iTrust UH11-0060, UH11-0060L, UH11-0100, UH11-0100L User Manual

iTrust Online UPS
UH11 Series-6kVA/10kVA
User Manual
E1-20010916-C-1.0
Avansys Power Co., Ltd.
iTrust Intelligent High Frequency Online UPS
UH11 Series-6kVA/10kVA
31010810BOM:
StandardPublication State:
E1-20010916-C-1.0Manual Ver.:
Avansys Power Co., Ltd.. provides customer with satisfactory
technical support. To obtain support, please contact the distributor in
the first instance. When failing to reach the distributor, please contact
your local technical support center or the company headquarters.
Avansys Power Co., Ltd..
Address: Huawei Manufacturing Center, Banxuegang Industrial Base, Longgang District, Shenzhen 518129, PRC
Homepage
http://www.avansys.com
E-mail
info@huawei.com
Copyright Information
Copyright by Avansys Power Co., Ltd. All rights reserved. The information in this document is subject to change without notice. No part of this document may in any form or by any means (electronic, mechanical, micro-copying, photocopying, recording or otherwise) be reproduced, stored in a retrieval system or transmitted without prior written permission from Avansys Power Co., Ltd..
Copyright by Avansys Power Co.,Ltd.. All rights reserved. The information in this document is subject to change without notice. No part of this document may in any form or by any means (electronic, mechanical, micro-copying, photocopying, recording or otherwise) be reproduced, stored in a retrieval system or transmitted without prior written permission from Avansys Power Co.,Ltd.
Publication Statement
Thank you for using iTrust series UPS by Avansys Power Co., Ltd. UH11 series is the latest single-phase input single-phase output intelligent online UPS developed by Avansys incorporating years of experience in power supply development. As a world-leading standard UPS product, this series delivers excellent electrical performance, is fully compliant with safety regulations and EMC standards, features perfect intelligent monitoring and network management, and is well-shaped with beautiful appearance.
Please read this manual carefully prior to installation and operation
Readers
This manual is intended for equipment operator and technical support personnel.
Conventions
Symbol
Notice
This symbol is used in this manual to alert you to
important information.
Safety Guidelines
. Prohibitions
1. As high voltage exists within UPS, no one but Avansys technician and Avansys-authorized technician should open the panel and the chassis cover. Otherwise, one may get electric shock and such situation is not covered under warranty.
2 2. When the UPS is purchased to supply the equipment listed below, please consult the distributor in advance on the UPS application, setting, management and maintenance, which need special consideration and design.
Life support medical apparatus;
Facilities such as lift which may endanger human life;
Mission-critical equipment like above.
3. Never dispose of battery in a fire, as battery may explode when exposed to flame.
. Matters needing attention
1. The UPS contains its own energy source-battery, the UPS output may carry live voltage even when the UPS is not connected to an AC supply.
2. To move or re-wire the UPS, please disconnect the input and make sure that the UPS is completely shut down. Otherwise, live voltage still exists at the output terminal, which may cause electric shock.
3. To ensure human safety, the UPS must be reliably grounded before use.
4. The operating environment and storage method will affect the lifetime and reliability of the UPS. Please don’t use the UPS long in the following environments
Place with temperature and relative humidity outside
specifications (temperature: 0
to 40 , relative humidity: 5% to
95%);
Place with direct sunlight or near heat source;
Place with vibration or shock;
Place with dust, corrosive material, salt or flammable gas.
5. Please keep the air inlet and outlet unblocked. Poor ventilation will increase the internal temperature, which will shorten the lifetime of the UPS components, hence that of the UPS.
6. Liquid and other irrelevant substances are strictly prohibited inside the UPS chassis.
7. In case of fire, please use dry-chemical fire extinguisher. Using foam fire extinguisher may cause electric shock.
8. High ambient temperature shortens battery lifetime, so battery should be replaced regularly to ensure normal UPS operation and adequate backup time. Battery replacement must be conducted by authorized technician.
9. If the UPS will not be used for long, it should be placed in dry
environment. Storage temperature of standard UPS (with battery):
20
+55 , storage temperature of long backup time UPS
(without battery): –40
+70 .
1
0. During the period the UPS is left unused, it is recommended
to supply the UPS with AC mains for more than 12 hours every 3 months, so that the battery will not be damaged due to long time of not-in-use.
11. Please don’t open or damage the battery, as the electrolyte is harmful to skin and eye. If tainted with electrolyte, wash it off immediately with plenty of water and go to hospital for a check.
Contents
243.1.2 Bypass Mode
---------------------------------
23
3.1.1 Normal Mode
----------------------------------
23
3.1 Operation Mode
------------------------------------
23
Chapter 3 Operation -------------------------------------
20
2.3 Wiring of Master/Slave Hot Standby System
---------------
15
2.2.2 Installing the UPS
------------------------------
13
2.2.1 Matters Needing Attention
------------------------
13
2.2 Installation
----------------------------------------
13
2.1 Unpacking Inspection
--------------------------------
13
Chapter 2 Installation ------------------------------------
11
1.5.3 Rear Panel
-----------------------------------
5
1.5.2 LCD Panel
-------------------------------------
4
1.5.1 Appearance
------------------------------------
4
1.5 Appearance and Panels
-------------------------------
3
1.4 Features
-------------------------------------------
2
1.3 Schematic Diagram
-----------------------------------
1
1.2 Model
---------------------------------------------
1
1.1 Application
-----------------------------------------
1
Chapter 1 Product Introduction -----------------------------
39
II. Battery Maintenance
----------------------------------
39
I. Fan
-----------------------------------------------
39
Chapter 4 Maintenance ----------------------------------
35
3.5 LCD Menu Operation
--------------------------------
35
3.4 UPS Monitoring
-------------------------------------
34
3.3.4 Output Short-circuit Protection
---------------------
34
3.3.3 Transfer to Bypass Mode in the Event of Overtemperature
------------------------------------
34
3.3.2 Transfer to Battery Mode in the Event of Mains Failure
-------------------------------------------
33
3.3.1 Transfer to Bypass Mode in the Event of Overload
------------------------------------------
33
3.3 Auto Transfer Between UPS Operation Modes
-------------
33
3.2.6 System Power-off
------------------------------
32
3.2.5 Turn off Inverter
--------------------------------
31
3.2.4 Manual Battery Test
----------------------------
28
3.2.3 Start Inverter Output
----------------------------
27
3.2.2 System Parameter Setting
------------------------
26
3.2.1 System Power-on
------------------------------
26
3.2 Operation
-----------------------------------------
25
3.1.4 Fault Mode
-----------------------------------
24
3.1.3 Battery Mode
----------------------------------
58
Appendix 4 Optional Component --------------------------
55
Appendix 3 Technical Specifications -----------------------
51
Appendix 2 Grounding & Lightning Protection ----------------
50
Dry Contact Communication Mode
--------------------------
49
RS-232 Communication Mode
-----------------------------
49
Appendix 1 Communication Port ---------------------------
47
Chapter 6 Service and Support ----------------------------
43
Chapter 5 Troubleshooting --------------------------------
41
V. Function Inspection
-----------------------------------
40
IV. UPS State Check
------------------------------------
40
III. Keep Air Vent Unblocked
------------------------------
Chapter 1 Product Introduction
1.1 Application
iTrust series UPS provides reliable and high quality AC power to your sophisticated equipment. It is applicable to supply AC power to computer center, network management center, communication system, auto control system, and precision instrument, etc.
