Jackson Systems T-32-TS Touchscreen Thermostat Installation Manual

COMF
RT SYSTEM
T-32-TS Touchscreen Thermostat
Installation Manual
TABLE OF CONTENTS
Introduction
Disassembly Thermostat Location Mounting The Subbase
Terminal Designations Setting The System Switches System Switch Functions Installing The Batteries Typical System Wiring Diagrams
Heat Only (Gas)
Heat Only (Electric)
Cool Only
1 Heat / 1 Cool (Gas)
2 Heat / 2 Cool (Gas)
2 Heat / 1 Cool Heat Pump
3 Heat / 2 Cool Heat Pump
2 Heat / 1 Cool Fossil Fuel
3 Heat / 2 Cool Fossil Fuel
4 5 6 6 6
6, 7
8
9 10 11 12 12 13 14 15 16 17 18 19 20
1
TABLE OF CONTENTS
Installer Setup Menu
Entering The Setup Menu Selecting The Program Selecting Program Days Selecting Temporary Program Override Selecting Programmable Fan Mode Selecting Mode Selecting Touchscreen Lock Options Selecting The Cooling Setpoint Limit Selecting The Heating Setpoint Limit Selecting The Temperature Display Selecting The Time Format Selecting The Setpoint Display Option Selecting Back Light Option Selecting Adaptive Recovery Option Selecting Filter Reminder Selecting First Stage Heating And Cooling Differential Option Selecting Second Stage Heating And Cooling Differential Option Selecting Third Stage Heating Differential Option Selecting Internal Or Indoor Remote Sensor Calibration Option Selecting Remote Sensor Option Selecting Equipment Configuration
21 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41
2
TABLE OF CONTENTS
Selecting Low Balance Point Option Selecting High Balance Point Option Selecting Audible Beep Option Selecting The Factory Default Option Selecting Daylight Savings Time Option
Remote Sensor Installation
Remote Sensors Indoor Sensor Wiring Using Multiple Sensors For Temperature Averaging
Outdoor Sensor Wiring Temperature Calibration Chart Testing
Testing Fan Operation
Testing Conventional Heating And Cooling Operation
Testing Conventional Heat Pump Operation
Testing Fossil Fuel Operation
Testing Low Balance Point (Heat Pump or Fossil Fuel)
Testing High Balance Point (Heat Pump or Fossil Fuel) Adaptive Recovery Basic Trouble Shooting T-32-TS Specifications
42 43 44 45 46 47 47
47, 48
49 50 51 52 52
52, 53
53
53, 54
54
54, 55
55
56, 58
59
3
INTRODUCTION
The Comfort System T-32-TS is a feature-rich touchscreen thermostat that can be
battery powered or hardwired to the HVAC equipment. Using a common sense approach to the installation will ensure this product is installed properly and to the customer’s satisfaction. Please take time to read and understand this manual so that installation and testing is performed in an efficient manner.
This manual is to be used in conjunction with the supplied User Manual.
Although great care has been taken in the preparation of this manual, Jackson Systems takes no responsibility for errors or omissions contained herein. It is the responsibility of the installer to ensure that this thermostat and the equipment connected to it operate in a safe and efficient manner.
Due to ongoing product improvements, Jackson Systems reserves the right to change the
specifications of the T-32-TS thermostat or its components without notice.
All rights reserved.
Jackson Systems, LLC 2012.
©
Intellectual rights apply.
4
GETTING STARTED
As with any HVAC project, careful installation is the key to a successful outcome. Tim taken during the installation process will be rewarded with fewer call-backs.
The steps required to install the T-32-TS thermostat are as follows.
1. Read and understand this Installation Manual and User Manual
2. Mount and wire the subbase.
3. Install the batteries.
4. Set the 4 system switches to match the equipment application. Heat / Cool Heat Pump Fossil Fuel
5. Wire optional remote temperature sensor(s).
6. Power the thermostat
7. Set the Advanced Installer settings.
8. Test the thermostat.
5
INSTALLING THE THERMOSTAT
DISASSEMBLY
There are two release slots located on the bottom of the thermostat. Gently push the flat blade of a small screwdriver into one slot at a time and pry upward until the catch disengages. Carefully swing the thermostat upward and away from the subbase.
THERMOSTAT LOCATION
The T-32-TS should be installed in a location that represents the ambient space temperature. Do not install the thermostat in an area where drafts are present, near the floor, behind doors or on an external wall. Avoid placing the thermostat in areas where the air movement is limited, affected by direct sunlight or other areas not typical of the temperature in the space.
