IVT GreenlineC, GreenlineE, GreenlineD Manual To Installation, Commissioning And Maintenance

Guide to installation,
commissioning and maintenance
Article nr: 290407-9 Version: 5.1
Greenline
C, D and E
3
This guide was designed to describe the operation, connection and maintenance of the heat pump as comprehensively as possible. As far as possible, the description has been written so that it can be followed step by step.
Please not that the guide consists of three separate series so it is especially important that the installation contractor reads the entire manual before commencing installa­tion.
The guide is in two parts, one for the user and one for the installer. The table of con­tents sets out clearly the various sections of the manual.
Warning! The Rego600 control unit contains an advanced settings level which should only be accessed by the installer. The end user must never change any settings on this level, since this might have serious consequences for the operation of the heat pump.
Before the heat pump is commissioned, the heating system and the heat transfer fluid
system, as well as the heat pump itself, must have been filled and vented. The heat transfer fluid system must be filled with antifreeze (-15°C).
Hot and cold connections might need checking after delivery.
If the heat pump has to be carried down steps or stairs it can be leaned temporarily
with the compressor downwards, but never for longer periods.
The heat transfer fluid system must be in operation when venting the system. See
chapter on refilling the heat transfer circuit.
The control unit measures the phase sequence and alarms if the power is connected
wrongly (only 3-phase units).
IVT Industrier AB
June 2003
4
PAGES FOR THE HOUSE OWNER
This is how your heat pump works:_____________________________________________ 7
Heat pump technology _______________________________________________________________________ 7
Heat pump components ______________________________________________________ 8
C series components ________________________________________________________________________ 8 D and E series components ___________________________________________________________________ 9
Principle _________________________________________________________________ 10
Principle of heating and hot water control ______________________________________________________ 10 Power failures ____________________________________________________________________________ 10
Three different operating modes ______________________________________________ 10
Operating mode A (not for C, D and E series) ___________________________________________________ 10 Operating mode B (D series only) _____________________________________________________________ 10 Operating mode C (D series only) _____________________________________________________________ 10
Controls _________________________________________________________________ 11
Curve control (operating modes A and B) _______________________________________________________ 11 Room sensor (operating modes A and B) _______________________________________________________ 11 Fixed temperature (operating mode C only) _____________________________________________________ 11
Control panel _____________________________________________________________12
Control panel buttons and displays ____________________________________________________________ 12 How to use the control panel _________________________________________________________________ 13 Examples of scrolling information ____________________________________________________________ 13
Basic functions at customer level 1 ____________________________________________ 14
Heating and extra hot water _________________________________________________________________ 14 Temperatures _____________________________________________________________________________ 14
Extra functions ____________________________________________________________ 15
Line 1
Room sensor affect ________________________________________________________________________ 15 Holiday function __________________________________________________________________________ 15 Remote control ___________________________________________________________________________ 15 Summer mode ____________________________________________________________________________ 15
Line 2
Interval for hot water peak __________________________________________________________________ 15
Line 4
Clock settings ____________________________________________________________________________ 16
Line 7
Display, operating times ____________________________________________________________________ 17
Line 10
Setting the clock __________________________________________________________________________ 17
Line 11
Alarm logging of all alarms _________________________________________________________________ 17
Line 12
Reset to factory settings ____________________________________________________________________ 17
Table of Contents
5
Setting the heating _________________________________________________________ 18
How to increase or reduce the heating in your house ______________________________________________ 18
Fixed temperature (D series only) _____________________________________________ 20
Setting the heating at fixed temperature ________________________________________________________ 20
Simple tips for saving _______________________________________________________20
Utilising the heat pump in the right way ________________________________________________________ 20
All sensor temperatures _____________________________________________________ 21
Description of all temperatures _______________________________________________________________ 21
If something is wrong ______________________________________________________ 22
Alarm examples and what to do ______________________________________________________________ 22 If the control panel is dark ___________________________________________________________________ 22 All alarms _______________________________________________________________________________ 23
Maintaining your heat pump _________________________________________________ 27
Working on the heat pump __________________________________________________________________ 27 Normal maintenance _______________________________________________________________________ 27 Control safety anode _______________________________________________________________________ 28
Where the various parts are located ___________________________________________ 28
The various parts in the C series ______________________________________________________________ 28 The various parts in the D and E series _________________________________________________________ 29
Notes ____________________________________________________________________ 64
What the shipment includes __________________________________________________ 30
Standard components ______________________________________________________________________ 30 Accessories ______________________________________________________________________________ 30
General __________________________________________________________________ 30
