AXA Power, Hobart, Houchin, Military and J&B has become ITW GSE.
As simply ITW GSE, we still offer the same premium products and service.
SAME PEOPLE - SAME PRODUCTS - SAME COMPANY
Operation Manual - ITW GSE 6400 Tier 4
We recommend that the battery that
is changed after 5 years of use in
IMPORTANT NOTICE
safeguards GPU settings etc.
order not to lose data.
Diagrams and drawings are subject to change without prior notice.
Latest diagram versions can be found at www.itwgse.com
OM2248 Rev B
Page 2 of 104
Operation Manual – ITW GSE 6400 Tier 4
Introduction
This manual contains operation and maintenance information for a diesel engine-generator manufactured
by ITW GSE, Palmetto, Florida 34221
This manual, including all information contained therein, is exclusive and confidential property of
ITW GSE. This manual is not to be copied, reproduced, or delivered or disclosed to others, in
whole or in part, except with express written permission of ITW GSE.
This manual is not intended to be a textbook on electricity or electronics. Its primary purpose is to provide
information and instructions to experienced operators, electricians, and mechanics that have never
operated this equipment. It is the intent of this manual to guide and assist operators and maintenance
personnel in the proper use and care of the equipment.
Use of the manual should not be put off until trouble or a need for help develops. Read the instructions
before starting the unit. Learn to use the manual and to locate information contained in it. Its style and
arrangement are very similar to commercial aircraft manuals.
The manual is divided into three chapters plus appendices. Each chapter is divided into as many se ctions
as required. Each page is identified by chapter, section and page number, which are located in the lower,
outside corner.
When information located in another portion of the manual is referred to, a chapter, section, and
paragraph or figure number identify its location. For example: “(see Section 2-3, Paragraph 1.a.)” refers
to information located in Chapter 2, Section 3, Paragraph 1.a. If a chapter and section are not indicated in
a reference, the referenced material is located in the same section as the reference, for example: “(see
Paragraph 1.a.).”
Contents of the manual are arranged as follows:
Chapter 1 Description/Operation
Chapter 2 Servicing/Troubleshooting
Chapter 3 Manufacturer’s Literature
Appendix A Options
Appendix B Operation in Unusual Service Conditions
Appendix C Software Installation Procedures
Appendix D Schematics
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 3 of 104
Safety Warnings and Cautions.
WARNING
IMPORTANT
WARNING
ELECTRIC SHOCK can KILL. Do not touch live electrical parts.
ELECTRIC ARC FLASH can injure eyes, burn skin, cause equipment damage, and
ignite combustible material. DO NOT use power cables to break load. Prevent tools
from causing short circuits.
IMPROPER PHASE CONNECTION, PARALLELING, OR USE can damage this and
attached equipment.
Protect all operating personnel. Read, understand, and follow all instructions in the
Operating/Instruction Manual before installing, operating, or servicing the equipment.
Keep the manual available for future use by all operators.
CALIFORNIA PROPOSITION 65 - DIESEL ENGINES. Diesel engine exhaust and
some of its constituents are known to cause cancer, birth defects and other illnesses.
1) General
Equipment that supplies electrical power can cause serious injury or death, damage to other equipment or
property. The operator must strictly observe all safety rules and take precautionary actions. Safe
practices have been developed from past experience in the use of power source equipment. While
certain practices below apply only to electrically powered equipment, other practices apply to enginedriven equipment, and some practices to both.
2) Shock Prevention
Bare conductors, terminals in the output circuit, or ungrounded, electrically live equipment can fatally
shock a person. Have a certified electrician verify that the equipment is adequately grounded and learn
what terminals and parts are electrically HOT. Avoid hot spots on machine. Use prop er safety clothing,
procedures and test equipment.
The electrical resistance of the body is decreased when wet, permitting dangerous currents to flow
through it. When inspecting or servicing the equipment, do not work in damp areas. Stand on a dry
rubber mat or dry wood, and use insulating gloves when dampness or sweat cannot be avoided. Keep
clothing dry, and never work alone.
a) Output Cables and Terminals
Inspect cables frequently for damage to the insulation and the connectors. Replace or repair
cracked or worn cables immediately. Do not overload cables. Do not touch output terminal while
equipment is energized.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 4 of 104
3) Service and Maintenance
This equipment must be maintained in good electrical condition to avoid hazards stemming from
disrepair. Report any equipment defect or safety hazard to the supervisor and discontinue use of the
equipment until its safety has been assured. Repairs should be made by qualified personnel only.
Before inspecting or servicing this equipment, take the following precautions:
a) Shut off all power at the battery disconnect before inspecting or servicing the equipment.
b) Lockout the equipment at the battery discon nect switch if it is out of service.
c) If troubleshooting must be done with the unit energized, have another person present who is
trained in turning off the equipment and providing or calling for first aid.
4) Fire and Explosion Prevention.
Fire and explosion are caused by electrical short circuits, combustible material near engine ex haust pipes,
misuse of batteries and fuel, or unsafe operating or fueling conditions.
a) Electrical Short Circuits and Overloads.
Overloaded or shorted equipment can become hot enough to cause fires by self-destruction or by
causing nearby combustibles to ignite.
b) Batteries.
Batteries may explode and/or give off flammable hydrogen gas. Acid and arcing from a ruptured
battery can cause fires and additional failures. When servicing, do not smoke, cause sparking, or
use open flame near the battery.
c) Engine Fuel.
Use only approved fuel container or fueling system. Fires and explosions can occur if the fuel
tank is not grounded prior to or during fuel transfer. Shut unit DOWN before opening fuel tank
cap. DO NOT completely fill tank, because heat from the equipment may cause fuel expansion
overflow. Remove all spilled fuel IMMEDIATELY, including any that penetrates the unit. After
clean-up, open equipment doors and blow fumes away with compressed air.
5) Toxic Fume Prevention.
Carbon monoxide - Engine exhaust fumes can kill and cause health problems. Pipe or vent the
exhaust fumes to a suitable exhaust duct or outdoors. Never locate engine exhausts near intake
ducts of air conditioners.
6) Bodily Injury Prevention.
Serious injury can result from contact with fans or hot spots inside some equipment. Shut DOWN
such equipment for inspection and routine maintenance. When equipment is in operation, use
extreme care in doing necessary troubleshooting and adjustment. Do not remove guards while
equipment is operating.
Operation Manual – ITW GSE 6400 Tier 4
g
OM2248 Rev B
Page 5 of 104
7) Medical and First Aid Treatment.
First aid facilities and a qualified first aid person should be available for each shift for immediate
treatment of all injury victims. Electric shock victims should be checked by a physician and taken to a
hospital immediately if any abnormal signs are observed.
EMERGENCY
FIRST AID
8) Equipment Precautionary Labels
Inspect all precautionary labels on the equipment monthly. Order and replace all labels that cannot
be easily read.
SEEK ADDITIONAL ASSISTANCE. Use First Aid techniques recommended by
American Red Cross until medical help arrives.
IF BREATHING IS DIFFICULT, give oxygen, if available, and have victim lie down.
FOR ELECTRICAL SHOCK, turn off power. Remove victim; if not breathing, begin
artificial respiration, preferably mouth-to-mouth. If no detectable pulse, begin external
heart massa
3) Component Locations 1-1/11
Figure 1-1-1: General Assembly of Generator Set1-1/11
Figure 1-1-2: Main Components of Generator Set (Right Side) 1-1/12
Figure 1-1-3: Main Components of Generator Set (Left Side) 1-1/13
Figure 1-1-4: Main Components of Generator Set (Bottom) 1-1/14
4) Specifications 1-1/15
5) Special Features 1-1/16
6) Canopy 1-1/17
7) Engine and Generator 1-1/17
8) Operator Controls 1-1/20
9) Power Module Assembly 1-1/25
10) Cold Weather Starting System 1-1/25
Section 2 Preparation for Use/Storage/Shipment 1-2/26
1) Preparation for Use 1-2/26
2) Preparation for Storage 1-2/28
3) Preparation for Shipment 1-2/29
Section 3 Operation 1-3/30
1) General 1-3/30
2) 28 VDC Operating Procedure 1-3/30
3) Icon Menu 1-3/37
a) View Parameters Menu 1-3/38
b) Setup Menu 1-3/39
c) Black Box 1-3/48
d) Power Log 1-3/49
5) Engine Fuel System 2-2/72
a) Fuel Tank 2-2/72
b) Fuel Water Separator or Lubricity Additive Filter 2-2/72
c) Primary Fuel Filter 2-2/73
d) Fuel Pump 2-2/74
e) Fuel Return 2-2/74
f) Fuel Level Indicators 2-2/74
g) Draining the Fuel Tank 2-2/75
6) Engine Cooling System 2-2/76
a) General 2-2/76
b) Radiator Cap 2-2/76
c) Coolant 2-2/76
d) Draining the Cooling System 2-2/77
e) Flushing the Cooling System 2-2/77
f) Cleaning the Radiator Core 2-2/78
g) Filling the Cooling System 2-2/78
h) Thermostat 2-2/78
Appendix A – Options
Appendix B – Operating in Unusual Service Conditions
Appendix C – Initial Software Installation Procedure
Appendix D – Schematics
hapter-Section/Page#
3-A/95
3-B/97
3-C/98
3-D/101
Operation Manual - ITW GSE 6400 Tier 4
OM2248 Rev B
Page 10 of 104
Chapter 1 Description/Operation
Section 1 Description
1) General
This manual describes a 28.5 V generator set manufactured by ITW GSE, Palmetto, FL 34221. This
generator system is designed to provide ground power for maintenance and startup of aircraft or other
loads.
Part Number Mounting
DCE6400CUTT4
Table 1: ITW GSE 6400 Series Generator Set Part Number Descriptions
Cable
Management
Trailer Cable Trays Standard
Model
Description
Power Rating
Unit rated
28.5 VDC,
600 A continuous (17 kW),
2000 A peak (56 kW),
single output
2) Optional Equipment - Appendix A
Chapters 1 through 3 of this Operation and Maintenance Manual identify only the basic version of the
ITW GSE 6400 Tier 4 generator set. Appendix A contains a list of the rest of the optional equipment
that can be ordered with the unit. Each item has a brief description of the optional equipment.
Operation Manual - ITW GSE 6400 Tier 4
OM2248 Rev B
Page 11 of 104
3) Component Locations
For purpose of orientation when designating RIGHT and LEFT throughout this manual, the radiator is
considered to be at the FRONT of the unit and the generator is at the REAR. RIGHT and LEFT are
determined by standing at the REAR facing the machine. As an example, the control panel is
mounted on the RIGHT FRONT side of the unit.
10
6
11
4
3
8
12
1
1. Fuel Filler Neck / Manual Gauge
2. Operator Control Panel
3. Composite Output Cable Trays
4. Emergency Stop Switch
5. Sliding/Removable Canopy
6. Clearance Lights (Option)
Figure 1-1-1: General Assembly of Generator Set
5
7
2
3
9
7. Radiator End
8. Generator End
9. Forklift Pockets
10. Low Fuel Beacon (Option)
11. Operating Beacon (Option)
12. Canopy Locking Latch
Operation Manual - ITW GSE 6400 Tier 4
OM2248 Rev B
Page 12 of 104
7
2
1
8
6
5
1. Cummins QSF2.8 Engine
2. Control Module Assembly
3. Battery (inside tray pocket)
4. Battery Disconnect
Figure 1-1-2: Main Components of Generator Set (Right Side)
4
3
5. Output Connections
6. Output Contactor (mounted under output
table)
7. Coolant fill access cover
8. Engine ECM Module
Operation Manual - ITW GSE 6400 Tier 4
OM2248 Rev B
Page 13 of 104
6
1. Lubricity Additive Fuel Pre-Filter
2. Engine Oil Filter
3. Fuel Filter
Figure 1-1-3: Main Components of Generator Set (Left Side)
4
7
132
4. Engine Oil Fill Tube
5. Generator
6. Air Filter Assembly
7. Tie Down Rings Location (Option)
5
Operation Manual - ITW GSE 6400 Tier 4
OM2248 Rev B
Page 14 of 104
4
1
3
1. Oil Drain Valve
2. Muffler Assembly
3. Fifth Wheel
Figure 1-1-4: Main Components of Generator Set (Bottom)
Operation Manual - ITW GSE 6400 Tier 4
(
(
)
(
)
(
)
(
)
)
g
)
)
g
OM2248 Rev B
Page 15 of 104
4) Specifications
a) Standards
This unit has been designed to be in compliance with the following standards:
US EPA Tier 4F/CARB Tier 4F
EU Stage IV
US MIL-STD-704F, SAE ARP5015
b) Physical Specifications
Physical
includes trailer)
Length 103 in.
Width 66.2 in.
Height 63.9 in.
Weight (dry fuel tank) 2800 lbs.
Ground Clearance 9 in. (22.86 cm
c) DC Output Specifications
Output power ratin
Output voltage 28.5 VDC
Rated load capacity 600 A continuous at 28.5 VDC
Starting current capacity 2000 A maximum
Current limiting capability 300 to 2000 A, continuously adjustable
d) DC Protective System Specifications
Condition Trip Point
Over voltage 32 to 34 volts
High engine coolant temperature225º F (107º C
Low Idle oil pressure 10 PSI (69 kPa
17.1 kW continuous
2615 mm) (w/ towbar up
1682 mm
1622 mm
1814 kg.
e) Generator Set Specifications
Output power ratin
Rated load capacity 800 A continuous at 28.5 VDC*
Operating speed 1600, 2000, 2400 RPM**
Idle speed 1000 RPM
* The generator rating is limited to 600 A by the current carrying capacity of the output cable.
** The Operating Speed is based on the Current Limit setting:
22.8 kW continuous
300A to 1100A –- 1600 RPM
1150A to 1400A –- 2000 RPM
1450A to 2000A –- 2400 RPM
Operation Manual - ITW GSE 6400 Tier 4
j
(
)
@
)
)
(
)
g
)
)
(
)
(
OM2248 Rev B
Page 16 of 104
f) Engine Specifications
Manufacturer Cummins, Inc.
Model No. QSF2.8
Type
Bore and Stroke 3.7 in x 3.94 in (94 mm x 100mm)
Displacement 171 in
Horsepower 74 hp/55 kw
Low Idle speed 1000 rpm
Electrical system 12 VDC
Ground Negative
Lubricating oil capacity (w/ filter
Coolant capacity system 5.3 Quarts
Fuel tank capacity 53
g) Normal Operating Characteristics
4 cylinder, 4 cycle diesel with turbocharger
and fuel in
8.66 Quarts (w/filter) (8.2L
ection
3
2.8 L
2400 RPM
5 liters
allons (200 L
Engine oil pressure (warm and at
rated speeds 1600 - 2400 RPM
Engine coolant temperature
normal operation)
45 - 55 PSI
310 - 379 kPa
180 ºF - 230º F (82ºC to 95ºC)
5) Special Features
The generator set has special features that are described more fully under the assemblies in which
they appear.
a) Protective Monitoring
The protective monitoring system receives signals from the fault sensing components in the
generator output circuit and functions to cause the load to be disconnected from the generator if
an abnormal condition of voltage, frequency, or load develops. The nature of that abnormal
condition is then presented on the graphical display.
b) Voltage Regulator
A microprocessor-type, adjustable voltage regulator provides automatic voltage regulation at the
aircraft. The regulated output is also adjustable for a variety of output cable sizes and lengths.
c) Engine Electronic Control Module (ECM)
The engine is equipped with an electronic control module (ECM) that monitors, records, and
controls engine performance.
d) Battery System Disconnect Switch
The generator set is equipped with a battery disconnect switch outside the unit on the RIGHT
side. The disconnect switch should be placed in the OFF position for long periods of shutdown.
NOTE: DO NOT disconnect the batteries when the engine is running or within two (2)
minutes after the engine stops.
Operation Manual - ITW GSE 6400 Tier 4
OM2248 Rev B
Page 17 of 104
6) Canopy
A composite enclosure, identified as a canopy, provides protection for the engine, generator and
electrical controls. The canopy is also designed to reduce the operational noise level in the
immediate area of the machine. The canopy is equipped with a bolted latch on the back left corner,
which will require the use of a wrench to remove the canopy. Once the bolt is loosened the canopy
can be slid to the rear and removed by two people for easy access to all engine and generator
components.
We recommend using Simple Green® Industrial Cleaner & Degreaser or an equivalent to clean the
canopy and cable trays.
7) Engine and Generator
The engine and generator comprise the principal components of the generator set. They are mounted
on a galvanized, welded steel frame chassis. The following figures show the locations of all major
components and sub-assemblies.
a) Diesel Engine
The diesel engine is a fuel injection, 4-cylinder, electronically controlled engine rated at 171
horsepower.
b) Engine Manufacturer’s Components
As received from the engine manufacturer, the engine includes some of the following
components, which are more fully described in the engine manufacturer’s manual.
1) Electrical System
The 12 VDC electrical generating and starting system includes an alternator and starter with
solenoid switch.
