Equipment Type: Electricity Meter With Dual RF Transmitters
Trade Name: CENTRON ™ ICARe
Model: C1A-2
Manual
5015 B.U. Bowman Drive Buford, GA 30518 USA Voice: 770-831-8048 Fax: 770-831-8598
CENTRON® Meter
Technical Reference Guide
Effective: January 2005
Proprietary Rights Notice
This manual is an unpublished work and contains the trade secrets and confidential information of Itron, Inc., which are not to be divulged to third parties and may not be reproduced or transmitted in whole or part, in any form or by any means, electronic or
mechanical for any purpose, without the express written permission of Itron, Inc. All rights
to designs or inventions disclosed herein, including the right to manufacture, are reserved to
Itron, Inc.
The information contained in this document is subject to change without notice. Itron, Inc.
reserves the right to change the product specifications at any time without incurring any
obligations.
Trademarks Used in This Manual
CENTRON, PC-PRO+, PRO-READ, and ReadOne are registered trademarks of Itron, Inc.
Windows is a trademark of Microsoft Corporation.
Cellnet is a registered trademark of Cellnet Technologies, Inc.
CENTRON® Meter Technical Reference Guide
Part Number: 100299GM-01
Itron, Inc.
Corporate Headquarters
2818 North Sullivan Road
Spokane, WA 99216
U.S.A.
Tel: (509) 924-9900
Fax: (509) 891-3355
www.itron.com
This equipment has been tested and found to comply with the limits for a Class B digital
device, pursuant to Part 15 of the FCC rules. These rules are designed to provide reasonable
protection against harmful interference when the equipment is operated in a residential/
commercial environment. This equipment generates, uses, and can radiate radio frequency
energy and, if not installed and used in accordance with the instructions, may cause harmful
interference to radio communications. However, there is no guarantee that interference will
not occur in a particular installation. If this equipment does cause harmful interference to
radio or television reception, which can be determined by turning the equipment off and on,
the user is encouraged to try to correct the interference by one or more of the following
measures:
•Re-orient or relocate the receiving antenna.
•Increase the separation between the equipment and the receiver.
•Connect the equipment into an outlet on a circuit different from that to which the
receiver is connected.
•Consult the dealer or an experienced radio/TV technician for help. This device complies
with Part 15 of the FCC rules.
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT
TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL
INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE
RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION
FCC Part 15, Subpart C
When equipped with a radio transmitter option, this equipment has been tested and found to
comply with the limits for an intentional radiator, pursuant to Part 15, Subpart C of the FCC
Rules. This equipment generates, uses, and can radiate radio frequency energy. If not
installed and used in accordance with the instructions, it may cause interference to radio
communications.
The limits are designed to provide reasonable protection against such interference in a residential situation. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause interference to radio or television reception.
which can be determined by turning the equipment on and off, the user is encouraged to try
to correct the interference by one of more of the following measures:
•Reorient or relocate the receiving antenna of the affected radio or television.
•Increase the separation between the equipment and the affected receiver.
•Connect the equipment and the affected receiver to power outlets on separate circuits.
•Consult the dealer or an experienced radio/TV technician for help.
Changes or modifications not expressly approved by Itron, Inc. could void the user’s authority to operate the equipment.
RF Exposure Information
This equipment complies with the FCC RF radiation requirements for uncontrolled environments. To maintain compliance with these requirements, the antenna and any radiating elements should be installed to ensure that a minimum separation distance of 20 cm is
maintained from the general population.
Canadian Interference Causing Equipment Regulations
This Class B digital apparatus meets all requirements of the Canadian Interference Causing
Equipment Regulations. Operation is subject to the following two conditions: (1) this device
may not cause harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
CENTRON Meter Technical Reference Guideiii
Cet appareillage numérique de la classe B répond à toutes les exigences de l'interférence
canadienne causant des règlements d'équipement. L'opération est sujette aux deux conditions suivantes: (1) ce dispositif peut ne pas causer l'interférence nocive, et (2) ce dispositif
doit accepter n'importe quelle interférence reçue, y compris l'interférence qui peut causer
l'opération peu désirée.
Factory Repair of Meters
Itron recommends that all repairs be performed at the factory. Certain repairs may be performed by the user; however, unauthorized repairs will void any existing warranty. All surface mounted parts must be replaced by the factory.
Repair of Meters Under Warranty
If the meter is under warranty, then Itron, Inc. will repair the meter at no charge if the meter
has failed due to components or workmanship. A return authorization number must be
obtained before the equipment can be sent back to the factory. Contact your Itron Sales
Representative for assistance.
Repair of Meters Not Under Warranty
The same procedure as above applies. Itron will charge for the necessary repairs based on
the failure.
Service Return Address
Itron, Inc.
Customer Repair Department
313 North Highway 11 Dock C
West Union, SC 29696
Recycling Information:
The product you have purchased contains a battery (or batteries), circuit boards, and switches. The
batteries are recyclable. At the end of the meter’s useful life, under various state and local laws,
it may be illegal to dispose of certain components into the municipal waste system. Check with
your local solid waste officials for details about recycling options or proper disposal.
Although polycarbonate is not a commonly recycled plastic, the recycling number for the polycarbonate base is seven (7).
This technical reference guide explains the installation, operation, and
maintenance of the Itron CENTRON® meter family. Itron urges you to read the
entire manual before attempting installation, testing, operation, or maintenance of
a meter. To operate the Itron PC-PRO+® Programming Software and the
PRO-READ® handheld reader programmer discussed in this manual, refer to their
respective user manuals.
About This Manual
This manual contains the following information as listed in the chapter
descriptions below:
Chapter 1
General Information
Chapter 2
Installation
Chapter 3
Operation: Base
Chapter 4
Operation: C1S
Chapter 5
Operation:C1SD, C1ST,
C1SL
Chapter 6
Operation: C1SR
Chapter 7
Operation: C1SC
Chapter 8
Testing, Troubleshooting,
and Maintenance
Chapter 9
Specification Numbers and
Drawings
Provides a general description, operation, physical and
functional descriptions, and complete meter specifications.
Gives instructions for the proper handling and installation.
Describes the measurement technique used for the base on
the CENTRON meter.
Provides a physical description and operational
characteristics of the basic watthour (kWh) only meter.
Provides detailed information and theoretical operation for
Demand (C1SD), Time-of-Use (C1ST), and Load Profile
(C1SL) versions. Gives step-by-step procedures for
accessing the three operational modes and associated
displays.
Provides a physical description and the operational
characteristics of the R300 900 MHz radio frequency
personality module.
Provides a physical description and the operational
characteristics of the CellNet personality module.
Provides an explanation of the testing, troubleshooting, and
maintenance of the CENTRON meter.
Provides a reference to meter part numbers as well as
CENTRON wiring diagrams.
CENTRON Meter Technical Reference Guide1-1
General Information
General Description
The CENTRON meter family is a solid-state, singlephase and network meter used
for measuring electrical energy consumption. The CENTRON incorporates a twopiece design combining a base metrology with a variety of personality modules
that snap on the standard meter base. Utilizing the Hall Effect technology for
accurate power measurement, the metrology portion of the meter contains all
measurement circuitry and calibration information, while the personality modules
contain the register functionality and communication mediums.
Each version of the meter is distinguished by the various personality modules that
mount to the standard meter metrology base (see Figure 1.1) The personality
modules available include the following versions:
•Energy only—C1S (LCD)
•Demand—C1SD
•Time-of-Use (TOU) with Demand—C1ST
•Load Profile with TOU and Demand—C1SL
•Energy only with radio frequency AMR—C1SR
•CellNet Fixed Network—C1SC
•Energy plus demand with radio frequency AMR - R300CD
Figure 1.1 Personality Modules
1-2CENTRON Meter Technical Reference Guide
Physical Description
Meter Base
General Information
The CENTRON meter features a common meter base to which various personality
modules are attached. The covers come in configurations of polycarbonate and
glass.
The CENTRON meter base contains all of the measurement circuitry and
calibration information on the metrology board.
The meter base assembly includes two current conductors, a flux-directing core, a
Hall Effect device, the metrology circuit board, and the ultrasonically welded
module support. The base also contains a MOV, metal oxide varistor, which is used
to protect the meter from line surges.
Meter bases are built specific to the metering form and are available in Form 1S, 2S
CL200, 2S CL320, 3S 120V, 3S 240V, 4S, and 12/25S configurations.Examples are
shown in Figure 1.2, Figure 1.3, and Figure 1.4.
Figure 1.2 Form 1S, 120 VoltFigure 1.3 Form 2S, CL200 240 Volt
Figure 1.4 Form 4S, 20 Amp Transformer-Rated
CENTRON Meter Technical Reference Guide1-3
General Information
Personality Modules
All of the personality modules in the CENTRON meter family snap into the module
holder located on the standard meter base (see Figure 1.5). From the base
metrology, the energy data is transmitted to the personality modules, which
contain the meter display, communication mediums, and register functionality.
Product Availability
Battery
Figure 1.5 Personality Module Assembly
The current offerings for the CENTRON are:
MetrologyClass 100, 120V, Form 1S
Class 200, 240V, Form 2S
Class 320, 240V, Form 2S
Class 20, 120V, Form 3S
Class 20, 240V, Form 3S
Personality
Modules
Option BoardsR300CD
The CENTRON C1ST and C1SL modules contain a battery that powers the clock
circuit during a power outage. The battery is permanently soldered to the module
and is expected to last the life of the module.
Refer to Chapter 5,"Operation: C1SD, C1ST, and C1SL Versions" for detailed battery
information.
C1S—LCD (5x1 or 4x10)
C1SR—R300C (Radio
Frequency)
C1SC—CellNet Data System
Class 20, 240V, Form 4S
Class 200, 120V, Form 12S
Class 200, 120V, Form 25S
C1SD—Demand
C1ST—Time-of-Use (TOU)
C1SL—Load Profile
1-4CENTRON Meter Technical Reference Guide
Covers
Outputs
Display Functions
General Information
The outer cover configurations available for CENTRON meter family are described
in Table 1.1.
The C1SD, C1ST, and C1SL personality modules are available input/output-ready
(I/O-ready). These modules contain circuitry that allows future functionality
expansion through I/O modules.
The C1S and C1SR modules can display kWh readings in either a 5x1 or 4x10
configuration.
The C1SD, C1ST, and C1SL modules can display a maximum of 32 Normal, 32
Alternate, and 8 Test display items, up to a total of 48 items.
Specifications
Electrical
Operating Environment
Voltage Rating120V, 240V
Operating Voltage± 20% (60 Hz); ± 10% (50 Hz)
Frequency60 Hz, 50 Hz
Operating Range± 3 Hz
Battery Voltage3.6 V nominal (C1ST, C1SL only)
Operating Range2.7V - 3.8V
Carryover8 year cumulative and 15 year shelf life
Temperature-40°C to +85°C
Humidity0% to 95% non-condensing
Accuracy± 0.5% @ unity power factor
The following weight measurements are shown in pounds and (kilograms).
PolycarbonateGlass
Meter1.375 (0.623)2.75 (1.247)
4 Meters and Carton8.90 (4.04)13.96 (6.35)
96 Meter Pallets214 (97.30)335 (152.30)
1-8CENTRON Meter Technical Reference Guide
Chapter 2Installation
This chapter of the guide gives instructions for the proper handling and installation
of the CENTRON meter.
Inspection
Perform the following inspections when you receive the meter:
•Inspect for obvious damage to the cover, base, and meter assembly.
•Be sure the optical connector is free of debris.
•Compare the meter and register nameplates to the record card and invoice.
Verify the type, class, voltage, form number, and other pertinent data.
•Save the original packing materials.
Battery
The lithium battery is soldered to the register module circuit board(C1ST and
C1SL only). A low-power mode for the battery preserves the capacity of the
battery. Factory-programmed C1ST and C1SL meters should be put into service in
a timely manner to avoid degradation of the battery. Programmed meters are not in
low-power mode.
Storage
The product you have purch ased co ntain s a recyclable lithiu m b attery, circuit boards, and
switches. At the end of its useful life, under various state and local laws, it may be illegal
to dispose of this battery into the municipal waste s tream. Check with y our local area
solid waste officials for details about recycling options or proper disposal.
The C1SR also contains a tilt switch that may contain mercury. Please dispose of
properly.
Store the meter in a clean, dry (Relative Humidity < 50%) environment between
-40° C to +85° C (-40° F to +185° F). Avoid prolonged storage (more than one year)
at temperatures above +70° C(+158° F). Store the meter in the original packing
material. The lithium battery has a shelf life of approximately fifteen (15) years.
CENTRON Meter Technical Reference Guide2-1
Installation
Unpacking
Selecting a Site
As with all precision electronic instruments, the meter should be handled with care
in an outdoor environment. Follow these precautions when handling the meter:
•Avoid damaging the meter base, cover, reset mechanism (if supplied), and
optical connector (if supplied).
•When handling personality modules, grip the circuit board by its edges. Do not
touch the liquid crystal display.
The meter is designed and manufactured to be installed in an outdoor
environment, at operating temperature ranges between -40° C and +85° C (-40° F to
+185° F). Operation in moderate temperatures increases reliability and product
life.
When using a Demand, TOU, or Load Profile meter where the line frequency is not
stable, Itron recommends using either the C1ST or C1SL meter version with
Crystal Time synchronization if a clock is needed (TOU or Load Profile).
Installing the Meter into Service
Install the meter base using standard meter installation practices.
The current and potential terminals extend as blades, or bayonets, from the back
of the meter. The meter is plugged into the socket so that the bayonets engage the
main socket jaws that connect to the service lines. Clamping pressure on the
bayonets is provided by the heavy spring pressure of the socket jaws. In some
heavy-duty sockets, jaw clamping pressure is provided by a handle or wrench.
On meters equipped with LCD displays, verify register operations by observing the
display:
•LCD displays the correct number of digits (4 or 5).
•If the test mode annunciator is flashing, depress the Test mode button to
return the meter to the Normal mode (C1S D/T/L only).
