ITI UltraGard Installation Instructions Manual

Page 1
Installation Instructions
This document describes the basic procedures necessary for an experienced installer to install, set up, and program an UltraGard
[Check with your central station to verify they have
updated their CS-4000 with version 6.0 or later soft­ware, for full UltraGard support.]
Security System.
Contents
UltraGard
and Custom Versions
Special Installation Requirements 1
Requirements for UL-Listed Installations 1 Canada Listings 1 California State Fire Marshall Listing 1
Installing the System 1
Determining the Panel Location 2 Running Wires to the Panel Location 2 Mounting the Panel 2 Installing the Panel Antennas 3 Wiring the Panel 3 Setting the Optional Energy Saver Module (ESM), Hardwire Input Module (HIM) and Hard­wire Output Module (HOM) Unit Number DIP Switches 4 Installing the Backup Battery 4 Powering Up the Panel 5 Adjusting Status Sound Volume 5
Programming the Panel 6
Clearing Memory 7 Entering and Exiting Program Mode 7 Deleting Sensor Text 8 Programming Sensor Text 8 Adding (Learning) Wireless Sensors 9 Adding (Learning) Hardwire Sensors 10 Deleting Sensors and Hardwire Zones 10 Programming Upper Sensors 11
Programming Optional Feature Numbers 11 Adding (Learning) Wireless Touchpads 11 Programming Panel Configuration Options 12 Programming the Primary Phone Number 12 Programming the Phone Format 12 Programming the Siren Time-out 13 Programming the Install Code 13 Programming the Account Number 13 Programming the Entry Delay 14 Programming the Extended Delay 14 Programming the Exit Delay 14 Programming the Activity Time-out 14 Programming the House Code 15 Programming the Energy Saver Module Freeze and Set Temperatures 15 Programming the Touchpad Options 15
Programming the Touchpad Unit Number 16 Programming the Touchpad Quiet 16 Programming Touchpad Key Beeps 17
Programming the Interrogator 200 Audio Verifi­cation Module Mode, Time-out, and Access Code 17 Programming HOM Points 18 Programming the Time Zone 18
Document Number: 466-1034-01-ITI Rev. F April 1997
Page 2
Contents
Viewing or Programming the User-Programma­ble System Settings 18 The Duress Code 19 Adjusting the Alphanumeric Touchpad Display Brightness 20 Requesting CS-4000/Downloader Program­ming 20
Installing Line Carrier Devices 21
Installing and Programming the Wireless Interior Siren (WIS) 21
Setting the WIS DIP Switches and Installing the Battery 21 Connecting an External Siren to the WIS 22 Programming the WIS House Code 22
Installing X-10 Lamp Modules 22
Testing the System 23
Testing Sensors 23
If a Sensor Fails the Sensor Test 24
Testing the Energy Saver Module (ESM) 24 Testing the Hardwire Input Module (HIM) 25 Testing the Hardwire Output Module (HOM) 25 Testing the X-10 Lamp Modules 25 Testing Phone Communication 26 Testing Central Station Communication 26 Displaying the Panel Version Code 26
Appendix A: Command Summary 27
User Operating Command Summary 27 System Settings (User-Programming) Command Summary 28
Appendix B: Troubleshooting 29 Appendix C: Programming Tables 37 Appendix D: System Planning Worksheets 42 Appendix E: Panel Connections and Wiring 50 Appendix F: UL Requirements 53
Page 3
Notices
This manual may refer to products that are announced but are not yet available.
FCC Notices
This equipment has been tested and found to comply with the limits for a class B digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment gen erates, uses, and can radiate radio frequency energy an d, if not installed an d used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is en­couraged to try to correct the interference by one or more of the following measures:
Install a quality radio or television outdoor antenna if the indoor antenna is not adequate.
Reorient or relocate the panel.
Move the panel away from the affected equipment.
Move the panel away from any wire runs to the affected equipment.
Connect the affected equipment and the panel to separate outlets, on different branch circuits.
Consult the dealer or an experienced radio/TV technician for help.
Send for the FCC booklet How to Identify and Resolve Radio-TV Interference Problems, available from the U.S. Government Printing Office, Washington, D.C.
20402. Stock Number: 004-000-00345-4.
This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
This equipment complies with part 68 of the FCC rules. On the FCC label affixed to this eq uip ment is the FCC Registration Number and Ringer Equivalence Number (REN) for this equipment. If requested, provide this information to your telephone company.
The REN is used to calculate the maximum number of devices your telephone line will support with ringing service. In most areas the sum of all device RENs should not exceed 5.0. Contact your local telephone company to determine the maximum REN for your calling area.
If your telephone equipment causes harm to the telephone network, your telephone company may temporarily disconnect your service. If possible, you will be notified in advance. When advance notice is not practical, you will be notified as soon as possible. You will also be advised of your right to file a complaint with the FCC.
Your telephone company may make changes in its facilities, equipment, operations, or procedures that cou ld affect the prop er operation of your equ ipment. You will be giv en advanced notice in order to maintain uninterrupted service.
If you experience trouble with this equipment, please contact
Interactive Technologies, Inc. 2266 Second Street North North Saint Paul, MN 55109 1-800-777-1415
for service and repair information. The telephone company may ask you to disconnect this equipment from the network until the problem has been corrected or until you are sure that the equipment is not malfunctioning.
This equipment may not be used on coin service provided by the telephone company. Connection to party lines is subject to state tariffs.
Canada Notice
The Canadian Department of Communications label identifies certified equipment. This certification means that the equipment meets certain telecommunications network pro­tective, operational, and safety requirements. The department does not guarantee the equipment will operate to the user’s satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications comp any. The eq uip men t must also be installed using an acceptable method of connection. In some cases, the company’s in side wiring associated with a sin gle-line individual service may be extended by means of a certified connector assembly (telephone extension cord). The customer sh ould be aware that co mpliance with the above con ditio ns may not prev ent degradation o f service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment.
For your protection, make sure that the electrical ground connections of the power utility, telephone lines, and internal metallic water pipe system, if present, are connected together.
Caution
Do not attempt to make connections yourself. Contact the appropriate electrician or electric inspections authority.
The Load Number (LN) assigned to each terminal device denotes the percentage of the total load to be connected to a telephone loop that is used by the device to prevent overloading. The termination on a loop may consist of any combination of devices subject only to the requirement that the total of the LNs of all the devices does not exceed
100. Load Number: 0.4B
Page 4
“AVIS: - L ´étiquette du ministère des Communications du Canada identifie le matériel homologué. Cette étiquette certifie que le matériel est conforme a certaines normes de protection, d ´ exploitation et de sécurité des réseaux de téléco mmunications. Le ministère n ´ ass ure toutefois pas que le matériel fon ctionnera a la s atisfaction de l ´ utilisateu r.
Avant d ´ installer ce matériel, l ´ utilisateur doit s ´ assurer qu´ il est permis de le raccorder aux installations de l ´ enterprise locale de télécommunication. Le matériel doit également etre installé en suivant une méthod acceptée de raccordement. Dans certains cas, les fils intérieurs de l´ enterprise utilisés pour un service individuel a ligne unique peuvent etre prolongés au moyen d´ un dispositif homologué de raccordement (cordon prolongateur téléphonique interne). L ´ abonné ne doit pas oublier qu ´ il est possible que la conformité aux conditions énoncées ci-dessus n ´ empechent pas le d égradation du service dans certaines situation s. Actuellement, les enterprises de télécommunication ne permettent pas que l ´ on raccorde leur matériel a des jacks d ´ abonné, sauf dans les cas précis prévus pas les tarrifs particuliers de ces enterprises.
Les réparations de matériel homologué doivent etre effectuées pas un centre d ´ entretien canadien autorisé désigné par le fournisseur. La compagne de télécommunications peut demander a l ´ utilisateur de débrancher un appareil a la suite de réparations ou de modifications effectuées par l ´ utilisateur ou a cause de mauvais fonctionnement.
Pour sa propre protection, l ´ utilisateur doit s ´ assurer que tous les fils de mise a la terre de la source d ´ énergie électrique, des lignes téléphoniques et des canalisations d ´´ eau métalliques, s ´ il y en a, sont raccordés ensemble. Cette précaution est particulièrement importante dans les régions rurales.
Avertissment. - L ´ utilisateur ne doit pas tenter de faire ces raccordements lui-meme; il doit avoir recours a un service d ´ inspection des installations électriques, ou a electricien, selon le cas”.
Une note explicative sur les indices de charge (voir 1.6) et leur emploi, a l ´ intention des utilisateurs du matériel terminal , doit etre incluse dans l ´ information qui accompagn e le materiel homologué. La note pourrait etre rédigée selon le modèle suivant:
“L ´ indice de charge (IC) assigné a chaque dispositif terminal indique, pour éviter toute surcharge, le pourcentage de la charge totale qui peut etre raccordée a un circuit télé­phonique bouclé utilisé par ce dispositif. La terminaison du circuit bouclé peut etre constituée de n ´ import somme des indices de charge de l ´ ensemble des dispositifs ne dépasse pas 100.”
L ´ Indice de charge de cet produit est ____________.
Trademarks
ITI is a registered trademark of Interactive Technologies, Inc. UltraGard is a trademark of Interactive Technologies, Inc. X-10 is a registered trademark of X-10 (USA), Inc.
Page 5
Special Installation
tion for more information.
Requirements
This security system can be used as a fire warning system, an intrusion alarm system, an emergency no­tification system, or any combination of the three.
Some installations may require certain configurations dictated by city codes, state codes, or insurance re­quirements. The following information indicates the components of various listings.

Requirements for UL-Listed Installations

If the system is to comply with UL household require­ments, there are specific guidelines you must follow. Refer to appendix F for a list of compatible accesso­ries, programming and wiring requirements in UL­listed systems.

Canada Listings

For 24-hour backup, external power drain is limited to 150 mA continuous using the heavy duty 6.5AH battery.
Residential Burglary Alarm System Unit (ULC-S309)
Basic system as described in appendix F for UL-listed installations plus:
Learn Mode Door/Window Sensors (60-362)

California State Fire Marshall Listing

The California State Fire Marshall listing is pending.

Installing the System

This section describes how to install the system con­trol panel. Plan your system layout using the work­sheets provided in appendix D before starting the installation.
Installing the system consists of the following:
The ULC (UL Canada) listing is pending.
CSA Certified Accessories Residential Fire Warning System Control Unit
(ULC-S545-M89)
Basic system as described in appendix F for UL-listed systems plus:
Wireless Smoke Sensor (60-506), Wireless Smoke Sensor (60-645-95), or Hardwire Smoke Detector (13-360) (ESL 449AT) with Power Supervision Module (60-391)
Option F21 (Immediate Trouble Beeps) set ON
SUPSYNC (Supervisory Synchronization) set to 2 (hours)
Note
SUPSYNC cannot be programmed from the panel. Refer to the “Requesting CS-4000/Downloader Programming” sec-
Determining the Panel Location
Running Wires to the Panel Location
Mounting the panel
Installing the panel antennas
Wiring the panel
Setting the optional Energy Saver and Hardwire Input Module unit number dip switches
Installing the backup battery
Powering up the panel
Adjusting status sound volume
1
Page 6
Installing the System

Determining the Panel Location

Before permanently mounting the panel, determine panel location using the following guidelines:
Centrally locate the panel with relation to wire­less sensor locations, whenever possible.
Avoid locations with excessive metal such as HVAC ducts, foil wallpaper, gas/water pipes, and electrical wiring.
Mount the panel at a comfortable working height (about 45 to 55 inches from the floor to the bot­tom of the panel, as shown in figure 1).
Allow a minimum of 10.5 inches above the panel for the antennas, as shown in figure 1.
Allow 6.5 inches to the right or left of the panel for wiring, phone jack, and optional module mounting.
Allow at least 24 inches in front of the panel for access to panel components.
PHONE JACK AND
OPTIONAL MODULE
MOUNTING AREA
21"
ANTENNA
AREA
14.5"

Running Wires to the Panel Location

Once you have determined the ideal panel location, run any necessary wires to that location, including:
Power transformer
Phone line
Sirens/speakers
SuperBus* Alphanumeric Touchpads
Hardwire zones
Optional SuperBus* modul es (suc h as Energy Saver Module [ESM], Hardwire Input Module [HIM], Hardwire Output Module [HOM], etc.)
* SuperBus is an improved technology bus configura­tion and is not compatible with older bus modules.
Refer to table E.3 in appendix E for wire size and type recommendations. If you are using the same cable type for several wire runs, use labels to mark the wires at the panel location to help identify these wires .

Mounting the Panel

PANEL
ACCESS FOR
PANEL COVER
45-55"
FLOOR
Figure 1 Determining Panel Location
SCREWS
NOTE ALLOW AT LEAST 24" IN FRONT OF PANEL FOR ACCESS TO PANEL COMPONENTS
14.5"
8"
25"
8557G04A.DS4
Use the procedure below to mount the panel to the wall or wall studs, using the supplied mounting hard­ware and the panel mounting holes shown in figure 2.
Caution
Make sure you are free of static electricity whenever you work on the panel with the cove r re moved. To discharge any static, first to uch the metal pa nel chassis , and then stay in contact with the chas sis when touc hing t he c ircu it boa rd.
An approved grounding strap is recommended.
To mount the panel:
1. Unlock the panel cover (if cover has a key lock installed) or remove the panel cover retaining screws at the bottom of the panel and remove the panel cover.
2. Swing the panel cover out and up to remove it from the enclosure.
3. Remove the necessary wiring knockouts. Be careful not to damage the circuit board.
4. Place the enclosure in position against the wall.
2
Page 7
Make sure enclosure is level and mark the loca­tions of the two mounting holes and two keyhole mounting holes. Remember to leave room for the panel antennas, which extend 9 inches above the top of the enclosure.
5. Use the appropriate anchors and screws. Partially insert screws into the two anchors at the two top keyhole locations, and then hang the panel chas­sis on the two screws.
6. Recheck for level, insert the two lower screws, and then tighten all four mounting screws.
KEYHOLE
MOUNTING
HOLES
ANTENNAS
COVER
LIP
Installing the System
ANTENNAS
ANTENNA
GROUNDING
SCREW
Figure 3 Installing the Panel Antennas
Caution
Do not overtighte n the te rmina l block screws ; if yo u do, p er­manent damage may result.
ENCLOSURE
ANTENNA
TERMINAL
STRIPS
PANEL CIRCUIT BOARD
ANTENNA
GROUNDING
SCREW
8557G49A.DS4
CONTROL
PANEL
CIRCUIT
BOARD
BACKUP
BATTERY
COVER
SCREWS
WIRING
KNOCKOUTS
CONTROL
PANEL
ENCLOSURE
EARTH GROUND
CHASSIS SCREW
MOUNTING
HOLES
8557G08A.DS4
Figure 2 Mounting the Panel

Installing the Panel Antennas

Wiring the Panel

Refer to appendix E for panel terminal descriptions, wire recommendations, and typical system wiring di­agram.
Refer to appendix F for panel programming and typi­cal system wiring diagram for UL-listed installations.
Refer to appendix D, table D.2 to calculate the hard­wire device power consumption for the system.
For more detailed information on installing hardwire devices, refer to the installation instructions that ac­company each device.
Caution
You must be free of static electricity before handling elec­tronic circuit boards. Touch a grounded, bare metal surface before handli ng circuit boards to discharge yourself of stati c electricity or wear a static grounding strap.
Insert one antenna into the inside screw terminal of each terminal block and gently tighten the screws us­ing a small pocket-size screwdriver (figure 3).
3
Page 8
Installing the System
Setting the Optional Energy Saver Module (ESM), Hardwire Input Module (HIM) and Hard­wire Output Module (HOM) Unit Number DIP Switches
All devices connected to the panel’s SuperBus hard­wire bus have individual unit numbers assigned. Al­phanumeric touchpad unit numbers are changed in software during programming. The Energy Saver Module (ESM), Hardware Input Module (HIM), and Hardware Output Module (HOM) are set wit h DIP switches inside the modules. For unit number setting details, refer to the installation instructions provided with the bus device.
Duplicated unit numbers will prevent those bus devic­es from operating. Refer to table D.3 in appendix D for recommended SuperBus device unit number set­tings.
unit number assigned is to more than one device. Su­perBus devices cannot share the same unit number.
UNIT NUMBER 0
5
4
12
12
12
12
12
12
12
3
4
3
4
3
4
3
4
3
4
3
4
3
6
UNIT NUMBER 1
5
6
UNIT NUMBER 2
5
6
UNIT NUMBER 3
5
6
UNIT NUMBER 4
5
6
UNIT NUMBER 5
5
6
UNIT NUMBER 6
5
6
UNIT NUMBER 7
7
8
7
8
7
8
7
8
7
8
7
8
7
8
To set your ESM, HIM, or HOM unit number:
1. Set the module unit number DIP switches to the desired unit number as shown the figure 4 per the recommendations in table D.3 in appendix D. The unit number is set to 0 (zero) at the factory and is OK for most single touchpad and single ESM, HIM, or HOM module applications. Make sure that no bus devices (including hardwire touchpads) share the same unit number (device address).
Caution
The alphanumeri c touchpad unit number default s to 1 (one). Do not set the ESM, HIM, or HOM unit number to 1. Doing so will prevent the touchpad from functioning.
2. Turn the c ontrol panel power switch off and then back on so the bus module can read the unit num­ber switch settings into its memory.
3. Enter and exit PROGRAM MODE by switching the panel PROGRAM/RUN switch to PRO­GRAM and back to RUN so the panel can “learn” the new bus device unit numbers.
12
4
3
6
7
8
8557G32A.DS4
5
Figure 4 Setting the ESM, HIM, or HOM Unit Num­ber Dip Switches
Note
All SuperBus devices such as Energy Saver, Hardwire In­put, and Hardwire Output Mo dules and alphan umeric touch­pads must have unique unit number (address) settings. Devices with the same (confli cting) add ress will not fu nction properly. Module address switches 1 –5 must remain down (off).

