Jackson Systems Z-600 Installation And Operation Manual

INSTALLATION
AND
ZONE CONTROL MADE SIMPLE™
OPERATION MANUAL
Z-600 Six Zone Comfort System™
READ THIS MANUAL THOROUGHLY BEFORE PROCEEDING WITH INSTALLATION
INTRODUCTION
The Z-600 Comfort System™ is a residential and light commercial forced air zone control system that allows a single HVAC unit to have up to six separate zones. The system can be expanded to as many as 12 zones by adding 3-zone expansion modules. Intuitive firmware allows the panel to be used with single stage, multi-stage, heat pump and dual fuel equipment having up to 3 stages of heating and 2 stages of cooling. Standard heat / cool or heat pump thermostats can be used with the Z-600, along with a choice of two or three-wire zone dampers. Simple slide switch configuration allows for a wide range of system setup and control options best suited for each zoning application. Additional features include, fuse protected inputs and outputs, easy-to-read and access wiring
stat
terminals, LED point controls, and selectable ventilation and purge modes. An adjustable upstage timer allows single stage thermostats to be used with multi-stage equipment. Capacity Control can also stage equipment based on the number of zones calling. The Z-600 comes in an attractive and rugged 2-piece anodized aluminum enclosure that provides easy access for wiring, system setup and diagnostics.
us indication of all system functions, time delay override, adjustable on-board limits, balance
WARNING
1. Turn power off to HVAC unit and control panel during installation to prevent serious injury from electrical shock and/or damage to system.
2. Use extreme care when making duct openings and handling sheet metal to avoid injury.
3. The Z-600 and all components must be installed in a con exceed 150°F.
4. Install all components in a manner that prevents access by children.
CAUTION
1. Installation of this system must be in compliance with all applicable codes.
2. HVAC system must be properly sized and balanced to assure optimum system performance.
3. A bypass damper must be installed to maintain proper system airflow and static pressure.
4. All low voltage wire must be 18 gauge or heavier.
5. All wiring should be color coded and tagged for proper identification.
6. When landing wires to the control panel make sure wires are snug but do not over-tighten screw terminals.
CONTROL PANEL MOUNTING
Mount the zone control panel on a flat, moisture-free surface in a conditioned space that will facilitate easy access for wiring and
CONTROL PANEL TRANSFORMER
1. Never use the 24 volt equipment transformer to power the control panel, regardless of it VA rating
2. Wire a separate 24 VAC transformer of the proper VA to the designated terminals on the zone control panel marked 24 VAC.
system
setup.
ditioned space
where the ambient temperature will not
.
SYSTEMS
INSTALLATION
ZONE DAMPERS
1. Zone dampers may be two-wire (powered closed, spring open) or three-wire (powered closed, powered open)
2. Two-wire dampers connect to the zone damper terminals marked ‘D’ and ‘D’. Three-wire dampers connect to the terminals marked PC (Powered Closed), C (Common), and PO (Powered Open).
3. As many as three dampers may be wired in parallel for any single zone, providing the total VA of all dampers does not exceed the VA rating of the zone control panel transformer.
4. A 40 VA transformer will power the panel and up to four (4) dampers. A 75 VA transformer will power the panel
and up to seven (7) dampers.
5. If the total VA of all dampers exceeds 75 VA, a relay and a separate 24 volt transformer will be required to
power additional dampers.
6. Use only 18 gauge thermostat wire. Do not exceed 300 feet from zone damper to control panel.
ZONE THERMOSTATS
1. Zone thermostats must match equipment type. (Heat / Cool or Heat Pump) Power stealing thermostats are not recommended.
2. Use only 18 gauge thermostat wire. Do not exceed 300 feet from zone thermostat to control panel.
REMOTE SENSORS
Z-600-DAS
1. Mount the Z-600-DAS Discharge Air Sensor in the supply trunk. Mount the sensor out of the line of sight of the heat exchanger and cooling coils whenever possible and before any zone dampers. The Z-600-DAS sensor has a resistance value of 10,000 Ohms @ 77° F.
