IVT Greenline HT Plus C, Greenline HT Plus E Manual To Installation, Commissioning And Maintenance

Greenline HT Plus
C and E
Guide to installation,
commissioning and maintenance
Art. no: 290410-29 Version: 1.1
FOR THE USER
FOR THE INSTALLER
2
Manual for Heat pump Greenline HT Plus C and E IVT Industrier AB, 20.12.04 Article number: 290410-29 Version 1.1
Copyright © 2004. IVT Industrier AB. All rights reserved.
This manual contains copyright protected information that is the property of IVT Industrier AB. No part of this document may be copied or forwarded, electronically or mechanically, without prior, written permission from IVT Industrier AB. This includes photographing and translation to another language.
Thank you for choosing a heat pump from IVT Industrier AB
We hope that our heat pump meets your expectations and gives you many years of energy saving. We want you and your family to enjoy a good economy at the same time as you actively safeguard the environment. We have taken today’s demands on heat pumps into consideration and believe that your Greenline HT will give you many useful functions in the future. Your heat pump features an advanced control unit that monitors and controls the temperature in the house and contributes towards improved overall economy. The heat pump Greenline HT Plus has, for example, a holiday function, that’s to say the heat pump can be set at a “low level” while you are away on holiday.
IVT is the leading heat pump manufacturer in the Nordic Countries. More than every second heat pump comes from IVT. We have worked with solutions to reduce energy consumption on the environment’s terms for more than 30 years. Today we can present the widest range of heat pumps for effi cient energy saving in all types of housing and properties.
Johnny Wärnelöv Managing director IVT Industrier AB
3
Table of Contents
Contents
FOR THE USER .................................................................................................... 5
Important information ....................................................................................... 5
This is how your heat pump works ..................................................................... 6
Technology in and around the heat pump ................................................................................................................6
Component parts of the heat pump .................................................................... 8
IVT Greenline HT Plus C ........................................................................................................................................8
IVT Greenline HT Plus E ........................................................................................................................................9
Control unit Rego 637 ..................................................................................... 10
The control unit’s two methods to control the heat pump ........................................................................................11
Control panel .................................................................................................. 12
Controls and status lamps .....................................................................................................................................12
Menu dial .............................................................................................................................................................13
How to use the control panel .................................................................................................................................13
Basic functions (Customer level 1) ................................................................... 13
Menu overview for Basic functions (Customer level 1) ..........................................................................................14
Select scrolling information on the menu display ...................................................................................................14
Set the heating ......................................................................................................................................................15
Set the desired room temperature ..........................................................................................................................18
Set the heat pump for extra hot water ....................................................................................................................18
Heating- and hot water settings .............................................................................................................................19
Read the temperatures on the heat pump ...............................................................................................................19
Extra functions (Customer level 2) ................................................................... 21
Menu outline for Extra functions (Customer level 2) .............................................................................................21
Temperature settings .............................................................................................................................................22
Set extra heat curve with mixing valve ..................................................................................................................23
Hot water settings .................................................................................................................................................24
Timer control ........................................................................................................................................................24
Reading operating times on the heat pump and additional heat ............................................................................25
Set the time and date ............................................................................................................................................26
Alarms given by the heat pump .............................................................................................................................27
Return to the heat pump’s factory settings ..............................................................................................................27
Care ............................................................................................................... 28
Unscrew the front cover ......................................................................................................................................... 28
Sight glass .............................................................................................................................................................28
Expansion tank ..................................................................................................................................................... 29
Particle fi lter .........................................................................................................................................................30
Checking the protective anode ...............................................................................................................................30
Savings .......................................................................................................... 31
What to do if a fault occurs .............................................................................. 32
Dimmed menu display ..........................................................................................................................................32
Fuses and reset buttons on the heat pump .............................................................................................................. 33
All Alarm ..............................................................................................................................................................33
4
FOR THE INSTALLER .......................................................................................... 40
Important information to the installer ............................................................... 41
Checklist ........................................................................................................ 41
What the shipment includes ............................................................................. 42
Dimensions and connections ........................................................................... 43
The heat pump and collector hose in general ..................................................... 44
Transporting the heat pump ..................................................................................................................................44
Positioning the heat pump .....................................................................................................................................44
Maximum working temperatures ..........................................................................................................................44
Fit the particle fi lter ..............................................................................................................................................44
Collector hose ........................................................................................................................................................ 45
Preparations before connection ........................................................................ 48
Moving the heat transfer fl uid pipe for side entry ...................................................................................................48
Supplementing the heat pump with a ground water system ....................................................................................51
Ground water system: Electrical connection ..........................................................................................................52
Connecting the heat pump to the heating system ............................................... 52
Connecting to the heating system without a bypass: ................................................................................................ 53
Connect heat pump C to the heating system ...........................................................................................................54
Connect heat pump E to the heating system ...........................................................................................................55
Connect the heat pump to a heating system with bypass .........................................................................................56
Filling water in the heating system .......................................................................................................................57
Filling the heat transfer fl uid in the collector hose .................................................................................................57
Installing the expansion vessel ...............................................................................................................................59
Connecting the heat pump to the power supply ................................................. 60
Safety switch and earth-fault breaker .....................................................................................................................60
External connections to the heat pump ..................................................................................................................61
Connecting the general alarm, external input and load monitor ............................................................................ 62
Installer and service menu (I/S) ...................................................................... 63
How to use the control panel .................................................................................................................................63
Commissioning the heat pump ......................................................................... 64
Menu displays you might need to adjust or check ...................................................................................................65
Manual test run of the heat pump .........................................................................................................................68
Start the heat pump with only additional heat ...................................................................................................... 68
Important points to check after star t up .................................................................................................................68
Technical information ...................................................................................... 69
The heat pump’s factory settings ............................................................................................................................69
Sensor table ...........................................................................................................................................................69
Technical information ...........................................................................................................................................70
Index ............................................................................................................. 71
Table of Contents
5
Note
It is important as the user that you read through the User manual. Under no circumstances may the user make settings that are designed for the installer. This can cause serious malfunction of the heat pump.
