IVT Greenline D14, Greenline D16, Greenline D20, D40, Greenline E20 Manual To Installation, Commissioning And Maintenance

...
Guide to installation,
commissioning and maintenance
Gr eenline D14-D40
Gr eenline E14-E25
Article nr: 290430-9 Version: 4.0
2
3
This guide is designed to describe the operation, installation and maintenance of the heat pump as comprehensively as possible. The description has been written as far as possible so that it can be followed step by step.
Please note that the guide consists of three separate parts, therefore it is espe­cially important that the installation contractor reads the entire manual before commencing installation.
The guide is in two parts, one for the user and one for the installer. The table of contents sets out clearly the various sections of the manual.
Warning! The Rego 600 control unit contains an advanced settings level which should only be accessed by the installer. The end user should never change any settings on this level, since this might cause problems with the operation of the heat pump.
Before the heat pump is commissioned, the heating system and the heat pump
must be filled and vented.
Hot and cold connections might need checking after delivery.
If the heat pump has to be carried down steps or stairs it can be tilted temporar-
ily with the compressor downwards, but never for long periods.
The heat transfer fluid system must be in operation when venting the system.
See chapter on refilling the heat transfer circuit.
Three phase heat pumps incorporate an alarm if the phasesare incorrectly wired.
IVT Industrier AB
October 2003
4
PAGES FOR THE HOUSE OWNER
Table of Contents
Important information ............................................................................................................. 3
This is how your heat pump works: ......................................................................................... 7
Heat pump technology .............................................................................................................................................7
Heat pump components ............................................................................................................8
Greenline 14-16 .......................................................................................................................................................... 8
Greenline 20-40 .......................................................................................................................................................... 9
Principle.................................................................................................................................. 10
Principle of heating and hot water control .............................................................................................................. 10
Power failures.......................................................................................................................................................... 10
Three different operating modes ............................................................................................ 10
Operating mode A (E and D series) ......................................................................................................................... 10
Operating mode B (D series only) ........................................................................................................................... 10
Operating mode C (D series only) ........................................................................................................................... 10
Controls.................................................................................................................................... 11
Curve control (operating modes A and B) ............................................................................................................... 11
Room sensor (operating modes A and B)................................................................................................................ 11
Fixed temperature (operating mode C only) ............................................................................................................ 11
Control panel .......................................................................................................................... 12
Control panel buttons and displays ........................................................................................................................ 12
How to use the control panel .................................................................................................................................. 13
Examples of scrolling information on the display .................................................................................................... 13
Basic functions and settings at customer level 1 .................................................................. 14
Temperature settings ............................................................................................................................................. 1 4
Extra hot water ...................................................................................................................................................... 14
Reading temperatures ........................................................................................................................................... 14
Extra functions and settings at customer level 2 .................................................................. 15
Line 1
Room sensor influence .......................................................................................................................................... 15
Holiday function ................................................................................................................................................... 15
Remote control ...................................................................................................................................................... 15
Summer disconnection .......................................................................................................................................... 15
Line 2
Interval for hot water peak ................................................................................................................................... 15
Line 4
Timer control ......................................................................................................................................................... 16
Line 7
Display, operating times ....................................................................................................................................... 17
Line 10
Setting the clock ................................................................................................................................................... 17
Line 11
Checking stored alarms ........................................................................................................................................ 17
Line 12
Reset to factory settings ........................................................................................................................................ 17
5
PAGES FOR THE INSTALLER
Setting the heating ................................................................................................................. 18
How to increase or reduce the heating in your house ............................................................................................ 18
The appearance of the heat curve ........................................................................................................................... 18
Fine-tuning ............................................................................................................................................................. 19
Fixed temperature (D series only) ......................................................................................... 20
Setting the heating at fixed temperature .................................................................................................................. 20
Simple tips for saving ............................................................................................................. 20
Utilising the heat pump in the right way ................................................................................................................. 20
All sensor temperatures .......................................................................................................... 21
