Page 1
The JA-120N BUS module for electric door locks
The product is a component of the JABLOTRON 100 system. It serves for powering and controlling electric door locks and access control units from the system BUS. During lock operation the included batteries supply enough current to open an electric lock, during the leading edge of the current pulse. The JA-120N can be mounted practically in any place where it is difficult to install an external power supply to control an electric lock.
This module reacts to control panel PG outputs or it can be activated by a release key connected to the IN terminal. The module is supplied inside a JA-190PL installation box.
It should be installed by a trained technician with a valid certificate issued by an authorised distributor.
Figure 1: 1 – rechargeable batteries; 2 – DOOR output indicator,
3 – JA-100 BUS activity indicator; 4 – IN input activation indicator;
1. We recommend removing the module’s PCB to avoid
unwanted damage during installation. Punch the holes into the JA-190PL rear plastic part for cables. Insert the BUS cables and attach the plastic base onto the required place using screws.
2. Put the PCB back onto the plastic base. Connect the BUS
wires to the BUS terminals (6) and the cables for door lock control to the I/O terminals (7). Always use CC-01 (Jablotron) cable for connecting to the control panel. For connection of the door lock or the external power supply use cables with an adequate cross-section.
Terminal descriptions: DOOR +12V output for electric lock control
COM, IN Input terminals serving for activation by the
GND Common terminal for an external power supply
+12V Input terminal for an external power supply
3. Proceed according to the control panel installation manual.
Basic procedure: a. When the system has been turned on then the yellow
b. Using F-Link software, select the required position in the
||
|
c. Press the
4. Put the cover on the module.
Installation
5 – LEARN (enrollment)/ tamper contact; 6 – BUS terminals;
7 – input and output terminals (I/O)
When connecting the module to the system BUS, always switch the power off.
release button (reaction NO/NC).
and for electric door lock control
(the DE 06-12 is recommended)
LED (3) flashes and it indicates the module has not been enrolled to the system yet.
Devices window and launch enrollment mode by clicking on the Enroll option.
LEARN/TAMPER (5) button in the module –
the module is thus enrolled to the system and the yellow LED indicator goes off.
Minimum PG switching time – Sets the minimum switching time of the DOOR output regardless of the PG output impulse length.
Maximum PG switching time – Sets the maximum switching time of the DOOR output regardless of the PG output impulse length. When the IN input is triggered the DOOR output is always switched on for that predefined time.
Note: the minimum switching time can´t be set to a higher value than the maximum value. The F-link software adjusts its offer of those parameters dynamically.
IN input options: Disabled The module doesn´t react to IN input
activation
Manual control Triggering the IN input switches on the
DOOR terminal for a predefined time according to the Maximum PG switching time
System Triggering the IN input causes the control
panel to react according to the reaction set at the module’s position in F-link (Reaction column)
IN input inverted: Determines the logic of the IN input NC/NO. The input is not balanced and is set to NO as a factory default (option disabled).
DOOR input inverted: This option inverts the logic of the DOOR output for e.g. reverse locks. When the option is checked and the input is in standby a voltage occurs on the DOOR output.
Note: for correct functioning it is necessary to power the module from an external power supply (for instance: the DE 06-12).
Blocking the IN input by section: This option can block the IN input by setting the section to which the module has been enrolled. The option is only available if Manual control of the IN input has been enabled.
Function button during communication fault: This option keeps the module active, with backup control of the DOOR output by IN input triggering when communication with the control panel is lost.
Unlock the IN input during a fire alarm: This parameter unlocks the IN input during a fire alarm even though blocking the IN input by the section has been enabled. This option is available only if the function Blocking the IN input by section
is enabled.
Triggered tamper: This parameter can disable the tamper contact for cases when the module is going to be installed inside a different box or into a box with different tamper protection.
Note: The module is designed for use with very high quality NiMH batteries (purchase code-BAT-1V2-NIMH) in a positive operational temperature range. NiMH batteries have unsuitable behaviour in a negative operational temperature range so in this case we recommend using NiCd batteries in the module.
Application recommendation:
We recommend using the module with door locks complying with the following parameters:
- Standard locks 12 V DC / max. 300 mA
- Reverse locks 12 V DC / 170 mA (for reverse door locks it is
necessary to plug in an external power supply, for example the DE 06-12)
Accumulators lifetime (approximate values)
Electromagnetic
lock current
consumption
(mA)
230 10 387 618 230 10 193 1241 230 10 55 3114
Duration of an impulse
(s)
Period of time
necessary to
recharge
accumulators after
one activation (s)
Number of
impulses from
fully charged
accumulators
(1900mAh)
JABLOTRON ALARMS a.s.
Pod Skalkou 4567/33 46601 Jablonec n. Nisou
Czech Republic www.jablotron.com
Setting the module properties
The module properties can be set in the Devices window of the F-Link software. When at the module position, use the Internal settings option to open a dialogue window where you can set the following options:
LED indication – Enable/disable optical indication by the red LED (4) of triggering the IN input.
DOOR reacts to PG status – Determines which PG output or outputs the module reacts to.
The JA-120N BUS module for electric door locks 1 / 2 MLY57704
Page 2
The JA-120N BUS module for electric door locks
Figure 2: JA-190PL installation box dimensions
Power from the control panel BUS (9…14 V)
External power +12 V Current consumption in standby mode 10 mA Current consumption for cable choice 60 mA DOOR output load (Eneloop batteries):
Pulse (1s) 600 mA
Continuous 300 mA Dimensions 90 x 90 x 35 mm Weight 185 g Operationa temperature range -10 °C - +40 °C Classification Grade 2 According to EN 50131-1, EN 50131-3, Operational environment according to EN 50131-1 II. General indoor Also complies with EN 50130-4, EN 55022
NiMh rechargable accumulator type AA Eneloop 1900 mAh
3x
JABLOTRON ALARMS a.s. hereby declares that the JA-120N is in a compliance with the relevant Union harmonisation legislation: Directives No: 2014/30/EU, 2011/65/EU. The original of the conformity assessment can be found at www.jablotron.com ­Section Downloads.
Note: Although this product does not contain any harmful materials we suggest you return the product to the dealer or directly to the producer after use.
Please note: Batteries are not included
Technical specifications
The JA-120N BUS module for electric door locks 2 / 2 MLY57704