ITT Goulds Pumps 3298 Series, Goulds Pumps SP 3298, Goulds Pumps V 3298 Installation, Operation And Maintenance Instructions

Installation, Operation and Maintenance Instructions
3298
Frame Mounted
V 3298
3298
Close Coupled
3298 Family
SP 3298
Close Coupled
Pump Safety Tips
Insulated work gloves when handling
·
hot bearings or using bearing heater
Heavy work gloves when handling
·
parts with sharp edges, especially impellers
Safety glasses (with side shields) for
·
eye protection, especially in machine shop areas
Steel-toed shoes for foot protection when
·
handling parts, heavy tools, etc.
Other personal protective equipment to protect against
·
hazardous/toxic fluids
Coupling Guards:
Never operate a pump without a coupling guard properly
·
installed
Flanged Connections:
· Never force piping to make a connection with a pump
· Use only fasteners of the proper size and material
Operation:
Do not operate below minimum rated flow, or with suction/discharge valves closed
Do not open vent or drain valves, or remove plugs while system is pressurized
Maintenance Safety:
Always lockout power
·
Ensure pump is isolated from system and pressure is
·
relieved before disassembling pump, removing plugs, or disconnecting piping
Use proper lifting and supporting equipment to prevent
·
serious injury
Observe proper decontamination procedures
·
Know and follow company safety regulations
·
· Never apply heat to remove impeller
· Observe all cautions and warnings highlighted in pump
Installation, Operation and Maintenance Instructions.
· Ensure there are no missing fasteners
· Beware of corroded or loose fasteners
IMPORTANT SAFETY REMINDER
To: Our Valued Customers
Goulds' pumps will provide safe, trouble-free service when properly installed, maintained, and operated. We have an extensive network of experienced sales and service professionals to assist in maximizing your satisfaction with our products.
Safe installation, operation, and maintenance of Goulds' equipment are an essential end user responsibility. This Instruction, Operation, and Maintenance (IOM) manual identifies specific safety risks that must be considered at all times during product life. Understanding and adhering to these safety warnings is mandatory to ensure person- nel, property, and/or the environment will not be harmed. Adherence to these warnings alone, however, is not sufficient — it is anticipated that the end user will also comply with industry and corporate safety standards. Identifying and eliminating unsafe installation, operating and maintenance practices is the responsibility of all individuals involved in the installation, operation, and maintenance of industrial equipment.
Specific to pumping equipment, two significant risks bear reinforcement above and beyond normal safety precautions.
! WARNING
Operation of any pumping system with a blocked suction and discharge must be avoided in all cases. Operation, even for a brief period under these conditions, can cause superheating of enclosed pumpage and result in a violent
1
explosion. All necessary measures must be taken by the end user to ensure this condition is avoided.
! WARNING
Pumping equipment Instruction, Operation, and Maintenance manuals clearly identify accepted methods for disassembling pumping units. These methods must be adhered to. Specifically, applying heat to impellers and/or
2
impeller retaining devices to aid in their removal is strictly forbidden. Trapped liquid can rapidly expand and result in a violent explosion and injury.
Please take the time to review and understand the safe installation, operation, and maintenance guidelines outlined in this manual.
FOREWORD
This manual provides instructions for the Installation, Operation, and Maintenance of the Goulds Model 3298 family of Magnetic Drive Process Pumps. This manual must be read and understood before installation and start-up.
The design, materials, and workmanship incorporated in the construction of Goulds pumps makes them capable of giving trouble-free service. The life and satisfactory service of any mechanical unit, however, is enhanced and extended by correct application, proper installation, periodic inspection, condition monitoring and careful maintenance. This instruction manual was prepared to assist operators in understanding the construction and the correct methods of installing, operating, and maintaining these pumps.
ITT Industries - Goulds shall not be liable for physical injury, damage or delays caused by a failure to observe the instructions for Installation, Operation, and Maintenance contained in this manual.
Warranty is valid only when genuine ITT Industries - Goulds Pumps parts are used.
Use of the equipment on a service other than stated in the order could nullify the warranty, unless written approval is obtained in advance from ITT Industries, Goulds Pumps.
Supervision by an authorized ITT Industries - Goulds representative is recommended to assure proper installation.
Additional manuals can be obtained by contacting your local ITT Industries - Goulds representative, by calling 1-800-446-8537, or visiting our website at www.gouldspumps.com.
THIS MANUAL EXPLAINS
Proper Installation
n
Start-Up Procedures
n
Operation Procedures
n
Routine Maintenance
n
Pump Overhaul
n
Troubleshooting
n
Ordering Spare or Repair Parts
n
4 3298 Family Rev. 4/07
TABLE OF CONTENTS
PAGE
7 SAFETY
11 GENERAL INFORMATION
15 INSTALLATION
27 OPERATION
33 PREVENTIVE MAINTENANCE
39 DISASSEMBLY & REASSEMBLY
SECTION
1
2
3
4
5
6
113 SPARE AND REPAIR PARTS
125 APPENDICES
I Hydraulic Coverage Charts
II Coupling Guard Installation
III Impeller Trim Procedures
IV Power Monitors
V Reliability Tips for Operating Lined Magnetically-Driven
Sealless Pumps (Quick Reference Guide
VI Polyshield®ANSI Combo Installation, Operation and
Maintenance Instructions
7
8
3298 Family Rev. 4/07 5
6 3298 Family Rev. 4/07
SAFETY
DEFINITIONS ................................7
MEDICAL PRECAUTIONS ........................8
GENERAL PRECAUTIONS ........................8
DEFINITIONS
1
These pumps have been designed for safe and reliable operation when properly used and maintained in accordance with instructions contained in this manual. A pump is a pressure containing device with rotating parts that can be hazardous. Operators and maintenance personnel must realize this and follow safety measures. ITT Industries Goulds Pumps shall not be liable for physical injury, damage or delays caused by a failure to observe the instructions in this manual.