Installing the Backup Battery

The panel uses one rechargeable, sealed 12V lead­acid backup battery.
Note
Both standard (60-681) 12V, 4AH and heavy duty (60-680) 12V, 6.5AH backup batteries are available. Always replace with the same battery type and size.
If the alphanumeric touchpad (or other SuperBus de­vice) no longer seems to function, check if the same
4
Page 9
Installing the System
To install (or replace) the backup battery:
1. Make sure the panel power switch is OFF and
that the transformer is unplugged from the outlet. While AC power is applied to the panel, the
charging voltage is present at the battery leads even with the power switch off.
2. Verify all wiring at the panel and devices for cor-
rect terminations.
3. Place the battery in the lower left or right portion
of the panel enclosure, with the termina ls facing up.
4. Connect the supplied black battery wire from the
panel circuit board negative (-) battery spade lug (located near the power switch) to the negative (­) battery terminal.
5. Connect the red battery wire from the panel cir-
cuit board positive (+) battery spade lug to the positive (+) battery terminal.
WARNING! Never short-circuit or reverse the battery wires. Possi­ble injury to you and/or permanent damage to the panel could result.

Powering Up the Panel

The green power LED on the panel turns on. Interior sirens and piezos sound one b eep an d in-
terior speakers announce the message Alarm sys- tem is off.
Alphanumeric touchpad displays 1 - OFF.
Note
If the power LED is off or flashing and no beeps or voice messages sound, turn off the panel power switch, discon­nect the backup ba tter y, an d un pl ug th e tra nsfo rmer. Re fe r to appendix B, “Troubleshooting.”
4. Turn the panel power switch OFF, unplug the transformer, and remove the existing screw securing the AC outlet cover.
WARNING! Use extreme caution when securing the transformer to a metal outlet cover. You could receive a serious shock if a metal outlet cover drops down onto the prongs of the plug while you are securing the transformer and cover to the outlet box.
5. Hold the outlet cover in place and plug the trans­former into the lower receptacle.
6. Use the screw supplied with the transformer to secure the transformer to the outlet cover.
7. Turn the panel power switch ON.
After wiring all devices to the panel and installing the backup battery, you are ready to power up the panel.
Note
If the installation includes more than one alphanumeric touchpad, disconnect all but one from their wiring harness­es to reduce the possibility of a unit number (address) con­flict. When powering up and programming are completed, connect the remaining touchpads to their wiring harnesses. For complete details on adding additional alph anumeric touchpads to a workin g system, refer to the
phanumeric Touchpad Installation Instructions
with each touchpad.
SuperBus Al-
included
To power up the panel:
1. Plug the transformer into an outlet that is not controlled by a switch.
2. Make sure the panel PROGRAM/RUN swi tch located between the two panel terminal strips is set to RUN (up).
3. Turn ON the panel power switch located on the left edge of the panel and note the following:

Adjusting Status Sound Volume

The panel allows you to set the volume level for status sounds and status messages from speakers connected to panel terminals 8 and 9 (VOICE). Alarm sounds and messages are preset to full volume .
To adjust the status sound volume:
1. Locate the speaker vol um e ad justment potenti­ometer on the panel (above terminal 8).
Caution
Never adjust the potentiometer labeled “Do Not Adjust” lo­cated near the power switch. Permanent damage to the panel could result.
5
Page 10

Programming the Panel

2. Press STATUS + STATUS on the alphanumeric
touchpad for a long system status display and voice message.
Note
User-programmabl e system s etting 77 (Quiet Exit ) must be off for voice so un ds to b e a nno unce d . (Se e Viewin g o r Pro­gramming the User-Programmable System Settings.)
3. While listening to the message, increase the vol­ume level by turning the volume potentiometer clockwise.
4. Repeat steps 2 and 3 until the desired volume level is reached.
Programming the Panel
The alphanumeric touchpad is the main programming device for the system on-site. This touchpad is used to enter values into panel memory, such as sensors, sen­sor text, and system-specific configuration informa­tion. During programming, the alphanum eri c touchpad prompts you for information in a certain or­der. You can cycle through this order of prompts to get to the desired programming area. For example, you can cycle past the prompts for sensor text to enter the system configuration information and later return to programming sensor text.
Figure 5 shows the order of the prompts, and the area of programming related to these prompts. Once you know this order of prompts, you will be able to move forward and backward in the prompt sequence to lo­cate the programming item you need.
Examine the flowchart shown in figure 5 to familiar­ize yourself with the sequence in which the program­ming procedures appear. The programming software is like a menu of choices displayed in a scroll. The di­rection of the chart arrows represents pressing the BYPASS button to scroll forward. To scroll back­ward, press the STATUS button. You can also go di­rectly to the menu choice by entering the two-digit number shown.
When you use the alphanumeric touchpad to program the system, the touchpad buttons have special pro­gramming meanings and functions. Table 1 describes the programming buttons.
PROGRAM
MODE
DELETE
TEXT
01
EXTENDED
PROGRAM
SENSOR
TEXT
02
LEARN
SENSORS
03
DELETE
SENSORS
04
UPPER
SENSORS
05
F
OPTIONS
06
LEARN
TOUCHPADS
07
PHONE
NUMBER
08
PHONE
FORMAT
09
SIREN
TIME-OUT
10
INSTALL CODE
11
ACCOUNT
NUMBER
12
ENTRY DELAY
13
DELAY
14
EXIT DELAY
15
ACTIVITY
TIME-OUT
16
HOUSE
CODE
17
FREEZE
TEMPERATURE
18
SET
TEMPERATURE
19
TOUCHPAD
OPTIONS
20
AVM MODE
21
AVM
TIME-OUT
22
AVM CODE
23
HOM
SETUP
24
TIME
ZONE
25
Figure 5 Programming Flow Chart
8557G45B.DS4
6
Page 11
Table 1 Alphanumeric Touchpad
Programming Button Functions
Button Programming Function
Numeric Buttons
STATUS Scrolls backward to previous program-
BYPASS Scrolls forward to next programming
COMMAND Used to proceed or confirm displayed
Used to enter numeric values such as delays and sensor numbers. Also used to enter text characters or word codes during sensor text programming.
ming function. Displays previous sensor text library character during sensor text programming. Also used to “lock in” new alphanumeric touchpad unit numb ers.
function. Displays next sensor text library character during sensor text pro­gramming.
entry. Displays next character/word posi­tion in sensor text programming. Also used to toggle between values, such as yes/no or on/off.
Programming the Panel
• Programming the house code
• Programming the freeze and set temperatures
• Programming the touchpad options
• Programming the Audio Verification Module mode, time-out, and access code
• Programming HOM Setup
• Programming the Time Zone
• Viewing or programming the user-programmable system settings
• The duress code
• Adjusting the alphanumeric touchpad display brightness
• Requesting CS-4000/Downloader programming
Note
All on-site programming must be done usin g a SuperBus Al­phanumeric Touchpad. The Alphanumeric Touchpad can be removed once the system has be en programmed.

Clearing Memory

FIRE Cancels and exits displayed program-
ming command (if pressed before COM­MAND).
Backs out to previous menu level. AUXILIARY Scrolls long display messages. POLICE Used to clear (blank) an access code.
Used to program a pause in central sta-
tion phone numb er.
Used to clear HOM points.
Programming the panel includes the following proce­dures:
• Clearing memory
• Entering and exiting program mode
• Deleting and programming sensor text
• Adding and deleting wireless sensors and hardwire zones
• Programming upper sensor numbers
• Programming optional feature numbers
• Adding wireless touchpads
• Programming panel configuration options
• Programming the phone number and format
• Programming the siren time-out
• Programming the install code
• Programming the account number
• Programming the entry, extended, and exit delays
• Programming the activity time-out
Clear memory on all newly installed panels before programming.
Note
Since all programming info rmation is cont ained in memo ry, clearing memory deletes all ex is ting programming informa­tion except sensor text (if any). Sensor text can be deleted separately.
To clear panel memory:
1. Open and remove the panel door.
2. Turn the panel power switch OFF and then ON.
3. Immediately (within 1 minute after turning panel power ON), press and hold the memory clear button located on the upper left edge of the panel until a relay click is heard at the panel or until interior speakers announce Memory good-bye.

Entering and Exiting Program Mode

The panel must be in program mode to perform any of the on-site programming operations.
7
Page 12
Programming the Panel
To enter program mode:
1. Open and remove the panel door.
2. Set the panel PROGRAM/RUN switch to PRO­GRAM (down).
Alphanumeric touchpads display PROGRAM MODE and interior speakers, sirens, and piezos sound six beeps every minute as a reminder that the panel is in the program mode.
Note
If touchpad(s) do not display switching the PROGRAM/RUN switch to PROGRAM (down), a special install code has been programmed into the panel and now must be entered into the touchpad using the number buttons. The touchpad will display
MODE
once the correct install code is entered.
PROGRAM MODE
PROGRAM
after
The program mode of operation must be exited for the system to operate normally (RUN). You can exit from program mode at any time.
To exit program mode:
1. Switch the panel PROGRAM/RUN switch to RUN (up).
2. The alphanumeric touchpad will display 1 - OFF to signal that the system is in the normal mode of operation.
3. When you are finished programming or working in the control panel, replace and secure the panel door with either the panel door screws or key lock.

Deleting Sensor Text

You can delete all sensor text (if any)—before pro­gramming or reprogramming, for example—by doing the following procedure.
To delete all existing sensor text:
1. In PROGRAM MODE, press BYPASS or STA­TUS until DELETE TEXT is displayed.
2. Press COMMAND. Flashing RDY is displayed.
Caution
Deleted text cannot be retrieved and must be repro­grammed.
TEXT DONE is displayed.
4. Press FIRE to exit.

Programming Sensor Text

This section describes how to program sensor names. Use the word and character numbers you recorded in appendix D (using table C.2 in appendix C) to pro­gram sensor text.
Before programming sensor text the first time, delete all existing text (if any) as detailed above.
To program sensor text:
1. In PROGRAM MODE, press BYPASS or STA­TUS until the display reads PROG SENSOR
TEXT.
2. Press COMMAND and the display reads S01
[Group number assigned, if any] [“-” if nor­mally closed, “*” if normally open] [existing sensor text, if any].
3. Enter the desired sensor numbe r from 01 to 76 and the display reads S## [existing sensor text, if any].
4. Press COMMAND and the display reads A 00.
5. Enter the appropriate word number or character number from table C.2 in appendix C.
6. Press COMMAND and the display reads B 00.
7. Repeat steps 5 and 6 until the whole sensor name is entered.
Note
Because the touch pad can o nly disp lay a limi ted number of characters, in some cases—such as alarms—all text may not be displayed.
8. Press FIRE. The display shows the sensor num­ber and name. Lines longer than the display will scroll horizontally. If desired, press AUXIL- IARY to scroll the long-line display again.
9. Press BYPASS to cycle to the next sensor num­ber and repeat steps 4 through 8 until all sensor names are programmed.
10. Press FIRE to exit.
3. Press POLICE to delete all sensor text. DELETE
8
Page 13
Programming the Panel

Adding (Learning) Wireless Sensors

Programming wireless and hardwire sensors involves switching the panel to the program mode of operation and setting sensor identificati on num be rs and group numbers for each wireless sensor and hardwire sensor loop. Once sensors IDs and group assignments are added (learned) into panel memory, the panel can re­spond appropriately for each sensor detection. Sen­sors can be added (learned) into or deleted from panel memory.
Use table C.1 in appendix C for selecting sensor groups and complete the group assignment for each wireless sensor in the system planning worksheets in appendix D.
Use the following procedure to add (learn) all Learn Mode wireless sensors.
To add Learn Mode wireless sensors into panel memory:
1. In PROGRAM MODE, press the touchpad
BYPASS or STATUS button repeatedly until LEARN SENSOR is displayed.
2. Press the COMMAND button to display
GROUP __ __.
3. Enter the desired group number (00 to 29, 32).
4. Press the COMMAND button to display SEN-
SOR ##.
5. Press the COMMAND button if the sensor num-
ber displayed is OK or enter another number from 01 to 76, and then press COMMAND again.
6. The display reads TRIP - ## . Trip the wireless sensor tamper switch as shown in table 2 or as described in the sensor’s installation instructions. When the sensor has been added (learned) the display reads TRIP - ## [next #] and interior speakers announce Sensor # okay. Sensor [next #
to be learned].
Note
To trip a wireless sensor with an e xternal h ard-wire c ontact connected to its screw terminals, check that the external contact is in its alarm state, and then trip the sensor.
The alarm state is either open or closed, depending on the
normal condition of the sensor. Multiple normally closed switches are wired in series and tripped while the loop is open. Multiple normally ope n switch es ar e wire d in paral lel and tripped while the loop is closed.
For high-security installations, always remove both internal reed switches when connecting an external contact to the wireless sensor terminals.
Only the normally closed configuration can be used in UL­listed installati ons.
Do not attempt to use the built-in reed switch nal contact on the same wireless sensor.
and
an exter-
Table 2 Tripping Learn Mode Wireless
Sensors
Sensor * Action
Door/Window Open sensor cover.
Fire Pull Station Open the sensor cover located
inside the Fire Pull Station. Freeze Open sensor cover. Gl ass Guard Open sensor cover . Portable Emergency But-
tons PIR Motion Open PIR case. K eychain Touchpad Simultaneously press arm and dis-
Rate-of-Rise Heat Open sensor cover and press learn
Recessed Door/Window Open sensor cover and remove
Shock
Open sensor cover.
Slim Line Door/Window Remove sensor from moun ting
Sound Open sound sensor cover, after
System Sensor Smoke
System Sensor 2300RF ITI
Press the appropriate emer-
gency button(s).
arm until the LED flashes.
switch on circuit board.
transmitter circuit board.
base.
spring is installed.
Press test button and hold for
30 se conds, until test alarm
begins sounding.
With sensor removed from base,
press the test b utton for at leas t
1 second.
* Refer to the particular sensor’s installation instructions for
more details on tripping Learn Mode wireless sensors.
When using an external contact with this sensor, the contact
must be in the alarm state while tripping the sensor to properly learn it into memory.
7. Continue adding sensors into the current group number by repeating step 6 for each sensor. Press BYPASS, STATUS, or number buttons to select new sensor numbers (other than what is automat­ically displayed).
8. To add sensors into other groups, press FIRE and follow steps 3 through 7.
9
Page 14
Programming the Panel
9. Press FIRE to exit. Proceed to your next pro-
gramming task.
10. If you are finished programming, switch the panel PROGRAM/RUN switch to RUN (up). The touchpad will display 1 - OFF to signal that the system is in the normal (RUN) mode of oper­ation.

Adding (Learning) Hardwire Sensors

After planning the installation, use table C.1 in appen­dix C to select sensor groups and complete the group assignment for each wireless sensor in the system planning worksheets in appendix D.
Use the following procedure to add (learn) all hard­wire sensors and zones into panel memory.
On hardwire zones containing multiple sensors, only one sensor per zone needs to be added (learned) into panel memory.
If the system uses hardwire sens ors only, turn off upper sensor 94 (Receiver Failure) in the panel.
Only the normally closed configuration can be used in UL­listed installati ons.
8. Continue adding sensors into the current group
number by repeating step 7. Press BYPASS, STATUS, or number buttons to select new sen­sor numbers.
9. To add sensors into other groups, press FIRE
and follow steps 4 through 8.
10. Press FIRE to exit. Proceed to your next pro-
gramming task.
11. If you are finished programming, switch the panel PROGRAM/RUN switch to RUN (up). The touchpad will display 1 - OFF to signal that the system is in the normal (RUN) mode of oper­ation.
To add (learn) hardwire sensors:
1. Place all hardwire sensors in their normal (non­alarm) state.
2. In PROGRAM MODE, press the touchpad BYPASS or STATUS button repeatedly until LEARN SENSOR is displayed.
3. Press the COMMAND button to display
GROUP __ __.
4. Enter the desired group number (00 to 29, 32).
5. Press the COMMAND button to display SEN- SOR ##.
6. Press the COMMAND button if the sensor num­ber displayed is correct or enter another number from 01 to 76, and then press COMMAND again.
7. The display reads TRIP - ## . Trip the sensor by placing it into the alarm state (open the door or window) or as described in the sensor’s installa­tion instructions. The display reads TRIP - ##
[next #] and interior speakers announce Sensor # okay. Sensor [next # to be learned].
Note
The alarm state is either open or closed, depending on the normal condition of the sensor. Multip le no rmally closed switches are wired in series and trip p ed while the loop is open. Multiple no rmally open switches are wired in para llel and tripped while the loop is closed.
Deleting Sensors and Hard­wire Zones
If you want to reassign a sensor or hardwire zone to another group, you must first delete that sensor or zone.
To delete a sensor from the panel:
1. In PROGRAM MODE, press STATUS or BYPASS until the display reads DELETE SEN-
SOR.
2. Press COMMAND and the display reads
DELETE ## [sensor text, if any].
Note
After pressing COMMAND in step 2, the display shows the lowest programmed sensor number.
3. If the sensor number displayed is not correct, enter the desired number (01 to 76).
4. Press COMMAND and the display reads DEL
## OK.
5. Continue deleting sensors by repeating steps 3 and 4.
10
Page 15
Programming the Panel
6. Press FIRE to exit.
Note
Sensor text is not deleted when its sensor is deleted.

Programming Upper Sensors

Upper sensors are optional values (see appendix D, table D.7) you turn on or off depending on your cus­tomer’s equipment and needs.
Note
We recommend tha t you d o not c hange upper sensors that default ON. Factory default settings will work for most appli­cations.
Use the settings recorded in appendix D, table D.7 when programming upper sensors.
To program upper sensor numbers:
1. In PROGRAM MODE, press BYPASS or STA­TUS until UPPER SENSOR is displayed.
2. Press COMMAND and the display reads 77 ­OFF TOUCHPAD TAMPER. (Press AUXIL-
IARY to scroll any long messages sideways.)
3. Press COMMAND to toggle upper sensor 77 ON, if desired, or press BYPASS to cycle to the next upper sensor.
Note
We recommend that you do not change feature numbers that default ON. Factory defa ul t set tings will work for most applications .
Use the settings recorded in table D.8 when program­ming optional feature numbers.
To program feature numbers:
1. In PROGRAM MODE, press BYPASS or STA­TUS until F OPTIONS is displayed.
2. Press COMMAND to display 00 - ON REMOTE ACCESS. (Press AUXILIARY to scroll long
messages in the display.)
3. Press COMMAND again to toggle the feature number ON or OFF as desired.
4. Press BYPASS to display the next feature num­ber.
Note
To jump directly to a particular feature number, enter its number instead of pressing BYPASS.
5. Repeat steps 3 and 4 for all of the remaining fea­ture numbers.
6. Press FIRE to exit.