Important information
The heat pump Greenline HT Plus represents a new generation of heat pumps from IVT Industrier. It contains numerous functions to control the temperature and production of hot water in the house. The control unit Rego 637 is the brains of the heat pump. Rego 637 includes a control and monitoring function that stores important settings about the heat pump’s operation and maintenance. The settings are made by the installer and the user via a control panel on the front of the heat pump. Settings intended for the user, are presented in this chapter under the headings Basic functions and Extra functions.
When the heat pump has been installed and started there are a number of points you should check regularly. This may concern an alarm triggering or performing basic maintenance actions. Initially you should perform these actions on your own. This manual describes each step in detail. If the problem remains you should contact your dealer.
For the user
6
FOR THE USER
This is how your heat pump works
The heat pump Greenline HT Plus represents a new generation of heat pumps from IVT Industrier. The heat pump has been manufactured for easy and reliable use as well as to provide your house with inexpensive and environment friendly heating. The easiest way to describe how a heat pump works is to say it works like a refrigerator, however, the other way round. In a refrigerator, heat is moved from the inside to the outside. In a heat pump, heat stored in the ground, rock or water, is moved into the house. The heat pump collects a few degrees of the stored solar energy. The heat is led into the house via a hose. The temperature is then increased in the heat pump and the heat is distributed to the house’s heating system.
The heat pump collects stored solar energy
Boiling point in relation to the pressure:
The boiling point of different liquids varies with pressure, the higher the pressure, the higher the boiling point. For example, water boils at +100ºC at normal pressure. Double the pres­sure and water boils at +120ºC. Half the pressure and water then boils at +80ºC. The refrigerant in the heat pump acts in the same way, the boil­ing point changes when the pressure changes. However, the boiling point of the refrigerant is as low as approxi­mately -40ºC at atmospheric pressure. Consequently, it is also suitable for low heat source temperatures.
Note
Rock heat Soil heat Lake heat
The heat pump consists of four main parts:
1. Evaporator
Evaporates the refrigerant to gas and at the same time transfers the
heat from the heat transfer fl uid to the refrigerant circuit.
2. Condenser
Condenses the gas to fl uid again and transfers the heat to the heating
system.
3. Expansion valve
Lowers the pressure of the refrigerant.
4. Compressor
Increases the pressure of the refrigerant.
These four main parts are linked in three circuits. A refrigerant circulates in the heat pump, which in some parts of the circuit is in a liquid state and in other parts in a gas state. Read more about the properties of the refriger­ant in the sidebar to the right.
See the detailed description of the technologies used in the heat pump on the next page.
Technology in and around the heat pump
This is how your heat pump works
7
FOR THE USER
Heat transfer fl uid in. A hose is connected here that collects the stored solar energy from, e.g., the soil or rock. The hose contains a heat transfer fl uid, which is a mixture of water and anti-freeze. The fl uid collects the heat from the rock and with the help of the HTF pump leads it into the heat pump and the evaporator. The temperature is then approximately 0ºC.
In the evaporator, the heat transfer fl uid meets the refrigerant. At this stage, the refrigerant is in a fl uid state and is at approximately -10ºC. When the refrigerant meets the zero degree heat transfer fl uid it starts to boil. It then forms a vapour, which is led into the compressor. The temperature of the vapour is 0ºC.
The pressure of the refrigerant increases in the compressor and the vapour temperature rises from 0ºC to approximately +100ºC. The warm gas is then forced into the condenser.