Throughout this manual the words WARNING, CAUTION, ELECTRICAL, ATEX, and NOTE are used to indicate procedures or situations which require special operator attention:
! WARNING
s
Operating procedure, practice, etc. which, if not correctly followed, could result in personal injury or loss of life.
! CAUTION
$
Operating procedure, practice, etc. which, if not followed, could result in damage or destruction of equipment.
Particular care must be taken when electrical power
"
source to the equipment is energized.
EXAMPLES
! WARNING
s
Pump shall never be operated without coupling guard installed correctly.
! CAUTION
$
Throttling flow from the suction side may cause cavitation and pump damage.
Improper impeller adjustment could cause contact
!
between the rotating and stationary parts, resulting in a spark and heat generation.
Lock out driver power to prevent electric shock,
!
accidental start-up, and physical injury.
Lock out driver power to prevent electric shock,
"
accidental start-up and physical injury.
NOTE: Proper alignment is essential for long pump life.
If equipment is to be installed in a potentially
!
explosive atmosphere and these procedures are not followed, personal injury or equipment damage from an explosion may result.
NOTE: Operating procedure, condition, etc. which is essential to observe.
3298 Family Rev. 4/07 7
MEDICAL PRECAUTIONS
! WARNING
s
Magnetic drive pumps contain very strong magnets which may pose health risks. The following guidelines shall always be observed.
1. When disassembled and magnets are exposed, individuals with artificial cardiac pacemakers, implanted defibrillators, metallic prosthetic heart valves, internal wound clips (from surgery), prosthetic joints, metallic wiring, or other metallic prosthetic devices shall avoid working with, being in proximity of, or handling the magnets contained in the pumps.
GENERAL PRECAUTIONS
! WARNING
s
Personal injuries will result if procedures outlined in this manual are not followed.
NEVER use heat to disassemble pump due to risk of
C
explosion from trapped liquid.
NEVER operate pump without coupling guard
AC AD
AD
correctly installed.
NEVER operate pump beyond the rated conditions to which the pump was sold.
NEVER start pump without proper prime (all models), or proper liquid level in self-priming pumps (Model SP3298).
2. When disassembled and magnets are exposed, individuals who have had previous surgeries (especially chest or head surgery) and who do not know if they have metallic clips internally should avoid work on this unit unless it can be established by his or her physician that no risk exists while working on a magnet drive pump.
NEVER run pump below recommended minimum
A C C
AC AD AC
flow or when dry.
ALWAYS lock out power to the driver before
B
performing pump maintenance.
NEVER operate pump without safety devices
C
installed.
NEVER operate pump with discharge valve closed.
NEVER operate pump with suction valve closed.
DO NOT change conditions of service without approval of an authorized ITT-Goulds representative.
EXPLOSION PREVENTION
In order to reduce the possibility of accidental explosions in atmospheres containing explosive gases and/or dust, the
!
instructions under the ATEX symbol must be closely followed. ATEX certification is a specification enforced in Europe for non-electrical and electrical equipment installed in Europe. The usefulness of the ATEX requirements is not limited to Europe. They are useful guidelines for equipment installed in any potentially explosive environment.
NOTE: When pumping unit is installed in a potentially explosive atmosphere, the instructions after the Ex symbol
!
must be followed. Personal injury and/or equipment damage may occur if these instructions are not followed. If there is any question regarding these requirements or if the equipment is to be modified, please contact a Goulds representative before proceeding.
8 3298 Family Rev. 4/07
SPECIAL ATEX CONSIDERATIONS
All installation and operation instructions in this manual must be strictly adhered to. In addition, care must be taken to ensure that the equipment is properly maintained. This includes but is not limited to:
1. Monitoring the pump frame and liquid end temperature.
ATEX IDENTIFICATION
For a pumping unit (pump, seal, coupling, motor and pump accessories) to be certified for use in an ATEX classified environment, the proper ATEX identification must be present.
The ATEX tag would be secured to the pump or the baseplate on which it is mounted. A typical tag would look like this:
The CE and the Ex designate the ATEX compliance. The code directly below these symbols reads as follows:
=
II
2=
G/D =
Tx =
Group 2 Category 2 Gas and Dust present Temperature class, can be T1 to T4
(see Table 1)
2. Maintaining proper bearing lubrication.
3. Ensuring that the pump is operated in the intended hydraulic range.
Table 1
Max
Max
permissible surface
temperature
Code
T1 842 (450) 700 (372) T2 572 (300) 530 (277) T3 392 (200) 350 (177) T4 275 (135) 235 (113)
T5 212 (100)
T6 185 (85)
The code classification marked on the equipment should be in accordance with the specified area where the equipment will be installed. If it is not, please contact your ITT/Goulds representative before proceeding.
o
F(oC)
permissible
liquid
temperature
o
F(oC)
Option not
available
Option not
available
2
INTENDED USE
The ATEX conformance is only applicable when the pump unit is operated within its intended use. All instructions within this manual must be followed at all times. Operat­ing, installing or maintaining the pump unit in any way that is not covered in this manual can cause serious personal injury or damage to the equipment. This includes
3298 Family Rev. 4/07 9
any modification to the equipment or use of parts not provided by ITT/Goulds. If there is any question regarding the intended use of the equipment, please contact an ITT/Goulds representative before proceeding.