•If the register only displays a Segment Test (all display items shown) and
flashes “CNTRON”, the register has not been programmed.
•Verify that no errors are displayed.
2-2CENTRON Meter Technical Reference Guide
The practice of knowingl y install ing Form 12S/25 S meters into meteri ng sock ets wi th
either missing or disconnected fifth terminal jaws in the meter socket is NOT
recommended for CENTRON Form 12S/25S meters.
The following guidance should be followed when using the Form 12S/25S CENTRON
meter:
•This version of the meter should not be used in a non-Form 12S or 25S metering
service.
•The meter's 5th terminal should be properly installed on the meter in a location
defined in the CENTRON Technical Reference Guide.
•The fifth terminal jaw in the meter socket should be properly connected to the
service neutral and installed in the correct location.
•The metering service should match the class, form and voltage rating on the meter's
nameplate.
Failure to follow these recomme ndations will result in damage to the CENTRON Form
12S/25S meter and void all product warranties.
Programming the C1SD,T,L Meter
Installation
The personality module should be powered prior to programming. The module can
be programmed using the optical connector. The default communications rate
when programming through the optical tower is 4800 baud; 9600 baud is
selectable. Refer to PC-PRO+ documentation for detailed programming
information.
Retrofitting with Personality Modules
CENTRON meters can be upgraded to increase functionality by changing the
Personality Modules.
Do not power ON the meter without the inner cover in place. Power the meter OFF before
removing the inner cover. Personality modules are sensitive to ESD damage. Take
appropriate grounding measures before retrofitting!
To change or add a Personality Module:
1Remove power from the meter.
2Remove the outer (polycarbonate or glass) cover.
3Remove plastic inner cover by holding the meter with both hands and applying
equal pressure on either side of the three and nine-o’clock positions. The inner
cover is held in place by four plastic tabs on the meter base.
4Remove the black board-to-board connector between the circuit board and the
metrology board by pulling it by its middle while moving it side-to-side (see
Figure 2.1). To maintain the integrity of the connector, only remove it when
you are upgrading the meter.
CENTRON Meter Technical Reference Guide2-3
Installation
Board-to-Board
Connector
Figure 2.1 Removing the Board-to-Board Connector
5Remove the register module, one side at a time, by pulling gently outward on
the meter frame snaps (see Figure 2.2) while lifting the module up.
Meter Frame
Snaps
Figure 2.2 Removing the Register Module
6Snap the new module into the meter frame by aligning the notches at bottom
of the circuit board with the lower two snaps (see Figure 2.3).
The module must be aligned properly in the snaps to avoid damaging the connector or circuit
board.
2-4CENTRON Meter Technical Reference Guide
Figure 2.3 New Module Snap-in
Installation
7Replace the board-to-board connector by aligning the top of the connector
with the notches in the circuit board (see Figure 2.4) and pressing gently at the
bottom of connector to mate the connector to metrology board (see Figure
2.5). Then, gently press the top of the connector to mate it to the register
module (see Figure 2.6). The connector is seated correctly when you hear it
snap into place.
Notches (2)
Figure 2.4 Circuit Board Notches
CENTRON Meter Technical Reference Guide2-5
Installation
Be sure to use the meter base for leverage instead of the LCD holder (see Figure 2.5). Pressure
on the LCD holder may damage the personality module.
Figure 2.5 Board-to-Board Connector, Bottom
8Ensure the board-to-board connector is fully seated by pressing firmly in on
the middle of the connector.
Figure 2.6 Board-to-Board Connector, Top
9Carefully replace the inner protective cover. Engage the top snaps first, taking
care to place the slot at the top of the cover over the IR light pipe. Failure to do
so could break the light pipe. Ensure that all four meter base tabs are engaged
with the slots at the top and bottom of the inner cover.
2-6CENTRON Meter Technical Reference Guide
Installation
10 Place the cover over the meter base until the flange on the cover is flush with
the flange on the meter base.
11 Turn the cover clockwise until the locking tabs are fully engaged with the
meter base.
12 If the cover has a Demand Reset or an Optical Connector, be sure these are
properly aligned with their corresponding accessory on the register faceplate.
If not aligned correctly, the Demand Reset or Optical Connector will not
function properly. If the Demand Reset plunger is not in the retracted position
before turning the outer cover, the mechanism may be damaged.
CENTRON Meter Technical Reference Guide2-7
Installation
Notes:
2-8CENTRON Meter Technical Reference Guide
Chapter 3Operation: Base Metrology
This chapter describes the measurement technique used for the base metrology on
the CENTRON meters.
CENTRON 1S, 2S CL200, and 3S
The CENTRON meter is a solid-state meter which uses the inherent multiplication
properties of the Hall Effect to measure power. The Hall Effect principle relies on a
physical property: a conductor which carries a current in a magnetic field
generates a voltage difference across the conductor proportional to the product of
the current and the magnetic field.
The voltage V
Where
i
is the biasing current (derived from the line voltage)
b
B is the magnetic field density (derived from the line current)
K is the Hall coefficient (analogous to a gain factor in any meter)
K could be viewed as the Hall sensor intrinsic gain and is maximized by the
appropriate choice of semiconductor materials that have been uniquely optimized
by Itron for the CENTRON meter.
For the metering application, the biasing current i
generated from the line voltage (V) using a resistor (R).
created at the output of the Hall device:
out
V
KibB×=
out
applied to the sensor is
b
VR⁄=
i
b
The magnetic field (B) is generated by the line currents (I = I
+ I2) that flow
1
through two conductors looped around the core.
BCI×CI1I2+()×==
Where
C is a constant that is dependent upon the geometric and magnetic properties
of the coil
This field is focused to flow through the Magnetic Core’s air gap where the Hall
sensor is precisely positioned. The voltage, Vout, which is formed on the Hall
Effect device is proportional to the input watts (see Figure 3.1).
CENTRON Meter Technical Reference Guide3-1
Operation: Base Metrology
The output voltage of the Hall Effect device is then:
V
V= outGIVGPower==
hall
Where GC R⁄()K=
G is the combined gain factor of the entire system (Voltage to biasing current, line
Current to flux density, Hall sensor).
i
b
Figure 3.1 Power Measurement Principle in 2S
From the power information available at the output voltage of the sensor, the
meter architecture is simplified over previous designs as the multiplication has
already taken place (see Figure 3.2).
The Hall sensor output voltage is amplified by a differential amplifier in order to
bring the signal within the nominal level of the analog to digital converter (ADC).
The output of the ADC is integrated over time to get the energy information and
generates a pulse stream that is accumulated into a counter. When the
accumulated pulses reach a threshold set by meter calibration, a Wh pulse is
emitted and the meter LED is flashed. The counter threshold is programmed at the
factory and serves as the permanent gain calibration for the life of the product. The
calibration is a digital feature and has no variation or adjustment. All the
processing steps described above are integrated into an Application Specific
Integrated Circuit (ASIC) to improve reliability and reduce cost.
3-2CENTRON Meter Technical Reference Guide
Operation: Base Metrology
Figure 3.2 Simplified CENTRON Architecture
The custom ASIC cancels all the offset generated by the meter and removes the
need for a light load adjustment of the metrology. This allows the meter to have
excellent accuracy over a very large dynamic range, especially at the low current
levels. For this reason, no offset adjustment is needed or provided for the
CENTRON meter.
There is a slight phase shift in the current to flux density conversion due to eddy
currents in the magnetic core material. This shift causes a small power factor error
that is uniform across the dynamic range (load curve) of the meter. Itron
compensates for this shift in the CENTRON by the use of a capacitor in the biasing
current circuit. This correction is permanent.
The custom ASIC provides:
•Wh pulses to drive the Test LED
The same signal is also provided to the electronic register attachments.
•energy direction (sign)
•60Hz clock signal synchronized with the line voltage (for time keeping)
•pulse that drives the stepper motor for the mechanical register attachment (1
pulse every 10 watthours)
The metrology board, which houses the measurement components described
above, passes the Wh pulse, energy direction, and 60Hz clock signals to the
personality module attached to the meter base. The two line voltages (one is
referred to as meter ground), and power supply references are also supplied for
reference purposes.
An inherent feature built into the design of each CENTRON ensures that the calibration of the
product is not affected by any electronic board (existing or planned) added to the meter. This is
achieved by a distributed power supply and documented design requirements in the CENTRON
developer’s kit.
CENTRON 2S CL320, 4S, 12/25S
The advanced metering forms of the CENTRON (2S CL320, 4S, and 12/25S) meter
use the same Hall Effect measurement principle that is used in the form 1S, 2S, and
3S metering forms described earlier in this chapter.
The major difference with these metering forms is the presence of two Hall cells,
magnetic cores, and ADCs (see Figure 3.3).
CENTRON Meter Technical Reference Guide3-3
Operation: Base Metrology
For these metering applications, the biasing current Ibias (I
each sensor is generated from the line voltage (V
magnetic field is generated by the line current (I
conductor looped around each core. The voltage (V
line1
line1
and V
and I
and V
out1
line2
line2
and I
bias1
) using a resistor. The
) that flows through the
) that is formed on
out2
) applied to
bias2
each Hall Effect device is proportional to the watts produced by each phase.
Each Hall sensor output voltage is amplified by a differential amplifier in order to
bring the signal within the nominal level of the ADC. ADC 1 sums the signal from
ADC 1 and ADC 2. The output of ADC 1 is integrated over time to get the energy
information. Each time the integrated signal exceeds a predetermined amount of
energy, a pulse is generated. The pulse stream is accumulated into a counter. When
the accumulated pulses reach a threshold, a Wh pulse is emitted and the meter
LED is flashed. The counter threshold is programmed at the factory and serves as
the permanent gain calibration for the life of the product. The calibration is a
digital feature and has no variation or adjustment. ADCs 1 and 2 are calibrated
independently, which means that each phase is calibrated independently.
Figure 3.3 Hall Cells and ADCs
3-4CENTRON Meter Technical Reference Guide
Chapter 4Operation: C1S Version
The kWh only version of the CENTRON meter is available with an LCD personality
module to register energy accumulation:
The LCD module may be ordered with a 5x1 or 4x10 register for self-contained
meters, and a 5xTR or 4xTR register for transformer-rated meters.
The kWh only version of the CENTRON provides very accurate measurement for
energy accumulation for today’s needs, but also provides a platform for easy
upgrade to higher functionality in the future.
Figure 4.1 C1S LCD Personality Module
Physical Description
The CENTRON Personality Modules snap into the meter register mounting
brackets to ease installation of the board.
The LCD module is connected to the metrology board using the board-to-board
connector. The following information is sent to the LCD module from the
metrology board:
•Line voltage
•Reference voltage
•Energy flow direction
•Energy pulse data
•Line frequency
A connector is located at the 12 o'clock position behind the LCD for resetting the
energy register. This is done using the ZRO-C2A Resetter.
CENTRON Meter Technical Reference Guide4-1
Operation: C1S Version
Registers
Kilowatt Hours
Resetting Values
Figure 4.2 Mounted LCD Register
The modules display energy in increments of whole values of kWh. Standard
operation for all modules is to add forward and reverse energy flow. Therefore, if
the meter is inverted, the registers will accumulate in the forward direction, thus
providing uni-directional operation. At the time of order, the LCD module can be
selected to have a detent register. Programmed at the factory, this feature will
cease registration while the meter is inverted, or power flow is otherwise reversed.
The module can also be selected to have a net register. This feature is factory
programmable and will subtract registration while the meter is inverted, or power
flow is otherwise reversed.
The ZRO-C2A (see Figure 4.3) resets the energy register through a direct
connection to the connector at the 12 o’clock position on the LCD and R300
modules.
4-2CENTRON Meter Technical Reference Guide
Figure 4.3 ZRO-C2A Resetter Connected to the CENTRON
Operation: C1S Version
The ZRO-C2A Resetter works with both pre-June 2003 and Post-June 2003 LCDs.
The ZRO-C2A is a pocket-sized handheld device for resetting the electronic meter
readings in the CENTRON LCD kWh meter (C1S) and the R300 meter (C1SR). The
ZRO-C2A also resets the tamper indicators in the C1SR.
The ZRO-C2A requires that the meter Not Be Powered. The device connects to
the CENTRON meter through a hole in the plastic inner cover located at the 12
o’clock position on the meter (see Figure 4.3). Extending from the ZRO-C2A is a
cable terminating in a connector which mates to the programming connector of
the CENTRON.
Beginning February 20, 2002, the C1SR module for the CENTRON meter uses a
new EEPROM component. This new EEPROM operates at a different voltage level
requiring revision to the CENTRON resetter.
Use of a ZRO-C or ZRO-C2 resetter without the C2A upgrade WILL CAUSE DAMAGE to
the personality modules on both the C1S LCD and C1SR me ters produc ed after the ne w
EEPROM implementation date; damaged modules will show “Error” on the display.
CENTRON Meter Technical Reference Guide4-3
Operation: C1S Version
All current production resetters and resetters produced after June of 2001 were
built with the C2A upgrade and are labeled accordingly as shown in Figure 4.4
below. Although personality modules with the new EEPROM are only compatible
with the C2A version of the CENTRON resetter (ZRO-C2A), the older revisions of
the personality modules are also compatible with the ZRO-C2A.
Figure 4.4 Reverse Side of ZRO Resetter
LCD Display Function
Pre-June 2003 LCDs
The CENTRON LCD has been updated as of June 2003. All CENTRON C1S meters
built after this date will incorporate the new LCD. The following sections describe
both the new LCD and the old LCD. The information on the pre-June 2003 LCD is
provided for users who purchased meters prior to the change. This display is no
longer available for order.
The pre-June 2003 LCD module is shown in Figure 4.5. Two separate versions of
the LCD are available. Both versions may be configured for either four or five digits
and will roll over at 100,000 kWh. The LCD is automatically adjusted for contrast
over the operating temperature range.
Figure 4.5 Pre-June 2003 LCD
4-4CENTRON Meter Technical Reference Guide
Operation: C1S Version
The non-segment check version displays only the kWh reading. A downward
pointing arrow on the LCD pulses at a rate equal to the energy consumption. The
arrow flashes on for 1 watthour and off for 1 watthour. This effectively produces
an equivalent Kh of 2.0.
