Jackson Systems Comfort System Z-300-HC Installation Instructions Manual

ZONE 1
CALLING
Comfort System
TM
Installation Instructions for Z-300-HC Zone Control Panel
Heat / Cool Auto Changeover - Cooling Priority
POWER
HEAT
COOL
FAN LED INDICATES
WHEN A
THERMOSTAT IS
CALLING FOR FAN.
ZONE 2
CALLING
ZONE 3
CALLING
COOLING PRIORITY
WYG RX
WYG RC
SINGLE STAGE
HEAT / COOL
THERMOSTAT
WYG RXDD
123456
ZONE 1
DD
DAMPER MOTOR
0.36 AMPS 10 VA
T5
ZONE 2
WYG RXDD
D
Installation Notes:
To install the panel, first slide the PC board out of its base and screw the base to a flat surface next to the HVAC equipment. The PC board should be reinstalled by centering it over the base and pushing firmly.
The control panel requires a separate 24 Volttransformer.
No special wire is required.
The thermostat and motorized dampers may be located up to 300 feet from the control panel when using 18 gauge thermostat wire.
The left fuse (4 Amp) protects the relay contacts. The right fuse (4 Amp) protects the printed circuit board.
Zone dampers are powered closed / spring return open.
If condensing unit is not equipped with short cycle protection timer, (TD-5) should be installed.
The two wires from the condensing
Comfort System™
Z-300-HC
PATENTED 5,944,098
ZONE 3
WYG RXDD
WIRE THE SAME
AS ZONE 1
unit should be connected to the ‘Y’ and transformer common terminals at the furnace.
The low limit (FS-38) should be wired to the ‘LL’ terminals on the panel (remove jumper). The compressor will shut off when low limit trips out.
The high limit (HL-170) should be wired to the ‘HL’ terminals on the panel (remove jumper). The furnace will shut off when high limit trips out.
A 40 VA transformer will power the panel and up to four (4) dampers. A 75 VA transformer will power the panel and up to seven (7) dampers.
Up to three (3) dampers can be connected in parallel. A total of no more than seven (7) dampers may be connected to the system. A system may be a single panel or multiple panels.
If more than three (3) zones are required, two additional panels can be used to control up to a total of nine (9) zones. T5 terminal strip is used only when more than three zones are required.
WYG R HXLL LL HL HL
WYG RC
HVAC UNIT
TERMINAL
STRIP
HVAC UNIT
JUMPERS
LOW
LIMIT
HIGH LIMIT
FAN
4 AMP
4 AMP
CONTACTS
4 AMP FUSES
HXW Y G R LL LL HL HL
120/24 VAC
TRANSFORMER
PC BOARD
WHEN GREEN ZONE
LEDS ARE ON, THOSE
ZONES ARE CALLING
FOR HEATING OR COOLING
Label the dampers, damper wires and thermostat wires with the zone number and the area they serve.
Specifications:
Panel Dimensions: Height: 5.0 inches Width: 10.0 inches Depth: 2.0 inches
Mounting: 2 back plate screws
OperatingAmbientTemperature:
-20° to 160° F
Power Supply: 24 Vac 40VA/ 75 VAtransformer
Terminal Designations:
W = Heat Y = Cool G = Fan R = Hot 24Volt X = Common D = Damper LL = Freeze Stat HL = High Limit H = Hot 24Volt X = Ground or Common
Zone Control Made Simple™
5418 Elmwood Avenue, Indianapolis, IN 46203-6025 Toll Free: 888.652.9663 Fax: 317.227.1034 www.jacksonsystems.com
Comfort System
TM
Installation Instructions for Z-300-HC Zone Control Panel
Heat / Cool Auto Changeover - Cooling Priority
Sequence of Operation:
Comfort System™ is a residential / light commercial zone control system that allows a single HVAC unit to have upto three separate zones (nine if three panels are connected together). Each zone is controlled by its own space thermostat and motorized zone damper. If any of the zone thermostats call for heating or cooling, the zones not calling will have their dampers powered closed, and the zone(s) calling will have its (their) damper(s) remain open. The heating or cooling equipment will also be brought on at the same time. When all zone thermostats are satisfied, the heating or cooling equipment turns off and all zone dampers return to the open position to allow for continuous air circulation.
If one of the zone thermostats is calling for heating and another zone thermostat is calling for cooling, the cooling thermostat will take priority and the system will operate in the cooling mode. When the thermostat that is calling for cooling is satisfied, the system will change over and take care of the heating requirement. This is referred to asAuto Changeover - Cooling Priority
Thermostats:
COMFORT SYSTEM™
PANEL
TRANSFORMER
24 VOLT 40VA
FURNACE
Typical System Layout
ZONE 2
STAT
ZONE DAMPER 2
MIGHT SERVE
BEDROOM AREA
ZONE 1
STAT
ZONE DAMPER 1
MIGHT SERVE
LIVING AREA
The zone control system works with standard, single­stage, heat / cool thermostats. The thermostats can be either manual or auto changeover.
System Checkout
Verify that all wires have been connected to the proper terminals and are secure.
Verify that the jumpers across the ‘LL’ and ‘HL’ terminals were removed before connecting the high and low limits.
The low limit (FS-38) should be wired to the ‘LL’ terminals on the zone control panel. The high limit (HL-170) should be wired to the ‘HL’terminals on thezone control panel.
Zone dampers are powered closed and spring return open. There will be no power on the panel damper terminals marked ‘D’ and ‘D’ when the damper is in the open position.
When a green zone LED is on, the zone is calling for heating or cooling.
To check the system for proper operation, pull the disconnect for the condensing unit to prevent short cycling. Next, place all the zone thermostat mode switches in heat mode and turn down all thermostat set points. Go to each zone thermostat, one at a time, and call for heat to verify that the proper zone dampers are open (and the rest are closed). Turn the zone thermostat back down before checking the next zone.
Zone Control Made Simple™
5418 Elmwood Avenue, Indianapolis, IN 46203-6025 Toll Free: 888.652.9663 Fax: 317.227.1034 www.jacksonsystems.com