Description of all the temperature you can see ....................................................................................................... 21
If something goes wrong ........................................................................................................ 22
Alarm examples and what to do .............................................................................................................................. 22
If the control panel is dark ...................................................................................................................................... 22
All the alarms visible in the control panel ............................................................................................................... 23
Emergency operation, E series ............................................................................................... 27
How to activate emergency operation .................................................................................................................... 27
Maintaining your heat pump ................................................................................................. 27
Working on the heat pump ..................................................................................................................................... 27
Normal maintenance ................................................................................................................................................ 27
Where the various parts are located ...................................................................................... 28
Greenline 14-16 ........................................................................................................................................................ 28
Greenline 20-40 ........................................................................................................................................................ 29
What the shipment includes ................................................................................................... 30
Standard components ............................................................................................................................................. 30
Accessories ............................................................................................................................................................ 30
General .................................................................................................................................... 30
Temperatures .......................................................................................................................................................... 30
Particle filter ............................................................................................................................................................ 30
Transportation ........................................................................................................................................................ 30
Positioning the heat pump ...................................................................................................................................... 30
Dimensions and connections ................................................................................................. 31
Pipe and electrical connections in Greenline 14-16 ................................................................................................. 31
Pipe and electrical connections in Greenline E20-E25 ............................................................................................. 32
Pipe and electrical connections in Greenline D20-D40 ............................................................................................ 33
Collector.................................................................................................................................. 34
Collector hose ......................................................................................................................................................... 34
Bending diameter .................................................................................................................................................... 34
Maximum lengths .................................................................................................................................................... 34
Connecting the collector to the heat pump ............................................................................................................. 35
Ground water system .............................................................................................................................................. 35
Connecting the heat pump to the heating system ................................................................. 36
General .................................................................................................................................................................... 36
Function E14-E25, work tank and coil tank (outline diagram) ................................................................................. 37
Function E14-E25, radiators and double shelled electric water heater (outline diagram) ........................................ 38
Function D14-D40, oil-fired boiler, radiators and coil tank (outline diagram) ......................................................... 39
Function D14-D40, new electric boiler, radiators and coil tank (outline diagram).................................................... 40
Connecting the 3-way valve, D series ..................................................................................................................... 41
6
Filling ..................................................................................................................................... 41
Filling the radiator system ...................................................................................................................................... 41
Filling of heat transfer fluid .................................................................................................................................... 41
Electrical connections ............................................................................................................ 43
Circuit diagram, Greenline D14-D16. Factory connections ..................................................................................... 43
Circuit diagram, Greenline E14-E16. Factory connections ...................................................................................... 44
Circuit diagram, Greenline D20-D40. Factory connections ..................................................................................... 45
Circuit diagram, Greenline E20. Factory connections ............................................................................................. 46
Circuit diagram, Greenline E25. Factory connections ............................................................................................. 47
External connections in the E series ....................................................................................................................... 48
External connections in the D series ...................................................................................................................... 49
Connecting the general alarm ................................................................................................................................. 50
Connecting the external input ................................................................................................................................ 50
Connecting the load guard .................................................................................................................................... 50
Control unit Rego 600 ............................................................................................................ 51
Installer/service settings ......................................................................................................................................... 51
Installer/service menu ............................................................................................................ 51
Joint displays for operating modes A, B and C ...................................................................................................... 51
Adapting the heating curve .................................................................................................................................. 51
