Jackson Systems THE GREEN ZONE Z-200-HC-MS Installation And Operation Instructions Manual

G
EHT
R
Zone Control Made Simple
Z
NEE
N
E
Z-200-HC-MS Installation and Operation Instructions
2 Heat / 2 Cool - Auto Changeover - First Call Priority - Time Share
High and Low Limit Protection:
The Z-200-DAS Discharge Air Sensor should be
mounted on the discharge air plenum of the
EHT
G
R
N
E
Z
Zone Control Made Simple
NEE
TM
HVAC unit and wired to the DAS terminals on the panel. If the heating temperature rises above 170° F or if the cooling temperature falls below 45° F, the sensor will cycle the equipment, while the fan continues to run. When the system goes out on low limit a 3 minute time delay is activated before cooling is allowed to energize (providing the discharge air temperature has risen above 45° F). LIMIT LED blinks when high or low limit is reached.
Sequence of Operation:
The Green Zone™ Z-200-HC-MS is a residential /
light commercial zone control system that allows a single HVAC unit to have up to two separate zones. Each zone is controlled by its own space thermostat and motorized zone damper. If a zone thermostat calls for heating or cooling, the zone not calling will have its damper powered closed, and the zone calling will have its damper opened. The heating or cooling equipment will also be brought on at the same time. When the zone calling is satisfied, the heating or cooling equipment turns off. If one zone calls for heating and another zone calls for cooling, the first zone to call receives priority. When the first call is satisfied, the system will changeover and take care of the opposite call. If a zone being served (heating or cooling) has not been satisfied within 20 minutes and an opposite call takes place, the system will changeover. When the zone is satisfied or 20 minutes has gone by, the system will again changeover if an opposite call exists. This is referred to as Auto Changeover - First Call Priority - Time Share. In the event of a tie, cooling will receive priority.
Ventilation Mode:
Zone ventilation is established by the individual zone thermostat fan setting. Any thermostat set in the fan AUTO mode will not receive ventilation air when no equipment calls are taking place. Any thermostat set in the fan ON mode will receive ventilation air whenever there are no heating or cooling calls taking place.
Power Requirements:
The Z-200 requires a separate 24 Vac transformer. A 40 VA transformer will power the panel and up to four (4) dampers. A 75 VA transformer will power the panel and up to six (6) dampers. If more than three (3) dampers for an individual zone are required, a RY-1-HB relay should be used with an additional properly sized transformer. Jackson Systems HD-XXXX rectangular and D-XX round dampers are powered closed/spring return open. Damper actuators are rated at 10 VA.
Wiring:
All wiring is done using conventional 18 gauge thermostat wire. Thermostats and zone dampers may be located up to 300 feet from the Z-200 panel.
Z-200-HC-MS Installation and Operation Instructions
2 Heat / 2 Cool - Auto Changeover - First Call Priority - Time Share
LED FUNCTIONS
24 V (ON with 24 Vac)
W1 (ON with first stage heat)
W2 (ON with second stage heat)
Y1 (ON with first stage cool)
Y2 (ON with second stage cool)
G (On with fan call)
LIMIT (ON when sensor is connected - Blinks when out on High or Low limit)
ZD1 (ON when damper is open)
ZD2 (ON when damper is open)
G
EHT
R
Z
NEE
Zone Control Made Simple
LOGIC PANEL WIRING DIAGRAM
JACKSON SYSTEMS, LLC
24V
Z-200-HC-MS
W1
W2
Y1
Y2
G
LIMIT
ZD1
ZD2
C
R
W1
W2
Y1
Y2
G
D
D
C
R
W1
W2
Y1
Y2
G
D
D
R
W1
W2
Y1
Y2
G
DAS DAS
X H
N
ZONE 1
ZONE 2
HVAC
24V
E
24V
C R
W1
MULTI-STAGE
HEAT / COOL
W2
THERMOSTAT
Y1
Y2
G
DAMPER MOTOR
D
0.42 AMPS 10 VA
C R
W1
MULTI-STAGE
HEAT / COOL
W2
THERMOSTAT
Y1
Y2
G
DAMPER MOTOR
D
0.42 AMPS 10 VA
R
W1
HVAC UNIT
W2
TERMINAL
Y1
Y2
G
STRIP
Z-200-DAS
DISCHARGE
AIR
SENSOR
120V
4AMP 4AMP
HVAC EQUIPMENT
4 AMP
4 Amp fuse protects
the relay contacts
120/24 VAC
TRANSFORMER
ZONE SYSTEM
4 AMP
4 Amp fuse protects
printed circuit board
G
EHT
R
Zone Control Made Simple
Z-200-HC-MS Installation and Operation Instructions
2 Heat / 2 Cool - Auto Changeover - First Call Priority - Time Share
Installation:
Mounting the Panel:
Carefully remove the Z-200 panel and cover from the shipping carton. Slide the PC board out of the snap track base and mount the base to a flat surface either on or near the HVAC indoor unit in an area that will facilitate easy access for wiring. Reinstall the PC board by carefully centering it over the base and snapping it back into the track groves.