CONDITION MONITORING
For additional safety precautions, and where noted
!
in this manual, condition monitoring devices should be used. If applicable, devices should comply with ATEX. This includes, but is not limited to:
Pressure gauges
u
Flow meters
u
Level indicators
u
Motor load readings
u
Temperature detectors
u
Bearing monitors
u
Leak detectors
u
PumpSmart
u
®
control system
For assistance in selecting the proper instrumentation and its use, please contact your ITT/Goulds representative.
10 3298 Family Rev. 4/07
GENERAL INFORMATION
PUMP DESCRIPTION ...........................11
NAMEPLATE INFORMATION .....................12
RECEIVING THE PUMP .........................13
Storage Requirements ..........................13
Handling .................................13
PUMP DESCRIPTION
2
The Model 3298 is a sealless close coupled or frame mounted centrifugal pump with an enclosed impeller that is driven by a synchronous magnetic coupling and meets
1
dimensional standards of ANSI B73.1. (The 1x1
-5 is not
2
ANSI dimensional.)
The SP 3298 is a self-priming sealless close coupled or frame mounted centrifugal pump with an enclosed impeller that is driven by a synchronous magnetic coupling. The pump and frame / adapter feet locations meet ANSI B73.1 dimensional standards.
The V 3298 is a vertical in-line sealless close coupled centrifugal pump with an enclosed impeller that is driven by a synchronous magnetic coupling and meets the dimensional standards of ANSI B73.2.
Casing - The casings are one piece cast ductile iron lined with 1/8" TEFZEL a TEFZEL
®
®1
and have ANSI class 150 flanges with
raised face. The 3298 and SP 3298 are end suction, top centerline discharge and are self-venting. The V 3298 is side suction, side discharge and is also self-venting.
Impeller Magnet Assembly - The 3298 family utilizes a one or two piece impeller magnet assembly. The magnet ring is balanced to ISO 1940 G6.3 levels and is sealed within the solid enclosed TEFZEL
®
impeller magnet
assembly.
Stationary Shaft - The impeller magnet assembly rotates about a solid stationary silicon carbide shaft. The shaft is supported at one end by the containment shell and the other end by the TEFZEL
®
bearing spider.
Rear Impeller Wear Ring - is standard on M and L group size pumps and is not required on S group sizes. The wear ring is pressed into the rear of the impeller assembly. The wear ring reduces axial thrust in the M and L group size pumps.
Magnetic Coupling - is a coaxial synchronous type using rare earth magnets. This concept results in a compact design and allows the impeller to turn at the same speed as the motor, (i.e. there is no slip between the drive and driven magnets.)
Magnets - Neodymium Iron (NdFe).
Containment Shell - isolates the pumped liquid from the
atmosphere. The containment shell construction is backed with vinylester FRP.
Radial Bearings and Thrust Bearings - Goulds standard bearing material is carbon with optional Pure Sintered Alpha Grade Silicon Carbide or DryGuard™ Pure Sintered Alpha Grade Silicon Carbide.
Standard Close Coupled Mounting - The drive magnet assembly is keyed, set screwed and mounted directly to the motor shaft. This arrangement eliminates the need to perform pump/motor alignment.
Optional Power End
3
- The standard configuration is cast iron with flood oil lubricated ball bearings. Pure oil mist systems are available as an option. For protection and reliability of the bearings and the lubricant, a labyrinth seal is provided. On the inboard side a lip seal is used to prevent leakage of oil into the magnetic drive assembly.
Bearing Spider - The bearing spider constructed from solid TEFZEL
®
houses one of the key silicon carbide thrust bearings in the pump and supports the stationary shaft at one end.
1
TEFLON®and TEFZEL®: Registered trademarks for fluoropolymer resins, films and fibers made by DuPont.
2
The 1x1
3
Frame mounted power end not available on the V 3298.
3298 Family Rev. 4/07 11
1
-5 is tangential discharge.
2
NAMEPLATE INFORMATION
Every pump has two Goulds nameplates that provide information about the pump. The tags are located on the casing and bearing frame.
Fig.
Description
Pump Casing Tag - provides information about
the pump’s hydraulic characteristics.
Note the format of the pump size: Discharge x Suction - Nominal maximum Impeller Diameter in inches
(Example: 2x3-8)
No. Example
Fig. 1
English
When ordering spare parts, you will need to identify pump model, size, serial number, and the item number of required parts. Information can be taken from the pump casing tag. Item numbers can be found in this manual
(Figs.1&2).
Bearing Frame Tag - provides information on the lubrication system used (Fig. 3).
ATEX Tag - If applicable, your pump unit may have the following ATEX tag affixed to the pump and/or baseplate. See the Safety section for a description of the symbols and codes (Fig. 4).
Fig. 2
Metric
Fig. 3
Fig. 4
12 3298 Family Rev. 4/07
RECEIVING THE PUMP
Inspect the pump as soon as it is received. Make notes of damaged or missing items on the receipt and freight bill. File any claims with the transportation company immediately.
STORAGE REQUIREMENTS
Short Term - (Less than 3 months) Goulds normal
packaging procedure is designed to protect the pump during shipping. Upon receipt store in a covered and dry location.
Long Term - (More than 6 months) Preservative treatment of bearings and machined surfaces will be required. Rotate shaft several times every 3 months. Refer to driver and coupling manuals for their long term storage procedures. Store in a dry covered location.
HANDLING
! WARNING
s
Failure to properly lift and support equipment could result in serious injury or damage to pumps.
