iTrust UH11-0060, UH11-0060L, UH11-0100, UH11-0100L User Manual

iTrust Online UPS
UH11 Series-6kVA/10kVA
User Manual
E1-20010916-C-1.0
Avansys Power Co., Ltd.
iTrust Intelligent High Frequency Online UPS
UH11 Series-6kVA/10kVA
31010810BOM:
StandardPublication State:
E1-20010916-C-1.0Manual Ver.:
Avansys Power Co., Ltd.. provides customer with satisfactory
technical support. To obtain support, please contact the distributor in
the first instance. When failing to reach the distributor, please contact
your local technical support center or the company headquarters.
Avansys Power Co., Ltd..
Address: Huawei Manufacturing Center, Banxuegang Industrial Base, Longgang District, Shenzhen 518129, PRC
Homepage
http://www.avansys.com
E-mail
info@huawei.com
Copyright Information
Copyright by Avansys Power Co., Ltd. All rights reserved. The information in this document is subject to change without notice. No part of this document may in any form or by any means (electronic, mechanical, micro-copying, photocopying, recording or otherwise) be reproduced, stored in a retrieval system or transmitted without prior written permission from Avansys Power Co., Ltd..
Copyright by Avansys Power Co.,Ltd.. All rights reserved. The information in this document is subject to change without notice. No part of this document may in any form or by any means (electronic, mechanical, micro-copying, photocopying, recording or otherwise) be reproduced, stored in a retrieval system or transmitted without prior written permission from Avansys Power Co.,Ltd.
Publication Statement
Thank you for using iTrust series UPS by Avansys Power Co., Ltd. UH11 series is the latest single-phase input single-phase output intelligent online UPS developed by Avansys incorporating years of experience in power supply development. As a world-leading standard UPS product, this series delivers excellent electrical performance, is fully compliant with safety regulations and EMC standards, features perfect intelligent monitoring and network management, and is well-shaped with beautiful appearance.
Please read this manual carefully prior to installation and operation
Readers
This manual is intended for equipment operator and technical support personnel.
Conventions
Symbol
Notice
This symbol is used in this manual to alert you to
important information.
Safety Guidelines
. Prohibitions
1. As high voltage exists within UPS, no one but Avansys technician and Avansys-authorized technician should open the panel and the chassis cover. Otherwise, one may get electric shock and such situation is not covered under warranty.
2 2. When the UPS is purchased to supply the equipment listed below, please consult the distributor in advance on the UPS application, setting, management and maintenance, which need special consideration and design.
Life support medical apparatus;
Facilities such as lift which may endanger human life;
Mission-critical equipment like above.
3. Never dispose of battery in a fire, as battery may explode when exposed to flame.
. Matters needing attention
1. The UPS contains its own energy source-battery, the UPS output may carry live voltage even when the UPS is not connected to an AC supply.
2. To move or re-wire the UPS, please disconnect the input and make sure that the UPS is completely shut down. Otherwise, live voltage still exists at the output terminal, which may cause electric shock.
3. To ensure human safety, the UPS must be reliably grounded before use.
4. The operating environment and storage method will affect the lifetime and reliability of the UPS. Please don’t use the UPS long in the following environments
Place with temperature and relative humidity outside
specifications (temperature: 0
to 40 , relative humidity: 5% to
95%);
Place with direct sunlight or near heat source;
Place with vibration or shock;
Place with dust, corrosive material, salt or flammable gas.
5. Please keep the air inlet and outlet unblocked. Poor ventilation will increase the internal temperature, which will shorten the lifetime of the UPS components, hence that of the UPS.
6. Liquid and other irrelevant substances are strictly prohibited inside the UPS chassis.
7. In case of fire, please use dry-chemical fire extinguisher. Using foam fire extinguisher may cause electric shock.
8. High ambient temperature shortens battery lifetime, so battery should be replaced regularly to ensure normal UPS operation and adequate backup time. Battery replacement must be conducted by authorized technician.
9. If the UPS will not be used for long, it should be placed in dry
environment. Storage temperature of standard UPS (with battery):
20
+55 , storage temperature of long backup time UPS
(without battery): –40
+70 .
1
0. During the period the UPS is left unused, it is recommended
to supply the UPS with AC mains for more than 12 hours every 3 months, so that the battery will not be damaged due to long time of not-in-use.
11. Please don’t open or damage the battery, as the electrolyte is harmful to skin and eye. If tainted with electrolyte, wash it off immediately with plenty of water and go to hospital for a check.