Clock setting of additional heat ........................................................................................................................... 51
Select operating mode .......................................................................................................................................... 51
Manual control ..................................................................................................................................................... 51
Quick restart of heat pump .................................................................................................................................... 52
Selecting external controls ................................................................................................................................... 52
Choice of language ............................................................................................................................................... 52
Selecting operating modes for heat carrier pump, G2 (P2) ................................................................................. 52
Selecting operating modes for heat transfer pump, G3 (P3) (natural cooling) .................................................. 52
Version number display......................................................................................................................................... 52
Extra sensor acknowledgement ............................................................................................................................ 52
Timer reading ......................................................................................................................................................... 53
Status of the timers when checking the plant ....................................................................................................... 53
Setting additional timers ...................................................................................................................................... 53
Commissioning the heat pump .............................................................................................. 54
Navigating the menu list ........................................................................................................................................ 54
General ................................................................................................................................................................... 55
Manual testing the functions ................................................................................................................................. 55
Operation with additional heat only ....................................................................................................................... 55
Putting into operation, operating mode A (D and E series) .................................................................................... 55
Putting into operation, operating mode B (D series only) ...................................................................................... 57
Putting into operation, operating mode C (D series only) ...................................................................................... 59
Important points to check ...................................................................................................................................... 60
Technical information ............................................................................................................ 60
Table of factory settings ........................................................................................................................................ 60
Technical spec. ...................................................................................................................................................... 61
Table of selected output in display P5.2 ................................................................................................................ 61
Sensor table ........................................................................................................................................................... 61
7
Rock/Ground/Lake
Heating system
Hot water
3-way valve (E series only)
Pressure switch
Heat transfer
fluid pump
Compressor max
Electric water heater
(E series only)
Evaporator
Heat carrier pump
Sight glass
Expansion valve
Pressure
switch
CondenserFilter
This is how your heat pump works
Heat pump technology
The compressor, which is driven by an electric motor, forces the heat transfer fluid into the heat pump condenser as a gas at about 100°C. The gas and the water from the radiator system pass through the condenser, which is a fully-welded stainless steel heat exchanger. When the hot gas is cooled by the circulating water, it condenses (changes to liquid). As it does so, it provides energy for the heating system or the hot water. After the condenser, the refrigerant, which is now in liquid form, continues through a drying filter and a tank. The filtercollects any moisture in the system and the tank is used as an expansion vessel for the heat transfer fluid to ensure there is always the correct amount in the condenser.
After the filter, the heat transfer fluid passes through a sight glass. The sight glass is used to check the amount of heat transfer fluid in the system. In normal operation there should be no bubbles in the sight glass. However, bubbles may appear for short periods, mainly on rapid changes between hot water and radiator operation and when the heat pump starts or stops.
After the sight glass the heat transfer fluid goes to an expansion valve. The valve acts as a flow restrictor between the high and low pressure sides of the system. The valve, which has a sensor (bulb) just before the compressor, releases the right amount of liquid into the next heat exchanger, the evaporator. In the evaporator, the liquid meets the circulating heat transfer fluid coming from the energy source in the ground or bore hole. In this process, the liquid turns to gas (evaporates) under low pressure, which uses heat. The heat is extracted from the outside air free of charge.
After passing through the evaporator, the heat transfer fluid is once more in the form of a gas (va­pour). The expansion valve sensor constantly checks that the evaporator is performing optimally, in order to use as much free energy as possible. The gaseous refrigerant then goes to the suction side of the compressor, where it is compressed again. This completes the heat transfer fluid circuit.
Pressure switches are fitted on the high and low-pressure sides of the system to protect the heat pump. These shut down the heat pump if the pressure in the system reaches an abnormal value. This is dealt with in more detail in the section on troubleshooting.
8
3- way valve that
alternates between
heating and hot water.
Reset buttonfor over-
heat protectionon the
electric heater.
Cleanable particle filter
with cut-off.
Electric boiler.
Circulation pump on
the hot side (G2 (P2)).
Flexible hoses on the
hot side for vibration
free operation.
Condenser.
Compressor with
frequency adapted
soundproof cover.
Electrical connections.
Control panel with large display.
Sealed electrical box with resetting of the motor cutout and circuit breaker for heat pump and electric heater.
Circulation pump on the cold side (G3 (P3)).
Control unit Rego 600.
Evaporator.
Sight glass.
Expansion valve.
Greenline 14 and 16 components
NOTE: The picture is of the E series
The D series has two connections on the hot side and does not include a 3-way valve and electric water heater. The particle filter is supplied separately and is mounted outside the heat pump.
9
3- way valve that
alternates between
heating and hot
water.
Reset button for
overheat protec-
tion on the electric
water heater.
Circulation pump
(G2 (P2)) on the
hot side.
Electric boiler.
Frequency
adapted sound-
proof cover.
Electrical connec­tions.
Control panel with large display.
Circulation pump on the cold side (G3 (P3)).
Sealed electrical box with resetting of the motor cutout and circuit breaker for heat pump and electric heater (the box is shown folded up).
Flexible hoses on the hot and cold sides for vibration free operation.
Sight glass.
Greenline 20 – 40 components
NOTE: The picture is of the E series
The D series has two connections on the hot side and does not include a 3-way valve and electric water heater. The particle filter is supplied separately and is mounted outside the heat pump.