2) Fuel/Water Filter
The fuel/Water filter is a spin-on disposable type located on the inside of the canopy, near the
engine’s fuel pump. Water that has been removed from the fuel should be removed daily.
(See Chapter 2-1)
The use of low lubricity fuels can shorten life and/or damage the engine’s fuel pump.
CAUTION
3) Oil Filter
The engine oil filter is a spin-on, full-flow type, located on the left side of the engine near the
front.
4) Pre-programmed Electronic Control Module (ECM)
The ECM is a pre-programmed engine control module, mounted directly to the engine block.
Only diesel fuel is recommended by the engine manufacturer. Refer to engine
manufacturer’s manual for approved fuels.
Operation Manual - ITW GSE 6400 Tier 4
OM2248 Rev B
Page 18 of 104
c) Factory Installed Components and Protective Systems
This generator set is assembled with the following components and protective systems:
1) Shutdown/Reset Systems
Emergency Shutdown
The emergency shutdown switch is to provide instant manual shut off of the generator
set by disconnecting power to the ECM through the control box. It is located on the
FRONT RIGHT of the generator set next to the control box.
To operate the EMERGENCY SHUTDOWN
Push button in until engine stops or until button travel stops
Pull the button back out to reset
CAUTION
Low Fuel Warning System
Do not use the “EMERGENCY STOP BUTTON” as a normal shutdown device.
Damage to the engine turbo charger may result without proper cooling time. Use the
Engine ON/OFF push-button for all normal engine shutdowns.
The low fuel warning system monitors the fuel level in the fuel tank. When the fuel
tank level reaches approximately 10%, a warning is generated signifying it is time to
put fuel in the tank. Once the engine is not running, a low fuel fault is generated and
the engine is not allowed to start.
2) Radiator and Charge-Air-Cooler (CAC)
The radiator and charge-air-cooler is a two-piece type designed for long periods of operation
without servicing.
3) Engine-Cooling Fan
The engine fan is designed to blow air outward through the radiator, rather than pulling air
inward like a conventional fan.
4) Master [Battery] Disconnect Switch
The master disconnect switch is designed to isolate the batteries from the entire electrical
system to eliminate the possibility of battery current draw by the engine ECM or any other
components during long periods of no operation. The switch can also be used to lock-out the
starting circuit of the equipment for maintenance safety purposes.
5) Air Cleaner
The diesel engine air cleaner is constructed so that air enters through its cylindrical body, and
then is filtered before being passed into the engine turbo-charger assembly. An air cleaner
service indicator device is mounted on the air cleaner assembly to monitor the airflow into the
air cleaner. As the air cleaner becomes filled with dust, dirt, and carbon, the intake system
airflow becomes increasingly restricted. This restriction causes a diaphragm inside the
indicator to move toward an electrical contact. When the maximum allowable restriction level
is reached, the circuit closes and the air cleaner indicator fault appears on the control panel
fault display to warn the operator that the air cleaner must be changed. The electrical
indicator automatically resets when the restriction level drops sufficiently. Note: This function
should not be used as a replacement indicator. Follow recommended replacement schedule
as specified in this manual.
Operation Manual - ITW GSE 6400 Tier 4
OM2248 Rev B
Page 19 of 104
d) Warnings/Faults
The control system reacts appropriately to different detected issues. These types can be
generalized between warnings and faults. Warnings are given when the system is able to function
but requires servicing/user interaction. Faults are generated when the unit cannot or should not
supply regulated power to the aircraft.
All faults prevent the engine from starting. However, they react differently to an operating unit.
Faults can be categorized into three subcategories as defined by the fault number.
Fault numbers less than 6000
o Minor faults: Will disconnect power to the aircraft but not affect engine and generator
Fault numbers between 6000 and 8000
o Mid-level faults: Will disconnect power to the aircraft, turn off the generator and shut
Fault numbers greater than 8000
o Major faults: Result in immediate shutdown of all system components including the
Engine generated warnings and faults are also monitored and their respective Cummins fault
numbers are shown on the display.
functions.
down the engine after the required 30 second cool down.
engine. Service is required on the unit before it is returned to operation.
e) Generator
The generator is a 3-phase AC generator whose output is rectified. The generator consists of the
generator housing assembly, which holds the stator windings, and a rotor, which holds the control
winding. The generator housing assembly bolts to the engine flywheel housing. A flexible coupling
assembly connects the front end of the rotor to the engine flywheel. At the rear of the generator, a
bearing supports the rotor and brushes and slip rings provide the electrical connection to the exciter
winding.
The generator consists of six windings, which result in 12 numbered output leads. When
connected at the rectifier assembly, these windings form two three-phase delta connections. The
rectifier assembly, described later in this section, converts the three-phase AC to the DC for the
generator set output.
The generator is self-excited. Part of the generator’s output powers the rotating control winding.
One positive and one negative brush in contact with slip rings supply controlled excitation current.
The voltage regulator controls the excitation current and maintains a constant output voltage.
Access to the brushes is through holes in the rear end bracket.
A radial-blade fan behind the coupling hub draws cooling air over the generator windings. Air
flows over the rectifier assembly and then enters through the rear end of the generator and is
discharged through openings in the flywheel housing at the drive end.
Operation Manual - ITW GSE 6400 Tier 4
OM2248 Rev B
Page 20 of 104
8) Operator Controls
The control box is a protected enclosure on the right front panel of the GPU that has a modern
graphical display and easy to understand controls. The display allows the user to easily have access
to all critical operational information as well as providing textual descriptions of all warnings and
failures.
a) Operator Controls – Screen icon’s
The table below shows the different icons used in the display and what they mean.
ICON Description ICONDescription
Check Engine
Fuel level is below 10% Fault, engine
won’t start until more fuel is added
Critical fault, the engine is stopping
Access the Information screens
Access the Black Box logs
Access the firmware upgrade screens and
the data save screen
Fuel level is below 10%, refuel as soon as
possible
Fuel level is acceptable
Exit Icon screen and return to the Default
screen
Access the Setup screens
Access the Power logs
Operation Manual - ITW GSE 6400 Tier 4
OM2248 Rev B
Page 21 of 104
1) LED Graphical Display
2) Navigation Keypad
3) Power ON "Blue" LED
4) Warning "Amber" LED
3
4
5
6
1
2
7
8
9
5) Alert/Failure "Red" LED
6) Output ON "Green" LEDs
7) Current Limit Increase/Decrease
8) Power ON & Engine Start/Stop (Reset)
Figure 1-1-5 Control Panel
1: The color LED Graphical Display and easy to use menu system places all required operational
information at the fingertips of the operator/maintenance personnel. Its color presentation accents
critical data and simplifies the troubleshooting process by giving textual descriptions of any
potential issues.
2: The Navigation Keypad is used to navigate through the simple menu systems.
3: The Blue LED indicates that power is ON. (It is off in sleep mode)
4: The Amber LED indicates a warning. The details of that warning are available on the display.
Up to five warnings can be displayed at one time.
5: The Red LED indicates a fault. The details of this fault are also visible on the graphics display.
Only one fault can be displayed at one time.
6: The Green LED’s indicate that the respective output is ON.
7: The current limit buttons increase or decrease the maximum amount of current the unit will
provide to the connected aircraft. The step size is selected in the SETUP menu.
Operation Manual - ITW GSE 6400 Tier 4
OM2248 Rev B
Page 22 of 104
8: The power ON & Engine Start/Stop button will wake the unit from low-power sleep mode.
Pressing it again will begin the start-up sequence for the diesel engine. Pressing it again will shut
down the engine. If the engine is already running, it will begin the manufacturer required 30
second cool down. If the unit has a fault, this button will reset the fault.
NOTE! – The screens shown in this manual reflect the current software version at the time
of publication. The screens on your unit might differ slightly based on the software version
running on your unit. Any changes will be described in a Service Bulletin which should be
placed in the back of this manual.
Default Screen:
There are two default displays depending on whether the engine is running or not. When the unit
finishes its self-check after first being powered up, the display will show the number of hours the
engine has been operating. After a short delay, the engine hours are replaced with the current
time. This then becomes the default display when engine is off. (The engine operating hours are
always available on the “Engine” information screen.)
During the engine start process, the screen will be modified to show the current status until the
engine is running and the unit is ready to output power.
Note: If the engine is configured to go to idle until the output is activated, it will still say it is ready
for use. However, the engine will have to ramp up to its normal running speed (1600, 2000 or
2400 RPM) and the voltage stabilized before the output contactor will close. The running speed is
determined by the current limit setting which is shown in the lower right corner of the display.
Current Limit Setting RPM
300 A to 1100 A 1600
1150 A to 1400 A 2000
1450 A to 2000 A 2400
Operation Manual - ITW GSE 6400 Tier 4
OM2248 Rev B
Page 23 of 104
When output power is being provided, the screen will appear as follows:
29.5 V:94%560 A
28 VDC
Output Activated
40%
1500
A
The selected current limit is changed by using the up and down arrow keys that are located just
below the navigation buttons. The amount the current limit value changes per button push is
selected in the SETUP menu. The values are 50 A, 100 A, 200 A or 300 A.
Both default screens enable the user to quickly have access to other pertinent information by
pressing the ▼ or▲ navigation buttons to cycle through the display screens:
Pressing the
◄ navigation button will return the screen to the
default menu screen.
Unit information is displayed using the Parameter Information
icon. To access the information icon, press the ● from the
default menu and hold it down for approximately 5 seconds.
Note: Access to the ICON screen might be restricted. If this is
the case, then the message ”DISABLED” is displayed.
Paragraph 4.17 describes how to enable and disable access to
the ICON screen.
To Select a submenu, simply use the navigation keys ◄▼▲►
to highlight the icon and then press the ● to enter the sub-menu.
To leave the Icon Menu highlight the ”Home” icon and press ●
Operation Manual - ITW GSE 6400 Tier 4
OM2248 Rev B
Page 24 of 104
Parameters – Menu structure
ENGINE
Status:Running
RPM:2000
Oil Pressure:54 psi
Temperature:180 °F
◄ Back ▼/▲ Next/Prev
Highlight the by using the navigation
◄▼▲► keys.
● to select ”View parameters” sub-menu.
Press
Use the the ▼/▲ to browse through the various
screens.
Use ◄ to leave the sub-menu and return to basic Icon
Menu.
Notice!
Parameters may vary depending on the mode of the unit
Standby / operating / load profile etc.
UNIT INFORMATION
Display FW:075100 F
Control FW:075100 F
Unit Serial:215PS00000
Unit Rating:90 kVA
MAC: C8:02:58:00:00:00
◄ Back ▼/▲ Next/Prev
SYSTEM
Battl Voltage: 28.1 V
Hour Meter:14:57:07
Consumption:4527 kWh
PWM Duty Cycle: 0 %
28 V
Voltage28.0 V
Current600 A
Power16.8 kW
◄ Back ▼/▲ Next/Prev
ENGINE
Engine Load::49 %
Engine Hours: 4122
FUEL:85%
Baro. Pressure: 101 kPa
◄ Back ▼/▲ Next/Prev
Operation Manual - ITW GSE 6400 Tier 4
A
OM2248 Rev B
Page 25 of 104
9) Power Module Assembly
The power module assembly is mounted under the output table which is located at the rear of the
machine over the generator. The assembly consists of the rectifier, a current transformer and an
output contactor. The rectifier converts the generator AC output to DC
10) Cold Weather Starting System (BH1)
The intake air heater, located on the intake manifold, is used for starting the engine at very cold
temperatures and reduces the white smoke associated with a cold start. The intake air heater (or grid
heater) is energized or de-energized from a power relay controlled by the ECM. The amount of time
the air intake heater stays on, in the preheat phase, is a function of the intake manifold temperature at
start up. (The pre-heat time increases with colder intake manifold temperatures). The maximum
duration of the pre-heat phase is around 30 seconds.
CAUTION
Never use an ether start system in conjunction with the air intake heater.
ir Intake Heater
Figure 1-1-6: Air Intake Heater
g
)
)
)
OM2248 Rev B
Page 26 of 104
Operation Manual ITW GSE 6400 Tier 4
Section 2 Preparation for Use, Storage, or Shipping
1) Preparation for use after receipt of unit
a) Inspection/Check
Inspect unit thoroughly prior to operation.
1) Remove blocking, banding, ties, and other securing material.
2) If Tie Down Rings are present, make sure they are secured with both bolts. (Typically one bolt
is used to secure middle blocks to unit during shipping.)
3) Inspect exterior for shipping damage such as broken lights, damaged sheet metal, etc.
4) Slide the canopy open and inspect the interior for foreign material such as rags, tools,
shipping papers, etc.
5) Check fuel, coolant, oil hoses and connections for visible leaks. Visually inspect compartment
floor and ground surface under unit for signs of leakage. Correct any leaks by tightening hose
clamps, tube fitting, etc., as required.
6) Check tightness of generator set retaining components.
7) Check fuel level. (A manual quick reference fuel gauge is located at back of unit. This gauge
is accurate only when fuel level is above 50%.)
NOTE: For recommended fuel specifications, refer to Engine Manufacturers Operation and
Maintenance Manual provided with this manual.
8) Check engine coolant. Remove radiator cap (under hatch on top of operator section) to check
coolant level. Coolant level should be at bottom of filler neck.
CAUTION
NOTE: For antifreeze protection, use a solution of 50% permanent antifreeze (Ethylene
Be sure cooling system antifreeze solution is adequate to protect below lowest
temperature expected.
glycol) and 50% clean water.
oil capacity (w/ filter
Figure 1-2-1: Engine Oil and Coolant Capacities
2.9 gallons(11 liters
OM2248 Rev B
Page 27 of 104
Operation Manual ITW GSE 6400 Tier 4
9) Check engine lubricating oil level. The oil gauge rod has “H” high-level and “L” low-level
marks to indicate operating lubrication oil supply. Oil level should be kept as near the high
mark as possible, without going over. See Figure 1-2-1 for capacity.
CAUTION
NOTE: See Engine Manufacturer’s Operation Maintenance Manual for oil recommendations.
NEVER operate engine with oil level below “L” level or above “H” level mark.
Dipstick
Oil Fill Cap
Figure 1-2-2: Oil Fill and Oil Level Check Locations
10) Check battery located inside the right-side cable tray. Inspect battery for proper connection of
terminals. Service or replace if necessary.
OM2248 Rev B
Page 28 of 104
Operation Manual ITW GSE 6400 Tier 4
2) Preparation for Storage
A generator set in storage or removed from operation, has special precautions that should be taken to
protect internal and external parts from rust, corrosion, and gumming in the engine fuel system.
a) General
Open battery disconnect switch and disconnect battery negative terminal at battery.
1) The unit should be prepared for storage as soon as possible after being removed from
service.
2) The unit should be stored in a building that is dry and can be heated during winter months.
3) Moisture-absorbing chemicals should be used where excessive dampness is a problem;
however, the unit must be completely packaged and sealed if moisture-absorbing chemicals
are to be effective.
b) Temporary Storage (30 days or less)
1) Lubricate unit completely in accordance with instructions in Chapter 2-2 Page 2. This will
include changing engine oil, and all filter elements.
2) Start engine and operate a minimum of two minutes so all internal engine components are
coated with new oil. (Note: if unit is operated outside of diagnostic mode, it will run for 30
seconds in cool down mode after stop button is pressed.)
NOTE: Do not drain fuel system or crankcase after this run.
3) Cooling system antifreeze solution must be adequate to protect below lowest temperatures
expected during storage period. Be sure solution is thoroughly mixed.
4) Clean exterior of engine. Dry with clean rags and compressed air.
5) Seal all engine openings. Use water-proof, vapor-proof material strong enough to resist
puncture damage from air pressure changes.
OM2248 Rev B
Page 29 of 104
Operation Manual ITW GSE 6400 Tier 4
c) Long-Term Storage (Over 30 Days)
To protect the generator and other electrical components, the complete unit sh ould be packaged
using moisture proof packaging and sealing material. Place containers of moisture-absorbing
chemicals in unit before packaging.
From the Cummins 4BT shop manual: long term storage is up to 24 months. Change the oil and
fill with 30W Preservative oil. Then start the engine with clean diesel fuel (the units needs to be
filled with at least 10% or more of fuel in order to start) and then switch fuel lines to a can of
preservative oil (Cummins specifies Dauber Chemical NoxRust # 518). When the preservative oil
is running out the injector return tube turn off the motor and cap ends of fuel return and supply
tubes. Drain 30W preservative oil from crankcase. Add rust inhibitor to the coolant and make sure
that the radiator is full. Spray preservative oil into intake and exhaust ports on cylinder head and
under rocker housing covers. Cover all openings. Do not rotate crankshaft. Drain the fuel tank.
The unit can be stored for long periods without the above preparation if engine can b e operated
once a week.
When operating once a week:
1) Make certain the cooling system is adequately protected.
WARNING
2) Start engine and operate under full load (using a resistive load bank or aircraft) until coolant
temperature has reached a minimum 176ºF (80ºC).
