JA-111H TRB BUS module - interface for wired detectors
a.s.
||
|
JABLOTRON ALARMS
Pod Skalkou 4567/33 46601 Jablonec n. Nisou
Czech Republic www.jablotron.com
The JA-111H TRB is a component of the JABLOTRON 100 system
and it serves for connecting a wired detector with NC / NO outputs
to the control panel BUS. It provides a power supply for the detector
and reports its activation, tampering and faults.
It is designed to be installed inside a standard wired detector (with
contact outputs) but thanks to the extended wires can also be installed
out of it in a protected installation box. The module occupies one
position in the system. The module should be installed by a trained
technician with a valid certificate issued by authorized distributor.
Installation
1. Install the module at a suitable place in the detector or inside
the protected installation box near the detector. The wire can
be extended to up to 3 m maximum. When the module is installed
inside the detector ensure that it cannot make a short circuit
because of poor isolation.
2. Connect the wires to the detector (according to Fig. 1).
Figure 1: 1 - BUS terminals; 2 - Production code; 3 - Yellow LED indicates
fault / not enrolled device, red LED indicates by flashing activation of any
input; 4 – connecting wires, see the following table:
Wire Meaning Function
Red + 12 V Power for detector
Black GND Common wire
White INP Alarm input
Blue TMP Tamper input
Yellow TRB Trouble input
3. Connect the BUS cable and switch on the control panel power.
When connecting the module to the system
bus, always switch the power off.
The power consumption of the connected
detector must not exceed 50 mA (the module
power supply output is not protected against
overloading.
4. The control panel has to be in service mode.
5. Proceed according to the control panel installation manual. Basic
procedure:
a) When the device is switched on, the yellow LED starts
flashing repeatedly to indicate that the module has not been
enrolled into the system.
b) Go to the F-Link software, select the required position in the
Devices window and launch the enrollment mode by clicking
on the Enroll option.
c) Click on the Add new BUS devices option, select
the JA-111H TRB and confirm its enrolling by a double
press – the yellow LED goes off.
6. Close the cover of the detector with the installed module inside.
Notes:
- The module can also be enrolled by pressing the tamper contact
of the connected detector (connection of the black and blue wire
together) or by entering the production code via the F-Link
software. The production code is printed on the sticker under
the bar code on the PCB of the product.
- If you need to remove the module from the system, erase it from
its position in the control panel.
Setting the module properties
The module properties can be set in the Devices window of the F-Link
software. Use the Internal settings option at the detector position to open
a dialog window where you can set:
LED indication: Factory settings indication is enabled. The function
serves for switching ON / OFF the LED indication of the red LED (3).
The LED reacts to activation of any input of the module.
INP input: By factory default it is enabled in NC mode (C connected
to GND). The input can be disabled completely and no activation will
be reported to the system. The following option is Roller which reacts
to short repeated pulses with a sensitivity adjustable to two levels:
Impulse 1 = activation by 3 pulses up to max. 2 minutes;
Impulse 2 = activation by 5 pulses up to max. 2 minutes. When the input
terminal is disconnected from GND longer than 0.5 s, a tamper alarm
is triggered. In the Roller mode the input is deactivated for 10 s after its
triggering.
When the INP input is enabled, it shows other options for setting:
Inverted input reaction: It has a NC reaction by default but it can
be changed to a NO reaction.
Impulse mode: The status mode is pre-set by factory default.
If the parameter is enabled, the input starts to react with an impulse reaction.
Ideal for pulse detectors (for instance movement detectors).
INP input reaction delay: A time filter for increasing false alarm
immunity – it can be set from 0.1 s to 300 s to define how long the INP input
must be active in order to be triggered in the control panel.
TRB input: By factory default it is disabled and no activation will
be reported to the system. If you select Trouble then input activation triggers
a fault from the position of the module (standby C connected to GND). If you
select the Antimasking option then input activation in an unset section
triggers a fault and in a set section fault + alarm (standby C connected
to GND).The input is meant for connection to detectors with an antimasking
function.
Inverted TRB reaction: It has an NC reaction by default but it can be
changed to a NO reaction.
TRB input reaction delay: A time filter – it can be set from 0.1 s
to 300 s to define how long the TRB input must be active in order
to be activated in the control panel.
TMP input: By factory default it is enabled in NC mode (C connected
to GND). The input can be disabled completely and no activation will
be reported to the system.
Inverted TMP reaction: It is an NC reaction by default but it can
be changed to an NO reaction.
The manufacturer only guarantees correct
functioning of this module. However, they
cannot guarantee the correct functioning of the
connected detector. We therefore recommend
using JABLOTRON 100 BUS detectors.
To set the module to comply with security grade
2 use F-Link SW, the
Parameters tab and
the option “Perform EN50131-1”.
Technical specifications
Power from control panel BUS 12 V DC (9…15 V)
Current consumption:
- Nominal consumption - to calculate backup 8 mA
(+ consumption of connected devices)
- Maximal consumption - for cable selection 12 mA
(+ consumption of connected devices)
Maximum allowed current of the connected detector 50 mA
Dimensions 16 x 30 x 12 mm
Weight 8 g
Classification Security grade 2/environmental class II
Note: valid only, if it is built-in to security grade 2 or higher certified
housing
- according to EN 50131-1, EN 50131-3 (ACE type B)
- environmental Indoor general
- operating temperature range -10 to +40 °C
- average humidity 75 % RH non condensing
- certification body Trezor Test s.r.o. (no. 3025)
Valid for installation of the module into a product certified for security
grade 2/environmental class II and also if the connection to the module
is compatible.
Also complies with EN 50130-4, EN 55022
JABLOTRON ALARMS a.s. hereby declares that the JA-111H
TRB is in a compliance with the relevant Union harmonisation
legislation: Directives No: 2014/30/EU, 2011/65/EU. The original
of the conformity assessment can be found at www.jablotron.com
- Section Downloads.
Note: Although this product does not contain any harmful
materials we suggest you return the product to the dealer
or directly to the producer after use.
all inputs connected to GND
JA-111H TRB BUS module - interface for wire detectors 1 / 1 MLN59104