1.2 Model
iTrust series UPS has among others 6kVA and 10kVA UPS products available, as listed below:
Long backup
time UPS, with
external
battery
Standard UPS,
with internal
battery
Long backup
time UPS, with
external
battery
Standard UPS,
with internal
battery
Explanation
UH11-0100LUH11-0100UH11-0060LUH11-0060Model
10kVA 6kVACapacity
Chapter 1 Product Introduction 1
E1--20010916-C-1.0
1.3 Schematic Diagram
The UPS supports single-unit operation, and master/slave hot standby operation as well for the purpose of increasing system reliability.
Rectifier
Inverter
AC mains
Mains switch
Load
Bypass
Bypass switch
Maintenance bypass
Electronic
transfer
switch
Charger
Hot standby
shorting
stub
Fig. 1-1 Single-unit System
Rectifier
Inverter
AC mains
Mains switch
Load
Bypass
Bypass switch
Maintenance bypass
Maintenance
switch
Electronic
transfer
switch
Charger
Slave
Master UPS
Fig. 1-2 Master/Slave Hot Standby System
2 Chapter 1 Product Introduction
E1-20010916-C-1.0
1.4 Features
iTrust series 6kVA/10kVA is an intelligent online UPS system with sine wave output newly developed by Avansys Power Co., Ltd.
The system adopts high-frequency double conversion topology structure with high input power factor, wide input voltage range, and output immune from interference, hence the product is suitable for areas with unstable mains supply;
It adopts advanced full digital control technology based on DSP to achieve high system reliability, features self-protection and fault diagnosis;
It features excellent intelligent battery management, extending battery life;
The panel operation interface adopts LCD and LED displays, facilitating user to learn about the system operation state and operating parameters (for instance: input/output voltage and frequency, load, battery capacity, internal temperature, etc.);
With Avansys monitoring software, flexible network management of UPS can be achieved;
The system has maintenance bypass switch, which enables online maintenance, ensuring no interruption in power to load during maintenance;
The system design features drawer-type battery installation, enabling easy and quick maintenance and replacement.
Chapter 1 Product Introduction 3
E1--20010916-C-1.0
1.5 Appearance and Panels
1.5.1 Appearance
LCD panel
LCD panel
Air inlet
Air inlet
wheel
wheel
Adjustable foot
Adjustable foot
Rear handle
Rear handle
Retractable supporting rack
6kVA UPS 10kVA UPS
Fig. 1-3 System Appearance
Notice:
1. The rear handle is only used to push or pull the UPS, it can not be used to lift it. Lifting the UPS by the handle will damage the UPS;
2. There are 2 retractable supporting racks at the bottom of the 10kVA UPS chassis, which are used to place the UPS securely when necessary.
4 Chapter 1 Product Introduction
E1-20010916-C-1.0
1.5.2 LCD Panel
The LCD panel consists of LCD, LED and buttons, as shown in Fig. 1-4, for the display and control of operating parameters, alarm information and function settings.
OFFbutton
Mains indicator
ON/SILENCEbutton
Fault indicator
ENTERbutton
Bypass indicator
CIRCLE
button
Battery indicator
LCD screen
Inverter indicator
Fig. 1-4 LCD Panel Components
I. Composition of LCD panel
This panel includes a group of LED indicators, a LCD screen, and 4 buttons.
1. The LED indicators include 4 green lights and 1 red light.
2. The LCD screen can display maximally 2 lines of information in Chinese or 4 lines of information in English.
3. The 4 buttons are ON/SILENCE button, OFF button, CIRCLE button, and ENTER button.
Chapter 1 Product Introduction 5
E1--20010916-C-1.0
II. LED display
1) Fault indicator (red): shines in the event of fault, and goes off
otherwise.
2) Mains indicator (green): shines when the mains is normal, goes off
in the event of mains failure, and flashes when the mains voltage is outside tolerances.
3) Inverter indicator (green): shines when the inverter is supplying
power, and goes off otherwise.
4) Bypass indicator (green): shines when the bypass is supplying
power, and goes off otherwise.
5) Battery indicator (green): shines when the battery is supplying
power, and goes off otherwise,
III. LCD display
1) Operating parameters
Input voltage, input frequency, output voltage, output frequency, output current, load, internal temperature, battery residual capacity/in charge state/full charged, battery voltage/charging voltage.
2) Alarm information (listed by order of priority from high to low)
UPS shutdown, auxiliary supply fault, output short-circuit, inverter fault, rectifier fault, internal overtemperature, overload, charger fault, battery fault, UPS shutdown imminent due to low battery, output fault.
3) Function setup
6 Chapter 1 Product Introduction
E1-20010916-C-1.0
Including setup of Chinese/English menu, equalize charge function, temperature compensation, battery capacity, master/slave/single-unit, alternate operation period.
Chinese/English menu setup: (factory default: Chinese
CHINESE
ENGLISH
CANCEL SET
Equalize charge setup: (factory default: enable)
ENABLE DISABLE
CANCEL SET
Temperature compensation setup: (factory default: enable)
ENABLE DISABLE
CANCEL SET
Battery capacity setup: the battery capacity shows the total
battery capacity of the UPS, options include: (factory default:
7Ah
6kVA /14Ah 10kVA )
7Ah
14Ah 24Ah
28Ah 38Ah
42Ah
48Ah
56Ah
65Ah76Ah84Ah
100Ah130Ah
200Ah
CANCEL SET
Master/slave/single-unit setting: (factory default: single)
Chapter 1 Product Introduction 7
E1--20010916-C-1.0
MASTER
SLAVE
SINGLE
CANCEL SET
Setup of alternate operation period is allowed only in the master UPS, specifying the master/slave alternate operation period;
(factory default: 7 days)
7 DAYS
30 DAYS 90 DAYS
180 DAYS
CANCEL
SET
IV. Buttons
For entering into menu, confirming parameter selection and returning to upper-level menu.
ENTER button
For shifting between menu items of the same level and selecting parameters, i.e., crosswise circling.
CIRCLE button
When the UPS is supplying power through inverter, pressing and holding this button for 1 second can stop the inverter output (i.e., turn off the inverter).
OFF button
When the UPS is supplying power through bypass, pressing and holding this button for 1 second can start the inverter output (i.e., turn on the inverter); when the UPS is supplying power through inverter, which obtains power from rectifier, pressing and holding this button for 4 seconds can perform manual battery test; when the UPS is giving audible alarm, pressing this button can silence the alarm sound.