Adding (Learning) Wireless Touchpads

Note
To jump directly to a particular upper sensor, enter its two­digit number instead of pressing BYPASS.
4. Repeat step 3 until all upper sensors are pro­grammed to suit the installation.
5. Press FIRE to exit.

Programming Optional Feature Numbers

Optional feature numbers are system features (see ap­pendix D, table D.8) you turn on or off depending on your customer’s needs.
You can add up to four wireless touchpads to the sys­tem (including keychain touchpads).
To add (learn) wireless touchpads:
1. In PROGRAM MODE, press BYPASS or STA­TUS until LEARN TOUCHPAD is displayed.
2. Press COMMAND to display PRESS BYP TP -
1.
3. Press BYPASS on the wireless touchpad (press and hold both lock and unlock buttons on the wireless keychain touchpad) until the display reads PRESS BYP TP 2 and One OK, Two is heard.
4. Repeat step 3 for each wireless touchpad until they are all added.
5. Press FIRE to exit.
11
Page 16
Programming the Panel
Caution
After exiting from learning touchpads, reentering the learn touchpads menu by pressing COMMAND automatically de­letes all learned touchpads. When adding wireless touch­pads to the system, you must also relearn existing touchpads.

Programming Panel Configuration Options

This section describes how to program the following:
Primary phone number and phone format
Siren time-out
Install code
Account number
Entry, extended, and exit delays
Activity time-out
House code
Energy Saver Module (ESM) freeze and set tem­peratures
Touchpad unit number, quiet, and key beeps options
Audio Verification Module (AVM) mode, time­out, and code
HOM setup
Time zone
User-programming system settings
Duress code
Use the panel configuration settings you recorded in table D.5 to program the system.
To program the central monitoring station tele­phone number:
1. In PROGRAM MODE, press BYPASS until the
display reads PHONE NUMBER.
2. Press COMMAND. The display shows [existing
phone number, if any].
3. Enter the central station receiver phone number (up to 18 digits). If you need a pause between digits, press POLICE for each 1-second pause desired.
4. Press COMMAND. The display reads [new
phone number].
5. Press FIRE to exit.

Programming the Phone Format

The phone format det ermines th e type of comm unica­tion the panel uses to report to the central monitoring station’s receiver. The default phone format is “ITI.”
To program the panel telephone format:
1. In PROGRAM MODE, press BYPASS until the display reads PHONE FORMAT.
2. Press COMMAND to display the currently selected format. For example, ITI FMT.
3. Press BYPASS or STATUS to cycle to the desired setting: SET ITI, -1400, or -2300.
Note
Phone format must be set to “ITI” for the panel to correctly communicate with the ITI ToolBox Downl oa de r.

Programming the Primary Phone Number

The panel can report alarms and all other reports to a central monitoring station by programming the prima­ry phone number (or central station’s phone number) into panel memory. The default phone number is blank (none).
12
4. Press COMMAND and the display reads SET [selected format] OK.
5. Press FIRE to exit.
Page 17
Programming the Panel

Programming the Siren Time-out

The siren time-out determines how long sirens sound an alarm condition, if no one is present to disarm the system. The default siren tim e -o ut is 4 min ute s.
To program a different siren time-out:
1. In PROGRAM MODE, press BYPASS until the
display reads SIREN TIMEOUT.
2. Press COMMAND and the display reads SIREN
- ## MIN.
3. Enter the desired two-digit time (01 to 30 min­utes).
4. Press COMMAND and the display reads SIREN
- ## MIN.
5. Press FIRE to exit.
To program an install code:
1. In PROGRAM MODE, press BYPASS until the
display reads INSTALL CODE.
2. Press COMMAND to display INSTALL - ****.
3. Enter any four digits from 0001 to 9998.
Note
See table D.6 in appen di x D for cod e number defaults and restrictions.
To return the install code to blank (****) press the POLICE button instead of a four-digit code.
4. Press COMMAND. INSTALL - #### is dis-
played.
5. Press FIRE to exit.

Programming the Account Number

Programming the Install Code

The install code is a special access code used to pre­vent accidental or unauthori zed cha nge s to syst em programming. The default install code is blank (****).
Caution
Always install and test all wired touchpads before entering an install code. Programming an install co de befor e all touchpads are installed and tested is risky. It can lead to a situation where memory must be cleared to get int o pr o­gram mode. This can happ en if a bus co nflict ren ders the al­phanumeric touchpad useless (and there are no wireless touchpads an d phone co ntrol i s turned off). In th is situat ion, there is no way to enter an install co de—there is no way to get back into the program mode except to erase the install code (and all other programming) by clearing memory.
If an install code is desired, program it after installation is complete and just before you leave the site.
Note
Once an install code is entered, it will start a 1-hour timer. For the next hour, the install code will not be requ ired. Th is timer is cleared by entering dealer sensor test.
The account number is a fiv e-character p anel identif i­cation for central monitoring stations. Used when the panel sends reports. The default account number is 00-000.
To program an account number:
1. In PROGRAM MODE, press BYPASS until the
display reads ACCOUNT NUM BER.
2. Press COMMAND to display ACCOUNT -
#####.
3. Enter any five digits.
4. Press COMMAND. ACCOUNT - ##### is dis-
played.
5. Press FIRE to exit.
Note
Only numbers can be pr ogrammed locally though the alpha ­numeric touchp ad . L etters can be programmed thoug h the CS-4000 or Downloader and will display correctly with the panel in program mode.
13
Page 18
Programming the Panel

Programming the Entry Delay

The entry delay determines the time a user has to enter the premises and disarm the system, before it goes into alarm. The default entry delay is 32 seconds.
To program a different entry delay:
1. In PROGRAM MODE, press BYPASS until the
display reads ENTRY DELAY.
2. Press COMMAND and the display reads ENTR Y
- ### SEC.
3. Enter the desired three-digit time (008 to 120 seconds).
Note
The system automatically rounds off the entry to the near est multiple of eight.
4. Press COMMAND a nd the display reads ENTR Y
- ### SEC.
5. Press FIRE to exit.

Programming the Exit Delay

The exit delay determines how much time system us­ers have to leave the premises through a designated delay door without causing an alarm, after arming the system. The default exit delay is 32 seconds.
To program the exit delay:
1. In PROGRAM MODE, press BYPASS until the
display reads EXIT DELAY.
2. Press COMMAND and the display reads EXIT -
### SEC.
3. Enter the desired three-digit time (008 to 184 seconds).
Note
The system automatically rounds off the entry to the nearest multiple of eight.
4. Press COMMAND and the display reads EXIT ­### SEC.
5. Press FIRE to exit.

Programming the Extended Delay

The extended delay affects both entry and exit delay times for sensors in groups 11 (extended delay) and 12 (twice extended delay). The extended delay setting determines how much time system users have to leave the premises after arming and how much time users have to disarm after entering, without causing an ac­cidental alarm. The default extended delay is 4 min­utes.
To program a different extended delay:
1. In PROGRAM MODE, press BYPASS until the
display reads EXTENDED DELAY.
2. Press COMMAND. The display reads DELAY -
## MIN.
3. Enter the desired two-digit time (01 to 08 min­utes).
4. Press COMMAND and the display reads
DELAY - ## MIN.
5. Press FIRE to exit.

Programming the Activity Time-out

The activity time-out determines how many hours of system non-use are sensed, before sending a report to the central monitoring station. The de fault activity time-out is 24 hours.
To program a different activity time-out:
1. In PROGRAM MODE, press BYPASS until the
display reads ACTIVITY TIMEOUT.
2. Press COMMAND to display ACTIVITY - ## H.
3. Enter the desired two-digit time (01 to 24 hours).
4. Press COMMAND. ACTIVITY - ## H is dis-
played.
5. Press FIRE to exit.
Note
Upper sensor S79 (No Activity) must be on for the activity timer to function. S79 defau lt is off.
14
Page 19
Programming the Panel

Programming the House Code

The house code is a three digit number used to com­municate panel signals to line carrier devices such as Wireless Interior Sirens (WIS) and X-10 Lamp and Appliance Modules. The default house code is 001(X­10 module house code “B”).
To program a different house code:
1. In PROGRAM MODE, press BYPASS until the
display reads HOUSE CODE.
2. Press COMMAND to display HOUSE CODE -
### [X-10 module unit code A–P].
3. Enter the desired three digit house code number
(001 to 254).
4. Press COMMAND. HOUSE CODE - ### [X-10
module unit code A–P] is displayed.
5. Press FIRE to exit.
5. Press FIRE to exit.
The Energy Saver Module set (readout) temperature setting lets you adjust the module to match the on-pre­mises thermostat. The default set temperature is the unadjusted ESM temperature.
To adjust the Energy Saver Module temperature readout, make sure that the module is wired and working, then:
1. In PROGRAM MODE, press BYPASS until the
display reads SET TEMP.
2. Press COMMAND to display TEMPERATURE
- ##.
3. Enter present two-digit room temperature (32 to
99).
4. Press COMMAND and the display reads TEM-
PERATURE - ##.
5. Press FIRE to exit.

Programming the Energy Saver Module Freeze and Set Temperatures

The freeze temperature setting determines when the Energy Saver Module’s freeze sensor activates, sounding interior sirens and reporting to the central monitoring station. The default freeze temperature is 42° F.
Note
Upper sensor 78 (Freeze Senso r) must be ON to enable th e freeze alarm. Upper sensor 78 defaults to OFF.
To program the Energy Saver Module freeze tem­perature:
1. In PROGRAM MODE, press BYPASS until the
display reads FREEZE TEMP.
2. Press COMMAND and the display reads
FREEZE TEMP - ##.
3. Enter the desired two-digit temperature (40 to
90).
4. Press COMMAND and the display reads
FREEZE TEMP - ##.

Programming the Touchpad Options

The touchpad options setting lets you set the touchpad unit number, touchpad quiet, and touchpad key beeps options.
To program the alphanumeric touchpad options:
1. In PROGRAM MODE, press BYPASS until
TOUCHPAD OPTIONS is displayed.
2. Press COMMAND to display UNIT NUMBER.
3. Press BYPASS to display the various touchpad
options.
4. Continue with the following touchpad option procedures.
15
Page 20
Programming the Panel

Programming the Touchpad Unit Number

The touchpad unit number lets the panel identify spe­cific touchpads connected to the bus. Each alphanu­meric touchpad must be assigned a unit number, different than any other bus device. Use the following guidelines when changing touchpad unit numbers:
Always start with on e to uch p ad co nn ected to the panel and get it operational with the panel, before connecting additional touchpads.
Whenever possible, such as in new installations, assign alphanumeric touchpad unit numbers before all other panel programming.
Always work from one touchpad location when assigning unit numbers for installations with multiple touchpads.
For complete details on installing additional alphanu­meric touchpads to a working system, refer to the Su-
perBus Alphanumeric Touchpad Installation Instructions included with each touchpad.
The default touchpad unit number is 001.
To change the alphanumeric touchpad unit num­ber:
1. In PROGRAM MODE, press BYPASS until
TOUCHPAD OPTIONS is displayed.
2. Press COMMAND. Display reads UNIT NUM-
BER.
3. Press COMMAND to display the present unit
number DA ###.
4. Press COMMAND to display ENTER _.
5. Enter the desired three digit touchpad unit num­ber (000 to 007).
6. Press STATUS to lock in the new unit number.
Note
The touchpad will be nonfunctional after its unit number is changed until it is reactivated as follows.
7. Switch the panel PROGRAM/RUN switch to RUN (up) and back to PROGRAM (down) to reactivate the touchpad with it s new unit number. Touchpad will display PROGRAM MODE.

Programming the Touchpad Quiet

Note
On systems with multiple alphanumeric touchpads, the fol­lowing procedure puts all touchpads into the address set mode.
Caution
Always delete (blank) the install code before adding wired touchpads o r ch ang in g wir ed to uc hp ad un it (a dd re ss ) n um­bers. The default install code is blank (****).
Programming an install code before all touch p ad s are in­stalled and tested may prevent correct touchpad installation and may require clearing memory and reprogra mming. If an install code is desired, program it after installation is com­plete and just before you leave th e site.
To delete (blank) the install code prior to changing the touchpad unit number:
1. In PROGRAM MODE, press BYPASS until the
display reads INSTALL CODE.
2. Press COMMAND to display INSTALL - ####.
3. Press the POLICE button. INSTALL - ****
(blank) is displayed.
4. Press FIRE to exit.
The touchpad quiet option determines whether status sounds are heard from a specific touchpad. If there is more than one touchpad, the following procedure must be done at each touchpad you want changed. The touchpad quiet default is N (no—not quiet).
To changed the alphanumeric touchpad quiet op­tion:
1. In PROGRAM MODE, press BYPASS until TOUCHPAD OPTIONS is displayed.
2. Press COMMAND. Display reads UNIT NUM­BER.
3. Press BYPASS or STATUS until the display reads TOUCHPAD QUIET N (no) or Y (yes).
4. Press COMMAND to toggle from Y or N.
5. Press FIRE to exit.
16
Page 21
Programming the Panel

Programming Touchpad Key Beeps

The touchpad key beeps option determines whether key-press sounds are heard from a specific touchpad. The following procedure must be done at the specific touchpad you want changed.
The touchpad key beeps default is Y (yes—keys beep when pressed).
To change alphanumeric touchpad key beeps:
1. In PROGRAM MODE, press BYPASS until
TOUCHPAD OPTIONS is displayed.
2. Press COMMAND. Display reads UNIT NUM-
BER.
3. Press BYPASS or STATUS until the display
reads KEYBEEPS N (no) or Y (yes).
4. Press COMMAND to toggle Y or N.
5. Press FIRE to exit.
Note
The key beeps option does not actually change until the panel RUN/PROGRAM switch is changed from PROGRAM to RUN.
2. Press COMMAND to display AVM MODE -
[present AVM mode number].
3. Enter the desired two-digit AVM mode number:
01 - One-ring 02 - One-ring Silent 03 - Instant 09 - One-ring Fire Siren Shutdown 10 - One-ring Silent Fire Siren Shutdown 11 - Instant Fire Siren Shutdown
4. Press COMMAND. AVM MODE - [new mode
number] is displayed.
5. Press FIRE to exit. The AVM time-out determines how long the AVM
will wait without hearing a command before hanging up. The default AVM time-out is 90 seconds.
To change the Audio Verification Module time­out:
1. In PROGRAM MODE, press BYPASS until
AVM TIME-OUT is displayed.
2. Press COMMAND to display AVM TIME-OUT
- [present time-out in seconds].
3. Enter the desired three digit AVM time-out (030
to 300 seconds in 2-second increments).
4. Press COMMAND. AVM TIME-OUT - [new
time-out] is displayed.
5. Press FIRE to exit.

Programming the Interrogator 200 Audio Verification Module Mode, Time-out, and Access Code

The optional Interrogator 200 Audio Verification Module* (AVM) allows for two-way voice communi­cation with the monitoring station in the event of an alarm. The AVM mode, time-out, and access code need to be programmed. The default AVM mode is 03 (instant).
* Not intended for use with UL-listed systems.
To change the Audio Verification Module mode of operation:
1. In PROGRAM MODE, press BYPASS until
AVM MODE is displayed.
The AVM access code helps prevent unauthorized lis­ten-in/talk-back audio sessions. The default AVM ac­cess code is blank (****).
To program the Audio Verification Module access code:
1. In PROGRAM MODE, press BYPASS until
AVM CODE is displayed.
2. Press COMMAND to display AVM CODE -
[pre sent access code].
3. Enter the desired four-digit AVM access code
(0001 to 9998) or press POLICE to clear the dis­played code.
Note
See table D.6 in appen di x D for cod e number defaults and restrictions.
4. Press COMMAND. AVM CODE - [new access
code] is displayed.
5. Press FIRE to exit.
17
Page 22
Programming the Panel

Programming HOM Points

The optional HOM (Hardwire Output Module) has 4 programmable output points that can be used to acti­vate other devices, based on the syste m event ( alarm, trouble, etc.). For example, a HOM output can be con­figured to activate CCTV during an intrusion alarm , turn on lights during a fire alarm, or activate cellular phones or long-range radios if primary phone com­munications are out of service.
The following describes the basic HOM output point configuration steps. For complete HOM setup and programming, see the SuperBus Hardwire Output Module Installation Instructions (466-1127) included with each HOM.
To program HOM output point configurations:
1. In PROGRAM MODE, press BYPASS until
HOM SETUP is displayed.
2. Press COMMAND to display POINT 01-#####
(the first point and it’s previously programmed configuration code [if any]). Blank or unpro­grammed points are displayed as POINT ##- * * * * *.
3. To display other points, press STATUS, BYPASS or enter the desired two-digit point number.
4. Press COMMAND to change the displayed point’s configuration code. The display will show POINT ##-_ _ _ _ _. Or press POLICE to enter a blank number for this point.
5. Enter the point’s new 5 digit configuration num­ber. The display will blink as you start entering numbers. To escape this sequence without chang­ing the previously programmed number, press FIRE.
6. Press COMMAND to enter the new point con­figuration into panel memory. The display will stop blinking. Note: If the entered number is invalid, the dis­play reverts to the points previously programmed configuration number.
7. To display and/or change other points, press STATUS or BYPASS.
8. When finished, press FIRE once to return to the Main menu.