Infrared LED Kh is 1.0.
Figure 4.6 LCD Display without Segment Check
A second version of the LCD is available which displays the kWh reading and a
segment check (see Figure 4.7). The display scrolls between the kWh reading and
segment check with 7 seconds of on-time for each display item.
Figure 4.7 LCD Display with Segment Check
The three triangle segments in the bottom right corner of the display represent a
watt disk emulator. This electronic load indicator will advance with each pulse,
since each pulse is equivalent to one watthour. Reverse power is indicated by a
reversal in the direction of the electronic load indicator.
CENTRON Meter Technical Reference Guide4-5
Operation: C1S Version
Post-June 2003 LCDs
The post-June 2003 LCD module is shown in Figure 4.8. This display uses five
7-segment digits, four icons to indicate the type of displayed data, and three icons
to represent a watt disk emulator. The display may be configured for either four or
five digits and will roll over at 100,000 kWh.
This module is compatible with the ZRO-C2A Resetter.
Figure 4.8 Post-June 2003 LCD
Non-Detented Register
The Non-Detented Register displays the delivered energy plus received energy.
Figure 4.9 Non-Detented Register
4-6CENTRON Meter Technical Reference Guide
Operation: C1S Version
Detented Register
The Detented Register addresses applications requiring the reading of delivered
kWh only. Received energy is discarded.
Figure 4.10 Delivered kWh with Detent Enabled
Net Register
The Net (kWh) Register addresses applications requiring residential net metering
points. Net kWh is the delivered kWh to the customer minus any received kWh
from the customer. Net metering emulates a non-detented J5 meter.
Figure 4.11 Net kWh
Segment Check
The Segment Check Register addresses applications requiring display scrolling
between kWh and a full segment check. See "Display Timing" on page 4-8 for
factory programming options.
Figure 4.12 Segment Test
CENTRON Meter Technical Reference Guide4-7
Operation: C1S Version
Although the DEL and REC indicators are ON during segment check, they are not currently used.
Factory Programming Options
Display Timing
The display will scroll between the billing register and the segment check mode
based on the factory programming option.
OptionDescription
17 second billing register display, 1 second blank, 7 second segment check display (7/7)
27 second billing register display, 1 second blank, 1 second segment check display (7/1)
3Only the billing register is displayed (7/0)
Digits and Multipliers
The following digit and multiplier settings are available for factory programming:
•4 digits x 1 kWh
•4 digits x 10 kWh
•5 digits x 1 kWh
4-8CENTRON Meter Technical Reference Guide
Chapter 5Operation: C1SD, C1ST, and C1SL Versions
The CENTRON meter is available with interchangeable personality modules that
snap-into the standard CENTRON metrology base. The three multifunction
modules available include the following versions:
•C1SD—a demand module
•C1ST—a Time-of-Use (TOU) module with demand
•C1SL—a load profile module with TOU and demand
Figure 5.1 C1SL Meter with Cover
These personality modules utilize the SCS protocol which allows the C1SD, C1ST,
and C1SL meters to mimic the Itron 200 Register Series product line for use with
existing systems.
Features
Features of these multifunction modules include:
•Non-Volatile Memory—Programming, register, and load profile data are
stored in the EEPROM during a power outage. The TOU and load profile
modules contain a battery that maintains the clock circuitry during a power
outage.
•Optical Port Communication—Each module can be programmed to
communicate 9600 or 4800 baud through the optical tower.
CENTRON Meter Technical Reference Guide5-1
Operation: C1SD, C1ST, and C1SL Versions
•Self-Read Capability—Billing data can be stored automatically at
programmable times to be read later.
•Expansion Capability—An expansion port is available for future functions.
•Bidirectional Metering—All three multifunction versions are capable of
measuring and displaying forward and reverse energy only (kWh). These
modules have two separate registers; one for forward kWh and one for reverse
kWh. When the meter is programmed with electronic detent, both the forward
kWh register and the reverse kWh register will be utilized. When the meter is
programmed to be undetented, the forward and reverse energy will
accumulate in the forward kWh register.
The C1SD, C1ST, C1SL modules are available with an LCD display and a
polycarbonate cover. The cover contains the optical port adapter and demand
reset button.
Controls and Indicators
All controls and indicators are shown in Figure 5.2. For detailed instructions about
a feature or control, refer to the appropriate subsection.
Magnetic Reed
Switch
LCD Display
Annunciators
Test LED
Test Mode
Switch
Optical Tower
Demand Reset
Figure 5.2 C1SL Controls
5-2CENTRON Meter Technical Reference Guide
Modes of Operations
Normal Mode
Operation: C1SD, C1ST, and C1SL Versions
When the C1SD, C1ST, and C1SL modules are powered, they automatically enter
the normal display mode, perform self-diagnostics and display any appropriate
error codes. If no error codes are detected, an unprogrammed module will
alternate between CNTRON and Segment Test. A programmed module will
scroll through the Normal display sequence, displaying each selected quantity,
annunciator, and code number for the programmed duration.
The C1SD, C1ST, and C1SL modules each have three modes of operation:
•Normal
•Alternate
•Test
In Normal mode, the module display automatically sequences through the
programmed displays and annunciators in the programmed sequence. Each
parameter is displayed for the program-specified period (from 1 to 15 seconds),
followed by a blank display for one second. Only the annunciator appropriate to
the selected module display can appear while its data is displayed. Each display
can have a two-digit identifier. If selected, this code can be programmed to be any
number from 00 to 99.
Calculations are performed to obtain programmed quantities. Specific details of
the calculated values are covered under Programmable Functions in this section.
The meter will continue to operate in Normal mode until power is disconnected,
the Alternate display sequence is initiated, Test mode is selected, or an error
condition occurs.
Alternate Mode
Test Mode
The Alternate mode provides an additional set of customizable display items that
are not typically used for billing applications. The Alternate mode is accessible
only from the Normal mode and is activated using either the magnetic reed switch
or a meter programming device. To activate the Alternate mode using the magnetic
reed switch, move a small magnet (approximately 30 gauss) near the reed switch
located at the 10 o'clock position on the side of the module (see Figure 5.2). The
magnetic reed switch can be accessed with the meter cover in place. To activate
the Alternate mode with a programming device, refer to the PC-PRO+
documentation. Immediately upon activation, Alternate mode is indicated by a
flashing ALT annunciator. The ALT annunciator will not appear if there are no
Alternate mode display items programmed.
Once the Alternate mode has been selected, the display will sequence once
through the alternate program items and return to the Normal display sequence.
The quantities displayed are selected during programming and have the same
display timing as in Normal mode. Like the displays in Normal mode, each display
in Alternate mode can have a two-digit identifier, programmable from 00 to 99. The
calculations and operations performed in Alternate mode are identical to those in
Normal mode.
Selecting the Test mode causes the current interval demand to be compared to the
stored maximum demand and the current billing data to be transferred to nonvolatile memory. If the current interval demand value is greater than the maximum
demand, the current interval demand becomes the maximum demand. All Test
CENTRON Meter Technical Reference Guide5-3
Operation: C1SD, C1ST, and C1SL Versions
mode program parameters are then retrieved from nonvolatile memory for use in
the Test mode. In the C1SL version, a status bit is set to indicate the register was
placed in Test mode.
The Test mode can be activated while in either Normal or Alternate mode using the
Test mode switch (see Figure 5.3) or a meter programming device. To activate the
Test mode with a programming device, refer to the PC-PRO+ documentation.
Immediately upon activation, the Test mode is indicated by a flashing “TEST”
annunciator in the lower left hand corner of the module display. The TEST
annunciator will not appear if there are no Alternate mode display items
programmed.
Test Mode
Switch
Figure 5.3 Test Mode
Refer to the PC-PRO+ documentation for information on selecting the Test mode
using a programming device. A programmable “Time-Out Length” from 1-to-99
minutes is available. After the programmed Time-Out Length has ended, the
register will automatically exit the Test mode. The demand test interval is
initialized whenever the Demand Reset button is pressed.
The magnetic reed switch, when activated, advances the Test mode display to the
next quantity. Calculations performed in Test mode are performed in the same
manner and based on the same program parameters as in Normal mode with the
exception of interval (subinterval) length. Test mode interval length and the
number of subintervals are specified independently for Test mode. The results are
displayed according to the display configuration selected when the register is
programmed. To exit the Test mode and return to the Normal mode, do one of the
following:
•De-energize the meter.
•Push the Test mode button.
•Wait for the selected Test mode time-out to occur.
Calculated values performed in Test mode are not added to previous billing values
or stored for retrieval. After exiting Test mode, all billing data previously
transferred to nonvolatile memory is retrieved, an End of Interval (EOI) is
initiated, and a new demand interval begins.
Any time-dependent events such as rate switches, self-read, or daylight savings
time that occur while the meter is in Test mode are performed when the Test mode
is exited.
5-4CENTRON Meter Technical Reference Guide
Low Power Mode
Displays
Operation: C1SD, C1ST, and C1SL Versions
The demand, TOU, and load profile modules are shipped from the factory in low
power mode unless factory programming is specified at time of order. This mode
consists of a default program and minimizes drain on the battery. The user can
place the meter in low power mode by performing a three button reset or by
programming the meter with the programming software as a demand-only meter.
While the module is on battery carryover, the display will show “on battry” while
the power is off. This can be observed by viewing the display at an angle at close
range.
Low power mode can be verified in one of the following ways:
•By observing that the minutes on battery counter does not increase during a
power outage.
•By observing the display during a power outage (from close range at an angle)
and verifying that the display does not show “on battry”.
See "Three Button Reset" on page 5-27 for instructions.
A nine-digit liquid crystal display, with a variety of annunciators, is provided on
these multifunction personality modules (see Figure 5.4).
Figure 5.4 Display
Six large digits are available to display all billing and informational data. Three
decimal points are provided for programmable resolution of billing data.
Three small digits in the upper left-hand corner of the display are used to provide
code numbers to identify any display item. These three digits are used along with
the six data digits to display ID numbers such as the meter serial number and user
fields.
There are three triangle segments in the bottom right corner of the display that
represent a watt disk emulator. This electronic load indicator will advance with
each pulse, since each pulse is equivalent to one watthour. Reverse power is
indicated by a reversal in the direction of the electronic load indicator.
Directly below the three code number digits is the Test mode annunciator (TEST).
This annunciator will flash on and off once per second whenever the meter is in
Tes t m o d e.
On the far left of the bottom line is the Alternate mode annunciator (ALT). This
annunciator will flash on and off once per second whenever the meter is in
Alternate mode.
To the right of the Alternate mode annunciator are the TOU rate indicators (A, B,
C, D, Total). These indicators correspond to the four programmable TOU and
TOTAL rate. The TOU rate indicators can be programmed to be displayed with the
CENTRON Meter Technical Reference Guide5-5
Operation: C1SD, C1ST, and C1SL Versions
appropriate energy and demand quantities. When an energy or demand quantity for
the currently active TOU rate (A, B, C, or D) is displayed, the corresponding TOU
rate indicator will flash on and off once per second.
To the right of the TOU rate annunciators is the kWh annunciator. This annunciator
can be programmed to display with any energy quantity. The kWh annunciator can
be programmed to display as kW with any demand quantity.
The EOI annunciator is located to the right of the kWh annunciator. This
annunciator will turn on for four seconds at the end of each demand interval (or at
the end of each subinterval when rolling demand is used).
Programmable Functions
The CENTRON can be programmed using Itron programming software: PC-PRO+
or PC-PRO+ 98.
Table 5.1 describes each display item and indicates the display mode in which each
is available. The display items and sequence of their display, along with any desired
annunciators or Identification (ID) code numbers, are selected during the
programming process. Detailed information on these display items can be found in
the PC-PRO+ documentation.
Table 5.1 LCD Display Items
Display Mode
Display ItemNormalAlternateTest
kWhxxx
Maximum kW Demandxxx
Cumulative kW Demandxx
Continuous Cumulative kW Demandxx
Previous Interval kW Demandxxx
Self Read kWhxx
Self Read kW Demandxx
Last Season Billing Values (TOU only)xx
Present Interval Demand kW Demandxx
Segment Testxx
Time Remaining in (Sub) intervalxx
Meter ID (up to two 9-digit fields)xx
User Defined Fields (up to three 9-digit fields)xx
Firmware Versionxx
Software Versionxx
Number of Times Programmedxx
Number of Demand Resetsxx
5-6CENTRON Meter Technical Reference Guide
Operation: C1SD, C1ST, and C1SL Versions
Table 5.1 LCD Display Items
Display Mode
Display ItemNormalAlternateTest
Number of Power Outagesxx
Number of Days Since Demand Resetxx
Demand (Sub) interval Lengthxx
Register Full Scale Valuexx
Kh Valuexx
Demand Threshold Valuexx
P/DR Valuexx
Register Multiplierxx
Date (C1ST and C1SL version only)xx
Time (C1ST and C1SL version only)xx
Day of Week (C1ST and C1SL version only)xx
Register Display Options
Date of Last Reset (C1ST and C1SL version only)xx
Time of Last Reset (C1ST and C1SL version only)xx
Time on Battery Carryover (min) (C1ST and C1SL
only)
Program ID Numberxx
TOU Schedule ID (TOU only)xx
Input Pulse Countx
Previous Interval Pulse Countx
Time Remaining in Test Modex
xx
All calculated billing quantities to be displayed are specified through the
programming software. The following billing quantities are available for display in
the Normal and Alternate modes:
•kWh
•Received kWh
•Max kW Demand
•Cumulative kW Demand
•Continuous Cumulative kW Demand
•Previous Interval kW Demand
•Self-read kWh
•Self-read kW Demand
CENTRON Meter Technical Reference Guide5-7
Operation: C1SD, C1ST, and C1SL Versions
Energy and demand registers can be programmed to be displayed in any of the
specified formats (see Table 5.2).
