Bell & Gossett®ZoneTrol II
Models Z-2, Z-3
McDonnell & Miller ZoneSmart
Models ZS-2, ZS-3
Installation, Operation and Service Instructions
INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.
SAFETY INSTRUCTION
This safety alert symbol will be used in this manual and on the unit safety instructions decal to draw attention to safety related instructions. When used, the safety alert symbol means ATTEN-
TION! BECOME ALERT! YOUR SAFETY IS INVOL VE D! FAILURE TO FOLLOW THE INSTRUCTIONS MAY RESULT IN A SAFETY HAZARD.
DESCRIPTION
The Bell & Gossett ZoneTrol II and McDonnell & Miller Zone­Smart Pump Controllers are designed to control 120 VAC circulating pumps in hydronic systems.
Model Current Zones per Pump
Z-2 / ZS-2
Z-3 / ZS-3 3
15 amps maximum combined load.
T-stat Number of Max. HP
0.085
Max.
2
1/3
FEATURES
• Indicator lights visible without removing cover.
Power LED will illuminate when input power is applied to the controller. Zone LEDs will illuminate when relay is energized.
• PRIORITY: This is typically used in domestic hot water applications where it may be desirable to give hot water production a priority over space heating requirements for a certain period of time. Zone 1 is the priority zone and the functionality is enabled via DIP switch 1. The priority timer is selectable for 30 or 60 minutes, via DIP switch 3.
• PURGE: In normal operation, the last circulator will stop and the boiler will shut down as soon as there is no longer a call for heat. If the purge functionality is enabled via DIP switch 2, the boiler will shut down, but the circulator will continue to run for 90 seconds to extract additional BTUs from the boiler.
• EXERCISE: When the exercise functionality is enabled via DIP switch 4, each circulator will run for 10 seconds after every 72 hours of inactivity. This prevents scale and other deposits from accumulating around the rotating parts and ensures a trouble free start up at the beginning of each heating season.
DIP SWITCH SETTINGS
Switch ON OFF
1 Priority OFF Priority ON 2 Purge On Purge Off 3 Priority 30 minutes Priority 60 minutes 4 Exercise On Exercise Off 5 Not Used Not Used
6 Power Delay On Power Delay Off
MECHANICAL INSTALLATION INSTRUCTIONS
The pump controller should be securely mounted on a wall near the pumps using four #8 screws (not included).
ELECTRICAL INSTALLATION
END SWITCH
X X ZC ZR
ZONE 1
L N
ZONE 2
L N
ZONE 3
L N
R W
Z
ONE 1
R W
Z
ONE 2
R W
Z
ONE 324 VAC
120 VAC
LNG
HN
THERMOSTATS
N
ote: Use these terminals for
3
& 4 wire thermostats
Thermostat(s)
To TT Boiler
Terminals
Factory
Installed
jumper
120 VAC to
Circulator(s)
120 VAC
Input Power
Note: Use these terminals for
3 & 4 wire thermostats
Thermostat(s)
To ZC on boiler aquastat To ZR on boiler aquastat
120 VAC to
Circulator(s)
120 VAC
Input Power
END SWITCH
X X ZC ZR
ZONE 1
L N
ZONE 2
L N
ZONE 3
L N
R W
ZONE 1
R W
ZONE 2
R W
ZONE 324 VAC
120 VAC
LNG
HN
THERMOSTATS
INSTRUCTIONS
WARNING: Electrical Shock Hazard
Electrical connections are to be made by a qualified electrician in accordance with all applicable codes, ordi­nances and good practices. Disconnect and lock out the
ower before making electrical connections. Failure to fol-
p low these instructions could result in serious personal injury and/or death.
1. Dis con nec t the electr ica l supply to the pump before installing the controller.
2. Refer to the applicable wiring diagram
- Figure 1: Cold Start Boiler
- Figure 2: Tankless Coil
3. Verify that the circulator(s) do not exceed the electrical rat­ing of the controller.
4. Make electrical connections according to the applicable wiring diagram. Run the pump power through the holes in the controller chassis to the applicable L/N terminals. Keep
GENERAL WIRING DIAGRAM
120 VAC and 24 VAC wiring separate. All 120 VAC wiring shou ld be 14 AWG (m inimum) coppe r elect rical wire. Perform all wiring in accordance with applicable codes.
5. If the priority function is to be enabled, the priority zone (e.g., Domestic Hot Water) pump should be wired to the Zone 1 L/N terminals.
6. Run the thermostat wires through the grommet(s) in the controller chassis and connect to the appropriate R/W ter­minals. If the priority function is to be enabled, the priority zone (e.g., Domestic Hot Water) T-Stat should be wired to the Zone 1 R/W terminals. Keep 24 VAC wiring separate from 120 VAC wiring.
NOTE: During the initial power-up of the zone controller, some “power stealing” thermostats may require up to 3 minutes to function properly. If the installation requires the pump relays and X-X relay to be held open during this power-up sequence, the installer can position DIP switch 6 to the “
ON” position
. This will cause the controller to suspend relay operation during the thermostat power-up period. Normal operation and cycling of the heating system will resume after the 3 minute time period. This affects ini­tial power-up only and does not impact normal system operation.
© COPYRIGHT 2008 BY ITT CORPORATION PRINTED IN U.S.A. 8-08
THE ITT ENGINEERED BLOCKS SYMBOL AND ENGINEERED FOR LIFE ARE REGISTERED TRADEMARKS OF ITT CORPORATION
ITT
8200 N. Austin Avenue Morton Grove, IL 60053 Phone: (847) 966-3700 Fax: (847) 966-9052 www.bellgossett.com www.mcdonnellmiller.com
Figure 1: Cold Start Boiler
When a thermostat calls for heat,
the corresponding circulator will
start and the XX end switch will
close to enable the boiler.
Figure 2: Tankless Coil
(Remove ZC/ZR Jumper)
When a thermostat calls for heat,
the corresponding circulator will
start when the boiler temperature
reaches the low limit setting.
WARNING: Electrical Shock Hazard
When wiring per the Tankless Coil Application, pump controller and boiler aquastat must be on the same circuit and have a common disconnect. Failure to follow these instructions may introduce a secondary source of power resulting in personal injury or death.
Loading...