This document describes the basic procedures
necessary for an experienced installer to install, set
up, and program an UltraGard
[Check with your central station to verify they have
updated their CS-4000 with version 6.0 or later software, for full UltraGard support.]
™
Security System.
Contents
UltraGard
and Custom Versions
Special Installation Requirements 1
Requirements for UL-Listed Installations 1
Canada Listings 1
California State Fire Marshall Listing 1
Installing the System 1
Determining the Panel
Location 2
Running Wires to the Panel Location 2
Mounting the Panel 2
Installing the Panel Antennas 3
Wiring the Panel 3
Setting the Optional Energy Saver Module
(ESM), Hardwire Input Module (HIM) and Hardwire Output Module (HOM) Unit Number DIP
Switches 4
Installing the Backup Battery 4
Powering Up the Panel 5
Adjusting Status Sound Volume 5
Programming the Panel 6
Clearing Memory 7
Entering and Exiting Program Mode 7
Deleting Sensor Text 8
Programming Sensor Text 8
Adding (Learning) Wireless Sensors 9
Adding (Learning) Hardwire Sensors 10
Deleting Sensors and Hardwire Zones 10
Programming Upper Sensors 11
Programming Optional Feature Numbers 11
Adding (Learning) Wireless Touchpads 11
Programming Panel Configuration Options 12
Programming the Primary Phone Number 12
Programming the Phone
Format 12
Programming the Siren
Time-out 13
Programming the Install Code 13
Programming the Account Number 13
Programming the Entry Delay 14
Programming the Extended Delay 14
Programming the Exit Delay 14
Programming the Activity Time-out 14
Programming the House Code 15
Programming the Energy Saver Module Freeze
and Set Temperatures 15
Programming the Touchpad Options 15
Programming the Touchpad Unit Number
16
Programming the Touchpad Quiet 16
Programming Touchpad Key Beeps 17
Programming the Interrogator 200 Audio Verification Module Mode, Time-out, and Access Code
17
Programming HOM Points 18
Programming the Time Zone 18
Document Number: 466-1034-01-ITI Rev. F
April 1997
Page 2
Contents
Viewing or Programming the User-Programmable System Settings 18
The Duress Code 19
Adjusting the Alphanumeric Touchpad Display
Brightness 20
Requesting CS-4000/Downloader Programming 20
Installing Line Carrier Devices 21
Installing and Programming the Wireless Interior
Siren (WIS) 21
Setting the WIS DIP Switches and Installing
the Battery 21
Connecting an External Siren to the WIS 22
Programming the WIS House Code 22
Installing X-10 Lamp Modules 22
Testing the System 23
Testing Sensors 23
If a Sensor Fails the Sensor Test 24
Testing the Energy Saver Module (ESM) 24
Testing the Hardwire Input Module (HIM) 25
Testing the Hardwire Output Module (HOM) 25
Testing the X-10 Lamp Modules 25
Testing Phone Communication 26
Testing Central Station Communication 26
Displaying the Panel
Version Code 26
Appendix A: Command Summary 27
User Operating Command Summary 27
System Settings (User-Programming) Command
Summary 28
Appendix B: Troubleshooting 29
Appendix C: Programming Tables 37
Appendix D: System Planning Worksheets 42
Appendix E: Panel Connections and Wiring 50
Appendix F: UL Requirements 53
Page 3
Notices
This manual may refer to products that are announced but are not yet available.
FCC Notices
This equipment has been tested and found to comply with the limits for a class B digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide
reasonable protection against harmful interference in a residential installation. This equipment gen erates, uses, and can radiate radio frequency energy an d, if not installed an d
used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
•Install a quality radio or television outdoor antenna if the indoor antenna is not adequate.
•Reorient or relocate the panel.
•Move the panel away from the affected equipment.
•Move the panel away from any wire runs to the affected equipment.
•Connect the affected equipment and the panel to separate outlets, on different branch circuits.
•Consult the dealer or an experienced radio/TV technician for help.
•Send for the FCC booklet How to Identify and Resolve Radio-TV Interference Problems, available from the U.S. Government Printing Office, Washington, D.C.
20402. Stock Number: 004-000-00345-4.
This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
This equipment complies with part 68 of the FCC rules. On the FCC label affixed to this eq uip ment is the FCC Registration Number and Ringer Equivalence Number (REN)
for this equipment. If requested, provide this information to your telephone company.
The REN is used to calculate the maximum number of devices your telephone line will support with ringing service. In most areas the sum of all device RENs should not
exceed 5.0. Contact your local telephone company to determine the maximum REN for your calling area.
If your telephone equipment causes harm to the telephone network, your telephone company may temporarily disconnect your service. If possible, you will be notified in
advance. When advance notice is not practical, you will be notified as soon as possible. You will also be advised of your right to file a complaint with the FCC.
Your telephone company may make changes in its facilities, equipment, operations, or procedures that cou ld affect the prop er operation of your equ ipment. You will be giv en
advanced notice in order to maintain uninterrupted service.
If you experience trouble with this equipment, please contact
Interactive Technologies, Inc.
2266 Second Street North
North Saint Paul, MN 55109
1-800-777-1415
for service and repair information. The telephone company may ask you to disconnect this equipment from the network until the problem has been corrected or until you are
sure that the equipment is not malfunctioning.
This equipment may not be used on coin service provided by the telephone company. Connection to party lines is subject to state tariffs.
Canada Notice
The Canadian Department of Communications label identifies certified equipment. This certification means that the equipment meets certain telecommunications network protective, operational, and safety requirements. The department does not guarantee the equipment will operate to the user’s satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications comp any. The eq uip men t must also
be installed using an acceptable method of connection. In some cases, the company’s in side wiring associated with a sin gle-line individual service may be extended by means
of a certified connector assembly (telephone extension cord). The customer sh ould be aware that co mpliance with the above con ditio ns may not prev ent degradation o f service
in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alterations made by the user to this
equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment.
For your protection, make sure that the electrical ground connections of the power utility, telephone lines, and internal metallic water pipe system, if present, are connected
together.
Caution
Do not attempt to make connections yourself. Contact the appropriate electrician or electric inspections authority.
The Load Number (LN) assigned to each terminal device denotes the percentage of the total load to be connected to a telephone loop that is used by the device to prevent
overloading. The termination on a loop may consist of any combination of devices subject only to the requirement that the total of the LNs of all the devices does not exceed
100. Load Number: 0.4B
Page 4
“AVIS: - L ´étiquette du ministère des Communications du Canada identifie le matériel homologué. Cette étiquette certifie que le matériel est conforme a certaines normes de
protection, d ´ exploitation et de sécurité des réseaux de téléco mmunications. Le ministère n ´ ass ure toutefois pas que le matériel fon ctionnera a la s atisfaction de l ´ utilisateu r.
Avant d ´ installer ce matériel, l ´ utilisateur doit s ´ assurer qu´ il est permis de le raccorder aux installations de l ´ enterprise locale de télécommunication. Le matériel doit
également etre installé en suivant une méthod acceptée de raccordement. Dans certains cas, les fils intérieurs de l´ enterprise utilisés pour un service individuel a ligne unique
peuvent etre prolongés au moyen d´ un dispositif homologué de raccordement (cordon prolongateur téléphonique interne). L ´ abonné ne doit pas oublier qu ´ il est possible
que la conformité aux conditions énoncées ci-dessus n ´ empechent pas le d égradation du service dans certaines situation s. Actuellement, les enterprises de télécommunication
ne permettent pas que l ´ on raccorde leur matériel a des jacks d ´ abonné, sauf dans les cas précis prévus pas les tarrifs particuliers de ces enterprises.
Les réparations de matériel homologué doivent etre effectuées pas un centre d ´ entretien canadien autorisé désigné par le fournisseur. La compagne de télécommunications
peut demander a l ´ utilisateur de débrancher un appareil a la suite de réparations ou de modifications effectuées par l ´ utilisateur ou a cause de mauvais fonctionnement.
Pour sa propre protection, l ´ utilisateur doit s ´ assurer que tous les fils de mise a la terre de la source d ´ énergie électrique, des lignes téléphoniques et des canalisations d ´´
eau métalliques, s ´ il y en a, sont raccordés ensemble. Cette précaution est particulièrement importante dans les régions rurales.
Avertissment. - L ´ utilisateur ne doit pas tenter de faire ces raccordements lui-meme; il doit avoir recours a un service d ´ inspection des installations électriques, ou
a electricien, selon le cas”.
Une note explicative sur les indices de charge (voir 1.6) et leur emploi, a l ´ intention des utilisateurs du matériel terminal , doit etre incluse dans l ´ information qui accompagn e
le materiel homologué. La note pourrait etre rédigée selon le modèle suivant:
“L ´ indice de charge (IC) assigné a chaque dispositif terminal indique, pour éviter toute surcharge, le pourcentage de la charge totale qui peut etre raccordée a un circuit téléphonique bouclé utilisé par ce dispositif. La terminaison du circuit bouclé peut etre constituée de n ´ import somme des indices de charge de l ´ ensemble des dispositifs ne
dépasse pas 100.”
L ´ Indice de charge de cet produit est ____________.
Trademarks
ITI is a registered trademark of Interactive Technologies, Inc. UltraGard is a trademark of Interactive Technologies, Inc. X-10 is a registered trademark of X-10 (USA), Inc.
Page 5
Special Installation
tion for more information.
Requirements
This security system can be used as a fire warning
system, an intrusion alarm system, an emergency notification system, or any combination of the three.
Some installations may require certain configurations
dictated by city codes, state codes, or insurance requirements. The following information indicates the
components of various listings.
Requirements for UL-Listed
Installations
If the system is to comply with UL household requirements, there are specific guidelines you must follow.
Refer to appendix F for a list of compatible accessories, programming and wiring requirements in ULlisted systems.
Canada Listings
For 24-hour backup, external power drain is limited to 150
mA continuous using the heavy duty 6.5AH battery.
Residential Burglary Alarm System Unit
(ULC-S309)
Basic system as described in appendix F for UL-listed
installations plus:
•Learn Mode Door/Window Sensors (60-362)
California State Fire Marshall
Listing
The California State Fire Marshall listing is pending.
Installing the System
This section describes how to install the system control panel. Plan your system layout using the worksheets provided in appendix D before starting the
installation.
Installing the system consists of the following:
The ULC (UL Canada) listing is pending.
CSA Certified Accessories
Residential Fire Warning System Control Unit
(ULC-S545-M89)
Basic system as described in appendix F for UL-listed
systems plus:
•Wireless Smoke Sensor (60-506), Wireless
Smoke Sensor (60-645-95), or Hardwire Smoke
Detector (13-360) (ESL 449AT) with Power
Supervision Module (60-391)
•Option F21 (Immediate Trouble Beeps) set ON
•SUPSYNC (Supervisory Synchronization) set to
2 (hours)
Note
SUPSYNC cannot be programmed from the panel. Refer to
the “Requesting CS-4000/Downloader Programming” sec-
•Determining the Panel Location
•Running Wires to the Panel Location
•Mounting the panel
•Installing the panel antennas
•Wiring the panel
•Setting the optional Energy Saver and Hardwire
Input Module unit number dip switches
•Installing the backup battery
•Powering up the panel
•Adjusting status sound volume
1
Page 6
Installing the System
Determining the Panel
Location
Before permanently mounting the panel, determine
panel location using the following guidelines:
•Centrally locate the panel with relation to wireless sensor locations, whenever possible.
•Avoid locations with excessive metal such as
HVAC ducts, foil wallpaper, gas/water pipes, and
electrical wiring.
•Mount the panel at a comfortable working height
(about 45 to 55 inches from the floor to the bottom of the panel, as shown in figure 1).
•Allow a minimum of 10.5 inches above the panel
for the antennas, as shown in figure 1.
•Allow 6.5 inches to the right or left of the panel
for wiring, phone jack, and optional module
mounting.
•Allow at least 24 inches in front of the panel for
access to panel components.
PHONE JACK AND
OPTIONAL MODULE
MOUNTING AREA
21"
ANTENNA
AREA
14.5"
Running Wires to the Panel
Location
Once you have determined the ideal panel location,
run any necessary wires to that location, including:
•Power transformer
•Phone line
•Sirens/speakers
•SuperBus* Alphanumeric Touchpads
•Hardwire zones
•Optional SuperBus* modul es (suc h as Energy
Saver Module [ESM], Hardwire Input Module
[HIM], Hardwire Output Module [HOM], etc.)
* SuperBus is an improved technology bus configuration and is not compatible with older bus modules.
Refer to table E.3 in appendix E for wire size and type
recommendations. If you are using the same cable
type for several wire runs, use labels to mark the wires
at the panel location to help identify these wires .
Mounting the Panel
PANEL
ACCESS FOR
PANEL COVER
45-55"
FLOOR
Figure 1 Determining Panel Location
SCREWS
NOTE
ALLOW AT LEAST 24"
IN FRONT OF PANEL
FOR ACCESS TO PANEL
COMPONENTS
14.5"
8"
25"
8557G04A.DS4
Use the procedure below to mount the panel to the
wall or wall studs, using the supplied mounting hardware and the panel mounting holes shown in figure 2.
Caution
Make sure you are free of static electricity whenever you
work on the panel with the cove r re moved. To discharge
any static, first to uch the metal pa nel chassis , and then stay
in contact with the chas sis when touc hing t he c ircu it boa rd.
An approved grounding strap is recommended.
To mount the panel:
1. Unlock the panel cover (if cover has a key lock
installed) or remove the panel cover retaining
screws at the bottom of the panel and remove the
panel cover.
2. Swing the panel cover out and up to remove it
from the enclosure.
3. Remove the necessary wiring knockouts. Be
careful not to damage the circuit board.
4. Place the enclosure in position against the wall.
2
Page 7
Make sure enclosure is level and mark the locations of the two mounting holes and two keyhole
mounting holes. Remember to leave room for the
panel antennas, which extend 9 inches above the
top of the enclosure.
5. Use the appropriate anchors and screws. Partially
insert screws into the two anchors at the two top
keyhole locations, and then hang the panel chassis on the two screws.
6. Recheck for level, insert the two lower screws,
and then tighten all four mounting screws.
KEYHOLE
MOUNTING
HOLES
ANTENNAS
COVER
LIP
Installing the System
ANTENNAS
ANTENNA
GROUNDING
SCREW
Figure 3 Installing the Panel Antennas
Caution
Do not overtighte n the te rmina l block screws ; if yo u do, p ermanent damage may result.
ENCLOSURE
ANTENNA
TERMINAL
STRIPS
PANEL CIRCUIT BOARD
ANTENNA
GROUNDING
SCREW
8557G49A.DS4
CONTROL
PANEL
CIRCUIT
BOARD
BACKUP
BATTERY
COVER
SCREWS
WIRING
KNOCKOUTS
CONTROL
PANEL
ENCLOSURE
EARTH GROUND
CHASSIS SCREW
MOUNTING
HOLES
8557G08A.DS4
Figure 2 Mounting the Panel
Installing the Panel Antennas
Wiring the Panel
Refer to appendix E for panel terminal descriptions,
wire recommendations, and typical system wiring diagram.
Refer to appendix F for panel programming and typical system wiring diagram for UL-listed installations.
Refer to appendix D, table D.2 to calculate the hardwire device power consumption for the system.
For more detailed information on installing hardwire
devices, refer to the installation instructions that accompany each device.
Caution
You must be free of static electricity before handling electronic circuit boards. Touch a grounded, bare metal surface
before handli ng circuit boards to discharge yourself of stati c
electricity or wear a static grounding strap.
Insert one antenna into the inside screw terminal of
each terminal block and gently tighten the screws using a small pocket-size screwdriver (figure 3).
3
Page 8
Installing the System
Setting the Optional Energy
Saver Module (ESM), Hardwire
Input Module (HIM) and Hardwire Output Module (HOM)
Unit Number DIP Switches
All devices connected to the panel’s SuperBus hardwire bus have individual unit numbers assigned. Alphanumeric touchpad unit numbers are changed in
software during programming. The Energy Saver
Module (ESM), Hardware Input Module (HIM), and
Hardware Output Module (HOM) are set wit h DIP
switches inside the modules. For unit number setting
details, refer to the installation instructions provided
with the bus device.
Duplicated unit numbers will prevent those bus devices from operating. Refer to table D.3 in appendix D
for recommended SuperBus device unit number settings.
unit number assigned is to more than one device. SuperBus devices cannot share the same unit number.