Programming the Time Zone

The TIME ZONE menu optio n is used to set th e time zone where the panel is installed.
To program the panel’s time zone:
1. In program mode, press BYPASS until TIME
ZONE is displayed.
2. Press COMMAND to display the current tim e zone setting (default = 05).
3. Enter the 2-digit number (see Table 3) that corre­sponds to the time zone where the panel is located.
Table 3 Time Zone Settings
Time Zone
Eastern 05 Central 06 Mountain 07 Pacific 08 Hawaii 10
4. Press COMMAND to display the new pro­grammed time zone.
5. Press FIRE to exit.
T o uchpad
Entry

Viewing or Programming the User-Programmable System Settings

Certain system settings can be user programmed while the system is in the normal (RUN) operating mode. These are:
Primary access code
Secondary access codes
Arm-disarm access codes
High and low Energy Saver Module tempera­tures
Quiet exit
Downloader enable
18
Page 23
Programming the Panel
Use the settings recorded in appendix D, table D.6, when programming user-programmable system set­tings.
To view or program the user-programmable sys­tem settings:
1. Press ACCESS CODE + STATUS + 8. SYS-
TEM SETTINGS is displayed and System mem­ory open is announced.
Note
User programming is automatically exited after 1 minute if no buttons are pressed.
2. Press BYPASS to display 00 - ARM CODE 1234
(default primary access code).
Note
You don’t have to program these settings in order. Press BYPASS repeatedly to display the desired setting.To jump directly to a system setting, enter its two-digit number (table D.6 in appendix D) instead of pressing BYPASS.
3. Press COMMAND to display _ _ _ _.
4. Enter the desired new four-digit primary access code (0001 to 9998).
Note
See table D.6 in appendix D for access code number de­faults and restrictions.
5. Wait 5 seconds or press COMMAND to set the new code. OK is displayed.
6. Press BYPASS to display 01 - ARM CODE **** (the first blank default secondary access code).
7. Press COMMAND to display _ _ _ _.
8. Enter the desired new four-digit secondary access code (0001 to 9998).
Note
See table D.6 in appendix D for access code number de­faults and restrictions.
Note
See table D.6 in appendix D for access code number de­faults and restrictions.
To delete a secondary or arm/disarm code, enter the same number as the primary code.
13. Wait 5 seconds or press COMMAND to set the
new code. OK is displayed.
14. Repeat steps 10–13 for the remaining secondary and arm-disarm access codes 03 though 23.
15. Press BYPASS to display 53 - ES LOW 50 (default Energy Saver Module low temperature setting).
16. Press COMMAND to display _ _.
17. Enter the desired two-digit ESM low temperature setting (45–89° F).
18. Wait 5 seconds or press COMMAND to set the new temperature. OK is displayed.
19. Press BYPASS to display 54 - ES HIGH 90 (default Energy Saver Module high temperature setting).
20. Press COMMAND to display _ _.
21. Enter the desired two-digit ESM high tempera­ture setting (46–90° F).
22. Wait 5 seconds or press COMMAND to set the new temperature. OK is displayed.
23. Press BYPASS to display 77 - QUIET OFF (default Quiet setting).
24. Press COMMAND to change the current quiet setting to OFF or ON. OK is displayed.
25. Press BYPASS to display 88 - DOWNLOAD OFF (default downloader setting).
26. Press COMMAND to change the current down­load setting to OFF or ON. OK is displayed.
27. Press BYPASS to display 99 - EXIT.
28. Press COMMAND to exit user-programmable system settings. Good bye is announ ce d an d 1- OFF is displayed.
To delete a sec ond ar y or arm /di sa rm code , en te r the sa me number as the primary code.
9. Wait 5 seconds or press COMMAND to set the
new code. OK is displayed.
10. Press BYPASS to display 02 - ARM CODE ****
(the second blank default seconda ry acces s code).
11. Press COMMAND to display _ _ _ _.
12. Enter the desired new four-digit secondary access code (0001 to 9998).

The Duress Code

The optional duress code (if enabled) lets a system user send a silent alarm report to the central monitor­ing station by entering any programmed access code, with the last two digits reversed. You don’t have to enter a specific duress code. For example, if the pri-
19
Page 24
Programming the Panel
mary access code is 1234, the duress code is automat­ically 1243.
Caution
Since the use of duress access codes often result in false alarms due to ke ystrok e err ors, it is stron gly re comme nded that the duress access code remain disabled (off). Enable only if absolutely necessary. If duress access codes are needed, their use in conjunction with the Interrogator 200 Audio Verification Module is high ly recommended to reduce false alarms and accidental disp atches.
Note
Upper Sensor number 86 (Dur ess Alarm) mus t be on to en­able the duress alarm. Upper sensor 86 defaults to off.
Although the panel will not allow access codes with the same last two digits to be programmed through the touch­pad, they are allowed using the CS-4000 or Downloader. Access codes with the same last two digits will duress alarm repo rt.
not
send a

Adjusting the Alphanumeric Touchpad Display Brightness

The alphanumeric touchpad vacuum fluorescent (blue/green) display brightness and LCD (silver/ black) display background brightness is adjustable. (Display brightness on touchpads having LED (red) type displays is not adjustable.)
To change display brightness:
Press and hold the 1, 2, 3, or 4 touchpad button for the desired brightness level.
Once a dimmed level is set, pressing any button mo­mentarily returns the display to full brightne s s.
Requesting CS-4000/Down­loader Programming
Although most information can be programmed from the panel, some optional information must be pro­grammed remotely from the central station CS-4000 or Downloader. Use the information you recorded in appendix D, table D.9 to inform the central station of
your installation’s special programming require­ments.
To set up for remote CS-4000 Central Station pro­gramming:
1. Contact your central station and ask the operator to program the panel for the values you recorded in appendix D, table D.9.
2. Give the operator the panel’s account number and the phone number of the premises, and ask them to call back immediately.
3. Hang up the phone.
4. When the phone rings, enter ACCESS CODE + 8 at the alphanumeric touchpad. The display reads 8 - PHONE TEST and communication will start.
5. When the central station releases the panel, 1 - OFF is displayed. The operator may call you to discuss the programming.
Note
Feature number F33 (Downloader Access Enable) or user­programmable system setting 88 (Download Enable) must be set to on in ord er for remot e downloade r programming t o be enabled. These are two different ways to change the same value, which defaults to off.
To initiate an ITI ToolBox download session:
1. Contact your download station and ask the oper­ator to prepare to download to the panel.
2. In PROGRAM MODE, enter the phone number of the downloader as the panel primary phone number.
3. Program the desired panel account number.
4. Make sure feature number F33 (Download Access Enable) is on. F33 defaults to off.
5. Exit PROGRAM MODE.
6. Enter ACCESS CODE + 8 at an alphanumeric touchpad.
7. The display reads 8 - PHON E TEST, the panel speaker and all interior sirens sound one long beep, and the speaker announces Phone test is on.
8. When the panel completes the test, the system returns to level 1 and the speaker announces Sys- tem phone test is OK. Alarm system is OFF.
9. If the panel announces Phone test failure, or Sys- tem phone test is invalid, call the downloader sta­tion to verify th e Downlo ader phone number and that the Downloader is set up properly.
20
Page 25

Installing Line Carrier Devices

This section describes how to install the following line carrier wireless devices:
Wireless Interior Siren (WIS)
X-10
Notes
The Class II Line Carrier Powe r Transfo rmer ( 60-678 ) is re­quired for line carrier device operation.
The operation o f the la mp mod ule is f or supp lemen tary pur­poses only.
Lamp Module

Installing and Programming the Wireless Interior Siren (WIS)

Installing and programming the Wireless Interior Si­ren (WIS) includes the following:
Setting the WIS DIP switches and installing the battery
Connecting an external siren to the WIS
Programming the WIS house code

Setting the WIS DIP Switches and Installing the Battery

A 9V backup battery (not included) powers the WIS during an AC power failure. The battery type can be alkaline, lithium, or NiCd. When backup battery volt­age gets low, the WIS sounds a single beep every 60 seconds until the battery is replaced.
To set DIP switches and install the backup batter­ies:
1. Remove the battery cover on the back of the WIS as shown in figure 61.
Installing Line Carrier Devices
TERMINALS FOR WIRING OPTIONAL HARDWIRE EXTERIOR SIREN (13-046)
BATTERY COMPARTMENT
(DIP SWITCHES INSIDE)
Figure 6 WIS Battery Cover Location
8557G21A.DS4
2. Set DIP switches as appropriate (see below).
DIP Switch 1—Battery Type
OFF—Install an alkaline or lithium type battery.
ON—Activates a trickle charge circuit for use with a NiCd battery.
WARNING! Never turn on DIP switch 1 when using an alkaline or lithium battery. Personal injury and equipment damage may result if these batteries are recharged, short-cir­cuited, punctured, or discharged at higher than accept­able rates.
DIP Switch 2—External Siren Delay
OFF—External siren terminals activate immedi­ately during an alarm condition. Use this setting when the siren connected to the external siren termi nals is located in side the pre­mises.
ON—External siren terminals activate 15 sec­onds after an alarm condition occurs. Use this setting when the siren connected to the external siren terminals is located outside. This helps prevent disturbing neighbors in cases of ac­cidental alarms that last fewer than 15 seconds.
DIP Switches 3 and 4—Status Tones
3 and 4 OFF—The WIS internal piezos and external siren do not produce any status tones. Use this setting wh en the WIS is installed in or near sleeping are as.
3 ON, 4 OFF—The WIS internal piezos produce normal-volume status tones. Use this setting when the WIS is installed in areas where status tones need to be heard.
21
Page 26
Installing Line Carrier Devices
3 OFF, 4 ON—The WIS internal piezos and external siren produce high-volume status tones. Use this setting when status tones need to be heard in remote areas, inside and out side of the premises.
Caution
Never turn on both DIP switches 3 and 4; doing so ma y per­manently damage the WIS.
3. Connect the battery to the battery clip and insert the battery into the compart m en t.
4. Replace the battery cover.

Connecting an External Siren to the WIS

Figure 7 shows how to connect the Hardwire Exterior Siren (13-046) to the WIS terminals. These terminals activate for alarms only and provide 100 mA maxi­mum current at 6 VDC.
Caution
Only the Hardwire Exter ior Siren (13-046) ca n be connected to the WIS terminals. Other sirens may draw more current than the WIS can provide and can cause permanent dam­age to the WIS.

Programming the WIS House Code

1. Plug the WIS into an outlet that is not controlled by a switch.
2. Press CODE + 1 on the alphanumeric touchpad.
3. The WIS sounds one beep and the WIS LED flashes, indicating the WIS received the signal from the panel.
Note
If WIS DIP switches 3 and 4 are set to OFF, no beep will be heard. You must cause an alarm for the WIS to sound.
4. If the WIS does not respond, unplug it and dis­connect the batte ry. Wait at least 30 seconds, and then reconnect the battery and repeat steps 1 and
2. If the WIS still does not respond, proceed to appendix B, “Troubleshooting.”
5. To permanently mount the WIS, unplug it and remove the outlet cover screw.
6. Plug the WIS into the outlet and secure it with the outlet screw.
WARNING! Use extreme caution when securing the WIS to a metal outlet cover. You could receive a serious shock if the metal outlet cover drops down onto the prongs of the plug while you are securing the WIS and cover to the outlet box.
OBSERVE
BATTERY
COMPARTMENT
(DIP SWITCHES
INSIDE)
Figure 7 Wiring the Hardwire Exterior Siren to the WIS
+
HARDWIRE EXTERIOR SIREN (13-046) 100 mA MAXIMUM DRAW
POLARITY
8557G23A.DS4
22

Installing X-10 Lamp Modules

When installing X-10 Lamp Modules:
• Use only incandescent lamps.
• Do not plug X-10 Lamp Modules into outlets con-
trolled by a switch.
• Do not use extension cords to connect several
lamps to one module.
Caution
Use X-10 X-10 trolled during an alarm.
Lamp
Appliance
Modules to control lig ht fixtures. Do n ot use
Modules. Appliance Modules are not con-
Page 27

Testing the System

To install X-10 Lamp Modules:
1. Plug the lamp cord into the bottom of the lamp module.
2. Plug the module into a lower AC outlet.
3. Refer to table D.5 in appendix D for the house code you programmed into the panel, and then find the letter that corresponds to that house code from table C.3 in appendix C. Each letter setting represents 16 possible panel hous e code s. Fo r example, house code 113 corresponds with “B” on the X-10 Lamp Module’s house dial.
4. Set the house dial on the module to the appropri­ate letter.
5. Set the unit number dial from 1 to 9 as shown in table C.4 in appendix C.
Note
X-10 Lamp Module unit numbers 1 and 2 have special sys­tem functions: unit 1 provides entry and exit lighting, and unit 2 provides visual ind icat io n of armin g le vel. X-10 App li­ance Modules as signed to unit s 3–9 can be individ ually con­trolled from the touc hp ad and are automatica lly t ur ned off during police alarms.
Testing the System
This section describes how to perform the following test procedures:
• Testing sensors
• Testing the Energy Saver Module
• Testing the Hardwire Input Module
• Testing the X-10 Lamp Modules
• Testing phone communication
• Testing central station communications
You should test the system after installing, after ser­vicing, and after adding or removing devices from the system. Refer to the troubleshooting chart in appendix B for troubleshooting help.

Testing Sensors

Note
While the sensor test is a valuable installation and service tool, it only tests sensor operation for the current conditions. You should perform a sensor test after any change in envi­ronment, equipment, or programming.
1. Set the panel PROGRAM/RUN switch to RUN (up) and attach, cl ose, a nd sec ure t he pan el cov er.
2. Place all sensors in their secured (nonalarm) state.
3. Enter ACCESS CODE + STATUS + 9 (dealer sensor test) at an alphanumeric touchpad.
4. The speaker announces “Sensor test is on,” inte­rior sirens and speakers sound one long beep, and the display reads 9 - SENSOR TEST.
5. Trip each sensor one at a time.
6. Interior sirens and speakers sound transmission beeps as each sensor is tripped. Each beep repre­sents one data round.
7. Count the number of transmission beeps and refer to table 3 for minimum requirements.
8. After the beeps, [sensor #] OK is displayed con- firming the sensor number tested. If the system does not respond, or if the sensor does not meet the minimum transmission beep requirements, refer to the “If a Sensor Fails the Sensor Test” section.
9. Press the STATUS button when you think all sensors are tested. The system announces any untested sensor numbers. If all sensors have been tested, the alphanumeric touchpad displays ALL SENSOR OKAY and the speaker announces “Sensor test is on. All sensor test okay.
10. Test all untested sensors. The system stays in sensor test for 15 minutes, preservi ng the list of untested sensors. After 15 minutes the panel dis­arms to level 1, aut omatically.
11. Enter ACCESS CODE + STATUS + 9 while the system is still in sensor test if you need more time to complete the sensor test.
12. Enter ACCESS CODE + 1 to exit sensor test.
13. The system disarms to level 1, and the speaker announces “Alarm system is off.”
We recommend that you test the sensors after all pro­gramming is completed and whenever a sensor-relat­ed problem occurs.
Note
While in dealer sensor test, a sensor will not beep unless there is at least 10 dB of wireless signal margin.
23
Page 28
Testing the System
Table 4 Minimum Transmission Beeps
Type of Sensor
Wireless Intrusion Sensors 7–8 beeps Wireless Smo ke & Heat Sensors 7–8 beeps Wireless Environmental/Panic Buttons 7–8 beeps Hardwire Loops 1 Panel Emergency Buttons 1
Number of
Beeps

If a Sensor Fails the Sensor Test

If sirens do not beep when a sensor is tripped, use an ITI RF Sniffer (60-401) test tool to verify that the sen­sor is transmitting. Constant beeps from the RF Sniff­er indicate a runaway (faulty) sensor. Remove the sensor’s battery and replace the sensor.
If possible, locate sensors within 100 feet of the panel. While a transmitter may have a range of 1,000 feet or more out in the open, the environment at the installa­tion site can have a significant effect on transmitter range. Sometimes a change in sensor location can help overcome adverse wireless conditions.
To improve sensor communication, you can
• reposition the sensor,
• relocate the sensor,
• if necessary, replace the sensor.
To reposition a sensor:
1. Rotate the sensor and test for improved sensor communication at 90 and 180 degrees from the original position.
2. If poor communication persists, relocate the sen­sor as described as follows.
To relocate a sensor:
1. Test the sensor a few inches from the original position.
2. Increase the distance from the original position and retest until an acceptable locatio n is found.
3. Mount the sensor in the new location.
4. If no location is acceptable, replace the sensor.
To replace a sensor:
1. Test a known good sensor at the same location.
2. If the transmission beeps remain below the mini­mum level, avoid mounting a sensor at that loca­tion.
3. If the replacement sensor functions, contact ITI for repair or replacement of the problem sensor.

Testing the Energy Saver Module (ESM)

Note
Upper sensor number 88 must be on to ena ble the Energy Saver Module.
To test the Energy Saver Module:
1. Press STATUS + STATUS to display the sys­tem status, ENERGY SAVER OFF, and the present TEMPERATURE ##. The temperature displayed (and/or announced) should match the house thermostat. If the temperatures do not match, refer to “Programming the Energy Saver Module Freeze and Set Temperatures” section or the “Troubleshooting” table in appendix B.
2. Press COMMAND + 5 to turn the energy saver function on. The display will indicate ENERGY SAVER ON and the ESM relay will click once.
3. Press COMMAND + 5 again to turn the energy saver function off. The display will indicate
ENERGY SAVER OFF.
Note
There is a 5-minute de lay after the Ene rgy Saver Module re ­turns control to the furnac e/AC before it will override the fur ­nace/AC again.
If the red ESM LED is not flashing continuously, set the pan­el PROGRAM/RUN switch to RUN and turn off the panel power switch. Verify th at all wiring is correct and th at all bus devices (including hardwire touchpads) are set with differ­ent unit numbers.
Whenever the ESM unit number is changed, you must turn off the panel power switch, turn it back on, and then enter the program mode for the panel and ESM to communicate successfully.
24
Page 29
Testing the System

Testing the Hardwire Input Module (HIM)

To test the optional Hardwire Input Module:
1. Verify that all wiring at the panel and the HIM are correct.
2. Turn on the panel power switch.
Note
If the red HIM LED is not flashing continuously, set the panel PROGRAM/RUN switch to RUN and turn off the panel pow­er switch. Verify that all wiring is correct and that all bus de­vices (including hardwire touchpads) are set with different unit ID numbers.
Whenever the HIM unit ID number is changed, you must turn off the pane l power switch , turn it bac k on, and the n en­ter the program mode for th e pane l an d HI M to commu ni­cate successfull y.
If the system uses hardwire sensors only, turn off upper sensor 94 (Receiver Failure) in the panel.
3. Set the panel’s PROGRAM/RUN switch to PROGRAM. If the alphanumeric display continues to read 1- OFF and the 1 is flashing, you must enter the in­stall code (four digit install access code) to get the panel into the program mode. The alphanumeric display should read PRO- GRAM MODE and the red HIM LED should be flashing continuously, indic atin g suc cess ful bus communication with the panel.
4. Set the panel’s PROGRAM/RUN switch to RUN and refer to the “Testing Sensors” section for testing hardwired sensors connected to the HIM.