MOUNTING THE SUBBASE
When mounting the T-32-TS subbase, be aware that drafts may travel down wall cavities and enter the back of the thermostat through the control wire hole in the wall. It is important to seal the
6
FIGURE 1
INSTALLING THE THERMOSTAT
hole to prevent any drafts that might affect the internal temperature sensor. Pull the control wires through the large opening in the thermostat subbase. Next, level and mount the subbase on the wall using the supplied anchors and screws. (Figure 2)
Do not over tighten the mounting screws as the subbase may warp causing the improper seating of the thermostat connecting pins to the terminal blocks.
Use a properly sized screwdriver and back each screw terminal out (counter clockwise) before landing each wire to its dedicated terminal. Do not over tighten the terminal screws. Check to ensure that all wires are landed correctly and dressed properly to prevent any shorts. Refer to Typical System Wiring Diagrams in this manual for proper wiring.
Jackson Systems, LLC
www.jacksonsystems.com
MOUNTING HOLES
W2
S2 SC S1
O/B
W1
7
WIRE
ACCESS
HOLE
MOUNTING
HOLE
FIGURE 2
BATTERY
COMPARTMENT
MOUNTING HOLES
Y1 Y2 GRC
INSTALLING THE THERMOSTAT
TERMINAL DESIGNATIONS
TERMINAL DESIGNATION
S2 Outdoor Sensor
SC Sensor Common
S1 Indoor Sensor
W2/OB Second Stage Heat or Reversing Valve
W1 First Stage Heat / Auxiliary / Emergency Heat
Y1 First Stage Cool or First Stage Compressor
Y2 Second Stage Cool or Second Stage Compressor
GFan
R 24 VAC Hot
C 24 VAC Common
8
SETTING THE SYSTEM SWITCHES
The T-32-TS contains a set of four system switches located on the thermostat printed circuit board. (Figure 3)The switches are used to match the thermostat operation and relay outputs with the HVAC system requirements. Refer to the system switch functions on the next page to properly configure the thermostat.
ON
1 2 3 4
SYSTEM SWITCHES
. . . . .. . . . .
FIGURE 3
9
SYSTEM SWITCH FUNCTIONS
Switch 1 - Equipment Type
Switch 2 - Fan or ReversingValve When Switch 1 is OFF
Switch 1 sets the equipment type. For conventional heat / cool equipment, set the switch to the OFF position (factory default). For heat pump equipment set the switch to the ON position.
For Gas heat, set the switch to the OFFposition (factory default). For electric heat, set the switch to the ON position.
When Switch 1 is ON
For‘O’reversing valve, set the switch to the OFF position (factory default). For ‘B’ reversing valve, set the switch to the ON position.
Switch 3 - Short Cycle Timer
Switch 4 - Fossil Fuel Mode
For 4 minute short cycle protection, set switch to the OFF position (factory default). To disable short cycle protection, set switch to the ON position.
For conventional heat pump equipment, leave switch in the OFF position (factory default). For fossil fuel equipment, set switch to the ON position.
10
INSTALLING THE BATTERIES
The T-32-TS comes with two AAA batteries. Even if the thermostat is hardwired, battery backup is recommended to maintain the real-time clock in the event of a power failure. All other memory is non-voilatile in the event of battery or primary power loss. Press in on the battery access compartment and slide the drawer out. Install the two AAA batteries matching the + and - orientation. Push the battery compartment in until it clicks shut. When the batteries are properly installed, the touchscreen display will light up. (Figure 4)
+
-
FIGURE 4
11
TYPICAL SYSTEM WIRING DIAGRAMS
HEAT ONLY (GAS)
OPTIONAL
REMOTE SENSOR
TERMINALS
S2
OUTDOOR
SENSOR
SC
S1
INDOOR
SENSOR
W2 O/B
W1
Y1 Y2 G R C
THERMOSTAT
EQUIPMENT
Switch Settings