The condenser is the heat pump’s heat emitting part. Here the heat is transferred to the house’s heating system (radiators and fl oor heating) and the hot water system. The vapour is cooled in the condenser and becomes fl uid. The pressure in the refrigerant is still high when it is led on to the expansion valve.
The refrigerant pressure is lowered in the expansion valve. At the same time, the temperature also drops to approximately -10ºC. When the refrigerant has passed through the valve and the evaporator it changes to vapour again.
In heat transfer fl uid out, the heat transfer fl uid is led out from the heat pump to the rock to collect new stored solar energy. The temperature of the fl uid is approximately -3ºC.
1
2
3
4
5
6
Floor heating
Radiator
Fan-assisted
radiator
Heat pump
Rock
Soil
0ºC
-3ºC
0ºC +100ºC
-10ºC
1
6
2 3 4
5
Heat carrier
pump
Heat
transfer pump
This is how your heat pump works
“The hot side”
“The cold side”
8
FOR THE USER
Component parts of the heat pump
Three-way valve
The valve switches between heating the heating water and hot water.
Hot water cylinder
The cylinder is double-shelled and holds approximately 165 litres of hot water and 60 litres of the heating water.
Electric water heater
The electric cassette is used to provide extra output in cold weather conditions, with large water consumption and at hot water peaks.
Reset button
Press in the button if the overheat protector on the electric cassette has tripped. The button is located on the side.
Heat carrier pump
The pump ensures the heating water circulates within the heating system.
Compressor
The compressor increases the pressure of the refrigerant. The temperature of the vapour increases from 0ºC to approxi­mately +100ºC. The compressor is insulated to reduce the noise level.
Electrical connections
Connections for the mains supply as well as sensors.
Control panel
The control panel has a back­ground lit menu display with four rows of text information, three buttons and a dial.
Electrical box
The distribution box is enclosed. It houses a reset function for the motor cut-out as well as miniature circuit breakers (MCB) for the heat pump and electric cassette.
Heat transfer fl uid pump
The pump is insulated and features an anti-corrosive fi nish. It ensures the heat transfer fl uid circulates from, e.g. the rock to the heat pump.
Control unit
The control unit is enclosed. It controls and monitors all heat pump functions.
Expansion valve
Lowers the pressure of the refrig­erant that enters the evaporator and collects energy from, e.g. the rock.
Sight glass
Sight glass to check the level in the refrigerant circuit. Air bubbles must not form in the sight glass when the heat pump is running. However, there might be bubbles when the heat pump is started and stopped.
Flexible hoses
The hoses counteract vibrations in the heat pump.
IVT Greenline HT Plus C
Evaporator
The evaporator evaporates the refrigerant to gas and transfers heat from the heat transfer fl uid to the refrigerant circuit (behind the heat pump).
Condenser
The condenser condenses the vapour to fl uid again and transfers the heat to the heating system.
Component parts of the heat pump
9
FOR THE USER
IVT Greenline HT Plus E
Reset button
Press in the button if the overheat protector on the electric cassette has tripped. The button is located on the side.
Heat carrier pump
The pump ensures the heating water circulates within the heating system.
Compressor
The compressor increases the pressure of the refrigerant. The temperature of the vapour increases from 0ºC to approxi­mately +100ºC. The compressor is insulated to reduce the noise level.
Electrical connections
Connections for the mains supply as well as sensors.
Control panel
The control panel has a back­ground lit menu display with four rows of text information, three buttons and a dial.
Electrical box
The distribution box is enclosed. It houses a reset function for the motor cut-out as well as miniature circuit breakers (MCB) for the heat pump and electric cassette.
Heat transfer fl uid pump
The pump is insulated and features an anti-corrosive fi nish. It ensures the heat transfer fl uid circulates from, e.g. the rock into the heat pump.
Control unit
The control unit is enclosed. It controls and monitors all heat pump functions.
Expansion valve
Lowers the pressure of the refrigerant that enters the evapora­tor and collects energy from, e.g. the rock.
Sight glass
Sight glass to check the level in the refrigerant circuit. Air bubbles must not form in the sight glass when the heat pump is running. However, there might be bubbles when the heat pump is started and stopped.
Flexible hoses
The hoses counteract vibra­tions in the heat pump.
Evaporator
The evaporator evaporates the refrigerant to gas and transfers heat from the heat transfer fl uid to the refrigerant circuit (behind the heat pump).
Particle fi lter
The fi lter can be opened for easy cleaning. It also has a shut off function.
Electric water heater
The electric cassette is used to provide extra output in cold weather conditions, with large water consumption and at hot water peaks.
Three-way valve
The valve switches between heating the heating water and hot water.