ON/SILENCE button
UsageButton
8 Chapter 1 Product Introduction
E1-20010916-C-1.0
V. UPS English menu
Internal overtemperatureTEMP OVER
Charger faultCHARGER FAIL
Battery faultBATTERY FAIL
Output short-circuitOUTPUT SHORT
overloadOVERLOAD
UPS shutdown imminent due to low
battery
BATTERY LOW TO BE
SHUTDOWN
Alarm informationWARNING INFO
Return back to the main menuBACK TO MAIN MENU
Internal temperatureUPS TEMP
loadLOAD STATUS
Battery residual capacityBATTERY STATUS
Battery full chargedFULL CHARGED
In charge stateCHARGING
Charging voltageCHARGER VOLT
Battery voltageBATTERY VOLT
Mains frequencyLINE FREQ
Mains voltageLINE VOLT
Output frequencyOUTPUT FREQ
Output currentOUTPUT CURRENT
Output voltageOUTPUT VOLT
Operating parametersOPERATION STATUS
Meaning
English menu
Chapter 1 Product Introduction 9
E1--20010916-C-1.0
Chinese CHINESE
English ENGLISH
Single-unit systemSINGLE
Slave UPSSLAVE
Master UPSMASTER
CancelCANCEL
Disable DISABLE
Enable ENABLE
Master/slave alternate operation timeM/S ALTERNATING WORK TIME
Master/slave setupM/S SET
Battery capacity setupBATT CAP SET
Enable or disable temperature
compensation
TEMP COMP SET
Enable or disable equalize chargingEQUALIZATION CHARGE SET
Language selectionLANGUAGE SET
Function setupFUNCTION SETUP
The alarm has been removed, return
back to the main menu
NO WARNING BACK TO MAIN
Under self-testSELF-TESTING
UPS shutdownUPS SHUTDOWN
Auxiliary supply failAUX SUPPLY FAIL
Rectifier faultRECTIFIER FAIL
Inverter faultINVERTER FAIL
Inverter static switch shortcircuitOUTPUT FAIL
Meaning
English menu
10 Chapter 1 Product Introduction
E1-20010916-C-1.0
1.5.3 Rear Panel
RS-232 DRY CONTACT
INTELLIGENT SLOT
INPUT BREAKERBYPASS BREAKER
MAINTAIN SWITCH
DRY CONTACTRS-232
INTELLIGENT SLOT
BYPASS BREAKERINPUT BREAKER
MAINTAIN SWITCH
Mains switch
Bypass switch
Air vent
Maintenance switch cover
RS-232 comm port
Dry contact port
SNMP adaptor slot
Terminal block cover
Bypass switch
Input/output terminel block
Mains switch
Maintenance switch
6kVA UPS 10kVA UPS
Fig. 1-4 Rear Panel Components
Usage of rear panel components:
For connecting UPS input/output, and external battery of long backup time UPS.
Input/output terminal block
Used to control the input power of the UPS bypass. 6kVA UPS adopts 40A/250V AC circuit breaker; 10kVA UPS adopts 80A/250V AC circuit breaker.
Bypass switch
Used to control the UPS mains input. 6kVA UPS adopts 63A/250V AC circuit breaker; 10kVA UPS adopts 80A/250V AC circuit breaker.
Mains switch
Chapter 1 Product Introduction 11
E1--20010916-C-1.0
For UPS heat dissipation.Air outlet
To prevent electric shock resulting from wiring terminal being exposed.
Terminal block cover
With the optocoupler dry contact port and monitoring software, the UPS can be monitored and controlled.
Dry contact port
With the standard RS-232 port and monitoring software (delivered with the UPS), the UPS can be monitored and controlled.
RS-232 port
Used to install SNMP adaptor (optional component), through which the UPS can be directly connected into network to achieve UPS monitoring.
SNMP adaptor slot
To ensure uninterrupted power supply to load during online maintenance.
Nonprofessional service personnel is
not allowed to use this switch at will.
Maintenance switch
12 Chapter 1 Product Introduction
E1-20010916-C-1.0
Chapter 2 Installation
2.1 Unpacking Inspection
1. Open the packing box and take out the UPS, be careful not to drop it as it is heavy.
2. Check whether the UPS has been damaged in transport. In the event of any damage to the UPS, please notify the distributor for a check and don’t turn it on.
3. Check the accessories against the delivery accessory list, please contact the distributor if any accessory is missing.
2.2 Installation
2.2.1 Matters Needing Attention
1. Please place the UPS on the even ground near load.
2. The distance from the rear and side panels of the UPS to the wall or other equipment should be greater than 20cm, and the air inlets on the front panel and at the bottom of the UPS should be kept unblocked, so as to facilitate ventilation and heat dissipation. Otherwise, the UPS internal temperature will rise, which will shorten UPS lifetime.
3. Install the UPS in environment with good ventilation, avoid installing it in environment with excessive temperature or humidity, keep the UPS away from water, flammable, explosive substances, corrosive materials, heat source and direct sunlight, and better keep the air inlet/outlet free of dust.
Chapter 2 Installation 13
E1-20010916-C-1.0
4. Install the UPS in environment free of dust, volatile gas, salt, and corrosive materials.
5. Don’t install it in open area.
6. Double-pole linkage circuit breaker with capacity greater than 63A (6kVA UPS) or 80A (10kVA UPS) should be installed on the input neutral line and live line, so that the input power can be quickly cut off in case of emergency.
7. To prevent UPS from moving during operation, see to it that the adjustable feet have been screwed down to place the UPS securely on the ground prior to use.
8. The UPS is suitable for resistive-capacitive load (like computer), resistive load and micro-inductive load; it is not suitable for purely inductive load and purely capacitive load (like motor, air-conditioner and duplicator); it can not assume half-wave rectifier load.
9. To ensure the safety of the UPS and user equipment, please adopt correct power distribution:
Input live
line
Input
neutral line
Output
neutral line
U P S
Load
N
E
Double-pole
linkage circuit
breaker
L
Output live
line
Fig. 2-1 a Correct Distribution
14 Chapter 2 Installation
E1-20010916-C-1.0
Input live
line
Input
neutral line
U P S
Load
N/E
L
Output live
line
Output
neutral line
Fig. 2-1
b Wrong Distribution
2.2.2 Installing the UPS
I. Connect external battery of long backup time UPS
This step is saved for standard UPS.
1. Be sure that the cell number is in compliance with the UPS specifications (twenty 12V cells in series). After connecting the cells in series, use a voltmeter to confirm that the battery voltage is about 240Vdc;
Notice:
Battery cells by different manufacturer, of different model or use state can not be combined together.
2. Make sure that the battery switch is placed to OFF;
3. Remove the terminal block cover, use a voltmeter to confirm that the battery wiring terminals on the UPS input/output terminal block have no DC voltage;
4. As shown in Fig. 2-2, respectively connect the positive pole (red) and negative pole (black) of the battery to the battery wiring
Chapter 2 Installation 15
E1-20010916-C-1.0
terminals “+” and “-” on the UPS input/output terminal block, and fasten the fixing screws. Be careful not to reversely connect the positive and negative poles of the battery. The length of the connection cables between the battery and the UPS should be as short as possible.
Battery (+)
Battery (-)
Battery
Battery switch
Fig. 2-2 Connection of External Battery
Notice:
Battery connection and replacement should be carried out when the UPS in power-off state . When conducting online replacement, be sure not to reversely connect the battery!
II. Connect UPS input/output cables
As to 6kVA UPS, all the input/output cables (including cables to connect the hot standby L terminal, B terminal and battery wring terminals
)
should be at least 10AWG or 6mm2 copper wires; as to 10kVA UPS, all the input/output cables (including cables to connect the hot standby L terminal, B terminal and battery wring terminals
)
should be at least 8AWG or 10mm2 copper wires.