Switch 1 = OFF Heat / Cool Switch 2 = OFF Equipment controls fan on call for heat Switch 3 = OFF Short Cycle Protection (No affect on setup) Switch 4 = OFF Leave OFF
HEAT 1 RELAY
12
FAN 1
RELAY
24 V
LINE
TYPICAL SYSTEM WIRING DIAGRAMS
HEAT ONLY (Electric)
OPTIONAL
REMOTE SENSOR
TERMINALS
S2
OUTDOOR
SENSOR
SC
S1
INDOOR SENSOR
W2 O/B
W1
Y1 Y2 G R C
THERMOSTAT
EQUIPMENT
Switch Settings
Switch 1 = OFF Heat / Cool Switch 2 = ON Thermostat controls fan on call for heat Switch 3 = OFF Short Cycle Protection (No affect on setup) Switch 4 = OFF Leave OFF
HEAT 1 RELAY
13
FAN 1
RELAY
24 V
LINE
TYPICAL SYSTEM WIRING DIAGRAMS
COOL ONLY
OPTIONAL
REMOTE SENSOR
TERMINALS
S2
OUTDOOR
SENSOR
SC
S1
INDOOR SENSOR
W2 O/B
W1
Y1 Y2 G R C
THERMOSTAT
EQUIPMENT
Switch Settings
Switch 1 = OFF Heat / Cool Switch 2 = OFF Fan energized on call for cooling Switch 3 = OFF Short Cycle Protection (Recommended) Switch 4 = OFF Leave OFF
COOL 1
RELAY
14
FAN 1
RELAY
24 V
LINE
TYPICAL SYSTEM WIRING DIAGRAMS
1 HEAT / 1 COOL (GAS)
OPTIONAL
REMOTE SENSOR
TERMINALS
S2
OUTDOOR
SENSOR
SC
S1
INDOOR SENSOR
Switch Settings
Switch 1 = OFF Heat / Cool Switch 2 = OFF Fan energized on call for cooling Switch 3 = OFF Short Cycle Protection (Recommended) Switch 4 = OFF Leave OFF
W2 O/B
W1
HEAT 1 RELAY
Y1 Y2 G R C
COOL 1
COOL 1
RELAY
RELAY
FAN 1
RELAY
15
THERMOSTAT
EQUIPMENT
24 V
LINE
TYPICAL SYSTEM WIRING DIAGRAMS
2 HEAT / 2 COOL (GAS)
OPTIONAL
REMOTE SENSOR
TERMINALS
S2
OUTDOOR
SENSOR
SC
S1
INDOOR SENSOR
W2 O/B
W1
HEAT 1 RELAY
Y1 Y2 G R C
COOL 2
RELAY
THERMOSTAT
EQUIPMENT
Switch Settings
Switch 1 = OFF Heat / Cool Switch 2 = OFF Fan energized on call for cooling Switch 3 = OFF Short Cycle Protection (Recommended) Switch 4 = OFF Leave OFF
HEAT 2 RELAY
COOL 1
COOL 1
RELAY
RELAY
16
FAN 1
RELAY
24 V
LINE
TYPICAL SYSTEM WIRING DIAGRAMS
2 HEAT / 1 COOL (HEAT PUMP)
OPTIONAL
REMOTE SENSOR
TERMINALS
S2
OUTDOOR
SENSOR
SC
S1
INDOOR SENSOR
W2 O/B
W1
AUX
RELAY
Y1 Y2 G R C
THERMOSTAT
EQUIPMENT
Switch Settings
Switch 1 = ON Heat Pump Switch 2 = OFF/ON OFF = ‘O’ ON = ‘B’ Switch 3 = OFF Short Cycle Protection (Recommended) Switch 4 = OFF Leave OFF
REV
VALV E
COOL 1
COMP 1
RELAY
RELAY
17
FAN 1
RELAY
24 V
LINE
TYPICAL SYSTEM WIRING DIAGRAMS
3 HEAT / 2 COOL (HEAT PUMP)
OPTIONAL
REMOTE SENSOR
TERMINALS
S2
OUTDOOR
SENSOR
SC
S1
INDOOR SENSOR
W2 O/B
W1
AUX
RELAY
Y1 Y2 G R C
COMP 2
RELAY
THERMOSTAT
EQUIPMENT
Switch Settings
Switch 1 = ON Heat Pump Switch 2 = OFF/ON OFF = ‘O’ ON = ‘B’ Switch 3 = OFF Short Cycle Protection (Recommended) Switch 4 = OFF Leave OFF
REV
VALV E
COOL 1
COMP 1
RELAY
RELAY
18
FAN 1
RELAY
24 V
LINE
TYPICAL SYSTEM WIRING DIAGRAMS
2 HEAT / 1 COOL (FOSSIL FUEL)
OPTIONAL
REMOTE SENSOR
TERMINALS
S2
OUTDOOR
SENSOR
SC
S1
INDOOR SENSOR
W2 O/B
W1
AUX
RELAY
Y1 Y2 G R C
THERMOSTAT
EQUIPMENT
Switch Settings
Switch 1 = ON Heat Pump Switch 2 = OFF/ON OFF = ‘O’ ON = ‘B’ ReversingValve Switch 3 = OFF Short Cycle Protection (Recommended) Switch 4 = ON Locks out heat pump when furnace is energized
REV
VALV E
COOL 1
COMP 1
RELAY
RELAY
19
FAN 1
RELAY
24 V
LINE
TYPICAL SYSTEM WIRING DIAGRAMS
3 HEAT / 2 COOL (FOSSIL FUEL)
OPTIONAL
REMOTE SENSOR
TERMINALS
S2
OUTDOOR
SENSOR
SC
S1
INDOOR SENSOR
W2 O/B
W1
AUX
RELAY
Y1 Y2 G R C
COMP 2
RELAY
THERMOSTAT
EQUIPMENT
Switch Settings
Switch 1 = ON Heat Pump Switch 2 = OFF/ON OFF = ‘O’ ON = ‘B’ ReversingValve Switch 3 = OFF Short Cycle Protection (Recommended) Switch 4 = ON Locks out heat pump when furnace is energized
REV
VALV E
COOL 1
COMP 1
RELAY
RELAY
20
FAN 1
RELAY
24 V
LINE
INSTALLER SETUP MENU
ENTERING THE SETUP MENU
Clock ModeTouch and hold both the and section for 5 seconds to enter the Installer
Menu.