Testing the Hardwire Output Module (HOM)

To test the optional Hardwire Output Module:
1. Verify that all wiring at the panel and the HOM is correct.
2. Turn on the panel power switch.
3. Set the panel’s PROGRAM/RUN switch to PROGRAM.
If the alphanumeric display continues to read 1- OFF and the 1 is flashing, you must enter the in­stall code (four digit install access code) to get the panel into the program mode. The alphanumeric display should read PRO- GRAM MODE and the red HOM LED should be flashing continuously, indicating successful bus communication with the panel.
4. Set the panel’s PROGRAM/RUN switch to RUN.
5. Activate each of the programmed system trigger­ing events to verify correct HOM output response.
Note
If the red HOM LED is not flashing continuously, set the panel PROGRAM/RUN switch to RUN and turn off the pan­el power switch. Verify that all wiring is correct and that all bus devices (inclu ding har dwire touc hpads ) are set wit h dif­ferent unit ID numbers.
Whenever the HOM unit ID number is changed, you must turn off the panel powe r switch, tur n it back on, and then en­ter the program mode for the panel and HOM to communi­cate successf ully.

Testing the X-10 Lamp Modules

Refer to table C.4 in appendix C for X-10 lamp and appliance module control operation.
To test the X-10 Lamp Modules:
1. Press COMMAND + 0 repeatedly to turn all lights on and off together. Appliance modules, if any, are all turned off by pressing COMMAND + 0 but are not all turned on this way.
2. Press BYPASS + 1 repeatedly to turn light 1 on and off.
3. Repeat step 2 for remaining assigned lamp and appliance module unit numbers.
4. Press ACCESS CODE + 3 to arm the system to Level 3-Away. Unit 1 light should turn on and stay on for 5 minutes. Unit 2 light should blink three times to indicate the arming level. All remaining lights should be unaffected.
5. Press ACCESS CODE + 1 to disarm the system. If Unit 1 light was on for an entry or alarm, it
25
Page 30
Testing the System
will turn off in 5 minutes. Unit 2 light should blink once to indicate arming Level 1-Off. All remaining lights should be unaffected.
6. Lights should turn on and remain on during fire and auxiliary/medical alarms and flash during a police or an intrusion alarm.

Testing Phone Communication

Perform a phone test to check the phone communica­tion between the panel and the central s tation.
To perform a phone test:
1. Enter ACCESS CODE + 8 at an alphanumeric touchpad.
2. The display reads 8 - PHONE TEST, the panel speaker and all interior sirens sound one long beep, and the speaker announces Phone test is on.
3. When the panel completes the test, the system returns to level 1 and the speaker announces Phone Test is OK. Alarm system is OFF.
4. If the panel announces Phone test failure, pro- ceed to the following instructions.
To test communication with the central station:
1. Call the central station and tell the operator that you will be testing the system.
2. Arm the system.
3. Test each of the touchpad and wireless panic but­tons and trip at least one sensor of each type— fire, intrusion, etc.—to verify that the appropriate alarms are working correctly.
4. If an Audio Verification Module is installed, ver­ify that it is operating correctly and that the cen­tral station can both listen-in and talk-back through it.
5. When you finish testing the system, call the cen­tral station to verify that the alarms were received.
Note
If you experience trouble commu nicating with the central station (or Downloader), ver ify the panel’s primary pho ne number and also that panel feature number F33 (Down load­er Access Enable) is turned on. Also verify panel feature number F43 (Demo Kit Mo de) is turned off (def ault sett ing). If F43 is on, the account number defaults to “UD-EMO” to let the central station know that the panel is in the demo kit mode of operation a nd that special demo d ef aults and spe­cial alarm handling is in force.
Displaying the Panel
If the phone test fails:
1. Check that the panel is plugged into the RJ-31X/ CA-38A phone jack.
2. Enter ACCESS CODE + 8 again.
3. If the phone test fails again, check the phone number programmed into the panel.
4. If the phone test fails again, check the phone con­nection wiring.

Testing Central Station Communication

After performing sensor and phone tests, check that the system is reporting alarms successfully to the cen­tral station.
Version Code
After testing and troubleshooting the system (as out­lined in this section and in appendix B) you may re­quire Technical Support assistance. To precisely identify the panel hardware and software to support personnel, you can display the panel hardware/soft­ware version code.
To display/announce the panel version code:
1. Set the panel RUN/PROGRAM switch to RUN.
2. Enter primary ACCESS CODE + STA TUS + 7.
The alphanumeric touchpad will display YYY*XXX and System YYY Level XXXX will be announced. YYY represents the panel family (hardware) product code and XXXX represents the EEPROM (software) version code.
26
Page 31

Appendix A: Command Summary

Appendix A: Command Summary
This appendix contains a summary of all system user commands and what each command does. For operating command details refer to the Security and Home Automation Owner’s Manual.

User Operating Command Summary

Table A.1 provides a description of all commands for operating the system. For commands that require an access code, use either the primary or secondary access code unless otherwise indicated. While these are called user operating commands, you may need to use some or all of these commands during the installation and program­ming process. In the table, CODE represents the four-digit access code (default is 1234).
Table A.1 Summary of User Operating Commands
Action Command Short Command Voice Message Confirmation
Disarm to level 1-Off CODE + 1 Arm to level 2-Sta y CODE + 2
Arm to level 2, no delay
Arm to level 2, indi­rect bypass
Arm to level 3-Awa y CODE + 3 Arm to level 3, no
delay Arm to level 3, indi-
rect bypass Direct bypass
Unbypass ‡ CODE + BYPASS + [sensor #] Energy Saver Mod-
ule on/off Chime on/off CODE + 7 COMMAND + 7
Phone test on CODE + 8 Sensor test on CODE + 9 All lights on/off CODE + 0 COMMAND + 0
Individual lights on/ off
Review alarm mem­ory
CODE + 2 + 4
CODE + 2 + BYPASS
CODE + 3 + 4
CODE + 3 + BYPASS
CODE + BYPASS + [sensor #]
CODE + 5 COMMAND + 5
BYPASS + n (n= 1-9)
CODE + STATUS + 5 COMMAND +
COMMAND + 2 * Alarm system is on, level 2. COMMAND + 2 + 4 * Alarm system is on, level 2, no delay.
COMMAND + 3 * Alarm system is on, level 3. COMMAND + 3 + 4 * Alarm system is on, level 3, no delay.
STATUS
Alarm system is off.
Alarm system is on, level 2. Sensor [sensor #] bypassed.
Alarm system is on, level 3. Sensor [sensor #] bypassed.
Sensor [sensor #] bypassed. Sensor [sensor #] okay. Energy Saver is on/off.
On, off. Phone test is on.
Sensor test is on. On, off. [Unit #] on/off.
Alarm memory is okay, or Sensor [sensor #] [alarm name] alarm memory.
Review short panel status
STATUS
Alarm system is [status message].
(continued)
27
Page 32
Appendix A: Command Summary
Table A.1 Summary of User Operating Commands (Continued)
Action Command Short Command Voice Message Confirmation
Review long panel status
CODE + STATUS + 1 STATUS + STATUS
Hello alarm system is... (see Owner’s
Manual for possible messages)...Good-
bye.
Panel Version CODE + STATUS + 7
Adjust alphanumeric displa y brightness
Press and hold buttons 1–4 (1–full dim, 4–full bright)
System yyy
(EEPROM code)
(product code)
Level xxxx
* Feature number F37 (Quick Arming) must be on to enable short arming commands. This short command only works
when arming to a higher level.
This command only works if the sensor you are bypassing is active in the cu rrent security le vel.
‡ This command only works when upp er sen so r 87 is off an d you are unbypas si ng a sen so r tha t is already bypass ed .

System Settings (User-Programming) Command Summary

Table A.1 provides a description of all user-programming commands. For commands that require an access code (CODE), use the primary access code (default is 1234).
To enter the user-programming mode, press CODE + STATUS + 8. The system will announce System memory open. Press BYPASS or STATUS buttons to scroll through the list of system settings. Proceed to any of the desired actions listed in table D.6.
To exit user-progamming mode at any time, press BYPASS + 99 + COMMAND + COMMAND. Or, wait 1 minute—system will automatically announce Good-bye and return to the normal mode of operation..
Table A.2 Summary of System Settings (User-Programming) Commands
Action Command Display/Voice Message Confirmation
Enter new primary access code 00
Enter new secondary access code (01-04)
Enter new arm/dis­arm code 05–23
Enter new Energy Saver Module low temperatur e setting
Enter new Energy Saver Module high temperatur e setting
Turn quiet exit on or off
Turn download enable on or off
00 + COMMAND + COMMAND + [new CODE] + COMMAND
[01–04] + COMMAND + COM­MAND + [new CODE] + COM­MAND
[05–23] + COMMAND + COM­MAND + [new CODE] + COM­MAND
53 + COMMAND + COMMAND + [new low temp.] + COMMAND
54 + COMMAND + COMMAND + [new high temp.] + COM­MAND
77 + COMMAND + COMMAND
88 + COMMAND + COMMAND
[new primary access code], okay.
[new secondary access code], okay.
[new arm/disarm access code], okay.
[new ESM low temperature], okay.
[new ESM high temperature], okay.
[On or off]
[On or off]
28
Page 33

