![](/html/ce/ce4e/ce4e57734c9952469cef6a5e6b279421889553d19edc677f0f6c4c1d6b040446/bg1.png)
The SD-503ST Stand-alone combined smoke and heat
Most false alarms are caused by improper detector
detector
The SD-503ST is used to detect fire hazards in the interior of
residential or commercial buildings. The detector can be installed in
mobile homes or caravans. The product is not designed to be installed
in industrial premises.
The detector indicates a fire hazard using the built-in LED indicator
and acoustic signalling.
The SD-503ST consists of two independent detectors – an optical
smoke detector and a heat detector. The optical smoke detector works
on the principle of scattered light. It is very sensitive to large dust
particles which are present in dense smoke. It is less sensitive to
smaller particles generated by the combustion of liquids such as
alcohol. That is why the fire detector also contains a built-in heat detector
which has a slower reaction but is much better at detecting fire which
generates only a small amount of smoke.
Detector range and location
The smoke detector must be installed so that any smoke easily drifts
into the detector owing to natural thermal currents, e.g. on the ceiling. It
is suitable for residential buildings but not suitable for free spaces,
outdoor environments or interiors with extremely high ceilings (above
5 m) where fire by-products can disperse over a large area – the
smoke would not reach the detector position.
The detectors should be installed by a trained technician with a valid
manufacturer’s certificate.
Detectors should be installed in the building according to the project
documentation. If such documentation is not available, the detector
positions should comply with the effective standards for fire alarm
signalling systems.
The detector must always be placed in the section leading to the exit
of the building (escape route), see Fig. 1. If the building has a floor
area greater than 150 m
other suitable place is required, see Fig.2.
2
, installation of an additional detector in some
1. kitchen,
2. living room,
3. – 6. bedrooms
/ / basic
coverage
/ / recommended
coverage
Installation on sloping ceilings
If the ceiling is not suitable for mounting on a level surface (e.g. a
room under a roof ridge), the detector can be installed as in Fig. 5.
g. 4
Fi
centre of the room, best location
acceptable location
Fig. 5
Walls, partitions, barriers and lattice ceilings
The SD-503ST detector must not be installed closer than 0.5 m
from any wall or partition. A narrow room with a width of less than 1.2 m
requires the detector(s) to be placed at a distance of at least one third of the
room’s width away. In a case when a room is separated into sections with
furniture, racks or semi partition walls which do not reach the ceiling, the
space is considered to be fully separated if the gap between the top of
these and the ceiling does not exceed 0.3 m. A free space of at least 0.5 m
is required under and around the detector. Any irregularities of the ceiling
(e.g. girders) exceeding 5 % of the ceiling height should be considered a wall
and the above mentioned limitations should apply.
Ventilation and air circulation
The detectors must not be installed directly by ventilation or air
conditioning vents. In the case of air being supplied through a
perforated ceiling, each detector must be placed so that no perforation
hole occurs within 0.6 m of the detector.
Avoid installing the detector in the following locations:
• places with poor air circulation (niches, corners, apexes of Ashaped roofs, etc.)
• places exposed to dust, cigarette smoke or steam
• places with over-intense air circulation (close to ventilators, heat
sources, air conditioning outlets, etc.)
• in kitchens and other cooking places (because steam, smoke or oily
fumes can cause false alarms or reduce detector sensitivity).
• beside fluorescent lights or energy-saving light bulbs (electrical
interference can cause a false alarm)
• in areas with lots of small insects
Warning:
location.
See CEN/TS 54-14 standards for detailed installation guidelines.
Installation
When installing the detector, abide by the procedures recommended
in the previous paragraphs.
In multi-storey flats and family houses the detector should be
installed above the stairs. It is recommended to place additional
detectors in rooms where people sleep. See Fig 3.
Installation on level ceilings
Place the detector in the centre of the room if possible. The detector
must not be recessed into the ceiling due to the possible existence
of a cool air layer on the ceiling. Never place the detector in the
corner of the room (always keep at least 0.5 m distance from the
corner - see Fig 4). There is an insufficient circulation of air in the
corners.
The SD-503ST stand-alone combined smoke and heat detector MLW55503
1– detector cover opening; 2 – detector cover closing; 3 – optical status
Fi
g. 6:
signalling (red LED); 4 – arrow showing where to insert the detector;
1. Open the detector cover, by turning it anti-clockwise (1)
2
.