Temperatures _____________________________________________________________________________ 30 Particle filter _____________________________________________________________________________ 30 Transportation ____________________________________________________________________________ 30 Positioning the heat pump ___________________________________________________________________ 30
Dimensions and connections _________________________________________________ 31
Dimensions and connections, C series _________________________________________________________ 31 Dimensions and connections, D and E series ____________________________________________________ 32
Collector _________________________________________________________________ 33
Collector hose ____________________________________________________________________________ 33 Bending diameter _________________________________________________________________________ 33 Maximal lengths __________________________________________________________________________ 33 Connecting the collector to the heat pump ______________________________________________________ 34
Switching to side mounting of the fluid transfer system ___________________________ 35
Ground water system _______________________________________________________________________ 37
Connecting to the heating system _____________________________________________ 37
General _________________________________________________________________________________ 37 Connecting the C series to the heating system and operating mode A _________________________________ 38 Connecting the D series to the heating system and operating mode A _________________________________ 39 Connecting the E series to the heating system and operating mode A__________________________________ 40 Connecting the D series to the heating system and operating mode B _________________________________ 41 Connecting the D series to the heating system and operating mode C _________________________________ 42 Connecting the 3-way valve _________________________________________________________________ 43
PAGES FOR THE INSTALLER
6
Filling ___________________________________________________________________ 43
Filling the radiator system ___________________________________________________________________ 43 Filling of heat transfer fluid __________________________________________________________________ 43
Electrical connections ______________________________________________________ 45
Circuit diagram Greenline C series. Factory connections ___________________________________________ 45 Circuit diagram Greenline D series. Factory connections ___________________________________________ 46 Circuit diagram Greenline E series. Factory connections ___________________________________________ 47 Working switch ___________________________________________________________________________ 48 Earth fault breaker _________________________________________________________________________ 48 External connections in the C and E series. _____________________________________________________ 48 External connections in the D series ___________________________________________________________ 49 Connecting the general alarm ________________________________________________________________ 50 Connecting the external input ________________________________________________________________ 50 Connecting the load guard ___________________________________________________________________ 50
Control unit Rego600 ______________________________________________________ 51
Installer/service settings ____________________________________________________________________ 51
Installer/service menu ______________________________________________________51
Joint displays for operating modes A, B and C ___________________________________________________ 51 Adapting the heat curve _____________________________________________________________________ 51 Clock setting of additional heat _______________________________________________________________ 51 Manual control ___________________________________________________________________________ 51 Quick restart of heat pump __________________________________________________________________ 52 Selecting external controls __________________________________________________________________ 52 Choice of language ________________________________________________________________________ 52 Selecting operating modes for heat carrier pump, P2 ______________________________________________ 52 Selecting operating modes for heat transfer pump, P3 (natural cooling) _______________________________ 52 Version number display _____________________________________________________________________ 52 Extra sensor acknowledgement _______________________________________________________________ 52 Timer reading ____________________________________________________________________________ 53 Status of the timers when checking the plant_____________________________________________________ 53 Setting additional timers ____________________________________________________________________ 53 Reset to factory settings ____________________________________________________________________ 53
Commissioning the heat pump _______________________________________________ 54
Navigating the menu list ____________________________________________________________________ 54 General _________________________________________________________________________________ 55 Manual testing ____________________________________________________________________________ 55 Operation with additional heat only ___________________________________________________________ 55 Putting into operation, operating mode A (C, D and E series) _______________________________________ 55 Putting into operation, operating mode B (D series only) ___________________________________________ 57 Putting into operation, operating mode C (D series only) ___________________________________________ 59 Important points to check ___________________________________________________________________ 60 Table of factory settings ____________________________________________________________________ 60
Technical information ______________________________________________________60
Table of selected output in display 5.2 _________________________________________________________ 60 Technical specifications ____________________________________________________________________ 61 Sensor table ______________________________________________________________________________ 61
Service journal ____________________________________________________________ 62
7
This is how your heat pump works:
Heat pump technology
The compressor, which is driven by an electric motor, forces the refrigerant into the heat pump condenser as a gas at about 100°C. The gas and the water from the radiator system pass through the condenser, which is a fully-welded stainless steel heat exchanger. When the hot gas is cooled by the circulating water, it condenses (changes to liquid). As it does so, it provides energy for the heating system or the hot water. After the condensor, the refrigerant, which is now in liquid form, continues through a drying filter and a tank. The filter collects any moisture in the system and the tank is used as an expansion vessel for the refrigerant to ensure there is always the correct amount in the condenser.