AM
01/01/2012
DST
E
E
To advance through the menu, touch the Mode section.
To backup in the menu, touch the Fan section.
To exit the menu at any time and save changes, touch and hold the Mode
section until the display shows normal operation.
21
INSTALLER SETUP MENU
SELECTING THE PROGRAM
The first menu 1:PR selects programmable or non-programmable operation. Press the
UP DOWN 4
or arrows to change the selection. The factory default is (4 schedules per
day).
Back Next
0 = Manual Mode (non-programmable) 2 = 2 Schedules Per Day (Day / Night) 4 = 4 Schedules Per Day (Morning / Day / Evening / Night
Program
Morning Day
Evening Night
22
E
INSTALLER SETUP MENU
SELECTING PROGRAM DAYS
If menu 1:PR is set to 2 or 4, 2:PD is used to select 5+2 programming or 7 day programming. Touch the or arrows to change the selection. The factory default is .
7
UP DOWN
E
Back Next
51 = 5+1+1 (Same schedule Mon-Fri and separate
schedules for Sat and Sun) 52 = 5 + 2 (Same schedule Mon-Fri and Sat-Sun) 7 = 7 (7 individual day programming)
23
INSTALLER SETUP MENU
SELECTING TEMPORARY PROGRAM OVERRIDE
Menu 3:TH provides temporary program override. When , (factory default) a change in setpoint will remain until the next scheduled event or a fixed override can be set from 1-12 hours. Use the or arrows to select override time.
UP DOWN
OFF
Back Next
OFF = Provides override to next scheduled event 1-12 = Override to selected time (1 - 12 hours in 1 hour
increments)
Program
24
E
INSTALLER SETUP MENU
SELECTING PROGRAMMABLE FAN MODE
Menu 4:PF is the Programmable Fan option which allows selecting continuous or auto fan operation for each program event. The factory default is . Use the or arrows to select Programmable Fan.
OFF UP DOWN
Back
ON = Programmable Fan OFF = No Programmable Fan
Refer to the User Manual for selecting continuous or auto fan for each
scheduled event when the Programmable Fan option is ON.
Program
Next
25
E
INSTALLER SETUP MENU
SELECTING MODE
Menu 5:FN selects the mode of operation. The factory default is for auto changeover. Touch the or arrows to change the selection.
UP DOWN
A
Back
-=Manual Changeover A = Auto Changeover (Heat / Cool / Auto / Off H = Heat / Off C =Cool / Off Ao = Auto / Off
Note: In Manual Changeover configuration the
heating and cooling setpoint can be the same.
26
Next
AUTO
E
INSTALLER SETUP MENU
SELECTING TOUCHSCREEN LOCK OPTIONS
Menu 6:LC allows you to prevent changes to all or part of the touchscreen functions. The factory default is . Touch the or arrows to change the selection.
OFF UP DOWN
Back
OFF = All functions unlocked 6 = Fan / Mode locked 1 = Program locked 7 = Fan / Program / Mode locked 2 = Mode locked 8 = Fan / Program / Mode / Clock 3 = Fan locked locked 4 = UP / DOWN arrows locked 9 = All functions locked 5 = Clock locked
27
Next
E
INSTALLER SETUP MENU
SELECTING THE COOLING SETPOINT LIMIT
Menu 7:CL selects the minimum cooling setpoint. The factory default is . Touch the
UP DOWN
or arrows to adjust the limit from 43° - 122°F.
Set
50
Back
28
Next
E
INSTALLER SETUP MENU
SELECTING THE HEATING SETPOINT LIMIT
Touch the or arrows to adjust the limit from 41° - 120°F.UP DOWN
Heat
90Menu 8:HL selects the maximum heating setpoint limit. The factory default is .
Set
Back
29
Next
E
INSTALLER SETUP MENU
SELECTING THE TEMPERATURE DISPLAY
Menu 9:TD selects the temperature to be displayed in Fahrenheit or Celsius. The factory default is (Fahrenheit). Touch the or arrows to change the
display setting.