UNIT NUMBER 0
5
4
12
12
12
12
12
12
12
3
4
3
4
3
4
3
4
3
4
3
4
3
6
UNIT NUMBER 1
5
6
UNIT NUMBER 2
5
6
UNIT NUMBER 3
5
6
UNIT NUMBER 4
5
6
UNIT NUMBER 5
5
6
UNIT NUMBER 6
5
6
UNIT NUMBER 7
7
8
7
8
7
8
7
8
7
8
7
8
7
8
To set your ESM, HIM, or HOM unit number:
1. Set the module unit number DIP switches to the
desired unit number as shown the figure 4 per the
recommendations in table D.3 in appendix D.
The unit number is set to 0 (zero) at the factory
and is OK for most single touchpad and single
ESM, HIM, or HOM module applications. Make
sure that no bus devices (including hardwire
touchpads) share the same unit number (device
address).
Caution
The alphanumeri c touchpad unit number default s to 1 (one).
Do not set the ESM, HIM, or HOM unit number to 1. Doing
so will prevent the touchpad from functioning.
2. Turn the c ontrol panel power switch off and then
back on so the bus module can read the unit number switch settings into its memory.
3. Enter and exit PROGRAM MODE by switching
the panel PROGRAM/RUN switch to PROGRAM and back to RUN so the panel can
“learn” the new bus device unit numbers.
12
4
3
6
7
8
8557G32A.DS4
5
Figure 4 Setting the ESM, HIM, or HOM Unit Number Dip Switches
Note
All SuperBus devices such as Energy Saver, Hardwire Input, and Hardwire Output Mo dules and alphan umeric touchpads must have unique unit number (address) settings.
Devices with the same (confli cting) add ress will not fu nction
properly. Module address switches 1 –5 must remain down
(off).
Installing the Backup Battery
The panel uses one rechargeable, sealed 12V leadacid backup battery.
Note
Both standard (60-681) 12V, 4AH and heavy duty (60-680)
12V, 6.5AH backup batteries are available. Always replace
with the same battery type and size.
If the alphanumeric touchpad (or other SuperBus device) no longer seems to function, check if the same
4
Page 9
Installing the System
To install (or replace) the backup battery:
1. Make sure the panel power switch is OFF and
that the transformer is unplugged from the outlet.
While AC power is applied to the panel, the
charging voltage is present at the battery leads
even with the power switch off.
2. Verify all wiring at the panel and devices for cor-
rect terminations.
3. Place the battery in the lower left or right portion
of the panel enclosure, with the termina ls facing
up.
4. Connect the supplied black battery wire from the
panel circuit board negative (-) battery spade lug
(located near the power switch) to the negative () battery terminal.
5. Connect the red battery wire from the panel cir-
cuit board positive (+) battery spade lug to the
positive (+) battery terminal.
WARNING!
Never short-circuit or reverse the battery wires. Possible injury to you and/or permanent damage to the panel
could result.
Powering Up the Panel
The green power LED on the panel turns on.
Interior sirens and piezos sound one b eep an d in-
terior speakers announce the message Alarm sys-tem is off.
Alphanumeric touchpad displays 1 - OFF.
Note
If the power LED is off or flashing and no beeps or voice
messages sound, turn off the panel power switch, disconnect the backup ba tter y, an d un pl ug th e tra nsfo rmer. Re fe r
to appendix B, “Troubleshooting.”
4. Turn the panel power switch OFF, unplug the
transformer, and remove the existing screw
securing the AC outlet cover.
WARNING!
Use extreme caution when securing the transformer to
a metal outlet cover. You could receive a serious shock
if a metal outlet cover drops down onto the prongs of
the plug while you are securing the transformer and
cover to the outlet box.
5. Hold the outlet cover in place and plug the transformer into the lower receptacle.
6. Use the screw supplied with the transformer to
secure the transformer to the outlet cover.
7. Turn the panel power switch ON.
After wiring all devices to the panel and installing the
backup battery, you are ready to power up the panel.
Note
If the installation includes more than one alphanumeric
touchpad, disconnect all but one from their wiring harnesses to reduce the possibility of a unit number (address) conflict. When powering up and programming are completed,
connect the remaining touchpads to their wiring harnesses.
For complete details on adding additional alph anumeric
touchpads to a workin g system, refer to the
phanumeric Touchpad Installation Instructions
with each touchpad.
SuperBus Al-
included
To power up the panel:
1. Plug the transformer into an outlet that is not
controlled by a switch.
2. Make sure the panel PROGRAM/RUN swi tch
located between the two panel terminal strips is
set to RUN (up).
3. Turn ON the panel power switch located on the
left edge of the panel and note the following:
Adjusting Status Sound
Volume
The panel allows you to set the volume level for status
sounds and status messages from speakers connected
to panel terminals 8 and 9 (VOICE). Alarm sounds
and messages are preset to full volume .
To adjust the status sound volume:
1. Locate the speaker vol um e ad justment potentiometer on the panel (above terminal 8).
Caution
Never adjust the potentiometer labeled “Do Not Adjust” located near the power switch. Permanent damage to the
panel could result.
5
Page 10
Programming the Panel
2. Press STATUS + STATUS on the alphanumeric
touchpad for a long system status display and
voice message.
Note
User-programmabl e system s etting 77 (Quiet Exit ) must be
off for voice so un ds to b e a nno unce d . (Se e Viewin g o r Programming the User-Programmable System Settings.)
3. While listening to the message, increase the volume level by turning the volume potentiometer
clockwise.
4. Repeat steps 2 and 3 until the desired volume
level is reached.
Programming the Panel
The alphanumeric touchpad is the main programming
device for the system on-site. This touchpad is used to
enter values into panel memory, such as sensors, sensor text, and system-specific configuration information. During programming, the alphanum eri c
touchpad prompts you for information in a certain order. You can cycle through this order of prompts to
get to the desired programming area. For example,
you can cycle past the prompts for sensor text to enter
the system configuration information and later return
to programming sensor text.
Figure 5 shows the order of the prompts, and the area
of programming related to these prompts. Once you
know this order of prompts, you will be able to move
forward and backward in the prompt sequence to locate the programming item you need.
Examine the flowchart shown in figure 5 to familiarize yourself with the sequence in which the programming procedures appear. The programming software
is like a menu of choices displayed in a scroll. The direction of the chart arrows represents pressing the
BYPASS button to scroll forward. To scroll backward, press the STATUS button. You can also go directly to the menu choice by entering the two-digit
number shown.
When you use the alphanumeric touchpad to program
the system, the touchpad buttons have special programming meanings and functions. Table 1 describes
the programming buttons.
PROGRAM
MODE
DELETE
TEXT
01
EXTENDED
PROGRAM
SENSOR
TEXT
02
LEARN
SENSORS
03
DELETE
SENSORS
04
UPPER
SENSORS
05
F
OPTIONS
06
LEARN
TOUCHPADS
07
PHONE
NUMBER
08
PHONE
FORMAT
09
SIREN
TIME-OUT
10
INSTALL
CODE
11
ACCOUNT
NUMBER
12
ENTRY
DELAY
13
DELAY
14
EXIT DELAY
15
ACTIVITY
TIME-OUT
16
HOUSE
CODE
17
FREEZE
TEMPERATURE
18
SET
TEMPERATURE
19
TOUCHPAD
OPTIONS
20
AVM MODE
21
AVM
TIME-OUT
22
AVM CODE
23
HOM
SETUP
24
TIME
ZONE
25
Figure 5 Programming Flow Chart
8557G45B.DS4
6
Page 11
Table 1 Alphanumeric Touchpad
Programming Button Functions
ButtonProgramming Function
Numeric
Buttons
STATUSScrolls backward to previous program-
BYPASSScrolls forward to next programming
COMMANDUsed to proceed or confirm displayed
Used to enter numeric values such as
delays and sensor numbers. Also used
to enter text characters or word codes
during sensor text programming.
ming function. Displays previous sensor
text library character during sensor text
programming. Also used to “lock in” new
alphanumeric touchpad unit numb ers.
function. Displays next sensor text
library character during sensor text programming.
entry. Displays next character/word position in sensor text programming. Also
used to toggle between values, such as
yes/no or on/off.
Programming the Panel
• Programming the house code
• Programming the freeze and set temperatures
• Programming the touchpad options
• Programming the Audio Verification Module
mode, time-out, and access code
• Programming HOM Setup
• Programming the Time Zone
• Viewing or programming the user-programmable
system settings
• The duress code
• Adjusting the alphanumeric touchpad display
brightness
• Requesting CS-4000/Downloader programming
Note
All on-site programming must be done usin g a SuperBus Alphanumeric Touchpad. The Alphanumeric Touchpad can
be removed once the system has be en programmed.
Clearing Memory
FIRECancels and exits displayed program-
ming command (if pressed before COMMAND).
Backs out to previous menu level.
AUXILIARYScrolls long display messages.
POLICEUsed to clear (blank) an access code.
Used to program a pause in central sta-
tion phone numb er.
Used to clear HOM points.
Programming the panel includes the following procedures:
• Clearing memory
• Entering and exiting program mode
• Deleting and programming sensor text
• Adding and deleting wireless sensors and hardwire
zones
• Programming upper sensor numbers
• Programming optional feature numbers
• Adding wireless touchpads
• Programming panel configuration options
• Programming the phone number and format
• Programming the siren time-out
• Programming the install code
• Programming the account number
• Programming the entry, extended, and exit delays
• Programming the activity time-out
Clear memory on all newly installed panels before
programming.
Note
Since all programming info rmation is cont ained in memo ry,
clearing memory deletes all ex is ting programming information except sensor text (if any). Sensor text can be deleted
separately.
To clear panel memory:
1. Open and remove the panel door.
2. Turn the panel power switch OFF and then ON.
3. Immediately (within 1 minute after turning panel
power ON), press and hold the memory clear
button located on the upper left edge of the panel
until a relay click is heard at the panel or until
interior speakers announce Memory good-bye.
Entering and Exiting Program
Mode
The panel must be in program mode to perform any of
the on-site programming operations.
7
Page 12
Programming the Panel
To enter program mode:
1. Open and remove the panel door.
2. Set the panel PROGRAM/RUN switch to PROGRAM (down).
Alphanumeric touchpads display PROGRAM MODE
and interior speakers, sirens, and piezos sound six
beeps every minute as a reminder that the panel is in
the program mode.
Note
If touchpad(s) do not display
switching the PROGRAM/RUN switch to PROGRAM
(down), a special install code has been programmed into
the panel and now must be entered into the touchpad using
the number buttons. The touchpad will display
MODE
once the correct install code is entered.
PROGRAM MODE
PROGRAM
after
The program mode of operation must be exited for the
system to operate normally (RUN). You can exit from
program mode at any time.
To exit program mode:
1. Switch the panel PROGRAM/RUN switch to
RUN (up).
2. The alphanumeric touchpad will display 1 - OFF
to signal that the system is in the normal mode of
operation.
3. When you are finished programming or working
in the control panel, replace and secure the panel
door with either the panel door screws or key
lock.
Deleting Sensor Text
You can delete all sensor text (if any)—before programming or reprogramming, for example—by doing
the following procedure.
To delete all existing sensor text:
1. In PROGRAM MODE, press BYPASS or STATUS until DELETE TEXT is displayed.
2. Press COMMAND. Flashing RDY is displayed.
Caution
Deleted text cannot be retrieved and must be reprogrammed.
TEXT DONE is displayed.
4. Press FIRE to exit.
Programming Sensor Text
This section describes how to program sensor names.
Use the word and character numbers you recorded in
appendix D (using table C.2 in appendix C) to program sensor text.
Before programming sensor text the first time, delete
all existing text (if any) as detailed above.
To program sensor text:
1. In PROGRAM MODE, press BYPASS or STATUS until the display reads PROG SENSOR
TEXT.
2. Press COMMAND and the display reads S01
[Group number assigned, if any] [“-” if normally closed, “*” if normally open] [existing
sensor text, if any].
3. Enter the desired sensor numbe r from 01 to 76
and the display reads S## [existing sensor text, if any].
4. Press COMMAND and the display reads A 00.
5. Enter the appropriate word number or character
number from table C.2 in appendix C.
6. Press COMMAND and the display reads B 00.
7. Repeat steps 5 and 6 until the whole sensor name
is entered.
Note
Because the touch pad can o nly disp lay a limi ted number of
characters, in some cases—such as alarms—all text may
not be displayed.
8. Press FIRE. The display shows the sensor number and name. Lines longer than the display will
scroll horizontally. If desired, press AUXIL-IARY to scroll the long-line display again.
9. Press BYPASS to cycle to the next sensor number and repeat steps 4 through 8 until all sensor
names are programmed.
10. Press FIRE to exit.
3. Press POLICE to delete all sensor text. DELETE
8
Page 13
Programming the Panel
Adding (Learning) Wireless
Sensors
Programming wireless and hardwire sensors involves
switching the panel to the program mode of operation
and setting sensor identificati on num be rs and group
numbers for each wireless sensor and hardwire sensor
loop. Once sensors IDs and group assignments are
added (learned) into panel memory, the panel can respond appropriately for each sensor detection. Sensors can be added (learned) into or deleted from panel
memory.
Use table C.1 in appendix C for selecting sensor
groups and complete the group assignment for each
wireless sensor in the system planning worksheets in
appendix D.
Use the following procedure to add (learn) all Learn
Mode wireless sensors.
To add Learn Mode wireless sensors into panel
memory:
1. In PROGRAM MODE, press the touchpad
BYPASS or STATUS button repeatedly until
LEARN SENSOR is displayed.
2. Press the COMMAND button to display
GROUP __ __.
3. Enter the desired group number (00 to 29, 32).
4. Press the COMMAND button to display SEN-
SOR ##.
5. Press the COMMAND button if the sensor num-
ber displayed is OK or enter another number
from 01 to 76, and then press COMMAND
again.
6. The display reads TRIP - ## . Trip the wireless
sensor tamper switch as shown in table 2 or as
described in the sensor’s installation instructions.
When the sensor has been added (learned) the
display reads TRIP - ## [next #] and interior
speakers announce Sensor # okay. Sensor [next #
to be learned].
Note
To trip a wireless sensor with an e xternal h ard-wire c ontact
connected to its screw terminals, check that the external
contact is in its alarm state, and then trip the sensor.
The alarm state is either open or closed, depending on the
normal condition of the sensor. Multiple normally closed
switches are wired in series and tripped while the loop is
open. Multiple normally ope n switch es ar e wire d in paral lel
and tripped while the loop is closed.
For high-security installations, always remove both internal
reed switches when connecting an external contact to the
wireless sensor terminals.
Only the normally closed configuration can be used in ULlisted installati ons.
Do not attempt to use the built-in reed switch
nal contact on the same wireless sensor.
and
an exter-
Table 2 Tripping Learn Mode Wireless
Sensors
Sensor *Action
Door/Window †Open sensor cover.
Fire Pull StationOpen the sensor cover located
inside the Fire Pull Station.
FreezeOpen sensor cover.
Gl ass GuardOpen sensor cover .
Portable Emergency But-
tons
PIR Motion Open PIR case.
K eychain TouchpadSimultaneously press arm and dis-
Rate-of-Rise HeatOpen sensor cover and press learn
Recessed Door/WindowOpen sensor cover and remove
Shock
†Open sensor cover.
Slim Line Door/WindowRemove sensor from moun ting
SoundOpen sound sensor cover, after
System Sensor Smoke
System Sensor 2300RF ITI
Press the appropriate emer-
gency button(s).
arm until the LED flashes.
switch on circuit board.
transmitter circuit board.
base.
spring is installed.
Press test button and hold for
30 se conds, until test alarm
begins sounding.
With sensor removed from base,
press the test b utton for at leas t
1 second.
* Refer to the particular sensor’s installation instructions for
more details on tripping Learn Mode wireless sensors.
† When using an external contact with this sensor, the contact
must be in the alarm state while tripping the sensor to properly
learn it into memory.
7. Continue adding sensors into the current group
number by repeating step 6 for each sensor. Press
BYPASS, STATUS, or number buttons to select
new sensor numbers (other than what is automatically displayed).
8. To add sensors into other groups, press FIRE
and follow steps 3 through 7.
9
Page 14
Programming the Panel
9. Press FIRE to exit. Proceed to your next pro-
gramming task.
10. If you are finished programming, switch the
panel PROGRAM/RUN switch to RUN (up).
The touchpad will display 1 - OFF to signal that
the system is in the normal (RUN) mode of operation.
Adding (Learning) Hardwire
Sensors
After planning the installation, use table C.1 in appendix C to select sensor groups and complete the group
assignment for each wireless sensor in the system
planning worksheets in appendix D.
Use the following procedure to add (learn) all hardwire sensors and zones into panel memory.