16 Chapter 2 Installation
E1-20010916-C-1.0
1. Before connection, please confirm that all input and output circuit breakers are placed to OFF;
2. As shown in Fig. 2-3, remove the terminal block cover, connect the input cables (live line, neutral line and ground line) respectively to the corresponding input terminals, and fasten the fixing screws;
Battery cable(-)(long backup time UPS)
Output live line
Output neutral line
Hot standby L terminal
Hot standby B terminal
Input live line
Input neutral line
Input ground line
L
N
B
L
+
_
N
L
Output ground line
Battery cable(+) (long backup time UPS)
Fig. 2-3 Wiring Diagram of Input/output Terminal Block
Notice:
1. To ensure reliable connection, all connection cables must use cable lug.
2. Never reversely connect the neutral line and the live line!
3. Wall socket power can not be used as UPS input power. Otherwise, the socket may be burned.
3. Connect the UPS output cables (live line, neutral line and ground line) and the load power lines (live line, neutral line and ground line) correctly to a power distribution cabinet, fasten the fixing screws, and mount the terminal block cover of the UPS.
Note: When connecting the output cables, be sure that the neutral line, live line and ground line are correctly and reliably connected. For the sake of safety, the ground line must be connected before the neutral line and live line.
Chapter 2 Installation 17
E1-20010916-C-1.0
III. Connect UPS communication cable
1. User may, according to actual needs, use the RS-232 cable (universal type) delivered with the UPS to connect the RS-232 port of
the UPS to that of the computer, or use the dry contact cable to connect the dry contact port of the UPS to the RS-232 port of the computer (connect the cable end marked with “UPS” to the dry
contact port, and the end marked with “PC” to the computer), as shown in
Fig. 2-4. The 2 connection methods result in different communication functions, as described in Appendix 1. User may refer to Appendix 1 to select suitable connection method.
RS-232
DRY CONTACT
INTELLIGENT SLOT
INPUT BREAKERBYPASS BREAKER
MAINTAIN SWITCH
RS232 cable
computer
Fig. 2-4 Connection Between UPS Communication Port and Computer
(Take RS-232 cable as an example)
2. For users who use SNMP adaptor, please follow the steps below to install the SNMP adaptor:
Remove the screws of the SNMP adaptor slot cover, then take off
the cover, as shown in Fig. 2-5(a). Retain the cover for future use;
Insert the SNMP adaptor into the slot, and fix it with screws, as
shown in Fig. 2-5(b);
18 Chapter 2 Installation
E1-20010916-C-1.0
Use network connection cable to connect the UPS to the network
port of the computer, as shown in Fig. 2-5(c);
For setting of the SNMP adaptor, please refer to the documents
delivered with the monitoring software.
Fig. 2-5 a Fig. 2-5 b
BYPASS BREAKERINPUT BREAKER
Concentrater
Network connection cable
MAINTAIN SWITCH
DRY CONTACT
RS-232
INTELLIGENT SLOT
Fig. 2-5 c
Fig. 2-5 Installation of SNMP Adaptor
Chapter 2 Installation 19
E1-20010916-C-1.0
2.3 Wiring of Master/Slave Hot Standby System
1. Be sure that the input circuit breakers of the master UPS and slave UPS are all in the OFF position, and neither UPS has output;
2. Remove the shorting stub between the hot standby L terminal and B terminal of the master UPS. Retain it, as it may be used in the future;
3. Perform wiring as shown in Fig. 2-6.
Note: Make sure that the neutral lines, live lines and ground lines are correctly and reliably connected. In the case of master/slave hot standby system adopting long backup time UPS, the master UPS and the slave UPS should have separate external battery, i.e. They can not share the same external battery.
Slave output live line connected to Master bypass
I n p u t
g r o u n d
l i n e
N
L
L
B
+
_
L
N
Slave
Output ground lines in parallel
Master
N
L
L
B+
_
L
N
Input live lives in parallel
Input neutral lines in parallel
Input ground lines in parallel
Slave neutral line connected to battery input terminel(-)
I n p u t
n e u t r a l
l i n e
I n p u t
l i v e
l i n e
M a s t e r
i n p u t
l i v e
l i n e
M a s t e r
i n p u t
n e u t r a l
l i n e
M a s t e r
i n p u t
g r o u n d
l i n e
Fig. 2-6 Wiring Diagram of 6kVA/10kVA Master/Slave Hot Standby System
20 Chapter 2 Installation
E1-20010916-C-1.0
Wiring requirements of master/slave hot standby system: The input/output cables of 6kVA UPS should be at least 10AWG or 6mm
2
copper wires; The input/output cables of 10kVA UPS should be at least 8AWG or 10mm
2
copper wires.
Chapter 2 Installation 21
E1-20010916-C-1.0
Chapter 3 Operation
3.1 Operation Mode
The UPS has 4 operation modes: Normal mode, Bypass mode, Battery mode, and Fault mode.
3.1.1 Normal Mode
When the input mains voltage and the load are within specifications, the load is supplied by inverter, which obtains power from rectifier; meanwhile, the charger float-charges or equalize-charges the battery. When in Normal mode, the mains indicator and inverter indicator on the LCD panel shine green, as shown in Fig. 3-1.
220.0V
OUTPUT VOLT
Fig. 3-1
Chapter 3 Operation 23
E1-20010916-C-1.0
Notice:
If the UPS is supplied by AC generator, please follow the requirements below
1
. Start up the AC generator first without switching on the loads, connect the UPS to the generator, then switch on the loads one by one till the generator operates stably (to ensure reliable operation of the generator, it is
recommended that the UPS load be less than 30% of generator capacity).
2. It is recommended that the generator capacity be 1.5~2 times of UPS rated capacity.
3.1.2 Bypass Mode
When the UPS is supplied with AC mains without being turned on, or in the event of overload or other faults after the UPS is turned on, the load is supplied by Bypass AC source, which comes directly from the AC mains input; and meanwhile the charger charges the battery. When in Bypass mode, the bypass indicator on the LCD panel shines green, as shown in Fig. 3-2. Please note: In the event of bypass power failure or bypass voltage outside tolerances when the UPS is in Bypass mode, the UPS is unable to supply the load.
215.0V
OUTPUT VOLT
Fig. 3-2
3.1.3 Battery Mode
When the UPS is in Normal mode, in the event of mains failure or mains voltage outside tolerances, the rectifier and charger stop
24 Chapter 3 Operation
E1-20010916-C-1.0
running, the battery begins to discharge and supply the load through inverter. When the UPS operates in Battery mode, the battery indicator and inverter indicator on the LCD panel shine green, as shown in Fig. 3-3, accompanied with a beep every 3 seconds, giving alarm that the UPS is operating in Battery mode.
220.0V
OUTPUT VOLT
Fig. 3-3
In Battery mode, when the battery voltage is low, there is a beep every 1 second, and the LCD screen reads “BATTERY LOW TO BE SHUTDOWN”, giving alarm for timely processing.
Note: Although the battery had been fully charged at factory before despatch, the transport and storage resulted in loss of electricity quantity, hence charging the battery for 8 hours is required before using the UPS for the first time, so as to ensure adequate battery backup time.