3) While engine is running, ensure normal operating controls are in good working condition
before shutdown and storage. If weekly operation is not possible, contact nearest engine
manufacturer distributor for instructions.
ENSURE adequate ventilation before starting the engine.
3) Preparation for Shipment
a) Disconnect battery negative terminal before shipping.
b) During long shipments, vibration, jolting, etc may loosen the generator set retaining hardware.
CAUTION
NOTE: It is suggested strong banding is used to secure generator set.
When shipping unit, provide sufficient retaining materials to ensure generator set
cannot roll out or off the vehicle in which it is being transported.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 30 of 104
Section 3 Operation
1) General
This section contains information and instructions for safe and efficient operation of the equipment. Operating
instructions are presented in systematic sequence of procedures to be followed in supplying 28.5 VDC power.
NOTE: Read ALL operating instructions before attempting operation of equipment.
WARNING
2) 28 VDC Operating Procedure
a) Pre-start Inspection
1) Check engine and generator compartments to make certain they are free of rags or other foreign
materials.
2) Make certain sufficient lubricating oil and coolant is in the engine.
3) Be sure that the battery isolation switch is closed, ensuring that 12 VDC power is available to the
engine starting and control systems.
Ear protection equipment may be necessary when working close to this equipment.
4) Make certain the control panel is on. If not, press the Power ON/Engine Start-Stop button to wake
the unit.
b) Engine Starting Procedures
CAUTION
1) Press and release engine “Start” button. The remaining portion of the startup procedure is
automated. Startup status is shown on the display. The procedure will begin by providing power to
the engine and other vital components. Next it will check the engine to insure proper operation.
Once verified, the engine data begins processing and the engine will start its initialization and
warmup procedures. When finished, the starter will begin to crank.
2) If the Idle Mode is active (default), once the engine starts it will quickly ramp to idle speed of 1,000
RPM and hold until an output pushbutton is pressed or the unit runs out of fuel.
3) If the Idle Mode is inactive, the engine starts and ramps up to its idle speed of 1,000 RPM pauses
for a moment and then continues to ramp up to its running speed of 1600 to 2400 RPM (the actual
running speed is determined by the current limit setting) and stays there until an output pushbutton
is pressed or the unit runs out of fuel.
4) Once the engine is running at idle or rated speed, check the oil pressure to make certain it is
normal and observe all other engine values on the display screen for normal operation.
CAUTION
Refer to operating instructions in the engine manufacturer’s operation manual
(provided with the unit), when starting engine for the first time.
Never use an ether start system in conjunction with the air intake heater.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 31 of 104
1
3
1. LED Graphical Display
2. Navigation Keypad
3. Power ON "Blue" LED
4. Warning "Amber" LED
4
5
6
7
2
8
9
5. Alert/Failure "Red" LED
6. Current Limit Adjustment Buttons
7. Output ON "Green" LEDs
8. Output ON/OFF (Reset) *
9. Power ON & Engine Start/Stop (Reset) *
* All output and engine buttons are multitasking buttons dependent on the status of the unit. The
displayed screen is NOT important. These buttons are always active.
CAUTION
c) Failed Starting Procedure
If an error during initialization occurs the engine fails to start after 3 automatic attempts (15 seconds
crank, 15 seconds wait per attempt), the display will show a fault. Diagnose and treat the reason for the
fault, clear the fault, and press the engine start button again.
To eliminate the possibility of wet stacking (See Appendix B), DO NOT allow the
engine to idle for long periods.
OM2248 Rev B
Page 32 of 104
d) Power Delivery
After the engine has started and the display has changed to the output status default screen, insert the
aircraft cable into the aircraft. Make sure the cable is inserted until you feel a natural resistance. The
plug may be equipped with a 90% insertion switch (split “C” pin). In this case, the unit will not function if
the plug is not fully inserted. Press the output ON/OFF button. If the unit is already at rated speed, the
contactor will immediately close. If at idle speed the engine will ramp up to rated speed, the generator
will set output voltage and the contactor will close. The green LED will turn ON next to the active output.
In addition, current power status information will appear on the output status default screen.
WARNING
1) Early in the power delivery run it is recommended that the operator check output voltage and
current in each of the three phases. Use ▼ ▲ pushbuttons to view voltage. If the load is changing,
observe the display until load conditions stabilize.
2) A condition of over-voltage, under-voltage or overload in the output circuit will automatically open
the load contactor and display a fault code to signal the operator which of the above faults caused
the protective monitor system to operate. After the fault has been corrected, press the output
pushbutton to reset the system. Proceed with power delivery by pressing the same switch.
Operation Manual – ITW GSE 6400 Tier 4
All output ON/OFF buttons are active regardless of the displayed screen.
WARNING
CAUTION
e) Failed Power Delivery
If the contactor indicator light goes out and EF fault is shown on the display, this indicates that the
aircraft plug interlock circuit is no longer receiving 28.5 VDC from the aircraft power connector. Correct
the condition and press the output pushbutton to reset the fault. Press the button again to close the
output contactor and provide 28.5 VDC to the aircraft/load bank.
1) If the aircraft cable does not have the Split-C wire, set the 28V Interlock to Bypassed through the
Setup icon menu using the following steps:
2) Press and hold
“DISABLED” appears in the display screen, contact the Maintenance department for access to the
SETUP menu to unlock.)
3) Use the navigation keys (
4) Set EF interlock to bypass.
NEVER disconnect the output cable while power is being delivered. Output
contactor’s must be open prior to removal of the cable from the aircraft.
The generator set must be shut down so the failed power delivery problems can be
diagnosed. Only personnel who are trained or qualified on this type of equipment
should work on this GPU.
● for approximately 5 seconds. (If the ICON screen doesn’t appear and
◄▼▲►) to highlight the setup icon. Press ● to select.
5) Press
6) Use the
● to accept the change.
◄ navigation key to go back to the Icon screen. The display will return to the default
screen after a period of inactivity.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 33 of 104
f) Discontinue Power Delivery with Unit Shutdown
1) Normal conditions
Push the Output ON/OFF pushbutton next to the lit green LED indicator to open the output load
contactor. The indicator light next to the button will go OFF, indicating the load contactor has
opened and power is no longer being delivered to the aircraft.
Once all contactors are opened:
a) If Idle Mode option is active (default), the generator will turn off and the engine will return to
idle speed after a 5 second delay.
b) If Idle Mode is inactive, the generator will turn off and the engine will remain at rated speed.
c) Pushing the engine Start/Stop pushbutton once while the engine is running begins the
automatic shutdown sequence which will shut off the engine after 30 seconds.
d) If the Engine Shutdown option is active, ten minutes after all outputs are opened (OFF) the
engine will slow to idle speed and 30 seconds later it will shut down.
2) Emergency conditions
a) Depress the “EMERGENCY STOP BUTTON” located on front of the unit to the right of the
control panel. When pushed, this button shuts the generator set off. Pull the button back
out to reset it before restarting the generator set.
CAUTION
g) Low Fuel Warning and Fault
1) A Low Fuel Warning occurs when the unit is running and fuel levels drops below 10% in the fuel
tank. The unit will continue to operate until it is out of fuel or the operator shuts off the engine.
2) A Low Fuel Fault will display if the fuel level is below 10% and the engine is off. The engine can’t be
started until the fuel level is above 10%.
h) Display
1) The display will automatically turn off if the engine has been off at least 10 minutes. Pushing any
button will return the display to full brightness. However, if there is a warning or fault message on
the display, it will not turn off.
2) If the display is off, and the battery disconnect switch is closed, press the Engine pushbutton to
return the display to full brightness.
i) Battery Disconnect Switch
Do not use the “EMERGENCY STOP BUTTON” as a normal shutdown device.
Damage to the engine turbo charger may result without proper cooling time. Use the
Engine ON/OFF pushbutton for all normal engine shutdowns.
b) A condition of over-voltage, under-voltage or overload in the output circuit will automatically
open the load contactor and display a fault code to signal the operator which of the above
faults caused the protective monitor system to operate. After the fault has been corrected,
press the respective output pushbutton to reset the system. Proceed with power delivery
by pressing the same switch.
If the unit is not going to be used for a long period of time, open the battery disconnect switch to remove
12 VDC power to the control board and Cummins ECM controller. DO NOT open the battery disconnect
switch while the engine is running or within two minutes after the engine has shut down.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 34 of 104
3) Starting the 28.5 VDC generator set
CAUTION
The unit can deliver up to 2000 amps of current during the starting of an aircraft
engine. This much current will shear the propeller shaft of some aircraft. Therefore,
1) Default setup values
28 V Voltage (V): 28.5 VDC
28 V Compensation (V/600A): 0.0 (Set if GPU supplied with cable)
28 V Current Limit (A): 800 A
Output Mode: Simultaneous
Fan Control: Normal
Plug Temperature: Normally Open
2) Adjusting the Current Limit
make sure that the current limit is correctly set for the aircraft that is being powered.
a) The unit remembers the last current limit that was selected. This value will be used whenever the
28VDC output is turned on.
b) If the current limit needs to be changed, use the following procedure:
i. With the unit’s engine running and the 28 VDC power is off, the up or down arrows in the
current limit section can be used to change the current limit value. The step size used for
changing the current limit is set in the Current Limit Step Size setup menu screen.
ii. Once the correct value is selected, use the below procedure to start the unit.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 35 of 104
With the engine running and DC
power OFF, press the “Up arrow”
to increase the DC current limit.
With the engine running and DC
power OFF, press the “Down arrow” to decrease the DC current
limit.
3) Providing 28.5 VDC power.
a) With the engine running and the output cable securely inserted into
the aircraft power receptacle, press the ON/OFF/Reset button to
start providing 28.5 VDC power to the aircraft.
b) During operation, various parameters can be viewed via the display. Use the navigation keys ▼▲
to browse through the available screens:
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 36 of 104
c) Turn off the unit by pressing the 28VDC Start/Stop button. The engine will slow down to 1000 rpm
and the display will show the amount of time left in the engine cool down period. Once the cool
down period is finished, the engine will turn off. Always ensure that the output is off before removing
the aircraft plug.
Note!
Please note that the 28 VDC Start/Stop button also functions as a Reset push button.
If, for some reason, the unit stops due to an error / failure, record the fault number and message and forward
this information to your maintenance personnel. If the fault is no longer active, press the Start/Stop/Reset to
reset the alarm and the unit.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 37 of 104
3) Icon Menu
The Icon Menu can only be accessed from the Default screen. Press the center navigation button ● while in the
default menu and hold it down for approximately 5 seconds. If access to the Icon menu has been locked out,
the word DISABLED will be displayed when the center button is pressed. Enter the correct unlock pattern and
then press and hold the center button for approximately 5 seconds.
Center Navigation
Button
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 38 of 104
a) View Parameters Menu
The View Parameters Menu is accessed from the Icon screen. Press the center navigation button ● while in
default menu and hold down for approximately 5 seconds. The Icon menu is displayed, press the right
navigation button to highlight the icon.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 39 of 104
b) Setup Menu
The Setup Menu is accessed from the Icon screen. Press the center navigation button ● while in the default
menu and hold down for approximately 5 seconds. The Icon menu is displayed, press the right navigation
button to highlight the Setup icon.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 40 of 104
Setup (continued) – Menu structure
11:27:47Setup Menu 28/06/2013
Cable Temperature
Normally Open
◄ Back ● Modify
Settings:
Normally Open
Normally Closed
Refer to Section 3 – 4.7
11:27:47Setup Menu 28/06/2013
Cable Temperature
Allow Engine Idle
Automatic Engine Shutdown
Real Time Clock Setup
Date / Time Format
Ethernet Configuration
◄ Back ● Select Parameter.
Highlight the by using the
navigation ◄▼▲► keys.
Press
● to select ”Setup” sub-menu.
Use the the ▼/▲ to browse through the
various set-up lines / parameters. The
selectable line will be highlighed in
green.
Press
● to select the parameter you
want to change.
● to Modify the parameter.
Press
Parameter will now be highlighted in
green.
Use the the ▼/▲ to adjust parameter.
Press
● to save changes.
Use ◄ to leave the sub-menu and
return to The basic Icon Menu.
Notice!
Availability of parameters may vary
depending on the mode of the unit
Standby / Engine Running etc.
11:27:47Setup Menu 28/06/2013
Allow Engine Idle
Enabled
◄ Back ● Modify
11:27:47Setup Menu 28/06/2013
Automatic Engine Shutdown
Bypassed
◄ Back ● Modify
11:27:47Setup Menu 28/06/2013
Real Time Clock Setup
◄ Back ● Modify
11:27:47Setup Menu 28/06/2013
Date / Time Format
HH:MM:SS I DD:MM:YYYY
◄ Back ● Modify
11:27:47Setup Menu 28/06/2013
Ethernet Configuration
◄ Back ● Modify
Settings:
Enabled
Disabled
Refer to Section 3 – 4.8
Settings:
Bypassed
Active
Refer to Section 3 – 4.9
Settings in additional sub-menu:
Month , Day, Year, Hour, Minute,
Second
Refer to Section 3 – 4.10
Settings:
HH:MM:SS I DD:MM:YYYY
HH:MM:SS AM I MM:DD:YYYY
Refer to Section 3 – 4.11
Settings in additional sub-menu:
Ethernet Mode
IP Address, Subnet Mask,
Gateway, DNS1
Format: 000.000.000.000
Refer to Section 3 – 4.12
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 41 of 104
Setup (continued) – Menu structure
11:27:47Setup Menu 28/06/2013
Modbus Slave Address
1
◄ Back ● Modify
Settings:
1 – 247
Refer to Section 3 – 4.13
11:27:47Setup Menu 28/06/2013
Modbus Slave Address
LED Brightness
Unit of Measure
Diagnostic Mode
Menu Lock Bypass
Battery Replaced
◄ B ack ● Se lect Parameter.
Highlight the by using the
navigation ◄▼▲► keys.
Press ● to select ”Setup” sub-menu.
Use the the ▼/▲ to browse through the
various set-up lines / parameters. The
selectable line will be highlighed in
green.
Press
● to select the parameter you
want to change.
● to Modify the parameter.
Press
Parameter will now be highlighted in
green.
Use the the ▼/▲ to adjust parameter.
● to save changes.
Press
Use ◄ to leave the sub-menu and
return to The basic Icon Menu.
Notice!
Availability of parameters may vary
depending on the mode of the unit
Standby / Engine Running etc.
11:27:47Setup Menu 28/06/2013
LED Brightness
Low
◄ Back ● Modify
11:27:47Setup Menu 28/06/2013
Unit of Measure
Imperial
◄ Back ● Modify
11:27:47Setup Menu 28/06/2013
Diagnostic Mode
Disabled
◄ Back ● Modify
11:27:47Setup Menu 28/06/2013
Menu Lock Bypass
Disabled
◄ Back ● Modify
11:27:47Setup Menu 2 8/06/2013
Warning: Do not confirm unless the
Control Board battery has been
replaced.
Confirm Battery Replaced
◄ B ack ● Modify
No
Settings:
Low
Medium
High
Refer to Section 3 – 4.14
Settings:
Metric
Imperial
Refer to Section 3 – 4.15
Settings:
Disabled
Engine Only
AVR Battery Only
Engine Interface
Refer to Section 3 – 4.16
Settings:
Disabled
Enabled
Refer to Section 3 – 4.17
Settings:
Yes
No
Refer to Section 3 – 4.18
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 42 of 104
Setup (continued) – Menu structure
11:27:47Setup Menu 28/06/2013
Language
◄ Ba ck ● Select Parameter.
Use the the ▼/▲ to browse through the
various set-up lines / parameters. The
selectable line will be highlighed in
green.
● to select the parameter you
Press
want to change.
11:27:47Setup Menu 28/06/2013
Language
English
◄ Ba ck ● Mod ify
Settings:
English, French, German,
Italian, Polish, Portuguese, etc.
Refer to Section 3 – 4.19
● to Modify parameter.
Press
Parameter will now be highlighted in
green.
Use the the ▼/▲ to adjust parameter.
Press
● to save changes.
Use ◄ to leave the sub-menu and
return to basic Icon Menu.
Notice!
Availability of parameters may vary
depending on the mode of the unit
Standby / Engine Running etc.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 43 of 104
1) 28V Voltage
This Setup submenu allows the 28 volt output to be adjusted between 19.0 VDC and 33.0 VDC using
the UP and DOWN navigation buttons. (Please note that the acceptable voltage range for all
commercial DC powered aircraft is 26V to 29V.
Enter the Setup Menu and then scroll up or down to the 28V Voltage submenu. Press the center ●
button to enter the submenu, and then press the ● button again to allow the value to be changed. Press
the up or down arrow buttons to change the selection. Press the center ● button to record the new
value. Press the LEFT arrow button to exit the submenu and return to the submenu list.