On hardwire zones containing multiple sensors, only one
sensor per zone needs to be added (learned) into panel
memory.
If the system uses hardwire sens ors only, turn off upper
sensor 94 (Receiver Failure) in the panel.
Only the normally closed configuration can be used in ULlisted installati ons.
8. Continue adding sensors into the current group
number by repeating step 7. Press BYPASS,
STATUS, or number buttons to select new sensor numbers.
9. To add sensors into other groups, press FIRE
and follow steps 4 through 8.
10. Press FIRE to exit. Proceed to your next pro-
gramming task.
11. If you are finished programming, switch the
panel PROGRAM/RUN switch to RUN (up).
The touchpad will display 1 - OFF to signal that
the system is in the normal (RUN) mode of operation.
To add (learn) hardwire sensors:
1. Place all hardwire sensors in their normal (nonalarm) state.
2. In PROGRAM MODE, press the touchpad
BYPASS or STATUS button repeatedly until
LEARN SENSOR is displayed.
3. Press the COMMAND button to display
GROUP __ __.
4. Enter the desired group number (00 to 29, 32).
5. Press the COMMAND button to display SEN-SOR ##.
6. Press the COMMAND button if the sensor number displayed is correct or enter another number
from 01 to 76, and then press COMMAND
again.
7. The display reads TRIP - ## . Trip the sensor by
placing it into the alarm state (open the door or
window) or as described in the sensor’s installation instructions. The display reads TRIP - ##
[next #] and interior speakers announce Sensor #
okay. Sensor [next # to be learned].
Note
The alarm state is either open or closed, depending on the
normal condition of the sensor. Multip le no rmally closed
switches are wired in series and trip p ed while the loop is
open. Multiple no rmally open switches are wired in para llel
and tripped while the loop is closed.
Deleting Sensors and Hardwire Zones
If you want to reassign a sensor or hardwire zone to
another group, you must first delete that sensor or
zone.
To delete a sensor from the panel:
1. In PROGRAM MODE, press STATUS or
BYPASS until the display reads DELETE SEN-
SOR.
2. Press COMMAND and the display reads
DELETE ## [sensor text, if any].
Note
After pressing COMMAND in step 2, the display shows the
lowest programmed sensor number.
3. If the sensor number displayed is not correct,
enter the desired number (01 to 76).
4. Press COMMAND and the display reads DEL
## OK.
5. Continue deleting sensors by repeating steps 3
and 4.
10
Page 15
Programming the Panel
6. Press FIRE to exit.
Note
Sensor text is not deleted when its sensor is deleted.
Programming Upper Sensors
Upper sensors are optional values (see appendix D,
table D.7) you turn on or off depending on your customer’s equipment and needs.
Note
We recommend tha t you d o not c hange upper sensors that
default ON. Factory default settings will work for most applications.
Use the settings recorded in appendix D, table D.7
when programming upper sensors.
To program upper sensor numbers:
1. In PROGRAM MODE, press BYPASS or STATUS until UPPER SENSOR is displayed.
2. Press COMMAND and the display reads 77 OFF TOUCHPAD TAMPER. (Press AUXIL-
IARY to scroll any long messages sideways.)
3. Press COMMAND to toggle upper sensor 77
ON, if desired, or press BYPASS to cycle to the
next upper sensor.
Note
We recommend that you do not change feature numbers
that default ON. Factory defa ul t set tings will work for most
applications .
Use the settings recorded in table D.8 when programming optional feature numbers.
To program feature numbers:
1. In PROGRAM MODE, press BYPASS or STATUS until F OPTIONS is displayed.
2. Press COMMAND to display 00 - ON REMOTE
ACCESS. (Press AUXILIARY to scroll long
messages in the display.)
3. Press COMMAND again to toggle the feature
number ON or OFF as desired.
4. Press BYPASS to display the next feature number.
Note
To jump directly to a particular feature number, enter its
number instead of pressing BYPASS.
5. Repeat steps 3 and 4 for all of the remaining feature numbers.
6. Press FIRE to exit.
Adding (Learning) Wireless
Touchpads
Note
To jump directly to a particular upper sensor, enter its twodigit number instead of pressing BYPASS.
4. Repeat step 3 until all upper sensors are programmed to suit the installation.
5. Press FIRE to exit.
Programming Optional
Feature Numbers
Optional feature numbers are system features (see appendix D, table D.8) you turn on or off depending on
your customer’s needs.
You can add up to four wireless touchpads to the system (including keychain touchpads).
To add (learn) wireless touchpads:
1. In PROGRAM MODE, press BYPASS or STATUS until LEARN TOUCHPAD is displayed.
2. Press COMMAND to display PRESS BYP TP -
1.
3. Press BYPASS on the wireless touchpad (press
and hold both lock and unlock buttons on the
wireless keychain touchpad) until the display
reads PRESS BYP TP 2 and One OK, Two is
heard.
4. Repeat step 3 for each wireless touchpad until
they are all added.
5. Press FIRE to exit.
11
Page 16
Programming the Panel
Caution
After exiting from learning touchpads, reentering the learn
touchpads menu by pressing COMMAND automatically deletes all learned touchpads. When adding wireless touchpads to the system, you must also relearn existing
touchpads.
Programming Panel
Configuration Options
This section describes how to program the following:
•Primary phone number and phone format
•Siren time-out
•Install code
•Account number
•Entry, extended, and exit delays
•Activity time-out
•House code
•Energy Saver Module (ESM) freeze and set temperatures
•Touchpad unit number, quiet, and key beeps
options
•Audio Verification Module (AVM) mode, timeout, and code
•HOM setup
•Time zone
•User-programming system settings
•Duress code
Use the panel configuration settings you recorded in
table D.5 to program the system.
To program the central monitoring station telephone number:
1. In PROGRAM MODE, press BYPASS until the
display reads PHONE NUMBER.
2. Press COMMAND. The display shows [existing
phone number, if any].
3. Enter the central station receiver phone number
(up to 18 digits). If you need a pause between
digits, press POLICE for each 1-second pause
desired.
4. Press COMMAND. The display reads [new
phone number].
5. Press FIRE to exit.
Programming the Phone
Format
The phone format det ermines th e type of comm unication the panel uses to report to the central monitoring
station’s receiver. The default phone format is “ITI.”
To program the panel telephone format:
1. In PROGRAM MODE, press BYPASS until the
display reads PHONE FORMAT.
2. Press COMMAND to display the currently
selected format. For example, ITI FMT.
3. Press BYPASS or STATUS to cycle to the
desired setting: SET ITI, -1400, or -2300.
Note
Phone format must be set to “ITI” for the panel to correctly
communicate with the ITI ToolBox Downl oa de r.
Programming the Primary
Phone Number
The panel can report alarms and all other reports to a
central monitoring station by programming the primary phone number (or central station’s phone number)
into panel memory. The default phone number is
blank (none).
12
4. Press COMMAND and the display reads SET
[selected format] OK.
5. Press FIRE to exit.
Page 17
Programming the Panel
Programming the Siren
Time-out
The siren time-out determines how long sirens sound
an alarm condition, if no one is present to disarm the
system. The default siren tim e -o ut is 4 min ute s.
To program a different siren time-out:
1. In PROGRAM MODE, press BYPASS until the
display reads SIREN TIMEOUT.
2. Press COMMAND and the display reads SIREN
- ## MIN.
3. Enter the desired two-digit time (01 to 30 minutes).
4. Press COMMAND and the display reads SIREN
- ## MIN.
5. Press FIRE to exit.
To program an install code:
1. In PROGRAM MODE, press BYPASS until the
display reads INSTALL CODE.
2. Press COMMAND to display INSTALL - ****.
3. Enter any four digits from 0001 to 9998.
Note
See table D.6 in appen di x D for cod e number defaults and
restrictions.
To return the install code to blank (****) press the POLICE
button instead of a four-digit code.
4. Press COMMAND. INSTALL - #### is dis-
played.
5. Press FIRE to exit.
Programming the Account
Number
Programming the Install Code
The install code is a special access code used to prevent accidental or unauthori zed cha nge s to syst em
programming. The default install code is blank
(****).
Caution
Always install and test all wired touchpads before entering
an install code. Programming an install co de befor e all
touchpads are installed and tested is risky. It can lead to a
situation where memory must be cleared to get int o pr ogram mode. This can happ en if a bus co nflict ren ders the alphanumeric touchpad useless (and there are no wireless
touchpads an d phone co ntrol i s turned off). In th is situat ion,
there is no way to enter an install co de—there is no way to
get back into the program mode except to erase the install
code (and all other programming) by clearing memory.
If an install code is desired, program it after installation is
complete and just before you leave the site.
Note
Once an install code is entered, it will start a 1-hour timer.
For the next hour, the install code will not be requ ired. Th is
timer is cleared by entering dealer sensor test.
The account number is a fiv e-character p anel identif ication for central monitoring stations. Used when the
panel sends reports. The default account number is
00-000.
To program an account number:
1. In PROGRAM MODE, press BYPASS until the
display reads ACCOUNT NUM BER.
2. Press COMMAND to display ACCOUNT -
#####.
3. Enter any five digits.
4. Press COMMAND. ACCOUNT - ##### is dis-
played.
5. Press FIRE to exit.
Note
Only numbers can be pr ogrammed locally though the alpha numeric touchp ad . L etters can be programmed thoug h the
CS-4000 or Downloader and will display correctly with the
panel in program mode.
13
Page 18
Programming the Panel
Programming the Entry Delay
The entry delay determines the time a user has to enter
the premises and disarm the system, before it goes
into alarm. The default entry delay is 32 seconds.
To program a different entry delay:
1. In PROGRAM MODE, press BYPASS until the
display reads ENTRY DELAY.
2. Press COMMAND and the display reads ENTR Y
- ### SEC.
3. Enter the desired three-digit time (008 to 120
seconds).
Note
The system automatically rounds off the entry to the near est
multiple of eight.
4. Press COMMAND a nd the display reads ENTR Y
- ### SEC.
5. Press FIRE to exit.
Programming the Exit Delay
The exit delay determines how much time system users have to leave the premises through a designated
delay door without causing an alarm, after arming the
system. The default exit delay is 32 seconds.
To program the exit delay:
1. In PROGRAM MODE, press BYPASS until the
display reads EXIT DELAY.
2. Press COMMAND and the display reads EXIT -
### SEC.
3. Enter the desired three-digit time (008 to 184
seconds).
Note
The system automatically rounds off the entry to the nearest
multiple of eight.
4. Press COMMAND and the display reads EXIT ### SEC.
5. Press FIRE to exit.
Programming the Extended
Delay
The extended delay affects both entry and exit delay
times for sensors in groups 11 (extended delay) and
12 (twice extended delay). The extended delay setting
determines how much time system users have to leave
the premises after arming and how much time users
have to disarm after entering, without causing an accidental alarm. The default extended delay is 4 minutes.
To program a different extended delay:
1. In PROGRAM MODE, press BYPASS until the
display reads EXTENDED DELAY.
2. Press COMMAND. The display reads DELAY -
## MIN.
3. Enter the desired two-digit time (01 to 08 minutes).
4. Press COMMAND and the display reads
DELAY - ## MIN.
5. Press FIRE to exit.
Programming the Activity
Time-out
The activity time-out determines how many hours of
system non-use are sensed, before sending a report to
the central monitoring station. The de fault activity
time-out is 24 hours.
To program a different activity time-out:
1. In PROGRAM MODE, press BYPASS until the
display reads ACTIVITY TIMEOUT.
2. Press COMMAND to display ACTIVITY - ## H.
3. Enter the desired two-digit time (01 to 24 hours).
4. Press COMMAND. ACTIVITY - ## H is dis-
played.
5. Press FIRE to exit.
Note
Upper sensor S79 (No Activity) must be on for the activity
timer to function. S79 defau lt is off.
14
Page 19
Programming the Panel
Programming the House Code
The house code is a three digit number used to communicate panel signals to line carrier devices such as
Wireless Interior Sirens (WIS) and X-10 Lamp and
Appliance Modules. The default house code is 001(X10 module house code “B”).
To program a different house code:
1. In PROGRAM MODE, press BYPASS until the
display reads HOUSE CODE.
2. Press COMMAND to display HOUSE CODE -
### [X-10 module unit code A–P].
3. Enter the desired three digit house code number
(001 to 254).
4. Press COMMAND. HOUSE CODE - ### [X-10
module unit code A–P] is displayed.
5. Press FIRE to exit.
5. Press FIRE to exit.
The Energy Saver Module set (readout) temperature
setting lets you adjust the module to match the on-premises thermostat. The default set temperature is the
unadjusted ESM temperature.
To adjust the Energy Saver Module temperature
readout, make sure that the module is wired and
working, then:
1. In PROGRAM MODE, press BYPASS until the
display reads SET TEMP.
2. Press COMMAND to display TEMPERATURE
- ##.
3. Enter present two-digit room temperature (32 to
99).
4. Press COMMAND and the display reads TEM-
PERATURE - ##.
5. Press FIRE to exit.
Programming the Energy
Saver Module Freeze and Set
Temperatures
The freeze temperature setting determines when the
Energy Saver Module’s freeze sensor activates,
sounding interior sirens and reporting to the central
monitoring station. The default freeze temperature is
42° F.
Note
Upper sensor 78 (Freeze Senso r) must be ON to enable th e
freeze alarm. Upper sensor 78 defaults to OFF.
To program the Energy Saver Module freeze temperature:
1. In PROGRAM MODE, press BYPASS until the
display reads FREEZE TEMP.
2. Press COMMAND and the display reads
FREEZE TEMP - ##.
3. Enter the desired two-digit temperature (40 to
90).
4. Press COMMAND and the display reads
FREEZE TEMP - ##.
Programming the Touchpad
Options
The touchpad options setting lets you set the touchpad
unit number, touchpad quiet, and touchpad key beeps
options.
To program the alphanumeric touchpad options:
1. In PROGRAM MODE, press BYPASS until
TOUCHPAD OPTIONS is displayed.
2. Press COMMAND to display UNIT NUMBER.
3. Press BYPASS to display the various touchpad
options.
4. Continue with the following touchpad option
procedures.
15
Page 20
Programming the Panel
Programming the Touchpad
Unit Number
The touchpad unit number lets the panel identify specific touchpads connected to the bus. Each alphanumeric touchpad must be assigned a unit number,
different than any other bus device. Use the following
guidelines when changing touchpad unit numbers:
•Always start with on e to uch p ad co nn ected to the
panel and get it operational with the panel, before
connecting additional touchpads.
•Whenever possible, such as in new installations,
assign alphanumeric touchpad unit numbers
before all other panel programming.
•Always work from one touchpad location when
assigning unit numbers for installations with
multiple touchpads.
For complete details on installing additional alphanumeric touchpads to a working system, refer to the Su-
perBus Alphanumeric Touchpad Installation
Instructions included with each touchpad.
The default touchpad unit number is 001.
To change the alphanumeric touchpad unit number:
1. In PROGRAM MODE, press BYPASS until
TOUCHPAD OPTIONS is displayed.
2. Press COMMAND. Display reads UNIT NUM-
BER.
3. Press COMMAND to display the present unit
number DA ###.
4. Press COMMAND to display ENTER _.
5. Enter the desired three digit touchpad unit number (000 to 007).
6. Press STATUS to lock in the new unit number.
Note
The touchpad will be nonfunctional after its unit number is
changed until it is reactivated as follows.
7. Switch the panel PROGRAM/RUN switch to
RUN (up) and back to PROGRAM (down) to
reactivate the touchpad with it s new unit number.
Touchpad will display PROGRAM MODE.
Programming the Touchpad
Quiet
Note
On systems with multiple alphanumeric touchpads, the following procedure puts all touchpads into the address set
mode.
Caution
Always delete (blank) the install code before adding wired
touchpads o r ch ang in g wir ed to uc hp ad un it (a dd re ss ) n umbers. The default install code is blank (****).
Programming an install code before all touch p ad s are installed and tested may prevent correct touchpad installation
and may require clearing memory and reprogra mming. If an
install code is desired, program it after installation is complete and just before you leave th e site.
To delete (blank) the install code prior to changing
the touchpad unit number:
1. In PROGRAM MODE, press BYPASS until the
display reads INSTALL CODE.
2. Press COMMAND to display INSTALL - ####.
3. Press the POLICE button. INSTALL - ****
(blank) is displayed.
4. Press FIRE to exit.
The touchpad quiet option determines whether status
sounds are heard from a specific touchpad. If there is
more than one touchpad, the following procedure
must be done at each touchpad you want changed.
The touchpad quiet default is N (no—not quiet).