2. Use 18 gauge thermostat wire to connect the sensor to the DAS terminals on the zone control panel.
Z-600-OTS
1. Mount the Z-600-OTS Outdoor Temperature Sensor inside the outdoor unit where it will not be directly exposed to sunlight, water, snow or ice. The Z-600-OTS sensor has a resistance value of 10,000 Ohms @ 77° F.
2. Use 18 gauge thermostat wire to connect the sensor to the OTS terminals on the control panel.
HVAC UNIT
1. Wire the HVAC unit to the HVAC System terminals on the zone control panel. For equipment having separate
heating and cooling transformers, cut the jumper marked RH-RC on the control board and wire independently.
2. Use 18 gauge thermostat wire to connect the zone control panel HVAC System terminals to the HVAC
unit terminals.
3. The 24 VAC equipment common does not
CAP CTRL Capacity Control BLINKS when below selected value. ON when equal to or greater than selected value. (See Capacity Control Settings on back page)
EMHT Emergency Heat BLINKS when heat pump system is in the emergency heat mode. ON to indicate that a zone thermostat is still in the emergency heat mode. (See Emergency Heat Reset instructions)
DAS LIMIT Discharge Air Sensor ON when DAS is connected. BLINKS when panel goes out on high or low limit.
PURGE Purge Cycle ON for 1 minute after heating or cooling call when Purge is selected. TEST Time Delay Speed Up BLINKS when time delays are in speed up mode. Resets in 15 minutes. OTS Outdoor Temperature Sensor ON when OT S is connected. BLINKS when panel goes out on high
or low balance point.
STATUS Continuous System Check BLINKS to confirm microprocessor is functioning properly. POWER System Power ON when system is receiving 24 Volts.
(For dual fuel applications)
wire to the Z-600 panel.
SYSTEM STATUS LED DEFINITIONS AND FUNCTIONS
SEQUENCE OF OPERATION
Each zone damper is controlled by its own space thermostat and motorized zone damper. If any of the zone thermostats call for heating or cooling, the zones not calling will have their dampers powered closed, and the zones calling will have their dampers open. The heating or cooling equipment will be brought on at the same time. When all zones are satisfied, the heating or cooling equipment turns off. Zone dampers then reposition based on ventilation mode selection. The system can be set up to operate in either Cooling Priority or Majority Wins mode.
COOLING PRIORITY MODE - If any zones are calling for heating and a zone calls for cooling, the cooling will receive priority and the system will operate in the cooling mode. When all cooling calls are satisfied, the system will automatically changeover and take care of the heating calls.
MAJORITY WINS MODE - If more zones call for heating than cooling, the system will be in the heating mode. If more zones call for cooling than heating, the system will be in the cooling mode. If the number of heating and cooling calls are equal, cooling wins.
ZONE
THERMOSTAT
TERMINALS
ZONE STAT 1
ZONE STAT 2
ZONE STAT 3
ZONE STAT 4
ZONE STAT 5
ZONE STAT 6
C R
OB
G Y2 Y1
W3/AUX
W2 W1
C
R
OB
G Y2 Y1
W3/AUX
W2 W1
C
R
OB
G Y2 Y1
W3/AUX
W2 W1
C
R
OB
G Y2 Y1
W3/AUX
W2 W1
C
R
OB
G Y2 Y1
W3/AUX
W2 W1
C
R
OB
G Y2 Y1
W3/AUX
W2 W1
EXPANSION
BOARD
CONNECTOR
TIME DELAY
SPEED UP
(3 SECONDS = 1 MINUTE)
SYSTEM
SETUP
SWITCHES
SYSTEM STATUS
LEDs
PC BOARD FUSE
Jackson Systems
Z-600
MODE
SPEED
UP
MODE
3 SEC = 1 MIN
HIGH AND LOW
LIMIT ADJUSTMENT
STAGE TIMER ADJUSTMENT
(2 MINUTE OFF TIME)
HVAC
EQUIPMENT
STATUS
LEDs
(ON WHEN OUTPUT IS
ENERGIZED)
ON OFF HP HC SYSTEM FOSSIL CONV HEAT PUMP B O REV VALVE ELECT GAS FAN ZONE ALL FAN MODE 1 MIN OFF PURGE 20 MIN OFF TIME SHARE MAJORITY COOL PRIORITY
4 ZONES OFF 3 ZONES OFF 2 ZONES OFF ON OFF STAGE TIMER
CAP CTRL EMHT
. . . . .
