Common AccessoriesApp. A 1........................................................
Appendix B
Printed Circuit Boards and Wiring InformationApp. B 1...................................
Appendix C
Programming LogApp. C 1...........................................................
C. 1998
Manual #50-14 Revised 1/03
1-1
Safety Instructions
Authorized Use of System
Only authorized persons who have read and understood the instruction manual or who
have been trained by ITW Dynatec may install, operate or dispose off this system.
Appropriate electrical safety procedures must be observed.
A copy of this manual should be kept with the installed system as reference material.
Proper Use of the System
This controller is designed for use only with ITW Dynatec hot melt or cold glue systems.
Other applications should be attempted only after consulting with ITW Dynatec.
Manual Symbols
Caution
This symbol means that failure to observe the specific instructions could
cause damage to the equipment.
Danger! High Voltage!
This symbol means there is a danger of electrical hazard.
Note!Provides useful information regarding the use of the system.
1-2
C. 1998
Safety Instructions
Manual #50-14 Revised 1/03
Modifications to the System
No modification can be made to the system without consulting ITW Dynatec. Use only
factory--recommended parts and fittings. ITW Dynatec does not assume any resonsibility
for damage which occurs as a result of using parts that are not factory recommended.
Working with the Cover Open
Never operate this controller with open cover. There are no servicable components inside.
All settings are done via Software.
Inside the controller are electric current--carrying components. To avoid personal injury, do
not touch them while input power is ON. Disconnect and lockout main power before opening
the cover. Then wait a few seconds until all electrical components have discharged.
C. 2002
Manual #50-14 Revised 1/03
2-1
Product Description
General
The DY 2008 Pattern Controller is one component of an adhesive application system
consisting of a hot-melt unit, cold glue pressure vessel or cold glue pump, adhesive hoses
and applicator heads. The controller can be used for hot--melt or cold glue application.
The pattern controller activates solenoids for four (Basic Version) up to 128 (Option)
applicator heads in order to create individual adhesive patterns. It is possible to program
up to 16 independent glue events (16 glue + 16 delay) per channel.
Each channel can operate in one of the possible modes: glue beads, dots, continuous
gluing, random product length and stitching.
Gluing can be triggered with a photo eye, proximity switch or by exceeding a certain
machine speed.
Every channel may be assigned to its own trigger input, if desired, to increase the accuracy
of multiple parallel running products.
In order to accelerate the timing of solenoids it is possible to apply initially a higher voltage
(Over--excitation). The voltage level and the duration time of this over--excitation is
programmable via software on a channel-by-channel basis. This enables applications for
hot--melt and cold glue.
The speed of the production machine will be registered with up to four encoders and
indicated on the display. It can be used to control the speed of one or more gear pumps of
adhesive supply units or to control the glue pressure on a cold glue system via I/P or U/P
transducers. Every time the machine speed varies the glue pressure will follow.
Working with four encoders enables application on machines with different speeds e.g.
Right--Angle machine.
The pressure vs. speed ramp can be linear or for better adaptation to production conditions
a 12--point curve is programmable.
A machine contact is available to enable or disable the controller. With this contact it is
possible to start and stop the gluing together with the parent machine.
The user can select whether the gluing stops immediately or continues.
The controller can provide an output signal to close a shutter devise (automatic tip sealer)
in order to prevent clogging of cold glue applicators from drying during production breaks.
If necessary this shutter output can be activated with a dedicated trigger input.
Alternatively the programming of the glue pattern can be done on a computer and
corresponding software. An optional RS232/485 or Profibus interface can be used to
communicate with the pattern controller from an external device.
Critical conditions can be signalled by means of two alarm outputs.
2-2
C. 2002
Product Description
Manual 50-14 Revised 11/15
Technical Data
General
Operating Temperature
Storage Temperature
Power Supply1/N/PE 230 V50--60 Hz
Power Consumption180w (8 channel version)
Operating LanguagesGerman, English, Finnish, French, Italian
Number of Programs60 stored in permanent memory
Protection ClassIP 40
CE Approval Grantedyes
Trigger
Input connectors24 V DC, max. 100 mA, NPN, PNP, Push--Pull
Max. Number4 Master Triggers (Triggers #1 thru 4)
Assignment (every channel can be assigned to a Master
Trigger or its Channel Trigger and any trigger may be “Anded”
to a Master Trigger)
Trigger Lock0--8000 mm (0.01 to 80.00 in)
0 °Cto+50°C(32°F to122 °F)
-- 1 0 °Cto50°C(32°F to122 °F)
1/N/PE 115 V 50--60 Hz
1/N/PE 200 V 50--60 Hz
(Option IP 54)
1 additional per channel (Channel #5 and above)
Every Trigger can be assigned to each of the channel
Via AND--Function multiple Triggers can be combined.