To changed the alphanumeric touchpad quiet option:
1. In PROGRAM MODE, press BYPASS until
TOUCHPAD OPTIONS is displayed.
2. Press COMMAND. Display reads UNIT NUMBER.
3. Press BYPASS or STATUS until the display
reads TOUCHPAD QUIET N (no) or Y (yes).
4. Press COMMAND to toggle from Y or N.
5. Press FIRE to exit.
16
Page 21
Programming the Panel
Programming Touchpad Key
Beeps
The touchpad key beeps option determines whether
key-press sounds are heard from a specific touchpad.
The following procedure must be done at the specific
touchpad you want changed.
The touchpad key beeps default is Y (yes—keys beep
when pressed).
To change alphanumeric touchpad key beeps:
1. In PROGRAM MODE, press BYPASS until
TOUCHPAD OPTIONS is displayed.
2. Press COMMAND. Display reads UNIT NUM-
BER.
3. Press BYPASS or STATUS until the display
reads KEYBEEPS N (no) or Y (yes).
4. Press COMMAND to toggle Y or N.
5. Press FIRE to exit.
Note
The key beeps option does not actually change until the
panel RUN/PROGRAM switch is changed from PROGRAM
to RUN.
2. Press COMMAND to display AVM MODE -
[present AVM mode number].
3. Enter the desired two-digit AVM mode number:
01 - One-ring
02 - One-ring Silent
03 - Instant
09 - One-ring Fire Siren Shutdown
10 - One-ring Silent Fire Siren Shutdown
11 - Instant Fire Siren Shutdown
4. Press COMMAND. AVM MODE - [new mode
number] is displayed.
5. Press FIRE to exit.
The AVM time-out determines how long the AVM
will wait without hearing a command before hanging
up. The default AVM time-out is 90 seconds.
To change the Audio Verification Module timeout:
1. In PROGRAM MODE, press BYPASS until
AVM TIME-OUT is displayed.
2. Press COMMAND to display AVM TIME-OUT
- [present time-out in seconds].
3. Enter the desired three digit AVM time-out (030
to 300 seconds in 2-second increments).
4. Press COMMAND. AVM TIME-OUT - [new
time-out] is displayed.
5. Press FIRE to exit.
Programming the Interrogator
200 Audio Verification Module
Mode, Time-out, and Access
Code
The optional Interrogator 200 Audio Verification
Module* (AVM) allows for two-way voice communication with the monitoring station in the event of an
alarm. The AVM mode, time-out, and access code
need to be programmed. The default AVM mode is 03
(instant).
* Not intended for use with UL-listed systems.
To change the Audio Verification Module mode of
operation:
1. In PROGRAM MODE, press BYPASS until
AVM MODE is displayed.
The AVM access code helps prevent unauthorized listen-in/talk-back audio sessions. The default AVM access code is blank (****).
To program the Audio Verification Module access
code:
1. In PROGRAM MODE, press BYPASS until
AVM CODE is displayed.
2. Press COMMAND to display AVM CODE -
[pre sent access code].
3. Enter the desired four-digit AVM access code
(0001 to 9998) or press POLICE to clear the displayed code.
Note
See table D.6 in appen di x D for cod e number defaults and
restrictions.
4. Press COMMAND. AVM CODE - [new access
code] is displayed.
5. Press FIRE to exit.
17
Page 22
Programming the Panel
Programming HOM Points
The optional HOM (Hardwire Output Module) has 4
programmable output points that can be used to activate other devices, based on the syste m event ( alarm,
trouble, etc.). For example, a HOM output can be configured to activate CCTV during an intrusion alarm ,
turn on lights during a fire alarm, or activate cellular
phones or long-range radios if primary phone communications are out of service.
The following describes the basic HOM output point
configuration steps. For complete HOM setup and
programming, see the SuperBus Hardwire Output Module Installation Instructions (466-1127) included
with each HOM.
To program HOM output point configurations:
1. In PROGRAM MODE, press BYPASS until
HOM SETUP is displayed.
2. Press COMMAND to display POINT 01-#####
(the first point and it’s previously programmed
configuration code [if any]). Blank or unprogrammed points are displayed as
POINT ##- * * * * *.
3. To display other points, press STATUS, BYPASS or enter the desired two-digit point
number.
4. Press COMMAND to change the displayed
point’s configuration code. The display will
show POINT ##-_ _ _ _ _. Or press POLICE to
enter a blank number for this point.
5. Enter the point’s new 5 digit configuration number. The display will blink as you start entering
numbers. To escape this sequence without changing the previously programmed number, press
FIRE.
6. Press COMMAND to enter the new point configuration into panel memory. The display will
stop blinking.
Note: If the entered number is invalid, the display reverts to the points previously programmed
configuration number.
7. To display and/or change other points, press
STATUS or BYPASS.
8. When finished, press FIRE once to return to the
Main menu.
Programming the Time Zone
The TIME ZONE menu optio n is used to set th e time
zone where the panel is installed.
To program the panel’s time zone:
1. In program mode, press BYPASS until TIME
ZONE is displayed.
2. Press COMMAND to display the current tim e
zone setting (default = 05).
3. Enter the 2-digit number (see Table 3) that corresponds to the time zone where the panel is
located.
Table 3 Time Zone Settings
Time Zone
Eastern05
Central06
Mountain07
Pacific08
Hawaii10
4. Press COMMAND to display the new programmed time zone.
5. Press FIRE to exit.
T o uchpad
Entry
Viewing or Programming the
User-Programmable System
Settings
Certain system settings can be user programmed
while the system is in the normal (RUN) operating
mode. These are:
•Primary access code
•Secondary access codes
•Arm-disarm access codes
•High and low Energy Saver Module temperatures
•Quiet exit
•Downloader enable
18
Page 23
Programming the Panel
Use the settings recorded in appendix D, table D.6,
when programming user-programmable system settings.
To view or program the user-programmable system settings:
1. Press ACCESS CODE + STATUS + 8. SYS-
TEM SETTINGS is displayed and System memory open is announced.
Note
User programming is automatically exited after 1 minute if
no buttons are pressed.
2. Press BYPASS to display 00 - ARM CODE 1234
(default primary access code).
Note
You don’t have to program these settings in order. Press
BYPASS repeatedly to display the desired setting.To jump
directly to a system setting, enter its two-digit number (table
D.6 in appendix D) instead of pressing BYPASS.
3. Press COMMAND to display _ _ _ _.
4. Enter the desired new four-digit primary access
code (0001 to 9998).
Note
See table D.6 in appendix D for access code number defaults and restrictions.
5. Wait 5 seconds or press COMMAND to set the
new code. OK is displayed.
6. Press BYPASS to display 01 - ARM CODE ****
(the first blank default secondary access code).
7. Press COMMAND to display _ _ _ _.
8. Enter the desired new four-digit secondary
access code (0001 to 9998).
Note
See table D.6 in appendix D for access code number defaults and restrictions.
Note
See table D.6 in appendix D for access code number defaults and restrictions.
To delete a secondary or arm/disarm code, enter the same
number as the primary code.
13. Wait 5 seconds or press COMMAND to set the
new code. OK is displayed.
14. Repeat steps 10–13 for the remaining secondary
and arm-disarm access codes 03 though 23.
15. Press BYPASS to display 53 - ES LOW 50
(default Energy Saver Module low temperature
setting).
16. Press COMMAND to display _ _.
17. Enter the desired two-digit ESM low temperature
setting (45–89° F).
18. Wait 5 seconds or press COMMAND to set the
new temperature. OK is displayed.
19. Press BYPASS to display 54 - ES HIGH 90
(default Energy Saver Module high temperature
setting).
20. Press COMMAND to display _ _.
21. Enter the desired two-digit ESM high temperature setting (46–90° F).
22. Wait 5 seconds or press COMMAND to set the
new temperature. OK is displayed.
23. Press BYPASS to display 77 - QUIET OFF
(default Quiet setting).
24. Press COMMAND to change the current quiet
setting to OFF or ON. OK is displayed.
25. Press BYPASS to display 88 - DOWNLOAD OFF (default downloader setting).
26. Press COMMAND to change the current download setting to OFF or ON. OK is displayed.
27. Press BYPASS to display 99 - EXIT.
28. Press COMMAND to exit user-programmable
system settings. Good bye is announ ce d an d 1-OFF is displayed.
To delete a sec ond ar y or arm /di sa rm code , en te r the sa me
number as the primary code.
9. Wait 5 seconds or press COMMAND to set the
new code. OK is displayed.
10. Press BYPASS to display 02 - ARM CODE ****
(the second blank default seconda ry acces s
code).
11. Press COMMAND to display _ _ _ _.
12. Enter the desired new four-digit secondary
access code (0001 to 9998).
The Duress Code
The optional duress code (if enabled) lets a system
user send a silent alarm report to the central monitoring station by entering any programmed access code,
with the last two digits reversed. You don’t have to
enter a specific duress code. For example, if the pri-
19
Page 24
Programming the Panel
mary access code is 1234, the duress code is automatically 1243.
Caution
Since the use of duress access codes often result in false
alarms due to ke ystrok e err ors, it is stron gly re comme nded
that the duress access code remain disabled (off). Enable
only if absolutely necessary. If duress access codes are
needed, their use in conjunction with the Interrogator 200
Audio Verification Module is high ly recommended to reduce
false alarms and accidental disp atches.
Note
Upper Sensor number 86 (Dur ess Alarm) mus t be on to enable the duress alarm. Upper sensor 86 defaults to off.
Although the panel will not allow access codes with the
same last two digits to be programmed through the touchpad, they are allowed using the CS-4000 or Downloader.
Access codes with the same last two digits will
duress alarm repo rt.
not
send a
Adjusting the Alphanumeric
Touchpad Display Brightness
The alphanumeric touchpad vacuum fluorescent
(blue/green) display brightness and LCD (silver/
black) display background brightness is adjustable.
(Display brightness on touchpads having LED (red)
type displays is not adjustable.)
To change display brightness:
Press and hold the 1, 2, 3, or 4 touchpad button for the
desired brightness level.
Once a dimmed level is set, pressing any button momentarily returns the display to full brightne s s.
Requesting CS-4000/Downloader Programming
Although most information can be programmed from
the panel, some optional information must be programmed remotely from the central station CS-4000
or Downloader. Use the information you recorded in
appendix D, table D.9 to inform the central station of
your installation’s special programming requirements.
To set up for remote CS-4000 Central Station programming:
1. Contact your central station and ask the operator
to program the panel for the values you recorded
in appendix D, table D.9.
2. Give the operator the panel’s account number
and the phone number of the premises, and ask
them to call back immediately.
3. Hang up the phone.
4. When the phone rings, enter ACCESS CODE +
8 at the alphanumeric touchpad. The display
reads 8 - PHONE TEST and communication will
start.
5. When the central station releases the panel, 1 - OFF is displayed. The operator may call you to
discuss the programming.
Note
Feature number F33 (Downloader Access Enable) or userprogrammable system setting 88 (Download Enable) must
be set to on in ord er for remot e downloade r programming t o
be enabled. These are two different ways to change the
same value, which defaults to off.
To initiate an ITI ToolBox download session:
1. Contact your download station and ask the operator to prepare to download to the panel.
2. In PROGRAM MODE, enter the phone number
of the downloader as the panel primary phone
number.
3. Program the desired panel account number.
4. Make sure feature number F33 (Download
Access Enable) is on. F33 defaults to off.
5. Exit PROGRAM MODE.
6. Enter ACCESS CODE + 8 at an alphanumeric
touchpad.
7. The display reads 8 - PHON E TEST, the panel
speaker and all interior sirens sound one long
beep, and the speaker announces Phone test is on.
8. When the panel completes the test, the system
returns to level 1 and the speaker announces Sys-temphone test is OK. Alarm system is OFF.
9. If the panel announces Phone test failure, or Sys-tem phone test is invalid, call the downloader station to verify th e Downlo ader phone number and
that the Downloader is set up properly.
20
Page 25
Installing Line Carrier Devices
This section describes how to install the following
line carrier wireless devices:
•Wireless Interior Siren (WIS)
•X-10
Notes
The Class II Line Carrier Powe r Transfo rmer ( 60-678 ) is required for line carrier device operation.
The operation o f the la mp mod ule is f or supp lemen tary purposes only.
Lamp Module
Installing and Programming
the Wireless Interior Siren
(WIS)
Installing and programming the Wireless Interior Siren (WIS) includes the following:
•Setting the WIS DIP switches and installing the
battery
•Connecting an external siren to the WIS
•Programming the WIS house code
Setting the WIS DIP Switches
and Installing the Battery
A 9V backup battery (not included) powers the WIS
during an AC power failure. The battery type can be
alkaline, lithium, or NiCd. When backup battery voltage gets low, the WIS sounds a single beep every 60
seconds until the battery is replaced.
To set DIP switches and install the backup batteries:
1. Remove the battery cover on the back of the WIS
as shown in figure 61.
Installing Line Carrier Devices
TERMINALS
FOR WIRING
OPTIONAL
HARDWIRE
EXTERIOR
SIREN
(13-046)
BATTERY COMPARTMENT
(DIP SWITCHES INSIDE)
Figure 6 WIS Battery Cover Location
8557G21A.DS4
2. Set DIP switches as appropriate (see below).
DIP Switch 1—Battery Type
•OFF—Install an alkaline or lithium type battery.
•ON—Activates a trickle charge circuit for use
with a NiCd battery.
WARNING!
Never turn on DIP switch 1 when using an alkaline or
lithium battery. Personal injury and equipment damage
may result if these batteries are recharged, short-circuited, punctured, or discharged at higher than acceptable rates.
DIP Switch 2—External Siren Delay
•OFF—External siren terminals activate immediately during an alarm condition.
Use this setting when the siren connected to the
external siren termi nals is located in side the premises.
•ON—External siren terminals activate 15 seconds after an alarm condition occurs.
Use this setting when the siren connected to the
external siren terminals is located outside. This
helps prevent disturbing neighbors in cases of accidental alarms that last fewer than 15 seconds.
DIP Switches 3 and 4—Status Tones
•3 and 4 OFF—The WIS internal piezos and
external siren do not produce any status tones.
Use this setting wh en the WIS is installed in or
near sleeping are as.
•3 ON, 4 OFF—The WIS internal piezos produce
normal-volume status tones.
Use this setting when the WIS is installed in areas
where status tones need to be heard.
21
Page 26
Installing Line Carrier Devices
•3 OFF, 4 ON—The WIS internal piezos and
external siren produce high-volume status tones.
Use this setting when status tones need to be
heard in remote areas, inside and out side of the
premises.
Caution
Never turn on both DIP switches 3 and 4; doing so ma y permanently damage the WIS.
3. Connect the battery to the battery clip and insert
the battery into the compart m en t.
4. Replace the battery cover.
Connecting an External Siren
to the WIS
Figure 7 shows how to connect the Hardwire Exterior
Siren (13-046) to the WIS terminals. These terminals
activate for alarms only and provide 100 mA maximum current at 6 VDC.
Caution
Only the Hardwire Exter ior Siren (13-046) ca n be connected
to the WIS terminals. Other sirens may draw more current
than the WIS can provide and can cause permanent damage to the WIS.
Programming the WIS House
Code
1. Plug the WIS into an outlet that is not controlled
by a switch.
2. Press CODE + 1 on the alphanumeric touchpad.
3. The WIS sounds one beep and the WIS LED
flashes, indicating the WIS received the signal
from the panel.
Note
If WIS DIP switches 3 and 4 are set to OFF, no beep will be
heard. You must cause an alarm for the WIS to sound.
4. If the WIS does not respond, unplug it and disconnect the batte ry. Wait at least 30 seconds, and
then reconnect the battery and repeat steps 1 and
2. If the WIS still does not respond, proceed to
appendix B, “Troubleshooting.”
5. To permanently mount the WIS, unplug it and
remove the outlet cover screw.
6. Plug the WIS into the outlet and secure it with
the outlet screw.
WARNING!
Use extreme caution when securing the WIS to a metal
outlet cover. You could receive a serious shock if the
metal outlet cover drops down onto the prongs of the
plug while you are securing the WIS and cover to the
outlet box.
OBSERVE
BATTERY
COMPARTMENT
(DIP SWITCHES
INSIDE)
Figure 7 Wiring the Hardwire Exterior Siren to the
WIS
+
HARDWIRE EXTERIOR SIREN (13-046)
100 mA MAXIMUM DRAW
POLARITY
8557G23A.DS4
22
Installing X-10 Lamp Modules
When installing X-10 Lamp Modules:
• Use only incandescent lamps.
• Do not plug X-10 Lamp Modules into outlets con-
trolled by a switch.
• Do not use extension cords to connect several
lamps to one module.