Table 5.2 Register Display Formats
3 Digits4 Digits5 Digits6 Digits
X.XXXXX.XXXXXX.XXX
X.XXXX.XXXXX.XXXXXX.XX
Demand
EnergyXX.X
*indicates floating decimal point format
XX.XXXX.XXXXX.XXXXXX.X
XXXXXXXXXXXXXXXXXX
X.X.X*X.X.X.X*XX.X.X.X*XXX.X.X.X*
XXX
XXX.X
XXXX
XXXX.X
XXXXX
XXXXX.X
XXXXXX
Self Reading
The C1SD is capable of storing one block of self-read data consisting of kWh and
maximum kW. The TOU versions, the C1ST and C1SL, will store one block of self
read data consisting of kWh and kW for all rates when a self-read is performed.
Self-read data is displayable in Normal or Alternate mode.
A self-read is programmed to initiate in one of three ways:
•Read on manual or electronic demand reset. When a demand reset is initiated,
all energy and maximum demand quantities are immediately transferred to
non-volatile memory.
•Read on a programmed day of the month (C1ST and C1SL only). A specified
date (1st - 28th) can be programmed into the meter to indicate the exact day
that a self-read is to be performed. On this date at 00:00 hours, register
readings are transferred to nonvolatile memory.
If desired, an automatic demand reset can be performed after this self-read.
Only the first 28 days of the month can be selected since February has only 28 days.
•Read on a programmable number of days since the last manual or automatic
demand reset (C1ST and C1SL only). If the selected number of days (1 to 150)
passes without a demand reset, a self-read is initiated.
If desired, an automatic demand reset can be performed after this self-read.
5-8CENTRON Meter Technical Reference Guide
Operation: C1SD, C1ST, and C1SL Versions
Last Season Registers
For a C1ST or C1SL meter, Last Season Registers are selectable in the
programming software. For every Current Season Register there is a Last Season
Register for the same quantity. Last Season registers are stored in memory when a
season change occurs. Last Season registers are designated as LS in the
programming software. Last Season Registers are selectable for display in Normal
and Alternate modes.
Operating Parameters
Programmable parameters establish the meter’s configuration and define its
operation in Normal, Alternate, and Test modes (see Table 5.3). Only parameters
specific to the Test mode are displayable in Test mode. Parameters that can be
uploaded using a reading device, but cannot be displayed on the meter are
indicated with an asterisk.
Table 5.3 Programmable Parameters
ParameterDescription
Display Scroll Time *
Cold Load Pickup Time *(CLPU)
Power Outage Length Prior to CLPU *
Normal Mode Demand Interval Length
Test Mode Demand Interval Length*
Normal Mode Number of Subintervals*
The number of seconds (1 to 15) that each item is to be
displayed before the next item appears.
The number of minutes (0-255) before demand
calculations are restarted after a recognized power
outage occurs. Setting this value to zero will cause
demand calculations to start immediately following a
power outage.
The number of minutes (0 to 255) that power must be
out for the CLPU to take effect. Defining this value as
zero will cause CLPU to be activated after any
recognized power outage.
The time in minutes (1 to 60) that each demand interval
lasts before a new interval begins. Valid interval lengths
are 1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, and 60 minutes.
The time in minutes (1 to 60) that each Test mode
demand interval lasts before a new interval begins. Valid
interval lengths are 1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30,
and 60 minutes.
The interval length divided by the sub-interval length is
equal to the number of subintervals. Valid entries are
from 1 to 10 and must be evenly divisible into the
demand interval length. For block demand, the number
of subintervals is 1.
The interval length divided by the sub-interval length is
equal to the number of subintervals. Valid entries are
Test Mode Number of Subintervals*
from 1 to 10 and must be evenly divisible into the
demand interval length. For block demand, the number
of subintervals is 1.
CENTRON Meter Technical Reference Guide5-9
Operation: C1SD, C1ST, and C1SL Versions
Register Full Scale
Test Mode Timeout
Table 5.3 Programmable Parameters
ParameterDescription
A kW demand value that defines the maximum rated
demand for a particular meter installation. Valid entries
range from 0 to 999999.
The number of minutes the meter will remain in Test
mode before exiting to Normal mode. This timeout
function is active when Test mode has been activated via
remote communications. Valid entries range from 1 to 99
minutes.
Operating Frequency*
Line or Crystal Sync*
Register Multiplier
Optical Communications Baud Rate*
Expansion Port Comm. Baud Rate*
*Indicates parameters that can be uploaded to a reading device but cannot be displayed.
The operating frequency must be programmed to 50 Hz
or 60 Hz line operation.
The real time clock can be synchronized off the input line
frequency or the internal crystal.
A programmable value that is used in calculations of
energy and demand readings. This can be used by
setting the register multiplier equal to the CT ratio times
the PT ratio of the installation for primary read meters.
Valid entries are from 1 to 9999.
Note: Energy and demand display formats should be
adjusted accordingly.
The optical communications default baud rate is 4800
baud, however, a rate of 9600 baud is selectable.
The expansion port communications default baud rate is
2400 baud; however, rates of 300, 1200, 2400, 4800,
and 9600 baud are selectable.
Informational Data
The following items are for information purposes (see Table 5.4). All informational
data, except those items indicated by an asterisk, can be displayed in Normal and
Alternate modes.
Table 5.4 Information Data Items
ItemDescription
Time and Date of Maximum Demands
(C1ST and C1SL only)
Time Remaining in (Sub) interval
Segment Test
The time and date that each maximum demand occurred
for A, B, C, D and Total Rates.
The amount of time in minutes and seconds before the end
of the current demand interval.
The display illuminates all segments and selected
annunciators on the LCD in order to verify proper operation.
The watt disk emulator continues to function normally.
5-10CENTRON Meter Technical Reference Guide
ItemDescription
Meter ID Numbers 1 and 2
User Fields
Firmware Revision
Software Revision
Operation: C1SD, C1ST, and C1SL Versions
Table 5.4 Information Data Items
Two separate nine digit display items that can be used to
identify the meter with an alpha character displayed as a
dash, a space displayed as a blank, and a number
displayed as the appropriate value.
Up to three separate user fields are available to display any
desired numerical information. Each user field can be up to
nine digits in length with an alpha character displayed as a
dash, a space displayed as a blank, and a number
displayed as the appropriate value.
A sequential number identifying the firmware revision level
of the meter. This number is automatically provided and
does not require operator input.
A sequential number identifying the revision level of the
software used to program the meter. This number is
automatically provided by the programming software and
does not require operator input.
Number of Times Programmed
Number of Power Outages
Number of Demand Resets
Number of Days Since Demand Reset
(C1ST and C1SL only)
Date and Time of Last Reset (C1ST and
C1SL only)
Date and Time Last Programmed (C1ST
and C1SL only)
Date (C1ST and C1SL only)The current date recognized by the meter
Time (C1ST and C1SL only)
Day of Week (C1ST and C1SL only)
A counter identifying the number of times (up to 9999) the
meter has been programmed.
A counter identifying the number of times (up to 9999) the
meter has recognized a power outage.
A counter identifying the number of times (up to 9999) a
demand reset has occurred.
A counter identifying the cumulative number of in service
days since the last demand reset.
The date and time of the last demand reset.
The date and time the meter was last programmed.
The current time recognized by the meter.
Note: For time of occurrence registers, time is displayed as
HH:MM:SS. All dates are displayed in the format chosen in
the programming software.
A single digit denoting the current day of the week is
displayed where Monday is denoted by a one and Sunday
by a seven.
Time on Battery (C1ST and C1SL only)
Program ID Number
TOU Schedule ID Number (C1ST and
C1SL only)
A counter identifying the cumulative number of minutes, 0
to 999,999, the meter has been in battery carryover mode.
A three digit number identifying the program downloaded to
the meter.
A three digit number identifying the TOU rate schedule
downloaded to the register.
CENTRON Meter Technical Reference Guide5-11
Operation: C1SD, C1ST, and C1SL Versions
Table 5.4 Information Data Items
ItemDescription
TOU Expiration Date *
Register Full Scale Value
Demand Threshold Value
Mass Memory Size * (C1SL only)
Note: * Indicates parameter that can be uploaded to a reading device but cannot be displayed.
A date that indicates when the register’s TOU schedule will
no longer be valid.
A kW demand value that represents the maximum rated
demand for a particular meter installation. Exceeding this
value triggers error code 100000.
A programmed threshold value in kW that determines when
the demand threshold output turns on.
The amount of mass memory actually being used for
recording of interval data. Valid entries are 0 to 32K, in 8K
increments.
Test Mode Data
The following items shown in Table 5.5 can be displayed in Test mode.
Table 5.5 Test Mode Data Items
ItemDescription
Time Remaining in the (Sub) interval
The amount of time in minutes and seconds before the end
of the current Test mode demand interval.
The maximum demand since the meter was put into Test
Maximum kW
Previous kW
Input Pulse Count
Previous Interval # of Input Pulses
kWhThe energy accumulated in Test mode.
Present (Accumulating) kW
Time Remaining until Test Mode
Timeout
mode. This value will be set to zero each time a demand
reset is performed.
The kW demand of the previous Test mode subinterval/
interval.
The number of pulses that have been received since the
last reset in Test mode.
Note: The display will be updated with each input pulse.
The number of pulses received during the last complete
interval or subinterval in Test mode.
The calculated demand value as it increases from the start
of a demand test interval to the end of the subinterval/
interval.
The amount of time in minutes and seconds before the
programmed Test mode timeout counter will expire.
5-12CENTRON Meter Technical Reference Guide
Programming the Meter With a 200 Series Program
A CENTRON meter can be programmed using an existing Series 200 program. This
procedure is a two-step process. First, export the 200 Series program you want to
use to a CENTRON file format and then import that file into PC-PRO+ as follows:
1Open the Program Editor.
2Select File | Export.
The Export screen shown in Figure 5.5 is displayed.
Operation: C1SD, C1ST, and C1SL Versions
Figure 5.5 Program File Export
3Select the 200 Series program to export from the list of available Programs.
4Click OK.
The Program File Export Type screen is displayed.
CENTRON Meter Technical Reference Guide5-13
Operation: C1SD, C1ST, and C1SL Versions
Figure 5.6 Program File Export Type
5Select CENTRON export format as shown in Figure 5.6 above.
6Click OK.
The file you selected in Figure 5.5 is converted to a CENTRON format. The
program ID remains the same, but the file type becomes CENTRON.
7Select File | Import.
The Import screen shown in Figure 5.7 is displayed.
Figure 5.7 Import Screen
8Select the CENTRON program to import from the list of available EXP files.
9Click OK.
The program is loaded into the Program Editor. Edit as necessary before
saving and using to program the meter.
5-14CENTRON Meter Technical Reference Guide
Demand Reset
Operation: C1SD, C1ST, and C1SL Versions
A demand reset can occur in both Normal and Alternate modes.
A demand reset can occur in two ways:
•Through the optical port using a compatible programming device
•With the standard push-button demand reset switch located on the face of the
meter (see Figure 5.2)
When a demand reset is initiated, the following events occur:
•As an indication of a demand reset, the display flashes all eights for six
seconds.
•The current maximum demand values are added to the corresponding
Cumulative Demand values.
•A self-read is performed (if selected).
•All Maximum Demand values are reset to zero. All corresponding times and
dates of maximum demands are cleared (C1ST and C1SL only).
•The number of demand resets is increased by one.
•The number of in-service days since the last reset is set to zero.
•The time and date of the last reset is updated (C1ST and C1SL only).
•The normal mode display resumes. Exception is when in test mode, the display
resumes with next item in display list.
As a security feature, additional manual demand resets are prevented for 60
seconds following a demand reset.
Time-of-Use
TOU Schedules
Calendar Schedule
When a demand reset is performed on a meter programmed for Block Demand, the current
interval becomes the first interval in the next billing period. For Rolling Demand, all previously
completed subintervals are zeroed. The current subi nterval becomes the first subinter val in the
next billing period. In Test mode, a demand reset will initialize the demand test interval.
The Time-of-Use capability is available on the C1ST and C1SL personality modules.
It requires additional circuitry to store TOU schedule information and a battery for
time-keeping purposes during power outages. Schedule information is
programmed on a PC using the PC PRO+ software packages.
When using TOU functions on a meter, energy and demand registration are
segregated into time blocks during the day. Each time block can be one of four rate
periods. In addition to these four rate periods, a total rate is also available.
The calendar schedule contains all daily and yearly information necessary to
perform TOU metering. This schedule contains rate schedules, daily schedules,
seasons, holidays, and daylight savings time dates. For information on the entry of
these parameters into PC-PRO+, refer to the PC-PRO+ documentation.
CENTRON Meter Technical Reference Guide5-15
Operation: C1SD, C1ST, and C1SL Versions
Rate Schedules
Four independent rates are available for TOU registration-designated A, B, C, and
D. Only one of these rates can be active at a time. The Total register is always
active, regardless of the active rate period. The currently active rate is indicated by
a flashing rate-specific annunciator.
Daily Schedules
Up to four daily schedules are available. Each schedule defines the beginning and
ending time of each of the four available rate periods (A, B, C, and D). Up to 32
switch points per rate may be specified for each daily schedule.
Weekdays, Saturday, Sunday, and holidays can be assigned to one of the four daily
schedules. Therefore, one to four daily schedules may be used in any combination
with the days of the week.
Seasonal Schedules
A season is a period of continuous days during the year when a particular rate
schedule is in effect. The year can be divided into a maximum of eight seasons. If
multiple seasons are not used, the TOU schedule contains one year-round season.
The Daily Schedules can be defined differently for each season. Up to eight Season
Change dates are specified for each year in the Calendar Schedule.
Season changes occur at midnight of the Season Change date (where midnight
corresponds to 00:00 hours) or can be programmed to occur at the first demand
reset following the Programmed Season Change date.
Registers
Holiday Schedules
Up to twenty-two holidays can be designated per year in the Calendar schedule.
One of the four Daily schedules is assigned to each of the Holidays in the Calendar
Schedule.
Daylight Savings Time
Daylight Savings Time switch points occur at 2:00 A.M. on the first Sunday in April
and the last Sunday in October. These dates are pre-assigned in the Calendar
Schedule; however, they can be modified by the user. The user can also elect not to
recognize Daylight Savings Time and operate the meter in standard time only.
