 2 Pump=15A/29A,
USE COPPER CONDUCTORS ONLY. WIRE SIZE MUST MEET NEC RECOMMENDATONS
AND/OR LOCAL CODES AND IS DETERMINED BY MAXIMUM CURRENT DRAW AND
LENGTH OF RUN.
2
1
TB1
2
BRN
1
BLU
BRNBLU
8
J18
F1
20A, 250V
BRN
K6 K7 K8
SC-20
J5
20
3 4
J6
BLU
J19
9
23
BLU
BRN
TB2
GRN
HI
HI
Pump 2
(not offered on all models)
678
12345
9
10
POWER
EXP BAR EXP BAR
OR
Standard
Ozonator
53
Page 58

A13 Load Box Connection Diagrams A - D (North American 60 Hz)

Red
Pigtail
Neutral Bus
Ground
TB2
TB1
Black
Green
Main
Service
Panel
with
GFCI
Hot Tub
Load Box
2-Pole GFCI Breaker
Ground
2-Pole Circuit Breaker with 2-Wire Grounded Load Connection
(3 Wires to Hot Tub, 2-Hot, 1-Ground)
Red
Pigtail
Neutral Bus
Ground
TB2
TB1
Black
White
Green
Main
Service
Panel
with
GFCI
Hot Tub
Load Box
White
Black
Red
240 VAC/120 VAC
White
Black
Red
240 VAC
2-Pole GFCI Breaker
Ground
Load Neutral Lug on Breaker
2-Pole Circuit Breaker with 3-Wire Grounded Load Connection
(4 Wires to Hot Tub, 2-Hot, 1-Neutral, 1-Ground)
A
B
No Load Neutral Wire
Note: service disconnect not shown in this diagram.
Note: service disconnect not shown in this diagram.
W BBR
R
54
Page 59
Red
Red (Hot)
Pigtail
Neutral Bus
Ground
TB2
TB1
Black
Black (Hot)
White
Green
GFCI Sub Panel*
Main Panel*
Hot Tub Load Box
2-Pole GFCI Breaker
Ground
Main Panel with Secondary GFCI Shut-Off Box Using a
2-Pole GFCI Breaker with 3-Wire Grounded Connection
(4 Wires to Hot Tub, 2-Hot, 1-Neutral, 1-Ground)
D
Red
Red (Hot)
Pigtail
Neutral Bus
Ground
TB2
Black
Black (Hot)
Green
GFCI Sub Panel*
Main Panel*
Hot Tub Load Box
2-Pole GFCI Breaker
Ground
No Load Neutral Wire
Main Panel with Secondary GFCI Shut-Off Box Using a
2-Pole GFCI Breaker with 2-Wire Grounded Connection
(3 Wires to Hot Tub, 2-Hot, 1-Ground)
C
TB1
White (Neutral)
Green (Ground)
White (Neutral)
Green (Ground)
Load Neutral Lug on Breaker
*GFCI Sub Panel commonly used when recommended GFCI does not install in Main Panel.
*GFCI Sub Panel commonly used when recommended GFCI does not install in Main Panel.
Note: service disconnect not shown in this diagram.
Note: service disconnect not shown in this diagram.
W B R
BR
55
Page 60

A14 Temperature Sensor/Hi-Limit Sensor Resistance Chart

Fahrenheit (°F) Celsius (°C) Ohms ()
59.0..............................15 ....................................................................................... 48840
60.8..............................16 ....................................................................................... 46J200
62.6..............................17 ....................................................................................... 44610
64.4..............................18 ....................................................................................... 42630
66.2..............................19 ....................................................................................... 40770
68.0..............................20 ....................................................................................... 39000
69.8..............................21 ....................................................................................... 37290
71.6..............................22 ....................................................................................... 35400
73.4..............................23 ....................................................................................... 34170
75.2..............................24 ....................................................................................... 32700
77.0..............................25 ....................................................................................... 30000
78.8..............................26 ....................................................................................... 28740
80.6..............................27 ....................................................................................... 27540
82.4..............................28 ....................................................................................... 26400
84.2..............................29 ....................................................................................... 25311
86.0..............................30 ....................................................................................... 24270
87.8..............................31 ....................................................................................... 23280
89.0..............................32 ....................................................................................... 22329
91.4..............................33 ....................................................................................... 21429
93.2..............................34 ....................................................................................... 20541
95.0..............................35 ....................................................................................... 19740
96.8..............................36 ....................................................................................... 18960
98.6..............................37 ....................................................................................... 18210
100.4............................38 ....................................................................................... 17490
102.2............................39 ....................................................................................... 1J2000
104.0............................40 ....................................................................................... 16149
105.8............................41 ....................................................................................... 15519
107.6............................42 ....................................................................................... 14919
109.4............................43 ....................................................................................... 14349
111.2 ............................44 ....................................................................................... 13800
113.0 ............................45 ....................................................................................... 13281
56
Page 61