Caution
Use X-10
X-10
trolled during an alarm.
Lamp
Appliance
Modules to control lig ht fixtures. Do n ot use
Modules. Appliance Modules are not con-
Page 27
Testing the System
To install X-10 Lamp Modules:
1. Plug the lamp cord into the bottom of the lamp
module.
2. Plug the module into a lower AC outlet.
3. Refer to table D.5 in appendix D for the house
code you programmed into the panel, and then
find the letter that corresponds to that house code
from table C.3 in appendix C. Each letter setting
represents 16 possible panel hous e code s. Fo r
example, house code 113 corresponds with “B”
on the X-10 Lamp Module’s house dial.
4. Set the house dial on the module to the appropriate letter.
5. Set the unit number dial from 1 to 9 as shown in
table C.4 in appendix C.
Note
X-10 Lamp Module unit numbers 1 and 2 have special system functions: unit 1 provides entry and exit lighting, and
unit 2 provides visual ind icat io n of armin g le vel. X-10 App liance Modules as signed to unit s 3–9 can be individ ually controlled from the touc hp ad and are automatica lly t ur ned off
during police alarms.
Testing the System
This section describes how to perform the following
test procedures:
• Testing sensors
• Testing the Energy Saver Module
• Testing the Hardwire Input Module
• Testing the X-10 Lamp Modules
• Testing phone communication
• Testing central station communications
You should test the system after installing, after servicing, and after adding or removing devices from the
system. Refer to the troubleshooting chart in appendix
B for troubleshooting help.
Testing Sensors
Note
While the sensor test is a valuable installation and service
tool, it only tests sensor operation for the current conditions.
You should perform a sensor test after any change in environment, equipment, or programming.
1. Set the panel PROGRAM/RUN switch to RUN
(up) and attach, cl ose, a nd sec ure t he pan el cov er.
2. Place all sensors in their secured (nonalarm)
state.
3. Enter ACCESS CODE + STATUS + 9 (dealer
sensor test) at an alphanumeric touchpad.
4. The speaker announces “Sensor test is on,” interior sirens and speakers sound one long beep, and
the display reads 9 - SENSOR TEST.
5. Trip each sensor one at a time.
6. Interior sirens and speakers sound transmission
beeps as each sensor is tripped. Each beep represents one data round.
7. Count the number of transmission beeps and
refer to table 3 for minimum requirements.
8. After the beeps, [sensor #] OK is displayed con-
firming the sensor number tested. If the system
does not respond, or if the sensor does not meet
the minimum transmission beep requirements,
refer to the “If a Sensor Fails the Sensor Test”
section.
9. Press the STATUS button when you think all
sensors are tested. The system announces any
untested sensor numbers.
If all sensors have been tested, the alphanumeric
touchpad displays ALL SENSOR OKAY and the
speaker announces “Sensor test is on. All sensor test okay.”
10. Test all untested sensors. The system stays in
sensor test for 15 minutes, preservi ng the list of
untested sensors. After 15 minutes the panel disarms to level 1, aut omatically.
11. Enter ACCESS CODE + STATUS + 9 while
the system is still in sensor test if you need more
time to complete the sensor test.
12. Enter ACCESS CODE + 1 to exit sensor test.
13. The system disarms to level 1, and the speaker
announces “Alarm system is off.”
We recommend that you test the sensors after all programming is completed and whenever a sensor-related problem occurs.
Note
While in dealer sensor test, a sensor will not beep unless
there is at least 10 dB of wireless signal margin.
23
Page 28
Testing the System
Table 4 Minimum Transmission Beeps
Type of Sensor
Wireless Intrusion Sensors7–8 beeps
Wireless Smo ke & Heat Sensors7–8 beeps
Wireless Environmental/Panic Buttons7–8 beeps
Hardwire Loops1
Panel Emergency Buttons1
Number of
Beeps
If a Sensor Fails the Sensor
Test
If sirens do not beep when a sensor is tripped, use an
ITI RF Sniffer (60-401) test tool to verify that the sensor is transmitting. Constant beeps from the RF Sniffer indicate a runaway (faulty) sensor. Remove the
sensor’s battery and replace the sensor.
If possible, locate sensors within 100 feet of the panel.
While a transmitter may have a range of 1,000 feet or
more out in the open, the environment at the installation site can have a significant effect on transmitter
range. Sometimes a change in sensor location can
help overcome adverse wireless conditions.
To improve sensor communication, you can
• reposition the sensor,
• relocate the sensor,
• if necessary, replace the sensor.
To reposition a sensor:
1. Rotate the sensor and test for improved sensor
communication at 90 and 180 degrees from the
original position.
2. If poor communication persists, relocate the sensor as described as follows.
To relocate a sensor:
1. Test the sensor a few inches from the original
position.
2. Increase the distance from the original position
and retest until an acceptable locatio n is found.
3. Mount the sensor in the new location.
4. If no location is acceptable, replace the sensor.
To replace a sensor:
1. Test a known good sensor at the same location.
2. If the transmission beeps remain below the minimum level, avoid mounting a sensor at that location.
3. If the replacement sensor functions, contact ITI
for repair or replacement of the problem sensor.
Testing the Energy Saver
Module (ESM)
Note
Upper sensor number 88 must be on to ena ble the Energy
Saver Module.
To test the Energy Saver Module:
1. Press STATUS + STATUS to display the system status, ENERGY SAVER OFF, and the
present TEMPERATURE ##. The temperature
displayed (and/or announced) should match the
house thermostat. If the temperatures do not
match, refer to “Programming the Energy Saver
Module Freeze and Set Temperatures” section or
the “Troubleshooting” table in appendix B.
2. Press COMMAND + 5 to turn the energy saver
function on. The display will indicate ENERGY SAVER ON and the ESM relay will click once.
3. Press COMMAND + 5 again to turn the energy
saver function off. The display will indicate
ENERGY SAVER OFF.
Note
There is a 5-minute de lay after the Ene rgy Saver Module re turns control to the furnac e/AC before it will override the fur nace/AC again.
If the red ESM LED is not flashing continuously, set the panel PROGRAM/RUN switch to RUN and turn off the panel
power switch. Verify th at all wiring is correct and th at all bus
devices (including hardwire touchpads) are set with different unit numbers.
Whenever the ESM unit number is changed, you must turn
off the panel power switch, turn it back on, and then enter
the program mode for the panel and ESM to communicate
successfully.
24
Page 29
Testing the System
Testing the Hardwire Input
Module (HIM)
To test the optional Hardwire Input Module:
1. Verify that all wiring at the panel and the HIM
are correct.
2. Turn on the panel power switch.
Note
If the red HIM LED is not flashing continuously, set the panel
PROGRAM/RUN switch to RUN and turn off the panel power switch. Verify that all wiring is correct and that all bus devices (including hardwire touchpads) are set with different
unit ID numbers.
Whenever the HIM unit ID number is changed, you must
turn off the pane l power switch , turn it bac k on, and the n enter the program mode for th e pane l an d HI M to commu nicate successfull y.
If the system uses hardwire sensors only, turn off upper
sensor 94 (Receiver Failure) in the panel.
3. Set the panel’s PROGRAM/RUN switch to
PROGRAM.
If the alphanumeric display continues to read 1-OFF and the 1 is flashing, you must enter the install code (four digit install access code) to get the
panel into the program mode.
The alphanumeric display should read PRO-GRAM MODE and the red HIM LED should be
flashing continuously, indic atin g suc cess ful bus
communication with the panel.
4. Set the panel’s PROGRAM/RUN switch to RUN
and refer to the “Testing Sensors” section for
testing hardwired sensors connected to the HIM.
Testing the Hardwire Output
Module (HOM)
To test the optional Hardwire Output Module:
1. Verify that all wiring at the panel and the HOM is
correct.
2. Turn on the panel power switch.
3. Set the panel’s PROGRAM/RUN switch to
PROGRAM.
If the alphanumeric display continues to read 1-OFF and the 1 is flashing, you must enter the install code (four digit install access code) to get the
panel into the program mode.
The alphanumeric display should read PRO-GRAM MODE and the red HOM LED should be
flashing continuously, indicating successful bus
communication with the panel.
4. Set the panel’s PROGRAM/RUN switch to
RUN.
5. Activate each of the programmed system triggering events to verify correct HOM output
response.
Note
If the red HOM LED is not flashing continuously, set the
panel PROGRAM/RUN switch to RUN and turn off the panel power switch. Verify that all wiring is correct and that all
bus devices (inclu ding har dwire touc hpads ) are set wit h different unit ID numbers.
Whenever the HOM unit ID number is changed, you must
turn off the panel powe r switch, tur n it back on, and then enter the program mode for the panel and HOM to communicate successf ully.
Testing the X-10 Lamp
Modules
Refer to table C.4 in appendix C for X-10 lamp and
appliance module control operation.
To test the X-10 Lamp Modules:
1. Press COMMAND + 0 repeatedly to turn all
lights on and off together. Appliance modules, if
any, are all turned off by pressing COMMAND + 0 but are not all turned on this way.
2. Press BYPASS + 1 repeatedly to turn light 1 on
and off.
3. Repeat step 2 for remaining assigned lamp and
appliance module unit numbers.
4. Press ACCESS CODE + 3 to arm the system to
Level 3-Away. Unit 1 light should turn on and
stay on for 5 minutes. Unit 2 light should blink
three times to indicate the arming level. All
remaining lights should be unaffected.
5. Press ACCESS CODE + 1 to disarm the system.
If Unit 1 light was on for an entry or alarm, it
25
Page 30
Testing the System
will turn off in 5 minutes. Unit 2 light should
blink once to indicate arming Level 1-Off. All
remaining lights should be unaffected.
6. Lights should turn on and remain on during fire
and auxiliary/medical alarms and flash during a
police or an intrusion alarm.
Testing Phone Communication
Perform a phone test to check the phone communication between the panel and the central s tation.
To perform a phone test:
1. Enter ACCESS CODE + 8 at an alphanumeric
touchpad.
2. The display reads 8 - PHONE TEST, the panel
speaker and all interior sirens sound one long
beep, and the speaker announces Phone test is on.
3. When the panel completes the test, the system
returns to level 1 and the speaker announces
Phone Test is OK. Alarm system is OFF.
4. If the panel announces Phone test failure, pro-
ceed to the following instructions.
To test communication with the central station:
1. Call the central station and tell the operator that
you will be testing the system.
2. Arm the system.
3. Test each of the touchpad and wireless panic buttons and trip at least one sensor of each type—
fire, intrusion, etc.—to verify that the appropriate
alarms are working correctly.
4. If an Audio Verification Module is installed, verify that it is operating correctly and that the central station can both listen-in and talk-back
through it.
5. When you finish testing the system, call the central station to verify that the alarms were
received.
Note
If you experience trouble commu nicating with the central
station (or Downloader), ver ify the panel’s primary pho ne
number and also that panel feature number F33 (Down loader Access Enable) is turned on. Also verify panel feature
number F43 (Demo Kit Mo de) is turned off (def ault sett ing).
If F43 is on, the account number defaults to “UD-EMO” to let
the central station know that the panel is in the demo kit
mode of operation a nd that special demo d ef aults and special alarm handling is in force.
Displaying the Panel
If the phone test fails:
1. Check that the panel is plugged into the RJ-31X/
CA-38A phone jack.
2. Enter ACCESS CODE + 8 again.
3. If the phone test fails again, check the phone
number programmed into the panel.
4. If the phone test fails again, check the phone connection wiring.
Testing Central Station
Communication
After performing sensor and phone tests, check that
the system is reporting alarms successfully to the central station.
Version Code
After testing and troubleshooting the system (as outlined in this section and in appendix B) you may require Technical Support assistance. To precisely
identify the panel hardware and software to support
personnel, you can display the panel hardware/software version code.
To display/announce the panel version code:
1. Set the panel RUN/PROGRAM switch to RUN.
2. Enter primary ACCESS CODE + STA TUS + 7.
The alphanumeric touchpad will display
YYY*XXX and System YYY Level XXXX will be
announced. YYY represents the panel family
(hardware) product code and XXXX represents
the EEPROM (software) version code.
26
Page 31
Appendix A: Command Summary
Appendix A: Command Summary
This appendix contains a summary of all system user commands and what each command does. For operating
command details refer to the Security and Home Automation Owner’s Manual.
User Operating Command Summary
Table A.1 provides a description of all commands for operating the system. For commands that require an access
code, use either the primary or secondary access code unless otherwise indicated. While these are called user operating commands, you may need to use some or all of these commands during the installation and programming process. In the table, CODE represents the four-digit access code (default is 1234).
Press and hold buttons 1–4
(1–full dim, 4–full bright)
System yyy
(EEPROM code)
(product code)
Level xxxx
* Feature number F37 (Quick Arming) must be on to enable short arming commands. This short command only works
when arming to a higher level.
† This command only works if the sensor you are bypassing is active in the cu rrent security le vel.
‡ This command only works when upp er sen so r 87 is off an d you are unbypas si ng a sen so r tha t is already bypass ed .
System Settings (User-Programming) Command Summary
Table A.1 provides a description of all user-programming commands. For commands that require an access code
(CODE), use the primary access code (default is 1234).
To enter the user-programming mode, press CODE + STATUS + 8. The system will announce System memory open. Press BYPASS or STATUS buttons to scroll through the list of system settings. Proceed to any of the
desired actions listed in table D.6.
To exit user-progamming mode at any time, press BYPASS + 99 + COMMAND + COMMAND. Or, wait 1
minute—system will automatically announce Good-bye and return to the normal mode of operation..
Table A.2 Summary of System Settings (User-Programming) Commands
ActionCommandDisplay/Voice Message Confirmation
Enter new primary
access code 00
Enter new secondary
access code (01-04)
Enter new arm/disarm code 05–23
Enter new Energy
Saver Module low
temperatur e setting
Enter new Energy
Saver Module high
temperatur e setting
This appendix contains a summary of system troubleshooting suggestions.
Table B.1 Troubleshooting System Problems
FeatureProblemSolution
Access Code
Customer cannot remember access code(s).
1. Check your records to see if you have the customer’s access
code(s) on file.
2. If panel is monitored, trap the panel and read the access code(s)
from the CS-4000 or read the access code(s) from the Downloader.
3. If panel is not monitored, clea r memory and reprogram the pane l
locally.
Installer cannot remember install code.
1. Check your records to see if you have the install code on file.
2. If panel is monitored, trap the panel and read the access code(s)
from the CS-4000 or read the access code(s) from the downloader.
3. If the panel is not monitored and has no access to downloading,
clear memory and reprogram the panel locall y.
Appendix B: Troubleshooting
Some access codes do “strange things.”
Arming/Disarming
System won’t arm.
Batteries
Touchpad indicates
Touchpad indicates
1. Codes containing the number 6 are reserved. 6 is used for phone
sensor bypassing.
2. Codes 7777, 8888, and 9999 are reserved for phone panic alarms.
3. Access code’s last two digits must not be the same for correct
duress code operation. (See duress code feature in this table.)
1. If arming to level 2, ma ke sure all monitored perimeter doors and
windows are closed.
2. If arming to level 3, make sure all perimeter and interior sensors are
closed.
3. Press STATUS for an indication of the problem.
CPU low battery
Check the panel backup batter y and connections and repl ace if necessary. Also, refer to the panel power LED section in this table.
[sensor #] trou ble
Replace the indicated sensor’s battery.
and/or
and/or
System battery failure
Sensor [sensor #] low battery
is heard.
is heard.
29
Page 34
Appendix B: Troubleshooting
Table B.1 Troubleshooting System Problems (Continued)
FeatureProblemSolution
Bypass
Touc hpad indicates
System cancels sensor bypass when you try to arm to level 2 or 3.
Central Station Reporting
Central station is not receiving reports from panel.
Duress Code
Optional duress code is not working.
Fail
and/or
Invalid
is heard when you attempt to bypass a sensor.
Sensor may already be bypassed or you are trying to bypass a 24hour sensor that cannot be bypassed or a sensor that is not active in
the current security level.
Arm to the d esired level before bypassing a sensor.
1. Check that the DB-8 Cord is plugged into the pane l phone ja c k and
into the RJ-31X/CA-38A Jack.
2. Check for proper RJ-31X/CA-38A Jack to phone line wiring.
3. Verify with the central station operator that the correct receiver line
phone number is programmed into the panel. Reprogram the phone
number and retes t, if necessary.
4 Ve rify th at the correct phone format (ITI or 4/2) is being used.
5. Replace faulty RJ-31X/CA-38A Jack.
6. Replace faulty DB-8 Cord.
7. Check that the pr emis es phone line is workin g.
8. Perform a phone test.
1. Make sure last two digits of access code are not the same. (See
access code feature in this table.)