Condenser
The condenser condenses the vapour to fl uid again and transfers the heat to the heating system.
Component parts of the heat pump
10
FOR THE USER
Control unit Rego 637
The control unit is the brains of the heat pump. It makes sure the heat pump gives the best energy savings and that it runs for many years. The control unit controls and monitors the heating and hot water supply in your house. The monitoring function is especially important. It shuts down the heat pump in the event of operational disturbances so that no critical parts are damaged.
Additional heat gives more output
When the heat pump can not manage to heat the house by itself, for example, if there is a considerable drop in the outdoor temperature, the control unit ensures the additional heat source is connected. Together the heat pump and additional heat guarantee the right temperature in the house. Additional heat in the Greenline HT Plus is provided by a built in electric cassette. Additional heat can never completely take over the heating from the heat pump. It only adds the output necessary for the heat pump to be able to produce the right temperature. When the heat pump can once again manage heating on its own the additional heat is automati­cally disconnected.
Hot water is given priority over heating water
In a house with water based heating a difference is made between heating water and hot water. The heating water is for radiators/fl oor heating and hot water is for showers and taps. Hot water is heated in a hot water heater. The hot water heater is fi tted with a sensor that senses the temperature of the hot water. C models include a hot water heater in the heat pump while E models have an external hot water heater. The heating water passes through the hot water cylinder’s outer shell and heats up the hot water heater’s inner tank. The control unit makes sure the heating of hot water is always given priority over the heating of the heating water. This means you never need to be without hot water. The control unit controls a three-way valve that switches between heating the heating water and hot water. Once the hot water has been heated the three-way valve switches so that the heating water is heated.
Control unit
Electric cassette (additional heat)
Three-way valve
Double-shelled
hot water cylinder
Heating water
Hot water
Control unit Rego 637
11
FOR THE USER
The control unit’s two methods to control the heat pump
The control unit uses two different methods to control the heat pump. These two methods are: Control with an outdoor sensor and Control with an outdoor sensor supplemented with a room sensor.
Control with outdoor sensor
Control with an outdoor sensor is the most common method used by the control unit to control the heat pump. When the heat pump is delivered it is set for this control method. A sensor is fi tted on the outside wall of the house. It sends signals to the control unit in the heat pump. Control with an outdoor sensor means that the heat pump automatically regulates the heating in the house depending on the outdoor temperature. If the outdoor temperature drops, i.e. it becomes colder; the radiators inside the house will become warmer.
You determine the temperature of the radiators, in relation to the outdoor temperature, with the help of a number of settings such as selecting the heat curve on the control unit. A lower curve gives higher energy savings.
Control with an outdoor sensor supplemented with room sensor
Control with an outdoor sensor supplemented with a room sensor means that you also place a sensor in a central position inside the house. This is connected to the heat pump and provides the control unit with information about the room temperature. The signals affect the control unit’s settings (curves) and ensure the heat pump gives the best possible energy savings.
This control method is used when factors other than the outdoor tempera­ture infl uence the indoor temperature. Examples include the use of a stove or fan-assisted radiator or if the house is sensitive to the wind.
It is only the room where the room sensor is located that can infl uence regulation of the temperature.
Note
Control unit Rego 637
12
FOR THE USER
Control panel
All settings are made from the control panel. It also displays heat produc­tion statistics and information about different alarms. When you have made your settings, the control panel makes sure they are saved in the control unit Rego 637 to carr y out your wishes.
Control panel
Menu dial
Status lamps
Power switch (ON/OFF)
Controls and status lamps
Power switch (ON/OFF)
You start and stop the heat pump using the power switch button. Lamp on: The heat pump is on. Lamp fl ashes: The heat pump is off.
Operating status
Lamp on: The heat pump (compressor) is operational.
Additional heat status
Lamp on: The heat pump is using additional heat from an electric cassette.
Hot water status
Lamp on: The heat pump is heating water in the heater. Lamp fl ashes: The heat pump has a hot water peak or is producing extra hot water.
Alarm status
Lamp fl ashes: A fault has occurred in the heat pump. Lamp on: The alarm has been acknowledged, but the fault remains.
Temperature
Temperature
Pressing once gives a shortcut to the most frequent temperature settings.
Info
Pressing once gives continuous information about the heat pump’s and additional heat’s operating conditions.
Menu
Press once to enter the main menu. The main menu contains all setting menus and temperature displays.
Info
Menu
Menu display
Menu buttons
Control panel
Rego 637 K1
040622 16:08:15 Tu Heat Info Menu
Rego 637 K1
040622 16:08:15 Tu Heat Info Menu
13
FOR THE USER
Rego 637 K1
040622 16:08:15 Tu Heat Info Menu
Control panel
Menu dial
The menu dial is used to scroll through the menu display windows. Turn the menu dial clockwise (to the right) to move down through the menus. Turn the menu dial anti-clockwise (to the left) to move up through the menus. You also determine the values of different settings by using the dial.