F
UP DOWN
Back
F = Fahrenheit C = Celsius
30
Next
E
INSTALLER SETUP MENU
SELECTING THE TIME FORMAT
Menu 10:CL selects the time format which can be 12 hour or 24 hour. The factory deault is (12 hour). Touch the or arrows to change the format.UP DOWN
12
Back
12 = 12 Hour 24 = 24 Hour (Military Time)
31
Next
E
INSTALLER SETUP MENU
SELECTING THE SETPOINT DISPLAY OPTION
Menu 11:ST allows the option of continuously displaying the setpoint temperture with the space temperature or only the sepoint temperature. The factory default is (Setpoint Displayed). Touch the or arrows to change the display option.UP DOWN
Set
ON
Back
ON = Setpoint displayed OFF = No sepoint displayed
32
Next
E
INSTALLER SETUP MENU
SELECTING BACK LIGHT OPTION
the or arrows to change the display option.UP DOWN
ONMenu 12:BL allows you to select the back light option. The factory default is . Touch
Back
ON = Back Light on for 10 seconds when screen is touched OFF = No Back Light ALL = Back Light on high for 10 seconds when screen is touched and then low continuously. (Thermostat must be hardwired to 24VAC for this option)
33
Next
E
INSTALLER SETUP MENU
SELECTING ADAPTIVE RECOVERY OPTION
Menu 13:RC allows you to select the Adaptive Recovery option when the thermostat is configured as programmable. Adaptive Recovery compares the space temperature deviation from setpoint and rate of recovery history to bring the equipment on and reach the setpont at the scheduled start time. The factory default is . Touch the
or arrows to select this option.UP DOWN
OFF
Back
OFF = No Adaptive Recovery ON = Adaptive Recovery On (For programmable mode only)
34
Next
E
INSTALLER SETUP MENU
SELECTING FILTER REMINDER
Menu 14:FT allows you to select a time when the thermostat will display as a reminder that the HVAC system filter(s) should be replaced. The factory default is .
Touch the or arrows to set the filter reminder time.UP DOWN
FLT
OFF
Back
OFF = No filter reminder 010 = 100 Hours 100 = 1000 Hours (Up to 9,000 hours in 100 hour steps)
To reset the Filter Reminder, touch and hold Mode and Fan.
35
Next
E
INSTALLER SETUP MENU
SELECTING FIRST STAGE HEATING AND COOLING DIFFERENTIAL OPTION
Menu 15:S1 is used to adjust the heating and cooling differential. The factory default is
2
( 2 This represents the temperature above the cooling setpoint or below the
°F).
heating setpoint when the equipment is energized.
to change the differential.
Touch the or arrows
UP DOWN
Back
1 = 1°F Differential 2 = 2°F Differential 3 = 3°F Differential
36
Next
E
INSTALLER SETUP MENU
SELECTING SECOND STAGE HEATING AND COOLING DIFFERENTIAL OPTION
Menu 16:S2 is used to adjust the second stage heating and cooling differential. The factory default is ( 2 This represents the temperature above the first stage cooling differential or below the first stage heating differential when second stage is energized. There is a 3 minute time delay before second stage is energized.
or arrows to change the differential.UP DOWN
2
°F).
Touch the
Back
Adjustable from 1 - 10°F in 1° increments
37
Next
E
INSTALLER SETUP MENU
SELECTING THIRD STAGE HEATING DIFFERENTIAL OPTION
Menu 17:S3 is used to adjust the third stage heating differential. The factory default is
2
( 2 This represents the temperature below the second stage heating differential
°F).
when third stage heat is energized. There is a 3 minute time delay before third stage heat is energized.
Touch the or arrows to change the differential.UP DOWN
Back
Adjustable from 1 - 10°F in 1° increments
38
Next
E
INSTALLER SETUP MENU
SELECTING INTERNAL OR INDOOR REMOTE SENSOR CALIBRATION OPTION
Menu 18:CA is used to re-calibrate the thermostat internal sensor when 19:TT = OFF, or a single remote indoor sensor when 19:TT = RS . Touch the or arrows to
adjust the calibration. The factory default is .
0
UP DOWN
Back
Adjustable from -9° to +9°F in 1° increments
39
Next
E
INSTALLER SETUP MENU
SELECTING REMOTE SENSOR OPTION
Menu 19:TT allows you to select indoor remote sensor only or remote sensor with internal sensor for temperature averaging. The factory default is . Touch the
or arrows to select the desired remote sensor option.