Appendix B: Troubleshooting

This appendix contains a summary of system troubleshooting suggestions.
Table B.1 Troubleshooting System Problems
Feature Problem Solution
Access Code
Customer cannot remember access code(s).
1. Check your records to see if you have the customer’s access code(s) on file.
2. If panel is monitored, trap the panel and read the access code(s) from the CS-4000 or read the access code(s) from the Downloader.
3. If panel is not monitored, clea r memory and reprogram the pane l locally.
Installer cannot remember install code.
1. Check your records to see if you have the install code on file.
2. If panel is monitored, trap the panel and read the access code(s) from the CS-4000 or read the access code(s) from the downloader.
3. If the panel is not monitored and has no access to downloading, clear memory and reprogram the panel locall y.
Appendix B: Troubleshooting
Some access codes do “strange things.”
Arming/Disarming
System won’t arm.
Batteries
Touchpad indicates
Touchpad indicates
1. Codes containing the number 6 are reserved. 6 is used for phone sensor bypassing.
2. Codes 7777, 8888, and 9999 are reserved for phone panic alarms.
3. Access code’s last two digits must not be the same for correct duress code operation. (See duress code feature in this table.)
1. If arming to level 2, ma ke sure all monitored perimeter doors and windows are closed.
2. If arming to level 3, make sure all perimeter and interior sensors are closed.
3. Press STATUS for an indication of the problem.
CPU low battery
Check the panel backup batter y and connections and repl ace if nec­essary. Also, refer to the panel power LED section in this table.
[sensor #] trou ble
Replace the indicated sensor’s battery.
and/or
and/or
System battery failure
Sensor [sensor #] low battery
is heard.
is heard.
29
Page 34
Appendix B: Troubleshooting
Table B.1 Troubleshooting System Problems (Continued)
Feature Problem Solution
Bypass
Touc hpad indicates
System cancels sensor bypass when you try to arm to level 2 or 3.
Central Station Reporting
Central station is not receiving reports from panel.
Duress Code
Optional duress code is not working.
Fail
and/or
Invalid
is heard when you attempt to bypass a sensor.
Sensor may already be bypassed or you are trying to bypass a 24­hour sensor that cannot be bypassed or a sensor that is not active in the current security level.
Arm to the d esired level before bypassing a sensor.
1. Check that the DB-8 Cord is plugged into the pane l phone ja c k and into the RJ-31X/CA-38A Jack.
2. Check for proper RJ-31X/CA-38A Jack to phone line wiring.
3. Verify with the central station operator that the correct receiver line phone number is programmed into the panel. Reprogram the phone number and retes t, if necessary. 4 Ve rify th at the correct phone format (ITI or 4/2) is being used.
5. Replace faulty RJ-31X/CA-38A Jack.
6. Replace faulty DB-8 Cord.
7. Check that the pr emis es phone line is workin g.
8. Perform a phone test.
1. Make sure last two digits of access code are not the same. (See access code feature in this table.)
2. Check that upper sensor 86 (duress alarm) is on.
False Alarm
Alarm is being sent by mist ake.
Enter ACCESS CODE + 1 immediately to cancel the alarm. This com- mand bypasses the alarm if done within 15 seconds after activation (feature nu mbe r F0 6 [Dia le r Ab ort] must be on). The sys te m will announce alarm bypassed and report will not be sent to the monitor­ing station.
Note
Fire alarms and duress detections cannot be bypassed.
Hardwire Alphanumeric Touchpad
Touchpad display seems “stuck” in the program mode.
Check that panel PROGRAM/R UN switch is set to RUN (up).
Touc hpad displays incorrectly or displays
1. If panel has been preprogrammed with an install code, enter the four-digit install code at a working touchpad or from a telephone .
2. Check for har dwir e bus address confilct (two device s having the same device address).
3. Check for out-of-range device address number. Should be 000–
007.
DA ###
and does not respond to buttons.
30
Page 35
Table B.1 Troubleshooting System Problems (Continued)
Feature Problem Solution
Hardwire Alphanumeric Touchpad (Continued)
Appendix B: Troubleshooting
Touchpad displays
Touchpad appears “dead” (no display or response to buttons).
Hardwire Output Module
LED is off (not blinking).
LED stays on.
**********
1. Reset the touchpad by switching into and out of program mode. Switch the panel PROGRAM/RUN switch from RUN to PROGRAM. Enter the f our-dig it in stall c ode if p anel h as been prepro gr ammed wit h one using a working touchpad or telephone. Switch the panel PRO­GRAM/RUN switch bac k to RUN again.
2. Check for har dwir e bus miswiring.
1. Check that the wiring connector is plugged into the back of the touchpad.
2. Check for har dwir e bus miswiring, op en s, or shorts.
3. Check panel fuse F2.
1. Check HOM and panel fuses.
2. Check wiring at HOM and panel.
3. Check that HOM unit numb er setting is differe nt from all other con­nected bus devices.
4. Check for proper panel/HOM initialization after changing unit num­bers.
’ and does not respond to buttons.
1. Reinitialize panel and HOM by turning panel power off and on.
2. HOM circuit failure. Replace HOM.
LED blinks but outputs don’t activate.
1. Check panel/HOM programmi ng .
One output never activates.
1. Check panel/HOM programmi ng .
2. Check that the po in t (HO M ou tput) programmed trigger event actu­ally occurs.
3. Check wiring at HOM terminals and connected device.
Output(s) activ a te s on ly mome n taril y.
1. Check that the panel/HOM point progr a mmin g (HOM outpu t) uses the correct re sponse configu ration.
Output(s) activates randomly.
1. Check HOM and panel fuses.
2. Check wiring routing and length between panel and HOM.
3. Check that HOM unit numb er set ting is different from all other con­nected bus devices.
Hardwire Output Module (Continued)
HOM tamper input is inoperable.
31
Page 36
Appendix B: Troubleshooting
Table B.1 Troubleshooting System Problems (Continued)
Feature Problem Solution
1. Some panels and panel ve rsions do not “read” the HOM’s built-in tamper input status. Conn e ct the HOM tamper switch to a pa ne l or HIM zone input.
One output stays activated.
1. Check to see if the point is pro grammed f or a 3-minute “on” time and if the triggering event for the point is repeatedly resetting the 3­minute timer.
2. Output may have failed or been overloaded. Reprogram to use a different (unused) output.
Hardwire Siren
Exterio r sirens are not pr oducing alarm sounds.
1. Check for 12 to 22 VDC between panel terminals 3 and 4 and for 12 VDC between terminals 4 and 12.
2. Check panel fuses F1 and F2.
3. Check for correct wiring at the siren and panel terminals.
4. Check for required jumper wire between panel terminals 5 and 12.
Exterior sirens produce status sounds.
Interior sirens are not producing sounds.
Hardwire Zones
Panel does no t res po n d to ha rd wire zone input.
Touc hpad indicates
Check for correct wiring at the siren and panel terminals.
1. Check for 12 VDC between panel terminals 17 and 18 with siren on.
2. Check panel fuses F1 and F2.
3. Check for correct wiring at the siren and panel terminals.
4. Make sure that F11 (Interior Siren Sounds Disable) feature is off.
1. Check that zones are programmed into panel and add if missing.
2. Make sure that z o ne is in a restoral-re q uired group or make sure that system is armed to active level before tripp ing sen sor.
3. If optional HIM zone, check that the HIM LED is blinking to show communication with panel .
Note
Panel hardwire zones are ignored for 1 minute following power-on (HIM zones are not ignored for this period).
[sensor #], trouble
1. Check that the 4.7K ohm end-of-line resistor is correctly installed in the zone loop circuit.
2. Check normally open (N/O) circ u it for a break in the wires.
3. Check normally closed (N/C) circ uit for a short in the wires.
and/or
Sensor [sensor #], trouble
is heard.
Lights
32
Light fixture using X-10 Lamp Module does not work.
Page 37
Table B.1 Troubleshooting System Problems (Continued)
Feature Problem Solution
See X-10 Lamp Modules feature in this table.
Panel
Panel does not power up. Panel LED is off and alphanumeric touchpad display is dark.
1. Check that panel power switch is on.
2. Check the AC circuit breaker to be sure the circuit is live.
3. Check that the backup battery is installed correctly, the battery wires are connected, and the AC power transformer is plugged in.
4. Check for proper panel and transformer wiring.
5. Measure the incoming AC voltage at th e pa nel terminals. Should read from 16 to 18.5 VAC at panel terminals 1 and 2.
No incoming AC voltage at panel terminals 1 and 2.
1. Unplug the AC power transformer and disconnect the wire s from the transformer and the panel.
2. Check transfomer to panel wire for short or open circuits.
3. Plug in the transformer and check for 16.5 VAC at the transformer unconnected terminals. If zero (0) volts, replace the transformer.
Appendix B: Troubleshooting
Panel power LED is on constantly, display indicates
Battery failure.
1. Check that the backup battery is installed correctly, the battery wires are connected, and the AC power transformer is plugged in.
2. Measure the incoming AC voltage at th e pa nel terminals. It should read from 16 to 18.5 VAC at panel terminals 1 and 2.
3. Remove the backup battery power by disconnecting the battery’s red (positive) wir e.
4. Check for 13.5 to 13.9 VDC battery charging voltage between panel terminal 4 (GND) and the disconnected battery red wire . If the charging voltage is not within range, call Technical Services.
5. Check for 11.5 to 13.9 VDC battery voltage between the backup battery’s spade lugs. If the battery voltage is not within the recom­mended range, replace the battery. Note When the panel is running a backup battery test, the reading at the connected battery can range from 11.4 to 13.7 VDC. The panel auto­matically runs a backup battery test under the following conditions: (1) on initial power-up. (2) during sensor test (not dealer sensor test), (3) once every minute when backup battery has failed, (4) once every 24 hours, at the programmed STIME.
6. Restore the ba ck up batt ery pow er by recon nectin g the ba ttery’ s red wire.
Note
While the AC po w er tran sf ormer is plug ged in, the pan el automati cally charges the bat tery. While the battery is chargin g f or t he first time it is normal for the system to indicate take a number of hours depending on the battery’s initial charge. Once the battery reaches 12.5 VDC (full charge as measured while in battery test), the arming level stops flashing. If the trouble condition persists after 24 hours, replac e the backup bat tery.
CPU Low Battery
or voice sounds
System battery fail ur e
. This can
Panel (Contin ued)
33
Page 38
Appendix B: Troubleshooting
Table B.1 Troubleshooting System Problems (Continued)
Feature Problem Solution
Phones
Panel power LED is flashing, and after pressing ST ATUS the touchpad indicates
power failure
Loss of dial tone on premises phones after wiring the RJ-31X Jack or connecting the DB-8 Cord.
. (Panel continues to operate from backup battery.)
1. Check the AC circuit breaker to be sure the circuit is live.
2. Check for proper panel and transformer wiring.
3. Check that the transformer is plugged into a nonswitched outlet and secured with the provided screw.
4.Check that the transformer is supplying AC to the panel. (Trans­former internal fuse may be blo wn .)
WARNING!
Be careful when securing the transformer to an outlet with a metal cover. Hold the cover tightly in place. You could receive a serious shock if the metal outlet cover drops down onto the prongs of the plug while you are securing the transformer and cover to the outlet box.
1. Wait 2 minutes and try again. The panel may be busy trying to report to the CS-4000.
2. Check the RJ-31X Jack’s wiring.
3. Check the panel connection to the DB-8 Cord.
4. Replace the RJ-31X Jack.
5. Replace the DB-8 Cord.
6. Perform a phone test after troubleshooting the phone line.
AC
Sensor
Smoke Sensor
Constant dial tone, preventing dial out on premises phones.
Polarity-sensitive phones exist on the premises. Reverse the phone wires connected to the brown and gray wire terminals on the RJ-31X Jack.
Phone does not work.
Disconnect the panel DB-8 Cord from the RJ-31 Jack. If the phone still doesn’t work, the system is ok ay and the problem is in the wiring.
Touc hpad indicates
Touchpad indicates
Touchpad indicates heard.
Beeps once every minute.
[sensor #] trouble
Replace the sensor’s cover, if it is off. Trip the sensor.
[sensor #] supervisory
The sensor is not co m m unicating with the panel.
Sensor [sensor #] trouble
Replace the indicated sensor’s battery.
and/or
Sensor [sensor #] trouble
and/or
Sensor [sensor #] failure
and/or
Sensor [sensor #] low battery
is heard.
is heard.
is
Trouble Beeps (see also
34
Batteries are low. Replace all of the smoke sensor batt eries.
Panel
)
Page 39
Table B.1 Troubleshooting System Problems (Continued)
Feature Problem Solution
Press STATUS for an indication of the problem. Doing a status or disarm (level 1) dis- ables the trouble beeps for 10 hours.
Wireless Interior Siren (WIS)
No sound or LED activity from the siren.
1. Check that the panel AC transformer is plugged into an outlet.
2. Check that the WIS is not plug ged into an outlet controlled by a switch. Relocate to a different outlet, if necessary.
3. Program the house code into the panel and set the WIS DIP switches.
4. Check that the panel i s powered by the special two-wire Class II Line Carrier Power Transformer.
5. Make sure that the WIS is on the sa me ele ctrica l ph as e wiring as the AC power transformer. Relocate the WIS to various outlets to identify compatible locations.
6. Move the WIS to a circuit that is not used by any other appliances.
Intermittent siren operation.
Appendix B: Troubleshooting
The WIS beeps once every minute.
Wireless Sensors
The panel does not respond to sensor activity . There are no alarm, chime, or sensor test sounds.
The panel responds intermittently to wireless sensor signals.
1. Check that the WIS is not plug ged into an outlet controlled by a switch. Relocate to an unswitched outlet.
2. Move the WIS to a circuit that is not used by any other appliances.
The WIS may ha ve a low battery. Replace with the appropriate battery based on the setting of DIP switch 1. (ON = NiCd, OFF = alkaline or lithium.)
1. Check that the wireless sensor battery is installed.
2. Check the sensor battery for low voltage. Replace batteries, if nec­essary.
3. Use an RF Sniffer (6 0- 401) to verify that se nsor is transmittin g .
4. Check that th e sens or is pr ogr ammed (learned) in to pa nel memo ry. Learn the sensor, if necessary.
5. Verify that both panel antennas are installed and connections tight.
1. Rotate the sensor posi tion from 90 to 180 degrees.
2. Mount the sensor in a different location.
3. Verify that both panel antennas are installed and connections tight.
Wireless Touchpads
The panel does not respond to wireless touchpad commands.
X-10 Lamp Modules
1. Operate touchpads from different locations to locate areas of inter­mittent operation.
2. Check and/or replace wireless touchpad battery.
3. Program or reprogram the touchpad(s) into the panel.
35
Page 40
Appendix B: Troubleshooting
Table B.1 Troubleshooting System Problems (Continued)
Feature Problem Solution
Light fixtures controlled by the X-10 Lamp Module are not working.
1. Check that the lamp ha s a working bulb and that the lamps switch is on.
2. Confirm the lamp’s operation at a working outlet.
3. Check tha t th e la mps are plug ged into X-10 Lamp Mod ules an d th e X-10 Lamp Modules are plugged into outlets that are not controlled by a switch. Relocat e to non switched outlets, if necessary.
4. Check that the panel is powered by the special two-wire Class II Line Carrier Power Transformer ((60-678).
5. Check that the HOUSE dial on the X-10 Lamp Module matches the house code programmed into the panel.
36
Page 41

Appendix C: Programming Tables

Appendix C: Programming Tables
This appendix contains tables for selecting sensor group numbers and X-10 Lamp and Appliance Module house and unit codes. Table notes appear at the bottom of the table, on the next page.
Ta ble C.1 Sensor Group Characteristics
No. Name Application Alarm Delay Restoral Supervisory
00 Fixed
Panic
01 Portable
Panic
02 Fixed
Panic
03 Portable
Panic
04 Fixed
Auxiliary
05 Fixed
Auxiliary
06 Portable
Auxiliary
07 Portable
Auxiliary
08 Special
Intrusion
09 Special
Intrusion
10 Entry/Exit
Delay
11 Entry/Exit
Delay
12 Entry/Exit
Delay Instant
13
Perimeter Instant
14
Interior Instant
15
Interior Instant
16
Interior Instant
17
Interior Instant
18
Interior
24-hour audible fixed emergency but­tons.
24-hour audible portable emergency buttons.
24-hour silent fixed emergency buttons. Silent Instant
24-hour silent portable emergency but­tons.
24-hour auxiliary sensor, such as Pen­dant Panic or holdup button.
24-hour auxiliary emergency button. Siren shutoff confirms CS report.
24-hour portable auxiliary alert button. Auxiliary Instant
24-hour portable auxiliary button. Siren shutoff confirms CS report.
Special belongings, such as gun cabi­nets and wall safes.
Special belongings, such as gun cabi­nets and wall safes.
Entry and exit doors that require a stan­dard delay time.
Garage doors and entrances that require an extended delay time.
Driveway gates and entrances that require a twice extended delay time.
Exterior doors and windows. Police Instant
Interior doors. Police Follower
Interior PIR motion sensors. * Police Follower
Interior doors. Police Follower
PIR motion sensors. * Police Follower
PIR motion sensors subject to false alarms.
*
*
Police Instant
Police Instant
Silent Instant
Auxiliary Instant
Auxiliary Instant
Auxiliary Instant
Police Instant
Police Standard
Police Standard
Police Extended
Police Twice
*
Police Follower
Extended
(continued)
√ √
√ √ √ √ √ √ √ √ √ √ √ √
√ √
CS
Report
√ √
Chime
Active Levels
1, 2, 3
1, 2, 3
1, 2, 3
1, 2, 3
1, 2, 3
1, 2, 3
1, 2, 3
1, 2, 3
1, 2, 3
1, 2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
3
3
3
Delayed
19
Interior
Interior doors that initiate a delay before going into alarm.
*
Police Standard
3
37
Page 42
Appendix C: Programming Tables
Table C.1 Sensor Group Characteristics (Continued)
No. Name Application Alarm Delay Restoral Supervisory
Delayed
20
Interior Local
Instant
21
Interior Local
Delayed
22
Interior Local
Instant
23
Auxiliary Local
Instant
24
Auxiliary Local
Special
25
Chime Fire 24-hour fire, rate-of-rise heat, and
26
Output
27
Module Output
28
Module
PIR motion sensors that initiate a delay before going into alarm.
24-hour local alarm zone protecting anything that opens and closes.
Same as group 21, plus activation ini­tiates a delay before going into alarm.
24-hour local alarm zone protecting anything that opens and closes. ‡
24-hour local alarm zone protecting anything that opens and closes. Sirens shut off at restoral.
Notify the user when a door is opened. Sounds emit from a local annunciator .
smoke sensors. Hardwire Output Module (HOM) lamp
control or other customer feature. HOM, PIR motion sensor, sound sen-
sor, or pressure mat.
*
*
§
Police Standard
Police Instant
Police Standard
Auxiliary Instant
Auxiliary Instant
Special Chime
*
Fire Instant
Silent Instant
Silent Instant
Instant
√ √
CS
Report
Chime
Active Levels
3
1, 2, 3
1, 2, 3
1, 2, 3
1, 2, 3
1, 2, 3
1, 2, 3
1, 2, 3
1, 2, 3
Auxiliary Freeze sensor. Auxiliary Instant
29
Output
32
Module
HOM, PIR motion sensor, sound sen­sor, or pressure mat.
Silent Instant
Note: Check marks () represent characteristics pres ent in a group.
* This group is not certified as a primary protection circuit for UL-listed systems and is for supplementary use only.
Sounds instant police siren if two or more sensors are tripped within 4 minutes. Otherwise sensors are followers to delayed
sensors. If central station feature 15 (Alarm Verification) is on, group 18 functions like group 17.
This group has not been investigated by UL.
§ This group is required for UL-listed residential fire alarm applications.
1, 2, 3
1, 2, 3
38
Page 43
Appendix C: Programming Tables
Table C.2 Sensor Text Numbers
Text No. Te xt No. Te xt No. Te xt No.
Null 00 0 30 Floor 60 Shock 90
A 01 1 31 Freeze 61 Side 91 B 02 2 32 Front 62 Sliding 92 C 03 3 33 Gallery 63 Smoke 93 D 04 4 34 Garage 64 Sound 94 E 05 5 35 Hall 65 South 95
F 06 6 36 Heat 66 Stairs 96 G 07 7 37 Kitchen 67 Top 97 H 08 8 38 Laundry 68 West 98
I09 939 Level69 Window99
J10 Area40 Library70
K 11 Attic 41 Living 71
L 12 Basement 42 Main 72 M 13 Bathroom 43 Master 73 N 14 Bedroom 44 Mat 74
0 15 Bottom 45 Medical 75
P 16 Breezeway 46 Motion 76 Q 17 Cabinet 47 North 77 R 18 Carpet 48 Office 78
S 19 Closet 49 Panic 79
T20 Den50 Patio80 U 21 Desk 51 Police 81
V 22 Dining 52 Pool 82
W 23 Door 53 Porch 83
X24 Drawer54 Rear84
Y 25 East 55 Room 85
Z 26 Entry 56 Safe 86
Space (blank) 27 Family 57 Scr een 87
Apostrophe (‘) 28 Fire 58 Second 88
Dash (-) 29 First 59 Sensor 89
39
Page 44
Appendix C: Programming Tables
Table C.3 X-10 Lamp and Appliance Module House Code Settings
X-10
Codes
A 16 32 48 64 80 96 112 128 144 160 176 192 208 224 240 B 1* 17 33 49 65 81 97 113 129 145 161 177 193 209 225 241 C 2 183450668298114130146162178194210226242 D 3 193551678399115131147163179195211227243 E 4 20 36 52 68 84 100 116 132 148 164 180 196 212 228 244 F 5 21 37 53 69 85 101 117 133 149 165 181 197 213 229 245
G 6 22 38 54 70 86 102 118 134 150 166 182 198 214 230 246
H 7 23 39 55 71 87 103 119 135 151 167 183 199 215 231 247
I 8 24 40 56 72 88 104 120 136 152 168 184 200 216 232 248
J 9 25 41 57 73 89 105 121 137 153 169 185 201 217 233 249 K 10 26 42 58 74 90 106 122 138 154 170 186 202 218 234 250 L 11 27 43 59 75 91 107 123 139 155 171 187 203 219 235 251
M 12 28 44 60 76 92 108 124 140 156 172 188 204 220 236 252
N 13 29 45 61 77 93 109 125 141 157 173 189 205 221 237 253
O 14 30 46 62 78 94 110 126 142 158 174 190 206 222 238 254
P 15 31 47 63 79 95 111 127 143 159 175 191 207 223 239
* Default setting.
Corresponding Panel House Codes
255
This house code is reserved for demo panels only.
40
Page 45
Appendix C: Programming Tables
Table C.4 X-10 Lamp and Appliance Module Operation
Condition
On Arming to Level 1-Off (Not if disarming to level 1 after an
alarm–see below)
On Arming to Level 2-St ay On for 5 minutes 2 Blinks Unchanged Unchange d On Arming to Level 3-Away On for 5 minutes 3 Blinks Unchanged Unchanged On Disarming Any Alarm to Level 1 On for 5 minutes 1 Blink On for 5 minutes If on, off after 5
On Fire Alarm* On† On† On† Unchanged† On Police Alarm* Flashing† Flashing† Flashing† Off On Auxilliary Alarm* On† On† On† Unchanged† After Fire or Auxiliary Alarm Time-
out COMMAND + 0 (All Lights On) On On On Unchanged COMMAND + 0 (All Lights Off) Off Off Off Off
Lamp Module
Unit No. 1
Unchanged if ini-
tially off
On for 5 more
minutes if initial ly
on
On† On† On† Unchanged
Lamp Module
Unit No. 2
1 Blink Unchanged Unchanged
Lamp Module
Unit Nos. 3–9
Appliance
Module Unit
Nos. 3–9
minutes
*Fire alarms hav e priority over bot h police and auxiliary alarms. Police alarms have priority over auxilliary alarms. †Stays on until ma nually turned off or until 5 minutes after the system is disarmed to Le vel 1-Off.
41
Page 46