Use care when moving pumps. Lifting equipment must be able to adequately support the entire assembly. Hoist bare pumps, using a sling under the suction flange and bearing housing. (Fig. 5)
Baseplate mounted units are moved with slings under the pump and driver. (Figs.5&7)
2
Fig. 6
! WARNING
s
These pumps use ceramic silicon carbide components. Do not drop pump or subject to shock loads, this may damage internal ceramic components.
Fig. 5
Fig. 7
3298 Family Rev. 4/07 13
Complete vertical pumps are lifted with straps under the pump and motor (Fig. 8). Bare vertical pumps (without a motor) are lifted with straps under the pump and motor adapter (Fig. 9).
Fig. 8
Fig. 9
14 3298 Family Rev. 4/07
INSTALLATION
BASEPLATE INSPECTION........................15
SITE/FOUNDATION............................15
LEVEL BASEPLATE ...........................16
Cast Iron/Fabricated Steel ........................16
Feature Fabricated Steel/API Style....................17
Baseplate Leveling Worksheet ......................18
ALIGNMENT AND ALIGNMENT PROCEDURE ...........19
Alignment Checks ............................19
Alignment Criteria ............................19
SetUp...................................20
Measurement ...............................20
Angular Alignment ............................20
Parallel Alignment ............................21
Complete Alignment ...........................21
Alignment Troubleshooting .......................22
GROUT BASEPLATE ...........................22
PIPING....................................23
General ..................................23
Suction Piping ..............................23
Discharge Piping .............................25
Final Piping Check ............................25
3
Equipment that is to be installed in a potentially explosive environment must be done so in accordance with the
!
following installation instructions.
BASEPLATE INSPECTION
1. Remove all equipment.
2. Completely clean the underside of baseplate. It is
sometimes necessary to coat the underside of the baseplate with an epoxy. This may have been purchased as an option.
3. Remove the rust preventative solution from the machined pads with an appropriate solution.
SITE / FOUNDATION
A pump should be located near the supply of liquid and have adequate space for operation, maintenance, and inspection.
Baseplate mounted pumps are normally grouted to a concrete foundation, which has been poured on a solid footing. The foundation must be able to
absorb any vibration and to form a permanent, rigid support for the pumping unit.
The location and size of the foundation bolts are shown on the outline assembly drawing, provided with the pump data package.
3298 Family Rev. 4/07 15
All equipment being installed must be properly
!
grounded to prevent unexpected static electric discharge. This includes ensuring that the PFA lined pumps are pumping fluids that are conductive. If not, a static electric discharge may occur when the pump is drained and disassembled for maintenance purposes.
Foundation bolts commonly used are sleeve type (Fig. 10) and J type (Fig. 11). Both designs permit movement for final bolt adjustment.
1. Inspect foundation for dust, dirt, oil, chips, water, etc. and remove any contaminants. Do not use oil-based cleaners as grout will not bond to it.
2. Prepare the foundation in accordance with the grout manufacturer’s recommendations.
Fig. 10
Fig. 11
LEVEL BASEPLATE
CAST IRON / FABRICATED STEEL
1. Place two sets of wedges or shims on the foundation, one set on each side of every foundation bolt
(Fig. 12, 13). The wedges should extend .75 in. (20 mm) to 1.5 in. (40 mm) above the foundation, to allow for adequate grouting. This will provide even support for the baseplate once it is grouted.
2. Remove water and/or debris from anchor bolt holes/sleeves. If the sleeve type bolts are being used, fill the sleeves with rags to prevent grout from entering.
3. Carefully lower baseplate onto foundation bolts.
4. Level baseplate to within .125 in.(3mm) over the length of the base and .062 in. (1.5 mm) over the width of the base by adjusting shims or wedges.
5. Hand tighten bolts.
Fig. 13
Fig. 12
16 3298 Family Rev. 4/07
FEATURE FABRICATED STEEL/ API STYLE
(BASEPLATES PROVIDED WITH VERTICAL
LEVELING ADJUSTORS)
1. Coat the jack screws with an anti-seizing compound to allow for easy removal after the grout has been cured.
2. Cut round circular plates from bar stock to set the jack screws on. The edges of the plates should be chamfered to reduce stress concentrations.
3. Set the baseplate on the foundation and use the four corner jack screws to raise the baseplate off the foundation 0.75" to 1.5" (Fig. 14). The two center jack screws should not be touching the foundation.
Fig. 14
4. Place two machinist levels on the motor pads, one lengthwise on a single motor pad, and another across the ends of both motor pads (Fig 15).
NOTE: When using a machinist level, it is important that the surface being leveled is free of all contaminants, such as dust, to ensure an accurate reading.
7. Place the two levels on the pump pads, one lengthwise on a single pump pad, and another across the middle of both pump pads. (Fig. 16)
Fig. 16
3
8. Level the pump pads as close to zero as possible, in both directions, by adjusting the jack screws.
9. Install the anchor bolts until they are hand tight.
10. Return the levels to the motor pads and check the level measurements.
11. Adjust the jack screws and anchor bolts, if necessary, until all level measurements are within the design requirements of 0.002 in./ft.
12. When taking readings, center the level over the pad being measured.
NOTE: The Baseplate Leveling Worksheet provided may be used when taking readings.
5. Level the motor pads as close to zero as possible, in both directions, by adjusting the four jack screws.
6. Next, turn down the center jack screws so that they are resting on their metal discs on the foundation.
Fig. 15
3298 Family Rev. 4/07 17
BASEPLATE LEVELING WORKSHEET
LEVEL MEASUREMENTS
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
11)
12)
13)
14)
15)
16)
17)
18)
18 3298 Family Rev. 4/07
ALIGNMENT AND ALIGNMENT PROCEDURE
! WARNING
B
s
Before beginning any alignment procedure, make sure driver power is locked out. Failure to lock out driver power can result in serious personal injury.