The menu display gives you information and the chance to make settings. You can:
Choose different temperature and hot water settings. Choose extra hot water and the holiday function. See alarm causes and receive corrective instructions. Obtain operating statistics.
How to use the control panel
The principle of the control panel is based on the user using three menu buttons and a menu dial to move between the different menus and settings. On the lower row of the menu display you will always see information about the signifi cance of the buttons. The function of the buttons changes depending on which window you are currently in.
Example
If, from the initial menu, you press the Heat button, you will access the menu Temp. incr. / decr. In this menu you can increase and decrease the heating in the house. Note that the signifi cance of the buttons has now changed. You can either return to the initial menu by pressing the Return button or you can choose to change the heating setting in the house by pressing the Adjust button. If you press the Adjust button you can increase or decrease the heating in the house by using the menu dial. Save your adjustment by pressing the Save button.
Initial menu display
+
Initial menu
Initial menu
Time Date
Customer level 1
Day
Basic functions ( Customer level 1)
Basic functions (Customer level 1) are the functions most frequently used and the ones you have the most benefi t of. You reach the basic functions by pressing one of the Heat, Info or Menu buttons in the initial menu. The designation K1 in the upper right corner indicates you are in Basic functions – Customer level 1.
Rego 637 K1
040622 16:08:15 Tu Heat Info Menu
Rego 637 K1
040622 16:08:15 Tu Heat Info Menu
Temp. incr. / decr.
0 5,0 10 Return Adjust
14
FOR THE USER
Basic functions - Customer level 1
The menu display is standard on all heat pumps.
=
=
Temp. fi ne-tune
Page 17
The menu display is only shown on the heat pump in combination with an extra sensor or for a specifi c model of Greenline HT Plus.
Temp. incr. / decr.
Page 16
Room temperature
Page 18
Extra hot water
Page 18
STANDBY No rad heat required No hotwater required
Page 15
HOT WATER MODE Heat pump only
Page 15
HEAT RAD MODE
Compr. + Add. heat
Page 15
HEAT RAD REQ Heat pump starts in #### seconds
Page 15
Main menu Indoor temperature settings 1
Page 19
Temperature settings Temp. incr. / decr. range 0-10 1.1
Page 16
Temperature settings Temp. fi ne-tune range -10/+10 1.2
Page 17
Temperature settings Setting of room temperature 1.10
Page 18
Main menu Adjust the hot water settings 2
Page 19
Hot water setting Number of hours for add. hot water 2.1
Page 18
Main menu Monitor all temperatures 3
Page 19
Temperature readings
Return radiator GT1
Temperature readings
Out GT2
Temperature readings
Hot water GT3
Temperature readings
Shunt, fl ow GT4
Temperature readings
Room GT5
Temperature readings
Compressor GT6
Temperature readings
Heat trfl uid out GT8
Temperature readings
Heat tr fl uid in GT9
Temperature readings
Ht trfl d(coll)inGT10
Temperature readings
Httrfl d(coll)outGT11
Page 20
Note
Each menu is numbered in the lower right-hand corner; this indicates which main display it is associated to.
Select scrolling information on the menu display
If you press the Info button in the initial menu, you will receive continuous information about the heat pump’s operation and working temperatures. This is what to do:
1. Press the Info button in the initial menu. Here follows a few of the windows displayed:
Menu overview for Basic functions (Customer level 1)
Rego 637 K1
040622 16:08:15 Tu Heat Info Menu
Rego 637 K1
040622 16:08:15 Tu Heat Info Menu
15
FOR THE USER
The heat pump is in standby mode.
The heat pump is producing hot water. You see at which temperature the heat pump will stop and the present temperature. Note that the stop temperature is read at the bottom of the heater. The hot water is a few degrees warmer.
The heat pump and additional heat are running.
The heat pump has received signals that it should produce heating. It now waits for the restart time to countdown to zero.
Return to the initial menu by pressing one of the buttons or turn the dial.
Basic functions - Customer level 1
Set the heating
It is easy to set the heating level on the heat pump. However, before we explain how to do this it is important to understand the relation between the outdoor temperature, return temperature and heat curve slope. The easiest way to explain the relation is with a heat curve.
Heat curve
You use the heat curve to help set the indoor temperature you would like. The heat pump is controlled by the outdoor temperature. When the weather becomes colder, the heat pump ensures more heating is produced automatically.
Return temperature:
The return temperature is the temperature of the water that returns to the heat pump from the radiators. The water led out from the heat pump to the heating system is normally 7-10ºC higher than the return temperature. When the outdoor temperature is -10ºC and curve 4 is set, the pump attempts to keep the return water at approximately 40ºC.