Attach the plastic base to the selected place using screws
3. Use t
see the table below
5 – configuration terminals; 6 – battery holders;
he terminals (5) to set the required detector function –
![](/html/ce/ce4e/ce4e57734c9952469cef6a5e6b279421889553d19edc677f0f6c4c1d6b040446/bg2.png)
1
Note: Although this product does not contain any har mful materials we
Memory enabled
3 ON
Smoke (EN 14604) or heat
(EN 54-5)
Heat only (EN 54-5) (no
smoke)
(no heat)
same time (both conditions
When the detector is installed in caravan trailers, use only the “smoke
only“ or “both smoke and heat” settings.
4. Insert the batteries (3 X AA, alkaline 1.5 V)
5. Close the detector cover. The detector can be inserted into the
astic base in one position only. The correct position is marked
pl
with arrows on both plastic parts (4).
Note: Detector cover closing is blocked unless all 3 batteries are
inserted!
The mounting base must not be replaced by bases meant for
detectors without the test button consisting of pressing the body
of the detector.
Fire alarm
A fire alarm is signalled both acoustically and optically.
When the conditions for fire alarm triggering are met (smoke is
detected in the room, the alarm temperature is reached, or both), the
detector signals the danger by sounding the siren and quickly flashing
the LED indicator (3).
Silencing the siren during an alarm: The siren can be silenced
by pressing the detector body against the base. The siren is then silent
for 10 minutes. If the detector still detects smoke or heat then, the
siren is reactivated.
When the need arises (e.g. in the case of a detector failure), it is
possible to postpone siren reactivation by up to 12 hours. This can be
done by pressing the detector again for 5 s after silencing the siren.
When the detector chirps, you have to release the pressure within 1s.
The switchover to the postponed siren mode is confirmed with 5
chirps. The detector LED flashes all the time during the postponement.
Alarm memory: If it is enabled, alarm indication continues even
when the smoke clears or when the temperature decreases. The slowflashing indication lasts 24 hours unless it is terminated by pressing
the detector body.
Detector testing
The detector should be tested at least once per month. To test
the detector press its body against the base and wait until the LED
indicator starts flashing. The LED flashing signals switchover to test
mode. The LED flashes for the whole duration of the test. When the test
is complete, the LED switches off. The detector then signals the result. If
the detector chirps once, no problems have been detected. If a fault is
discovered, the LED flashes three times. The detector flashes once
without acoustic indication if the test is finished and a low battery is
detected. If the battery is low, there is no acoustic signalling
The complete function of the detector can be tested with a testing
spray (e.g.. SD- TESTER) or hot air (e.g a hair dryer).
Warning: never test the detector with fire.
Fault indication
The detector checks its functioning. If it discovers a fault, it beeps
and flashes three times simultaneously, and then flashes three times
every 30 s.
A detector test can be carried out when a fault is signalled. To test the
detector, press its whole body against the base. During test the detector
checks whether the fault still exists. The LED flashes during the testing.
When the test is completed, the LED stops flashing and then signals the
result. A persistent fault is signalled by 3 flashes and 3 beeps. If the fault
has been removed, the detector chirps briefly.
If you have not managed to repair the fault, the detector must be sent to
a service centre.
Battery replacement
The detector checks the battery status and if the batteries are
running low, the detector signals that they need replacing by short
flashes every 30 s. Replace the batteries as soon as possible. Always
replace all three batteries with the same type and manufacturer.
Note: For the best possible operation we strongly recommend using
only batteries supplied by Jablotron’s authorized distribution (avoid
usage of so called no-name batteries).
Do not throw used batteries into ordinary household waste.
Deposit them at authorized collection points.
Technical specifications
Power 3 x alkaline batteries AA (LR6) 1.5 V
Typical battery lifetime approx. 3 years
Smoke detection optical light scattering
Smoke detector sensitivity m = 0.11 - 0.13 dB/m pursuant to EN 14604:2005
Heat detection class A1 according to EN 54-5
Alarm temperature +60 °C to +65 °C
Operating temperature range -10 °C to +65 °C
Dimensions, weight diameter 126 mm, height 52 mm, 150 g
Conformity EN 50130-4, EN 55022
14
1293
JABLOTRON ALARMS a.s. hereby declares that the SD-503ST detector is in comp liance
with the essential requirements and other relevant provisions of Regulation 2011/305/EU,
2011/65/EU and Directive 2004/108/EC. The original of the conformity assessment can be
found at www.jablotron.com
suggest you return the product to the dealer or directly to the producer after
use. For more detailed information visit
- Technical Support section
Please note: Batteries are not included
1293-CPR-0390
www.jablotron.com.
The SD-503ST stand-alone combined smoke and heat detector MLW55503