Alignment procedures must be followed to prevent
!
unintended contact of rotating parts. Follow coupling manufacturer's coupling installation and operation procedures.
To remove guard, refer to coupling guard assembly/ disassembly instructions.
The points at which alignment is checked and adjusted are:
Initial Alignment is done prior to operation when
·
the pump and the driver are at ambient temperature.
Final Alignment is done after operation when the
·
pump and driver are at operating temperature.
Alignment is achieved by adding or removing shims from under the feet of the driver and shifting equipment horizontally as needed.
NOTE: Proper alignment is the responsibility of the installer of the unit.
Accurate alignment of the equipment must be attained. Trouble-free operation can be accomplished by following these procedures:
ALIGNMENT CHECKS
Initial Alignment (Cold Alignment)
Before Grouting Baseplate - To ensure alignment can be
·
obtained.
Final Alignment (Hot Alignment)
After First Run - To obtain correct alignment when both
·
pump and driver are at operating temperature. Thereafter, alignment should be checked periodically in accordance with plant operating and maintenance procedures.
NOTE: Alignment check must be made if process temperature changes, piping changes, and/or pump service is performed.
ALIGNMENT CRITERIA
Good alignment is achieved when the dial indicator readings as specified in the alignment procedure are .002 in. (.05 mm) Total Indicated Reading (T.I.R.) or less when the pump and driver are at operating temperature (Final Alignment).
During the installation phase, however, it is necessary to set the parallel alignment in the vertical direction to a different criteria due to differences in expansion rates of the pump and driver. Table 2 below shows recommended cold settings for electric motor driven pumps based on different pumpage temperatures. Driver manufacturers should be consulted for recommended cold settings for other types of drivers (steam turbines, engines, etc.).
Table 2
Cold Settings of Parallel
Vertical Alignment
Pumpage
Temperature Set Driver Shaft
50°F (10°C) .002in. (.05mm) LOW
150°F (65°C) .001in. (.03mm) HIGH
250°F (120°C) .005in. (.12mm) HIGH
3
After Grouting Baseplate - To ensure no changes to
·
alignment have occurred during grouting process.
After Connecting Piping - To ensure that pipe strains
·
haven’t altered alignment. If changes have occurred, alter piping to remove pipe strains on pump flanges.
3298 Family Rev. 4/07 19
SET UP
1. Mount two dial indicators on one of the coupling halves (X) so they contact the other coupling half (Y) (Fig. 17).
2. Check setting of indicators by rotating coupling half X to ensure indicators stay in contact with coupling half Y but do not bottom out. Adjust indicators accordingly.
Fig. 17
MEASUREMENT
1. To ensure accuracy of indicator readings, always rotate both coupling halves together so indicators contact the same point on coupling half Y. This will eliminate any measurement problems due to runout on coupling half Y.
2. Take indicator measurements with driver feet hold down bolts tightened. Loosen hold down bolts prior to making alignment corrections.
3. Take care not to damage indicators when moving driver during alignment corrections.
Fig. 18
4. Repeat steps 1 through 3 until indicator A reads .002 in (.05 mm) or less.
Horizontal Correction (Side to Side)
1. Zero indicator A on left side of coupling half Y, 90° from top dead center (9 o’clock).
2. Rotate indicators through top dead center to the right side, 180° from the start (3 o’clock). Observe needle and record reading.
3. Negative Reading - The coupling halves are further apart on the right side than the left. Correct by either sliding the shaft end of the driver to the left or the other end to the right.
Positive Reading - The coupling halves are closer together on the right side than the left. Correct by either sliding the shaft end of the driver to the right or the other end to the left (Fig. 19).
4. Repeat steps 1 through 3 until indicator A reads .002 in. (.05 mm) or less.
ANGULAR ALIGNMENT
A unit is in angular alignment when indicator A (Angular indicator) does not vary by more that .002 in. (.05 mm) as measured at four locations 90° apart.
Vertical Correction (Top to Bottom)
1. Zero indicator A at top dead center (12 o’clock) of coupling half Y.
2. Rotate indicators to bottom dead center (6 o’clock). Observe needle and record reading.
3. Negative Reading - The coupling halves are further apart at the bottom than at the top. Correct by either raising the driver feet at the shaft end (add shims) or lowering the driver feet at the other end (remove shims) (Fig. 18).
Positive Reading - The coupling halves are closer at the bottom than at the top. Correct by either lowering the driver feet at the shaft end (remove shims) or raising the driver feet at the other end (add shims).
5. Re-check both horizontal and vertical readings to ensure adjustment of one did not disturb the other. Correct as necessary.
20 3298 Family Rev. 4/07
Fig. 19
PARALLEL ALIGNMENT
A unit is in parallel alignment when indicator P (parallel indicator) does not vary by more than .002 in. (.05 mm) as measured at four points 90° apart at operating temperature. Note the preliminary cold setting criteria, Table 2.
Vertical Correction (Top to Bottom)
1. Zero indicator P at top dead center of coupling (12 o’clock) half Y (Fig. 19).
2. Rotate indicator to bottom dead center (6 o’clock). Observe needle and record reading.
3. Negative Reading - Coupling half X is lower than coupling half Y. Correct by removing shims of thickness equal to half of the indicator reading under each driver foot.
Positive Reading - Coupling half X is higher than coupling half Y. Correct by adding shims of thickness equal to half of the indicator reading from each driver foot (Fig. 20).