After the filter, the refrigerant passes through a sight glass. The sight glass is used to check the amount of refrigerant in the system. In normal operation there should be no bubbles in the sight glass. How­ever, bubbles may appear for short periods, mainly on rapid changes between hot water and radiator operation and when the heat pump starts or stops.
After the sight glass the refrigerant goes to an expansion valve. The valve acts as a flow restrictor between the high and low pressure sides of the system. The valve, which has a sensor (bulb) just before the compressor, releases the right amount of liquid into the next heat exchanger, the evaporator. In the evaporator, the liquid meets the circulating heat transfer fluid coming from the energy source in the ground or bore hole. In this process, the liquid turns to gas (evaporates) under low pressure, which uses heat. The heat is extracted from the the ground or bore hole free of charge.
After passing through the evaporator, the refrigerant is once more in the form of a gas (vapour). The expansion valve sensor constantly checks that the evaporator is performing optimally, in order to use as much free energy as possible. The gaseous refrigerant then goes to the suction side of the com­pressor, where it is compressed again. This completes the refrigerant circuit.
To protect the heat pump, pressure switches are fitted on the high and low-pressure sides of the sys­tem. These shut down the heat pump if the pressure in the system reaches an abnormal value. This is dealt with in more detail in the section on troubleshooting.
Rock/Ground/Lake
Heating system
Hot water 3-way valve
(not D)
Pressure switch
Heat transfer fluid pump
Compressor
Immersion
heater
(not D)
Evaporator
Heat transfer pump
Sight glass
Expansion valve
Pressure switch
CondenserFilter
8
C series components
Please note: The picture shows a 1-phase unit.
3-way valve that switches
between heating and
domestic hot water.
Double-shelled
hot water heater.
Immersion heater.
Reset button for overheat protection on the immer­sion heater.
Circulation pump on
the hot side.
Flexible hoses on the hot side
for vibration free operation.
Frequency adapted sound-
proof cover on compressor.
Electrical connection.
Control panel with large display.
Enclosed electrical box with motor protection reset and circuit breaker for heat pump and immer­sion heater.
Control unit Rego600.
Insulated corrosion protected circulation pump for the heat transfer fluid system.
Expansion valve.
Sight glass.
9
D and E series components
Please note: The picture is of the E series, 1-phase.
The D series has two connections on the hot side and does not include a 3-way valve and immersion heater. The particle filter is supplied separately and is mounted outside the heat pump.
3-way valve that changes
between heating and
domestic hot water.
Cleanable particle
filter with cut-off.
Immersion heater.
Reset button for over­heat protection on the immersion heater.
Circulation pump
on the hot side.
Flexible hoses on the hot side for vibration
free operation.
Frequency adapted
soundproof cover.
Electrical connection.
Control panel with large display.
Enclosed electrical box with motor protection reset and circuit breaker for heat pump and immersion heater.
Control unit Rego600.
Heat exchanger.
Insulated corrosion protected circulation pump for the heat transfer fluid system.
Compressor.
Expansion valve.
Sight glass.
10
Principle
Principle of heating and hot water control
Your heat pump is fitted with a Rego600 control unit to guarantee you maximum savings and many years of service. The unit, which has advanced monitoring functions, controls the heating and hot water in your home. This ensures that all vital functions are monitored and that, if problems arise, the heat pump is shut down before it is damaged.