2) 28V Compensation
a) DC voltage drops quickly as the current increases over a given length of cable. This Setup
submenu allows the 28 volt output to be automatically adjusted as the load increases. The allowed
setting is between 0.0 and 3.0 VDC per 600 amps. Note that the maximum output voltage of the
unit is 33 VDC.
b) Enter the Setup Menu and then scroll up or down to the 28V Compensation submenu. Press the
center ● button to enter the submenu, and then press the ● button again to allow the value to be
changed. Press the up or down arrow buttons to change the selection. Press the center ● button to
record the new value. Press the LEFT arrow button to exit the submenu and return to the submenu
list.
3) Current Limit Step Size
a) If too much current is supplied to an aircraft engine, it is possible for the engine to shear the
propeller shaft. The Current Limit should be set to the maximum current the aircraft to be powered
can take (per the aircraft manufacturers recommendations). The Current Limit is set using the UP
and Down arrows on the Operators Panel. This submenu is used to set the step size the current
limit is changed by every time the UP or Down button is pressed. The current limit settings are from
300 amps to 2000 amps in steps of 50/100/200/300 amps. This menu selects the size of the steps
that the operator uses to adjust the current limit before turning on the 28 VDC to the aircraft.
b) Enter the Setup Menu and then scroll up or down to the Current Limit Step Size submenu. Press
the center ● button to enter the submenu, and then press the ● button again to allow the value to
be changed. Press the up or down arrow buttons to change the selection. Press the center ● button
to record the new value. Press the LEFT arrow button to exit the submenu and return to the
submenu list.
4) 28V Interlock
a) The 28V interlock is a personnel and equipment safety feature. This 28VDC signal will not be
present until the GPU closes its output contactor and provides power to the aircraft connector. The
connector typically has a split “C” socket with +28VDC on one side and a jumper to the return wire
on the other side of the socket. The GPU will not keep the output contactor closed if this voltage is
not detected on the return wire in the cable. (This option requires a special cable such as the
JB2840-30CS, JB2840-40CS or JB2840-50CS.)
Note! The value will be automatically reset to Active if the unit detects 28 volts on the "F" pin input of
the I/O board.
b) Go into the Setup Menu and then scroll up or down to the 28V Interlock submenu. Press the center
● button to enter the submenu, and then press the ● button again to allow the value to be changed.
Press the up or down arrow buttons to change the selection. Press the center ● button to record the
new value. Press the LEFT arrow button to exit the submenu and return to the submenu list.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 44 of 104
5) 28V Interlock Delay
a) The default value is 3.5 seconds. For safety, it is recommended to remain at this value or less.
b) Go into the Setup Menu and then scroll up or down to the 28V Interlock Delay submenu. Press the
center ● button to enter the submenu, and then press the ● button again to allow the value to be
changed. Press the up or down arrow buttons to change the selection. Press the center ● button to
record the new value. Press the LEFT arrow button to exit the submenu and return to the submenu
list.
6) Aircraft Connector Insertion
a) Some aircraft power cables are equipped with a split "C" socket in the connector. This device sends
a 28 VDC signal to the unit when the connector is inserted at least 90% of the way into the aircraft
power receptacle. Set this sub-menu value to Enable when such a cable is connected to the unit.
The default value is set to Disable.
b) Go into the Setup Menu and then scroll up or down to the Aircraft Connector Insertion submenu.
Press the center ● button to enter the submenu, and then press the ● button again to allow the
value to be changed. Press the up or down arrow buttons to change the selection. Press the center
● button to record the new value. Press the LEFT arrow button to exit the submenu and return to
the submenu list.
7) Cable Temperature
a) Some aircraft cables have temperature sensors installed in the connector body and/or replaceable
nose. This sub-menu allows the unit to accept Normally Opened or Normally Closed temperature
sensor switches to be used.
b) Go into the Setup Menu and then scroll up or down to the Plug Temperature submenu. Press the
center ● button to enter the submenu, and then press the ● button again to allow the value to be
changed. Press the up or down arrow buttons to change the selection. Press the center ● button to
record the new value. Press the LEFT arrow button to exit the submenu and return to the submenu
list.
8) Allow Engine Idle
a) When this option is set to Enable, the engine will ramp up to its idle speed (1,000 RPM) and wait for
an output to be turned on. Once an output is turned on, the unit will ramp up to its running speed
(1,600, 2,000 or 2,400 RPM) and energize the generator and close the selected output contactor
when the generator is stabilised. The unit will return to idle speed five seconds after all outputs are
turned off.
b) Enter the Setup Menu and scroll up or down to the Allow Engine Idle submenu. Press the center ●
button to enter the submenu, and press the ● button again to allow the value to be changed. Press
the up or down arrow buttons to change selection. Press the center ● button to record the new
value. Press the LEFT arrow button to exit the submenu and return to the submenu list.
9) Automatic Engine Shutdown
a) If the engine is running at its rated speed and all outputs are off for ten (10) minutes or the total load
is less than 5 amps, the engine will automatically go into its 30 second shutdown mode when this
function is active. The Setup submenu allows this option to be activated or bypassed.
b) Enter the Setup Menu and then scroll up or down to the Automatic Engine Shutdown submenu.
Press the center ● button to enter the submenu, and then press the ● button again to allow the
value to be changed. Press the up or down arrow buttons to change the selection. Press the center
● button to record the new value. Press the LEFT arro
the submenu list.
w button to exit the submenu and return to
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 45 of 104
10) Real Time Clock Setup
a) This set of sub-menu s allows the user to adjust the internal clock to the correct local time.
b) Go into the Setup Menu and then scroll up or down to the Real-Time Clock Setup submenu. Press
the center ● button to enter the submenu, and then press the ● button again to allow the value to
be changed. Press the up or down arrow buttons to change the selection. Press the center ● button
to record the new value. Press the LEFT arrow button to exit the submenu and return to the
submenu list.
11) Date/Time Format
a) The date and time format that is displayed on all the screens and reports can be adjusted using this
submenu. The selection is a 24 hour clock and DD:MM:YYYY date format or a 12 hour clock with
the MM:DD:YYYY date format.
b) Go into the Setup Menu and then scroll up or down to the Date/Time Format submenu. Press the
center ● button to enter the submenu, and then press the ● button again to allow the value to be
changed. Press the up or down arrow buttons to change the selection. Press the center ● button to
record the new value. Press the LEFT arrow button to exit the submenu and return to the submenu
list.
12) Ethernet Configuration
a) The sub-menu s allows the user to enter the Ethernet IP address, Subnet Mask, Gateway address
and DNS1 values for TCP/IP communications with a BMS or RMS central monitoring system.
b) Go into the Setup Menu and then scroll up or down to the Ethernet Configuration submenu. Press
the center ● button to enter the submenu, and then press the ● button again to allow the value to
be changed. Press the up or down arrow buttons to change selection. Press the center ● button to
record the new value. Press the LEFT arrow button to exit the submenu and return to the submenu
list.
13) Modbus Slave Address
a) If the unit will be part of an RS-485 Modbus RTU BMS/RMS monitoring system, it must be assigned
a Modbus Slave Address. This sub-menu allows the user to enter the slave address.
b) Go into the Setup Menu and scroll up or down to the Modbus Slave Address submenu. Press
center ● button to enter the submenu, and press the ● button again to allow the value to changed.
Press the up or down arrow buttons to change the selection. Press the center ● button to record the
new value. Press the LEFT arrow button to exit the submenu and return to the submenu list.
14) LED Brightness
a) The unit status LED’s have three brightness levels. The default is set to medium.
b) Go into the Setup Menu and then scroll up or down to the LED Brightness submenu. Press the
center ● button to enter the submenu, and then press the ● button again to allow the value to be
changed. Press the up or down arrow buttons to change the selection. Press the center ● button to
record the new value. Press the LEFT arrow button to exit the submenu and return to the submenu
list.
15) Unit of Measure
a) This submenu is used to set the unit of measurements to Metric or Imperial.
b) Go into the Setup Menu and then scroll up or down to the Unit of Measure submenu. Press the
center ● button to enter the submenu, and then press the ● button again to allow the value to be
changed. Press the up or down arrow buttons to change the selection. Press the center ● button to
record the ne
list.
w value. Press the LEFT arrow button to exit the submenu and return to the submenu
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 46 of 104
16) Diagnostic Mode Disabled
a) This setup submenu is used to assist in the troubleshooting procedure. The default setting is
“Disabled”; use the “Engine Only” to verify engine performance. The “Engine Interface” allows read
only access to the engine ECM module. In the “Engine Interface” mode, the engine ECM will
perform a self-test and then enter its Run mode. (The display will indicate running in the engine
screen). In this mode the output contactor can be toggled on and off to verify that is functioning
correctly.
b) The engine must be stopped before any of these modes can be changed.
c) Enter the Setup Menu and then scroll up or down to the Diagnostic Mode submenu. Press the
center ● button to enter the submenu, and then press the ● button again to allow the value to be
changed. Press the up or down arrow buttons to change the selection. Press the center ● button to
record the new value. Press the LEFT arrow button to exit the submenu and return to the submenu
list.
17) Menu Lock Bypass
a) This submenu is used to lock out the center button on the navigation keypad which will prevent
access to the ICON screen. Disabled allows access to the Icon screen when the center button is
pressed for 5 seconds. Enabled locks out the center button. When the center button is pressed the
screen will display DISABLED. Technicians can gain temporary access to the Icon menu by
performing the following sequence of button presses: Right Arrow, Up Arrow, Down Arrow, Down
Arrow. Holding the center button again (approx. 5 seconds) will take you to the main Icon menu.
The default is set to disabled.
b) Go into the Setup Menu and then scroll up or down to the Menu Lock Bypass submenu. Press the
center ● button to enter the submenu, and then press the ● button again to allow the value to be
changed. Press the up or down arrow buttons to change the selection. Press the center ● button to
record the new value. Press the LEFT arrow button to exit the submenu and return to the submenu
list.
18) Confirm Battery Replaced
Situated on the back of the control board, is a coin type lithium battery which ensures that Firmware /
Set-up data etc. are not lost during utility drop-outs. The expected life of the battery is approximately 7
years. Note, a low battery voltage does not affect the internal safety system of the GPU that monitors
the output voltage, among others. Thus, aircraft connected to the GPU are not exposed to any danger.
However, to avoid loss of data and Control Board lock up *, we recommend changing the battery after 5
years of use.
Note!
A time stamp is stored in the ID chip (A6) upon production and after 5 years a warning occurs at the
display, telling the user/operator to replace the Control Board battery. It is strongly recommended to
change the battery when this message is shown:
Fig. 8.2.1
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 47 of 104
To allow the user/operator to use the converter, it is possible to postpone the battery change, by
pressing the ◄ (left arrow) push button. The warning message occurs 90 seconds after the unit is
powered on or the output contactor(s) are opened (the unit is in Standby Mode). If this message is
ignored for 6 months, the controls will be locked out and the below failure message will be displayed.
Fig. 8.2.2
The battery must be changed before the unit can be operated again.
To ensure high reliability of the back-up battery, the only type of battery that can be used on
the Control Board is the Panasonic BR-2032
Go into the Setup Menu and then scroll up or down to the Confirm Battery Replaced submenu. Press
the center ● button to enter the submenu, and then press the ● button again to allow the value to be
changed. Press the up or down arrow buttons to change the selection. Press the center ● button to
record the new value. Press the LEFT arrow button to exit the submenu and return to the submenu list.
19) Language
This submenu is used to change the language that all of the display screens, messages, alarms and
reports are displayed in. The unit comes with English, French, German, Italian, Polish, Portuguese,
Czech, Russian, Turkish and Spanish already installed. Other languages can be added as required.
The default is set to English.
Go into the Setup Menu and then scroll up or down to the Language submenu. Press the center ●
button to enter the submenu, and then press the ● button again to allow the value to be changed. Press
the up or down arrow buttons to change the selection. Press the center ● button to record the new
value. Press the LEFT arrow button to exit the submenu and return to the submenu list.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 48 of 104
c) Black Box
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 49 of 104
d) Power Log
The Power Log Menu is accessed from the Icon screen. Press the center navigation button ● while in
the default menu and hold it down for approximately 5 seconds. The Icon menu is displayed, press the
right navigation button to highlight the Power Log icon.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 50 of 104
e) Update/Save Log Menu
The Update/Save Log Menu is accessed from the Icon screen. Press the center navigation button ● while in the
default menu and hold it down for approximately 5 seconds. The Icon menu is displayed, press the right
navigation button then the down button to highlight the Update/Save Log icon.
Update/Save Log – Menu structure
10:30:00USB MENU 28/06/2013
USB Firmware Update Detected
Do you wish to update?
Press ● to update firmware
10:30:00USB MENU 28/06/2013
Update Display Software
Update Control Card Software
Save Logs
◄ Back ● Select
Highlight the by using the navigation ◄▼▲►
keys.
● to select ”Update/Save Log Menu” sub-menu.
Press
The default function ”Update Display Software”
is green highlighted. If another function is wanted, use
the the ▼/▲ to highlight the function.
Before pressing
please remember to insert a USB stick into the USB port
on the Display (located on the side of the Display
enclosure inside the unit).
● to select the function.
Press
● to confirm update firmware.
Press
● to select ”Update Display Software”,
10:30:00USB MENU 28/06/2013
Update in Progress
Do not turn off or reset during update
18%
10:30:00USB MENU 28/06/2013
Updating Display
Update Succesful! Please Reboot!
The firmware is now being uploaded to the display card.
Upload % is counting from 0% to 100%. The system
automatically reboots if the update is successful.
Otherwise, an Update has failed! Message is displayed.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 51 of 104
Update/Save Log (continued) – Menu structure
10:30:00USB MENU 28/06/2013
USB Firmware Update Detected
Do you wish to update?
0.0%
Press ● to update firmware
10:30:00USB MENU 28/06/2013
Update Display Software
Update Control Card Software
Save Logs
◄ Back ● Select
Highlight the by using the navigation
◄▼▲► keys.
Press
● to select ”USB Menu” sub-menu.
Use the the ▼/▲ to highlight the function
”Update Control Card software”.
Before pressing
● to select ”Update control card
software”, please remember to insert an USB stick
into the USB port on the control card (located on
the interface board).
● to select function.
Press
Press
● to confirm update firmware.
10:30:00USB MENU 28/06/2013
Updating Control Card
8%
10:30:00USB MENU 28/06/2013
Updating Control Card
Update Succesful! Please Reboot!
The firmware is now being uploaded to the display
card. Upload % is counting from 0% to 100%. The
system automatically reboots if the update is
successful. Otherwise, an Update has failed!
Message is displayed.
USB connection
Control card
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 52 of 104
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 53 of 104
Chapter 2 Service and Troubleshooting
Section 1 Maintenance Inspection/Check
1) General
To make certain the generator set is always ready for operation, it must be inspected and
maintained regularly and systematically so that defects may be discovered and corrected before
they result in serious damage to components, or failure of the equipment.
Warning
STOP operations at once if a serious or possibly dangerous fault is discovered
2) Maintenance Schedule
a) General
A periodic maintenance schedule should be established and maintained. A suggested schedule
is provided in Figure 2-1-1 on the following pages. It may be modified, as required to meet
varying operating and environmental conditions. It is suggested that generator set and vehicle
inspections
be coordinated as much as possible.
b) Maintenance Schedule Check Sheet
It is strongly recommended that the customer use a maintenance schedule check sheet such
as the one in the engine manufacture’s operation manual. The check sheet will provide a record
and serve as a guide for establishment of a schedule to meet the customer’s maintenance
requirements for his specific operation.
c) Time Intervals.
The schedule is based on both hours of operation and calendar intervals. These two intervals
are not necessarily the same. For example, in normal operation the oil change period, based
on hours of operation, will be reached long before the three months calendar period. The
calendar period is included to make certain services are performed regularly when the
equipment is stored, or being operated infrequently. Lubricating oil standing in engines that are
stored, or used very little, may tend to oxidize and may require changing although it is not dirty.
Perform all services on a whichever- comes-first basis.
d) Identification o f Interval Periods.
Each interval period is identified by a letter A, B, C, etc. For example, services under B
schedule should be performed at the end of each 250 hours of operation, or every three
months, BR service is performed during the BREAK IN period (first 50-150 hours) and AR
service is performed AS REQUIRED.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 54 of 104
WARNNGHourly Interval AR 50-150
Calendar Interval
Symbol AR
Engine
Change Air Cleaner Cartridge
Check Coolant Hose and Clamps
Check Crankcase Oil Level
Drain Fuel PreFilter Elements
Check Coolant Level
Check for Leaks and Correct
Check Air Cleaner Indicator
Check Exhaust System
Charge-Air-Cooler (CAC) and Piping
Change Lubricity Fuel Filter Element
Check Radiator Core and Hoses
Check Oil Pressure and Record
Change Crankcase Oil
Change Oil Filter Element
Check Engine and Generator Mounts
Check Coolant, Additive-Concentration
Check Fan Hub and Drive Pulley
Check Hose Clamps on Air Intake Side
Check Belt Conditions and Tensioner
Check and/or Adjust Valve Clearance
Check Water Pump
Steam Clean Engine
Clean Fuel System
Check Alternator
Check Starter Motor
Check Vibration Damper
Check Cooling and CAC systems
X
X
Once Daily3 Mo. 6 Mo. 1 Yr. 1.5 Yr. 2 Yr.