. . . . .
EXPANSION
CONNECTOR
DAS LIMIT PURGE TEST
OTS STATUS POWER
4 AMP
ZONE
DAMPER
POSITION
LEDs
(ON WHEN
DAMPER IS
OPEN)
CAPACITY CONTROL
PC BOARD
4 AMP
ZONE
OPEN
ZD1
ZD2
ZD3
ZD4
ZD5
ZD6
137
55
175
100
49
12
HIGH BP
0
58
20
SYSTEM RC
SYSTEM RH
HIGH LIMIT
40
LOW LIMIT LOW BP
5
STAGE TIMER
O/B
FAN
Y2
Y1
W3 AUX/EH
W2
W1
SPARE
2 AMP 2 AMP
R
NOT USED
C
PC D
C D
PO
PC D
C D
PO
PC D
C D
PO
PC D
C D
PO
PC D
C D
PO
PC D
C D
PO
62
70
25
50
DAS = DISCHARGE
AIR SENSOR
DAS
DAS
OTS
OTS
OTS = OUTDOOR
SENSOR
O/B
G
Y2
Y1
W3/AUX/EH
W2
W1
RH
RC
2 AMP
2 AMP 2 AMP
ZD6 ZD5 ZD4 ZD3 ZD2 ZD1 24VAC
SENSORS
HVAC SYSTEM
24 VAC
TRANSFORMER
INPUT
ZONE DAMPER
TERMINALS
CENTER OF
FLAT SPOT
IS SETPOINT
POSITION
HIGH AND LOW
BALANCE POINT
ADJUSTMENT
SENSOR
TERMINALS
HVAC
SYSTEM
TERMINALS
2 AMP
SYSTEM
FUSES
RH-RC
JUMPER
SYSTEM SETUP
SYSTEM SWITCH SETTINGS
There are twelve, two-position slide switches located on the control panel. Set applicable switches in their proper position for HVAC equipment configuration and control options.
DEFINITIONS
fo
r 1 minute (Do not use with constant fan)
ON OFF
HP HC SYSTEM FOSSIL CONV HEAT PUMP B O REV VALVE ELEC GAS FAN ZONE ALL FAN MODE 1 MIN OFF PURGE 20 MIN OFF TIME SHARE MAJORITY COOL PRIORITY
HP Heat pump equipment HC Conventional heating and cooling equipment FOSSIL Heat pump with fossil fuel furnace CONV Heat pump with or without electric auxiliary heat B Heat pump reversing valve energized in heating O Heat pump reversing valve energized in cooling ELEC Fan energized on call for heat GAS Fan controlled by furnace ZONE Ventilation controlled by individual zone thermostat ALL Ventilation for all zones when any zone thermostat is set on continuous fan 1 MIN Fan purges to last zone calling 20 MIN 20 minute Time Share used with Majority Wins or Cooling Priority mode MAJORITY Heating and cooling controlled by greatest demand COOL Cooling calls receive priority over heating calls
TIME SHARE
Time Share can be used with either the Cooling Priority Mode or Majority Wins Mode. If zones being served (heating or cooling) have not been satisfied within 20 minutes and an opposite call takes place, the system will changeover. When that mode is satisfied or 20 minutes has gone by, the system will again changeover if an opposite call exists.
FAN MO
Wh
DE
en the Fan Mode slide switch is set in the ALL position and at least one zone thermostat is set in the fan ON mode, all zone dampers will open for ventilation air between equipment calls. When the Fan Mode slide switch is set in the ZONE position, only those zone thermostats set in the fan ON mode will have their dampers open for ventilation air between equipment calls.