Positive Reading - Coupling half Y is to the right of coupling half X. Correct by sliding driver evenly in the appropriate direction.
Fig. 21
3
NOTE: Failure to slide motor evenly will affect horizontal angular correction.
4. Repeat steps 1 through 3 until indicator P reads .002 in. (.05 mm) or less.
5. Re-check both horizontal and vertical readings to ensure adjustment of one did not disturb the other. Correct as necessary.
Fig. 20
NOTE: Equal amounts of shims must be added to or removed from each driver foot. Otherwise the vertical angular alignment will be affected.
4. Repeat steps 1 through 3 until indicator P reads within .002 in. (.05 mm) or less when hot, or per Table 1 when cold.
Horizontal Correction (Side to Side)
1. Zero indicator P on the left side of coupling half Y, 90° from top dead center (9 o’clock).
2. Rotate indicators through top dead center to the right side, 180° from the start. Observe needle and record reading (3 o’clock).
3. Negative Reading - Coupling half Y is to the left of coupling half X. Correct by sliding driver evenly in the appropriate direction (Fig. 21).
COMPLETE ALIGNMENT
A unit is in complete alignment when both indicators A (angular) and P (parallel) do not vary by more than .002 in. (.05 mm) as measured at four points 90° apart.
Vertical Correction (Top to Bottom)
1. Zero indicators A and P at top dead center (12 o’clock) of coupling half Y.
2. Rotate indicator to bottom dead center (6 o’clock). Observe the needles and record the readings.
3. Make corrections as outlined previously.
Horizontal Correction (Side to Side)
1. Zero indicators A and P on the left side of coupling half Y, 90° from top dead center (9 o’clock).
2. Rotate indicators through top dead center to the right side, 180° from the start (3 o’clock). Observe the needle, measure and record the reading.
3. Make corrections as outlined previously.
4. Recheck both vertical and horizontal readings to ensure adjustment of one did not disturb the other. Correct as necessary.
3298 Family Rev. 4/07 21
ALIGNMENT TROUBLESHOOTING
Alignment Troubleshooting
PROBLEM PROBABLE CAUSE REMEDY
Cannot obtain horizontal (Side-to-Side) alignment, angular or parallel.
Cannot obtain vertical (Top to Bottom) alignment, angular or parallel.
NOTE: With experience, the installer will understand the interaction between angular and parallel and will make corrections appropriately.
Driver feet bolt bound.
Baseplate not leveled properly, probably bowed.
GROUT BASEPLATE
Table 3
Loosen pump hold down bolts and slide pump and driver until horizontal alignment is achieved.
Determine if center of baseplate should be raised or lowered and correct by evenly adding or removing shims at the center of the baseplate.
1. Clean areas of baseplate that will contact grout. Do not use an oil-based cleaner because grout will not bond to it.
2. Build a dam around foundation (Fig. 22). Thoroughly wet foundation.
3. Pour grout through grout hole in baseplate up to level of dam. Remove air bubbles from grout as it is poured by puddling, using a vibrator, or pumping the grout into place. Non-shrink grout is recommended (Fig. 22).
Fig. 22
4. Allow grout to set.
5. Fill remainder of baseplate with grout. Remove air as before (Fig. 23).
Fig. 23
6. Allow grout to set at least 48 hours.
7. Tighten foundation bolts.
ALIGNMENT CHECK
Re-check alignment before continuing, using methods previously described.
22 3298 Family Rev. 4/07
PIPING
Guidelines for piping are given in the Centrifugal Pump section of the “Hydraulic Institute Standards” and should be reviewed prior to pump installation.
A
! WARNING
s
Never draw piping into place by forcing at the flanged connections of the pump. This will impose dangerous strains on the unit and cause misalignment between pump and driver. Pipe strain can adversely effect the operation of the pump. That could result in serious personal injury and damage to equipment.
Flange loads from the piping system, including
!
those from thermal expansion of the piping, must not exceed the limits of the pump. Casing deforma­tion can result in contact with rotating parts and result in excess heat generation, sparks and premature failure.
1. All piping must be supported independently and must line up naturally with the pump flanges.
2. Piping runs shall be designed to minimize friction losses.
3. DO NOT make final connection of piping to pump until grout has hardened and pump and driver hold-down bolts have been tightened.
4. It is suggested that expansion loops or joints, if used, be properly installed in suction and/or discharge lines when handling liquids at elevated temperatures, so linear expansion of piping will not draw pump out of alignment (Fig. 24 & 25).
Fig. 25
5. The piping should be arranged to allow pump flushing prior to removal of the unit on services handling corrosive liquids.
6. System should be thoroughly cleaned prior to installation.
SUCTION PIPING
A
! WARNING
s
NPSHAmust always exceed NPSHRas shown on Goulds performance curves received with order. Reference Hydraulic Institute for NPSH and pipe friction values needed to evaluate suction piping.
Properly installed suction piping is a necessity for trouble free pump operation. Suction piping should be flushed
BEFORE connection to the pump.
3
1. Use of elbows close to the pump suction flange should be avoided. There should be a minimum of 2 pipe diameters of straight pipe between the elbow and suction inlet. Where used, elbows should be long radius (Fig. 26)
Fig. 24
3298 Family Rev. 4/07 23
CORRECT
CORRECT PIPING
Fig. 26
Fig. 28
Suction Lift Conditions
1. Suction pipe must be free from air pockets
Fig. 27
2. Use suction pipe one or two sizes larger than the pump suction, with a reducer at the suction flange. Suction
piping should never be of smaller diameter than the pump suction.