X
X
Figure 2-1-1 Maintenan ce
(Sheet 1 of
10
250500100015002000
BR
X
X
X
X
X
X
X
X
A
X
X
X
X
X
X
B
X
X
X
X
Schedule
2)
C
X
X
X
X
X
D
E
X
X
X
X
X
X
X
X
X
F
X
X
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 55 of 104
Hourly Interval AR 50-150
Calendar Interval
Symbol AR
Engine (continued )
Flush and Change Coolant
Drain & Inspect Fuel Tank
Check Fan Mounting
Clean Cooling System
Check Hoses
Clean Electrical Connections
Check Thermostats and Seals
Electrical (12 VDC System)
Check All Lights
Check Alternator Charging Rate
Check Battery
Clean Battery Terminals
Check Wiring and Connections
Check All Engine Meters
Once Daily3 Mo. 6 Mo. 1 Yr. 1.5 Yr. 2 Yr.
X
X
X
10
250
BR
A
B
X
X
X
Spring & Fall
Spring & Fall
Spring & Fall
Spring & Fall
Fall
X
X
Note: “G” service (10,000+ hours) items are covered in section j) below.
500 1000 1500 2000
C
D
X
E
F
X
3) Inspection/Checks
a) General
1) See Chapter 2-2 for detailed maintenance procedures.
2) See Chapter 2-3 for adjustment and test procedures.
b) “AR” Checks and Operations (As Required)
1) Engine
a) Change Air Cleaner
i. Replace the air filter when the “Air Filter Clogged” warning is displayed. These filters
ii. Check and tighten, as required, all coolant hose clamps, air intake hose clamps and
Figure 2-1-1 Maintenan ce
(Sheet 2 of 2
should not be washed because washing breaks down the material inside the filters.
exhaust clamps. Check all coolant hoses, air intake hoses and exhaust pipes for leaks.
Schedule
)
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 56 of 104
b) Electrical System (12 VDC) – Check Battery Terminals
i. Periodically, open the battery compartment panel in the right cable tray and visually
check the battery cable connectors and battery posts. If corrosion is observed,
disconnect the cables and clean battery posts and connectors with a wire brush or
special battery post-cleaning tool. Coat the posts and connectors with a light film of
petroleum lubricant before reconnecting the cables.
c) Electrical (28.5 VDC System) -- Check Output Voltage
i. Check the output voltage and be sure it is set for 28.5 VDC System. Adjustment can be
made using the Setup menu. (See Chapter 1-3, paragraph 3.a.)
c) “BR” Checks and Operations (Break-In Period, Once After 50-150 hrs.)
The following procedures are precautionary measures taken on most new engines. If a problem
occurs with any of the following issues, be sure to recheck it after the next 50-150 hours.
1) Engine
a) Check for leaks and correct. This involves an overall inspection of the engine and may
require some maintenance if leaks are found. Refer to the engine manufacturer’s
operations manual for assistance.
b) Change all fuel filter elements. Metal shavings from the new fuel tank can clog the filter.
c) Change crankcase oil. New engines often release metal shavings more frequently.
Therefore, the crankcase oil must be changed as a precautionary measure.
d) Change oil filter element. The oil filter should be changed with the oil.
e) Check engine and generator mounts to ensure they are properly installed and they have not
worked loose. (Torque i s set at 100 N-m, 73.7 ft-lb.).
f) Check coolant additive concentration. Refer to the engine manufacturer’s o perations
manual for assistance.
g) Steam clean the engine to free it of oil and dirt to prevent uneven engine cooling “hot
spots”. The oil and dirt can also fall into the engine and fuel system when covers are
removed during repair work.
h) Inspect the water pump weep hole for indication of a steady leak. If a steady flow of coolant
or oil is observed, replace the water pump with a new or rebuilt unit. Refer to the engine
manufacturer’s operations manual for assistance.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 57 of 104
d) “A” Checks and Operations (10 Hours or Daily).
1) Engine.
CAUTION
CAUTION
a)
Check Crankcase Oil Level.
DO NOT overfill. DO NOT operate the engine with oil level below the lower bar or
above the upper bar on the dipstick.
i. Check oil level daily with oil gauge dipstick.
ii. Oil level should not be checked until 3 to 5 minutes after engine shutdown. Keep oil level
as near the upper bar as possible.
b) Drain Fuel Lubricity Filter/Pre-Filter Element
The life of the fuel pump and injectors can be extended if the operator drains about a cup
of fuel from the fuel pre-filter element to remove water and sediment before starting the
engine each day.
BE SURE to prime and bleed the fuel system after draining the filters, replacing filter
element, or if the fuel tank has run empty. Failure to do so can cause engine-starting
problems.
i. Provide a container for catching drained fuel.
ii. Open the drain valve on the fuel/water filter by turning it counterclockwise.)
WARNING
iii. Drain the filter until clear fuel is visible.
iv. Tighten the drain valve.
v. Safely dispose of drained fuel.
vi. Purge air from fuel system if necessary.
c) Check Coolant Level
i.
Check coolant level daily or at each fuel fill interval. Investigate for cause of any coolant
loss.
Cooling system is pressurized. To avoid personal injury, DO NOT remove radiator
cap when engine is hot.
d) Check for Leaks and Correct
At each daily start-up, check for coolant, fuel, and oil leaks. Coolant leaks may be more
noticeable when components are cold. Observe pumps, hoses, fittings, gasket connections,
etc., for signs of leakage. Correct as required.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 58 of 104
Water Drain
WARNING
Figure 2-1-2 Fuel Lubrici ty
Drain
r Drain
e) Check Fault Code Meter.
At each daily start-up, observe the fault screen on the display of the control panel. If the
display shows “AIR FILTER CLOGGED”, change the air filter. See Chapter 2-4 for other
fault codes.
f) Check Exhaust System.
Visually inspect muffler and exhaust pipes for rust and signs of approaching failure.
Listen for any gasket or joint leaks.
A leaking and defective exhaust system could be a fire hazard.
2) Electrical System (12 VDC)
a) Check All Lights.
Check all indicating l igh ts to be sure they operate when they should. If any light fails to
operate, check the indicator and insure proper power is being given. If power is present and
the light does not activate, replace the light fixture.
b) Check Engine Battery Voltage.
Observe the engine voltmeter each time the engine is started to be sure the alternator is
functioning correctly and charging the batteries. If the batteries need to be replaced, be sure
the replacements meet the specifications for Cold Cranking Amps (CCA) and Reserve
Capacity.
c) Check the operation of all the engine indicators.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 59 of 104
3) Electrical (28.5 VDC System).
a) Check Output Cables and Connector.
Check the output cable and plug connection for damaged insulation and contacts each time
the connector is detached from the aircraft.
b) Monitoring sensors.
Verify that the voltage, amps and frequency readings are di splaying correctly (use up and
down arrows) each time the unit is started.
e) “B” Check and Operations (250 Hours or 3
1) Engine.
a) Prevent Diesel Engines Wet Stacking.
All diesel engines operated for extended periods under light load may develop a condition
commonly referred to as wet-stacking. This condition results from the accumulation of
unburned fuel in the exhaust system. It is recognizable by fuel oil wetness around the
exhaust manifold, pipes, and muffler along with an excessive amount of soot.
Wet-stacking is common, and can be expected in diesel engines operated under light loads.
Light loads do not allow the engine to reach the most efficient operating temperature for
complete combustion of fuel and will also increase the fuel consumption rate. The unburned
fuel collects in the exhaust system to create the wet condition known as wet-stacking.
To alleviate wet-stacking in lightly loaded engines, it is recommended that the machine be
connected to a load bank after each 250 hours of use and operated under full rated load for
one hour. This will burn away and evaporate the accumulation of fuel and soot in the exhaust
system. This clean-out procedure should be considered as a regular maintenance operation
for machines operated under light loads.
b) Charge-Air-Cooler and Piping.
i. Inspect the charge-air-cooler for dirt and debris blocking the fins. Check for cracks,
holes, or other damage.
ii. Inspect the pipes and hoses for leaks, holes, cracks, or loose connections. Tighten
the hose clamps if necessary.
Months).
c) Check and record oil pressure.
After each oil change, check and record oil pressure at operating speed after oil has
warmed to approximately 140º F. Record oil pressure under identical conditions at each
oil change interval. A comparison of pressure at idle speed with previous readings will
give an indication of progressive wear of oil pump, bearings, shafts, etc. Investigate any
abnormal change in pressure readings.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 60 of 104
d) Check Radiator Core and Hoses.
i. Inspect the radiator core for dirt and debris blocking the fins. Clean as necessary.
Check for cracks, holes, or other damage.
ii. Check Fuel Pump.
iii. Inspect the fuel injection pump mounting nuts for loose or damaged hardware.
2) Electrical (12 VDC System).
NOTE: The battery furnished with this generator set is MAINTENANCE FREE. Check battery
terminals and clean if necessary.
a) Check the battery terminals and clean if necessary.
f) “C” Checks and Operations (500 Hours or 6 Months)
1) Engine.
CAUTION
a)
Check Engine and Generator Mounts
An unstable or loosely mounted engine can create hazardous environment and may
damage equipment.
i. Engine mount bolts must be torqued to 100 N-m (73.7 ft-lb.).
ii. Generator mount bolts must be torqued to 100 N-m (73.7 ft-lb.).
b) Change oil and oil filters.
c) Change all fuel filters.
d) Check Coolant Additive Concentration.
The cooling system protective liquid (nitrite-, am ine- an d phosphate free) provides
effective protection against corrosion, cavitation, and freezing. See engine
manufacturer’s operation manual for ordering and mixture details.
2) Electrical (12 VDC sy st em).
3) Wiring.
a) Inspect all cables and leads for worn or damaged insulation.
b) Connections.
i. Inspect connectors for damaged or corroded condition.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 61 of 104
1) Electrical (28.5 VDC System).
a) Protective Monitoring Circuits.
Check operation of all protective monitoring circuits to make certain they will function if a
fault occurs in the output circuit. Procedures for testing these circuits are contained in the
Adjustment/Test section of this manual.
b) Inspect Wiring and Connections.
Check all cables, leads, and wiring for broken, worn and damaged insulation. Check all
connections for tightness.
c) Clean and inspect generally.
g) “D” Checks and Operations (1000 Hours or 1
1) Engine.
a) Check Fan Hub and Drive Pulley.
Inspect for loose bolts or worn features. Tighten bolts and replace parts if necessary. Refer
to the engine manufacturer’s operations and maintenance manual for assistance and the
most update to date information.
b) Check Hose Clamps on Air Intake Side.
Be sure that all clamps are properly secured to prevent l eaks and all hose are in good
condition.
c) Check Belt Condition and Tensioner.
Refer to the engine manufacturer’s operations and maintenance manual for assistance and
the most update to date information.
d) Check and/or Adjust Valve Clearance.
Refer to the engine manufacturer’s operations and maintenance manual for assistance and
the most update to date information.
e) Check Water Pump.
Inspect the water pump weep hole for indication of a steady leak. If a steady flow of coolant
or oil is observed, replace the water pump with a new or rebuilt unit. Refer to the engine
manufacturer’s operations manual for assistance.
Year)
f) Drain and Inspect Fuel Tank
Annually drain the fuel tank and inspect it for dirt, debris or Diesel fuel “algae”. Clean the
tank if necessary. (See Chapter 2-2)
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 62 of 104
h) “E” Checks and Operations (1500 Hours or 1.5 Years)
1) Engine.
a) Steam Clean Engine.
There are several reasons why the engine exterior should be kept clean. Dirt on the outside
will enter fuel and oil filter cases and rocker housings when covers are removed, unless dirt
is removed first. A clean engine will run cooler and develop fewer hot-spots. Steam
cleaning is one of the most satisfactory methods of cleaning and engine; however, there are
some CAUTIONS to be observ e d.
WARNING
Exercise care to avoid injury and damage to eyes and skin
CAUTION
1. If a cleaning compound is used, select one that is free from acid and will not
remove paint.
2. Protect (or remove) all electrical accessories, such as voltage regulator, alternator,
and electrical wiring.
3. Seal all openings. DO NOT use a flammable solvent.
4. DO NOT use mineral spirits or solvents on a hot engine.
5. Remove or protect bottom panel of unit (belly pan) to protect insulation.
b) Clean Fuel System.
See engine manufacturer’s operation manual for instructions.
c) Check Alternator and Cranking Motor.
The alternator and cranking motor on this engine require no periodic lubrication.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 63 of 104
i) “F” Checks and Operations (2000 Hours or 2 Years).
1) Engine.
a)
Check Vibration Damper.
2
3
1
4
6
1. Fan
2. Exhaust Outlet
3. Alternator
Pulley
Figure 2-1-3 Engine
4. Belt Tensioner
5. Fuel Pump
6. Vibration Damper
Accessories
5
Check vibration damper for looseness, wobble, chunking and streaking. Also verify the hub
bolts are tightened to the engine manufacturer’s specifications.
Refer to the engine manufacturer’s operations and maintenance manual for assistance
and the most update to date information.
b) Check Charge-Air-Cooler and Radiator Systems.
i. Check for damaged hoses and loose or damaged hose clamps.
ii. Check the radiator for leaks, damage, and build-up of dirt in the fins. Clean or
replace as necessary.
c) Flush cooling system and change coolant.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 64 of 104
j) “G” Checks and Operations (Over 10,000 Hours).
1) Engine.
a. Refer to Cummins Engine Manual for recommended maintenance and overhaul.
2) Engine/ Generator Assembly
a. Note: All Generator Overhaul items to be performed by a qualified generator/ motor
facility
b. Replace Generator Bearings
i. Contact Factory for Detailed Instructions
c. Inspect Front and Rear Bearing Housings
i. Bearing is a press fit, contact the factory for detailed instructions
d. Inspect Generator Shaft for Wear
i. Replace Rotor Assembly if required. Contact the factory for detailed
3) Check Fan Mounting.
a) Check fan to be sure it is securely mounted.
b) Check for fan wobble and/or broken/cracked blades.
c) Check fan hub and crankshaft pulley for secure mounting. (2) Check cooling system each
spring and fall. Clean if necessary. (3) Check All Hoses.
4) In addition to daily checks of hoses for leaks, inspect hoses thoroughly each time the cooling
system is cleaned and serviced.
a) Inspect for signs of deterioration and collapse. Inspect for cracks and cuts. Inspect for
cutting and deformation caused by hose clamps. Replace hoses as required.
5) Check thermostat and seals each fall when cooling system is serviced.
Operation Manual – ITW GSE 6400 Tier 4
(Ig
OM2248 Rev B
Page 65 of 104
l) Lamps and Fuses:
1) Check all lamps daily.
2) Check fuses as required.
3)
The fuse cha rt l i st s all fuses wi th th ei r l o cati on , siz e , and ty pe.
Item Protected
Display Board Interface Board
Control Board Interface Board
Exciter Circuit (12V) Interface Board
Contactors Interface Board F4
Relays
Key
Switch
ECM Dongle Interface Board
Exciter (Out) Interface Board
Engine Ai r
Heater
nition)
ECM
Interface Board F9
Intake
Location
Interface Board
Interface Board
Engine
Panel
Electrical
Schematic
Identifier
F1
F2
F3
F5
F6
F7
F8
F10
Type
2A
5A
5A
5A
2A
5A
5A
10A
500V Cylindrical
30A
ANL-150
ITW PART NO.
AP-SI2076
AP-SI2075
AP-SI2075
AP-SI2075
AP-SI2076
AP-SI2075
AP-SI2075
AP-SI2085
AP-SI2078
FU11370
Figure 2-1-4 Fuse Identification Chart
Operation Manual – ITW GSE 6400 Tier 4
g
(
)
A
A
A
A
OM2248 Rev B
Page 66 of 104
Section 2 Maintenance Procedures
1) General
A suggested maintenance schedule is provided in Section 1 of this Servicing Chapter. Each step of
the schedule is also covered in general in Section 1. This Section covers maintenance in more detail,
where necessary.
Item Maintenance Required
Check oil level daily or after every 10 hours of use. Change oil and the oil filter
Engine Oil
Fuel/water Pre-Filter Drain filters daily. Change the filter elements every 500 hours or after 6 months
Coolant
after the first 50 to 150 hours of use, then at 500 hours or 6 month intervals
thereafter. En
of use, whichever comes first.
Check coolant level daily. Service and maintain coolant system according to
Section 2-2, paragraph 6. Engine coolant capacity is approximately 15.5 quarts
14.7 liters
ine oil capacity is approximately 11.6 quarts (11 liters).
Coolant hoses and
connections
Air Cleaner
Fan Belt Check fan belt condition and tension every 1000 hours or 1 year of use.
lternator
Starter Starter motor bearings are sealed and require no periodic lubrication.
Water Pump The water pump is packed at assembly and requires no periodic lubrication.