When the heat pump is not able to meet the heating requirements, additional heat is connected that together with the heat pump provides the required temperature. The Greenline C and E series has a built-in immersion heater that can be connected in three steps. Factory setting is 2/3 electrical output. The additional heat only provides the output that the heat pump cannot generate and in this way can never take over heating the house completely. When the heat pump is once more able to meet the heating demand, the additional heat is automatically switched off. An oil-fired boiler is normally used to provide additional heat for the Greenline D series. In which case Rego600 controls the oil-fired boiler and the existing mixing valve.
The heat pump is connected to the heating system’s return flow. The water is heated in the heat pump and is then fed back to the heating system. While the heat pump is heating the water in the immersion heater, the heating system is disconnected temporarily through the 3-way valve. A sensor in the hot water cylinder makes sure that priority is always given to heating the hot water. When the water in the cylinder reaches the required temperature, heat is once more supplied to the heating system.
Power failure
If the power supply fails, the control unit remembers all its settings and re-starts the heat pump when the power returns.
Three different operating modes
The control unit can be used for three different operating modes: A, B and C. Please note that the C series can only utilise operating mode A. The three operating modes are also outlined under Installer.
Operating mode A (C, D and E series)
This is the factory set operating mode based on an outdoor sensor that sends signals to the heat pump control unit and controls it through an adjustable control curve. Water heating takes priority over space heating. As well as operating the heat pump, Rego600 can also regulate other heat curves with a mixing valve, e.g. through a combination of radiator and floor heating systems. An immersion heater is used for additional heat.
Operating mode B (D series only)
Used when additional heat is from an oil-fired boiler. Operation is the same as for operating mode A. Rego600 cannot control other heat curves in this operating mode.
Operating mode C (D series only)
Used in exceptional cases, it does not provide optimal operation for the heat pump because it always works with a high temperature, or Fixed Temperature. This is most commonly used together with existing electric boilers. This mode of operation is based on the existing electric boiler’s heater being kept warm by the heat pump and by utilising the existing immersion heater in the boiler.
11
Controls
The control unit operates the heat pump in three ways. We call them Curve Control, Room Sensor and Fixed Temperature. Below follows a brief description.
Curve control (operating modes A and B)
This is the most common mode and is also the factory setting. This means that the heat pump adjusts the heat in the house based on the outdoor temperature so that the radiator temperature increases as the outdoor temperature reduces. An outside sensor sends signals to the control unit, which automatically adjusts the supply of heat to the radiators. To set the temperature of a radiator for a certain outdoor temperature, you can choose between a number of different curves on the control unit. This maximises savings, since the heat pump never needs to work at a higher temperature than necessary. The heat pump only delivers the maximum temperature when heating the hot water. Normally, hot water heating accounts for 20% of the total annual requirement.
Room sensor (operational modes A and B)
A room sensor can be connected to the heat pump. It sends signals to the control unit and in this way affects the curve control. The amount of affect the room sensor has on the curve control can be set on the control panel. The room sensor is normally only used in combination with an outdoor sensor; when a fan-assisted radiator is used in houses with electric radiators or a fire place, or in houses that are wind sensitive.
Fixed temperature (operating mode C only)
This control technique is rarely used, and does not offer optimum savings from the heat pump. The principle is that the heat pump is switched on and off by the built-in return sensor and always works up to its maximum working temperature. The most common use for this control technique is when there is a relatively new electric boiler and the heat pump is connected to it. The heat pump heats the hot water cylinder in the boiler, and any additional heat required is provided by the boiler’ immersion heater. There are unfortunately not many electric boilers on the market that are suitable for use in conjunction with a heat pump.
12
Control panel
Control panel buttons and displays
The control panel is the heart of your heat pump installation. From the control panel, instructions are sent to the Rego600 control unit, which ensures that the house is uniformly heated. All settings are carried out here and the display shows the settings that have been set.
Rego600 K1
020301 12.00.00 Fr Heat Info Menu
The heat pump is in operation when this lamp is lit.
This lamp is lit when the heat pump needs additional heat.