Current Season Register
All energy and demand registers selected for the active season are considered
current season registers. If a single rate schedule is applicable year-round, then
only current season registers are used.
5-16CENTRON Meter Technical Reference Guide
Operation: C1SD, C1ST, and C1SL Versions
Last Season Registers
Last Season Registers are selected when two or more seasons are used during the
year. For every Current Season Register there is a Last Season Register for the
same quantity. Last Season Registers are designated LS in the programming
software. Last Season Registers can also be selected for display in Normal and
Alternate display modes.
Operation
At the end of a specified season, all Last Season Registers are updated with
Current Season register data. The meter can be programmed to activate an
automatic demand reset at a season change. A season change can be programmed
to occur at midnight at the beginning of the programmed Season Change date or at
the first demand reset following the Season Change date.
Season Change
The following events take place when an automatic demand reset occurs at season
change:
•The Current Season energy registers are copied directly to the Last Season
energy registers.
•The Current Season maximum demand registers are copied directly to the Last
Season maximum demand registers and added to the cumulative demand
registers.
•After the demand reset, the maximum demand registers are reset to zero. Both
the cumulative and the continuous cumulative demand registers are copied to
the Last Season cumulative and continuous cumulative demand registers,
respectively.
If there is no demand reset at season change, all current season registers are
directly copied to Last Season registers at season change but no current season
registers are zeroed.
Load Profile Specifications
Capacity
The C1SL module provides 32k bytes of EEPROM for one channel of interval load
profile data. The amount of installed EEPROM actually used for load profile
recording is programmable from 1 to 32k bytes in one kbyte increments.
34 bytes of the 32k bytes is reserved for firmware and software parameters.
Bit Resolution
The mass memory is configured for 12 bit data resolution. Equivalent pulse count
resolution per interval is as follows:
Bits = 12
Pulse Counts = 4096
CENTRON Meter Technical Reference Guide5-17
Operation: C1SD, C1ST, and C1SL Versions
Interval Lengths
The load profile records data on a block interval basis. The interval length is
programmable: 1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, or 60 minutes. This interval length is
independent of the interval length chosen for displayed demand quantities.
Power Outage
The C1SL module can flag an interval when a power outage exceeds a specified
number of seconds. The power outage duration is programmable from 0 to 255
seconds.
Channel Configurations
The Load Profile register has one channel of interval load profile data. This
channel corresponds to kWh. The pulse constant is programmable from 0.02 to
99,999 watthours per pulse in 0.01 increments. This pulse constant applies to
secondary readings only. For example, a watthour pulse constant of 1.8
corresponds to 1.8 watthours per pulse.
Some example pulse weight calculations:
Example 1: Calculation of Pulse Weight
If the customer pulls a 240V, CL200, singlephase, Form 2S electromechanical meter
from service, with the following:
Meter Kh = 7.2 watthours/disk revolution
Pulse Initiator = 4 pulses/disk, revolution
then this electromechanical meter has the following pulse weight (PW):
PW
Kh
-------------
PDR
7.2 watt hours
⎛⎞
--------------------------------------
⎝⎠
disk revolution
1.8 watt hours
--------------------------------------
PW
=
pulse
4 pulses
⎛⎞
--------------------------------------
⁄==
⎝⎠
disk revolution
If this meter is replaced by a Load Profile register of the same form number,
voltage and current ratings, and if the utility wants the register to operate the same
way, the pulse weight would be entered in the customer files as 1.8 watthours per
pulse.
Example 2: Calculation of Pulse Weight
A Load Profile register on a singlephase, 240V, CL200, meter is programmed so that
kWh is recorded into mass memory. The maximum 12-bit data resolution is desired
for 15 minute intervals.
First, calculate the maximum watthour accumulation during 15 minutes intervals:
Wh Max,240volts 200A 1phase 0.25×××=
Wh Max,12 000 watt hours,=
5-18CENTRON Meter Technical Reference Guide
Operation: C1SD, C1ST, and C1SL Versions
The maximum number of pulses is 4095; therefore, the smallest pulse weight (PW)
that can be used is:
Data Storage
PW Min,
12 000Wh,
-----------------------------
==
4095P
2.94Wh
---------------------
Pulse
The Load Profile register stores data in mass memory at the end of each interval.
This data stored is the pulse data for that interval. This process continues for each
interval until sixty intervals have been recorded. The mass memory is grouped into
segments of sixty intervals defined as a record or block. In addition to the profile
data, each record contains the following information:
Time Tag
Power Outage
Status Bits
Time Adjust
Saturation
RAM Error
Field TestStatus bit is set if Test mode is activated during an interval.
Register Readings
Specifies the month, day, and hour of the end of the data
record (or block).
Status bit is set for each interval during which a power
outage occurs (interval status).
There are four types of status bits written into each data
block:
Status bit set along with power outage bit when time is
adjusted with Load Profile running.
Status bit is set when the pulse count for any interval in
the block exceeds 4,095 pulses.
Status bit is set if any memory address within the record
fails the memory check (block status).
A register reading is maintained in the data record to be
used for data validation. This register reading is updated
at the end of each interval.
Recording Duration
Use the following equation to determine the recording duration for the load profile
register:
M1024×
Duration (days)
------------------------
107
M= Memory size in kilobytes
I = Interval Length in minutes
Truncate all decimals before multiplying by I/24.
CENTRON Meter Technical Reference Guide5-19
I
------
×=
24
Operation: C1SD, C1ST, and C1SL Versions
Table 5.6 Recording Duration for 32Kb
Optional Features
Electronic Detent
Expansion Port
Interval Length (min)
112.75
225.50
563.75
10127.50
15191.25
30382.50
60765.00
Programming electronic detent prevents received energy from accumulating in the
delivered energy register. When detent is enabled, the received energy is
accumulated in a separate register.
A connector located on these personality modules provides the option of using
expansion modules (when available), such as the R300CD board in conjunction
with the C1SD, C1ST, and C1SL personality modules.
Recording Duration
(days)
Security Codes
Register security can be provided with primary, secondary, and tertiary security
codes that prevent unauthorized communication with CENTRON products. A
Primary security code allows complete access to the meter. A Secondary security
code allows full read access with limited write access to perform an automatic
demand reset and to access the Alternate and Test modes. A tertiary security code
allows read-only access. For more information about security codes, refer to the
PC-PRO+ documentation.
5-20CENTRON Meter Technical Reference Guide
Calculations
h
Energy
Operation: C1SD, C1ST, and C1SL Versions
Calculation of energy is continuously incremented by multiplying the energy pulse
weight by the measured energy. The energy pulse weight is calculated by the
following formula:
kwh
⎛⎞
kWh Pulse Weight
--------------- -
⎝⎠
Pulse
Kh 1000×Register Multiplier==
The energy in a given interval is the product of the number of pulses received
during that interval times the pulse weight:
kWh
⎛⎞
Energy kWh()Number of Pulses
----------------
×=
⎝⎠
Pulse
Demand
Calculation of demand is always based on rolling or block intervals. Demand
calculations use three constants; the watthour constant (Kh), the demand interval
length, and the register multiplier.
The weight of an incoming pulse is determined according to the following formula:
kW pulse weight
---------------
⎝⎠
pulse
Kh 1000 Register Multiplier 60/Dem. Int. Lengt
××⁄=
kw
⎛⎞
The demand in a given interval is the product of the number of pulses received
during that interval times the pulse weight:
Demand kW()Number of Pulses kW Pulse Weight×=
The Demand value is continuously compared against the stored maximum value. If
a demand value is greater than the corresponding maximum demand, it is saved as
the new maximum demand. If the demand value is less than the corresponding
maximum demand, it is discarded. At the beginning of an interval, the current
interval demand is reset to zero and new demand values begin accumulating.
CENTRON Meter Technical Reference Guide5-21
Operation: C1SD, C1ST, and C1SL Versions
Demand Calculations
Block Interval Demand
Block demand corresponds to the number of subintervals being equal to one. At
the end of every interval, the microprocessor compares the last completed block
interval demand value to the demand value in memory. If the new value is greater
than the stored value, the new demand value is stored as Maximum Demand. When
a demand reset occurs, maximum demands are reset to zero and the current
interval continues. C1SD will begin a new demand interval. New maximum
demand values are calculated.
Rolling Interval Demand
For rolling interval demand, the programmed number of subintervals make up the
demand interval. At the end of every subinterval, the microprocessor calculates a
demand value based on the last full demand interval. When a demand reset occurs,
all Maximum Demands are reset to zero along with all completed subintervals. The
current subinterval continues (unless C1SD) accumulating data and the new
maximum demand value(s) is (are) calculated for the next subinterval.
Cumulative Demand
When a demand reset is performed, Maximum Demand values are added to the
existing corresponding Cumulative Demand values and written into memory as the
new Cumulative Demand values. These values remain in storage until the next
demand reset.
Continuous Cumulative Demand
Continuous Cumulative Demand is the sum of Maximum and Cumulative Demand
at any time. The calculated interval demand is continuously compared to the
previous Maximum Demand. If this demand is a new peak, it is stored as a
Maximum Demand and adjusts the continuous cumulative register to reflect the
new demand. A demand reset signal clears the Maximum Demand value, but does
not affect the Continuous Cumulative reading.
Previous Interval Demand
Previous interval demand is the calculated demand from the most recently
completed demand interval. When using rolling interval demand, this quantity is
updated after each subinterval. Previous interval demand is not saved in nonvolatile memory. When an interval is completed the demand value is transferred to
the previous interval demand register for display. Upon power up or demand reset,
the previous interval demand register is set to zero and is updated when the first
subinterval is complete.
Present Interval Demand
The present interval demand value is the demand value at the present time
normalized to the demand interval length. Present demand reports the calculated
demand value as it increases from the start of a demand interval to the end of the
interval. For rolling demand intervals, present demand reports the calculated
demand value from the present subinterval as it is accumulating with the previous
set of subintervals.
5-22CENTRON Meter Technical Reference Guide
Power Procedures
Applying Power
Personality Modules are powered directly from line voltage via the board-to-board
connector. These modules are energized when AC power is present. During power
outages, the permanently installed lithium battery runs the clock circuit on C1ST
and C1SL versions. The battery normally lasts for the life of the meter. However, in
the unlikely event of a low battery notification, the battery or Register Module may
need to be replaced.
Do NOT remove the el ectronic s housi ng while the mete r is p owered. Li ne lev el voltag es
are present on the circui t board . Failur e to f ollow this proce dure coul d resu lt in seriou s
personal injury or death. The warning label should always be visible on the housing.
Battery Life (Load Profile & TOU)
The CENTRON TOU and Load Profile personality modules have a permanently
soldered battery present on their circuit boards. This battery powers the clock
when power is disconnected from the meter. The module program is transferred to
EEPROM for recall when power is restored.
The battery life is longer for the CENTRON TOU and Load Profile modules than
the J5 200 Series electromechanical hybrid meters. The capacity of the new battery
is larger than equivalent older products, and the current consumption is reduced
with new electronics technology.
In the process of determining this factor, battery life calculations are made
assuming worst case conditions for both the battery capacity (at the lowest end of
the manufacturer published initial limit) and the meter current consumption
(assuming all the components are at the maximum side of their published
tolerance).
Operation: C1SD, C1ST, and C1SL Versions
Meters shipped from the factory unprogrammed or meters removed from the field and given a
3-button reset will not use battery carryover time.
The CENTRON battery life is illustrated in Figure 5.8.
CENTRON Meter Technical Reference Guide5-23
Operation: C1SD, C1ST, and C1SL Versions
An explanation of Figure 5.8 is as follows:
The Available Battery Capacity line is a function of time. Recent changes made to
the design (optimized battery current consumption at the transition phase from AC
power ON to AC power OFF), allowed the CENTRON to further improve the
available battery budget over time.
With the estimated available battery capacity, a carryover capacity of 8 years is
shown by the cross over point between the Available Battery Capacity curve and
the Battery Usage when the meter is not powered curve.
A very small amount of current is required to keep the real time clock running
when the meter is not powered from the AC line. The clock is running from
battery power (when not powered from the AC line) when the meter is
programmed with a TOU or LP configuration that requires clock or calendar
functionality. An even smaller amount of current is required of the battery while
the meter is powered or is in low power mode. The meter is in low power mode
when the meter is programmed with a demand only configuration (no clock or
calendar functions) or when given a three button reset. The lower Current Draw
AC Power line on Figure 5.8 represents this lowest current (low power mode or AC
power). When the meter is either powered from the beginning of life or in low
power mode, the available battery capacity is not used until beyond 15 years of
service life.
The series of lines is intended to help the user to assess the battery life under
different usage profiles (time while the meter is not powered versus time while the
meter is powered).
The following examples illustrate usage of the below Battery Life Graph.
Figure 5.8 CENTRON C1ST/L Battery Life
Example 1
For example 1 (see Figure 5.9), the meter is unpowered (with battery running the
clock) for two years then installed in the field under AC power. Follow the Current
Draw: the Battery Power line from year zero to year two, then follow the Current
Draw: the AC Power line from year 2 to the right. This shows that the battery will
5-24CENTRON Meter Technical Reference Guide
Operation: C1SD, C1ST, and C1SL Versions
not cross the Battery Capacity line until beyond year 15. The battery is not
considered depleted until the Current Draw line crosses the Available Battery
Capacity line.
Figure 5.9 Example 1
Example 2
For example 2 (see Figure 5.10), the meter is unpowered (with battery running the
clock) for six years then installed in the field under AC power. Follow the Current
Draw: the Battery Power line from year zero to year six, then follow the Current
Draw: the AC Power line from year 6 to the right. This shows that the battery will
not cross the Battery Capacity line until after year 15. The battery is not
considered depleted until the Current Draw line crosses the Available Battery
Capacity line.