3.1.4 Fault Mode
In the event of inverter fault, internal overtemperature or other faults in Normal mode, the UPS transfers to Bypass mode; in the same cases in Battery mode, the UPS shuts down.
In the event of UPS fault, the fault indicator on the LCD panel shines red, as shown in Fig. 3-4. Meanwhile, the buzzer beeps (except
Chapter 3 Operation 25
E1-20010916-C-1.0
battery and charger fault), and the LCD screen displays corresponding fault information.
215.0V
OUTPUT VOLT
Fig. 3-4
3.2 Operation
3.2.1 System Power-on
After checking and making sure that the input and output cables are connected correctly, turn on the mains switch and the bypass switch (for long backup time UPS, turn on the battery switch before closing the mains switch). Then the system starts up, the internal fan begins to run, and the system begins to conduct self-test. After system self-test (the buzzer beeping twice means normal startup), the system enters in Bypass mode, the mains indicator and bypass indicator shine green, as shown in Fig. 3-5:
26 Chapter 3 Operation
E1-20010916-C-1.0
215.0V
OUTPUT VOLT
Fig. 3-5
3.2.2 System Parameter Setting
After system power-on, press the CIRCLE button to view the LCD display. When the LCD screen displays “BACK TO MAIN MENU”, press the ENTER button to return to the main menu. Again press the CIRCLE button, when the LCD screen displays “FUNCTION SETUP”, as shown in Fig. 3-6, press and hold the ENTER button for more than 5 seconds to enter the function setup state. User may set according to the actual UPS configuration the equalize charge function, temperature compensation function, battery capacity (the aforesaid setup is needed only for long backup time UPS, that of standard UPS had been completed at factory), master/slave/single and alternate operation time (this step is saved for single-unit system). See Section 1.5.2 for detailed information.
Chapter 3 Operation 27
E1-20010916-C-1.0
FUNCTION
SETUP
3
Fig. 3-6
After setting system parameter, please save the settings following the steps below:
1. Make sure the UPS is in Bypass mode, disconnect the mains input and bypass switches (don’t switch off the battery air breaker of the long backup time UPS, if any);
2. Wait for about 30 seconds until the internal fan stops and the LCD screen has no display (only after that can the set parameters be saved in the system);
3. Turn on the mains input and bypass switches to start up the system, up to now, the settings have been saved in the system.
3.2.3 Start Inverter Output
I. Start Normal mode
1. After system power-on, press and hold the ON/SILENCE button for 1 second, then a beep is heard. Several seconds later, the bypass indicator goes off and the inverter indicator shines, as shown in Fig. 3-7, which means the UPS is operating in Normal mode.
28 Chapter 3 Operation
E1-20010916-C-1.0
220.0V
OUTPUT VOLT
Fig. 3-7
Note: If the previous shutdown is automatic resulting from termination of battery discharge because of AC mains failure, the automatic turn-on function (this function is settable through background monitoring software and had been set at factory ) will be activated when the AC mains restores.
2. When the system begins to operate stably, gradually add loads to the system. The load information can be queried through the LCD screen, as shown in Fig. 3-8:
70.0%
LOAD STATUS
Fig. 3-8
3. If the buzzer beeps every 0.5 second and the LCD displays “OVERLOAD”, it indicates that overload exists. In this case, some less critical loads should be disconnected. Usually it is
Chapter 3 Operation 29
E1-20010916-C-1.0
recommended the UPS assume no more than 70% rated load so that the system operation won’t be affected by abrupt load fluctuation and the UPS lifetime can be extended.
Notice
If the system transfers from Normal mode to Bypass mode for 3 times within 1 hour due to overload, it will remain in Bypass mode for 1 hour and can’t transfer back to Normal mode till the overload is removed.
II. Start Battery mode
In the event of mains failure, user may turn on the UPS to start Battery mode to supply the load.
1. Press and hold the ON/SILENCE button for about 1 second, after a beep and system self-test, the battery indicator and inverter indicator shine green, as shown in Fig. 3-9, and the buzzer beeps every 3 seconds, indicating the UPS is operating in Battery mode.
220.0V
OUTPUT VOLT
Fig. 3-9
2. The loading process is the same as described in Section “Start Normal mode”.
30 Chapter 3 Operation
E1-20010916-C-1.0
Notice
In the event of overload during the loading process after starting Battery mode, immediately disconnect some loads till the overload alarm stops, otherwise, the system will stop output after a delay time.
3.2.4 Manual Battery Test
When in Normal mode, provided that the mains voltage is normal, no overload exists, and the battery voltage is no lower than 240V, battery test can be conducted by pressing button on the LCD panel (for battery test through background monitoring software, see the documents delivered with the software): press and hold the ON/SILENCE button for 4 seconds (a beep is heard 3 times) and then relieve it. 3 seconds later, the battery test begins, the battery indicator shines, and the buzzer beeps as in Battery mode. After battery test, the buzzer stops beeping, the battery indicator goes off, and the displays of the panel indicators restore to the state prior to test. When battery fault is detected (no battery, faulty battery, or battery reverse connection) during test, the fault indicator shines, and the LCD screen displays “BATTERY FAIL”, as shown in Fig. 3-10.
BATTERY FAIL
Fig. 3-10
Chapter 3 Operation 31
E1-20010916-C-1.0
Notice
After battery test, the battery state information will be refreshed. In the event battery fault that the battery is not fully charged is detected during test, user may re-test the battery after fully charging it to confirm that the fault is removed.
3.2.5 Turn off Inverter
1. When the system has AC mains input and the AC mains is normal, press and hold the OFF button for about 1 second, then a beep is heard, the inverter indicator goes off and the bypass indicator shines, as shown in Fig. 3-11, indicating the UPS has transferred to Bypass mode.
215.0V
OUTPUT VOLT
Fig. 3-11
2. When the system has no AC mains input (in Battery mode), press
and hold the OFF button for about 1 second, then a beep is heard, the UPS stops output and the LCD screen displays “UPS SHUTDOWN”. About 30 seconds later, all panel indicators go off, and the fan stops running.
32 Chapter 3 Operation
E1-20010916-C-1.0
3.2.6 System Power-off
After turning off the inverter, place the mains switch and the bypass switch to OFF, all panel indicators go off, and the fan stops running (if there is a battery, a delay time of 30 seconds is needed before the fan stops). Up to now, the system is powered off. If the UPS is connected to external battery, place the switch of the external battery to OFF. After system power-off, the UPS has no output to supply the load.
3.3 Auto Transfer Between UPS Operation Modes
In normal case, user should set the UPS to Normal mode. When operating in Normal mode, in the event of mains failure, the UPS automatically transfers to Battery mode without interruption to load; in the event of overload, the UPS automatically transfers to Bypass mode without interruption to load; in the event of inverter fault or internal overtemperature, the UPS operates in Fault mode.
3.3.1 Transfer to Bypass Mode in the Event of Overload
When the UPS remains overloaded for a specified time, the UPS transfers from Normal mode to Bypass mode, and meanwhile gives audible alarm every 0.5 second. In such case, the UPS output is mains voltage. At this time, some loads should be disconnected until the alarm stops, and 5 minutes after that, the UPS automatically transfers back to Normal mode. To protect the load and UPS, the transfer times within 1 hour from Normal mode to Bypass mode due to overload should be less than 3, otherwise, the UPS will remain in Bypass mode for 1 hour before it transfers back to Normal mode.