2. Check that upper sensor 86 (duress alarm) is on.
False Alarm
Alarm is being sent by mist ake.
Enter ACCESS CODE + 1 immediately to cancel the alarm. This com-
mand bypasses the alarm if done within 15 seconds after activation
(feature nu mbe r F0 6 [Dia le r Ab ort] must be on). The sys te m will
announce alarm bypassed and report will not be sent to the monitoring station.
Note
Fire alarms and duress detections cannot be bypassed.
Hardwire Alphanumeric Touchpad
Touchpad display seems “stuck” in the program mode.
Check that panel PROGRAM/R UN switch is set to RUN (up).
Touc hpad displays incorrectly or displays
1. If panel has been preprogrammed with an install code, enter the
four-digit install code at a working touchpad or from a telephone .
2. Check for har dwir e bus address confilct (two device s having the
same device address).
3. Check for out-of-range device address number. Should be 000–
007.
DA ###
and does not respond to buttons.
30
Page 35
Table B.1 Troubleshooting System Problems (Continued)
FeatureProblemSolution
Hardwire Alphanumeric Touchpad (Continued)
Appendix B: Troubleshooting
Touchpad displays
Touchpad appears “dead” (no display or response to buttons).
Hardwire Output Module
LED is off (not blinking).
LED stays on.
**********
1. Reset the touchpad by switching into and out of program mode.
Switch the panel PROGRAM/RUN switch from RUN to PROGRAM.
Enter the f our-dig it in stall c ode if p anel h as been prepro gr ammed wit h
one using a working touchpad or telephone. Switch the panel PROGRAM/RUN switch bac k to RUN again.
2. Check for har dwir e bus miswiring.
1. Check that the wiring connector is plugged into the back of the
touchpad.
2. Check for har dwir e bus miswiring, op en s, or shorts.
3. Check panel fuse F2.
1. Check HOM and panel fuses.
2. Check wiring at HOM and panel.
3. Check that HOM unit numb er setting is differe nt from all other connected bus devices.
4. Check for proper panel/HOM initialization after changing unit numbers.
’ and does not respond to buttons.
1. Reinitialize panel and HOM by turning panel power off and on.
2. HOM circuit failure. Replace HOM.
LED blinks but outputs don’t activate.
1. Check panel/HOM programmi ng .
One output never activates.
1. Check panel/HOM programmi ng .
2. Check that the po in t (HO M ou tput) programmed trigger event actually occurs.
3. Check wiring at HOM terminals and connected device.
Output(s) activ a te s on ly mome n taril y.
1. Check that the panel/HOM point progr a mmin g (HOM outpu t) uses
the correct re sponse configu ration.
Output(s) activates randomly.
1. Check HOM and panel fuses.
2. Check wiring routing and length between panel and HOM.
3. Check that HOM unit numb er set ting is different from all other connected bus devices.
Hardwire Output Module (Continued)
HOM tamper input is inoperable.
31
Page 36
Appendix B: Troubleshooting
Table B.1 Troubleshooting System Problems (Continued)
FeatureProblemSolution
1. Some panels and panel ve rsions do not “read” the HOM’s built-in
tamper input status. Conn e ct the HOM tamper switch to a pa ne l or
HIM zone input.
One output stays activated.
1. Check to see if the point is pro grammed f or a 3-minute “on” time
and if the triggering event for the point is repeatedly resetting the 3minute timer.
2. Output may have failed or been overloaded. Reprogram to use a
different (unused) output.
Hardwire Siren
Exterio r sirens are not pr oducing alarm sounds.
1. Check for 12 to 22 VDC between panel terminals 3 and 4 and
for 12 VDC between terminals 4 and 12.
2. Check panel fuses F1 and F2.
3. Check for correct wiring at the siren and panel terminals.
4. Check for required jumper wire between panel terminals 5 and 12.
Exterior sirens produce status sounds.
Interior sirens are not producing sounds.
Hardwire Zones
Panel does no t res po n d to ha rd wire zone input.
Touc hpad indicates
Check for correct wiring at the siren and panel terminals.
1. Check for 12 VDC between panel terminals 17 and 18 with siren
on.
2. Check panel fuses F1 and F2.
3. Check for correct wiring at the siren and panel terminals.
4. Make sure that F11 (Interior Siren Sounds Disable) feature is off.
1. Check that zones are programmed into panel and add if missing.
2. Make sure that z o ne is in a restoral-re q uired group or make sure
that system is armed to active level before tripp ing sen sor.
3. If optional HIM zone, check that the HIM LED is blinking to show
communication with panel .
Note
Panel hardwire zones are ignored for 1 minute following power-on
(HIM zones are not ignored for this period).
[sensor #], trouble
1. Check that the 4.7K ohm end-of-line resistor is correctly installed in
the zone loop circuit.
2. Check normally open (N/O) circ u it for a break in the wires.
3. Check normally closed (N/C) circ uit for a short in the wires.
and/or
Sensor [sensor #], trouble
is heard.
Lights
32
Light fixture using X-10 Lamp Module does not work.
Page 37
Table B.1 Troubleshooting System Problems (Continued)
FeatureProblemSolution
See X-10 Lamp Modules feature in this table.
Panel
Panel does not power up. Panel LED is off and alphanumeric touchpad display is dark.
1. Check that panel power switch is on.
2. Check the AC circuit breaker to be sure the circuit is live.
3. Check that the backup battery is installed correctly, the battery
wires are connected, and the AC power transformer is plugged in.
4. Check for proper panel and transformer wiring.
5. Measure the incoming AC voltage at th e pa nel terminals. Should
read from 16 to 18.5 VAC at panel terminals 1 and 2.
No incoming AC voltage at panel terminals 1 and 2.
1. Unplug the AC power transformer and disconnect the wire s from
the transformer and the panel.
2. Check transfomer to panel wire for short or open circuits.
3. Plug in the transformer and check for 16.5 VAC at the transformer
unconnected terminals. If zero (0) volts, replace the transformer.
Appendix B: Troubleshooting
Panel power LED is on constantly, display indicates
Battery failure.
1. Check that the backup battery is installed correctly, the battery
wires are connected, and the AC power transformer is plugged in.
2. Measure the incoming AC voltage at th e pa nel terminals. It should
read from 16 to 18.5 VAC at panel terminals 1 and 2.
3. Remove the backup battery power by disconnecting the battery’s
red (positive) wir e.
4. Check for 13.5 to 13.9 VDC battery charging voltage between
panel terminal 4 (GND) and the disconnected battery red wire . If the
charging voltage is not within range, call Technical Services.
5. Check for 11.5 to 13.9 VDC battery voltage between the backup
battery’s spade lugs. If the battery voltage is not within the recommended range, replace the battery.
Note
When the panel is running a backup battery test, the reading at the
connected battery can range from 11.4 to 13.7 VDC. The panel automatically runs a backup battery test under the following conditions:
(1) on initial power-up. (2) during sensor test (not dealer sensor test),
(3) once every minute when backup battery has failed, (4) once every
24 hours, at the programmed STIME.
6. Restore the ba ck up batt ery pow er by recon nectin g the ba ttery’ s red
wire.
Note
While the AC po w er tran sf ormer is plug ged in, the pan el automati cally
charges the bat tery. While the battery is chargin g f or t he first time it is
normal for the system to indicate
take a number of hours depending on the battery’s initial charge.
Once the battery reaches 12.5 VDC (full charge as measured while in
battery test), the arming level stops flashing. If the trouble condition
persists after 24 hours, replac e the backup bat tery.
CPU Low Battery
or voice sounds
System battery fail ur e
. This can
Panel (Contin ued)
33
Page 38
Appendix B: Troubleshooting
Table B.1 Troubleshooting System Problems (Continued)
FeatureProblemSolution
Phones
Panel power LED is flashing, and after pressing ST ATUS the touchpad indicates
power failure
Loss of dial tone on premises phones after wiring the RJ-31X Jack or connecting the
DB-8 Cord.
. (Panel continues to operate from backup battery.)
1. Check the AC circuit breaker to be sure the circuit is live.
2. Check for proper panel and transformer wiring.
3. Check that the transformer is plugged into a nonswitched outlet and
secured with the provided screw.
4.Check that the transformer is supplying AC to the panel. (Transformer internal fuse may be blo wn .)
WARNING!
Be careful when securing the transformer to an outlet with a metal
cover. Hold the cover tightly in place. You could receive a serious
shock if the metal outlet cover drops down onto the prongs of the plug
while you are securing the transformer and cover to the outlet box.
1. Wait 2 minutes and try again. The panel may be busy trying to
report to the CS-4000.
2. Check the RJ-31X Jack’s wiring.
3. Check the panel connection to the DB-8 Cord.
4. Replace the RJ-31X Jack.
5. Replace the DB-8 Cord.
6. Perform a phone test after troubleshooting the phone line.
AC
Sensor
Smoke Sensor
Constant dial tone, preventing dial out on premises phones.
Polarity-sensitive phones exist on the premises. Reverse the phone
wires connected to the brown and gray wire terminals on the RJ-31X
Jack.
Phone does not work.
Disconnect the panel DB-8 Cord from the RJ-31 Jack. If the phone
still doesn’t work, the system is ok ay and the problem is in the wiring.
Touc hpad indicates
Touchpad indicates
Touchpad indicates
heard.
Beeps once every minute.
[sensor #] trouble
Replace the sensor’s cover, if it is off. Trip the sensor.
[sensor #] supervisory
The sensor is not co m m unicating with the panel.
Sensor [sensor #] trouble
Replace the indicated sensor’s battery.
and/or
Sensor [sensor #] trouble
and/or
Sensor [sensor #] failure
and/or
Sensor [sensor #] low battery
is heard.
is heard.
is
Trouble Beeps (see also
34
Batteries are low. Replace all of the smoke sensor batt eries.
Panel
)
Page 39
Table B.1 Troubleshooting System Problems (Continued)
FeatureProblemSolution
Press STATUS for an indication of the problem. Doing a status or disarm (level 1) dis-
ables the trouble beeps for 10 hours.
Wireless Interior Siren (WIS)
No sound or LED activity from the siren.
1. Check that the panel AC transformer is plugged into an outlet.
2. Check that the WIS is not plug ged into an outlet controlled by a
switch. Relocate to a different outlet, if necessary.
3. Program the house code into the panel and set the WIS DIP
switches.
4. Check that the panel i s powered by the special two-wire Class II
Line Carrier Power Transformer.
5. Make sure that the WIS is on the sa me ele ctrica l ph as e wiring as
the AC power transformer. Relocate the WIS to various outlets to
identify compatible locations.
6. Move the WIS to a circuit that is not used by any other appliances.
Intermittent siren operation.
Appendix B: Troubleshooting
The WIS beeps once every minute.
Wireless Sensors
The panel does not respond to sensor activity . There are no alarm, chime, or sensor test
sounds.
The panel responds intermittently to wireless sensor signals.
1. Check that the WIS is not plug ged into an outlet controlled by a
switch. Relocate to an unswitched outlet.
2. Move the WIS to a circuit that is not used by any other appliances.
The WIS may ha ve a low battery. Replace with the appropriate battery
based on the setting of DIP switch 1. (ON = NiCd, OFF = alkaline or
lithium.)
1. Check that the wireless sensor battery is installed.
2. Check the sensor battery for low voltage. Replace batteries, if necessary.
3. Use an RF Sniffer (6 0- 401) to verify that se nsor is transmittin g .
4. Check that th e sens or is pr ogr ammed (learned) in to pa nel memo ry.
Learn the sensor, if necessary.
5. Verify that both panel antennas are installed and connections tight.
1. Rotate the sensor posi tion from 90 to 180 degrees.
2. Mount the sensor in a different location.
3. Verify that both panel antennas are installed and connections tight.
Wireless Touchpads
The panel does not respond to wireless touchpad commands.
X-10 Lamp Modules
1. Operate touchpads from different locations to locate areas of intermittent operation.
3. Program or reprogram the touchpad(s) into the panel.
35
Page 40
Appendix B: Troubleshooting
Table B.1 Troubleshooting System Problems (Continued)
FeatureProblemSolution
Light fixtures controlled by the X-10 Lamp Module are not working.
1. Check that the lamp ha s a working bulb and that the lamps switch
is on.
2. Confirm the lamp’s operation at a working outlet.
3. Check tha t th e la mps are plug ged into X-10 Lamp Mod ules an d th e
X-10 Lamp Modules are plugged into outlets that are not controlled by
a switch. Relocat e to non switched outlets, if necessary.
4. Check that the panel is powered by the special two-wire Class II
Line Carrier Power Transformer ((60-678).
5. Check that the HOUSE dial on the X-10 Lamp Module matches the
house code programmed into the panel.
36
Page 41
Appendix C: Programming Tables
Appendix C: Programming Tables
This appendix contains tables for selecting sensor group numbers and X-10 Lamp and Appliance Module house
and unit codes. Table notes appear at the bottom of the table, on the next page.
† This house code is reserved for demo panels only.
40
Page 45
Appendix C: Programming Tables
Table C.4 X-10 Lamp and Appliance Module Operation
Condition
On Arming to Level 1-Off
(Not if disarming to level 1 after an
alarm–see below)
On Arming to Level 2-St ayOn for 5 minutes2 BlinksUnchangedUnchange d
On Arming to Level 3-AwayOn for 5 minutes3 BlinksUnchangedUnchanged
On Disarming Any Alarm to Level 1On for 5 minutes1 BlinkOn for 5 minutesIf on, off after 5
On Fire Alarm*On†On†On†Unchanged†
On Police Alarm*Flashing†Flashing†Flashing†Off
On Auxilliary Alarm*On†On†On†Unchanged†
After Fire or Auxiliary Alarm Time-
*Fire alarms hav e priority over bot h police and auxiliary alarms. Police alarms have priority over
auxilliary alarms.
†Stays on until ma nually turned off or until 5 minutes after the system is disarmed to Le vel 1-Off.
41
Page 46
Appendix D: System Planning Worksheets
_
_
_
_
Appendix D: System Planning
Worksheets
Fill in customer information about this installation:
Customer
Address
City
Country
* Not UL listed; not intended for use in UL listed systems.
Siren Time-out01–30 min.4 min.
Install Code0001–9998 or
Account Number00000–99999 00 –0 00
Entry Delay008–120 sec. 32 sec.
Extended Delay01–08 min.4 min.
Exit Delay008–18 4 se c. 32 sec.
Activity Time-out01–24 hr.24 hr.
House Code001–254001
Freeze Temp (ESM) 40–90° F42° F
Set Temp (ESM)32–99° F –
Touchpad Options:
Unit Number 000–0071
Touchpad Quiet Y or NN
Key Beeps Y or NY
AVM Mode01–03, 09–
AVM Time-out030–300 sec.90 sec.
AVM Code0001–9998* or
HOM Setup‡
Time Zone05 (Eastern)
* Any four dig it sequence different than primary, install,
secondary, or arm-disarm access codes, 7777, 8888,
9999, or any number of 6s. Last two digits cannot be the
same.
† If the Phone Format is set to 4/2 1400 or 2300Hz for-
If the AVM Mode is set to instant modes 3 or 11 and the
Phone Format is set for 4/2 1400 or 2300Hz format, the
central station must be set with the panel’s account number in the ATRAP (audio trap) table. The panel will not
hang up the phone when the report is complete, but will
remain on the line for the AVM Time-out duration.
‡ For HOM setup refer to the Hardwire Output Module
(HOM) Installation Instructions document 466-1032,
included with each HOM.