10
Principle
Principle of heating and hot water control
Your heat pump is fitted with a Rego 600 control unit to guarantee you maximum savings and many years of service. The unit, which has advanced monitoring functions, controls the heating and hot water in your home. This ensures that all vital functions are monitored and that, if problems arise, the heat pump is shut down before it is damaged.
When the heat pump is not able to meet the heating requirements, supplementary heat is connected that together with the heat pump provides the required temperature. The Greenline E series has a built-in electric heater that can be connected in three steps. The supplementary heat only provides the output that the heat pump cannot generate and in this way can never take over heating the house completely. When the heat pump is once more able to meet the heating demand, the supplementary heat is automatically switched off. An oil-fired boiler is normally used to provide supplementary heat for the Greenline D series. In which case Rego 600 controls the oil-fired boiler and the existing mixer valve.
The heat pump is connected to the return line of the heating system so that it always receives the coldest water. The water is heated in the heat pump and is then fed back to the heating system. While the heat pump is heating the domestic hot water by using the electric water heater, the heating system is disconnected temporarily through the three-way valve. A sensor in the hot water cylinder makes sure that priority is always given to heating the hot water. When the water in the cylinder reaches the required temperature, heat is once more supplied to the heating system.
Power failures
If the power supply fails, the control unit remembers all its settings and re-starts the heat pump when the power returns.
Three different operating modes
The control unit can be used for three different operating modes: A, B and C. The three operating modes are described schematically in the Installer chapter.
Operating mode A (D and E series)
This is the factory setting, based on an outdoor sensor and controls the heating temperature through an adjustable control curve. Water heating takes priority over space heating. As well as operating the heat pump, Rego 600 can also regulate other heat curves with a mixing valve, e.g. through a combination of radiator and floor heating systems. An electric water heater is used for additional heat.
Operating mode B (D series only)
Used when additional heat is from an oil-fired boiler. Operation is the same as for operating mode A. Rego 600 cannot control other heat curves in this operating mode.
Operating mode C (D series only)
Used in exceptional cases, it does not provide optimal operation for the heat pump because it always works with a high temperature, or “Fixed Temperature”. This is often used in operation with one or more accumulator tanks. The tank is always kept at a high temperature and the hot water is often heated in one or more coils.
11
Controls
The control unit operates the heat pump in three ways. We call them Curve Control, Room Sensor and Fixed Temperature. Below follows a brief description.
Curve control (operating modes A and B)
This is the most common mode and is also the factory setting. With curve control, the heat pump adapts the heating inside the house on the basis of the outside temperature. An outside sensor sends signals to the control unit, which automatically adjusts the supply of heat to the heating system. This maximises savings, since the heat pump never needs to work at a higher temperature than necessary. The heat pump only delivers the maximum temperature when heating the hot water. Normally, hot water heating accounts for 20% of the total annual energy requirement.
Room sensor (operational modes A and B)
A room sensor can be connected to the heat pump. It sends signals to the control unit and in this way affects the curve control. The sensor influences the curve control and the amount of influence can be set on the control panel. Normally, room sensors are only used when a fan-assisted radiator is used in a house with direct electric heating or when a wood-burning stove is used in the house or where the house is effected by wind chill or solar gain.
Fixed temperature (operating mode C only)
This control technique is rarely used, and does not offer optimum savings from the heat pump. The principle is that the heat pump is switched on and off by the built-in return sensor and always works up to its maximum working temperature. The normal area of use for this is together with existing accumulator tanks.
12
Control panel
Control panel buttons and displays
The control panel is the heart of your heat pump installation. From the control panel, instructions are sent to the Rego 600 control unit, which ensures that the house is uniformly heated. All settings are carried out here and the display shows the settings that have been set.
Rego600 K1
020301 12.00.00 Fr Heat Info Menu
The heat pump is in operation when this lamp is lit.
This lamp is lit when the heat pump needs additional heat.
This lamp is lit when hot water is being heated. It blinks during hot water peaks and additional hot water.
This lamp blinks when a fault has occurred.
This switch is used to turn the heat pump on and off. The heat pump is in operation when the lamp is lit The heat pump is off when it blinks.
This dial is used to navigate the menu and to change settings.
This shows you which user level you are in.
This display shows informa­tion such as text and tempera­tures.
Press once to come to the complete menu for settings and temperatures.