Contents
243.1.2 Bypass Mode
---------------------------------
23
3.1.1 Normal Mode
----------------------------------
23
3.1 Operation Mode
------------------------------------
23
Chapter 3 Operation -------------------------------------
20
2.3 Wiring of Master/Slave Hot Standby System
---------------
15
2.2.2 Installing the UPS
------------------------------
13
2.2.1 Matters Needing Attention
------------------------
13
2.2 Installation
----------------------------------------
13
2.1 Unpacking Inspection
--------------------------------
13
Chapter 2 Installation ------------------------------------
11
1.5.3 Rear Panel
-----------------------------------
5
1.5.2 LCD Panel
-------------------------------------
4
1.5.1 Appearance
------------------------------------
4
1.5 Appearance and Panels
-------------------------------
3
1.4 Features
-------------------------------------------
2
1.3 Schematic Diagram
-----------------------------------
1
1.2 Model
---------------------------------------------
1
1.1 Application
-----------------------------------------
1
Chapter 1 Product Introduction -----------------------------
39
II. Battery Maintenance
----------------------------------
39
I. Fan
-----------------------------------------------
39
Chapter 4 Maintenance ----------------------------------
35
3.5 LCD Menu Operation
--------------------------------
35
3.4 UPS Monitoring
-------------------------------------
34
3.3.4 Output Short-circuit Protection
---------------------
34
3.3.3 Transfer to Bypass Mode in the Event of Overtemperature
------------------------------------
34
3.3.2 Transfer to Battery Mode in the Event of Mains Failure
-------------------------------------------
33
3.3.1 Transfer to Bypass Mode in the Event of Overload
------------------------------------------
33
3.3 Auto Transfer Between UPS Operation Modes
-------------
33
3.2.6 System Power-off
------------------------------
32
3.2.5 Turn off Inverter
--------------------------------
31
3.2.4 Manual Battery Test
----------------------------
28
3.2.3 Start Inverter Output
----------------------------
27
3.2.2 System Parameter Setting
------------------------
26
3.2.1 System Power-on
------------------------------
26
3.2 Operation
-----------------------------------------
25
3.1.4 Fault Mode
-----------------------------------
24
3.1.3 Battery Mode
----------------------------------
58
Appendix 4 Optional Component --------------------------
55
Appendix 3 Technical Specifications -----------------------
51
Appendix 2 Grounding & Lightning Protection ----------------
50
Dry Contact Communication Mode
--------------------------
49
RS-232 Communication Mode
-----------------------------
49
Appendix 1 Communication Port ---------------------------
47
Chapter 6 Service and Support ----------------------------
43
Chapter 5 Troubleshooting --------------------------------
41
V. Function Inspection
-----------------------------------
40
IV. UPS State Check
------------------------------------
40
III. Keep Air Vent Unblocked
------------------------------
Chapter 1 Product Introduction
1.1 Application
iTrust series UPS provides reliable and high quality AC power to your sophisticated equipment. It is applicable to supply AC power to computer center, network management center, communication system, auto control system, and precision instrument, etc.
1.2 Model
iTrust series UPS has among others 6kVA and 10kVA UPS products available, as listed below:
Long backup
time UPS, with
external
battery
Standard UPS,
with internal
battery
Long backup
time UPS, with
external
battery
Standard UPS,
with internal
battery
Explanation
UH11-0100LUH11-0100UH11-0060LUH11-0060Model
10kVA 6kVACapacity
Chapter 1 Product Introduction 1
E1--20010916-C-1.0
1.3 Schematic Diagram
The UPS supports single-unit operation, and master/slave hot standby operation as well for the purpose of increasing system reliability.
Rectifier
Inverter
AC mains
Mains switch
Load
Bypass
Bypass switch
Maintenance bypass
Electronic
transfer
switch
Charger
Hot standby
shorting
stub
Fig. 1-1 Single-unit System
Rectifier
Inverter
AC mains
Mains switch
Load
Bypass
Bypass switch
Maintenance bypass
Maintenance
switch
Electronic
transfer
switch
Charger
Slave
Master UPS
Fig. 1-2 Master/Slave Hot Standby System
2 Chapter 1 Product Introduction
E1-20010916-C-1.0
1.4 Features
iTrust series 6kVA/10kVA is an intelligent online UPS system with sine wave output newly developed by Avansys Power Co., Ltd.
The system adopts high-frequency double conversion topology structure with high input power factor, wide input voltage range, and output immune from interference, hence the product is suitable for areas with unstable mains supply;
It adopts advanced full digital control technology based on DSP to achieve high system reliability, features self-protection and fault diagnosis;
It features excellent intelligent battery management, extending battery life;
The panel operation interface adopts LCD and LED displays, facilitating user to learn about the system operation state and operating parameters (for instance: input/output voltage and frequency, load, battery capacity, internal temperature, etc.);
With Avansys monitoring software, flexible network management of UPS can be achieved;
The system has maintenance bypass switch, which enables online maintenance, ensuring no interruption in power to load during maintenance;
The system design features drawer-type battery installation, enabling easy and quick maintenance and replacement.
Chapter 1 Product Introduction 3
E1--20010916-C-1.0
1.5 Appearance and Panels
1.5.1 Appearance
LCD panel
LCD panel
Air inlet
Air inlet
wheel
wheel
Adjustable foot
Adjustable foot
Rear handle
Rear handle
Retractable supporting rack
6kVA UPS 10kVA UPS
Fig. 1-3 System Appearance
Notice:
1. The rear handle is only used to push or pull the UPS, it can not be used to lift it. Lifting the UPS by the handle will damage the UPS;
2. There are 2 retractable supporting racks at the bottom of the 10kVA UPS chassis, which are used to place the UPS securely when necessary.