44
Page 49
Appendix D: System Planning Worksheets
Table D.7 System Settings
NO.FeatureChoicesSetting
System Setting (default)
00Arm Code
(Primary)
01Arm Code
(Secondary)
02Arm Code
(Secondary)
03Arm Code
(Secondary)
04Arm Code
(Secondary)
05Arm Code
(Arm-Disarm)
06Arm Code
(Arm-Disarm)
07Arm Code
(Arm-Disarm)
08Arm Code
(Arm-Disarm)
09Arm Code
(Arm-Disarm)
10Arm Code
(Arm-Disarm)
11Arm Code
(Arm-Disarm)
12Arm Code
(Arm-Disarm)
13Arm Code
(Arm-Disarm)
14Arm Code
(Arm-Disarm)
15Arm Code
(Arm-Disarm)
16Arm Code
(Arm-Disarm)
17Arm Code
(Arm-Disarm)
18Arm Code
(Arm-Disarm)
19Arm Code
(Arm-Disarm)
20Arm Code
(Arm-Disarm)
21Arm Code
(Arm-Disarm)
22Arm Code
(Arm-Disarm)
23Arm Code
(Arm-Disarm)
0001–9998
(Defaul t: 1234)
0001–9998 or
****(blank)
0001–9998 or
****(blank)
0001–9998 or
****(blank)
0001–9998 or
****(blank)
0001–9998 or
****(blank)
0001–9998 or
****(blank)
0001–9998 or
****(blank)
0001–9998 or
****(blank)
0001–9998 or
****(blank)
0001–9998 or
****(blank)
0001–9998 or
****(blank)
0001–9998 or
****(blank)
0001–9998 or
****(blank)
0001–9998 or
****(blank)
0001–9998 or
****(blank)
0001–9998 or
****(blank)
0001–9998 or
****(blank)
0001–9998 or
****(blank)
0001–9998 or
****(blank)
0001–9998 or
****(blank)
0001–9998 or
****(blank)
0001–9998 or
****(blank)
0001–9998 or
****(blank)
Table D.7 System Settings (Continued)
NO.FeatureChoicesSetting
53ES Low (ESM)45-89° F (50°)
54ES High (ESM) 46-90° F (90°)
77Quiet ExitON or (OFF)
88Download
Enable
Notes:
1. 6s should not be used in any part of an access code,
since such a code interferes with bypassing sensors
from a touch-tone phone.
2. Access codes cannot be programmed as 7777, 8888,
or 9999 since these codes are reserved for fire, police,
and auxiliary panics from a touch-tone phone.
3. Each access code whether primary, secondary, armdisarm, or AVM must be unique. No two codes can be
the same.
4. 4s or 0s should not be programmed as the first digit in
an access code, since this can interfere with system
disarming.
5. The last two digits of an access code cannot be the
same.
ON or (OFF)
45
Page 50
Appendix D: System Planning Worksheets
Table D.8 Upper Sensor Numbers
No.Sensor NameDescriptionDefault Setting
77Touchpad Tamper Reports a touchpad tamper to the Central Station (CS) if 40 digits are
entered without a valid access code.
78Freeze SensorOn will activate and report a Freeze Alarm when the room temperature
reaches the programmed freeze temperature. Whe n on, an d no temperature data is received from the Energy Saver Module (ESM), a 78 TROUBLE
alarm is reported.
79No ActivityWhen on, if no activity is detected on the premises within the programmed
Activity Time-out, the au xiliary siren will sound . The panel repo rts to the CS
if the alarm is not canceled within 5 minutes.
80Touchpad Fire
Panic
81Touchpad Police
Panic
82T ouchpad A uxiliary
Panic
83Manual Phone
Test
84Opening ReportReports to the CS when the user disarms the system.OFF
85Closing ReportReports to the CS when the user arms the system.OFF
86Duress AlarmReports a silent POLICE EMERGENCY to the CS.OFF
87Force ArmedReports a FORCE ARMED when user directly or indirectly bypasses any
88Energy Saver
Enable
89Wireless Touch-
pad Supervisory
or Low Battery
90AC Po wer FailureIf on, reports an AC FAILURE to the CS if the panel has been without AC
91Low Pan el Ba ttery If on, reports LOW CPU BATTERY to t he CS if th e panel's back -up battery
92Panel TamperIf on and armed to level 2 or 3, changing from run to program will activate
93Automatic Phone
Test
94Receiver FailureIf on, the panel reports to the CS if the panel does not hear from any wire-
95Panel Back In
Service
96Phone FailureIf the panel is unsuccessful reporting to the CS after the third of eight
98Events ReportIf on (and panel is set up for ITI phone f o rmat), the pa ne l au tomatically
On enables the FIRE button on all touchpads (and telephones if F35 is on).ON
ON enables the POLICE button on all touchpads (and telephones if F35 is
on).
On enables the AUXIL IARY button on all touchpads (and telephones if F35
is on).
Allows the user to instruct the system to dial CS and report a phone test.ON
sensor. Security level and bypassed sensor are reported. (Auto Force
Armed is always reported.)
When on, the Energy Saver Module (ESM) is ab le to o verride the connected thermostat. When on and no temperature data is received from the
ESM, an 88 TROUBLE alarm is reported.
When on, the panel checks for and reports supervisory conditions on Wall
Mount Wireless touchpads. Reports a SUPERVISORY alarm to the alphanumeric touchpad if the pane l do es n 't hea r fro m ea ch touc h pa d with in the
set time (SUPSYNC). If on, the panel will report a touchpad low battery
when any touchpad has a low battery condition.
power for 15 minutes.
voltage dr ops below 11.4 VDC.
and report a CPU TAMPER alarm.
If on, the panel reports to the CS at a progr ammed interval (from daily to
every 255 days).
less transmitter for 2 hours. Trouble beeps alert user of the problem.
When on, the panel reports to the CS at power-up and if a panel reset
occurs.
attempts, the panel activ a te s a FAIL TO COMMUNICATE alarm. It continues to dial the remaining five attempts.
reports to the CS whe n 28 e v en ts are accum ulate d in the e v ent b uff er. If off,
the panel doesn’t report but still accumulates events in the bu ffer.
Note: Must be off if panel is set up for 4/2 Phone Format.
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
ON
OFF
ON
ON
ON
OFF
46
Page 51
Appendix D: System Planning Worksheets
.
Ta ble D.9 Feature Numbers
No.Feature NameDescriptionDefault Setting
F00Remote Phone Access On enables, off disables remote phone access. Works in conjunction
with feature F01 below. Off-premises accessing must be done with
primary access code.
Dialer AbortDetermines if the phone dialer aborts calls canceled by the owner
F06
Access Key TypeOn = ‚ phone key accesses the panel.
F07
Interior Siren Sounds
F11
Disable
F12Alarm Restoral Reports On = sensor/zone alarm restorals are reported to the CS.
F13Low Battery Restoral
Reports
F14Hourly Phone TestOn enables and off disables the hourly phone line voltage test.OFF
F15Alarm VerificationOn = panel reports alarm to CS only if two different sensors (in
F16Trouble Beeps Disable On = no trouble beeps and panel protests open sensors only.
F1724-Hour Sensor
Tamper Alarm
F20Audio Verification Mod-
ule (AVM) Enable
F21Immediate Trouble
Beeps
F22Touch-Tone DialingOn = DTMF(tone). Off = pulse.ON
F23Event ControlOn = only arming level and time chang es are logg e d in event buffer.
F25Keychain T ouchpad
Direct Arming
F32Keychain T ouchpad
Energy Saver/No Delay
On = call premises and l et phon e ring twice, hang-up and wait 10 seconds, call back premises and panel answers after first ring.
Off = call premises and wait for panel to answer (about 12 rings).
Off = exterior siren ac tivation is immediate.
ation. On = 8 rings, Off = 12 rings.
Off = sensor low-battery conditions are reported daily .
Determines uncorrected supervisory trouble conditions to re-report
daily (off) or weekly (on).
before panel dialing is completed.
Off = ƒ phone key accesses the panel.
On = Interior sirens sound alarms only.
Off = Interior sirens sound alarms and status.
Off = sensor/zone alarm restorals are not reported to the CS.
On = sensor battery restorals are reported to the CS.
Off = sensor battery restorals are not reported to the CS.
groups 10–20) are tripped within 4 minutes.
Off = panel reports alarms to CS without second sensor trip.
Off = trouble beeps sound for sensor low-batterty/supervisory conditions and panel protests upon arming when these conditions exist.
Must be off for UL-investigated systems.
On = sensor tamper alarms are generated in any protection level.
Off = sensor tamper alarms are generated only if the system is armed
to a level where the sensor is active.
On enables and off disables 2-way voice communication with the
Central Station during an alarm.
On = trouble beeps sound immediately when a supervisory condition
is detected. Must be on for UL-investigated systems.
Off = trouble beeps sound within 10 hours.
Off = all event buffer flagged events are logged.
On = pressing Lock b utton onc e arms system to Le vel 3- A wa y with No
Delay.
Off = pressing Lo c k b utto n onc e arms syst em to l e vel Level 2-Stay; to
Level 3-Away when pressed again.
On = * button activates No Delay feature.
Off = * button turns Energy Saver on and off.
(continued)
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
47
Page 52
Appendix D: System Planning Worksheets
Table D.9 Feature Numbers (Continued)
No.Feature NameDescriptionDefault Setting
F33Downloader Access
Enable
F35Telephone PanicsOn enables, off disables phone button panics and upper sensors 80,
F36On-Premise Telephone
Control
F37Quick ArmingOn enables, off disables touchpad quick-arming commands.ON
F40Smoke V e rific a tio nOn = if a hardwire smoke sen s or trips, the panel resets all hardwire
F41Interior Siren Verifica-
tion
F42Source ReportingOn = panel reports source of alarm (which touchpad/device) to the
F43Demo Kit ModeOn enables, off disables special demo kit mode of operati on .OFF
F44Constant Exterior Siren On = exterior siren relay output latches and remains latched for intru-
F45Keyswitch Control
(Arming/Disarming)
F46Daylight Savin gs Time On automatically adjusts the panel clock at 2:00am on the first Sun-
F474-Hour T rouble TimerOn = group 26 (fire) sensors reporting a low battery, tamper, pre-
On enables, off disables remote downloader station programming.
(Same as option 88 in User-Programming menu.)
81, and 82 are not generated from the telephone.
On enables, off disables on-premise phone control of panel.ON
smoke sensors and waits for a second trip (within 5 minutes) before
alarm is generated. An alarm is also generated if the panel doesn’t
receive a re storal after the fi rst trip.
Off = panel only req uires one trip .
On = panel monitors interior siren wiring for shorts/opens.OFF
central station when S77 and S80-87 reports are sent.
sion alarms, for siren timeout duration or until alarm is canceled.
OFF = exterior siren relay output modulates between open and
closed states for normal intrusion alarm output.
On = allows zone 1 to arm and disarm the system, using a keyswitch
or dry relay contact output of an access system connected to a panel
hardwire input, HIM, or door/window sensor terminals.
Off = no keyswitch arming/disarming
day in April for daylight-savings time and the last Sunday in October
for standard time. These changes are logged in the event buffer.
alarm, or trouble condition cause the system to sound trouble beeps.
Pressing STATUS or changing arming level stops trouble beeps for 4
hours. Trouble beeps sound again in 4 hou rs if problem is no t fixed.
Must be on for UL Listed installations.
Off = group 26 sensors initia te trouble beeps imme diately or within
10-hours (a s per F21 setting).
OFF
OFF
OFF
ON
OFF
OFF
ON
ON
48
Page 53
Table D.10 Central Station Programming
FeatureChoicesDefaultSetting
ACCOUNT##-###. Num bers or Letters00-0 00
AVBEEPDLY
(Audio Verification Beep Delay)
PHONE2
(Secondary
phone number)
PMODE (Phone
Dialer Mode)
PTFREQ (Automatic Phone Test
Frequency)*
STIME (Supervi-
sory Time)
SUPSYNC
(Supervisory
Synchronization)
XTENDELAY2 - OFF or ONOFF
(X-10 Module 3 - OFF or ONOFF
Delay)4 - OFF or ONOFF
TRIPTIME (HOM
Momentary
Response Trip
Time)
0–300 seconds in 2-second
increments.
Up to 14 digits, including *,#,
and D.
0 (ITI and 4/2 formats) - All
reports to phone 1. Phone 2 not
used.
1 (ITI and 4/2 formats) - All
reports to phone 1. Phone 2
used if other attempts fail.
3 (ITI format only) - All alarms,
opening, and closing reports to
phone 1. All reports to phone 2.
5 (ITI and 4/2 formats) - All
alarms, opening, and closing
reports to phone 1 using 4/2 format. All reports to phone 2 using
ITI format.
1–255 days in cycle, 1–255 days
remaining.
00–23 hours:00–59 minutes12 hours
02–24 hours12 hours
5 - OFF or ONOFF
6 - OFF or ONOFF
7 - OFF or ONOFF
8 - OFF or ONOFF
9 - OFF or ONOFF
01–12 seconds04
002
seconds
(none)
0
7,7 days
after any
powerup.
seconds
* This feature only functions if upper sensor 93 is on.
Appendix D: System Planning Worksheets
49
Page 54
Appendix E: Panel Connections and Wiring
Appendix E: Panel Connections and Wiring
This appendix contains a description of the control panel terminal connections, wire recommendations, and a
typical system wiring diagram (figure E.1, last page of document). Refer to appendix F for UL requirements.
Table E.1 Panel Terminal Strip 1 Connections
TerminalNameWhat It’s Used for
116.5 VAC16.5 VAC power transformer connection (or negative [-] DC connection if operating
from an external DC source or battery).
Warning
Never connect both AC power transformer and an external DC source at the same
time. Permanant damage to transformer, DC source, and panel could result.
216.5 VAC16.5 VAC power transformer connection (or positive [+] DC connection if operating
from external DC source or battery). See above warning.
3+ DC
(SIREN)
4GNDCommon ground connection for hardwire and other devices
5SIREN COMCommon (C) side of external siren dry relay N/C and N/O contacts (terminals 6 and 7)
6SIREN N/CNormally closed (N/C) (opens on alarm) external siren dry relay contact connection
7SIREN N/ONormally open (N/O) (closes on alarm) external siren dry relay contact connection
8VOICE
SIREN
9VOICE
SIREN
10TP VOICEReserved for future use.
11TP VOICEReserved for future use.
12+12V DC
OUT
13BUS ASuperbus communication connection
Hardwire device DC power supply. Unregulated 12-24 VDC@ 0.75 amp maximum.
Fused (F1).
Note
For 24 VDC sirens and bells only.
One side of speaker and Interrogator 200 AVM talk-back speaker connection
Warning
The maximum number of speakers connected to terminals 8 and 9 is two. Connect
multiple speakers in series only. Connecting m ore than two speakers or connecting
multiple speakers in parall el could result in permanan t dama g e to the panel.
Other side of spea ker and Interr og ator 200 AVM talk-back speaker co nnection
Superbus, Fail-to-Communicate, Interrogator 200 AVM and exterior siren DC power
supply. Regulated 12 VDC@ 0.75 amp maximum. Fused (F2).
14BUS BSuperbus communication connection
15GNDSuperbus, AVM, FTC, etc, common ground connection
16FTCO ne side of Failure-to-Communicate (FTC) device connection. 12 VDC@100 mA
maximum. Other side to DC OUT terminal 12. (Other side to GND terminal 4 if wired to
external contact of a wireless door/window sensor.)
17+ INT SIRENPositive (+) side of interior siren connection. 12 VDC@100 mA maximum. Other side
to - INT SIREN terminal 18. Connect multiple piez o s in parallel. A 1N4001 di ode (in
series) is required at each piezo location. A 4.7K ohm EOL resistor (i n para lle l) i s reqiuired at the peiz o or at th e la st p eiz o in a cha in (s ee wi ring d iag ra m). Th is t erminal normally measures zero volts (to GND).
18- INT SIRENNegati v e (-) side o f interior si ren co nnect ion. 12 VDC@100 m A maxim um. Othe r side
to + INT SIREN terminal 17. This terminal normally measures +12 volts (to GND)
when siren is off. This is the normal monitoring (supervision) voltage.
19GNDInterrogator 200 AVM microphone (listen-in) common ground connection
20AVM MICInterrogator 200 AVM microphone (listen-in) connection
WARNING!
The maximum numbe r of micro phone s to be connec ted to te rminals 19 and 20 is two .
Connect multiple microphones in parallel.
Table E.2 Panel Terminal Strip 2 Connections
TerminalNameWhat It’s Used For
21+12V DC
SW
22GNDCommon ground for hardwire zones 1 and 2, Smoke, and Rate-of-Rise Heat sensors
23ZONE 1Hardwire zone 1
24ZONE 2Hardwire zone 2
25GNDCommon ground for zones 3 and 4
26ZONE 3Hardwire zone 3
27ZONE 4Hardwire zone 4
28GNDCommon ground for zones 5 and 6
28ZONE 5Hardwire zone 5
30ZONE 6Hardwire zone 6
Smoke and Rate-of-Rise Heat sensor power supply. Switched 12 VDC @100 mA
maximum.
51
Page 56
Appendix E: Panel Connections and Wiring
Table E.3 Wire Recommendations
Device
AC Power Transformer18Stranded25–
Earth Ground14Solid or stranded25–
Superbus Devices (Touchpads,
ESM, HIM, etc.)
Hardwire Zones and De v ic es22Stra nd ed(See resis-
Sirens, Piezos, and Speakers18Stranded500–
Interrogator 200 AVM Micro-
phone*
Tel ephone22Phone grade solid or
* Run Interrogat or 200 AVM speaker and microphone wires in separat e cab les to prevent cross talk. Some applica tions ma y
require shielded cable for long or electrically noisy microphone wire runs.