Press once for continuous informa­tion about operation conditions for the heat pump and additional heat.
Press once for a short cut to the heating settings.
13
Examples of scrolling information
Here are some of the displays you see if you choose scrolling information with the “Info” button:
Heat pump is not operating.
The heat pump is producing hot water and you see the current temperature and the temperature it stops at.
The heat pump and additional heat is in operation.
A need for heat has arisen and the heat pump is waiting for the reset time to count down to zero.
STANDBY No rad heat required No hot water required
HOTWATER MODE Heat pump only Stop temp 47.5° Present temp 42°
HEAT RAD MODE Compr. + Add. heat Stop temp 45° Present temp 44°
HEAT RAD REQUIRED Heat pump starts in 320 seconds
How to use the control panel
With the help of three buttons and a dial you can navigate to the various displays for settings and readings. The last line at the bottom of the display contains information about the functions of the buttons in the current display. If you choose “Heat” or “Info” the display you have chosen to stay in will always remain.
Press “Heat” once more and you come to the shortcut for heat settings. You can choose to stay in which display you want.
Press “Info” once and you receive continuous information about what the heat pump is doing and at which temperature it stops at. You can choose to remain in this display and always receive this information. Press the middle button again to return to the first display.
Press “Menu” once and you come to the main menu for settings or temperature readings.
With the dial you navigate up and down between the displays or change the settings.
Rego600 K1
020301 12:00:00 Fr Heat Info Menu
14
House heating settings in areas 0 to 10. See more detailed description in “Heat Settings” chapter.
Fine adjustment settings in areas -10°C to 10°C. See more detailed description in “Heat Settings” chapter.
Here you can set the heat in areas 0 to 10 if you use an extra heat curve with a mixing valve.
Here you set the fine adjustment of the mixing valve curve in –10°C to 10°C.
If a room sensor is connected you can set the required room temperature here. On customer level 2 you can set how much you want the sensor to affect the heating sys­tem.
You can temporarily increase the hot water temperature with the electric water heater here. The heat pump first increases it to around 50°C and then the electric water heater to around 65°C. The electric heater starts again at 60°C and increases the temperature to 65°C in the set time. The area is 1-48 hours and when the set time has elapsed the settings must be repeated in order to receive extra hotwater.
With extra sensor only.
With extra sensor only.
With extra sensor only.
Operat­ing mode A only.
The radiator temperature settings you make in the short cut to “Heat” can also be made on row 1 and for the hot water setting on row 2.
In row 3 you can see all the temperatures where sensors are connected.
Main menu Monitor all temperatures 3 Return Select
Main menu Indoor temperature settings 1 Return Select
Extra hotwater
1h 0h 48h Return Adjust
Room temperature
10° 20° 30° Return Adjust
Mix. valve fine-tune
-10° 0,0° 10° Return Adjust
Mix. valve incr/decr
0 4 10 Return Adjust
Temp. fine-tune
-10° 0,0° 10° Return Adjust
Temp. incr. / decr.
0 4,0 10 Return Adjust
Basic functions (customer level 1)
Heating and extra hot water
Press “Heat” to come to the short cut to the heat settings. These displays are then available.
Rego600 K1
020301 12:00:00 Fr Heat Info Menu
Temperatures
Press “Menu” to come to the main menu. Where you can also carry out heat settings and see the temperatures. These displays are then available.
15
You have pressed “Menu” and are on row 1. Press “Se­lect” and turn the dial and the display will scroll. You can then choose to enter the display you require. Each display has a number.
With a room sensor installed you can set the value here how much you want it to affect the outdoor sensor. A high value gives more effect from the room sensor. Please note the
room sensor only fine tunes the heat curve. It is there­fore important that you set the basic settings for the heat curve and fine tuning from the start.
If a room sensor is installed you can utilise the holiday mode function, you can set the number of days that the room temperature is lowered to 15°C here. The temperature is not adjustable and it does not affect the hot water. Normal operation is resumed when the period is over.
If a room sensor and remote control is installed you can set the required room temperature here. You can then use the telephone to increase the temperature to normal. This equipment is available as an accessory.
At this set temperature the heat pump only produces hot water.
Line 1
With extra sensor and in ope­rating mode A only
With extra sensor only
With extra sensor, remote control and in operating mode A only
Operating mode A and B only
Operating mode A only
Using the dial you have moved to the hot water settings in row 2.