Encoder
Max. Number4
Input connectors X17 and X1824 V DC, max. 100 mA, NPN (scalable)
AssignmentAny encoder can be assigned to any channel.
ConfigurationMetric or inch
Scaling
Indication of Production Machine Speedmax. 1200 m/min (2000 pulses/m)
Speed Configuration
Start Gluing above (Vmin START)0--999 m/min
Stop Gluing below (V min STOP)0--999 m/min
Maximum Machine Speed (V max)0--1200 m/min
Output (Valve Output)
Channel X1 to X4 (Basic Version) for Controlling of Solenoids Valves (Short circuit proof)
Max. Number4 (Option max. 128)
Output VoltageNominal: 24 V DC
Overexcitation Timing0.5--2.5 ms adjustable per software in steps of 0.5 ms
Wattage Capacity per Channelmax. 20 W
Total Wattage Capacity for Channels 1--8max. 160 W
Speed Compensation0--999 mm
1--4000 pulse/m
0.01--99.99 pulse/inch
4000 ft/min (50 pulses/inch)
0--999 ft/min
0--999 ft/min
0--4000 ft/min
Overexcitation:
55 V (Factory Default) or 170 V
all Channels are individually adjustable
9.99 inch
C. 2002
2-3
Manual #50-14 Revised 11/14
Valve M od e
Standard ModeGlue pattern, with or without stitching, is initiated by a trigger
signal. Gluing at speeds between Vmin and Vmax
Standard with Dot-ModeGlue pattern, with or without stitching, is initiated by a trigger
signal. Gluing at speeds between V-min START and V-min STOP
is Dot Mode. Gluing at speeds above V-min STOP is Standard
Mode.
Dot ModeDot- Mode between Vmin and Vmax
Random Product LengthAutomatic adjustment of the pattern length to different product
length. Start and Stop of the pattern is controlled with a trigger
signal. Pattern can be stitched or continuous.
Continuous Gluing with TriggerContinuous gluing controlled with a trigger signal (i.e. glue active
when trigger active). Gluing starts above 1 m/min or 1 ft/min
Continuous with Trigger and Low Speed Cut OffContinuous gluing controlled with a trigger signal (i.e. glue active
when trigger active).Gluing starts when machine speed between
Vmin and Vmax
Continuous Gluing with Low SpeedContinuous gluing starts at machine speed between Vmin and
Vmax, no trigger input is required
Glue Pattern
Maximum selectable Pattern and Delay Length0- 8000 mm in steps of 1 mm
0- 80.00 inch in steps of 0.01 inch
Stitching: Glue Bead and Break Length1- 200 mm in steps of 1 mm
0.01- 2.00 inch in steps of 0.01 inch
Dot ModeBreaks:
1- 8000 mm in steps of 1 mm
0.01- 9.99 inch in steps of 0.01 inch
Dot Length:
0.10- 9.90 ms
Product Description
Pressure Control Output
Max. Number4
Connectors X24 to X274- 20 mA or 0- 20 mA and 0- 10 V scalable
AssignmentEach Pressure Control Output can be assigned to any Encoder
Pressure Rangemin/max-Limits 0 to 100 %
Pressure Control Mode2- or 12- Point Curve
Shutter Control
Output Connector X2324V DC, max. 2 A
Trigger Input X20Controlled by dedicated input or one of the Master Triggers
Machine contact, Alarm outputs and Interfaces
Machine contact X19NPN, normally open contact required
Kanal 1:
Kanal 2:
Kanal 3:
Kanal 4:
Kanal 5:
Kanal 6:
Kanal 7:
Kanal 8:
Druck1: 0%
Druck3: 0%
Druck2: 0%
MUSTER DRUCK SYSTEM KOMPENSAT.