This lamp is lit when hot water is being heated. It blinks during hot water peaks and additional hot water.
This lamp blinks when a fault has occurred.
This switch is used to turn the heat pump on and off. The heat pump is in operation when the lamp is lit. The heat pump is off when it blinks.
This shows you which user level you are in.
This display shows information such as text and temperatures.
Press once to come to the complete menu for settings and tempera­tures.
Press once for continuous informa­tion about operation conditions for the heat pump and additional heat.
Press once for a short cut to the heat settings.
This knob is used to navigate the menu and to change settings.
13
How to use the control panel
With three buttons and a knob you can navigate to the various displays for settings and readings. The last line at the bottom of the display contains information about the functions of the buttons in the current display. If you choose Heat or Info the display you have chosen to stay in will always remain.
Examples of scrolling information
Here are some of the displays you see if you choose scroll­ing information with the Info button:
Heat pump is not operating.
The heat pump is producing hot water and you see the current temperature and the temperature it stops at.
The heat pump and additional heat is in operation.
A need for heat has arisen and the heat pump is waiting for the reset time to count down to zero.
STANDBY No rad heat required No hotwater required
HOT WATER MODE Heat pump only Stop temp 47.5° Present temp 42.0°
HEAT RAD MODE Compr. + Add. heat Stop temp 45.0° Present temp 44.0°
HEAT RAD REQ Heat pump starts in 320 seconds
Press “Heat” once and you come to the shortcut for heat settings. You can choose to stay in which display you want.
Press “Info” once and you receive continuous information about what the heat pump is doing and at which temperature it stops. You can choose to remain in this display and always receive this information. Press the middle button again to return to the first display.
Press “Menu” once and you come to the main menu for settings or temperature readings.
With the knob you navigate up and down be­tween the dis­plays or change the settings.
Rego600 K1
020301 12:00:00 Fr Värme Info Meny
14
Basic functions (at customer level 1)
Heating and extra hot water
Press Heat to come to the short cut to the heat settings. These displays are then available.
House heating settings in areas 0 to 10. See more detailed description in Heat Settings chapter.
Fine adjustment settings in areas -10 to +10. See more detailed description in Heat Settings chapter.
Here you can set the heat in areas 0 to 10 if you use an extra heat curve with a mixing valve.
Here you set the fine adjustment of the mixing valve curve in –10°C to 10°C.
If a room sensor is connected you can set the required room temperature here. At customer level 2 you can set how much you want the sensor to affect the heating system.
You can temporarily increase the hot water temperature with the electric water heater here. The heat pump first increases it to around 50° and then the electric water heater to around 65°. The electric heater starts again at 60° and increases the temperature to 65° in set time. The area is 1­48 hours and when the set time has passed, the normal operation is resumed.
Temperatures
Press “Menu” to come to the main menu. Where you can also carry out heat settings and see the temperatures. These displays are then available.
The radiator temperature settings you make in the short cut to Heat you can also make in line 1 and hot water setting in line 2.
In line 3 you can see all the temperatures where sensors are connected.
With extra sensor only
With extra sensor only
With extra sensor only
Opera­ting mode A only
Extra DHW:
1hr 20hrs 48hrs Return Adjust
Room temperature
10° 20° 30° Return Adjust
Mix. valve fine-tune
-10° 0,0° 10° Return Adjust
Mix. valve incr/decr
0 4 10 Return Adjust
Temp. fine-tune
-10° 0,0° 10° Return Adjust
Temp. incr. / decr.
0 4 10 Return Adjust
Main menu Monitor all temperatures 3 Return Select
Main menu Indoor temperature settings 1 Return Select
Rego600 K1
020312 12.00.00 Ti Heat Info Menu
15
Enhanced functions
As user you have access to extra functions. Keep the Heat button pressed down for five seconds and go into Menu to gain access to these displays. You will automatically return to level 1 again after 30 seconds.
Keep the button pressed down for 5 seconds.
You have pressed Menu and are on row 1. Press “Select” and turn the knob and the displays scroll up. You can then choose to enter the display you require. Each display has a number.