Setting intervals for the continual raising of the hot water temperature. If you choose for example 7 days, the tem­perature is raised using the electric water heater once a week to around 65°C (Operating mode A with electric water heater only).
Line 2
Hot water setting Interval for hot water peak 2.2 Return Select
Main menu Adjusting the hot water settings 2 Return Select
Temperature settings Setting of summer disconnection 1.14 Return Select
Temperature settings Remote control temperature 1.13 Return Select
Temperature settings Setting of holiday function 1.12 Return Select
Temperature settings Setting of room sensor infl. 1.11 Return Select
Main menu Indoor temperature settings 1 Return Select
Enhanced functions
As a user you have access to enhanced functions. Keep the “Heat” button pressed down for five seconds and go into ”Menu” to gain access to these displays. You will automatically return to level 1 again after 30 seconds.
Keep the button pressed down for 5 seconds.
Rego600 K2
020301 12:00:00 Fr Heat Info Menu
16
Line 4
You have now moved to timer control settings line 4.
Here you can set the times, day for day, that you want to utilise the clock settings. You can set all the weekdays independently of each other. Press “Select”.
The example describes how you set Monday between 22:00 and 06:00. Press “Adjust”.
There is now a cursor under Monday. Turn the dial and mo becomes Mo. Monday is now activated.
Now set the clock setting to between 22:00 and 06:00 in the morning. Press the right arrow button until the cursor is under the first 00. Turn the dial until 22:00 appears. Press the button twice more (the cursor moves two steps to the right) and turn the dial until 06:00 appears. Press the ”right arrow” button once more and the arrow is replaced by “Save”. Press “Save” to set the timer controls.
You can now do the same for all the other days of the week you want to timer control. Use the dial in this display to access other days.
In display 4.1.1 you set how much you want the tempera­ture to be raised or lowered in the above time zone set­tings. If you choose, for example, –5°C the heating system temperature is lowered by 5°C.
In display 4.3 you can disconnect the hot water completely during e.g. peak rate times. This is done in the same way as with the heat pump time controls.
Not operating mode C
Tidsstyrning Tidsstyrning tillsk. enligt klocka 4.2 Tillbaka Välj
Clock setting Setting level heat pump +/- 4.1.1 Return Select
Clock setting HP 1 Mo 22:00-06:00
Return Adjust
Clock setting HP 1 Mo 22:00-06:00 ^^ Cancel <- ->
Clock setting HP 1 Mo 00:00-00:00 ^^ Cancel ->
Clock setting HP 1 mo 00:00-00:00
Return Adjust
Clock setting Clock setting HP accord. to clock 4.1 Return Select
Main menu Timer control settings 4 Return Select
17
Line 7
Not operating mode C
Not operating mode C
Line 10
Line 11
Line 12
Main menu Return to factory settings 12 Return Select
Main menu Alarm logging of all alarms 11 Return Select
Main menu Clock, setting time and date 10 Return Select
Op. time readings Distribut. add. heat DHW-Rad in % 7.4 Return Select
Op. time readings Add. heat in operat. number of hours? 7.3 Return Select
Op. time readings Distribution HP DHW-Rad in % 7.2 Return Select
Op. time readings Heat pump in operat. number of hours? 7.1 Return Select
Main menu Op. time readings on HP and add. heat 7 Return Select
In line 7 you can read the running times for the heat pump and additional heat. Press “Select” to enter these menus.
Here you can see how many hours the heat pump has been in operation.
This shows the distribution of the heat pump between hot water and heating as percentages.
Here you can see how many hours the additional heat has been in operation.
This shows the distribution of the additional heat between hot water and heating as percentages.
You can set the heat pump’s clock to the correct time if it is wrong on line 10.
Line 11 shows a record of the alarms that may have oc­curred on your heat pump. You can see the type of alarm and when it occurred. An * in the display means the alarm is still active.
If you want to change your settings at customer levels 1 and 2 you can return to factory settings on line 12.
Please note: If you are on the installer/service level when you choose factory settings, the installer must carry out a new start-up of the plant with the new settings. The installer/ service level is for installer only. As an end-user you should never go into this level!