Fan Hub The fan hub is lubricated at assembly and requires no periodic lubrication.
C Generator Periodic cleaning –no lubrication or adjustment required
Generator Controls No periodic maintenance is required. Adjustments are covered in Section 2-3.
Trailer
WARNING
STOP alloperations at once if a serious or dangerous fault is discovered.
Check coolant hoses and connections daily for leaks.
Change air cleaner filter as required when the fault code display on engine control
panel shows the “Air” code.
lternator bearings are sealed and require no periodic lubrication.
nnually grease the wheel bearings.
Figure 2-2-1: Lubrication and Maintenance Chart
Operation Manual – ITW GSE 6400 Tier 4
A
)
(
)
OM2248 Rev B
Page 67 of 104
2) Lubrication
a) General
Proper lubrication is one of the most important steps in good maintenance procedure. Proper
lubrication means the use of correct lubricants and adherence to a proper time schedule.
Lubrication points, frequency of lubrication, recommended lubricants and filters are indicated in
Figures 2-2-1 and 2-2-2.
This section incorporates the engine maker’s, engine lubrication recommend atio ns from their
Operation and Maintenance Manual.
b) Lubrication schedule
Time schedules indicated on the Maintenance Schedule, Figure 2-2-1, are approximate and
based on average operating conditions. It may be necessary to lubricate more frequently under
severe operating conditions such as: low engine temperatures, high oil temperatures, or
intermittent operation. However, time intervals should not exceed those indicated in the chart
without careful evaluation.
c) Oil specification
The engine lubricating oil that is recommended by the engine manufacturer is identified by an API
(American Petroleum Institute) classification designation. The manufacturer does not recommend
any specific brand of lubricating oil.
The use of quality lubricating oil, combined with appropriate lubricating oil drain and filter change
intervals, are important factors in extending engine life.
Oil Type
Capacity
Oil Filter
Replacement
Part Number
Lube Oil Viscosity
Required as per
Ambient
Temperatures
Synthetic Oils
Use oil specification API CF-4, HT/HS Viscosity 3.7cP minimum.
Oil recommended for the diesel engines in this application is API Class CCMC.
Refer to the manufacturer’s operation manual.
pproximately 10 quarts (9.5 liters
Cummins: LF9279
VISCOSITY
SAE 15W40 (Preferred)
SAE 10W30
SAE 5W30
SAE 0W30
See the engine manufacturer’s operations manual for usable synthetic oils and
instructions.
Figure 2-2-2: Lubrication Specifications
AMBIENT TEMPERATURE CONDITIONS
0ºF (-18ºC) and above for most climates
-10ºF to +50ºF (-23ºC to +10ºC) Winter conditions
-20ºF to +50ºF (-29ºC to +10ºC) Arctic Conditions
-20ºF and below to +50ºF
-29ºC and Below to +10ºC
Operation Manual – ITW GSE 6400 Tier 4
A
g
OM2248 Rev B
Page 68 of 104
d) Changing engine oil
Change the oil once after the first 50 - 150 hours of use and then every 500 hours of engine
operation thereafter. The generator set is equipped with an hour meter to record actu al engine
operating time.
The ideal time to change engine oil is soon after a power delivery run, when the engine is at
operating temperature. If lubricating oil is drained immediately after the unit has been run for
some time, most of the sediment will be in suspension and will drain readily.
Change the oil filter element each time the oil is changed.
CAUTION
High ash oils may produce harmful deposits on valves that can cause valve
burning.
Do not use solvents as flushing oils in running engines.
lways use clean containers, funnels, etc.
Dipstick
ure 2-2-3: Oil Fill and Check Locations
Fi
Oil Fill
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 69 of 104
Change oil as follows:
1) Provide an open container for catching the old oil below the oil drain plug. Container capacity
must be greater than 20 quarts (18.9 liters).
2) The oil drain tube can be found by the
muffler at the front of the unit.
3) Remove the drain cap (older models or
turn the valve handle.
4) While oil is draining, change the oil
filter element. See instructions below.
5) Provide a container for catching spilled
oil from the filter.
6) Remove the oil filter by turning it counter-clockwise
and inspecting it.
7) NOTE: The gasket can stick to the filter head. Make sure it is removed before installing a
new filter.
8) Fill the new filter with clean lubricating oil before installation.
9) Apply a light coating of lubricating oil to the gasket-sealing surface and install the filter. DO
NOT over tighten the filter.
CAUTION
CAUTION
WARNING
10) Clean the drain cap and install when engine oil has completely drained or close the drain
valve.
11) Refill the engine with new, clean oil that meets engine manufacturer’s recommendations. Use
the oil fill tube by the filter or the oil fill opening at the top of the engine.
Remember to close the drain cap and install the new oil before starting the engine.
12) Start engine and check oil pressure at once. Allow engine to run for 5 minutes, check for
leaks then stop the engine.
13) After the engine has been stopped for about 5 minutes, recheck the oil level. Add oil, if
required, to bring the level up to the high bar on the oil dipstick.
If bearing metal particles are found on the element or in the shell, the source should
be determined before a failure.
STOP operations at once, if a serious or possibly dangerous fault is discovered.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 70 of 104
e) Engine Accessories Lubrication
1) Alternator
Most alternators contain sealed bearings and require no periodic lubrication, however,
check to make certain there are no lubrication points on your particular alternator.
2) Starter
Most starting motors are lubricated at assembly and should be re-lubricated only when
the starter is removed and disassembled, however, inspect the starter to make certain it
has no lubrication points.
3) Water Pump
The water pump is packed at assembly and requires no periodic lubrication. Replace
pump if signs of lubricant leakage are found.
4) Fan Pulley
The fan hub is also lubricated at assembly and requires no periodic lubrication. Replace
hub if lubricant is leaking.
f) Trailer Lubrication
1) Wheel bearings
Inspect each wheel bearing annually to ensure that there is sufficient grease in the
assembly.
2) Fifth Wheel Hub Bearings
Inspect the Fifth Wheel Hub bearing every three years to ensure that there is sufficient
grease in the assembly.
Excludes those of sodium or soda
soap thickness.
NLGI #2 Grade Lithium Complex EP
Grease
Operation Manual – ITW GSE 6400 Tier 4
r
OM2248 Rev B
Page 71 of 104
3) Servicing the Air Cleaner
A definite time schedule for cleaning or changing the air cleaner cannot be determined because of
varying operating conditions. Pull the yellow tab out (about 1 inch) then rotate the hub counterclockwise about one inch and pull it off of the housing to access the air cleaner filter. It may be
inspected either at prescribed service intervals or at any time deemed necessary.
Replacement air filter
element ITW GSE part
numbers: EB11485
Primary – AF55020
Secondary – AF55320
Inspect regularly.
Replace when the “Air
Filter Clogged” warning
appears on the display
Restriction Senso
Latches
Latches
Hidden
a) Inspecting the Air Cleaner
1) Make periodic checks of air cleaner inlet screen for obstructions. If any obstructions are
present, remove them.
2) Check outlet connection for proper seal.
b) Changing the Air Filter
1) Release (4) Clips - (2) on each end of air filter housing.
2) Remove the end cover of housing.
3) Pull out air filter elements and replace.
4) Replace end cover on housing, making certain that the filter is centered in the housing.
5) Snap (4) clips back into place.
c) Disposal
Normal trash pick-up should be acceptable. NEVER burn the air filter for disposal.
Figure 2-2-4: Air Cleaner Assembly
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 72 of 104
4) Engine Fuel
a) How to select Fuel—Quality
The quality of fuel oil used in the diesel engine is a major factor in engine performance and life.
Fuel oil must be clean, completely distilled, stable and non-corrosive.
CAUTION
CAUTION
Ultra-Low Sulfur Diesel (ULSD) with a maximum content of 15 ppm or less must be used for Tier
4 Final engines. This is a regulatory requirement; failure to do so will result in damage to the
engine and after-treatment system within a short period of time.
For more information regarding the selection of fuel to use, refer to publication “Engine
Requirements—Lubricating Oil, Fuel, and Filters” available from authorized engine maker’s
service
outlets.
Due to the precise tolerances of diesel injection systems, it is extremely important that
the fuel be kept clean and free of dirt or water. Dirt or water in the system can cause
severe damage to both the injection pump and the injection nozzles.
The use of low lubricity fuels can shorten life and/or damage the engine’s fuel pump.
The engine manufacturer recommends only diesel fuel.
b) Cold Weather Operation
In cold weather, diesel fuel will form wax crystals, which can restrict flow and clog filters. Fuel oil
suppliers approach this problem several ways. Some provide a specially refined product, while
others may use flow-improving additives or winter blends. Winter blended fuel will likely contain
kerosene or 1-D fuel, which provide good cloud point temperatures, but result in a lighter fuel with
a lower heat content. These fuels may be used, but they may result in reduced engine power
and/or increased fuel consumption.
In most cases, adequate resistance to cold can be obtained by adding an additive. For further
assistance contact the nearest engine manufacturer’s service representative.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 73 of 104
5) Engine Fuel System
The fuel system consists of five primary components: fuel tank, lubricity filter, primary fuel filter, fuel lift
pump, and the fuel return line. The following are maintenance procedures for each of these items.
a) Fuel Tank
Be sure that no foreign objects are permitted in the fuel tank. The fuel tank must be removed and
flushed out if objects are found in the Fuel Water Separator or Lubricity Additive Filter.
b) Fuel Water Separator or Lubricity Additive Filter
A lubricity fuel filter, which is also a fuel/water separator, is mounted in the generator
compartment above the fuel tank outlet. The filter’s function is to add a lubricant to the fuel to
help prolong the engine seals and fuel pump life when fuels other than diesel are used (i.e., jet
fuel). The filter also removes foreign material and removes both free and emulsified water from
the fuel before it enters the fuel lift pump. Daily draining of the filter is required.
Replacement Filter Element:
Fleetguard: FS90168
Drain the water daily.
Change the filter after every 500
hours of operation.
Water Drain
Figure 2-2-5: Lubricity Filter
1) To drain the water:
a) Open drain valve.
b) Drain accumulated water and contaminants.
c) Close drain valve.
The lubricity filter must be changed every 500 hours of operation for the fuel filter to continue
adding the proper amounts of the lubricity additive into the fuel system.
Operation Manual – ITW GSE 6400 Tier 4
r
OM2248 Rev B
Page 74 of 104
2) To change the lubricity filter:
CAUTION
c) Primary Fuel Filter
When installing new element, do not over tighten it; mechanical tools may distort or
crack filter head.
a) Place a pan underneath the fuel filter to catch spilled fuel.
b) Shut off fuel valve.
c) Drain off some fuel by opening the drain valve.
d) Undo fuel filter with commercial tool and spin off.
e) Clean any dirt from the filter carrier rim
f) Apply a light film of oil or diesel on the rubber seal on the new filter.
g) Fill new filter with diesel fuel.
h) Screw in the new fuel filter “snug”.
i) Check that the cartridge is seated correctly against the gasket and tighten with a final
half turn.
j) Make sure that all rags, or absorbent sheets, are clear of moving engine parts and
cannot be drawn in to the radiator fan.
k) Open fuel valve.
l) Start the engine and check for leaks. Correct as necessary with the engine off.
A primary fuel filter is mounted above the engine starter in the engine compartment. The filter’s
function is to remove foreign material from the fuel before it enters the fuel lift pump.
Replacement fuel filter
part number:
Fleetguard: FF90567
Change the fuel filter after
every 500 hours of
operation.
Figure 2-2-6: Primary Fuel Filte
jury
OM2248 Rev B
Page 75 of 104
Operation Manual – ITW GSE 6400 Tier 4
1) To change the fuel filter:
a) Shut off fuel valve.
b) Place a pan underneath the fuel filter to catch spilled fuel.
c) Undo fuel filter with commercial tool and spin off.
d) Catch any fuel.
e) Clean any dirt from the filter carrier rim
f) Apply a light film of oil or diesel on the rubber seal on the new filter.
CAUTION
CAUTION
When installing new element, do not over tighten it; mechanical tools may distort or
crack filter head.
Make sure that all rags, or absorbent sheets, are clear of moving engine parts and
cannot be drawn in to the radiator fan.
g) Fill new filter with diesel fuel. Screw in the new fuel filter “snug”. Check that the
cartridge is seated correctly against the gasket and tighten with a final half turn.
h) Open fuel valve.
d) Fuel Pump
The fuel pump supplies high pressure to the fuel system so the diesel fuel can circulate freely.
This engine is equipped with a common rail fuel system that is under very high pressure. DO NOT
attempt to crack fuel lines.
WARNING
e) Fuel Return
The fuel return is a fuel line (tube) that takes unused fuel from the engine, and delivers it to the
fuel tank. No maintenance is required.
f) Fuel Level Indicators
There are two fuel level indicators in the unit; a mechanical dial indicator on the back of the unit
that is only accurate when the fuel tank is above 50% full and is for the use of the refueler, and an
electronic sensor in the fuel tank that is used to display the actual fuel level on the operator’s
screen.
DO NOT attempt to crack fuel lines. This engine is equipped with a common rail fuel
system that is under very high pressure. Failure to follow this guideline could result in
or death.
in
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 76 of 104
g) Draining the Fuel Tank
1) The fuel tank should be drained and cleaned out annually, when the various fuel filters
start to become excessively fouled and before storing the unit for long periods of time.
2) Before draining the fuel tank, we recommend pumping at least 90% of the fuel out of the
tank (use the operator display to determine the amount of fuel remaining). The fuel tank
has two 1/8” NPT fittings with thread sealant on them that are accessible under the trailer,
once it is lifted up. (Use a 7/16” wrench or socket to remove the fitting.)
3) Once the tank is fully drained, verify that there is no debris in the bottom of the tank on
either side. If any dirt, material or build up exists inside the tank, flush with diesel fluid to
remove the foreign material.
4) Use the following procedure to re-install the fittings:
a) The proper method of assembling tapered threaded connectors is to assemble them
finger tight, then wrench tighten to the specified number of turns from finger tight. The
following assembly procedure is recommended to minimize the risk of leakage and/or
damage to components.
i. Inspect components to ensure that male and female port threads and sealing
surfaces are free of burrs, nicks and scratches, or any foreign material.
ii. Apply sealant/lubricant to male pipe threads if not pre-applied.
b) With any sealant, the first one to two threads should be left uncovered to avoid
system contamination. If PTFE tape is used it should be wrapped 1-1/2 to 2 turns in
clockwise direction when viewed from the pipe thread end. (Caution: More than two
turns of tape may cause distortion or cracking of the port.)
c) Screw the connector into the port to the finger tight position.
d) Wrench tighten the connector to 1.5 - 3 turns past finger tight. Never back off (loosen)
pipe threaded connectors to achieve alignment.
e) If leakage persists after following the above steps, check for damaged threads and
total number of threads engaged.
f) If threads on the fitting are badly nicked or galled, replace the fitting. If port threads
are damaged, re-tap, if possible, or replace the component. If the port is cracked,
replace the component.
g) Normally, the total number of tapered threads engaged should be between 3-1/2 and
6. Any number outside of this range may indicate either under or over tightening of
the joint or out of tolerance threads. If the joint is under tightened, tighten it further but
no more than one full turn. If it is over tightened, check both threads, and replace the
part which has out-of-tolerance threads.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 77 of 104
6) Engine Cooling System
a) General
Cooling system service requires more than maintaining the proper coolant level in the radiato r
and protecting the system against freezing. Water should be clean and free of any corrosive
chemicals such as chloride, sulfate, and acids. It should be kept slightly alkaline with a pH value
in the range of 8.0 to 9.5. Any water, which is suitable for drinking, can be used in the engine
when properly treated as described in engine maker’s operation manual. The engine maker’s
representative should be consulted regarding the selection of satisfactory brand, perm anent-type
antifreeze for use in the cooling system.
b) Radiator Cap
1) General
A pressure relief valve is built into the radiator cap. It is designed to open at a pressure of
approximately 15 psi (103.4 Kpa).
WARNING
2) Removal
When removing cap from a very hot radiator, DO NOT turn cap past safety stop until
the pressure or steam has escaped.
To remove, turn the cap to the left (counterclockwise) to the safety stop. When all pressure is
released, press down on the cap and continue to turn until the cap is free to be removed.
CAUTION
CAUTION
3) Installation
When installing the cap, be sure it is turned clockwise as far as it will go so that the pressure
retaining valve will be functional.
c) Coolant
The preparation and maintenance of the coolant solution is important to engine life and is
completely covered in the engine manufacturer’s operation manual. For information reg arding
coolant specifications, testing equipment, antifreeze, etc., refer to engine maker’s operation
manual that accompanies the equipment’s manual or consult the local engine make r’s
representative.
Allow engine to cool before adding coolant.
Do not attempt to repair the valve in a radiator cap in case of failure. Replace with a
new cap.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 78 of 104
CAUTION
1) General.
A permanent type antifreeze is recommended for use in the cooling system.