3. Reducers should be eccentric at the pump suction flange with sloping side down and horizontal side at the top (Figs. 26, 27, 28).
$
Pump must never be throttled on suction side.
4. Suction strainers, when used, must have a net “free area” of at least three times the suction pipe area.
5. Separate suction lines are recommended when more than one pump is operating from the same source of supply.
CAUTION
2. Suction piping must slope upwards to pump.
3. All joints must be air tight.
4. A means of priming the pump must be provided, such as a foot valve, except for the self priming pump.
Suction Head/Flooded Suction Conditions
1. An isolation valve should be installed in the suction line at least two pipe diameters from the suction to permit closing of the line for pump inspection and maintenance.
2. Keep suction pipe free from air pockets.
3. Piping should be level or slope gradually downward from the source of supply
4. No portion of the piping should extend below pump suction flnge.
5. The size of entrance from supply should be one or two sizes larger than the suction pipe.
6. The suction pipe must be adequately submerged below the liquid surface to prevent vortices and air entrainment at the supply.
24 3298 Family Rev. 4/07
INCORRECT PIPING
DISCHARGE PIPING
1. Isolation and check valves should be installed in discharge line. Locate the check valve between isolation valve and pump, this will permit inspection of the check valve. The isolation valve is required for priming, regulation of flow, and for inspection and maintenance of pump. The check valve prevents pump or seal damage due to reverse flow through the pump when the driver is turned off.
2. Increasers, if used, should be placed between pump and check valves.
3. Cushioning devices should be used to protect the pump from surges and water hammer, if quick-closing valves are installed in system.
3
FINAL PIPING CHECK
After Connecting Piping to the Pump
CORRECT PIPING
Fig. 29
Rotate shaft by hand to ensure it rotates smoothly
!
and there is no rubbing which could lead to excess heat generation and or sparks.
1. Rotate shaft several times by hand to be sure that there is no binding and all parts are free.
2. Check alignment, per the alignment procedure outlined previously to determine absence of pipe strain. If pipe strain exists, correct piping.
A build up of gases within the pump, sealing system
!
and or process piping system may result in an explosive environment within the pump or process piping system. Ensure process piping system, pump and sealing system are properly vented prior to operation.
Fig. 30
3298 Family Rev. 4/07 25
26 3298 Family Rev. 4/07
OPERATION
PREPARATION FOR START-UP ....................27
Checking Rotation - Frame Mounted ..................27
Couple Pump and Driver .........................27
Install Coupling Guard ..........................27
Checking Rotation - Close Coupled ...................28
Lubricating Bearings ...........................28
Connect Condition Monitoring Devices .................28
Priming Pump ..............................28
STARTING PUMP .............................28
OPERATION ................................29
General Considerations..........................29
Operating at Reduced Capacity .....................29
Suction Valve Closed / Dry Run Operation ...............29
Draining Tanks / Dry Run Operation ..................29
Discharge Valve Closed .........................29
Operating Under Freezing Conditions ..................30
3298 MINIMUM CONTINUOUS RECOMMENDED FLOW .....30
SHUTDOWN ................................31
FINAL ALIGNMENT ...........................31
4
PREPARATION FOR START-UP
When installing in a potentially explosive environ-
!
ment, please ensure that the motor is properly certified.
CHECKING ROTATION ­FRAME MOUNTED
$
Serious damage may result if pump is run in the wrong rotation.
1. Lock out power to driver.
! WARNING
B
s
Lock out driver power to prevent accidental start-up that could result in serious personal injury.
2. Make sure coupling spacer is removed and coupling hubs are fastened tightly to the shafts and are not loose.
NOTE: Pump is shipped with coupling spacer removed.
3. Unlock driver power.
CAUTION
4. Make sure everyone is clear. Jog driver just long enough to determine direction of rotation. Rotation must correspond to arrow on bearing frame.
5. Lock out power to driver.
COUPLE PUMP AND DRIVER
! WARNING
B
s
Lock out driver power to prevent accidental start-up that could result in serious personal injury.
Lubricate coupling per manufacturer’s instructions and install coupling spacer.
INSTALL COUPLING GUARD
Install coupling guard as defined in the appendix.
! WARNING
s
Never operate a pump without a coupling guard properly installed. Operating pump without a properly installed coupling guard can result in serious personal injury.
3298 Family Rev. 4/07 27
CHECKING ROTATION - CLOSE COUPLED
! CAUTION
$
Serious damage may result if pump is run in the wrong rotation.
1. Unlock driver power.
2. Make sure everyone is clear. Jog driver just long enough to determine direction of rotation. Rotation of motor fan must correspond to arrow on close coupled frame.
LUBRICATING BEARINGS
Bearings must be lubricated properly in order to
!
prevent excess heat generation, sparks, and premature failure.
Flood Oil Lubrication - Pumps are shipped without oil. Fill bearing frame with oil through filler connection until oil level reaches center of sight-glass (Fig. 31). A high quality turbine type oil with rust and oxidation inhibitors should be used as specified in Table 6.
Close Coupled Pumps - Pump does not have ball bearings. Consult motor instruction book for required lubrication.
! WARNING
s
Operation of the unit without proper lubrication will cause bearing failure and pump seizure.
STARTING PUMP
1. Make sure suction valve and any recirculation or cooling lines are open.
2. Fully close or partially open discharge valve as dictated by system conditions.
3. Start driver.
Fig. 31
CONNECT CONDITION MONITORING DEVICES
If unit is equipped with power monitoring systems, this must be connected.