With a room sensor installed you can set the value of how much you want it to affect the outdoor sensor. A high value gives more affect from the room sensor. Please note the
room sensor only fine tunes the heat curve. It is therefore important that you set the basic settings for the heat curve and fine tuning from the start.
If a room sensor is installed you can set the number of days that the room temperature is lowered to 15°C here. The temperature is not adjustable and it does not affect the hot water. Normal operation is resumed when the period is over.
If a room sensor and remote control is installed you can set the required room temperature here. You can then use the telephone to increase the temperature to normal. This equipment is available as an accessory.
At this set temperature the heat pump only produces hot water.
Line 1
Only with extra sensor and at operating mode A only
With extra sensor only
With extra sensor , remote control and at operating mode A only
At operating modes A and B only
At operating mode A only
Using the knob you have moved to the hot water settings in row 2.
Setting for intervals for the continual raising of the hot water temperature. If you choose for example7 days, the temperature is raised using the electric water heater once a week to around 65°C (Operating mode A with electric water heater only).
Line 2
Hot water setting Interval for hot water peak 2.2 Return Select
Main menu Adjusting the hot water settings 2 Return Select
Temperature settings Setting of summer disconnection 1.14 Return Select
Temperature settings Remote control temperature 1.13 Return Select
Temperature settings Setting of holiday function 1.12 Return Select
Temperature settings Setting of room sensor infl. 1.11 Return Select
Main menu Indoor temperature settings 1 Return Select
Rego600 K2
020312 12.00.00 Ti Heat Info Menu
16
Line 4
You have now moved to timer control settings line 4.
Here you can set the times day for day that you want to utilise the clock settings. You can set all the weekdays independent of each other. Press “Select”.
The example describes how you set Monday between 22:00 and 06:00. Press “Adjust”.
There is now a cursor under Monday. Turn the knob and mo becomes Mo. Monday is now activated.
Now set the clock setting for between 22:00 and 06:00 in the morning. Press the right arrow button until the cursor is under the first 00. Turn the knob until 22:00 appears. Press the button twice more (the cursor moves two steps to the right) and turn the knob until 06:00 appears. Press the right arrow button once more and the arrow is replaced by Save. Press “Save” to set the timer controls.
You can now do the same for all the other days of the week you want to timer control. Use the knob in this display to come to the other days.
In display 4.1.1 you set how much you want the temperature to be raised or lowered in the above time zone settings. If you choose for example -5°C, the heating system tempera­ture is lowered by 5°C.
In display 4.3 you can disconnect the hot water completely during e.g. peak rate times. This is done in the same way as with the heat pump time controls.
Not operating mode C
Clock setting Clock setting DHW accord. to clock 4.3 Return Select
Clock setting Setting level heat pump +/- 4.1.1 Return Select
Clock setting HP 1 Mo 22:00-06:00
Return Adjust
Clock setting HP 1 Mo 22:00-06:00 ^^ Cancel <- ->
Clock setting HP 1 Mo 00:00­00:00 ^^ Cancel ->
Clock setting HP 1 Mo 00:00-00:00
Return Adjust
Clock setting Clock setting HP accord. to clock 4.1 Return Select
Main menu Timer control settings 4 Return Select
17
Line 7
Not operating mode C
In line 7 you can read the running times for the heat pump and additional heat. Press “Select” to enter these menus.
Here you can see how many hours the heat pump has been in operation.
This shows the distribution of the heat pump between hot water and heating in percentage.
Here you can see how many hours the additional heat has been in operation.
This shows the distribution of the additional heat between hot water and heating in percentage.
You can set the clock to the correct time if it is wrong.
Line 11 shows a record of the alarms that may have occurred on your heat pump. You can see the type of alarm and when it occurred. An * in the display means the alarm is still active.
If you want to change your settings at customer levels 1 and 2 you can return to factory settings on line 12.
Please note: If you at the level for installer/service when you choose factory settings, the installer must carry out a new start-up of the plant with new settings. The installer/service level is for installer only. As end-user you must never go into this level!