Outdoor temperature:
The outdoor temperature determines how much heating the heat pump should produce. A sensor placed outdoors sends signals to the control unit, which then adjusts the heat pump.
Cur ve slope:
You can change the curve slope to increase or decrease the heating in the house. The scale is between 0-10.
On delivery the heat pump curve slope is set to position 4. This means that the return temperature is +35ºC when it is 0ºC outdoors.
Note
STANDBY No rad heat required No hotwater required
HOT WATER MODE Heat pump only Stop temp 53.0° Present temp 50.0°
HEAT RAD MODE Compr. + Add. heat Stop temp 45.0° Present temp 44.0°
HEAT RAD REQ Heat pump starts in 320 seconds
16
FOR THE USER
In cold weather (below -5ºC):
If you are not satisfi ed with the indoor temperature when it is colder than +5ºC outdoors, you need to change the slope of the heat curve. This is what to do:
1. Press the Heat button in the initial menu.
2. Press the Adjust button.
3. Turn the menu dial clockwise to increase the heating. Turn the menu dial anti-clockwise to lower the heating.
(Adjust in small increments, 0.2-0.6 units, is usually enough.)
4. Save the new value by pressing the Save button.
Basic functions - Customer level 1
Dashed line:
If the return temperature exceeds 57ºC an alarm is given and the compres­sor switches off. The heat pump star ts automatically when the return temperature drops.
Curve slope:
2-4 Normal setting for fl oor heating. 4-6,5 Normal setting for radiators. 7-10 Abnormal high setting.
From the heat curve we see that curve slope 4 gives a return tempera­ture of +35ºC when it is 0ºC outdoors. If the outdoor temperature drops we can see that the return temperature increases. The colder the outdoor temperature the higher the return temperature. At an outdoor tempera­ture of approximately -30ºC we see the curve slope has nearly reached the limit value (+57ºC) for the return temperature.
You should wait at least two days when increasing or decreasing the heating before making a new adjust­ment.
If it is still diffi cult to get a comfor t­able indoor temperature at an outdoor temperature around 0ºC, despite several attempts, you should adapt the heat curve. Read about how to “adapt the curve” in the section Extra func-
tions – Customer level 2 / Temperature settings / Adapting the heat curve.
Note
Change the curve slope
The heat pump’s production of heating is adjusted by increasing or de­creasing the curve slope in the Temp. incr. / decr. menu. This is especially effective in cold weather conditions.
Return temperature (ºC) Curve slope (0-10)
Outdoor temperature (ºC)
Temp. incr. / decr.
0 4,0 10 Return Adjust
Temp. incr. / decr.
0 5,0 10 Return Adjust
17
FOR THE USER
Basic functions - Customer level 1
Fine-tune the heat curve
The heat curve can also be fi ne-tuned. Fine-tuning means that you offset the heat curve in parallel. Fine-tuning is done from the Temp. fi ne-tune menu. The diagram for fi ne-tuning shows how the dashed line has been offset upwards in parallel. This means the heating has been fi ne-tuned in a positive direction and the heat pump will be instructed to maintain a higher temperature on the return water at all outdoor temperatures.
Outdoor temperature (ºC)
Return temperature (ºC)
By using the menu dial on the control panel the fi ne-tuning line has been moved up so the heat pump produces more heat.
In warm weather (above +5ºC):
If you are not satisfi ed with the indoor temperature when it is warmer than +5ºC outdoors, you should offset the cur ve in the Temp. fi ne-tune menu. This is what to do:
1. Press the Heat button in the initial menu.
2. Turn the menu dial clockwise until you reach the menu Temp. fi ne-tune.
3. Press the Adjust button.
4. Turn the menu dial clockwise to increase the heating. Turn the menu dial anti-clockwise to lower the heating. (Adjust in small increments, 0.5-1.0 units, is usually enough.)
5. Save the new value by pressing the Save button.
Temp. fi ne-tune
-10° 0,0 10° Return Adjust
18
FOR THE USER
Room temperature
10° 20,0 30° Return Adjust
Set the desired room temperature
If you have a room sensor connected to the heat pump you can set the required temperature in the room from the Room temperature menu. From Extra functions (Customer level 2) you can also set how much you want the sensor to infl uence the heating system.
This is what to do:
1. Press the Heat button in the initial menu.
2. Turn the menu dial clockwise until you reach the menu Room temperature.
3. Press the Adjust button.
4. Turn the menu dial clockwise to increase the room temperature.
Turn the menu dial anti-clockwise to lower the room temperature.
5. Save the new value by pressing the Save button.
Note
The example describes how to set the required room temperature with the help of a connected room sensor. The range is 10ºC to 30ºC.