Figure 5.10 Example 2
CENTRON Meter Technical Reference Guide5-25
Operation: C1SD, C1ST, and C1SL Versions
Example 3
For example 3 (see Figure 5.11), the meter is unpowered (with battery running the
clock) for an infinite amount of time. This shows that the Current Draw line will
not cross the Battery Capacity line until past year 8.
Figure 5.11 Example 3
Low Battery Error
The TOU and LP module firmware counts minutes on battery (when the battery is
enabled) during power outages. Current production revision (10.30) firmware has
a hard coded limit which will trigger a Low Battery Error in the event that one year
of carryover has accumulated regardless of hardware revision. When a Low
Battery Error has been triggered on TOU or LP modules with part number 442701xxx, the module can be reprogrammed to clear the error. Alternatively, the Low
Battery Error can be set to be ignored via programming software. This is done by
opening the CENTRON program in PC-PRO+, and then selecting Displayable
Errors. When the list of displayable errors is shown, select Low Battery. The user
will be prompted to select Ignore, Scroll or Lock. Select Ignore and save this
configuration. Reprogram the meters with this saved file. If the meter is
programmed with the Low Battery Error set to Ignore, the error will be triggered in
the meter and stored in memory, but it will not be shown on the meter’s display.
An ignored error can be read via software. A Low Battery error will NOT stop
TOU or Load Profile functions in the meter. If the battery has reached its end of
life and does not have sufficient capacity to run the clock during a power outage,
only then will clock functions like TOU and/or Load Profile stop functioning if
programmed.
The minutes on battery counter can store up to 999,999 minutes. When this
number is exceeded, the counter will rollover to zero. Rollover of minutes on
battery counter will not clear the Low Battery error. Low Battery Error can only
be cleared by reprogramming the meter and setting the minutes on battery field to
a value less than 525,500 minutes.
5-26CENTRON Meter Technical Reference Guide
Three Button Reset
Operation: C1SD, C1ST, and C1SL Versions
Effectivity Date
Meters shipped after October 1, 2003 have this revision of hardware with extended
battery life capability. This revision of module can also be identified by the
inspection of the module part number etched into the module itself. This revision
has a part number of 442701-xxx. The previous revision with one year battery
carryover capability has a part number of 442079-xxx
To perform a three button reset, follow these steps:
Performing a three button reset returns selected program parameters to a default state.
1Remove power to meter.
2Remove the meter cover.
3Activate the magnetic reed switch using a small magnet positioned at the 10
o’clock point of the meter.
4Depress the test mode button and the demand reset button.
5Apply power to the meter while simultaneously performing steps 3 & 4.
6Remove the magnet; release the test mode and demand reset buttons after 3
seconds.
7The meter display should alternate between CNTRON and Segment Test if
the reset is successful.
8Replace the meter cover.
Option Boards
CENTRON R300CD Operation
The R300CD option provides two RF transmission messages for energy and
demand readings. It is programmed with two unit ID's, one for identifying energy
(kWh) related Standard Consumption Messages (SCMs), and one for demand
(kW). The even ERT ID number will always correspond to the energy value, and
the odd ID will always correspond to the demand value. Only the even ID number
will be displayed on the meter nameplate, and the demand ID will be the next
sequential number.
The R300CD transmits two different types of SCMs representing energy and
demand. This is the only mode of operation used by the R300CD. R300CD option
boards must be installed in a Time-of-Use (TOU) equipped (battery and full
calendar clock capability) CENTRON. The R300CD will interrogate the TOU
module once per minute and read the self read kWh and self read kW values. These
values will typically change only once per billing period.
CENTRON Meter Technical Reference Guide5-27
Operation: C1SD, C1ST, and C1SL Versions
The kWh value broadcast in its SCM shall have six (6) significant digits. The
R300CD converts the floating point BCD kW reading extracted from the
CENTRON self read register to a fixed implied decimal with two digits of
resolution to the right of the decimal point (.01 kW). The maximum kW measured
is therefore restricted to 9999.99 kW.
Figure 5.12 on page 5-28 is a block diagram of R300CD hardware. R300CD
hardware consists of two option boards: a control section and RF section. The
control section communicates to the TOU module at rate of once per minute using
the expansion port on the TOU module. The communication speed is fixed at 2400
baud in the control section and uses the SCS protocol. In each of the two SCMs
described, the respective parameter reported is converted to a binary format for
the RF transmission. No register information is saved in the R300CD option
boards. In the instance of a power outage, the option board will update the kW and
kWh values from the self read register upon power restoration.
The R300CD features the Itron patented method of tamper detection that senses
both meter removal and inversion. The removal tamper (RTPR) increments a
counter each time the meter is abruptly removed from a live meter socket. The
tamper counter utilizes a tilt switch to detect when the meter is removed from the
meter socket. The inversion tamper (ITPR) increments a separate counter each
time the meter senses an inversion. The inversion tamper will be incremented
when an inverted status is detected through a closed tilt switch upon power up.
Each of these tamper indications are then transmitted through the radio frequency
transmission.
TOU
Module
Meter Base
Figure 5.12 CENTRON TOU Personality Module with R300CD Option
Control
Board
RF Board
Programming the R300CD Meter
In order for the R300CD meter to operate properly, you must set certain
parameters. Incorrectly set parameters will result in improper operation of the
R300CD.
The R300CD option boards use either a Load Profile (LP) or Time of Use (TOU)
CENTRON personality module. In order for the R300CD to transmit it must have a
kWh register.
5-28CENTRON Meter Technical Reference Guide
Errors
Operation: C1SD, C1ST, and C1SL Versions
The meter will transmit zeros for kWh and kW until it is programmed. For detailed programming
instructions, see the PC-PRO+ documentation. Also refer to the CENTRON R300CD QuickInstall Guide.
The table below shows how fatal and non-fatal errors affect R300CD RF
transmission.
ErrorError CodeError Type
Low Battery000001Non-FatalYes
EEPROM 000010FatalYes
Reverse Direction007000Non-FatalNo
Clock010000Non-FatalYes
Full Scale Overflow100000Non-FatalYes
TOU Error020000Non-FatalYes
Load Profile Error030000Non-FatalYes
Metrology Error000004FatalYes
Stops RF
Transmission
CENTRON Meter Technical Reference Guide5-29
Operation: C1SD, C1ST, and C1SL Versions
Notes:
5-30CENTRON Meter Technical Reference Guide
Chapter 6Operation: C1SR Version
The Itron CENTRON C1SR is a one-way, unlicensed Radio Frequency (RF)
Personality Module that attaches to the CENTRON meter base (See Figure 6.1). It
offers a cost-effective solution for the endpoints in automatic and off-site meter
reading applications. The CENTRON C1SR operates similar to the existing R300
module that is utilized by the J5 electromechanical meter.
Standard Consumption Message (SCM)
Utilizing the 96-bit Itron® Standard Consumption Message protocol (SCM), the
C1SR provides the energy (kWh) consumption, module ID number, tamper
indications, meter type, and error checking information in each radio frequency
transmission. Within the 96-bit SCM, 26 bits are allocated to the module ID number
for meter identification (also referred to as ERT ID number). As of October 15,
1999, all CENTRON C1SR meters utilize 26-bit identification numbers.
The C1SR uses frequency hopping and transmits within the unlicensed 910 to 920
MHz band. In order to avoid interference from other devices, the transmission
frequencies and time interval between transmission cycles are completely random
in nature.
The C1SR is factory programmed with tuning information, module ID, tamper
indicators (ITPR and RTPR), meter type, energy consumption, and scaling factor.
The program and all register information are stored in non-volatile memory in the
event of a power outage. Upon power restoration, all of the information in the nonvolatile memory is restored to the appropriate registers.
Interval Data Message (IDM)
The Radio Frequency Personality Module allows meter data to be collected
automatically, helping to save time, improve reliability, increase accuracy, and
ensure data security.
The R300 IDM is a Radio Frequency Personality Module based on the CENTRON
solid-state metering platform. Kilowatt-hours and tamper data are reported
through RF transmissions. The R300 IDM module provides both baseline and
advanced data collection functionality, including interval data recording and
enhanced tamper reporting capability. The R300 IDM delivers the ERT Standard
Consumption Message to any of Itron’s radio-based data collection technologies,
including handheld computers (OMR), a vehicle-based Mobile AMR unit such as
the Mobile Collector, or a network data collection solution such as the Itron Fixed
Network or MicroNetwork. In addition, the R300 IDM is also capable of delivering
the Interval Data Message to the Itron Fixed Network AMR system to calculate
ANSI standard demand, time-of-use, and load profiling information.
CENTRON Meter Technical Reference Guide6-1
Operation: C1SR Version
Physical Description
Figure 6.1 C1SR
The C1SR personality module is constructed of a flame retardant printed circuit
board material which supports the discrete, surface-mounted, and integrated
circuit components. A microstrip etched on the circuit board serves as the RF
antenna. The C1SR personality module easily snaps into the meter module
mounting bracket. This module is then electronically attached to the metrology
board via a board to board connector. The following information is sent to the
personality module from the base metrology board:
•Line voltage
•Reference voltage
•Energy flow direction
•Energy pulse data
•Line frequency
The C1SR contains contacts on the module board, located at the 12 o'clock
position behind the LCD, for resetting the energy register and tamper counters.
This can be accomplished with the ZRO-C2A Resetter.
The C1SR uses a unique module identification number, provided by Itron. This ID
number is contained in each message transmission and is used by the handheld
and billing system to determine meter identity and location. This ID number, which
is contained on a bar-coded label, is placed on the LCD housing directly above the
LCD display.
6-2CENTRON Meter Technical Reference Guide
Registers
Display
Operation: C1SR Version
The C1SR personality module is only available with a liquid crystal display (LCD).
The LCD is automatically adjusted for contrast over the operating temperature
range.
Figure 6.2 C1SR LCD
This module can be configured to display either four or five digits of energy
consumption and will rollover at 100,000 kWh for both self-contained (Form 1S, 2S,
12S, 25S) and transformer rated meters (3S, 4S). The self-contained meters can be
programmed to display normal kWh consumption (5X1 register configuration) or
tens of kWh consumption (4X10 register configuration). If the C1SR is
programmed for a 4x10 display, a “Mult by 10" label is placed on the module to the
left of the LCD display. Thus, the actual energy consumption is obtained by
multiplying the value on LCD display by 10.
The transformer rated meters can be programmed to display either a 5xTR or
4xTR. In order to determine the actual energy consumption, the display reading
needs to be multiplied by the transformer ratio (TR). If the transformer ratio is 1,
then the reading on the display is the actual energy consumption.
Regardless of the register configuration, the transmitted energy will always be in a
5x1 configuration.
The LCD display contains an electronic load indicator (or watt disk emulator). The
disk emulator is three square segments in the lower right-hand corner of the
display, which scroll in the direction of energy flow.
Icons are illuminated on the display when the meter is programmed with a nonstandard algorithm. The LCD will display DET for detented energy. Icons for
delivered (DEL) and received (REC) are not used. NET metering functionality for
the R300 will be added in a future release. There is no additional indicator for the
standard undetented configuration (i.e., where reverse energy is accumulated in
the forward register).
Factory programmable multipliers are available for CL20 (x20, x40 and x80)
applications. This allows the meter to display and transmit via RF primary
readings. Meters are labeled accordingly when factory programmed.
The display will scroll between the billing register and the segment check mode
based on the factory programming option.
OptionDescription
17 second billing register display, 1 second blank, 7 second segment check display (7/7)
CENTRON Meter Technical Reference Guide6-3
Operation: C1SR Version
Electronic Detent
OptionDescription
27 second billing register display, 1 second blank, 1 second segment check display (7/1)
3Only the billing register is displayed (7/0)
The C1SR module displays energy in increments of whole values of kWh. Standard
operation for this module is to accumulate both forward and reverse energy flow
in the positive direction. However, the C1SR personality module is available with
an electronic detent that will cause the meter to ignore reverse energy flow.
Therefore, if the meter is inverted, the registers will accumulate in the forward
direction only, thus providing uni-directional operation. At the time of order, the
C1SR module can be selected to have a detent register.
When the meter is undetented, both forward and reverse energy will be
accumulated. Therefore, the electronic load indicator will flash at a rate equal to
the energy consumption, regardless of the direction of the energy flow.
When the electronic detent is enabled, only forward energy flow will be
accumulated. Thus, the single load indicator will not flash, nor will the meter
accumulate when reverse energy flow is present.
Net Metering
Resetting Values
Transmission Scheme
<coming from David>
The ZRO-C2A Resetter zeros both the energy registers and tamper counters by
direct connection to the C1SR module See also The ZRO-C2A Handheld Meter Resetter for the CENTRON C1S and C1SR Operating Instructions.
A transmission cycle contains a wait period before and after each message burst
and a period of random silent time. The silent time is determined by the scaling
factor, which sets a minimum and maximum silent time between each
transmission cycle.
The transmission frequencies (within the 910-920 MHz band), the frequency
hopping pattern, and the time interval between transmission cycles are completely
random in nature. This randomness provides a method for avoiding interference
with transmissions from other devices. Figure 6.3 shows an example of the
CENTRON C1SR transmission cycle containing one message burst.
6-4CENTRON Meter Technical Reference Guide
Operation: C1SR Version
.
Figure 6.3 CENTRON C1SR Transmission Cycle
FCC Regulations
Tamper Detection
The C1SR communicates in the unlicensed, 910-920 MHz band governed by the US
Code of Federal Regulations (CFR) Title 47, Part 15 Radio Frequency Devices, Sub
Part C Paragraph 249 Intentional Radiator.
Changes or modifications not expressly approved by Itron could void the users authority
to operate the equipment.
The CENTRON C1SR features the Itron patented method of tamper detection that
senses both meter removal and meter inversion. The removal tamper (RTPR)
increments a counter each time the meter is abruptly removed from a live meter
socket. The tamper counter utilizes a tilt switch to detect when the meter is
removed from a meter socket.
The inversion tamper (ITPR) increments a separate counter each time the meter
senses reverse power flow caused by meter inversion. The metrology board senses
reverse power flow and sends this status to the C1SR module. Although the C1SR
increments an inversion counter when reverse power flow is detected, the meter,
when undetented, will still accumulate the energy consumption in the positive
direction. Each of these tamper indications, along with the kWh consumption, is
then transmitted through the radio frequency transmission.