18
Cold weather:
If the indoor temperature is too low or too high during cold weather, you use Temp. incr./decr. to change it. Press “Heat”.
The set value is shown on the display; in the shape of a bar but also as a digit. The range is between 0 and 10. Press “Adjust”.
Turn the dial to the right to increase, to the left to decrease. The example shows how you increase the value to 5. Turn the dial until 5 appears on the display. The new value now appears on the display. Press “Save” to save the new value.
Rego600 K1
020301 12.00.00 Ti Heat Info Menu
Temp. incr. / decr.
0 4 10 Return Adjust
Temp. incr. / decr.
0 5 10 Return Save
Setting the heating
In the Temperature “increase/decrease” display you use the dial to change the heat curve. The lines show how the return temperature varies with the outside temperature for different set­tings. The colder the weather the warmer the heating system. Curve 4 is the factory setting and in the example you can see that this gives a return temperature of around 35°C at an out­door temperature of 0°C.
Please note that the flow temperature is then around 7-10°C warmer. During the first winter, the heating curve must be set up so that the temperature in the house is pleasant whatever the weather. You should adjust the heating curve when the outdoor temperature is around 0ºC. You should wait two days after adjusting before carrying out any readjustments.
Rego600 K1
020301 12:00:00 Fr Heat Info Menu
The example describes how to change the “heat curve” in the Heating increase/decrease menu. Please note that a high value could cause the heat pump to stop if the return temperature is too high.
Heat curve
Radiator return
temperature
Setting
Outdoor temperature
The appearance of the heat curve
The limit when the heat pump stops for a too high a return tempera­ture.
The line shows that if heat curve 4 is chosen, the heat pump stops at around 35°C when the outdoor tempera­ture is 0°C.
19
Warm weather (above +5ºC): If the indoor temperature is too low or too high during warm weather, you use fine tuning to change it. You come to Temp. Fine Tuning by pressing “Heat” and turning the dial to the right.
Fine tuning can be set in areas –10°C to 10°C. You change the fine tuning in the same way as “Temp. increase/de­crease” as described on the previous page.
The heat curve can also be fine tuned. You do this in the “Temp. fine tune” display. The dotted line illustrates how the parallel offset has been turned towards plus. The entire curve moves upwards, in contrast to increasing the slope, when only the slope changes.
The dotted line illustrates how the fine tuning adjust­ment has been turned towards plus.
Fine tuning adjustment
Radiator return
temperature
Outdoor temperature
Rego600 K1
020301 12:00:00 Fr Heat Info Menu
Temp. fine-tune.
-10° 0,0° 10° Return Adjust
20
Fixed temperature (D series only)
If the heat pump is set at operating mode C with a fixed temperature, then it can only be engaged and disengaged by the built-in return sensor. There are two displays available for this mode. Please note that if a mixing valve is connected to the heat pump, the “Temp. incr/decre” and “Temp. fine tune” displays control the settings for the mixing valve opening to the heating system.
Rego600 K1
020301 12.00.00 Ti Heat Info Menu
To adjust the engaging and disengaging temperature, press “Menu” followed by “Select”. You are now in line 1.
Use the dial to navigate to display 1.16 and press “Select”.
The factory setting is 48°. Please note that this concerns the engaging temperature to the heat pump. The temperature from the pump is normally 5-10°C higher. Settings above 48°C are not recommended for technical reasons.
You can also set the difference between engaging and disengaging the heat pump in display 1.17. The factory setting is 5ºC. A lower setting results in the heat pump starting and stopping more frequently. Press “Select” to adjust.
Simple tips for saving
The lower you can keep the temperature of the heating system in the house, the better your heating economy will be. So make sure not to set your heat curve too high. It is important that the heating system is carefully balanced so that all parts or the heat emitters (radiators or underfloor) are at the same temperature.
Thermostatic valves on your radiators or floor heating may have a negative effect on your heating system because they restrict the flow so that the system has to compensate with a higher water temperature. If thermostat valves are fitted, they should be fully opened, except in bedrooms, where they can be turned down slightly.
Temperature settings Return thermostat stop temp sett. 1.16 Return Select
Return thermos. stop
30° 48° 50° Return Adjust
Temperature settings Return thermostat hysteresis set 1.17 Return Select
Loading...
+ 46 hidden pages