PRIMING PUMP
Never start pump until properly primed (pump casing and suction piping are full of liquid). Components such as internal sleeve bearings depend on liquid for lubrication and will quickly fail if run dry.
Your particular system conditions will dictate method used to prime pump.
! CAUTION
$
Continuous operation against closed discharge valve will cause pump to overheat. Overheating the magnetic drive assembly will weaken or ruin the magnets.
! CAUTION
$
Immediately observe pressure gauges. If discharge pressure is not quickly attained, stop driver, reprime and attempt to restart.
4. Slowly open discharge valve until the desired flow is obtained.
Continuous operation against closed discharge valve may vaporize liquid creating an explosive hazard due to confined vapor under high pressure and temperature.
! WARNING
s
28 3298 Family Rev. 4/07
OPERATION
GENERAL CONSIDERATIONS
Always vary capacity with valve in discharge line. NEVER throttle flow from suction side.
Driver may overload or magnets de-couple if pumpage specific gravity (density) is greater than originally assumed, or rated flow rate is exceeded.
Always operate the pump at or near the rated conditions to prevent damage resulting from cavitation or recirculation.
$
Do not operate above rated temperature range of magnets as this will weaken or ruin the magnets.
Service temperature in an ATEX classified environ-
!
ment is limited by Table 1 in the Safety section.
CAUTION
Table 4
Temperature Ratings
Group Size Rated Temperature
XS 1x1.5-5 250° F (121° C)
S All 250° F (121° C)
M All 250° F (121° C)
L All 250° F (121° C)
$
Driver may overload if the pumpage specific gravity (density) is greater than originally assumed, or the rated flow rate is exceeded.
$
Always operate the pump at or near the rated conditions to prevent damage resulting from cavitation or recirculation.
$
Damage occurs from:
1. Increased vibration levels - Affects bearings.
2. Increased radial loads - Stresses on shaft and bearings.
3. Heat build up - Vaporization causing rotating parts to score or seize.
4. Cavitation - Damage to internal surfaces of pump.
Goulds recommends the use of a power monitor to prevent pump damage from systems which have the potential for dry run operation. Refer to Appendix for information on power monitors.
CAUTION
CAUTION
CAUTION
DRAINING TANKS / DRY RUN OPERATION
4
OPERATING AT REDUCED CAPACITY
! WARNING
s
Do NOT operate pump below minimum rated flows or with discharge valve closed. These conditions may vaporize liquid creating an explosive hazard due to confined vapor under high pressure and temperature.
SUCTION VALVE CLOSED / DRY RUN OPERATION
! WARNING
s
Do not operate pump with suction valve closed. Operating pump after suction valve closed will cause wear of thrust and radial bearings and pump failure. Operating pump with suction valve closed may vaporize liquid creating an explosvie hazard due to confined vapor under high pressure and temperature.
$
Always vary capacity with regulating valve in the discharge line. NEVER throttle flow from the suction side.
CAUTION
! WARNING
s
After pump has drained tank, it should be shut down immediately. Operating pump after the tank has been drained of liquid will cause wear of thrust and radial bearings and pump failure. Operating pump after tank has been drained of liquid may vaporize liquid creating an explosive hazard due to confined vapor under high pressure and temperature.
Goulds recommends the use of a power monitor to prevent pump damage from systems which have the potential for dry run operation.
DISCHARGE VALVE CLOSED
! WARNING
s
Do not operate pump with discharge valve closed. Operating pump with a closed discharge valve may vaporize liquid creating an explosive hazard due to confined vapor under high pressure and temperature.
Goulds recommends the use of a power monitor and/or a minimum flow by-pass line to prevent pump damage from systems which have the potential for closed discharge operation.
3298 Family Rev. 4/07 29
OPERATING UNDER FREEZING CONDITIONS
Exposure to freezing conditions, while pump is idle, could cause liquid to freeze and damage the pump. Liquid inside pump should be drained. Liquid inside cooling coils, if supplied, should also be drained.
3298 Minimum Continuous Recommended Flow
Group Pump Size
3298
XS
S
M
L
SP 3298
S
V 3298
S
M
NOTES:
1½x2-6 5 3 1 0.5
1½x3-7 20 10 6521
1½x3-8 30 15 8631
1x2-10 30 53532
1½x3-10 60 30 20 11 5 4
2x3-10 100 50 33 19 10 6 3x4-10G 175 90 60 33 16 11 3x4-10H 90 30 17 3
4x6-10
1x1½-6532210.5
1½x2-6 532210.5
1½x2-10 30 5 3 5 0.7 0.5
Table 5 - Minimum Flow
1
60 Hertz 50 Hertz
GPM m3/hr
3600 1800 1200 3000 1500 1000
1 x 1 - 5 1 0.5 0.2 0.1
1x1-6532210.5 1x1-81584321
2x3-6 30 15 8631
2x3-8 50 95921 3x4-7 80 13 9 18 9 6
(5)
475
2x3-6 30 15 8631
1½2-8 60 30 20 11 7 4 2x3-6 60 30 20 11 7 4
(5)
325
(5)
95
(5)
55
1. All flows are continuous operation 24 hours/day - 7 days/week.
2. Based on water with a specific gravity of 1.0 and specific heat of 1.0
3. Pumps can be operated reliably at lower minimum flows under intermittent operating conditions. Contact Goulds Pumps. Intermittent Operation = operating under these conditions less than 15% of the time.
4. Contact factory for pump efficiency at minimum flows.
5. Can be operated at substantially lower flows with adequate NPSH margin. Contact Goulds for details.
30 3298 Family Rev. 4/07
Loading...
+ 118 hidden pages