CENTRON Meter Technical Reference Guide6-5
Operation: C1SR Version
Testing the CENTRON C1SR Tamper Counter
SCM Testing
In order to test the power removal counter, the meter must sense a shaken
condition associated with a power outage.
1Place the meter in a socket.
2Apply power to the meter.
3Remove the meter from the live socket.
4Replace the meter in the socket.
The meter has incremented the removal tamper counter.
The C1SR uses the power outage (the meter being removed from a live socket) in
conjunction with the meter being shaken simultaneously to increment the power
removal counter.
In order to test the inversion counter, the meter must sense reverse current flow.
1Place the meter in the meter socket inverted (test LED pointing down).
2Apply a load to the meter in the forward direction.
The meter has incremented the inversion counter due to reverse energy flow
through the meter.
The inversion counter increments when the meter senses reverse current flow. The
metrology board senses reverse power flow and sends this status to the C1SR
personality module. The C1SR then increments the counter and transmits the
count.
As part of the 96-bit Standard Consumption Message, 4 bits are allocated for
tamper indications, which include the power removal and meter inversion
counters. The ReadOne
its equivalent value between 0 and 15. Table 6.1 shows the removal and inversion
information based on the reported tamper count. For example, a tamper count of 6
on the ReadOne Pro would translate as 1 meter removal and 2 meter inversions
since the last read.
®
Pro handheld reader converts the 4 bit binary number to
In order to test the power removal counter, the meter must sense a shaken
condition associated with a power outage.
1Place the meter in a socket.
2Apply power to the meter.
3Remove the meter from the live socket.
4Replace the meter in the socket.
The meter has incremented the removal tamper counter.
The C1SR uses the power outage (the meter being removed from a live socket) in
conjunction with the meter being shaken simultaneously to increment the power
removal counter.
In order to test the inversion counter, the meter must sense reverse current flow.
1Place the meter in the meter socket inverted (test LED pointing down).
2Apply a load to the meter in the forward direction.
The meter has incremented the inversion counter due to reverse energy flow
through the meter.
<additional tamper info coming from David>
Retrofitting the C1SR Personality Module
The CENTRON R300 is a one-way radio frequency personality module that
transmits within the unlicensed 910-920 MHz frequency band governed by the US
Code of Federal Regulations (CFR) Title 47, Part 15 Radio Frequency Devices, Sub
Part C Paragraph 249 Intentional Radiator. Any device operating within this
unlicensed frequency band must contain an FCC Identification number. Therefore,
the FCC ID Label included in the Retrofit Kits must be placed on the meter as
shown below.
CENTRON Meter Technical Reference Guide6-7
Operation: C1SR Version
Figure 6.4 C1SR FCC Label Location
Changes or mo dificat ions n ot expres sly a pproved by It ron could void the user’s au thorit y to
operate the equipment.
To retrofit an existing meter with an R300 module, follow "Retrofitting with
Personality Modules" on page 2-3.
R300 IDM
This section describes the Interval Data Messages (IDM) module of the CENTRON
meter. This module provides compatibility with Itron fixed networks (V2.0). The
changes consist of three main areas: addition of IDM, new message formats, new
received energy handling and possibly the measurement of VRMS and
transmission of the VRMS quantity in a second ERT message.
The IDM contains the SCM data. IDM stores 48 intervals of delivered kWh data
with the interval length set to five minutes.
Interval Data Message (IDM) Format
There are two formats for IDM messages. They are associated to two SCM message
types. The first pair is an ERT type 7 SCM and an ERT type 23 IDM message. ERT
type 7 indicates that the device sending this message supports transmitting a single
SCM with an XXXXX.XX format. The type 23 ERT indicates that it is an IDM
message with the format described in <find this: Appendix A, Table 2, ERT Type
23>.
The second pair is an ERT type 8 SCM and an ERT type 24 IDM message. ERT type
8 indicates that the device sending this message supports transmitting three SCM
messages with an XXXXX.XX format. The type 24 ERT indicates that it is an IDM
message with the format described in <find this: Appendix A, Table 3 - ERT Type
24>.
6-8CENTRON Meter Technical Reference Guide
IDM Tamper Detection
Operation: C1SR Version
Removal Tamper
Inversion Tamper
Reverse Rotation
Tamper
Power Loss Tamper
Reprogramming
Tamper
Physical Tamper
Encoder TamperThe lower two bits of the Removal Tamper Counter
Spare Tamper0 - Not used
Async Counters0 - Not used, Future use
Time OffsetSee "Time Offset" in section 7.9 Message Timing
This will be implemented by observing a tilt event in
close proximity to a power outage.
We will implement this by taking advantage of the tilt
switch. On power-up we do a prolonged read of the tilt
switch to see if it is inverted. If so then we can flag this as
an inversion and increment the counter. This will
distinguish it from a removal tamper which would
happen on a loss of power.
We will monitor the sign signal along with the energy
coming from the metrology to determine when the meter
is operating in the reverse direction and increment the
counter.
This will be implemented by incrementing the counter
each tme we power up.
0 - Not applicable because it will not be field
programmable.
On the 51ESS this is simply implemented as the lower 2
bits of the Inversion Tamper Counter. We will do the
same.
CENTRON Meter Technical Reference Guide6-9
Operation: C1SR Version
6-10CENTRON Meter Technical Reference Guide
Chapter 7Operation: C1SC Version
The Itron C1SC is a one-way transmitter used for the CellNet fixed network
technology. The personality module transmits a formatted data packet consisting
of the preamble, the utility billing ID, kWh information, and Cyclic Redundancy
Checks (CRC) to ensure message integrity. The module also features built in power
outage notification, reverse power flow detection, power restoration notification,
and redundant transmissions. The C1SC uses spread spectrum to broadcast its
message in the 902 to 928 MHz frequency range once every five minutes.
The C1SC is factory programmed to include the utility billing ID, LAN Address ID,
and Register configuration. The utility billing ID is a value decided upon by the
utility and CellNet. The LAN address is a value that is assigned by Itron and
programmed into every meter within the network. LAN addresses and utility billing
IDs are unique to each meter. Itron activates the LAN ID upon receipt of the meter
association file.
After programming, the module is tested to verify the operating system parameters
and FCC compliance. A final test is performed via RF to verify a correct LAN
address meter ID number of digits and RF signal.
Figure 7.1 C1SC
CENTRON Meter Technical Reference Guide7-1
Operation: C1SC Version
Physical Description
The C1SC is constructed of a flame retardant, glass-filled printed circuit board
material which supports the discrete, surface-mounted, and integrated circuitry
components. A slot antenna etched on the circuit board serves as the RF antenna.
The C1SC board snaps into the meter register mounting brackets to ease in the
installation of the board. The LAN address barcode and interpretation is placed on
the LCD housing for meter identification.
The C1SC personality module is attached to the metrology board using a board to
board connector. The following information is passed from the metrology board to
the C1SC:
•Line Voltage
•Reference Voltage
•Energy Flow direction
•Energy pulse data
•Line frequency
The C1SC has two additional labels called the meter change-out labels that are
affixed to the bottom of the meter. The change out labels are identical and contain
the AEP barcode information and a utility descriptor.
Transmission Scheme
The RF transmission is spread spectrum using Binary Phase Shift Keyed (BPSK)
modulation. A chipping signal is used to spread the carrier and actual data is onoff-keyed (OOK). The modulator output drives the amplifier chain that provides a
signal of approximately 100mW. The antenna is tuned for maximum efficiency at
the carrier frequency.
Figure 7.2 shows how messages are typically transmitted. In the example, an
interval packet made up of 18 intervals is transmitted every five minutes. Each
interval contains a pulse count equivalent to the energy consumption for a 2.5
minute interval. The interval packet transmission represents a sliding 45 minute
window of data.
Also shown in Figure 7.2, Interval packet 0 shows that the 2.5 minute interval is
transmitted in one of the 18 packets of 2.5 minute information. Interval packet 1 is
transmitted 5 minutes later and the selected 2.5 minute interval of data is now
transmitted as the 16th packet (numbered 15). The following packet slides the
information by two 2.5 minute intervals and continues for a total of nine
transmissions. The information is then no longer in the sliding 45 minute window.
7-2CENTRON Meter Technical Reference Guide
Operation: C1SC Version
e
kWh
(Pulses)
(Pulses)
2.5 minutes
2.5 minutes
(Interval
(Interval
Resolution)
Resolution)
Interval 0
Interval 0
kWh
Interval 1
Interval 1
Interval 2
Interval 2
C
ELLNET ELECTRICITY INTERVAL TELEMETRY
C
ELLNET ELECTRICITY INTERVAL TELEMETRY
0
0
1
1
45 minutes
0 1 2 3 4 5 6 7 8 9
0123456789
0 1 2 3 4 5 6 7 8 9
0123456789
0 1 2 3 4 5 6 7 8 9
0123456789
Interval 4
Interval 4
Interval 5
Interval 5
0 1 2 3 4 5 6 7 8 9
Interval 6
Interval 6
Interval 3
Interval 3
45 minutes
101112131415161
101112131415161
101112131415161
101112131415161
1011121314151
0123456789
0 1 2 3 4 5 6 7 8 9
0123456789
0 1 2 3 4 5 6 7 8 9
0123456789
0 1 2 3 4 5 6 7 8 9
0123456789
1
0
0
Interval packets contain 18 intervals
Interval packets contain 18 intervals
7
7
7
7
1011121314151
6
101112131415161
101112131415161
101112131415161
101112131415161
101112131415161
1
Intervals close every 2.5 minutes
Intervals close every 2.5 minutes
1
Endpoints transmit approx. every 5 minutes
1
Endpoints transmit approx. every 5 minutes
7
Transmissions are randomized over 5 minute period.
6
7
Transmissions are randomized over 5 minute period.
Each interval is transmitted nine times, thus nine times the redundency.
Each interval is transmitted nine times, thus nine times the redundency.
7
7
7
7
101112131415161
7
101112131415161
101112131415161
7
7
7
Time
Tim
FCC Regulations
Display Functions
101112131415161
Interval 7
Interval 7
Interval 8
Interval 8
Interval 9
0 1 2 3 4 5 6 7 8 9
0123456789
0 1 2 3 4 5 6 7 8 9
0123456789
Interval 9
0 1 2 3 4 5 6 7 8 9
0123456789
101112131415161
7
101112131415161
101112131415161
101112131415161
101112131415161
7
7
7
7
7
Figure 7.2 CellNet Telemetry
The C1SC communicates in the unlicensed 902-928 MHz band governed by the US
Code of Federal Regulations (CFR) Title 47, Part 15, Subpart C, Paragraph 247.
This device complies with Title 47, Part 15, Subpart C, Paragraph 247 of the FCC
rules.
The LCD is configured for five digits of energy consumption and will rollover at
100,000 kWh. The LCD is automatically adjusted for contrast over the operating
temperature range.
A watt disk emulator is located on the lower right hand corner of the display. The
indicator consists of three square segments in the lower right-hand corner of the
display, which scroll in the direction of energy flow. Figure 7.3 below illustrates
this revision.
CENTRON Meter Technical Reference Guide7-3
Operation: C1SC Version
Figure 7.3 C1SC LCD
The display will scroll between the billing register and the segment check mode
based on the factory programming option.
OptionDescription
17 second billing register display, 1 second blank, 7 second segment check display (7/7)
27 second billing register display, 1 second blank, 1 second segment check display (7/1)
3Only the billing register is displayed (7/0)
Resetting Values
The C1SC can be reset using the CellNet Shooter device in conjunction with a
computer.
Programming the C1SC/CN1SC
The CENTRON C1SC/CN1SC CellNet personality module programming port is
located such that the CENTRON inner cover does not have to be removed when
programming or testing the CellNet module.
In order to communicate with the CENTRON CellNet module, insert the
programming slide into the hole in the inner cover of the CENTRON meter that is
located at the 12 o’clock position (see Figure 7.4).
7-4CENTRON Meter Technical Reference Guide
Figure 7.4 C1SC/CN1SC Programming Port Location
Operation: C1SC Version
CENTRON Meter Technical Reference Guide7-5
Operation: C1SC Version
7-6CENTRON Meter Technical Reference Guide
Chapter 8Testing, Troubleshooting, and Maintenance
This section provides information and instructions to help you test and maintain
the CENTRON meter. Topics covered include:
•Testing support features
•Energy testing
•Recommended testing procedures
•TOU schedule testing
•Field testing
•Troubleshooting (Fatal and non-fatal errors)
•Maintenance
Testing Support Features
Infrared Test LED
The CENTRON meter is equipped with an Infrared Test Light Emitting Diode
(LED) where each pulse represents a fixed value of watthour measurement. The
LED is located on the top of the meter as the meter is viewed from a typical
installation (see Figure 8.1). The pulse weight represented by the LED pulses is 1.0
watthour per pulse (Kh=1.0).
Test Led
Figure 8.1 LED Location
Pulse Detector
An optional pulse detector is available for the CENTRON meter. The pulse detector
has an infrared pickup with two visible LEDs. When positioned over the
CENTRON light pipe, it will produce a visible flash when an infrared pulse is
received from the metrology. The right LED will flash once for each infrared Wh
CENTRON Meter Technical Reference Guide8-1
Testing, Troubleshooting, and Maintenance
pulse while the left LED will flash once for every 10Wh infrared pulses received.
The left LED on the pulse detector is helpful when heavier loads are present on the
system being examined. This can be used to verify that the metrology is measuring
energy when installed and to conduct timing tests to determine the amount of load
on meter.
Annunciators
Figure 8.2 Pulse Detector
Watthour Annunciators
C1SR meters (and some C1S versions) are equipped with LCD displays that utilize
a single flashing triangular annunciator to show that power is being metered. The
annunciator represents 1.0 watthour each time it turns on and 1.0 watthour each
time it turns off for a total of 2.0 watthours.