CAUTION
2) Selecting antifreeze.
a) Select a permanent type antifreeze known to be satisfactory for use with chromate
b) When it is not known if the antifreeze is satisfactory for use with chromate resistor, check
(3) Checking antifreeze solution.
Check the solution with a reliable tester when in doubt about antifreeze protection.
d) Draining the Cooling System
To completely empty the cooling system requires draining the radiator assembly. Follow these
steps to drain the cooling system:
Never use soluble oil in the cooling system.
1. DO NOT use methanol or alcohol as antifreeze.
2. DO NOT mix brands or type of antifreeze. A solution containing two or more types
of antifreeze is impossible to test accurately.
corrosion resistor.
with local engine manufacturer’s representative for a list of compatible antifreezes.
1) Remove radiator cap.
2) Place a drain pan with at least a 40 quarts (28.4 liters) capacity under radiator to catch
coolant.
3) Remove the front grill to access the hose & valve. Place the drain hose into the drain pan.
4) Open the radiator drain valve.
5) Allow the system to drain completely.
NOTE: Be sure the drain valve doesn’t clog during draining.
6) When the system is completely drained, close the drain valve and coil the
hose back up.
7) Replace the front canopy cover.
e) Flushing the Cooling System
Flushing the cooling system should be a yearly maintenance procedure. By flushing the system,
clean water is forced through the engine block to remove expired coolant and other contaminants.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 79 of 104
f) Cleaning the Radiator Core
Blow out accumulated dirt from the radiator core air passages, using water. Bent or clogged
radiator fins often cause engine overheating. When straightening bent fins, be careful not to
damage the tubes or to break the bond between fins and tubes.
NOTE: Direct the water in a reverse direction to normal air flow. Normal flow on this installation
is from the engine compartment out ward.
g) Filling the Cooling System
The preparation and monitoring of coolant in liquid-cooled engines is especially important
because corrosion, cavitation, and freezing can lead to engine damage. For coolant system
protection details see the engine manufacturer’s operations manual.
1) Install coolant
a) Remove radiator cap. Be sure the radiator drain valve is closed (Front panel must be
removed to access this location).
b) Pour coolant into radiator very slowly until it reaches the bottom of fill neck. Allow time for
trapped air to escape from the system then continue filling until the coolant level remains
at the bottom of the fill neck.
c) Start the engine and bring up to rated speed and allow the thermostat to open. Add
coolant as trapped air escapes from the system and the coolant level falls.
d) Continue to check coolant level until all trapped air escapes. Add coolant if needed to fill
2) Inspection/Check
a) Check system for evidence of leaks.
b) Inspect all hoses. Install new hoses as necessary. Tighten hose clamps as required.
c) Check the condition of fan and water pump belts. Replace belts if necessary.
NOTE: It is good practice to attach a card, indicating the cooling system contents and date
serviced, to the radiator filler neck.
h) Thermostat
The thermostat should be checked each fall, or as required. Refer to engine manufacturer’s
operations manual for recommended instructions.
to the bottom of fill neck. Install radiator cap.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 80 of 104
7) Engine Drive Belt
a) General
The engine cooling fan, alternator, and water pumps are driven by one serpentine belt, which
must be replaced if worn or damaged.
b) Preparation for Belt Check and Adjustment
All driven assemblies must be securely mounted in operating position before checking belt
tension.
c) Checking Belt Tension
WARNING
Check belt tension every 1000 hours, or once year, whichever comes first. A belt that is too tight
is destructive to bearings of the driven part. A loose belt will slip and cause inefficient operation of
the part being driven as well as wear to the belt.
CAUTION
Belt tension may be checked by manually depressing the belt with an index finger to determine
the amount of belt deflection obtained. When a force is applied at a point halfway between
pulleys on the longest span of a belt, there should be no more than 1/2 inch of deflection attained.
Refer to the engine manufacturer’s operation manual for checking belt tension and changing worn
belts.
DO NOT Check belt tension with engine running
Inspect and replace the belt if it has unacceptable cracks, is frayed, or has pieces of
material missing.
8) Generator Maintenance
The 400 Hz generator requires no maintenance or service other than periodic cleaning. The unit
is brushless and has bearings that are permanently lubricated and sealed.
a) Cleaning
The generator may be cleaned by careful use of compressed air and/or a good, SAFE
commercial cleaner. Steam cleaning of the generator is not recommended because the use of
steam and harsh chemical compounds may result in damage to insulation and other gene rator
components.
WARNING
b) Adjustment
The generator itself requires no adjustment. Adjustment procedures for generator controls are
covered in Section 2-3.
Never use solvents as this is a fire hazard
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 81 of 104
9) Replacing the Control Board Battery
Before removing the Control Board and to avoid any static discharge to the Control Board during
the replacement of the battery, please take ESD (Electro Static Discharge) precautions.
*Important Note!
Before you remove the battery from the holder, make sure that the replacement battery is within reach, as
the Control Board must not be without battery power for more than 30 seconds.
Otherwise, all software and the setup data will be erased. *
Fig. 8.2.3 Control Board (front view)
Blue LED (D5)
To replace the battery, Switch OFF the unit by means of Q1. Remove the Control Board from its 4 posts
marked with a in Figure 8.2.3. Place the PCB on an insulated surface, with the back side face up.
Fig. 8.2.4 Control Board (rearview)
Battery holder and
battery
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 82 of 104
Remove the battery from the holder using a small insulated screwdriver to push out the battery,
direction indicated by the two red arrows on Figure 8.2.4 and insert the new battery in the direction of the
singe green arrow on Figure 8.2.4.
Mount the control board on the interface board again by gently pressing the PCB to its rest on the
Interface Board. Make sure that all 4 corners are fully pressed towards the Interface Board.
Switch on the unit via the input switch Q1 and close the door. The unit now passes through the
initialization test and goes into standby mode.
Enter the setup menu and select menu item “Battery Replaced” to confirm new battery installation.
Important Note!
*
If the blue LED on the Control Board (location can be found on the Fig. 8.2.3) flashes with
approximate 2 flashes per second and the display reports “Communication Error”, the firmware
on the Control Board has been erased. The Control Board must be sent to ITW GSE to be
reloaded.
To ensure high reliability of the back-up battery, the only type of battery that can be used
on the Control Board is the Panasonic BR-2032
OM2248 Rev B
Page 83 of 104
Operation Manual – ITW GSE 6400 Tier 4
Section 3 Troubleshooting Procedures
1) General
The Troubleshooting Chart located in this section covers the common faults and malfunctio ns that can
be found during operation or maintenance of this equipment. The chart may not list all faults and
malfunctions that can occur. If a fault or malfunction is not listed in the chart, start looking for the
cause at the source of power in the affected circuit. Refer to the schematic and connection diagram.
Test the circuit systematically until the source of the malfunction is i solated.
The Troubleshooting Chart is arranged by Error code, Error text, Description and then four columns of
possible corrective actions. Always try the 1
corrective action.
WARNING
CAUTION
Exercise extreme care to avoid contact with high voltage leads and components.
HIGH VOLTAGE CAN KILL!
Maintenance personnel must be very careful when performing terminal-to-terminal
checks to be certain the proper terminals are being used, especially when using
jumper leads. Damage to electrical components may result from the application of
improper voltage and current.
2) Equipment for Troubleshooting
A good quality multimeter is the only instrument required for troubleshooting. At least two jumper
leads with alligator, or similar clips, will be required. The engine electrical system can be used as a
12 VDC power source.
3) Parts Replacement
To lessen down time and get a faulty machine back on line as quickly as possible, the black box
concept of parts replacement is reflected in the Troubleshooting Chart. For example, if a component
on a control box board is defective, the quickest way to remedy the situation is to replace the
complete board and send the old to stock.
4) Normal Operational Parameters
The system specifications, which are listed in Chapter 1-1, provide useful information when
troubleshooting abnormal operation. The Protective System Specifications and Normal Operating
Characteristics provide information about how the generator set should be operated.
st
corrective action before proceeding to the next
OM2248 Rev B
Page 84 of 104
Operation Manual – ITW GSE 6400 Tier 4
5) Check Connections and Leads
ALWAYS check connections and leads to a component suspected of being faulty. Generally, it is
assumed that connections and wiring have been checked first and that power ha s not been lost as a
result of defective wiring or connections.
6) Engine Troubleshooting
Remember that the ability of the engine to start and run properly depends upon the following:
An adequate supply of 12 VDC power reaching a good starter and control board
An adequate supply of air, compressed to a sufficiently high pressure
The injection of the correct amount of clean fuel at the proper time
7) GPU Control Monitoring
The GPU control system performs complete diagnostic testing and continuous monitoring of all critical
circuits and operating electrical values. If the control system senses a problem with one of the circuits
or if any of the electrical values exceeds its safe operating limit, the control system will shut the GPU
down, or may allow the GPU to continue operation depending on the severity of the condition.
a) Operating Modes
1) Self-Test Mode
When power is first applied to the control circuit, the GPU performs complete self-diagnostics
of the internal circuitry. If a fault is detected during the self-test, the Alert/Failure LED will be lit
and the first (if there are more than one) failure will be displayed on the LED display.
2) Engine Run Mode
When the ENGINE pushbutton is pressed, the blue power indicator LED and the Operating
Beacon will start flashing. The starter will engage when the engine is ready. After the engine
reaches its idle speed (1000 rpm) the GPU is ready to supply power to the aircraft. (Note that the
engine will make three 15 second attempts to start the engine. If the engine doesn’t successfully
start after the third attempt, the fault LED will be lit and an Engine Start Failure message will be
displayed.)
3) Engine Shutdown Mode
Pressing the ENGINE pushbutton starts the 30 seconds delayed shutdown period. If any
output contactors are closed, they will open before starting countdown. The shutdown period is
required to cool the engine’s turbocharger.
4) Automatic Engine Shutdown
Automatic Shutdown mode will turn off the engine after 10 minutes when all contactors are
open or if they are closed and the total generator current is less than 5 amps. (This timer is
internal and not visible.) After 10 minutes, it puts the engine in shutdown mode. (All
contactors are opened and the generator is no longer regulating voltage.) A visible 30 second
timer is displayed and the engine will turn off when the timer expires. The Automatic Engine
Shutdown mode is changed in the Setup menu and the choices are enabled or disabled.
5) Engine Stop Mode
After the 30 seconds delayed shutdown period, the engine stops running.
6) System Off Mode
The power is removed from the GPU’s entire control system when the battery disconnect is
opened.
OM2248 Rev B
Page 85 of 104
b) Faults
Operation Manual – ITW GSE 6400 Tier 4
Faults result when any of the fault limits are exceeded, an internal problem, or under certain
conditions where an injury to personnel or damage to an aircraft or the GPU could occur. Faults
are also stored in the Black Box memory as event records. The fault limits and conditions are
preset at the factory.
1) Warning
Warning faults have no effect on the operation of the GPU. An example is an intake air
restriction fault due to a dirty filter. Although the GPU continues to operate, the fault LED is lit
and the fault text appears on the display. Pressing the Engine pushbutton or shutting down
the GPU resets the fault.
2) Run Mode
Run mode faults remove power form the aircraft but do not change the operating speed of the
engine. An example is an over voltage fault. Although the contactors open and remove
power from the aircraft, the engine remains at rated speed, the fault LED is lit and the fault
text appears on the display. Pressing the Engine pushbutton or shutting down the GPU
resets the fault.
3) Stop Mode
Stop mode faults remove power form the aircraft and shut the engine down. An example is a
low oil pressure fault. The contactors open and remove power from the aircraft, the engine
shuts down, the Alert/Failure LED is lit and the fault text appears display. Pressing the
Engine pushbutton or shutting down the GPU resets the fault.
8) Cummins Engine Fault Codes & Trouble Shooting
The best source of information to aid in trouble shooting Cummins engine issues is at the
quickserve.cummins.com website. Go to this website and register up to five engine serial numb ers fo r
free. (It is recommended that if you have more than one engine type/size, that you register one serial
number per type/size.) Once you are registered, this website gives you access to engine information,
troubleshooting assistance by fault code, parts information and service bulletin information for each
serial number/engine type that you have registered with the site.
9) Error Codes
If the displayed text does not provide sufficient information to solve the problem, the tables on the
next pages suggest corrective actions to be carried out for each error code.
Additional error information regarding the output voltage and overload, can be derived from the
error code according to the following directions:
xx02 = Phase B xx06 = Phase B & C xx03 = Phase A & B xx07 = Phase A, B & C
xx04 = Phase C
Examples: Error Code 3501 refers to “Output Voltage Too Low” at phase A.
Error Code 4407 refers to “Overload I > 300% - 1 sec.” at all 3 output phases.
OM2248 Rev B
Page 86 of 104
Operation Manual – ITW GSE 6400 Tier 4
10.0 Troubleshooting Chart
Error
Code
For faults in this section: Disconnect from Aircraft (if connected). Do not stop engine (if running). Do not let engine start (if not running).
100
201
202
250
300 FUEL LEVEL < 10%
500 STARTER FAILURE
Error Text in display Description
LOGGING
UNSUCCESSFUL
CONTROL BOARD
FAILURE
WRONG SOFTWARE
VERSION
FAILED SOFTWARE
UPDATE
Communication
Failure
ID chip is
missing or
unreadable
Wrong Software
Version Installed
The new software
didn’t load
properly
Fuel Level is too
low to attempt an
engine start.
Engine rotation is
not detected
when starter was
activated.
1st Corrective
Action
Press Engine
button to Reset
Inspect ID chip
connection. for
damage.
Install correct
software version
Try to install the
software again
Add Fuel
Press Engine
button to Reset
2nd Corrective
Action
Contact ITWGSE
Replace display
or control board
Inspect fuel
Sender wiring
Check starter
circuit to ensure
that it is properly
energized.
(Replace Starter
Solenoid)
3rd Corrective
Action
Inspect fuel Sender
Replace Starter
4th Corrective
Action
600
700
2400
3200
3300
3400
3800
4000
UNABLE TO START
ENGINE
BATTERY LEVEL
TOO LOW
28V PLUG
TEMPERATURE TOO
HIGH
28V OUTPUT
VOLTAGE TOO HIGH
OUTPUT VOLTAGE
TOO HIGH
28V OUTPUT
VOLTAGE TOO LOW
28V INTERLOCK
LEVEL TOO LOW
28V OUTPUT
CURRENT TOO HIGH
Engine did not
start after 3 tries.
Battery voltage
level is too low to
attempt startup
sequence.
The temperature
sensor in output
2 plug has
tripped.
Voltage > 32V 4s
Voltage > 40V 1s
Voltage < 20V 4s
28V F Level too
low
28V Output
Voltage is too
high
Press Engine
button to Reset
Press Engine
button to Reset
Press ARU
button to reset
Press ARU
button to reset
Press ARU
button to reset
Press ARU
button to reset
Press ARU
button to reset
Press ARU
button to reset
Check fuel valve
to ensure it is
open.
Check battery
cables
Remove load and
let plug cool
down
Check output
voltage setup
value
Check output
voltage setup
value
Check output
voltage setup
value
Verify that output
cable is correct
inserted
Remove overload
and re-engage
output
Service Engine
Charge Battery Replace Battery
Check connector /
output cabling for
any malfunction
Check ARU Module
and wiring
Check ARU Module
and wiring
Check ARU Module
and wiring
Check / correct
installation
Replace Control
Board A1
Replace Control
Boards A1 & A2
Replace Control
Board A1
Replace Interface
Board A2
Replace Interface
Board A2
OM2248 Rev B
Page 87 of 104
Operation Manual – ITW GSE 6400 Tier 4
4100
4200
4300
4700
4800
For faults in this section: Disconnect from aircraft. Shut down engine after cooldown.
6000
6100
6600
8000
8200
8400
28V OUTPUT
CURRENT TOO HIGH
28V OUTPUT
CURRENT TOO HIGH
28V OUTPUT
CURRENT TOO HIGH
BACKUP BATTERY
TIME
RTC TIME
CONTROL BOARD
FAILURE
AVR SOFTSTART
ERROR
ECM ERROR CODE
RECEIVED
CONTROL VOLTAGE
LOW
EMERGENCY STOP
ACTIVATED
ECM
COMMUNICATION
FAILURE
Output Current is
over 1200A for 60
seconds
Output Current is
over 1500A for 30
seconds
Output Current is
over 1500A for 30
seconds
Time to change
the control board
battery
Real Time Clock
Fault
Watchdog
Timeout
AVR Soft start
Error
Engine Error
Code Received
from ECM
Control Voltage <
20V (Running)
J1939
Communication
Failure
Press ARU
button to reset
Press ARU
button to reset
Press Engine
button to reset
Correct Date in
SETUP Menu
Press Engine
Button to reset
Press Engine
Button to reset
Service Engine
Press Engine
button to reset
Release
emergency stop
and press
Engine button to
reset
Check ECM
Power (Replace
Interface Board)
Remove overload
and re-engage
output
Remove overload
and re-engage
output
Remove overload
and re-engage
output
Replace Battery &
Reset Date
Replace Control
Board A1
Check Excitation
Wiring/Fuse
Check Alternator Check Battery
Check emergency
stop
Service Engine
Replace Control
Board A1
Replace Control
Board A1
Replace Control
Board A1
Replace Control
Board A1
Replace Control
Board A1
Check user EPO
(A2:X14)
Replace Interface
Board A2
Replace Interface
Board A2
Replace Interface
Board A2
Replace Interface
Board A2
Replace Control
Board A1
8500
ENGINE RPM OUT OF
SPEC
Engine RPM out
of specification
or stopped
Service Engine
g
g
y
OM2248 Rev B
Page 88 of 104
Operation Manual – ITW GSE 6400 Tier 4
Engine Controls
Trouble, Symptom,
Condition
1. The engine will not
start, and the
starter will not
crank the engine.