F1F2F3F4
Programm.: 1
Druck4: 0%
DY 2008
241.3mm (9.5”)
279.4mm (11”)
326mm (13”)345 mm (14”)
Operating and Connecting Elements (Basic Version)
Manual 50-14 Revised 7/03
150mm (6”)
Operating Panel
Connectors
Main Switch
Power Inlet
C. 1998
Manual #50-14 Revised 1/03
Installation
Caution!
Only authorized person should execute the following procedures. Observe
all applicable safety rules.
Danger!
Place this controller in a dry and dust-free environment and not in the
danger zone of other machines. The operating elements must be accesable
without hazards.
Connectors and Contact Definitions
6
3--1
REMOTE
X31
Connector Function
X1--X8Output for Solenoids 1 to 8+--Shield
X9--X16Trigger 1 to 8GND+24 V
X17Encoder 1 and 3GND+24 VEncoder 1 Encoder 3
X18Encoder 2 and 4GND+24 VEncoder 2 Encoder 4
X19Machine contactGND
X20Trigger for Shutter ControlGND+24 V
X21Alarm/ Zero SpeedN.O.CommonN.C.
X21Stop/ System ReadyN.O.CommonN.C.
X22Not Used
X23Shutter Output+--Shield
X24--X27Pressure Control OutputGND0(4)-20mA0-10 V+24 V
X28Profi--Bus Connector MaleBus ABus BShield
X29
X30
X31Remote Control RS 485only for ITW Dynatec Remote Control
Profi--Bus Connector
Female
PC--Interface RS 232
or RS 485
1
5VDCBus AGNDBus BShield
234567
Signal
NPN
TXD (232)
B (485)
Contact Definition
Signal
NPN/PNP
Signal
NPN/PNP
RXD
(232)
GND
A (485)
3--2
C. 2002
Installation
Manual #50-14 Revised 8/2008
Connecting the System
Caution!
The over-excitation (spike) voltage for the outputs is shut off as a factory
default. Make sure this voltage is set appropriately for the applicator heads
being used. If necessary change the over-excitation as per instructions
provided in Chapter 4 of this manual.
Note!ITW Dynatec DynaCold and DynaCold Mini applicators always require an
over-excitation voltage of 170V.
(1)
1. Plug all connectors in the corresponding
receptacles.
2. Engage the locking ring (1) of the connector plugs
to the receptacles.
3. Connect the controller to the power supply.
Locating an Optical Trigger (Sensor)
Use the information below to assist in the proper location of an optical triggering device.
TRIGGER LOCATION GUIDELINES (All Conditions Must Be Met)
All Intermittent Modes Except RANDOM
D + L > On Compensation
D < Repeat Length
RANDOM Mode
D + L > On Compensation
D > T + Off Compensation
D < Repeat Length
D = Distance from Optical Sensor to Glue Applicator (i.e. OFFSET)
L = Leading gap on product prior to first glue bead application.
T = Trailing gap on product after last glue bead application.
See the following diagram for additional clarification on this subject.
C. 1998
3--3
2008 D 12/98
Manual #50-14 Revised 3/2005
Connecting Optional Accessories
Installation
The DY2008 may be supplied with optional accessories as follows:
1. Remote Front Panel (28.11101.601): this allows the DY2008 operator interface to be
installed up to 10 meters (33 feet) away from the main control box. This is provided as an
option for the four and eight channel units and is standard for 12 or more channel units.
2. Remote Purge Control (28.11101.602): this allows one-person operation of the manual
gluing (purge) function at distances up to 10 meters (33 feet) from the Main Control Unit or
Remote Front Panel (if installed).
3. Data Interface Option (28.00005.107): this provides the ability to control the
programming of the DY2008 from another CPU via a RS232 or RS485 data interface.
Use the diagrams that follow as a guide in connecting the above accessories to the DY2008
Control Unit.
3--4
C. 2002
Installation
Manual #50-14 Revised 8/2008
Purge Control
Magnet mount
PC
DY 2008
ConnectingOptions Directlyto Control Unit
C. 1998
3--5
2008 D 12/98
Turn mounting
clip clockwise in
slot.
Ground Wire
Manual #50-14 Revised 3/2005
Installation
Purge Control
Magnet mount
Mounting Clip (used
for panel mounting)
Remote Panel
Remove screw
to attach Mounting
Bracket.