Chapter 3 Operation 33
E1-20010916-C-1.0
3.3.2 Transfer to Battery Mode in the Event of Mains Failure
In the event of mains failure, the UPS transfers to Battery mode. when the battery is completely discharged, the UPS automatically shuts down. When the mains restores, the UPS automatically turns on and operates in Normal mode. This function is designed for unattendance. If the UPS is manually shut down in Battery mode, it can only be turned on to inverter manually when the mains restores.
3.3.3 Transfer to Bypass Mode in the Event of Overtemperature
High ambient temperature and poor ventilation may result in overtemperature inside UPS. In the event of internal overtemperature, the UPS transfers to Bypass mode, the fault indicator shines red, the LCD screen displays “TEMP OVER”, and the UPS gives audible alarm. In such case, cut off the input AC mains (by switching off the input air breaker), remove any substances blocking ventilation, or widen the distance from wall. After the UPS cools down, supply it with AC mains and turn it on.
3.3.4 Output Short-circuit Protection
In the event of load short-circuit, the UPS stops output, the fault indicator shines red, the LCD screen displays “OUTPUT SHORT”, and the UPS gives audible alarm. In such case, disconnect the concerned load, and cut off the input power of the UPS. 10 minutes later, the UPS automatically shuts down (or manually shut down the UPS 10 seconds later by pressing the OFF button). After removing the short-circuit fault, connect the load back to the UPS, supply the UPS with AC mains and turn it on.
34 Chapter 3 Operation
E1-20010916-C-1.0
3.4 UPS Monitoring
For the information on background monitoring of UPS, please see the documents delivered with the monitoring software.
3.5 LCD Menu Operation
The button operation process is shown in Fig. 3-11:
Chapter 3 Operation 35
E1-20010916-C-1.0
WARNING INFO
... ...
...
FUNCTION SETUP
Press and hold
for 5 seconds
OUTPUT FREQ
BACK TO MAIN MENU
CIRCLE
( )
( )
ENTER
OPERATION STATUS
OPERATION STATUS
OPERATION STATUS
OUTPUT VOLT
BACK TO MAIN MENU
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
OPERATION STATUS
BACK TO MAIN MENU
EQUALIZATION CHARGE SET
Current value
Current value
ENTER
The 1st current alarm
The 2st current alarm
ENABLE
TEMP COMP SET
CANCEL SET
DISABLE
CIRCLE
CIRCLE
CIRCLE
CIRCLE
CIRCLE
CIRCLE
CIRCLE
CIRCLE
CIRCLE
CIRCLE
CIRCLE
CIRCLE
CIRCLE
CIRCLE
CIRCLE
CIRCLE
CIRCLE
Fig. 3-11 Button Operation Block Diagram
36 Chapter 3 Operation
E1-20010916-C-1.0
1. Shift between level 1 menus
Press the CIRCLE button to shift between the WARNING INFO, OPERATION STATUS and FUNCTION SETUP menus. Press the ENTER button to enter the WARNING INFO, OPERATION STATUS or FUNCTION SETUP menus.
Note: It is required to press and hold the ENTER button for more than 5 seconds to enter into the FUNCTION SETUP menu.
2. Shift between level 2 menus
A. After entering into the OPERATION STATUS menu, pressing the CIRCLE button can circularly view the running data; when the screen displays “BACK TO MAIN MENU”, press the ENTER button to return to the main menu.
B. After entering into the FUNCTION SETUP menu, pressing the CIRCLE button can circularly view the settable function information; when the screen displays “BACK TO MAIN MENU”, press the ENTER button to return to the main menu OPERATION STATUS.
C. After entering into level 2 menu under FUNCTION SETUP menu, the parameter value is displayed in highlight; at this time, pressing the CIRCLE button can circularly modify the value; press the ENTER button to save the modifications; after that, the parameter value is not displayed in highlight.
D. In the event of alarm, pressing the CIRCLE button can circularly view historical alarm; when the screen displays “BACK TO MAIN MENU”, press the ENTER button to return to the main menu OPERATION STATUS.
Chapter 3 Operation 37
E1-20010916-C-1.0
3. Priority of LCD display information
A. When the system is in alarm state, the LCD screen will automatically display the alarm information of the highest priority if there is no effective button operation within 30 seconds.
B. When there is no alarm, and the LCD screen is displaying level 2 menu under OPERATION STATUS menu, say, OUTPUT CURRENT, the LCD display information will remain unchanged if there is no effective button operation; however, when there is no alarm, and the LCD screen is not displaying level 2 menu under OPERATION STATUS menu, the LCD will automatically display “OUTPUT VOLT: xxx” if there is no effective button operation within 30 seconds.
38 Chapter 3 Operation
E1-20010916-C-1.0
Chapter 4 Maintenance
Using Avansys iTrust series UPS in specified ambient environment (see Section 2.2.1) can reduce maintenance.
I. Fan
The fan is expected to be able to run for 20000~40000 hours continuously. The higher the ambient temperature, the shorter the fan life. During system operation, please regularly check whether all fans are operating normally and there is air blowing out from inside.
II. Battery Maintenance
The internal battery of iTrust series UPS is sealed, lead-acid, maintenance-free battery. The battery life depends on the ambient temperature, charge and discharge times. High ambient temperature and deep discharge will shorten battery life.
To ensure battery life, the battery should be maintained regularly:
Keep the ambient temperature between 15
and 25 .
To prevent small current discharge, continuous battery discharge time exceeding 24 hours is strictly prohibited.
When the UPS hasn’t been used for a long time, and the battery hasn’t been charged for 3 months at specified ambient temperature, or 2 months at high ambient temperature, please
charge it for at least 12 hours.
Chapter 4 Maintenance 39
E1-20010916-C-1.0
As to external battery of long backup time UPS, the wiring terminals of the external battery must be checked regularly and, when necessary, should be cleaned.
If the battery backup time is found greatly shortened, or when the UPS LCD displays “BATTERY FAIL”, please contact the distributor to confirm whether the battery needs to be replaced. Before replacement, please make sure that the specifications of the new battery are correct.
Notice
1. Never short-circuit the battery terminals, which will result in fire.
2. Never open the battery, as the electrolyte is harmful to human body. In the event of inadvertent contact of electrolyte, immediately rinse it off and go to hospital for a check.
III. Keep Air Vent Unblocked
1. Regularly clean the system, especially the air inlet and air outlet. Make sure the air flows freely inside the chassis. Use dust collector for cleaning when necessary.
2. Check the air vents on the front, rear, and side panels, make sure they are not blocked.
IV. UPS State Check
1. Check whether the UPS is faulty: is the fault indicator shining? Is fault alarm being given?
2. Is the UPS operating in Bypass mode: in normal case, the UPS operates in Normal mode; if it is operating in Bypass mode, please
40 Chapter 4 Maintenance
E1-20010916-C-1.0
find out the reason, for instance: operator intervention, overload, internal fault, etc.