DOWN
OFF
UP
Back
OFF = Internal sensor only RS = Indoor remote sensor only AU = Internal sensor with indoor remote sensor
40
Next
E
INSTALLER SETUP MENU
SELECTING EQUIPMENT CONFIGURATION
Menu 20:R4 is used to select the specific equipment configuration. The factory default
1S H2
is for Heat / Cool and for heat pump and fossil fuel. Touch the or arrows to select the proper equipment configuration.
UP DOWN
HEAT / COOL
1S2S= Single Stage
= Multi-stage
Back
HEAT PUMP
= 1 Heat / 1 Cool
OFF
= 2 Heat / 1 Cool
H2
= 3 Heat / 2 Cool
H3
41
Next
FOSSIL FUEL
H2H3= 2 Heat / 1 Cool
= 3 Heat / 2 Cool
E
INSTALLER SETUP MENU
SELECTING LOW BALANCE POINT OPTION
Menu 21:LB allows you to select a low balance point setting when the thermostat is configured for Heat Pump or Fossil Fuel. When the outdoor temperature falls below the balance point setting, the compressor is locked out and only auxiliary electric heat or fossil fuel furnace is used for heating. The factory default is . Touch the or
DOWN
arrows to select an low balance point setting.
OFF
UP
Back
Adjustable from OFF, 1° to 77°F
Remote outdoor sensor must be used
42
Next
E
INSTALLER SETUP MENU
SELECTING HIGH BALANCE POINT OPTION
Menu 22:HB allows you to select a high balance point setting when the thermostat is configured for Heat Pump or Fossil Fuel. When the outdoor temperature rises above the balance point setting, the auxiliary electric heat or fossil fuel furnace is locked out and only the heat pump is used for heating. The factory default is . Touch the
or arrows to select an low balance point setting.
DOWN
OFF
UP
Back
Adjustable from OFF, 32° to 122°F
Remote outdoor sensor must be used
43
Next
E
INSTALLER SETUP MENU
SELECTING AUDIBLE BEEP OPTION
Touch the or arrows to change the setting.UP DOWN
ONMenu 23:BP allows you to turn the audible beep on or off. The factory default is .
Back
ON = Audible beep when screen is touched OFF = No audible beep
44
Next
E
INSTALLER SETUP MENU
SELECTING THE FACTORY DEFAULT OPTION
Menu 24:RS can be used to reset the thermostat to the original factory defaults. The factory default is . To reset the thermostat, touch the or arrows and
set to .
ON
OFF
UP DOWN
E
Back
OFF = Factory default disabled ON = Factory default enabled
45
Next
INSTALLER SETUP MENU
SELECTING DAYLIGHT SAVINGS TIME OPTION
Menu 25:DS is used to enable Daylight Savings Time for the real-time clock. The factory default setting is . To disable this option, use the or arrows and set to
.
OFF
ON
UP DOWN
Back
ON = Daylight Saving Time OFF = Daylight Saving Time disabled
Refer to User Manual to set Daylight Saving Time Calender
46
Next
E
REMOTE SENSOR INSTALLATION
REMOTE SENSORS
There are two types of remote sensors. The T-32-S1 is a single sensor that can be used indoors or outdoors. TheT-32-S2 contains two sensors. A combination of both sensors can be used for indoor temperature averaging with or without the onboard sensor. Use separate 18-2 shielded cable when wiring sensors to prevent interference.
INDOOR SENSOR WIRING
When the T-32-S1 is used as an indoor sensor, theT-32-TS can be configured to allow only the remote sensor to control the temperature or a combination of remote and onboard sensors can be used for temperature averaging. Refer to 18:TT in the installer setup menu to select the proper remote sensor option. The indoor sensor wires to terminals S1 and SC.
S2 SC S1
47
FIGURE 5
T-32-S1
SENSOR
REMOTE SENSOR INSTALLATION
Locate the sensor in the same manner as the thermostat. Mount the sensor 18”away from any outside wall. Do not install the sensor behind doors, in corners or other dead air spaces. Keep the sensor away from direct air flow, supply registers or near sources of heat such as lamps and appliances. The maximum wire length from the sensor to the thermostat is 300 feet. Use a separate 18-2 shielded cable for sensor wiring. Prior to wiring the sensor to the thermostat, use an ohm-meter or multi-meter to measure the resistance of the sensor. Measure at the end of the wires that will connect to the thermostat. Confirm the resistance value (within 5%) to the temperature where the sensor is mounted. Use a quality digital electronic thermometer to read the temperature at the sensor. Remove the sensor cover and place the thermometer probe next to the sensor element to verify an accurate reading. Disconnect power to the thermostat when wiring the sensor, strip only as much insulation off of the wires as necessary to provide a good contact with the terminals. The sensor is not polarity specific so either sensor lead may be connected to the SC or S1 terminals on the thermostat.