Remote Panel
Mounting Bracket.
Data Cable
DY 2008
PC
Attach terminal
to ground wire
Connecting Options Through Remote Front Panel
3--6
C. 2002
Installation
Manual #50-14 Revised 8/2008
ITW Dynatec
An Illinois Tool Works Company
Operation
Operator’s Panel
Machine Speed
Encoder 2Encoder 1
C. 1998
Manual #50-14 Revised 8/08
COM-STOP
COM 2-STOP
BUS-STOP
STOP
EXTER.STOP
All Channels stopped via serial interface
All Channels stopped via Purge Control
All Channels stopped via Profi--Bus
All Channels manually stopped
Stop cause by external contact
S: Trigger Indication for Standard Mode Gluing
C: Trigger Indication for Continuous Mode Gluing
D: Trigger Indicator for Dot Mode Gluing
R: Trigger Indication for Random Mode Gluing
Function Keys F1, F2, F3, F4
STOP
EXTER.STOP
Encoder 3
3: 0 m/min
4: 0 m/min
Encoder 4
PROGRAM:
DY2008
1
Clear Button
Program Number
Numeric Keys
Enter Button
These keys can have changing functions. The lower line of the display above
the keys will indicate the current function.
Manual Gluing (Purge) Button
This button is used to activate the valve outputs manually. It is possible to select individual
channels. The button operates only when manual stop (see below) mode is activated.
Service Button
Use this button to open the configurationmenu. The button operates only when manual stop (see
below) mode is activated.
Stop Button
Pressing this button will stop gluing. “STOP” will flash at the top, center of the display when this
mode is active.
Numeric Keys
Use these keys to enter parameter values.
Clear Button
Pressing this button will reset a parameter to the previously programmed value or to “0” (zero),
depending upon the specific parameter.
Enter Button
This button is used to confirm a new entry.
Page 4-- 2
Remote Purge Control
Manual #50-14 Revised 8/08
Channel
Indicator
C. 1998
Stop Button
Manual Gluing
Button
Channel Indicator
Channel Select Buttons
Use the “increment” or “decrement” button to change the current channel displayed in the
Channel Indicator.
Channel
Select
}
Purge Control
Displays the current channel selected from the Remote Purge Control Unit.
Stop Button
Used to place the control into a STOP condition for manual gluing activation. Also causes the
pressure output circuitry (X24 through X27) to output programmed PURGE PRESSURE when
STOP is activated. STOP activation is indicated by an amber LED that is continuously
illuminated. See the section of this chapter on Stop Conditions for more detail. Deactivating
STOP will also automatically cease manual gluing operations on any channels that are still
active.
Manual Gluing (Purge) Button
Used to activate (amber LED on continuously) or deactivate (amber LED is either OFF or
flashing) the current channel displayed in the Channel Indicator LED’s.
Mounting Note
A magnet is attached to the back side of the Remote Purge Control unit for convenient mounting to any ferrous
metal object.
C. 1998
Manual #50-14 Revised 8/08
Page 4-- 3
Service Setting Menus
Changing these settings may be neccesary during initial installation or after modification
to the system. After pressing the Stop button, these menus are selectable with the Service
button. The following settings are some of the available selections:
Turn power on to the control unit.
Adhesive Applic ation S ystems
Version: V2.xx
INITIALIZING CHANNEL
F1F2F3F4
0 m/min
The Main Menu will come up after a few seconds
K 1:C
K2:
K3:
c4:
K5:
KC6:
K7:
K8:
PRESS1: 20%
PRESS2: 10%
Pattern
PRESS3: 10%
PRESS4: 10%
Pressure
Programm: 1
System
F1F2F3F4
Compensat.
Press the Stop button,
and then the Service Settings Button.
Service Settings Menu 1 appears.
Select the desired parameter menu with the numeric
keys and procede with programming.
Press the Service Settings key again
Service Settings Menu 2 appears.
Select the desired parameter menu with the numeric
keys and procede with programming.
Press the Service Settings button again
Service Settings Menu 3 appears.
Select the desired parameter menu with the numeric
keys and procede with programming.
Modification of these settings will be necessary at initial
installation or after modifications to the system. After
pressing the Stop button the menus can be selected
with the Service button.