CAPACITY CONTROL SETTINGS
The three Capacity Control slide switches have a numerical value of 2, 3 and 4. Any switch or combination of switches set in the ON position establishes the Capacity Control value. This value equals the minimum number of zones that must be calling in the same mode before a second stage can be energized. Capacity Control only allows for the upstaging to occur; it still requires a second stage call from the
thermostat
or Stage Timer to actually initiate the second stage of the equipment. It is recommended that the Capacity Control value equal no more than 50% of the total number of zones. This feature works with multi-stage and single-stage thermostats. The Stage Timer must be ON when single-stage thermostats are used with multi-stage equipment.
4 ZONES OFF 3 ZONES OFF 2 ZONES OFF
CAPACITY CONTROL
2 ON = 2 Zones 2 & 4 ON = 6 Zones
3 ON = 3 Zones 3 & 4 ON = 7 Zones 4 ON = 4 Zones 2, 3 & 4 ON = 9 Zones 2 & 3 ON = 5 Zones
CAPACITY CONTROL VALUES
STAGE TIMER
The Stage Timer switch is located below the Capacity Control switches. When the switch is set in the ON position, the adjustable Stage Timer is activated. This feature allows for the use of single-stage zone thermostats with multi-stage and heat pump equipment. The Stage Timer can be set from 5 to 20 minute upstaging. (Typically set at 10 minutes)
ADJUSTABLE LIMITS
High Limit
(Z-600-DAS Sensor) - Set at 170° for conventional heating systems and dual fuel applications. Set at 120° for heat pump. Allows fan to run but shuts off or down-stages equipment to prevent overheating. Low Limit
(Z-600-DAS Sensor) - Adjustable from 40° to 58° for both heat pump systems and conventional air con­ditioning. Allows fan to run but shuts off or down-stages equipment to prevent the coil from freezing. Low BP
(Z-600-OTS Sensor) - Set balance point to prevent heat pump operation when outdoor temperature falls below setpoint. (Typically set at 35° F) High BP
(Z-600-OTS Sensor) - Set balance point to prevent fossil fuel heat operation when outdoor temperature
rises above setpoint. (Typically set at 55° F)
5418 Elmwood Avenue, Indianapolis, IN 46203-6025 Toll Free: 888.652.9663 Fax: 317.227.1034 www.jacksonsystems.com
SYSTEMS
06-1007-021109
Z-600 TYPICAL THERMOSTAT WIRING DIAGRAMS
C R
TSOMREHT TA
G
Y1
W1
SINGLE STAGE 1H/1C
C R
O/B
TSOMREHT TA
G
Y1
HEAT PUMP WITH
NO AUXILIARY HEAT 1H/1C
C R
O/B
TSOMREHT TA
G Y2 Y1
MULTI-STAGE HEAT PUMP WITH
NO AUXILIARY HEAT 2H/2C
1
IF HEAT PUMP THERMOSTAT HAS AN ‘E’ EMERGENCY HEAT
C R O/B G Y2 Y1 W3/AUX W2 W1
C R O/B G Y2 Y1 W3/AUX W2 W1
C R O/B G Y2 Y1 W3/AUX W2 W1
C R
TSOMREHT TA
G
ENOZ006-Z SLANIMRET
ENOZ006-Z SLANIMRET
ENOZ006-Z SLANIMRET
Y2 Y1
W2 W1
MULTI-STAGE 2H/2C
C R
O/B
TSOMREHT TA
G
Y1
W2
E
1
HEAT PUMP WITH
AUXILIARY HEAT 2H/1C
C R
O/B
TSOMREHT TA
G Y2 Y1
W2
E
1
MULTI-STAGE HEAT PUMP WITH
AUXILIARY HEAT 3H/2C
C R O/B G Y2 Y1 W3/AUX W2 W1
C R O/B G Y2 Y1 W3/AUX W2 W1
C R O/B G Y2 Y1 W3/AUX W2 W1
TERMINAL, FIELD JUMPER THE ‘E’ TERMINAL TO THE AUXILIARY
HEAT TERMINAL ON THE THERMOSTAT.