48
REMOTE SENSOR INSTALLATION
USING MULTIPLE SENSORS FOR TEMPERATURE AVERAGING
Multiple indoor remote sensors can be wired in series/parallel for temperature averaging. The total value of the sensors must equal 10KΩ @ 77° F. The onboard sensor is not part of the equation even if it is configured as part of the averaging circuit. However, when the onboard sensor is used with remote sensors, it represents 50% of the averaging value. Figure 6 illustrates two T-32-S2 sensors used for averaging.
S2 SC S1
SENSOR
49
T-21-S2
FIGURE 6
T-21-S2
SENSOR
REMOTE SENSOR INSTALLATION
OUTDOOR SENSOR WIRING
When the T-32-S1 is used as an outdoor sensor, theT-32-TS thermostat will display the outside air temperature as well as control high and low balance points for heat pump and fossil fuel systems. Refer to 18:TT in the installer setup menu to select the proper sensor option. The outdoor sensor wires to the SC and S2 terminals on the thermostat. Figure 7 illustrates both an indoor and outdoor sensor configuration. Mount the sensor on a vertical exterior surface below an overhang. Choose a location protected from direct sunlight and exposure to excessive moisture. Follow the same wiring procedures as installing an indoor sensor.
FIGURE 7
S2 SC S1
INDOOR SENSOROUTDOOR SENSOR
T-32-S1
SENSOR
50
T-32-S1
SENSOR
TEMPERATURE CALIBRATION CHART
Temperature Resistance Temperature Resistance
(°F) (K ) ( F) (K )ΩΩ
30 34.6 70 11.9
40 26.1 80 9.4
50 19.9 90 7.4
60 15.3 100 5.9
NTC type 2 sensor - 10K @ 77° FΩ
51
TESTING
The T-32-TS incorporates a short-cycle timer which can be disabled during testing by setting slide switch 3 to the ON position. Once testing is completed, the time should be enabled by setting the switch to OFF.
TESTING FAN OPERATION
Touch until the word is displayed. Touch until the words
MODE OFF FAN Always On
appear. After a brief moment, the internal fan relay ‘G’ will energize and the system fan should operate. Touch again until the word appears. After a brief moment, the internal fan relay will de-energize and the system fan will shut off.
TESTING CONVENTIONAL HEATING AND COOLING OPERATION
Touch until the word appears. Touch the arrow and raise the setpoint
MODE Heat UP
above the space temperature and the first stage differential. After a brief moment, the internal heating relay‘W1’ will energize and the heating system should operate. The word will flash continuously. If the thermostat has been configured for two stage
Heat
heating, raise the setpoint above the second stage differential and the second stage heating relay‘W2’ will energize. The word will flash twice, pause and repeat the sequence to indicate second stage has been energized.
FAN Automatic
Heat
52
TESTING
Touch until the word appears. Touch the arrow and lower the
MODE Cool DOWN
setpoint below the space temperature and the first stage cooling differential. After a brief moment, the internal heating relay‘Y1’ will energize and the cooling system should operate. The word will flash continuously. If the thermostat has been configured for two stage cooling, lower the setpoint below the second stage differential and the second stage cooling relay‘Y2’ will energize. The word will flash twice, pause and repeat the sequence to indicate second stage has been energized.
TESTING CONVENTIONAL HEAT PUMP OPERATION
When the T-32-TS is configured for conventional heat pump operation, testing is the same as a heating and cooling system with the exception that the fan‘G’relay is always energized with compressor, auxiliary and emergency heat calls.
TESTING FOSSIL FUEL OPERATION
When the T-32-TS is configured for fossil fuel operation, testing is the same as a conventional heat pump system with the exception that the heat pump is never allowed to run when the fossil fuel furnace is energized. Whenever the thermostat calls for auxiliary heat, the compressor Y1 and/orY2 relays are de-energized along with the fan ‘G’ relay and the ‘W1’relay will energize the fossil fuel furnace.
Cool
Cool
53
TESTING
With the installation of an outdoor sensor, both high and/or low balance point control can be used to prioritize heat pump or fossil fuel operation based on a selected outdoor temperature.
TESTING LOW BALANCE POINT (Heat Pump or Fossil Fuel)
When an outdoor sensor is used with the T-32-TS, Installer Option 21:LB allows you to select a low balance point temperature. When the outdoor temperature falls below the low balance point setting, the Y1 and/or Y2 compressor relays will be bypassed and only the W1 (auxiliary heat) relay will be energized.To test the low balance point setting, set 21:LB the displayed outdoor temperature and force a call for heating. TheW1 relay will energize and the compressor Y1 and/or Y2 relays will be bypassed. After testing, reset the low balance point temperature to a normal operating range.