Set the heat pump for extra hot water
You can obtain extra hot water by temporarily increasing the temperature of the water in the hot water cylinder. This may be appropriate when, for example, a large number of people need to shower. You choose how long the function should run using the Extra DHW menu. This is what to do:
1. Press the Heat button in the initial menu.
2. Turn the menu dial clockwise until you reach the menu Extra DHW.
3. Press the Adjust button.
4. Turn the menu dial clockwise to choose the number of hours that the electric cassette should be on (e.g. 24 hours).
5. Save the value by pressing the Save button.
When the set time has elapsed you must repeat the setting to get extra hot water again.
Note
Basic functions - Customer level 1
Extra DHW
1h 24h 48h Return Adjust
Extra DHW
1h 24h 48h Return Save
19
FOR THE USER
Basic functions - Customer level 1
Heating- and hot water settings
Move to the temperature settings for heating on Customer level 1 like this:
1. Press the Menu button in the initial menu.
2. Press the Select button and scroll through the heating menus with the menu dial.
Move to the temperature settings for hot water on Customer level 1 like this:
1. Turn the menu dial clockwise until you reach the menu Here you can adjust the hot water settings.
2. Press the Select button and scroll through the hot water menus with the menu dial.
Read the temperatures on the heat pump
There are several different temperature sensors in the heat pump. Each sensor plays an important par t in the heat pump’s daily operations. It may, for example, adjust the heating production so that the pump does not become overheated. Proceed as follows to read the temperatures on the heat pump:
1. Press the Menu button in the initial menu.
2. Turn the menu dial clockwise until you reach the menu Here you can monitor all temperatures (menu 3).
3. Press the Select button.
4. Turn the menu dial to scroll through all the heat pump’s temperature sensors. See the next page.
Note
Each menu is numbered in the lower right-hand corner; this indicates which main display it is associated to.
Rego 637 K1
040622 16:08:15 Tu Heat Info Menu
Main menu Indoor temperature settings 1 Return Select
Main menu Adjusting the hot water settings 2 Return Select
Main menu Monitor all temperatures 3 Return Select
20
FOR THE USER
All the temperature sensor menus
All the windows associated with the heat pump’s temperature sensors are presented below. Note that you cannot make any settings in these menus, only read the current values. Some menus are standard for all models of Greenline HT Plus while others are only available in combination with different accessories. The sensors give an alarm if the temperature is outside of the permitted interval/values.
Note
All sensors are not included as standard on the heat pump, some are available as accessories for different application areas. See more informa­tion under respective menus.
The menu shows the temperature in the heating system’s return, i.e. the water from the radiators back to the heat pump in heating mode. This temperature varies depending on the outdoor temperature.
The menu shows the outdoor temperature. Some deviation compared to the true tempera­ture may occur due to thermal radiation from the house to the installed outdoor sensor.
The menu shows the set and present temperature in the lower section of the outer container in the hot water cylinder. The temperature is approximately 5ºC lower than the temperature of the hot water inside the inner container.
The menu only applies together with a fl ow sensor. If an extra curve with mixing valve is used, for example, for a fl oor heating system, you can see the temperature on the fl ow water in the circuit. The temperature varies with the outdoor temperature.
The menu only applies together with a room sensor. The menu shows the set point value and present temperature in the room where the sensor is fi tted.
The menu shows the compressor’s working temperature. The temperature varies between 70ºC and 125ºC during operations.
The menu shows the temperature of the radiator water as it leaves the heat pump. It varies depending on the outdoor temperature and whether the heat pump is in hot water production mode.
The menu shows the temperature of the water that is led into the heat pump. It varies depending on the outdoor temperature and whether the heat pump is in hot water produc­tion mode. The heat pump stops at 57ºC for reasons of safety.
The menu shows the temperature of the heat transfer fl uid that is led into the heat pump from the bore hole or the ground. It can vary between -5ºC to +15ºC during a season.
The menu shows the temperature of the heat transfer fl uid that is led out of the heat pump to the bore hole or the ground. Normally, during operations, it is 1.5 - 5.0 degrees lower than the heat transfer fl uid that is led into the heat pump.