ENOZ006-Z SLANIMRET
ENOZ006-Z SLANIMRET
ENOZ006-Z SLANIMRET
Z-600 TIME DELAYS
DELAY NORMAL MODE SPEED UP MODE
MINIMUM OFF TIME 2 MINUTES 5 SECONDS
CHANGEOVER 5 MINUTES 12 SECONDS
TIME SHARE 20 MINUTES 50 SECONDS
SDNOCES5.2ETUNIM1EGRUP
High and Low Limits -
Whenever the system down stages the HVAC equipment or shuts orst stage due to high or low limit control, 2 minutes must pass before rst stage or upstaging can be initiated providing the discharge air temperature has dropped below the heating limit setpoint or risen above the cooling limit setpoint.
Dual Fuel Low Balance Point -
Whenever the outdoor temperature drops below the low balance point setting and the system changes over from heat pump to the auxiliary heat source (gas or oil), auxiliary heat will remain on until the call is satised regardless if the outdoor temperature rises above the low balance point during the heating call.
SYSTEMS
5418 Elmwood Avenue, Indianapolis, IN 46203-6025 Toll Free: 888.652.9663 Fax: 317.227.1034 www.jacksonsystems.com
USING THE Z-600 WITH HEAT PUMPS AND DUAL FUEL EQUIPMENT
REVERSING VALVE:
Make sure that the heat pump thermostats and Z-600 reversing valve system switch are congured in the same mode.
O = Reversing valve energized on a call for cooling B=Reversing valve energized onacall for heating
When the reversing valve is energized on a call for heating (B) or cooling (O), the O/B LED will be ON, The reversing valve will remain energized until an opposite call takes place.
HEAT PUMP AUXILIARY HEAT WIRING:
The zone thermostat auxiliary heat terminals are marked . The HVAC System auxiliary heat terminal is marked . (See Typical Thermostat Wiring Diagrams)
THERMOSTAT CONTROL OF AUXILIARY HEAT:
When a zone thermostat calls for auxiliary heat in standard heat pump mode, the auxiliary heat cycles and the heat pump compressor will be on at the same time.
When a zone thermostat calls for auxiliary heat in dual fuel (fossil fuel) mode, the heat pump compressor is locked out and auxiliary heat (fossil fuel) becomes rst stage until the heating call is satised.
BALANCE POINT CONTROL:
Low Balance Point When a zone thermostat calls for rst stage heat in dual fuel (fossil fuel) mode and the outdoor temperature is below the selected low balance point setting, the heat pump compressor is locked out and auxiliary heat (fossil fuel) replaces heat pump operation. This feature does not apply for standard heat pump operation.
High Balance Point When a zone thermostat call above the selected high balance point setting, the auxiliary heat will be locked out. This feature does not apply for dual fuel (fossil fuel) operation.
EMERGENCY HEAT:
In the event ofaheat pump failure, only one zone thermostat needs to be placed in the Emergency Heat mode. The Z-600 panel remembers the zone thermostat set in the Emergency Heat mode and treats all calls for heating from any zone as an emergency heat call. The LED will be ON to signify that an emergency heat call has taken place. To reset the system back to standard heat pump operation, take the zone thermostat out of the Emergency Heat mode. On the next call for heating the LED will be OFF and the panel will resume normal heat pump operation.
W3/AUX/EH
s for auxiliary heat in standard heat pump mode and the outdoor temperature is
EMHT
W3/AUX
EMHT
PANEL FUSES:
4 AMP PC Board Fuse The 4 AMP PC board fuse is designed to protect the Z-600 panel, zone thermostats and zone dampers from a 24 Volt short. Replacement fuse should not exceed 4 AMPS.
2 AMP System Fuses The two, RC and RH 2 AMP system fuses are designed to protect the Z-600 panel froma24 Volt HVAC equipment short. A2AMP spare fuse is located on the panel. However, replacement fuses shoul AMPS.
SYSTEMS
t exceed 3
d no
5418 Elmwood Avenue, Indianapolis, IN 46203-6025 Toll Free: 888.652.9663 Fax: 317.227.1034
www.jacksonsystems.com
07-1091-031511
Loading...