TESTING HIGH BALANCE POINT (Heat Pump or Fossil Fuel)
High balance point is designed to prevent the W1 (auxiliary heat) relay from energizing when the outdoor temperature is above the balance point setting.To test the high balance point setting, set 22:HB in the installer options menu the displayed outdoor temperature and force a call for heating by adjusting the thermostat setpoint
above
below
54
TESTING
above the first and/or second stage heating differential.The Y1 and/or Y2 compressor relays will be energized and the W1 (auxiliary heat) relay will be bypassed. After testing, reset the high balance point temperature to a normal operating range.
ADAPTIVE RECOVERY
Adaptive Recovery is only available in programmable mode (Installer Options Menu 13:RC = ON). The Adaptive Recovery function of the T-32-TS permits the user to program a time that a desired set temperature is required. The thermostat then calculates the most energy efficient time to energize the equipment to reach the setpoint at the designated time. The calculation involves a complex control algorithm that compares the space temperature deviation from setpoint and rate of recovery history.
55
BASIC TROUBLE SHOOTING
SYMPTOM POSSIBLE FAULT AND REMEDY
No LCD display If thermostat is battery powered only, remove battery
compartment and check to see that the positive (+) and negative (-) ends of each battery are oriented properly. If thermostat is hardwired, remove the thermostat from the subbase and check for 24 Volts across terminals ‘C’ and‘R’. If no voltage, fault could be equipment or wiring related.
Thermostat can In the Installer Options menu, set 5:FN=A or AO for not be set for auto changeover. auto changeover - = Manual Changeover
A = Heat / Cool / Auto / Off H = Heat / Off C = Cool / Off AO = Auto / Off
Temperature display Air from wall cavity may be leaking into rear of is inaccurate thermostat. Seal hole where wires enter subbase. Move
lamps or other sources of heat away from thermostat.
56
BASIC TROUBLE SHOOTING
SYMPTOM POSSIBLE FAULT AND REMEDY
Thermostat will not No outdoor sensor installed. Check wiring at outdoor sensor display outdoor and sensor terminals on thermostat subbase. Outdoor temperature sensor wires to terminals S2 and SC.
Heat or Cool is flashing This is not a fault but indicates that the thermostat heating
or cooling relay is energized.
Lock icon is displayed This is not a fault. The thermostat heating and cooling limits when attempting to may be preventing setting a temperature above or below set a higher or lower the limit values. These values can be changed in the Installer setpoint Options menu.
7:CL (Cooling Limit) can be set from43 - 122 F.
8:HL (Heating Limit) can be set from 41 - 120 F.
Touchscreen lock option 6:LC may be set to 4 which prevents setpoint changes.
57
°°
°°
BASIC TROUBLE SHOOTING
SYMPTOM POSSIBLE FAULT AND REMEDY
Thermostat displays The T-32-TS can be configured to display temperature in wrong temperature either Fahrenheit or Celsius. Check Installer Option menu
9:TD. F = Fahrenheit and C = Celsius.
The fan continues to The thermostat fan mode may be set to Always On. Touch the run after a heating or FAN icon and change it to Automatic. When the T-32-TS is cooling call is satisfied configured for programmable operation, fan operation can
be programmed for Automatic or Always On for any scheduled event. If the Programmable Fan feature is not required, set 4:PF in the Installer Option menu to OFF.
Some functions on the Lock values have been set. Refer to 6:CL in the Installer Option thermostat cannot be menu. To remove all lock values, set 6:CL = OFF. changed and a padlock icon is displayed
58
T-32-TS SPECIFICATIONS
Input Voltage (Hardwired) 20-30 VAC 50/60 Hz Relay Rating 24 VAC @ 1 Amp maximum per relay Battery Power (2) AAA 1.5 V Operating Temperature 32° F to 150° F Operating Humidity 0-95% (non-condensing) Storage Temperature 32° F to 150° F Size:
Enclosure 5.0” W x 3.375” H x 1.0” D
LCD Display 3.75” W x 2.125” H Back Light LED Short-cycle Delay Off or 3 minutes Displayed Temperature Resolution 1° F Setpoint Ranges:
Heating 41° F - 120° F
Cooling 43° F - 122° F Limits:
Heating (Factory default = 90° F) Fully adjustable within heating setpoint range
Cooling (Factory default = 50° F) Fully adjustable within cooling setpoint range Onboard and Remote Sensors NTC Type 2
Resistance 10K @ 77 F
Tolerance +/- 3% @ 77 F Warranty 5 Years
Ω°
°
59
INDIANAPOLIS, IN 46203 www.jacksonsystems.com
06-1097-080212
Loading...