A15 Flow Switch Illustration (Models with a circulation pump)

P S I
FLOW
J3 Connector (Cable Side)
Shown while Plugged into Circuit Board
Hi-limit
Sensor wires
Temperature
Sensor wires
J3 Connector (Cable Side)
Shown while Plugged into Circuit Board
J2 Connector (Cable Side)
Shown while Plugged into Circuit Board
Shown while Plugged into Circuit Board
Flow Switch #6560-852
6560-852
2011-2013 J315, J-325 Models
Connection: This ow switch style has spade connectors at top for easy cable removal for
electronic troubleshooting.
Flow Switch #2560-040
2011+ JLX
2011-2013 J300 (except J-315 and J-325)
2011-2012 J-230, J-270, J-280 (with Circulation Pump)
Connection: This ow switch style has cable with curled nger connectors that can be removed from plug for
electronic troubleshooting.
2560-040

A16 Pressure Switch Illustration (Models without a circulation pump)

Pressure Switch #6560-869
2012+ J J-235, J-245, J-275
2011+ J-210, J-280
2011-2012 J-230, J-270 Connection: This pressure switch has spade connectors at top for easy cable removal for elec-
tronic troubleshooting.

A17 Sensor Harness Diagram

J2 Connector (Cable Side)
Shown while Plugged into Circuit Board
Temperature Sensor wires
Hi-limit Sensor, Temperature Sensor, Flow Switch Wires
TINE
PIN
Hi-limit
Sensor wires
Connector
(Side View)
Paper Clip
J3 Connector (Cable Side)
Flow Switch
Pressure Switch
To remove a sensor/switch wire from the either J2 or J3 connectors, insert the end of a paper clip into the slot cor­responding with the wire to be removed. This will depress the tine on the pin allowing the wire to be pulled from the harness.
IMPORTANT! When reinstalling the sensor/switch, make sure the tine on the pin is lifted so the sensor wire will lock into the connector body.
57
Page 62

A18 Transformer Test

W
BK Y
Y
120 VAC/240 VAC
Convertible Models*
(Wire End View)
Red
BK
Y
Y
240 VAC Models
(Wire End View)
Blk
Blk
Y
Y
Export 50 Hz Models
(Wire Side View)
To Test Transformer:
1. Leave transformer connector J4 plugged into the circuit board.
2. Set your Voltmeter to the 500 VAC range.
3. Place Voltmeter probes directly into backside (wire side) of J4 connector and test as follows:
North American 60 Hz 2011-2013 J-315/J-325 (120 VAC or 240 VAC Powered*) Connector J4 Voltage
Black to White 120 VAC* Yellow to Yellow 12-14 VAC*
North American 60 Hz J-210 (120 VAC or 240 VAC Powered*) Connector J4 Voltage
Black to White 120 VAC* Yellow to Yellow 12-14 VAC*
*Special instructions for all 120 VAC/240 VAC convertible power models.
120 VAC Power Conguration: Convertible models include a factory installed 10 foot GFCI cord rated at 15A/120 VAC. To use cord the hot tub must be installed within 10 feet of a dedicated, grounded type electrical outlet. Do not use an extension cord of any type! If the hot tub is more than 10 feet from an outlet, it must be hard wired to a single pole 15 amp GFCI breaker. Refer to pages
50-53 for specic circuit board congurations.
240 VAC Power Conguration: Convertible models can be hard wired for 4-wire 120 VAC/240
VAC power. This conguration powers the heater with 240 VAC while powering both pumps and
ozone with 120 VAC. An external 30 or 40 amp dual pole GFCI breaker is required. Refer to pages
50-53 for specic circuit board congurations.
North American 60 Hz J-LX, J-LXL, (240 VAC Powered) 2011-2013 J-335, J-345, J-355, J-365, J375 (240 VAC Powered) Connector J4 Voltage
Black to Red 240 VAC Yellow to Yellow 12-14 VAC
North American 60 Hz J-230, J-235, J-245, J-270, J-275, J-280 (240 VAC Powered) Connector J4 Voltage
Black to Red 240 VAC Yellow to Yellow 12-14 VAC
All Export 50 Hz Models
230 VAC Powered Connector J4 Voltage
Black to Black 230 VAC Yellow to Yellow 12-14 VAC
58
Page 63