Not operating mode C
Line 10
Line 11
Line 12
Main menu Return to factory settings 12 Return Select
Main menu Alarm logging of all alarms 11 Return Select
Main menu Clock, setting time and date 10 Return Select
Op. time readings Distribut. add. heat DHW-Rad in % 7.4 Return Select
Op. time readings Add. heat in operat. number of hours? 7.3 Return Select
Op. time readings Distribution HP DHW-Rad in % 7.2 Return Select
Op. time readings Heat pump in operat. number of hours? 7.1 Return Select
Main menu Op. time readings on HP and add. heat 7 Return Select
18
Setting the heating
In the Temperature increase/decrease display you use the knob to change the heat curve. The lines show how the return temperature varies with the outdoor temperature for different settings. The colder the weather the warmer the heating system. Curve 4 is the factory setting and in the example you can see that this gives a return temperature of around 35
o
C at an outdoor temperature of 0oC.
The example describes how to change the heat curve in the Heating increase/decrease menu. Please note that a high value could cause the heat pump to stop if the return temperature is too high.
Heat curve
Radiator return
temperature
Setting
Outdoor temperature
The appearance of the heat curve
The limit for when the heat pump stops for too high a return tempera­ture.
The line shows that if heat curve 4 is chosen, the heat pump stops at around 35
o
C when the outdoor temperature is 0
o
C.
Cold weather:
If the indoor temperature is too low or too high during cold weather, you use Temp. incr./decr. to change it. Press “Heat”.
The set value is shown in the display. In the shape of a bar but also as a digit. The area is between 0 and 10. Press “Adjust”.
Turn the knob to the right to increase, to the left to decrease. The example shows how you increase the value to 5. Turn the knob until 5 appears in the display. The new value now appears in the display. Press “Save” to save the new value.
Rego600 K1
020312 12.00.00 Ti Heat Info Menu
Temp. incr. / decr.
0 4 10 Return Adjust
Temp. incr. / decr.
0 5 10 Return Save
Rego600 K1
020312 12.00.00 Ti Heat Info Menu
Please note that the flow temperature is then around 7-10oC warmer. During the first winter, the heat curve must be set up so that the temperature in the house is pleasant whatever the weather. The heat curve should preferably be adjusted at a low temperature under 3
o
C. You should wait two days after adjusting
before carrying out any readjustments. Also note that a lower curve setting gives a lower runnig cost.
19
Warm weather:
If the indoor temperature is too low or too high during warm weather, you use fine tuning to change it. You come to “Temp. fine-tune” by pressing “Heat” and turning the knob to the right.
Fine tuning can be set in areas –10°C to 10°C. You change the fine tuning in the same way as “Temp. increase/de­crease” as described on the previous page.
The heat curve can also be fine tuned. You do this in the Temp. fine tune display. The dotted line illus­trates how the parallel offset has been turned towards plus. The entire curve moves upwards, in contrast to increasing the slope, when only the slope changes.
Rego600 K1
020312 12.00.00 Ti Heat Info Menu
Temp. fine-tune
-10° 0,0° 10° Return Adjust
The dotted line illustrates how the fine tuning adjust­ment has been turned towards plus.
Fine tuning adjustment
Radiator return
temperature
Outdoor temperature
20
Fixed temperature (D series only)
If the heat pump is set at operating mode C with a fixed temperature, then it can only be engaged and disengaged by the built-in return sensor. There are two displays available for this mode. Please note that if a mixing valve is connected to the heat pump, the Temp. incr/decre and Temp. fine tune displays control the settings for the mixing valve opening to the heating system.
To adjust the engaging and disengaging temperature, press “Menu” followed by “Select”. You are now in line 1.
Use the knob to navigate to display 1.16 and press “Se­lect”.
The factory setting is 48°C. Please note that this concerns the return temperature to the heat pump. The temperature from the pump is normally 5-10C higher. Settings above 48°C are not allowed for technical reasons.
You can also set the difference between starting and stopping the heat pump in display 1.17. The factory setting is 5°C. A lower setting gives more frequent starts and stops for the heat pump. Press “Select” to adjust.
Simple tips for saving
The lower you can keep the temperature of the radiators in the house, the better your heating economy will be. So take make sure not to set your heat curve too high. Operate your heating system as effi­ciently as possible by making sure that the entire surface of your radiators or your underfloor heating coils are kept hot.