Appendix D: System Planning Worksheets

_
_
_
_
Appendix D: System Planning Worksheets
Fill in customer information about this installation:
Customer
Address
City
Country
* Not UL listed; not intended for use in UL listed systems.
________________________________________
_________________________________________
_____________________
__________________
Phone
_________________
State/Zip
___________________
Table D.1 Wireless Sensors
Part No. Description Qty.
60-362 Learn Mode Door/Window Sensor 60-409 Learn Mode Recessed Door/Win-
dow Sensor
60-499 Learn Mode Slim Line Door/Win-
dow Sensor
60-461* Learn Mode Shock Sensor
60-459* Learn Mode Sound Sensor (ITI) 60-462* Learn Mode Glass Guard Sensor
60-506 Learn Mode System Smoke Sen-
sor
60-460 Rate-of-Rise Heat Sensor
60-589* Manual Fire Pull Sensor 60-504* Learn Mode Freeze Sensor
60-452 Learn Mode Pendant Panic Sensor 60-458 Single Button Panic Sensor 60-457 Dual Button Panic Sensor 60-578 Water-Resistant Panic Sensor 60-348 Handheld Wireless Touchpad 60-453 Wall-Mount Wireless Touchpad 60-511 Learn ModeDS924i PIR Motion
Sensor
60-592 DS926 PIR Ceiling Mount Motion
Sensor
60-582 Learn Mode Sound Sensor
(IntelliSense)
60-645-95 Wireless Smoke Sensor
(System Sensor 2300RFITI)
Table D.2 Hardwire Devices
Part No. Description Qty. mA SubTot.
Hardwire Sensors/De te ct ors
13-068* Magnetic Contact
3/8” press fit
13-070* Magnetic Contact –
surface mount
13-360 ESL 449AT Smoke/
Heat Detector
13-391 Power Supervision
Module 79-004* Fire Pull Station N/A 13-028* PIR Motion Detector 10 mA
Hardwire Si rens
60-252 Hardwire Interior
Speaker & Piezo 60-278 Hardwire Interior Siren
& Piezo 60-483-01Slim Line Hardwire
Interior Siren & Piezo 13-046 Hardwire Exterior
Siren
Miscellaneous Components
60-584 Superbus Hardwire
Input Module (HIM) 60-586 Superbus Alphanu-
meric Touchpad 60-620 Superbus Energy
Saver Module (ESM) 60-661 Superbus 2-Line, LCD
Alphanumeric TP 60-662 Superbus 2-Line, V/F
Alphanumeric TP 60-677* Interrogator 200 Audio
Verification Module
(AVM)
Total power consumption not to exceed: 750 mA
N/A
N/A
15 mA
20 mA
5 mA
75 mA
85 mA
145 mA
18 mA
75 mA
10 mA
115 mA
120 mA
10 mA
Table D.3 Recommended Superbus Device
Unit Numbers (addresses)
Superbus Device
First Alpha. Touchpad 1 1 Second Alpha. Touchpad 1 2 Third Alpha. Touchpad 1 3 Fourth Alpha. Touchpad 1 4 Hardwire Output Module
(HOM) Hardwire Input Modu le (HIM) 0 6 Energy Saver Module (ESM) 0 7
Factory
Default
Recom mened
05
Actual
Setting
42
Page 47
Appendix D: System Planning Worksheets
Table D.4 Sensor Groups and Locations
No. Group Type and Location
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46
Table D.4 Sensor Groups and Locations
No. Group Type and Location
47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76
43
Page 48
Appendix D: System Planning Worksheets
Table D.5 Panel Configuration Settings
Feature Choices Default Setting
Primary Phone Number
Phone Format - ITI
Siren Time-out 01–30 min. 4 min. Install Code 0001–9998 or
Account Number 00000–99999 00 –0 00 Entry Delay 008–120 sec. 32 sec. Extended Delay 01–08 min. 4 min. Exit Delay 008–18 4 se c. 32 sec. Activity Time-out 01–24 hr. 24 hr. House Code 001–254 001 Freeze Temp (ESM) 40–90° F 42° F Set Temp (ESM) 32–99° F – Touchpad Options:
Unit Number 000–007 1
Touchpad Quiet Y or N N
Key Beeps Y or N Y
AVM Mode 01–03, 09–
AVM Time-out 030–300 sec. 90 sec. AVM Code 0001–9998* or
HOM Setup ‡ Time Zone 05 (Eastern)
* Any four dig it sequence different than primary, install,
secondary, or arm-disarm access codes, 7777, 8888, 9999, or any number of 6s. Last two digits cannot be the same.
† If the Phone Format is set to 4/2 1400 or 2300Hz for-
mat, upper sensor 98—Events Report must be off.
2 to 18 digits, incl. pauses
- 4/2, 1400Hz†
- 4/2, 2300Hz†
****(blank)
11†
****(blank)
06 (Central) 07 (Mountain) 08 (Pacific) 10 (Hawaii)
ITI
****
03
****
05
Table D.6 HOM Configuration Settings
Unit
Output Point Configuration Number
No.
0101
202 303 404
1105
206 307 408
2109
210 311 412
3113
214 315 416
4117
218 319 420
5121
222 323 424
6125
226 327 428
7129
230 331 432
If the AVM Mode is set to instant modes 3 or 11 and the
Phone Format is set for 4/2 1400 or 2300Hz format, the central station must be set with the panel’s account num­ber in the ATRAP (audio trap) table. The panel will not hang up the phone when the report is complete, but will remain on the line for the AVM Time-out duration.
‡ For HOM setup refer to the Hardwire Output Module
(HOM) Installation Instructions document 466-1032, included with each HOM.
44
Page 49
Appendix D: System Planning Worksheets
Table D.7 System Settings
NO. Feature Choices Setting
System Setting (default)
00 Arm Code
(Primary)
01 Arm Code
(Secondary)
02 Arm Code
(Secondary)
03 Arm Code
(Secondary)
04 Arm Code
(Secondary)
05 Arm Code
(Arm-Disarm)
06 Arm Code
(Arm-Disarm)
07 Arm Code
(Arm-Disarm)
08 Arm Code
(Arm-Disarm)
09 Arm Code
(Arm-Disarm)
10 Arm Code
(Arm-Disarm)
11 Arm Code
(Arm-Disarm)
12 Arm Code
(Arm-Disarm)
13 Arm Code
(Arm-Disarm)
14 Arm Code
(Arm-Disarm)
15 Arm Code
(Arm-Disarm)
16 Arm Code
(Arm-Disarm)
17 Arm Code
(Arm-Disarm)
18 Arm Code
(Arm-Disarm)
19 Arm Code
(Arm-Disarm)
20 Arm Code
(Arm-Disarm)
21 Arm Code
(Arm-Disarm)
22 Arm Code
(Arm-Disarm)
23 Arm Code
(Arm-Disarm)
0001–9998 (Defaul t: 1234)
0001–9998 or ****(blank)
0001–9998 or ****(blank)
0001–9998 or ****(blank)
0001–9998 or ****(blank)
0001–9998 or ****(blank)
0001–9998 or ****(blank)
0001–9998 or ****(blank)
0001–9998 or ****(blank)
0001–9998 or ****(blank)
0001–9998 or ****(blank)
0001–9998 or ****(blank)
0001–9998 or ****(blank)
0001–9998 or ****(blank)
0001–9998 or ****(blank)
0001–9998 or ****(blank)
0001–9998 or ****(blank)
0001–9998 or ****(blank)
0001–9998 or ****(blank)
0001–9998 or ****(blank)
0001–9998 or ****(blank)
0001–9998 or ****(blank)
0001–9998 or ****(blank)
0001–9998 or ****(blank)
Table D.7 System Settings (Continued)
NO. Feature Choices Setting
53 ES Low (ESM) 45-89° F (50°) 54 ES High (ESM) 46-90° F (90°) 77 Quiet Exit ON or (OFF) 88 Download
Enable
Notes:
1. 6s should not be used in any part of an access code,
since such a code interferes with bypassing sensors from a touch-tone phone.
2. Access codes cannot be programmed as 7777, 8888, or 9999 since these codes are reserved for fire, police, and auxiliary panics from a touch-tone phone.
3. Each access code whether primary, secondary, arm­disarm, or AVM must be unique. No two codes can be the same.
4. 4s or 0s should not be programmed as the first digit in an access code, since this can interfere with system disarming.
5. The last two digits of an access code cannot be the same.
ON or (OFF)
45
Page 50
Appendix D: System Planning Worksheets
Table D.8 Upper Sensor Numbers
No. Sensor Name Description Default Setting
77 Touchpad Tamper Reports a touchpad tamper to the Central Station (CS) if 40 digits are
entered without a valid access code.
78 Freeze Sensor On will activate and report a Freeze Alarm when the room temperature
reaches the programmed freeze temperature. Whe n on, an d no tempera­ture data is received from the Energy Saver Module (ESM), a 78 TROUBLE alarm is reported.
79 No Activity When on, if no activity is detected on the premises within the programmed
Activity Time-out, the au xiliary siren will sound . The panel repo rts to the CS if the alarm is not canceled within 5 minutes.
80 Touchpad Fire
Panic
81 Touchpad Police
Panic
82 T ouchpad A uxiliary
Panic
83 Manual Phone
Test 84 Opening Report Reports to the CS when the user disarms the system. OFF 85 Closing Report Reports to the CS when the user arms the system. OFF 86 Duress Alarm Reports a silent POLICE EMERGENCY to the CS. OFF 87 Force Armed Reports a FORCE ARMED when user directly or indirectly bypasses any
88 Energy Saver
Enable
89 Wireless Touch-
pad Supervisory
or Low Battery
90 AC Po wer Failure If on, reports an AC FAILURE to the CS if the panel has been without AC
91 Low Pan el Ba ttery If on, reports LOW CPU BATTERY to t he CS if th e panel's back -up battery
92 Panel Tamper If on and armed to level 2 or 3, changing from run to program will activate
93 Automatic Phone
Test 94 Receiver Failure If on, the panel reports to the CS if the panel does not hear from any wire-
95 Panel Back In
Service 96 Phone Failure If the panel is unsuccessful reporting to the CS after the third of eight
98 Events Report If on (and panel is set up for ITI phone f o rmat), the pa ne l au tomatically
On enables the FIRE button on all touchpads (and telephones if F35 is on). ON
ON enables the POLICE button on all touchpads (and telephones if F35 is on).
On enables the AUXIL IARY button on all touchpads (and telephones if F35 is on).
Allows the user to instruct the system to dial CS and report a phone test. ON
sensor. Security level and bypassed sensor are reported. (Auto Force Armed is always reported.)
When on, the Energy Saver Module (ESM) is ab le to o verride the con­nected thermostat. When on and no temperature data is received from the ESM, an 88 TROUBLE alarm is reported.
When on, the panel checks for and reports supervisory conditions on Wall Mount Wireless touchpads. Reports a SUPERVISORY alarm to the alpha­numeric touchpad if the pane l do es n 't hea r fro m ea ch touc h pa d with in the set time (SUPSYNC). If on, the panel will report a touchpad low battery when any touchpad has a low battery condition.
power for 15 minutes.
voltage dr ops below 11.4 VDC.
and report a CPU TAMPER alarm. If on, the panel reports to the CS at a progr ammed interval (from daily to
every 255 days).
less transmitter for 2 hours. Trouble beeps alert user of the problem. When on, the panel reports to the CS at power-up and if a panel reset
occurs.
attempts, the panel activ a te s a FAIL TO COMMUNICATE alarm. It contin­ues to dial the remaining five attempts.
reports to the CS whe n 28 e v en ts are accum ulate d in the e v ent b uff er. If off, the panel doesn’t report but still accumulates events in the bu ffer. Note: Must be off if panel is set up for 4/2 Phone Format.
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
ON
OFF
ON
ON
ON
OFF
46
Page 51
Appendix D: System Planning Worksheets
.
Ta ble D.9 Feature Numbers
No. Feature Name Description Default Setting
F00 Remote Phone Access On enables, off disables remote phone access. Works in conjunction
with feature F01 below. Off-premises accessing must be done with primary access code.
Ring Twice–Hang-up–
F01
Ring–Answer
Exterior Siren Delay On = exterior siren activ ation is delayed 15 seconds.
F02
Toll Saver Determines on which ring the panel answers an alarm or trouble situ-
F03
F04 Low Battery Reports On = sensor low-battery conditions are reported weekly .
F05 Sensor Supervisory
Reports
Dialer Abort Determines if the phone dialer aborts calls canceled by the owner
F06
Access Key Type On = phone key accesses the panel.
F07
Interior Siren Sounds
F11
Disable
F12 Alarm Restoral Reports On = sensor/zone alarm restorals are reported to the CS.
F13 Low Battery Restoral
Reports
F14 Hourly Phone Test On enables and off disables the hourly phone line voltage test. OFF F15 Alarm Verification On = panel reports alarm to CS only if two different sensors (in
F16 Trouble Beeps Disable On = no trouble beeps and panel protests open sensors only.
F17 24-Hour Sensor
Tamper Alarm
F20 Audio Verification Mod-
ule (AVM) Enable
F21 Immediate Trouble
Beeps
F22 Touch-Tone Dialing On = DTMF(tone). Off = pulse. ON F23 Event Control On = only arming level and time chang es are logg e d in event buffer.
F25 Keychain T ouchpad
Direct Arming
F32 Keychain T ouchpad
Energy Saver/No Delay
On = call premises and l et phon e ring twice, hang-up and wait 10 sec­onds, call back premises and panel answers after first ring. Off = call premises and wait for panel to answer (about 12 rings).
Off = exterior siren ac tivation is immediate.
ation. On = 8 rings, Off = 12 rings.
Off = sensor low-battery conditions are reported daily . Determines uncorrected supervisory trouble conditions to re-report
daily (off) or weekly (on).
before panel dialing is completed.
Off = ƒ phone key accesses the panel. On = Interior sirens sound alarms only.
Off = Interior sirens sound alarms and status.
Off = sensor/zone alarm restorals are not reported to the CS. On = sensor battery restorals are reported to the CS.
Off = sensor battery restorals are not reported to the CS.
groups 10–20) are tripped within 4 minutes. Off = panel reports alarms to CS without second sensor trip.
Off = trouble beeps sound for sensor low-batterty/supervisory condi­tions and panel protests upon arming when these conditions exist. Must be off for UL-investigated systems.
On = sensor tamper alarms are generated in any protection level. Off = sensor tamper alarms are generated only if the system is armed to a level where the sensor is active.
On enables and off disables 2-way voice communication with the Central Station during an alarm.
On = trouble beeps sound immediately when a supervisory condition is detected. Must be on for UL-investigated systems. Off = trouble beeps sound within 10 hours.
Off = all event buffer flagged events are logged. On = pressing Lock b utton onc e arms system to Le vel 3- A wa y with No
Delay. Off = pressing Lo c k b utto n onc e arms syst em to l e vel Level 2-Stay; to Level 3-Away when pressed again.
On = * button activates No Delay feature. Off = * button turns Energy Saver on and off.
(continued)
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
47
Page 52
Appendix D: System Planning Worksheets
Table D.9 Feature Numbers (Continued)
No. Feature Name Description Default Setting
F33 Downloader Access
Enable
F35 Telephone Panics On enables, off disables phone button panics and upper sensors 80,
F36 On-Premise Telephone
Control F37 Quick Arming On enables, off disables touchpad quick-arming commands. ON F40 Smoke V e rific a tio n On = if a hardwire smoke sen s or trips, the panel resets all hardwire
F41 Interior Siren Verifica-
tion F42 Source Reporting On = panel reports source of alarm (which touchpad/device) to the
F43 Demo Kit Mode On enables, off disables special demo kit mode of operati on . OFF F44 Constant Exterior Siren On = exterior siren relay output latches and remains latched for intru-
F45 Keyswitch Control
(Arming/Disarming)
F46 Daylight Savin gs Time On automatically adjusts the panel clock at 2:00am on the first Sun-
F47 4-Hour T rouble Timer On = group 26 (fire) sensors reporting a low battery, tamper, pre-
On enables, off disables remote downloader station programming. (Same as option 88 in User-Programming menu.)
81, and 82 are not generated from the telephone. On enables, off disables on-premise phone control of panel. ON
smoke sensors and waits for a second trip (within 5 minutes) before alarm is generated. An alarm is also generated if the panel doesn’t receive a re storal after the fi rst trip. Off = panel only req uires one trip .
On = panel monitors interior siren wiring for shorts/opens. OFF
central station when S77 and S80-87 reports are sent.
sion alarms, for siren timeout duration or until alarm is canceled. OFF = exterior siren relay output modulates between open and closed states for normal intrusion alarm output.
On = allows zone 1 to arm and disarm the system, using a keyswitch or dry relay contact output of an access system connected to a panel hardwire input, HIM, or door/window sensor terminals. Off = no keyswitch arming/disarming
day in April for daylight-savings time and the last Sunday in October for standard time. These changes are logged in the event buffer.
alarm, or trouble condition cause the system to sound trouble beeps. Pressing STATUS or changing arming level stops trouble beeps for 4 hours. Trouble beeps sound again in 4 hou rs if problem is no t fixed. Must be on for UL Listed installations. Off = group 26 sensors initia te trouble beeps imme diately or within 10-hours (a s per F21 setting).
OFF
OFF
OFF
ON
OFF
OFF
ON
ON
48
Page 53
Table D.10 Central Station Programming
Feature Choices Default Setting
ACCOUNT ##-###. Num bers or Letters 00-0 00 AVBEEPDLY
(Audio Verifica­tion Beep Delay)
PHONE2 (Secondary phone number)
PMODE (Phone Dialer Mode)
PTFREQ (Auto­matic Phone Test
Frequency)* STIME (Supervi-
sory Time)
SUPSYNC (Supervisory Synchronization)
XTENDELAY 2 - OFF or ON OFF (X-10 Module 3 - OFF or ON OFF Delay) 4 - OFF or ON OFF
TRIPTIME (HOM Momentary Response Trip Time)
0–300 seconds in 2-second increments.
Up to 14 digits, including *,#, and D.
0 (ITI and 4/2 formats) - All reports to phone 1. Phone 2 not used. 1 (ITI and 4/2 formats) - All reports to phone 1. Phone 2 used if other attempts fail. 3 (ITI format only) - All alarms, opening, and closing reports to phone 1. All reports to phone 2. 5 (ITI and 4/2 formats) - All alarms, opening, and closing reports to phone 1 using 4/2 for­mat. All reports to phone 2 using ITI format.
1–255 days in cycle, 1–255 days remaining.
00–23 hours:00–59 minutes 12 hours
02–24 hours 12 hours
5 - OFF or ON OFF 6 - OFF or ON OFF 7 - OFF or ON OFF 8 - OFF or ON OFF 9 - OFF or ON OFF 01–12 seconds 04
002 seconds
(none)
0
7,7 days
after any power­up.
seconds
* This feature only functions if upper sensor 93 is on.
Appendix D: System Planning Worksheets
49
Page 54