C. 1998
Service Settings Menu 1 (of 3) Overview
1Language: Use this menu to select the
language. All display texts will appear in the
selected language.
2Load Program: Use this menu to store all
settings within one of 60 available programs or
recall a previously saved program.
3Channel: Trigger: Use this m enu to determine
which trigger should be assigned for the selected
channel or to deactivate this channel. It is also
possible to combine with an additional trigger via
AND--function. In this case that channel will be
triggered only when both trigger inputs are active.
4Trigger Lock: This function determines for what
length of distance after a trigger signal additional
trigger signals will be ignored . This function can
be necessary gluing products with cut-outs (e.g.
envelopes with window).This will prevent the
detection of the window from triggering a new
glue cycle. It is possible to select values between
1 and 9999 mm (0.01 and 99.99 inch).
5Channel: Encoder: Use this menu to assign one of the encoder inputs to each
channel.
6Encoder Scaling: Use this menu to configure the installed encoder. Program the
number of pulse per meter (inch). If metric unit is selected, all distances will be
shown in mm and all speed indications will be shown in m/min. If inch is selected, all
distances are shown in inch and all speed indications are shown in ft/min.
7Min/Max Speed Set: This menu determines the speed conditions for start and stop
of gluing.The start is valid for increasing speed and stop for decreasing speed.
Additionally the maximum machine speed can be selected. This value is used to
determine the pressure output curve and valve compensation.
8Channel Mode: Use this m enu to select the valve mode. The following modes are
available:
Standard, Standard with Dot, Dot, Random Product Length, Continuous with
C. 1998
Manual #50-14 Revised 8/08
Page 4-- 7
Trigger, Continuous with Trigger and Speed, Continuous with Speed (Vmin).
9Change Security Lock: This menu is used to lock individual functions to prevent
unauthorized modification. Additionally it is possible to change the access code. You
can lock/unlock every above mentioned function. After locking, these functions are
only available via access code. Locking/Unlocking is only possible if you know the
access code.
Page 4-- 8
Manual #50-14 Revised 8/08
C. 1998
Service Settings Menu 2 (of 3) Overview
1Trigger Setup: Use this menu to select the
properties of the trigger devices used.That
means the NPN--PNP selection.
1: 0 m/min
2: 0 m/min
TRIGGER SETUP
PRESSURE SIGNALING
PRESSURE ASSIGNMENT
PRESSURE CURVE
SPIKE VOLTAGE
SPIKE DURATION
SHUTTER ASSIGNMENT
SHUTTER DWELL TIME
CHANGE SECURITY LOCK
STOP
SERVICE SETTINGS 2 OF 3
3: 0 m/min
4: 0 m/min
1
2
3
4
5
6
7
8
9
Code
--
--
--
--
--
--
--
--
2Pressure Signaling: Use this menu to configure
the pressure control outputs. You can select from
CONTRAST+
CONTRAST-
RETURN
0--10VDC/ 0--20 mA or 4--20 mA.
3Pressure Assignment: Use this menu to assign each of the pressure control
outputs to one of the encoders.
4Pressure Curve: Use this menu to select between 2 or 12 point pressure curve.
5Spike Voltage: You can select the overexcitation voltage 55V or 170V for each
channel, or you can deactivate the overexcitation for this channel.
6Spike Duration: The duration time of the overexcitation is programmable between
0.5ms and 2.5ms.
7Shutter Assignment: Use this menu to assign the shutter output (X23) to one of
the triggers.
123
8Shutter Dwell Time: Use this menu to adjust the duration of time the shutter circuit
remains active after the last trigger input. Values range from 1 to 99 seconds.
9Change Security Lock: This menu is used to lock individual functions to prevent
unauthorized modification. Additionally it is possible to change the access code. You
can lock/unlock every above mentioned function. After locking, these functions are
only available via access code. Locking/Unlocking is only possible if you know the
access code.
C. 1998
Manual #50-14 Revised 8/08
Page 4-- 9
Service Settings Menu 3 (of 3) Overview
1STOP--Configuration: Use this menu to select
the Stop Mode for each channel: Complete or do
not complete an interrupted gluing pattern upon
machine restart.
RS232 or RS485 data protocol and to adjust the
baud rate.