2. Engine will not
start. Starter clicks
on and off.
Probable Cause Test, Check, and/or Remedy
a. Emergency Stop
b. Battery Disconnect
switch is in the OFF
position.
c. Battery discharged or
loose battery or ground
connection.
d. Defective starter
solenoid (SW3).
e. No voltage at starter
solenoid coil.
f. Defective starter. Remove the starter motor from engine and apply
g. Internal seizure. If the starter is good, attempt to hand crank the engine
i. Defective Control PanelReplace the Control Panel.
a. Low batter
b. Loose starting circuit
connections or faulty
cables
output Check the battery and recharge or replace
Make sure the Emergency Stop switch is pulled out
and switch has been pressed.
Make sure the battery disconnect switch is in the ON
position.
Make sure the voltage across the batteries is
approximately 13 VDC.
Check battery terminals.
Make sure 13 volts DC is reaching the starter solenoid
input terminal.
Check if you can hear the starter solenoid activate
when the start button is pressed. If not, check for
voltage on the starter solenoid coil (see e. below).
Temporarily connect a large-capacity jumper cable
(No. 1/0 minimum) between the hot side of the starter
solenoid and the starter input terminal. If starter does
not crank en
Check connector X5 on the PC1 Interface board.
Verify that there is 12 VDC across the starter solenoid
+ and – terminals when the engine start pushbutton is
pressed.
Check and replace (if necessary) the Interface board.
12 VDC to test it. Replace the starter if non-operable.
using a 3/4-inch square drive on the crankshaft pulley. If
engine cannot be turned one complete revolution,
internal seizure is indicated. Remove engine and
contact the en
Check all connections and cables. Tighten or replace as
required.
ine, the starter may be defective
ine manufacturer and/or nearest dealer.
y
y
y
g
j
g
OM2248 Rev B
Page 89 of 104
Operation Manual – ITW GSE 6400 Tier 4
Engine Controls (continued)
Trouble,
Symptom,
Condition
3. Engine will not
start. Cranking
speed is low.
4. Engine cranks
but will not
start.
Caution: To
prevent damage
to the starting
motor, do not
engage the
starting motor for
more than 30
seconds. Wait
two (2) minutes
between each
attempt to start.
5. Engine cranks,
but will not
start. Overtemperature
indication
appears
immediately.
6. Engine is hard
to start.
Cranking speed
is normal and
the fuel supply
is adequate.
7. Engine starts
but then stops
after a few
seconds by
automatic
shutdown.
Probable Cause Test, Check, and/or Remedy
a. Low batter
b. Loose starting circuit
connections or fault
c. Improper lubricating oil
viscosit
a. Low fuelMake sure there is sufficient fuel in the fuel tank.
b. Fuel shutoff valve closedOpen the shutoff valve on the fuel tank.
c. Plugged or defective filterReplace fuel filters. Also, check the gaskets for
d. Loose connections,
damaged hoses or fuel
lines between tank and fuel
pump
a. Defective engine
temperature switch
b. Defective PC1 board Replace the PC1 Interface board.
a. Low compression, which
may be caused by sticking
or burned exhaust valves,
worn or broken
compression rings, leaking
cylinder head gasket, or
valve clearance ad
a. Low oil pressure or
defective oil pressure
switch.
b. Defective PC1 board.Replace PC1 Interface board.
output Check the battery and recharge or replace
Check all connections and cables. Tighten or replace
cables
ustment.
as required.
Check the oil. Refer to Section 2-2.
Remove and replace the oil as necessary.
If engine will not start, the fuel pump may be
defective.
If engine starts and then stops after a short time,
check fuel lines, and filters.
leakin
Tighten all fittings and connections. Replace any
damaged hoses or fuel links.
Check wiring to engine high temperature switch (S49
on schematic), which is located on top of the engine
block. If wiring is correct, remove wires and check
resistance between terminals C and N.O. A
resistance of less than 10 ohms indicates a defective
switch. Replace switch if defective.
Check the compression in accordance with
instructions in the engine manufacturer’s operation
manual. Overhaul the engine to make repairs as
necessary.
Restart the engine and observe oil pressure gauge. If
oil pressure is 12 psi or more, disconnect wire from
the normally-closed switch terminal on the oil pressure
switch. Restart engine. If engine continues to run,
the oil pressure switch is defective. Replace oil
pressure switch. If engine stops, the PC1 Interface
board mi
or damaged condition.
ht be defective.
g
g
g
OM2248 Rev B
Page 90 of 104
Operation Manual – ITW GSE 6400 Tier 4
Engine Controls (continued)
Trouble, Symptom,
Condition
8. Engine either goes
from rated speed to
idle speed, or shuts
down.
9. Engine has slow
response time
when a load is
applied.
10. Engine misses or
runs unevenly.
11. Engine lacks
power
12. Front clearance
lights aren’t ON.
Probable Cause Test, Check, and/or Remedy
a. Low fuel was detected or the
PC1 board could be
defective.
a. Engine needs tune-up.Tune-up as required. Refer to engine
a. Insufficient fuel.Check fuel system in accordance with engine
b. Faulty injector.Check injectors in accordance with engine
c. Low compression pressure.Check compression in accordance with engine
d. Air in fuel system.Check all fittings to be sure they are tight and
a. Improper engine adjustments
ear train timing.
and
b. Insufficient fuel.Check low fuel level in accordance with engine
c. Insufficient inlet air due to
dama
d. Restricted exhaust system.Check exhaust pipes for restrictions. Check
a. Loose connection
b. Defective Interface board. Replace Interface board.
build up voltage
when the engine is
at the rated speed.
Probable Cause Test, Check, and/or Remedy
Problem with brushesRemove, clean, and reinstall the generator brushes, replacing them
if they are shorter than 7/16 of an inch (11mm).
Exciter fuse (F3 or F8)
blown
Defective wiring between
interface board and
generator
Defective diode on control
winding.
Defective voltage regulator
on interface board
Defective generator
control winding
Defective generator
armature G402
Problem with brushesRemove, clean, and reinstall the generator brushes, replacing them
Replace exciter fuse(s).
Check all connectors and wires between interface board and
generator. Pull gently on wires to insure proper insertion in the
connector.
The diode is located on the generator’s brush holder mounting
bracket. Check it with an ohmmeter to see if good.
Replace interface board.
Measure resistance between two yellow wires coming from
generator. It should be around 13 ohms. It is defective if shorted
or open.
If no problem was found with the control winding, the generator
stator is defective. Send unit to overhaul.
if they are shorter than 7/16 of an inch (11mm).
Exciter fuse (F3 or F8)
blown
Defective wiring between
interface board and
generator
Replace exciter fuse(s).
Check all connectors and wires between the interface board and the
generator. Pull gently on wires to insure proper insertion in the
connector.
g
g
g
g g
OM2248 Rev B
Page 92 of 104
Operation Manual – ITW GSE 6400 Tier 4
Load Contactor Operating Circuits
Output 1: Contactor K1
Output 2: Contactor K2
Trouble, Symptom, Condition Probable Cause Test, Check, and/or Remedy
1. Load contactor will not close
when the corresponding
Output pushbutton is pressed.
Generator is running at normal
voltage.
2. Load contactor closes when
the Output pushbutton is
pressed, but opens within 10
seconds.
a. Blown contactor fuse (F3) on
ulator board.
re
b. Defective display module Check to make sure that the other
a. The plug interlock EF circuit on
Interface board could be
defective.
b. 28.5 VDC is not reaching the plug
interlock EF circuit from aircraft
for followin
c. Generator-to-aircraft cable
connector defective or not
plugged into aircraft receptacle
connector
reasons:
Check the fuse and replace if blown.
If it blows again, check the contactor.
pushbuttons on the control panel
work. Replace the display board and
test all buttons a
Set 400 Hz Interlock to Bypassed. If
load contactor remains closed,
proceed to step b.
Proceed as follows to find the cause
of this malfunction.
Inspect cable connector plug
thoroughly for damaged E and F
terminals. Be sure plug is fully
mated with aircraft receptacle
connector and makin
ain.
ood contact.
d. Aircraft rejecting power.Check aircraft on-board electrical
e. Defective contacts in switch
mounted on side of contactor.
equipment and controls.
Connect a jumper lead between
terminals of the normally-open
auxiliary switch. If the contactor now
remains closed, replace the auxiliary
switch or the entire contactor.
g
OM2248 Rev B
Page 93 of 104
Operation Manual – ITW GSE 6400 Tier 4
Protective Circuit
NOTE: Protective monitoring is not completely functional until the load contactor is CLOSED. Since it is not
advisable to vary voltages for test purposes while delivering power to an aircraft, the GPU should be
connected to a load bank for trouble shootin
protective circuits.
Trouble, Symptom,
Condition
1. Load contactor
opens during power
delivery. Over
voltage fault
indicated.
2. Load contactor
opens during power
delivery. Under
voltage fault
indicated.
Probable Cause Test, Check, and/or Remedy
a. Over-voltage condition
may have been the result
of a sudden drop in load
and may have been a
normal action.
b. Defective Interface or
control board.
a. Under-voltage condition
may have been result of
a sudden shock load, or
possible tampering with
REG potentiometer, and
may have been a normal
action.
b. Defective Interface or
Control board.
Press appropriate Output pushbutton and resume
power delivery. Observe voltmeter to be certain
voltage is normal (28.5 VDC). Adjust to normal if
necessary. If load contactor is opened again and
the fault message indicates an over-voltage
condition, proceed to step b.
Replace the control and/or the interface board.
Press appropriate Output pushbutton and resume
power delivery. Observe voltmeter to be certain
voltage is normal (28.5 VDC). Adjust to normal if
necessary. If load contactor is opened again and
the fault message indicates an under-voltage
condition, proceed to step b.
Replace the control and/or the interface board.
Operation Manual – ITW GSE 6400 Tier 4
g
)
(
)
g
OM2248 Rev B
Page 94 of 104
Chapter 3 Manufacturer’s Literature
Vendor Literature
Type Diagram Description
ine Operation and Maintenance Manual (Cummins Bulletin # 4358560
En
Service Manual
- Not Included -- purchased separately from Cummins.
Diagram Number Diagram Description
293194 Dia
Contact ITW GSE if copies of these drawings or manuals are not delivered with the unit (unless otherwise
noted above). Refer to Appendix A for specific information on the ITW GSE 6400, 28.5 VDC. Generator
Set, optional equipment.
ram, Schematic & Connection
Cummins Bulletin # 4358561
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 95 of 104
This page is intentionally left blank.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 96 of 104
Appendix A Options
The following is a list of options available for the ITW GSE 6400 Generator Set.
This option replaces the standard Towbar with a 40mm diameter eye version.
293098 Kit, Clearance Lights
This option adds clearance lights to the four top corners of the canopy.
293099-001 Kit, Beacon, Unit Operating, Amber
293099-002 Kit, Beacon, Unit Operating, Blue
293099-003 Kit, Beacon, Unit Operating, Clear
293099-004 Kit, Beacon, Unit Operating, Red
This option adds the selected color beacon light to the top of the front canopy. These beacons are
delivered with a flashing light. If a steady light is desired, the jumper in the bottom of the light should be
cut.
This option adds the selected color beacon light to the top of the front canopy. These beacons are
delivered with a flashing light. If a steady light is desired, the jumper in the bottom of the light should be
cut.
293498-01 Kit, Battery Blanket, 120V
This option adds an independently powered 120 VAC powered battery blanket on top of the batteries in
the right cable tray.
293498-03 Kit, Battery Blanket, 240V
This option adds an independently powered 240 VAC powered battery blanket on top of the batteries in
the right cable tray.
293503-XX Kit, Block Heater, 120V
This option adds an independently powered 120 VAC powered block heater to the engine.
293503-XX Kit, Block Heater, 240V
This option adds an independently powered 240 VAC powered block heater to the engine.
293337-02 Kit, 28VDC Only Tow Hitch Interlock
This option adds a lock to the tow bar assembly to prevent it from being lowered if the 28VDC cable isn’t
properly inserted into the receptacle at the front of the cable tray. NOTE: When this option is installed, the
unit will not supply 28VDC power if the tow bar hitch is not up and locked in place.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 98 of 104
Appendix B Operating in Unusual Service Conditions
This information is a general guideline and cannot cover all possible conditions of equipment use. The
specific local environments may be dependent upon conditions beyond the manufacturer’s control. The
manufacturer should be consulted if any unusual conditions of use exist which may affect the physical
condition or operation of the equipment or safety to surrounding personnel.
Among such conditions are:
1) Exposure to:
a) Combustible, explosive, abrasive or conducting dusts.
b) Environments where the accumulation of lint or excessive dirt will interfere with normal ventilation.
c) Chemical fumes, flammable, or explosive gases.
d) Nuclear radiation.
e) Steam, salt-laden air, or oil vapor.
f) Damp or very dry locations, radiant heat, vermin infestation, or atmospheres conducive to fungus growth.
g) Abnormal shock, vibration or mechanical loading from external sources during equipment operation.
h) Abnormal axial or side thrust imposed on rotating equipment shafts.
i) Low and/or high ambient temperatures.
j) High electromagnetic fields
2) Operation at:
a) Voltages above or below rated voltage.
b) Speeds other than rated speed.
c) Frequency other than rated frequency.
d) Standstill with rotating equipment windings energized.
e) Unbalanced voltages.
f) Operation at loads greater than rated.
3) Operation where low acoustical noise levels are required.
4) Operation with:
a) Improper fuel, lubricants or coolant.
b) Parts or elements unauthorized by the manufacturer.
c) Unauthorized modifications.
5) Operation in poorly ventilated areas.
Operation Manual – ITW GSE 6400 Tier 4
OM2248 Rev B
Page 99 of 104
Appendix C Initial Software Installation Procedure
RR
Introduction:
The ITW GSE 6400 GPU contains two circuit boards that may need to be programmed if they are
replaced. (The Control Board (P/N AP-579526) and the Display Board (P/N AP-579536).
This document instructs you how to perform this task. Make sure to program the boards with the correct
software number and revision. Install the Control Board software first, then the Display Board software.
First time programming of the Control Board (P/N AP-579526):
1) Make sure the Control Board is installed onto the Interface Board (P/N AP-279534), and the GPU
is powered.
2) Copy the correct Control Board software onto a USB stick. The file must be located in the root
folder of the USB stick, and the filename must be XXXXX.itw. Other files, e.g. the Display Board
software, may also be on the USB stick.
3) Inspect the blue LED next to the USB socket on the Control Board. The blue LED must be
flashing in a sequence of two rapid flashes, then a pause, then two rapid flashes, and so on.
4) Insert the USB stick into the USB socket on the Control Board. Check that the blue LED turns off.
Wait until the blue LED turns on (this may take some time).
5) When the blue LED turns constantly on, the software has been programmed into the Control
Board. Remove the USB stick from the Control Board.
If the blue LED is constantly on, the Control Board has already been programmed. Use the update
function on the Display Board to program the Control Board. (The Display Board must be programmed
first)
If the blue LED is flashing slowly in a sequence of one flash, a pause, one flash and so on, the
microcontroller on the Control Board has lost its internal programming, most likely due to a faulty or
missing battery. Contact ITW GSE technical support and request a replacement control board.
First time programming of the Display Board (P/N AP-579536):
1) Make sure that switch 1 on DIP-switch SW2 is in the ON position. This allows access to the
Display Board menu.
2) Copy the correct Display Board software onto a USB stick. The Display Board software consists
of two files: a XXXXX.itw file, and a file like AAxxxxxx.pbe, where xxxxxx is a number.
3) Do not change the filenames. The two files will only work together.
4) The files are located in the root folder of the USB stick. Other files, e.g. the Control Board
software, may also be on the USB stick.
5) Insert the USB stick into the USB socket on the Display Board.
6) Press and hold the center navigation key on the GPU to access the update function.
7) Press the center navigation key again to confirm the software update.
8) Wait for the software update to complete. Press the center navigation key when instructed to
reset the Display Board.
9) If the software update does not complete, start over from step 4.
Verify the software is installed correctly.
1) Hold the center navigation key to access the menu on the Display Board.
2) Access the Parameter Info, and navigate up/down to the Unit Information page.
3) Verify that the display reports the expected software number and revision for both Display Board
(Display FW) and Control Board (Control FW).
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.