3. Is the battery discharging: when the AC mains is normal, the battery shouldn’t discharge; if the UPS is operating in Battery mode, please find out the reason, for instance: mains failure, battery test, operator intervention, etc.
V. Function Inspection
It is recommended to inspect the UPS functions once half year.
1. Press the OFF button, check whether the buzzer, LED indications and LCD display are normal (see Section 3.1 Operation Mode). Please do this after confirming that the AC mains is normal and data backup has been done.
2. Press the ON/SILENCE button, check again whether the LED indications and LCD display are normal and the UPS transfers to Normal mode.
3. When the inverter is in Normal mode (the inverter indicator shines), press and hold the ON/SILENCE button for 4 seconds to start battery test. Should any battery problem be found, immediately find out the problem and solve it.
Chapter 4 Maintenance 41
E1-20010916-C-1.0
Chapter 5 Troubleshooting
In the event of UPS fault, please check it and remove the fault in the first instance following the methods described in the table below. If the fault still exists, please contact the distributor, we’ll help you out of trouble in the shortest time.
If the UPS is operating in Battery mode, please note the battery backup time.
The mains voltage is outside tolerances.
The mains indicator flashes.
5
A. Pressing and holding the ON button for more than 1 second; B. Turn on the UPS again after disconnecting all loads.
A. The button holding time is too short; B. overload.
After pressing the ON button, the UPS does not start up.
4
Make sure that the output power line is properly connected.
The output power line is not properly connected.
No alarm is given, but there is no voltage output.
3
A. Turn on the input switch; B. Make sure that the input power line is properly connected;
A. The input switch is turned off; B. The input power line is not properly connected;
The AC mains is normal, but the mains indicator does not shine and the UPS operates in Battery mode.
2
Use voltmeter to check whether the input mains voltage is within tolerances.
A. AC mains hasn’t been introduced into the system; B. Input undervoltage.
No panel display and system self-test when the mains switch is in the ON position.
1
ActionPossible CauseAlarm or Condition
Serial
No.
Chapter 5 Troubleshooting 43
E1-20010916-C-1.0
A. Allow the battery to charge for more than 8 hours when the AC mains is normal, and then re-test the discharge time; B. The battery needs replacement, please contact the distributor.
A. The battery is not fully charged; B. The battery is not able to hold a full charge due to age.
The UPS has
reduced battery time.
9
Contact the distributor for charger replacement/maintenanc e.
Charger fault
The fault indicator
shines, and the LCD
displays “CHARGER
FAIL”.
8
A. Check whether the external battery switch is turned on and its lead is properly connected; B. Check whether the battery is reversely connected; C. Contact the distributor for battery replacement;
A. The external battery
switch is turned off, or its
lead is not properly
connected;
B. Battery reverse
connection;
C. Battery damaged;
The fault indicator
shines and the LCD
displays “BATTERY
FAIL”.
7
Disconnect some loads from the UPS.
Overload.
The buzzer beeps
every 0.5 second,
and the LCD
displays
“OVERLOAD”
6
ActionPossible CauseAlarm or Condition
Serial
No.
44 Chapter 5 Troubleshooting
E1-20010916-C-1.0
Turn off the UPS and cut off the power input immediately, contact the distributor for help.
UPS internal fault
Abnormal noise or smell inside the UPS.
13
The UPS needs maintenance, please contact the distributor.
UPS internal fault
The buzzer beeps, the fault indicator shines, and the LCD displays “RECTIFIER FAIL”, “INVERTER FAIL”, “AUX SUPPLY FAIL”, or “OUTPUT FAIL”.
12
Restart the UPS after confirming that load short-circuit does not exist.
UPS output short-circuit.
The buzzer beeps, the fault indicator shines, and the LCD displays “OUTPUT SHORT”
11
A. Check whether there is air blowing out from inside. B. Remove the substances blocking the vent, or widen the distance from the wall; C. Wait for 10 minutes until the UPS cools down, then restart it.
Internal overtemperature
The buzzer beeps, the fault indicator shines, and the LCD displays “TEMP OVER”
10
ActionPossible CauseAlarm or Condition
Serial
No.
When reporting UPS fault to our company or the distributor, please inform the machine model and machine No. (the bar code on the rear panel of the UPS).
Chapter 5 Troubleshooting 45
E1-20010916-C-1.0
Chapter 6 Service and Support
Avansys Power Co., Ltd. provides customer with satisfactory technical support. To obtain support, please contact the distributor in the first instance. When failing to reach the distributor, please contact your local technical support center or the company headquarters:
1. User can obtain service through dialing our free toll telephone.
Free toll
800-8302118
2. Web site technical service
User can seek technical support by visiting our technical support web site.
Technical support web site of Avansys Power Co., Ltd.:
http://www.avansys.com
To facilitate user, we also have special UPS service mailboxes:
hwdy@huawei.com
upsserver@huawei.com
3. We provide 3 years of free service for our 6kVA UPS (including the internal battery), and 1 year of free service for our 10kVA UPS (including the internal battery), provided that they are used properly.
The above warranty shall not apply in the following circumstances:
The battery is provided by user;
Damage resulting from operation not in accordance with the user manual;
Damage as a result of fire, flood, etc.;
Damage caused by transport, move or neglect after purchase;
Chapter 6 After-sales Service 47
E1-20010916-C-1.0
Damage caused by power supply not in accordance with relevant electrical regulations or operation in ambient environment not in compliance with requirements;
For detailed information on warranty, please see the warranty items.
4. Different levels of customized service packages are available with reasonable charge, including responsive, preventive maintenance, warranty period extension, etc. For detailed information, please contact the distributor or the local technical support center.
48 Chapter 6 After-sales Service
E1-20010916-C-1.0
Appendix 1 Communication Port
RS-232 Communication Mode
Port description male)
NC
RXD
TXD
NC
NC NC NC NC
1 2 3 4 5
6 7 8 9
GND
Pin 2: receiving terminal;
Pin 3: transmitting terminal;
Pin 5: common;
Other pins: unconnected.
Connection relationship between RS-232 port of computer and
RS-232 port of UPS
Computer --------------------- UPS RDX
pin 2
<------------------- TX
pin 3
TDX
pin 3
--------------------> RX
pin 2
GND
pin 5
--------------------- GND
pin 5
RS-232 communication mode provides the following functions:
Monitor the current power supply state of UPS;
Monitor the current alarm information of UPS;
Monitor the current running parameters of UPS;
Time the ON/OFF control of the UPS, and set system parameters.
Appendix 1 Communication Port 49
E1-20010916-C-1.0
RS-232 communication data format
Baud rate ---------- 4800bps Byte length ---------- 8bit Stop bit ---------- 1bit Parity check ---------- none
Dry Contact Communication Mode
Port description
NC
NC
GND
BATTERY LOW
OFF
GND
NC
NC
1 2 3 4 5
6
7
8 9
MAIN FAILURE
Pin 2: this pin turns from OPEN to CLOSE in the event of mains failure, its
normal state is OPEN;
Pin 5: this pin turns from OPEN to CLOSE in the event of battery low voltage,
its normal state is OPEN;
Pin 6: when applying +5V voltage for more than 1 second, the UPS is turned off;
Pin 4: signal ground;
Pin 7: signal ground;
Other pins: unconnected.