Wiring Zone Thermostats and Dampers:
Refer to the logic panel wiring diagram. Wire zone 1 thermostat and its associated damper to the ZONE 1 terminals on the logic panel. Wire zone 2 thermostat and damper in the same manner.
Wiring HVAC Equipment:
Wire the HVAC unit to the Z-200-HC-MS HVAC panel terminals. Note: Do not wire the equipment common to the Z-200-HC-MS panel.
Installing and Wiring the Z-200-DAS Discharge Air Sensor:
Drill a ½”hole in the middle of the main discharge air plenum approximately 18” downstream of the heat exchanger. Remove the Z-200-DAS cover. Slide the probe into the hole and use two self­tapping sheet metal screws to secure the base making sure that the gasket is in place. Use 18-2 thermostat wire and wire nuts to attach the sensor leads. Replace the cover and wire the sensor to the DAS terminals on the
Z-200-HC-MS panel.
Z-200-DAS
SENSOR PROBE
MOUNTING
SCREWS
PLENUM
GASKET
COVER
COVER
RETAINER
SCREW
TO
Z-200-HC-MS
DAS
TERMINALS
Z
NEE
Wiring the Transformer:
Wire a separate 24 volt transformer of the proper VA to the logic panel terminals marked (X) and (H). Note: Do not power the panel up until all wiring is completed.
N
E
Test, Check and Startup:
1. Verify that all component wires have been connected to the proper terminals and are secure.
2. Disconnect the HVAC equipment ( R ) terminal wire at the panel and apply 24 volts to panel.
3. Take a jumper wire and momentarily short the DAS terminals. This will put the panel time delays in “speed up” mode.
4. Place both zone thermostats in the OFF position.
5. Place zone 1 thermostat in the heating mode and have the thermostat call for heat. Confirm that (ZD1) LED is ON and that (W) LED is ON. Confirm that zone 1 damper is open and zone 2 damper is closed. There will be no voltage across zone 1 (D) and (D) terminals and 24 volts on zone 2 (D) and (D) terminals.
6. Put zone #1thermostat in the cooling mode and have the thermostat call for cooling. Confirm that (ZD1) LED is ON and that the (Y) and (G) LEDs are ON. If the thermostat has internal time delays, the cooling call may not activate immediately.
7. Turn zone #1 thermostat off and repeat steps 5 and 6 with zone #2 thermostat. Remember, the zone calling will have its damper open and there will be no 24 Vac on the ‘D’ and ‘D’ terminals for that zone.
8. Determine the ventilation mode of each zone thermostat by setting the thermostats in the Fan Auto or ON mode.
9. Remove 24 Volts to the panel and reconnect the HVAC ‘R’ wire.
10. When 24 Volts is again applied to the panel, the internal time delays will be activated.
11. Confirm that the LIMIT LED is ON. If not, check LIMIT wiring. If the system goes out on high or low limit, the LIMIT LED will blink.
G
EHT
Z-200-HC-MS Installation and Operation Instructions
2 Heat / 2 Cool - Auto Changeover - First Call Priority - Time Share
Specifications:
Panel Dimensions:
Height: 8.0 Inches Width: 6.0 Inches Depth: 1.375 Inches
Mounting:
Snap Track with 2 back plate screws
Operating Temperature Rating:
-40° F to 150° F
Operating Humidity:
5% to 90% RH non-condensing
Wiring:
18-gauge wire for all equipment
and system connections
Time Delays:
3 minutes minimum off between cooling calls 3 minutes minimum off on low limit 20 minute time share
Thermostats:
Single-stage heat / cool thermostats Programmable or non-programmable Auto or manual changeover
R
Z
NEE
N
E
Zone Control Made Simple
Dampers:
D Powered Closed / Spring Open D (2 wire)
High / Low Limit
DAS Discharge Air Sensor DAS (2 wire)
HVAC Equipment:
R 24Vac (Hot) W1 First Stage Heat W2 Second Stage Heat Y1 First Stage Cool Y2 Second Stage Cool G Fan
Panel Power:
X 24Vac (Common) H 24Vac (Hot)
Typical System Layout
ZONE 2
STAT
ZONE DAMPER 2
MIGHT SERVE
BEDROOM AREA
ZONE 1
STAT
ZONE DAMPER 1
MIGHT SERVE
LIVING AREA
Terminal Designations:
Thermostats:
C 24Vac (Common) R 24Vac (Hot) W1 First Stage Heat W2 Second Stage Heat Y1 First Stage Cool Y2 Second Stage Cool G Fan
Zone Control Made Simple™
HIGH/LOW
LIMIT
SENSOR
Z-200-HC-MS
PANEL
24 VOLT 40VA
TRANSFORMER
FURNACE
5418 Elmwood Avenue, Indianapolis, IN 46203-6025 Toll Free: 888.652.9663 Fax: 317.227.1034 www.jacksonsystems.com
06-1035-072011