A19 Troubleshooting The Optional Stereo System

The optional Stereo System provides a stereo receiver with high quality hot tub engineered speakers for supe­rior sound quality. If the stereo deck does not turn on, refer to the following test procedure.
I. BLUEWAVE stereo diagram (follow the testing procedures for the Aquatic stereo)
K
L
D
E
M
F
G
C
B
H
A
J
I
30-pin
3.5 mm cable
USB
AUX
Connector
AUDIO
MODE
FM JET
1
2
1
2
REPEAT RANDOM
DIR- DIR+
USB connector
A BLUEWAVE stereo with connections H Spade connectors (connect to the power supply) B Control Panel connection I Power supply (located in equipment bay) C Antenna connection on stereo J TB1 terminal (located in control box)
Stereo harness (connects to wiring harness
D
“E”) Spa wiring harness (connects spa compo-
E
nents to stereo)
K Spa speakers (connect to wiring harness)
L Stereo antenna
F Spa harness speaker connectors M Crossovers for the speakers
Subwoofer connector (connects to spa wiring
G
harness)
59
Page 64
II. Aquatic stereo diagram
M
L
N
D
C
B
A
E
H
F
G
K
J
I
A Aquatic stereo with connections H Spade connectors (connect to the power supply)
Remote sensor connection (connects to
B
remote sensor unit)
I Power supply (located in equipment bay)
C Antenna connection on stereo J TB1 terminal (located in control box)
Stereo harness (connects to wiring harness
D
“E”) Spa wiring harness (connects spa compo-
E
nents to stereo)
K Spa speakers (connect to wiring harness)
L Wireless remote sensor unit
F Spa harness speaker connectors M Stereo antenna
Subwoofer connector (connects to spa wiring
G
harness)
N Crossovers for the speakers
B. Testing power to stereo
1. Set voltage meter to 750 VAC.
J
2. Test across the TB1 terminal block (
) for 230 VAC.
3. If voltage is present, proceed to step C. If no voltage is present, check the breaker.
60
Page 65
C. Testing the fuses
1. Turn power to the spa OFF.
2. Locate the red fuse wire on the stereo wiring harness (
), Figure K. Not found on the BLUEWAVE
D
system.
3. Open the black casing that encloses the fuse and remove the 1A fuse.
4. Set your meter to test for continuity.
5. Test across the fuse.
A. A reading of “1” indicates a bad fuse. Replace the fuse and retest. B. A reading of “0” indicates a good fuse. Proceed to testing the 10A fuse.
D
6. Locate the yellow fuse wire on the stereo wiring harness (
), Figure L. The BLUEWAVE system will only
have this fuse.
7. Open the black casing that encloses the fuse and remove the 15A fuse.
8. Set your meter to test for continuity.
9. Test across the fuse.
A. A reading of “1” indicates a bad fuse. Replace the fuse and retest. B. A reading of “0” indicates a good fuse. Proceed to testing the power supply.
D
15A
1A
1A
15A
15A
1A
DCV ACV
1000
200
20
2000m
200m
2000k
200k
20k
2000
200
reading of 1 indicates a
OFF
750
200
DCA
200µ
2000µ
20m
200m
10A
+
DCV ACV
2000m
200m
2000k
reading of 0 indicates a
Figure K
OFF
750
1000
200
DCA
200
200µ
20
2000µ
20m
200m
10A
200k
20k
2000
200
+
DCV ACV
OFF
1000
200
20
2000m
200m
2000k
200k
20k
2000
200
reading of 1 indicates a
DCV ACV
750
200
DCA
200µ
2000µ
20m
200m
10A
+
1000
200
20
2000m
200m
2000k
200k
20k
2000
200
reading of 0 indicates a
OFF
750
200
DCA
200µ
2000µ
20m
200m
10A
+
Figure L
D. Testing the power supply
1. Turn power to the spa OFF.
I
2. Disconnect the spade connectors between the power supply (
) and the spa wiring harness ( H ).
3. Turn power to the spa back ON.
4. Set your meter to 20 VDC.
I
5. Test across the spade connectors for the power supply (
) for 12-15 VDC, Figure M.
6. If voltage is good then the stereo unit is bad. If voltage is bad then the power supply is bad.
Figure M
Test points
I
61
Page 66