On other CENTRON meters equipped with LCD’s, there are three such
annunciators which also show the direction of energy flow (C1S, C1SC, C1SD,
C1ST, C1SL). The triangles will scroll left to right for positive (line to load) energy
flow, and right to left for negative energy flow.
The Kh value of the single triangle is twice the Kh of the LED and, therefore, 2.0
watthours per pulse. On the three triangle units the Kh of each triangle is further
multiplied by three as each triangle is turned on and off in sequence, resulting on a
Kh of 6.0.
TOU Rate Annunciators
The CENTRON meter is equipped with five Time-of-Use annunciators on the LCD
(see Figure 8.3). Located on the right side of the display, the annunciator A, B, C, D,
or TOTAL flashes when the applicable rate is active and is enabled to display their
respective values. (Available on the C1ST and C1SL.)
8-2CENTRON Meter Technical Reference Guide
Test Mode Annunciator
The CENTRON meter is equipped with a Test Mode LCD annunciator located in
the left portion of the display. This annunciator is enabled when Test Mode is
activated. The word TEST appears on the display and flashes at a steady rate when
test mode is activated. (Available on the C1SD, C1ST, and C1SL.)
Testing with the Infrared Test LED
The CENTRON meter is equipped with an Infrared Test LED (Light Emitting
Diode) which is located on the top of the meter at the 12 o’clock position.
The pulse weight represented by the LED pulses is always 1.0 watt-hour per pulse.
Since the Kh value for the meter is 1.0, make sure the test board is programmed to
accept this Kh value.
Testing, Troubleshooting, and Maintenance
Figure 8.3 TOU Rate Annunciators
# OF PULSES REQUIRED ON TEST BOARDS
1S & 2S CL200120V 3S,
240V 3S,
12S & 25S, 2S
CL 320
240V 4S
Full Load107 15
Light Load1067
Power Factor10712
1 pulse = 1 Watt-hour as compared to 1 pulse = 7.2 Watt-hours in
Electromechanical meters.
To obtain test uncertainties of 0.01% (plus the uncertainties of the test equipment),
use a minimum of 30 pulses.With a constant load applied (real or phantom), the
LED pulses are compared to the output of a high accuracy watthour standard. This
is accomplished using a compatible optical pickup and a comparator.
Follow these steps to test the Wh LED:
1Apply a constant delivered watts load (Wapp) to the meter.
2Verify that the LED pulses properly either by counting the pulses or using a
comparator to compare the pulses from the meter under test to the standard.
CENTRON Meter Technical Reference Guide8-3
Testing, Troubleshooting, and Maintenance
To determine the number of pulses per second, use the following equation:
Number of Pulses per secWapp
Testing Using the Disk Emulation Annunciator
The CENTRON meter is capable of visually being tested by using the Watt Disk
Emulation Annunciator.
Recommended Energy Testing Procedures
Testing solid-state meters on test boards that were designed primarily for
electromechanical meters may give unexpected results. Erroneous readings have
been known to occur on “light load” tests when the test sequence calls for said
light load test to follow immediately after the full load test. The problem is caused
by improper “jogging” and can be avoided by sequencing the test in order of
applied power such that the lowest power is tested first. This problem does not
exist on modern test boards with the latest test software.
Field testing of the CENTRON meter may be accomplished with conventional
methods using either the infrared test LED or the disk emulation annunciator
(when supplied). For details on the operation of the annunciator, see Page 8-2.
Required Hardware
The typical field test setup consists of a phantom load, portable standard, and an
infrared test pulse adapter with a counter or snap switch assembly. CENTRON
meters purchased without a test link will require a more sophisticated loading
circuit.
8-4CENTRON Meter Technical Reference Guide
Troubleshooting
Error Codes (R300)
Non-Fatal Error
CauseEffectIndication
Checksum Error of the
Energy Register
Fatal Error
CauseEffectIndication
Unsuccessful writing to or
reading from EEPROM
memory.
Metrology error.
Stops RF transmission but
continues energy
accumulation and will be
cleared after a power cycle.
All metering and RF functions
are halted. Return the module
to the factory for repair.
All metering and RF functions
are halted. Return the meter
and module to the factory for
repair.
Testing, Troubleshooting, and Maintenance
The LCD will display the
annunciator, a downward
pointing arrow, in the lower
right hand corner.
The LCD will display the word
Error in the area normally
used for energy
accumulation.
The LCD will display the word
Error in the area normally
used for energy
accumulation.
Error Codes (Demand, TOU, and Load Profile)
The firmware performs error checks to confirm proper register operation. Table
8.2 lists possible errors and associated error codes.
Fatal errors cause the display to lock on the error code. If multiple fatal errors
occur, the one that was detected first will be the error code that locks on the
display.
Table 8.2 Error Codes
ErrorError CodeError Type
CENTRON Meter Technical Reference Guide8-5
Testing, Troubleshooting, and Maintenance
Non-fatal errors can be programmed to scroll during the one second display offtime or lock on the register display. If multiple non-fatal errors occur, the meter
will display a combined error message. For example, if a low battery error and a
clock error exist, the error display will read ER 010001. In this case, if one of the
errors had been programmed to lock, and the other error had been programmed to
scroll, the display will lock on the combined error message.
Activating the Alternate Mode Magnetic Reed Switch allows the Normal Mode
Display Sequence to scroll one time during a locked non-fatal error. At the end of
the display sequence, the error message locks onto the display again.
Non-Fatal Error Codes
CodeErrorPossible Causes
Er 000001Low Battery Error
Er 007000
Er 010000Clock Error
Er 020000T OU Error
Table 8.3 Non-Fatal Error Codes
Number of minutes on the battery has exceeded one year—
checked on power up and once per second.
Discussion:
A low battery check is performed once every second. If a low battery level is detected
during this procedure, error code Er 000001 is displayed in Normal mode. This error can
be programmed to continuously scroll during the one second display off-time or lock on
the register display. A low battery continues to function; however, its reliability decreases
over time.
If a low battery level error occurs during normal operation, TOU and Mass Memory will
continue to operate until an outage occurs. If a low battery level is detected upon
programming or upon restoration of power after an outage, ER 000001 will display. Total
registers remain functional during a Low Battery Condition; however, TOU (rates A, B,
C, D) registers and load profile will not accumulate.
Reverse Direction
Error
Discussion:
A Reverse Direction error exists when the register detects 10 Wh in the reverse
direction. Reverse Direction detection is a selected feature during programming. If a
Reverse Direction error occurs, Er 007000 is displayed during the one second off-time
in Normal mode.
The Reverse Direction error will clear when a demand reset is performed.
Discussion:
A Clock error exists when a clock parameter is determined to be out of range. If this
error occurs, Er 010000 is displayed in Normal mode. This error is programmable to
continuously scroll during the one second display off-time or lock on the register display.
If a Clock error occurs, the Load Profile and TOU operations will be discontinued until
the meter is reprogrammed. The error will then clear, and the meter will resume normal
operation.
Discussion:
A TOU error occurs when the TOU calendar is out of range. TOU is disabled.
Reverse Direction Error Indicator—Clear on demand reset or
reprogram register; checked continuously.
Clock Error—Reprogram register and check for proper
operation; checked upon programming and once per second
TOU Error—Reprogram register and check for proper
operation; checked upon programming and once per second
8-6CENTRON Meter Technical Reference Guide
Testing, Troubleshooting, and Maintenance
Table 8.3 Non-Fatal Error Codes
CodeErrorPossible Causes
Er 030000Load Profile Error
Discussion:
A Load Profile error occurs when the Load Profile parameter is out of range or inactive.
Er 100000
Full Scale Overflow
Error
Discussion:
A Full Scale overflow error exists when the calculated demand at an EOI exceeds the
register Full Scale value. The register Full Scale value is selected during programming.
If an overflow occurs, the error code Er 100000 is displayed in Normal mode. This error
is programmable to display during the one second display off-time or lock on the register
display.
The Full Scale overflow error displays when the overflow occurred. The Maximum
Demand register continues to accumulate and display kW as long as the format
limitations are not exceeded. When a demand reset is performed, the correct Max kW
value will be added to the cumulative registers and the error code will no longer be
displayed. If a Full Scale overflow occurs, check the installation to ensure that the
current metering capability has not been exceeded. A Full Scale overflow in no way
affects the existing billing data.
Load Profile Error—Reprogram register and check for proper
operation; checked upon programming and once per second
Programmed Full Scale Value exceeded—Check programmed
Full-Scale value and meter installation for proper sizing of
equipment; checked continuously.
Fatal Error Codes
Table 8.4 Fatal Error Codes
CodeErrorPossible Causes
(Available in firmware revisions 10.27 and above.) Defective
Er 000004Metrology Error
Discussion:
The direction of energy flow signal is monitored for rate of change. If the rate of change
exceeds 14 Hz, the metrology error is triggered. Under this condition the base metrology
has become defective and the energy pulse signal being sent from metrology to the
D/T/L module is no longer valid. Base metrology should be replaced in the event of this
error.
Er 000010EEPROM Error
Discussion:
If the module has an EEPROM error, the error code ER 000010 will be continuously
displayed. If this error occurs, program the module and check for proper operation. If the
error continues to exist, replace the module.
component in the base metrology causing invalid energy pulse
signal.
Energy value checksum failure; EEPROM failure—reprogram
module and check for proper operation. If error still does not
clear, replace module; checked upon programming and at
power up.
CENTRON Meter Technical Reference Guide8-7
Testing, Troubleshooting, and Maintenance
Inspecting and Troubleshooting—General
Due to the modular architecture of the CENTRON meter, modules of similar
voltage (120V or 240V) may be interchanged. Therefore, the personality module of
the CENTRON you are troubleshooting can be placed on a known working base to
verify proper operation of the personality module. Likewise, a known working
personality module may be placed on the base of a meter to verify proper
operation of the meter.
This section provides a list of the most likely problems that you may encounter,
along with possible causes and solutions.
Blank Display
CauseSolution
Power Not Applied to MeterApply power.
LCD/LCD Driver FailureReplace Register Circuit Board.
Loose Power Supply ConnectionRemove and re-seat board-to-board connector.
Time and Date Wrong (TOU or Load Profile Only)
Time/Date Wrong in PC or Handheld device
Wrong Line Frequency
Battery Failure During Power OutageReplace module.
Daylight Savings Time not Programmed
Verify and update time/date in programming device
and download new time and date to register. See
appropriate software manual for more detailed
directions.
Verify proper line frequency is selected in Setup
routine in programming software. Select proper
frequency and reconfigure meter.
Verify DST is selected in program. Reconfigure
meter with correct program.
CauseSolution
kW will not immediately accumulate after a power
outage if CLPU (Demand Delay) has been selected.
Accumulation will begin immediately after Demand
Delay has expired. Verify register program and
reconfigure meter.
Accumulation of kW or kWh will not take place while
register is in Test mode. Exit Test mode and verify
proper accumulation begins.
Verify that meter is accumulating energy by testing
infrared test LED.
Verify TOU schedule contains continuous 24-hour
periods for all weekdays, weekends, or holidays. All
24-hour periods throughout every year must be
accounted for within the TOU schedule.
Check cable with known register that
communicates. Check cable against known cable
that is functioning. Also check batteries in cable
assembly.
Verify proper Com Port number has been selected
in the programming software. If the wrong Com Port
is selected, communications will not occur.
If security codes have been downloaded to the
register, the programming device must have the
proper code to make connection to the module.
Verify security codes in the programming software.
Verify Optical Probe lines up properly over the
optical connector. Re-install cover for proper
alignment. Verify PC or handheld and cable are
securely connected and attached to the correct Com
Port.
Optical port can be programmed to operate at 4800
or 9600 baud. Factory default baud rate is 4800.
Reed Switch Does Not Activate the Alternate Mode
CauseSolution
Magnetic Field is too Weak
Reed Switch FailureReplace module.
Alternate Mode Items Not Selected
Reset Mechanism Does Not Initiate Demand Reset
CauseSolution
Reset Mechanism Does Not
Initiate Demand Reset
Reset Has Occurred Within Last 60 Seconds
Reset Button Is DefectiveReplace module.
Demand Reset Cannot be Initiated Through PC or Handheld
CauseSolution
Communication Cannot Be EstablishedSee Programming Problems.
Place magnet closer to switch or use stronger
magnet.
Re-program meter with items to be displayed in
Alternate mode.
Re-install or Replace cover assembly.
Manual demand reset cannot occur within 60
seconds of the previous demand reset. Wait 60
seconds and perform a second Demand Reset.
CENTRON Meter Technical Reference Guide8-9
Testing, Troubleshooting, and Maintenance
Test Mode Switch Does Not Place Module in Test Mode
CauseSolution
Switch Not Fully Depressed
Switch or Electronic FailureReplace module.
Test Mode Items Not Selected
Inspecting and Troubleshooting—C1S LCD and C1SR
Blank Display
CauseSolution
Power not applied to the meterApply power.
Loose power supply connectionRemove and re-seat board to board connector.
LCD/LCD Driver failure
Verify that the test mode pushbutton has been
completely depressed.
Re-program module with items to be displayed in
Test mode.
Replace Register circuit board.
Note: Energy reading and tamper flags may be
uploaded with the ZRO-C2A.
8-10CENTRON Meter Technical Reference Guide
Chapter 9Specifications and Drawings
Specifications
For a complete list of the latest CENTRON specification numbers, refer to the
CENTRON Meter Specification Numbers Bulletin, Part Number 428601-220.
Drawings
10
LINE
1
0
++
10
LOAD
Figure 9.1 Form 1S Wiring Diagram
CENTRON Meter Technical Reference Guide9-1
Specifications and Drawings
102
LINE
1
102
02
LOAD
Figure 9.2 Form 2S Wiring Diagram
Figure 9.3 Form 3S Wiring Diagram
9-2CENTRON Meter Technical Reference Guide
Specifications and Drawings
Alternate positions
of movable potential
terminal
Figure 9.4 Form 4S Wiring Diagram
Alternate
positions of
fifth
terminal
jaw
Figure 9.5 Form 12S Wiring Diagram
CENTRON Meter Technical Reference Guide9-3
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.