Basic functions - Customer level 1
Temperature readings
Return radiator GT1
Off 41.3
O
Now 40.3
O
Return
Temperature readings
Out GT2
14,0°
Return
Temperature readings
Hot water GT3 Set 51,0° Now 50.0° Return
Temperature readings
Shunt, fl ow GT4 Tgt 40,3° Now 43.0° Return
Temperature readings
Room GT5
Tgt 20.0°
Now 19.5°
Return
Temperature readings
Compressor GT6
90,0°
Return
Temperature readings
Heat trfl uid out GT8
45,0°
Return
Temperature readings
Heat tr fl uid in GT9
40,3°
Return
Temperature readings
Ht trfl d(coll)inGT10
0,0°
Return
Temperature readings
Httrfl d(coll)outGT11
-4,0°
Return
21
FOR THE USER
Extra functions ( Customer level 2)
In the section Basic functions (Customer level 1) we presented the functions that you will probably use the most and which you will receive the most benefi t from. However, there are numerous extra functions that you can use to control your heat pump. This can, for example, include activating the heat pump’s holiday function or setting the time and date. If no settings are made on Customer level 2 (K2), the menu display will automatically return to Customer level 1 (K1) after 30 minutes. Proceed as follows to access the extra functions on Customer level 2:
1. Press the Heat button until Access = CUSTOMER2 is displayed.
2. Press the Menu button to open the Main menu From Customer level 2 you also have access to all Customer level 1 functions.
Note
You also have access to all the basic functions on Customer level 1 from Customer level 2.
Only the most frequently used menus in Customer level 2 are shown in the menu outline. All the menus cannot be pre­sented due to space limitations. Use the menu dial to scroll through the menus.
Press the Heat button until Access = CUSTOMER2 is displayed.
( Initial menu)
Extra functions - Customer level 2
The menu display is standard on all heat pumps.
=
=
The menu display is only shown on the heat pump in combination with an extra sensor or for a specifi c model of Greenline HT Plus.
Heat curve adjust. (break) 1.3
Page 22
Main menu Indoor temperature settings 1
Page 23
Mix. valve incr/decr range 0-10 1.5
Page 23
Mix. valve fi ne-tune range -10/+10 1.6
Page 23
Adjusting mix. valve curve (break) 1.7
Page 23
Setting of room sensor infl 1.11
Page 22
Setting of holiday function 1.12
Page 22
Remote control temperature 1.13
Page 22
Setting of summer disconnection 1.14
Page 22
Main menu Adjusting the hot water settings 2
Page 24
Interval for hot water peak 2.2
Page 24
Main menu Timer control accord. to clock 4
Page 24
Clock setting HP accord. to clock 4.1
Page 24
Setting level heat pump +/- 4.1.1
Page 25
Clock setting DHW accord. to clock 4.3
Page 25
Main menu Op. time readings on HP and add. heat 7
Page 25
Heat pump in operat. number of hours? 7.1
Page 26
Distribution HP DHW-Rad in % 7.2
Page 26
Add. heat in operat. number of hours? 7.3
Page 26
Distribut. add. heat DHW-Rad in % 7.4
Page 26
Main menu Clock, setting time and date 10
Page 27
Main menu Alarm logging of all alarms 11
Page 27
Main menu
Return to factory settings 12
Page 27
Menu outline for Extra functions (Customer level 2)
Rego 637 K2
040622 16:08:15 Tu Heat Info Menu
Rego 637 K2
040622 16:08:15 Tu Heat Info Menu
22
FOR THE USER
Temperature settings
Proceed as follows to access the temperature settings for the heating on Customer level 2:
1. Press the Heat button until Access = CUSTOMER2 is displayed.
2. Press the Menu button.
3. Press the Select button and scroll through the menus with the menu dial.
Adapting the heat curve
You can “break” the heat curve up or down every fi fth outdoor degree. For example, you can make a hump in the curve at 0ºC. The purpose of breaking the curve is to be able to infl uence the heat pump’s heat produc­tion at extra sensitive outdoor temperatures.
Room sensor infl uence
The menu is only shown for heat pumps having a room sensor installed. You use the menu to set how much the room sensor should infl uence the heat curve. A higher value will have a greater effect. Please note that the room sensor only fi ne-tunes the heat curve. Consequently, it is important the basic setting of the heat curve’s slope and fi ne-tuning are correct.
Holiday mode
The menu is only shown for heat pumps having a room sensor installed. The holiday function gives you the possibility to choose a number of days when the room temperature will be lowered to 15ºC (the temperature is not adjustable). When the days have passed the heat pump returns to the normal heating setting. Hot water production is not affected by the holiday function.
Remote control
The menu is only shown for heat pumps having a room sensor installed. In addition, special remote control equipment is needed. This equipment is available as an accessory. You can switch between the remote control mode and normal mode using a telephone.
Summer disconnection
The function means the heat pump only produces hot water when the outdoor temperature rises above the set value.
Extra functions - Customer level 2
Main menu Indoor temperature settings 1 Return Select
Temperature settings Heat curve adjust. (break) 1.3 Return Select
Temperature settings Setting of room sensor infl . 1.11 Return Select
Temperature settings Setting of holiday function 1.12 Return Select
Temperature settings Remote control temperature 1.13 Return Select
Temperature settings Setting of summer disconnection 1.14 Return Select
Loading...
+ 51 hidden pages