Minimum
Gauge
22
18
22Stranded/shielded500–
Type
Stranded
Stranded
stranded
Maximum
Length (feet)
500
1,000
tance)
––
Maximum
Resistance
–
50 ohms per zone
(including devic e resis-
tance)
52
Page 57
Appendix F: UL Requirements
Appendix F: UL Requirements
This appendix contains a description of the requirements for UL-listed systems and a UL-listed system wiring
diagram. This section describes the minimum system configurations for UL-listed Grade A (supervised) systems. Also refer to the other appendices for proper programming and other compatible sensors.
Basic System
All UL-listed systems require the following basic components. The basic system does not require sensors and
can use the Handheld Wireless Touchpad (60-348) as a signaling device.
•Control Panel (60-650)
•Superbus Alphanumeric Touchpad (60-586)
•Class II Line Carrier Power Transformer (60-678)
•Heavy Duty 6.5AH Backup Battery (60-680)
•Wireless Interior Siren and Piezo (WIS) (60-353-235), Hardwire Exterior Siren and Piezo (13-046), or
Slim Line Hardwire Interior Siren (60-483-01)
Household Fire Warning System (UL 985)
Basic system as described above plus:
•Wireless Smoke Sensor (60-506), Wireless Smoke Sensor (60-645-95), or Hardwire Smoke/Heat Detector
(13-360) (ESL 449AT) with Power Supervision Module (60-391). This shall be programmed as Sensor
Group 26.
•When utilizing a hardwire zone for fire alarm (Group 26), the panel shall not be connected to earth ground.
•Option F21 (Immediate Trouble Beeps) set to ON
•Option F47 (4-Hour Trouble Timer) set to ON
•SUPSYNC (Supervisory Synchronization) set to 2 (hours)
Note
SUPSYNC can not be programmed from the panel. Refer to the “Requestin g CS-4000/Do wnloader Programming” section
for more informatio n.
For 24-hour backup, external power drain is limited to 150 mA continuous using the heavy duty 6.5AH battery.
53
Page 58
Appendix F: UL Requirements
The smoke detector insta ll at io n sh all ad he re to t he followi ng:
A smoke detector should
Bedroom
Bedroom
Hall
be located on each level.
Living
Room
Basement
Dining
Room
TV
Room
Bedroom
NOTE: Ceiling-mounted smoke detectors should be located in the center of the room
or hall, or not less than 4 inches from the wall. When the detector is mounted
on the wall, the top of the detector should be 4 to 12 inches from the ceiling.
NOTE: Do not install smoke detectors where normal ambient temperatures are above
100°F or below 40°F. Also, do not locate detectors in front of AC/ Heat
registers or other locations where normal air circulation will keep smoke
from entering the detector.
Kitchen
H
Living
Room
Dining
Room
Dining
Room
Living
Room
Bedroom
Kitchen
H
Hall
Bedroom
Bedroom
Bedroom
Living
Room
Basement
Bedroom
In family living units with more
than one sleeping area, locate a
smoke detector at each area.
Smoke detectors should
be located between the
sleeping area and the rest
of the family living unit.
Bedroom
x
Recreation
Room
Bedroom
Hall
NOTE: Additional information on household fire warning is available at nominal
cost from: The National Fire Protection Association, Batterymarch Park,
Quincy, MA 02269. Request Standard No. NFPA74.
Required smoke detector
H
Heat detector
x
Indicates smoke detector is optional if door is not provided between
basement and recreation rooms.
Household Burglar Alarm System (UL 1023)
Basic system as described above plus:
•Learn Mode Door/Window Sensors (60-362)
54
Page 59
Appendix F: UL Requirements
Home Health Care Signaling Equipment
(UL 1637)
Basic system as described above plus:
•Water-Resistant Panic Sensor (60-578-10-95)
The following wireless sensors and hardwire devices may be used in a UL-listed system:
Part No.Description
Wireless Sensors
60-362Learn Mode Door/Window Sensor
60-409Learn Mode Recessed Door/Windo w Se ns o r
60-499Learn Mode Slim Line Door/Window Sensor
60-506Learn Mode System Smoke Sensor
60-460Rate-of-Rise Heat Sensor
60-452Learn Mode Pendant Panic Sensor
60-458Single Button Panic Sensor
60-457Dual Button Panic Sensor
60-578Water-Resistant Panic Sensor
60-348Handheld Wireless Touchpad
60-453Wall-Mount Wireless Touchpad
60-511Learn ModeDS924i PIR Motion Sensor
60-592DS926 PIR Ceiling Mount Motion Sensor
60-582Learn Mode Sound Sensor (IntelliSense)
1.A maximum of two Audio Verification Modules are allowed. Wire multiple speakers in series and the remaining
Table E.4 System Wiring Notes
(power and microphone) wires in parallel. Use shielded cables to prevent cross talk between the speaker and
microphone.
2.W ire multiple piezo locations in parallel (daisy chain). Mount the required diode at each piezo loca ti on as
shown with the cathode (band marking) towards the piezo device terminal. Mount a single EOL resistor at the
last piezo in the chain.
3.A maximu m of two speakers are allowed. Wire multi pl e sp eaker s in seri es only. Wiring more than two speakers or multiple speakers in parallel can result in permanent damage to the panel.
4.Jumper terminals 4 to 5 to supply GND to exterior SIREN COM terminal. To avoid bothering neighbors unnecessarily during initial system testi ng , leave exterior siren(s) disconne cted at the panel un til you are ready to
test them.
5.Both line carrier (60-678) and nonline carrier (60-679) AC power transformer types are wired the same. Do not
plug transformer into any AC receptacle controlled by a switch. AC power must not be interrupted. Do not
short the transformer outputs together. The transformer contains an internal fuse that will permanently disable
the output if shorted.
6.Co n ne ct the r ight-bottom panel board mounti ng s crew to electr ical ground (if the installation site has a tr ue
electrical ground). Cold water pipe groundin g can be used if it is an uninter rupted metal pipe.
7.Only high-volume Slim-Line siren sounds are used. Internal jumpers and switches have no effect.
8.All SuperBus devices such as Energy Saver, Hardwire Input and Output Modules, and Alphanumeric Touchpads must have unique unit number (address) settings. Devices with the same (conflicting) address will not
function properly. Default settings are ok for one module and one touchpad. Refer to instructions text for setting unit numbers (addresses).
9.Refer to the Installation Instructions shipped with the Energy Saver Module for thermostat wiring details.
10.If more than one alphanumeric touchpad is required, wire all touchpad harnesses in parallel, but only connect
one touchpad until programming is complete and tested. Additional touchpads require their touchpad unit
numbers to be changed from the factory default. Refer to touchpad installation instructions text.
11.The touchpad hardwire loop is supplementary and is not intended for use as a primary initiating circuit
because the loop is not end-of-line supervised.
12.Wire Hardwire Input Module hardwire zones as shown for the panel. Mount a single EOL resistor as shown at
the last device in the chain.
13.Zone (loop) terminal shown is an example. Any zone (loop) terminal may be used. Install EOL resistors across
all unused zone (loop) inputs and GND (common on Hardwire Input Module).
14.Power Supervision Module is required for supervised (UL-investigated) applications. Wire multiple or supervised hardwire smoke/heat detectors only as shown.
15.For nonsupervised applications, replace the power supervision module with singl e EOL resistor acro s s ter m inals 3 and 4 of the last detector in the chain.
16.Some telephones are polarity-sensitive. Green and red wires may need to be reversed.
17.P ho ne jack tampering is optional. If used, assignment to sensor group 8 (specia l int r usion) is recommended.
PHONE
CONNECTIONS
ZONE3ZONE
GND
4.7k Ohm
EOL RESISTOR
49-365
26
NOTE 13:
NORMALLY
CLOSED
(N/C)
CONTACTS
IN SERIES
GND
4
272829
ZONE5ZONE
NOTE 13:
NORMALLY
OPEN
(N/O)
CONTACTS
IN PARALLEL
4.7k Ohm
EOL RESISTOR
49-365
6
30
BLACK
BLACK
GREEN
DUAL DB-8
PHONE CORD
49-426
NOTE 16: RJ-31X
(CA-38A)
PHONE JACK
BRN
GRN
GREEN(C)
TELCO
PROTECTOR
BLOCK
(A)
GRN RED
GRY
RED
(B)
RED(D)
DUAL DB-8
PHONE CORD 49-425
TO PANEL
NOTE 17: TAMPERING THE
RJ-31X (CA-38A)
PHONE JACK (OPTIONAL)
4.7k Ohm
EOL RESISTOR
49-365
WHITE OR YELLOW
RED
SPLICE
WIRE
WHITE OR YELLOW
TO
PREMISES
PHONES
6, BLU
7, YEL
TO PANEL HARDWIRE
3, ORG
2, BLK
ZONE TERMINALS.
8557139C.DS4
Page 64
Figure F.1 UL-Listed System Wiring
NOTE 4: STANDARD
TRANSFORMER
NOTE 4: LINE CARRIER
TRANSFORMER
NOTE 5:
16.5 VAC 50 VA
LOWER
RIGHT
CHASSIS
SCREW
EARTH
GROUND
16.5
VAC
TERMINAL
STRIP 1
N/C – INDICATES NO CONNECTION
SHALL BE MADE.
NOTE 1: HARDWIRE INTERIOR SIREN, 60-278
RED
BLACK
17
NOTES 1 & 2: SPEAKER/PIEZO
60-252
BLACK
RED
60-679
OR
60-678
LINE
CLASS 2
LOAD
12
16.5
+DC
VAC
(SIREN)
BLACK
NOTE 3: HARDWIRE
EXTERIOR SIREN
ITI PART NO. 07-001 DIODE
(LOCATE AT PIEZO)
18
17
NOTE 3
SIREN
GND
COM
345
N/CN/C N/CN/CN/CN/C
13-046
SIREN
SIREN
RED
N/C
67
VOICE
VOICE
N/O
SIREN
SIREN
89
ITI PART NO. 49-365
(LOCATE AT PIEZO)
THERMOSTAT
TO FURNACE
NOTE 16
TP
VOICETPVOICE
10
4.7k Ohm
EOL RESISTOR
1
+12V
DC OUT
11
12131415
NOTE 10:
HARDWIRE
LOOP INPUT
NOTE 7 & 8: SUPERBUS
ENERGY SAVER MODULE
60-620
2 3 4 5
BUS
BUS
BFTC
GND
A
YELLOW
6
16
BLACK
WHITE
GREEN
RED
NOT USED
WIRING
HARNESS
49-283
NOTES 7 & 9: SUPERBUS
ALPHANUMERIC TOUCHPAD
NOTES 7,11,12 & 13: SUPERBUS
BLACK
RED
ITI PART NO. 07-001 DIODE
(LOCATE AT SIREN)
4.7k Ohm
EOL RESISTOR
ITI PART NO. 49-365
(LOCATE AT SIREN)
18
-INT
+INT
SIREN
SIREN
17181920
TAB SLOT (4)
60-586
HARDWIRE INPUT MODULE
(HIM) 60-584
COMMON
LOOP 2
LOOP 3
COMMON
67
LOOP 4
LOOP 5
9
8
COMMON
LOOP 6
12345
LOOP 1
NOTES 1 & 6: SLIM LINE HARDWIRE
INTERIOR SIREN AND PIEZO, 60-483-01
17
NOTE 12: LISTED PIR MOTION SENSOR
4.7k Ohm
EOL RESISTOR
ITI PART NO. 49-365
(LOCATE AT SENSOR)
AVM
MIC
GND
10
LOOP 7
11 12
COMMON
LOOP 8
TERMINAL
STRIP 2
14 15
13
16
18
-
+
NOTE 17
+12V
DC SW
21
1234
1234
LP
LN
ZONE
GND
NOTES 12 & 13:
LISTED HARDWIRE
SMOKE/HEAT
DETECTOR SUCH
AS ESL 449AT
USE IN AND OUT
WIRING METHODS ONLY
NOTES 13: POWER SUPERVISON
ZONE
1
22232425
(DAISY-CHAIN)
RED
BLACK
GREEN
WHITE
(INSTALL AT LAST DEVICE)
2
MODULE
ITI PART NO. 60-391
1.Wir e multiple piezo locations in parallel (dais y chai n). Mou nt th e re qu ire d diod e at ea ch pie zo locati on as
Table F.1 UL-Listed System Wiring Notes
shown with the cathode (band marking) towards the piezo device terminal. Mount a single EOL resistor at the
last piezo in the chain.
2.A maximum of two speakers are allowed. Wire multiple speakers in series only. Wiring more than two speakers
or multiple speakers in parallel can result in permanent damage to the panel.
3.Jumper ter m in als 4 to 5 to supply GND to exterior SIREN COM ter m in al. To avoid bothering neighbors unnecessarily during initial system testing, leave exterior siren(s) disconnected at the panel until you are ready to test
them.
4.Both line carrier (60-678) and nonline carrier (60-679) AC power transformer types are wired the same. Do not
plug transformer into any AC receptacle controlled by a switch. AC power must not be interrupted. Do not short
the transformer outputs together. The transformer contains an internal fuse that will permanently disable the
output if shorted.
5.Con ne ct the r ig ht-bottom panel board mounting screw to electr ical ground (if the inst al la tion site has a true
electrical ground). Cold water pipe groundin g can be used if it is an uninte rrupted metal pipe.
6.Only hig h-volume Slim -L in e siren sounds are used. Internal jumper s and switches have no effect.
7.All superbus devices such as Energy Saver and Hardwire Input Modules and Alphanumeric Touchpads must
have unique unit number (address) settings. Devices with the same (conflicting) address will not function properly. Default settings are ok for one module and one touchpad. Refer to instructions text for setting unit numbers
(addresses).
8.Refer to Installation Instructions shipped with the Energy Saver Module for thermostat wiring details.
9.If mo re tha n on e alph anu me r ic tou ch pa d is requ ire d, wire all touchpad harnesses in parallel , but only conn e ct
one touchpad until programming is complete and tested. Additional touchpads require their touchpad unit numbers to be changed from the factory default. Refer to touchpad installation instructions text.
10.The touchpad hardwire loop is supplementary and is not intended for use as a primary initiating circuit because
the loop is not end-of-line supervised. Refer to touchpad installation instructions text for further restrictions.
11.Wir e Hard wire Input Module hardwire zones as shown for the panel. Mount a single EOL resistor as shown at
the last device in the chain.
12.Zone (loop) terminal shown is an example. Any zone (loop) terminal may be used. Install EOL resistors across
all unused zone (loop) inputs and GND (common on Hardwire Input Module).
13.Power Supervision Modu le is requir ed . Wire multip le or supervised hardwire smoke/heat detectors only as
shown.
14.Som e teleph on es are po larity-sensitive. Green and red wires may need to be reversed.
15.Pho ne ja ck tamper ing is option al . If used, assignm e nt to se nso r group 8 (special in tr usion) is recommended.
16.Terminal 12 (+12VDC OUT) is rated 10.4 to 12VDC; refer to installation instructions for maximum current ratings.
17.Terminal 17 (+12VDC SW) is rated 9.9 to 12VDC: refer to installation instructions for maximum current ratings.
PHONE
CONNECTIONS
ZONE3ZONE
GND
26
4.7k Ohm
EOL RESISTOR
ITI PART NO. 49-365
NOTE 12:
NORMALLY
CLOSED
(N/C)
CONTACTS
IN SERIES
GND
4
272829
ZONE5ZONE
6
30
NOTE 12:
NORMALLY OPEN
(N/O) CONTACTS
IN PARALLEL
4.7k Ohm
EOL RESISTOR
ITI PART
NO. 49-365
BLACK
BLACK
GREEN
DUAL DB-8
PHONE CORD
49-426
NOTE 16: RJ-31X
(CA-38A)
PHONE JACK
BRN
GRN
GREEN(C)
TELCO
PROTECTOR
BLOCK
(A)
(B)
GRN RED
GRY
RED
RED(D)
DUAL DB-8
PHONE CORD 49-425
TO PANEL
NOTE 15: TAMPERING THE
RJ-31X (CA-38A)
PHONE JACK (OPTIONAL)
4.7k Ohm
EOL RESISTOR
49-365
WHITE OR YELLOW
RED
SPLICE
WIRE
WHITE OR YELLOW
TO
PREMISES
PHONES
6, BLU
7, YEL
TO PANEL HARDWIRE
ZONE TERMINALS.
8557150B.DS4
3, ORG
2, BLK
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.