Thermostatic valves on your radiators or underfloor heating may have a negative effect on your heating system because they restrict the flow so that the system has to compensate with a higher water temperature. If thermostat valves are fitted, they should be fully opened, except in bedrooms, where they can be turned down slightly.
Temperature settings Return thermostat stop temp sett. 1.16 Return Select
Return thermos. stop
30° 48,0° 50° Return Adjust
Temperature settings Return thermostat hysteresis set 1.17 Return Select
Rego600 K1
020312 12.00.00 Ti Heat Info Menu
21
All sensor temperatures
Below are the various sensor temperatures that are visible under line 3 in the control panel. Note that not all the sensors are standard but are available as accessories for different areas of use. To get there press ”Menu” in the control panel and then turn the knob to line 3. Then press ”Select”.
Shows the temperature of the heating system return flow. This varies depending on the outdoor temperature.
Shows the outdoor temperature.
Shows the temperature in the outer container of the electric water heater’s bottom part. This temperature is around 5°C lower than the temperature in the hot water tank.
If an extra mixing valve is used for e.g. floor heating then the flow pipe is visible on the circuit. It varies with the outdoor temperature.
If a room sensor is used, you see the temperature of the room where the sensor is located.
The sensor shows the working temperature of the compres­sor. It varies between around 70°C and 125°C.
The sensor shows the outgoing temperature from the heat pump. It varies depending on the outdoor temperature and if the heat pump is in hot water production mode.
The sensor shows the ingoing temperature to the heat pump. It varies as mentioned above. Please note that for safety reasons the heat pump stops when this shows a temperature of more than 48°C.
The sensor shows the temperature from the bore hole or the ground. It normally varies between -5°C and 8°C throughout the year.
The sensor shows the temperature to the bore hole or the ground. It is normally 1.5°C till 5°C lower than heat transfer in.
Line 3
Standard
Standard
Only in C­serie
Accesso­ries
Accesso­ries
Standard
Standard
Standard
Standard
Standard
Temperature readings Return radiator GT1 Off ##,#° Now ##,#° Return
Temperature readings Out GT2 ###,#° Return
Temperature readings Hot water GT3 Off ##,#° Now ##,#° Return
Temperature readings Shunt, flow GT4 Tgt ##,#° Now ##,#° Return
Temperature readings Room GT5 Tgt ##,#° Now ##,#° Return
Temperature readings Compressor GT6 ###,#° Return
Temperature readings Heat trfluid out GT8 ###,#° Return
Temperature readings Heat tr fluid in GT9 ###,#° Return
Temperature reading Ht trfld(coll)inGT10 ###,#° Return
Temperature reading Httrfld(coll)outGT11 ###,#° Return
22
If something is wrong
The control unit provides a lot of information about faults and how to remedy them. The control unit incorporates advanced functions to monitor and protect your heat pump. This means there is no risk involved in resetting an alarm. If a fault persists, you should contact the installer.
Alarm examples and what to do
If the control panel is dark
Possible faults:
The fuses or MCBs (miniature circuit-breakers) in your fuse box.
This is what to do: Check the fuse (or MCB) for your heat pump. If the small plate at the bottom of the fuse has come off, the fuse has blown and must be replaced. If you have MCBs, and they have tripped, move the switch to the up position.
Note that the heat pump cannot restart until after 15 minutes. This delay is needed for technical reasons!
If the heat pump MCB has tripped, this is what to do:
Press ”Ackn” and the fault is remedied, the alarm lamp goes off and the heat pump starts again within 15 minutes. If the lamp is lit with a steady glow then the alarm is remedied but the fault remains. If several alarms have trig­gered, use the knob to navigate to them.
If you press ”Info” and then turn the knob you will see informa­tion about the possible causes and how you can remedy the fault yourself.
ALARM Power failure 020312 16.08.15 Info Ackn.
Time and date for when the fault occurred.
Cause
On D and E series:
Reset by pushing the toggle to the up position.
The C series
Reset by pushing the toggle to the up position.
Loading...
+ 46 hidden pages