4 Chapter 1 Product Introduction
E1-20010916-C-1.0
1.5.2 LCD Panel
The LCD panel consists of LCD, LED and buttons, as shown in Fig. 1-4, for the display and control of operating parameters, alarm information and function settings.
OFFbutton
Mains indicator
ON/SILENCEbutton
Fault indicator
ENTERbutton
Bypass indicator
CIRCLE
button
Battery indicator
LCD screen
Inverter indicator
Fig. 1-4 LCD Panel Components
I. Composition of LCD panel
This panel includes a group of LED indicators, a LCD screen, and 4 buttons.
1. The LED indicators include 4 green lights and 1 red light.
2. The LCD screen can display maximally 2 lines of information in Chinese or 4 lines of information in English.
3. The 4 buttons are ON/SILENCE button, OFF button, CIRCLE button, and ENTER button.
Chapter 1 Product Introduction 5
E1--20010916-C-1.0
II. LED display
1) Fault indicator (red): shines in the event of fault, and goes off
otherwise.
2) Mains indicator (green): shines when the mains is normal, goes off
in the event of mains failure, and flashes when the mains voltage is outside tolerances.
3) Inverter indicator (green): shines when the inverter is supplying
power, and goes off otherwise.
4) Bypass indicator (green): shines when the bypass is supplying
power, and goes off otherwise.
5) Battery indicator (green): shines when the battery is supplying
power, and goes off otherwise,
III. LCD display
1) Operating parameters
Input voltage, input frequency, output voltage, output frequency, output current, load, internal temperature, battery residual capacity/in charge state/full charged, battery voltage/charging voltage.
2) Alarm information (listed by order of priority from high to low)
UPS shutdown, auxiliary supply fault, output short-circuit, inverter fault, rectifier fault, internal overtemperature, overload, charger fault, battery fault, UPS shutdown imminent due to low battery, output fault.
3) Function setup
6 Chapter 1 Product Introduction
E1-20010916-C-1.0
Including setup of Chinese/English menu, equalize charge function, temperature compensation, battery capacity, master/slave/single-unit, alternate operation period.
Chinese/English menu setup: (factory default: Chinese
CHINESE
ENGLISH
CANCEL SET
Equalize charge setup: (factory default: enable)
ENABLE DISABLE
CANCEL SET
Temperature compensation setup: (factory default: enable)
ENABLE DISABLE
CANCEL SET
Battery capacity setup: the battery capacity shows the total
battery capacity of the UPS, options include: (factory default:
7Ah
6kVA /14Ah 10kVA )
7Ah
14Ah 24Ah
28Ah 38Ah
42Ah
48Ah
56Ah
65Ah76Ah84Ah
100Ah130Ah
200Ah
CANCEL SET
Master/slave/single-unit setting: (factory default: single)
Chapter 1 Product Introduction 7
E1--20010916-C-1.0
MASTER
SLAVE
SINGLE
CANCEL SET
Setup of alternate operation period is allowed only in the master UPS, specifying the master/slave alternate operation period;
(factory default: 7 days)
7 DAYS
30 DAYS 90 DAYS
180 DAYS
CANCEL
SET
IV. Buttons
For entering into menu, confirming parameter selection and returning to upper-level menu.
ENTER button
For shifting between menu items of the same level and selecting parameters, i.e., crosswise circling.
CIRCLE button
When the UPS is supplying power through inverter, pressing and holding this button for 1 second can stop the inverter output (i.e., turn off the inverter).
OFF button
When the UPS is supplying power through bypass, pressing and holding this button for 1 second can start the inverter output (i.e., turn on the inverter); when the UPS is supplying power through inverter, which obtains power from rectifier, pressing and holding this button for 4 seconds can perform manual battery test; when the UPS is giving audible alarm, pressing this button can silence the alarm sound.
ON/SILENCE button
UsageButton
8 Chapter 1 Product Introduction
E1-20010916-C-1.0
V. UPS English menu
Internal overtemperatureTEMP OVER
Charger faultCHARGER FAIL
Battery faultBATTERY FAIL
Output short-circuitOUTPUT SHORT
overloadOVERLOAD
UPS shutdown imminent due to low
battery
BATTERY LOW TO BE
SHUTDOWN
Alarm informationWARNING INFO
Return back to the main menuBACK TO MAIN MENU
Internal temperatureUPS TEMP
loadLOAD STATUS
Battery residual capacityBATTERY STATUS
Battery full chargedFULL CHARGED
In charge stateCHARGING
Charging voltageCHARGER VOLT
Battery voltageBATTERY VOLT
Mains frequencyLINE FREQ
Mains voltageLINE VOLT
Output frequencyOUTPUT FREQ
Output currentOUTPUT CURRENT
Output voltageOUTPUT VOLT
Operating parametersOPERATION STATUS
Meaning
English menu
Chapter 1 Product Introduction 9
E1--20010916-C-1.0