A20 Glossary of Terms

Circuit Board: Printed circuit board assembly that distributes voltage to selected compo-
nents.
Control Panel: Component that allows user to access functions provided by the circuit
board.
Ammeter: Device which measures electrical current conducted through a wire or
electrical device.
Micro Chip: Chip on circuit board that stores hot tub software.
Flow Switch: Switch that informs circuit board there is sufcient water movement to acti-
vate heater. This switch identies water ow.
Hi-limit Sensor/Disk: Sensor that monitors water temperature inside heater.
Jumper: Device on circuit board that mechanically connects (bridges) two points
together.
Ohmmeter: Device that measures the resistance in ohms (Ω) of a component or tem-
perature sensitive device (e.g. temperature sensor, heater element etc).
CD Ozonator: A device that produces ozone gas by passing air through a corona dis-
charge (high voltage arc) chamber.
2011-2013 J300/J200 Models (with circ pump): Introduce ozone 24 hours a
day until a JETS button is pressed. Both lter cycle and ozone production
is canceled after a JETS button is pressed and then turn back on approxi­mately 5 minutes after jets turn off.
J-LX/J200 Models: Introduce ozone only during a lter cycle or a heat call.
Pin Assignments: Locations identied by numbers on circuit board.
Pressure Switch: J200 Models Only - Switch that informs circuit board there is sufcient wa-
ter movement to activate heater. This switch identies water pressure.
Sensor Connector: Plug in connector containing the temperature sensor and hi-limit sensor
device connections.
Summer Logic: Deactivates Circulation Pump, CLEARRAY and/or optional ozone genera-
tor when hot tub water reaches 2°F (1°C) above the set temperature. Hot tub water must be 95°F (35°C) or higher for summer logic to activate.
Temperature Sensor: Sensor that monitors hot tub water temperature.
Transformer: Device that converts primary high voltage AC signal to a secondary low
voltage AC signal.
Voltage Meter: Device that measures AC or DC voltage potentials across components or
from a specic test point to ground.
62
Page 67

A21 Troubleshooting Data Collection Form

Troubleshooting Data Collection Form
Customer Name ___________________________________________________________ Address _________________________________________ Phone ( ) _______________
Before troubleshooting, collect the following:
1. Model # of Hot Tub ______________________
2. Serial Number __________________________
3. Operating Voltage ______ Input Voltage______
Before calling Technical Support, collect the following:
4. Low Speed Pump Amps _____________
5. Pump with Heater Amps _____________
6. High Speed Pump Amps _____Pump #2 Amps ____
7. High Speed Pump + Heater Amps ______
8. Circuit Board Rev. _______Eprom Rev. ___________
Technical Support (866) 234-7727
63
Page 68
Jacuzzi Hot Tubs
14525 Monte Vista Ave, Chino, CA 91710
Phone: (909) 606-7733, Fax: (909) 606-0195,
Website: http://www.Jacuzzi.com
(A-08/14) © 2014 Jacuzzi, Inc. Printed in U.S.A.
Loading...