Dry contact communication mode provides the following functions:
Provide mains fault information in the event of mains failure;
Provide battery low voltage information when the battery discharge is about to terminate;
Provide OFF control of UPS
50 Appendix 1 Communication Port
E1-20010916-C-1.0
Appendix 2 Grounding & Lightning Protection
The grounding and lightning protection of low voltage power supply system is a systematic engineering, of which the grounding and lightning protection of UPS is only a part. According to relevant
international, domestic and industry standards, lightning protection
measures should be taken at the primary and secondary sides of the AC
power transformer before the power line is introduced into the UPS
machine room, and there are stringent requirements on the length and
grounding mode of the low voltage power cable introduced into the UPS
machine room, on the lightning protection, shielding, and lightning
protection ground cable of the UPS machine room.
To ensure human safety, the UPS must be reliably grounded prior to use, i.e., the UPS protective ground (the metal case of the UPS) must be reliably connected to the ground bar in the machine room by connecting the input ground line terminal on the UPS terminal block to the machine room ground bar. In addition, the mains frequency ground resistance of the machine room ground bar should be in compliance with relevant standards, normally less than 5 ohms. To ensure that the ground cable inside the UPS is reliably and safely connected, the iTrust UPS had undergone stringent internal ground resistance test at factory before despatch.
The iTrust UPS provides perfect lightning protection. All lightning protection elements are made by world known manufacturer or military standard products, and the SPD (surge protection device) is designed and installed in strict accordance with the IEC standard. After other lightning protection actions of low voltage power supply system stated above are taken in compliance with requirements, the harm that the lightning strike may do to the UPS machine room is minimized.
Appendix 2 Grounding & Lightning Protection 51
E1-20010916-C-1.0
Classified by the different throughput capacity and installation place, usually the UPS system has no more than 2 levels of lightning protection. The first level lightning protection adopts C-class SPD (
or
-class) with a max throughput capacity of 40kA, waveform 8/20 s, installed between the UPS and the AC distributor; the second level lightning protection adopts D-class SPD
(or -class
) with a max
throughput capacity of 8kA, waveform 8/20
s, installed inside the UPS. Standard D-class SPD is installed inside the iTrust UPS, and the SPD24SZ C-class SPD produced by Avansys is recommended. User may decide whether to select C-class SPD according to the actual situation of the machine room. Whichever brand C-class SPD is selected, the connection method shown in the following figure must be adopted between the C-class SPD and the UPS, i.e., the protective ground (the UPS metal case) and the C-class lightning protection ground of the UPS share the same ground, and are then connected to the ground bar in the machine room.
52 Appendix 2 Grounding & Lightning Protection
E1-20010916-C-1.0
wiring
diagram
User
UPS
Protective
ground
Ground
bar
1. Fixation hole 2. Air breaker 3. Integrated lightning protection element
4. Ground copper bar
C-class lightning protection ground
Connection of SPD24SZ SPD
Notes:
1. It is recommended to use copper core cable with sectional area between 6
25mm² as the live line (L) and neutral line (N) of the SPD24SZ SPD, and copper core cable with sectional area 10mm² (minimally 6mm²) as the protective ground cable (PE line). For detailed installation, please refer to relevant specifications by Avansys.
2. According to test result, the length of the connection cable between the C-class SPD box and the UPS is required to be within 5
10m, and it must be ensured that this cable will not suffer lightning strike. Too short cable length will affect the lightning protection effect.
3. In applications with high lightning strike hazard, it is recommended to install B-class (or
-class SPD at 12m or even
Appendix 2 Grounding & Lightning Protection 53
E1-20010916-C-1.0
further before the C-class SPD. User may buy and install the B-class SPD by itself under the technical guidance of Avansys.
54 Appendix 2 Grounding & Lightning Protection
E1-20010916-C-1.0
Appendix 3 Technical Specifications
89%88%Efficiency
120 ~253Vac Bypass voltage
105~125% rated load, 5min; 125~150% rated load, 10sOverload capacity
60mS
Transient
recovery time
5% at 100% load step change resistive load
Dynamic
response
4% linear load
5% nonlinear load
Voltage harmonic
distortion
3:1Crest factor
0.7Power factor
1Hz/S
Frequency
synchronization
speed
In Normal mode: synchronizes the bypass frequency when the bypass frequency is within 50Hz 10%; is 50Hz
0.2% when the bypass frequency is outside tolerances. In Battery mode: is 50Hz 0.2%
Frequency
220Vac±2%Voltage
10kVA/7kW6kVA/4.2kWPower rating
Output
0.99Power factor
50Hz±5HzFrequency
176-276Vac, full load; 120-176Vac, linear derating in loading; 120Vac, half load.
160-276Vac, full load; 120-160Vac, linear derating in loading; 120Vac, half load.
Voltage range
220VacRated voltage
Input
UH11-0100LUH11-0060L
UH11-0100UH11-0060
Model
Appendix 3 Technical Specifications 55
E1-20010916-C-1.0
IP21
Protection class
IEC60664-1-IV, 6kV/3kA hybrid wave for
1.2/50µS+8/20µS
Surge protection
Conduction, emission EN50091-2 EN55022 Class A Immunity EN61000-4-2.3.4.6.8.11 Level III EN61000-4-5 Level IV
EMC
CCEE GB4943-1995Safety
LCDDisplay
48dB
45dB
Audible noise (1m)
0
Inverter
Bypass
0
Normal
Battery
Transfer
time
4A, expandable in parallel to 8A (external charger is
needed when battery capacity ≥200Ah)
Charge current
long backup
time UPS
8 hours to 90% rated capacity
Recharge time
standard
UPS
8
min
6min
Backup time at
full load
standard
UPS
240Vdc240VdcRated voltage
4020
Internal cell
number
Sealed, lead-acid, maintenance-free battery 12V/7Ah
Type
Battery
UH11-0100LUH11-0060L
UH11-0100UH11-0060
Model
56 Appendix 3 Technical Specifications
E1-20010916-C-1.0
8553
Long backup
time UPS (kg)
190100
Standard UPS
(kg)
Weight
280 875 770280 635 670
W H D (mm)Size
<1500m, derating in accordance with GB/T3859.2 when
it is higher than 1500m
Elevation
5% 95%, non-condensing
Relative humidity
–40°C +70°C( without battery ) –20°C +55°C ( with
battery)
Storage
temperature
0°C +40°C
Operating
temperature
Environ mental condition
UH11-0100LUH11-0060L
UH11-0100UH11-0060
Model
Appendix 3 Technical Specifications 57
E1-20010916-C-1.0
Appendix 4 Optional Component
Class-C SPDSPD-24SSPD
Max charge current 4A, for battery consisting of 20 12V cells in series.
UH-BCH240/4Charger
20 100Ah cellsUF-B0100-100
20 65Ah cellsUF-B0100-65
20 38Ah cellsUF-B0100-38
Battery cubicle
UF-SNMP110-WEBWEB/SNMP AGENT
UF-WIN100NNetwork software
UF-SNMP110SNMP adaptor
RemarkModelProduct
58 Appendix 4 Optional Component
E1-20010916-C-1.0
Loading...