3Reserve: This menu is not used.
4Shutter Trigger Setup: Use this menu to select a NPN or PNP shutter trigger
device.
5Reserve: This menu is not used.
6Digital Configuration: Use this menu to configure the Machine Contact (X19) and
Alarm Output (X21).
7Reserve: This menu is not used.
8Load Factory Setup: In this menu you can reload the factory default for the active
program. After entering the access code the active program will be reset to the
values listed below.
9Change Security Lock: This menu is used to lock individual functions to prevent
unauthorized modification. Additionally it is possible to change the access code. You
can lock/unlock every above mentioned function. After locking, these functions are
only available via access code. Locking/Unlocking is only possible if you know the
access code.
Factory Default Values
Service Settings Menu 1 of 3
No
FunctionSetting
.
1LanguageEnglish
2ProgramAs per operator selection
3Trigger AssignmentAll Channels are assigned to Trigger 1.
The ’AND’--function is deactivated
4Trigger LockAll Channels set to 1 mm (0.01 in)
5Encoder AssignmentAll Channels are assigned to Encoder 1.
6Encoder ScalingAll Encoders are scaled to 1000 pulses/meter (10.00 ppi)
StitchAll Channels: Glue 4mm (0.04 in), Gap 4 mm (0.04 in), no stitch
functions are active
OffsetAll Channels: 20mm (0.20 in)
CompensationAll Channels: ON: 0, OFF: 0
C. 1998
C. 1998
Manual #50-14 Revised 8/08
Page 4-- 11
Service Setting Programming Conventions
The following programming conventions are employed in the Service Settings Menus:
123
RETURN
The “numeral” icon is displayed in the lower
right corner of the screen to indicate that the
numeric keypad should be used to enter the
desired value.
The “enter” icon is displayed in the lower
right corner of the screen to indicate that the
ENTER button (see page 4-1) should be
pressed in order to accept the selected
value.
Press the CLEAR Button on the numeric
keypad to revert a modified parameter to its
original value provided the ENTER button
has not already been pressed.
Press the RETURN (F4) button to go to the
next higher level of programming menus or
to undo a programming change as long as
the ENTER button has not been pressed.
1: 0 m/min
2: 0 m/min
ENCODER 1:
ENCODER 2:
ENCODER 3:
ENCODER 4:
STOP
ENCODER SCALING MENU
500
1000
1000
1000
inch
3: 0 m/min
4: 0 m/min
PULSES / Meter
PULSES / Meter
PULSES / Meter
PULSES / Meter
RETURN
123
Display Contrast Adjustments
The display brightness (contrast) is adjusted from any of the three Service Settings Menus
via the following procedure. Take care not to adjust the display too bright as this will tend
to reduce the life of the display.
1
2
3
4
5
6
7
8
9
3: 0 m/min
4: 0 m/min
Code
--
--
--
--
--
--
--
--
RETURN
123
CONTRAST +
CONTRAST-
This button is used to make the display
background darker.
This button is used to make the display
background lighter. NOTE: do not set the
display too bright as this will tend to reduce
the life of the display.
After the controller is switched on the
display shortly indicates the ITW Dynatec
logo and the Software revision.
After a few seconds the display changes
to the Main Menu. That means glue
pattern, pressure and program number will
be shown.
1: 0 m/min
C1:
C2:
C3:
C4:
C5:
C6:
C7:
C8:
PRESS1: 0%
PRESS2: 0%
PATTERNPRESSURESYSTEMCOMP.
PRESS3: 0%
PRESS4: 0%
PROGRAM:
1
Press the STOP Button.
Press the Service Button.
Select one of the listed functions by pressing the
corresponding numeric key.
Use this menu to select the operating language. All display texts will appear in the selected
language. Following languages are available: German, English, Finnish, French, Italian,
Swedish, Dutch, Spanish and Czech.
1
Press Button 1.
Enter Access Code if this function is
protected.
Press Enter Button.
Press a numeric key to select a language.
1: 0 m/min
1: 0m/min
0 m/min
STOP
ACCESS CODE: ----
STOP
LANGUAGE MENU
DEUTSCH
ENGLISH2
ENGLISH
Suomi
Francais
Italiano
123
RETURN
1
2
3
4
5
123
RETURN
Loading...
+ 68 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.