Appendix E: Panel Connections and Wiring

Appendix E: Panel Connections and Wiring
This appendix contains a description of the control panel terminal connections, wire recommendations, and a typical system wiring diagram (figure E.1, last page of document). Refer to appendix F for UL requirements.
Table E.1 Panel Terminal Strip 1 Connections
Terminal Name What It’s Used for
1 16.5 VAC 16.5 VAC power transformer connection (or negative [-] DC connection if operating
from an external DC source or battery).
Warning
Never connect both AC power transformer and an external DC source at the same time. Permanant damage to transformer, DC source, and panel could result.
2 16.5 VAC 16.5 VAC power transformer connection (or positive [+] DC connection if operating
from external DC source or battery). See above warning.
3 + DC
(SIREN)
4 GND Common ground connection for hardwire and other devices 5 SIREN COM Common (C) side of external siren dry relay N/C and N/O contacts (terminals 6 and 7) 6 SIREN N/C Normally closed (N/C) (opens on alarm) external siren dry relay contact connection 7 SIREN N/O Normally open (N/O) (closes on alarm) external siren dry relay contact connection 8 VOICE
SIREN
9 VOICE
SIREN 10 TP VOICE Reserved for future use. 11 TP VOICE Reserved for future use. 12 +12V DC
OUT 13 BUS A Superbus communication connection
Hardwire device DC power supply. Unregulated 12-24 VDC@ 0.75 amp maximum. Fused (F1).
Note
For 24 VDC sirens and bells only.
One side of speaker and Interrogator 200 AVM talk-back speaker connection
Warning
The maximum number of speakers connected to terminals 8 and 9 is two. Connect multiple speakers in series only. Connecting m ore than two speakers or connecting multiple speakers in parall el could result in permanan t dama g e to the panel.
Other side of spea ker and Interr og ator 200 AVM talk-back speaker co nnection
Superbus, Fail-to-Communicate, Interrogator 200 AVM and exterior siren DC power supply. Regulated 12 VDC@ 0.75 amp maximum. Fused (F2).
14 BUS B Superbus communication connection 15 GND Superbus, AVM, FTC, etc, common ground connection 16 FTC O ne side of Failure-to-Communicate (FTC) device connection. 12 VDC@100 mA
maximum. Other side to DC OUT terminal 12. (Other side to GND terminal 4 if wired to external contact of a wireless door/window sensor.)
(continued)
50
Page 55
Appendix E: Panel Connections and Wiring
Table E.1 Panel Terminal Strip 1 Connections (Continued)
Terminal Name What It’s Used for
17 + INT SIREN Positive (+) side of interior siren connection. 12 VDC@100 mA maximum. Other side
to - INT SIREN terminal 18. Connect multiple piez o s in parallel. A 1N4001 di ode (in series) is required at each piezo location. A 4.7K ohm EOL resistor (i n para lle l) i s reqi­uired at the peiz o or at th e la st p eiz o in a cha in (s ee wi ring d iag ra m). Th is t erminal nor­mally measures zero volts (to GND).
18 - INT SIREN Negati v e (-) side o f interior si ren co nnect ion. 12 VDC@100 m A maxim um. Othe r side
to + INT SIREN terminal 17. This terminal normally measures +12 volts (to GND)
when siren is off. This is the normal monitoring (supervision) voltage. 19 GND Interrogator 200 AVM microphone (listen-in) common ground connection 20 AVM MIC Interrogator 200 AVM microphone (listen-in) connection
WARNING!
The maximum numbe r of micro phone s to be connec ted to te rminals 19 and 20 is two .
Connect multiple microphones in parallel.
Table E.2 Panel Terminal Strip 2 Connections
Terminal Name What It’s Used For
21 +12V DC
SW 22 GND Common ground for hardwire zones 1 and 2, Smoke, and Rate-of-Rise Heat sensors 23 ZONE 1 Hardwire zone 1 24 ZONE 2 Hardwire zone 2 25 GND Common ground for zones 3 and 4 26 ZONE 3 Hardwire zone 3 27 ZONE 4 Hardwire zone 4 28 GND Common ground for zones 5 and 6 28 ZONE 5 Hardwire zone 5 30 ZONE 6 Hardwire zone 6
Smoke and Rate-of-Rise Heat sensor power supply. Switched 12 VDC @100 mA maximum.
51
Page 56
Appendix E: Panel Connections and Wiring
Table E.3 Wire Recommendations
Device
AC Power Transformer 18 Stranded 25 – Earth Ground 14 Solid or stranded 25 – Superbus Devices (Touchpads,
ESM, HIM, etc.) Hardwire Zones and De v ic es 22 Stra nd ed (See resis-
Sirens, Piezos, and Speakers 18 Stranded 500 – Interrogator 200 AVM Micro-
phone* Tel ephone 22 Phone grade solid or
* Run Interrogat or 200 AVM speaker and microphone wires in separat e cab les to prevent cross talk. Some applica tions ma y require shielded cable for long or electrically noisy microphone wire runs.
Minimum
Gauge
22 18
22 Stranded/shielded 500
Type
Stranded Stranded
stranded
Maximum
Length (feet)
500
1,000
tance)
––
Maximum
Resistance
50 ohms per zone
(including devic e resis-
tance)
52
Page 57

Appendix F: UL Requirements

Appendix F: UL Requirements
This appendix contains a description of the requirements for UL-listed systems and a UL-listed system wiring diagram. This section describes the minimum system configurations for UL-listed Grade A (supervised) sys­tems. Also refer to the other appendices for proper programming and other compatible sensors.
Basic System
All UL-listed systems require the following basic components. The basic system does not require sensors and can use the Handheld Wireless Touchpad (60-348) as a signaling device.
Control Panel (60-650)
Superbus Alphanumeric Touchpad (60-586)
Class II Line Carrier Power Transformer (60-678)
Heavy Duty 6.5AH Backup Battery (60-680)
Wireless Interior Siren and Piezo (WIS) (60-353-235), Hardwire Exterior Siren and Piezo (13-046), or Slim Line Hardwire Interior Siren (60-483-01)
Household Fire Warning System (UL 985)
Basic system as described above plus:
Wireless Smoke Sensor (60-506), Wireless Smoke Sensor (60-645-95), or Hardwire Smoke/Heat Detector (13-360) (ESL 449AT) with Power Supervision Module (60-391). This shall be programmed as Sensor Group 26.
When utilizing a hardwire zone for fire alarm (Group 26), the panel shall not be connected to earth ground.
Option F21 (Immediate Trouble Beeps) set to ON
Option F47 (4-Hour Trouble Timer) set to ON
SUPSYNC (Supervisory Synchronization) set to 2 (hours)
Note
SUPSYNC can not be programmed from the panel. Refer to the “Requestin g CS-4000/Do wnloader Programming” section for more informatio n.
For 24-hour backup, external power drain is limited to 150 mA continuous using the heavy duty 6.5AH battery.
53
Page 58
Appendix F: UL Requirements
The smoke detector insta ll at io n sh all ad he re to t he followi ng:
A smoke detector should
Bedroom
Bedroom
Hall
be located on each level.
Living
Room
Basement
Dining
Room
TV
Room
Bedroom
NOTE: Ceiling-mounted smoke detectors should be located in the center of the room or hall, or not less than 4 inches from the wall. When the detector is mounted on the wall, the top of the detector should be 4 to 12 inches from the ceiling.
NOTE: Do not install smoke detectors where normal ambient temperatures are above 100°F or below 40°F. Also, do not locate detectors in front of AC/ Heat registers or other locations where normal air circulation will keep smoke from entering the detector.
Kitchen
H
Living
Room
Dining
Room
Dining
Room
Living
Room
Bedroom
Kitchen
H
Hall
Bedroom
Bedroom
Bedroom
Living
Room
Basement
Bedroom
In family living units with more than one sleeping area, locate a smoke detector at each area.
Smoke detectors should be located between the sleeping area and the rest of the family living unit.
Bedroom
x
Recreation
Room
Bedroom
Hall
NOTE: Additional information on household fire warning is available at nominal cost from: The National Fire Protection Association, Batterymarch Park, Quincy, MA 02269. Request Standard No. NFPA74.
Required smoke detector
H
Heat detector
x
Indicates smoke detector is optional if door is not provided between basement and recreation rooms.
Household Burglar Alarm System (UL 1023)
Basic system as described above plus:
Learn Mode Door/Window Sensors (60-362)
54
Page 59
Appendix F: UL Requirements
Home Health Care Signaling Equipment (UL 1637)
Basic system as described above plus:
Water-Resistant Panic Sensor (60-578-10-95)
The following wireless sensors and hardwire devices may be used in a UL-listed system:
Part No. Description
Wireless Sensors
60-362 Learn Mode Door/Window Sensor 60-409 Learn Mode Recessed Door/Windo w Se ns o r 60-499 Learn Mode Slim Line Door/Window Sensor 60-506 Learn Mode System Smoke Sensor 60-460 Rate-of-Rise Heat Sensor 60-452 Learn Mode Pendant Panic Sensor 60-458 Single Button Panic Sensor 60-457 Dual Button Panic Sensor 60-578 Water-Resistant Panic Sensor 60-348 Handheld Wireless Touchpad 60-453 Wall-Mount Wireless Touchpad 60-511 Learn ModeDS924i PIR Motion Sensor 60-592 DS926 PIR Ceiling Mount Motion Sensor 60-582 Learn Mode Sound Sensor (IntelliSense)
60-645-95 Wireless Smoke Sen sor
(System Sensor 2300RFITI)
Hardwire Sensors/Detectors
13-360 ESL 449AT Smoke/Heat Detector 13-391 Power Supervision Module
Hardwire Sirens
60-252 Hardwire Interior Speaker & Piezo 60-278 Hardwire Interior Siren & Piezo 60-483 Slim Line Hardwire Interior Siren & Piezo 13-046 Hardwire Exterior Siren
Miscellaneous Components
60-584 SuperBus Hardwire Input Module (HIM) 60-585 SuperBus Hardwire Output Module (HOM) 60-586 SuperBus Alphanumeric Touchpad 60-620 SuperBus Energy Saver Module (ESM) 60-661 SuperBus 2-Line, LCD Alphanumeric TP 60-662 SuperBus 2-Line, V/F Alphanumeric TP
55
Page 60
Appendix F: UL Requirements
The following Sensor Groups are not to be used as a primary protection circuit for UL-listed systems and are for supplementary use only:
No. Name
11 Extended Enty/Exit Delay 12 Twice Extended Delay 15 Instant Inter ior 17 Instant Inter ior 18 Instant Inter ior 19 Delayed Interior 20 Delayed Interior 24 Local Instant Auxiliary 25 Local Special Chime
The following Sensor Groups shall not be used in UL-listed systems:
No. Name
27 Output Module 28 Output Module 32 Output Module
The following panel configuratio n set tin gs sha ll be follow ed:
Feature Required Setting
Phone Format ITI Siren Time-Out 4 min., minimum Entry Delay 40 sec., maximum Exit Delay 56 sec., max imum
Note:
Common user access codes su ch as 1111 or 12 34 shou ld no t be pro gr ammed.
The Upper Sensor Numbers shall be set as follows:
No. Sensor Name Required Setting
89 Wireless Touchpad
Supervisory or Low
Battery 90 AC Power Failure ON 91 Low Panel Battery ON 93 Automatic Phone Test ON 96 Phone Failure ON
ON*
* If wall-mount touchpads are used.
56
Page 61
The Feature Numbers shall be programmed as follows:
No. Sensor Name Required Setting
F04 Low Battery Reports ON F12 Alarm Restoral Reports ON F13 Low Battery Restoral Reports ON F15 Alarm Verification OFF F16 Trouble Beeps Disable OFF F20 Audio Verification Module
(AVM) Enable F21 Immediate Trouble Beeps ON F40 Smoke Verification OFF F41 Interior Siren Verification ON F43 Demo Kit Mode OFF F47 4-Hour Trouble Timer ON
OFF
The following Central Station programming shall be made:
Appendix F: UL Requirements
PTFREQ: 1,1 (Automatic Phone Test Frequency = 1 day in cycle, 1 day remaining.)
57
Page 62
Appendix F: UL Requirements
58
Page 63
Figure E.1 Typical System Wiring
NOTE1: AUDIO VERIFICATION MODULE, 60-677
BLACK
YELLOW
SPLICE
WIRE IN
SEPARATE
CABLES
BLACK
RED
9
18
8
17
VOICE SIREN
VOICE SIREN
OR
TP
VOICETPVOICE
10
VOICE SIREN
8 9
NOTE 3: 13-060 (15 WATT) NOTE 3: 13-061 (30 WATT)
8 - OHM SPEAKER
NOTE 3: 2 8-OHM SPEAKERS
IN SERIES (16 OHMS)
VOICE SIREN
8 9
EOL RESISTOR 49-365
THERMOSTAT
EARTH
GROUND
NOTE 6 LOWER
RIGHT
CHASSIS
SCREW
TERMINAL
NOTE 5: STANDARD
TRANSFORMER
NOTE 5: LINE CARRIER
TRANSFORMER
16.5 VAC 50 VA
16.5 VAC
STRIP 1
60-679
OR
60-678
LINE
CLASS 2
LOAD
1 2
16.5
+DC
VAC
(SIREN)
3 4 5
NOTE 18
BLACK
NOTE 4: HARDWIRE
EXTERIOR SIREN
13-046
CABLE
SHIELD
WIRE
NOTES 2 & 3: SPEAKER/PIEZO
IN 4001 DIODE 07-001
(LOCATE AT PIEZO)
NOTE 4
SIREN
GND
COM
RED
SIREN
N/C
6 7
4 201912
60-252
SIREN
N/O
SPLICE
NOTE 2: HARDWIRE INTERIOR SIREN, 60-278
RED
BLACK
9
8
4.7k Ohm
(LOCATE AT PIEZO)
1
2 3 4 5
+12V
DC OUT
11
12 13 14 15
NOTE: 11
HARDWIRE
LOOP INPUT
NOTE 8 & 9: SUPERBUS
ENERGY SAVER MODULE
60-620
BUS
BUS
B FTC
A
YELLOW
TO FURNACE
BLACK
RED
IN 4001 DIODE 07-001
(LOCATE AT SIREN)
EOL RESISTOR 49-365
18
17
NOTE 8 SUPERBUS HARDWIRE OUTPUT MODULE (HOM) 60-585
12345
67
1 COM
1 N/C
1 N/O
3 COM
2 COM
2 N/C
2 N/O
6
+INT
GND
ALPHANUMERIC TOUCHPAD
SIREN
16
17 18 19 20
BLACK WHITE GREEN RED
NOT USED WIRING
HARNESS 49-283
TAB SLOT (4)
NOTES 8 & 10: SUPERBUS
60-586
NOTES 8,12,13 & 14: SUPERBUS
HARDWIRE INPUT MODULE
(HIM) 60-584
12345
COMMON
LOOP 1
LOOP 2
LOOP 3
4.7k Ohm
(LOCATE AT SIREN)
9
11 12
14 15
10
8
13
3 N/C
3 N/O
4 COM
4 N/C
4 N/O
12 14
-INT
SIREN
GND
9
67
10
8
COMMON
LOOP 7
LOOP 4
COMMON
LOOP 5
LOOP 6
NOTES 2 & 7: SLIM LINE HARDWIRE
INTERIOR SIREN AND PIEZO, 60-483-01
18
17
16
17
4.7k Ohm
EOL RESISTOR
49-365
(LOCATE AT
SENSOR)
AVM MIC
14 15
16
NOTE 13: PIR MOTION SENSOR
TERMINAL
STRIP 2
13
11 12
13
COMMON
LOOP 8
15
13-082
LP
LN
-
+
+12V
DC SW
GND
21
22 23 24 25
NOTES 13,14 & 15:
LISTED HARWIRE
1234
SMOKE/HEAT
DETECTOR SUCH
AS ESL 449AT
USE IN AND OUT
(DAISY-CHAIN)
1234
WIRING METHODS ONLY
RED
BLACK GREEN WHITE
NOTES 14 & 15:
POWER SUPERVISON MODULE
(INSTALL AT LAST DEVICE)
ZONE
1
60-391
ZONE
2
1. A maximum of two Audio Verification Modules are allowed. Wire multiple speakers in series and the remaining
Table E.4 System Wiring Notes
(power and microphone) wires in parallel. Use shielded cables to prevent cross talk between the speaker and microphone.
2. W ire multiple piezo locations in parallel (daisy chain). Mount the required diode at each piezo loca ti on as shown with the cathode (band marking) towards the piezo device terminal. Mount a single EOL resistor at the last piezo in the chain.
3. A maximu m of two speakers are allowed. Wire multi pl e sp eaker s in seri es only. Wiring more than two speak­ers or multiple speakers in parallel can result in permanent damage to the panel.
4. Jumper terminals 4 to 5 to supply GND to exterior SIREN COM terminal. To avoid bothering neighbors unnec­essarily during initial system testi ng , leave exterior siren(s) disconne cted at the panel un til you are ready to test them.
5. Both line carrier (60-678) and nonline carrier (60-679) AC power transformer types are wired the same. Do not plug transformer into any AC receptacle controlled by a switch. AC power must not be interrupted. Do not short the transformer outputs together. The transformer contains an internal fuse that will permanently disable the output if shorted.
6. Co n ne ct the r ight-bottom panel board mounti ng s crew to electr ical ground (if the installation site has a tr ue electrical ground). Cold water pipe groundin g can be used if it is an uninter rupted metal pipe.
7. Only high-volume Slim-Line siren sounds are used. Internal jumpers and switches have no effect.
8. All SuperBus devices such as Energy Saver, Hardwire Input and Output Modules, and Alphanumeric Touch­pads must have unique unit number (address) settings. Devices with the same (conflicting) address will not function properly. Default settings are ok for one module and one touchpad. Refer to instructions text for set­ting unit numbers (addresses).
9. Refer to the Installation Instructions shipped with the Energy Saver Module for thermostat wiring details.
10. If more than one alphanumeric touchpad is required, wire all touchpad harnesses in parallel, but only connect one touchpad until programming is complete and tested. Additional touchpads require their touchpad unit numbers to be changed from the factory default. Refer to touchpad installation instructions text.
11. The touchpad hardwire loop is supplementary and is not intended for use as a primary initiating circuit because the loop is not end-of-line supervised.
12. Wire Hardwire Input Module hardwire zones as shown for the panel. Mount a single EOL resistor as shown at the last device in the chain.
13. Zone (loop) terminal shown is an example. Any zone (loop) terminal may be used. Install EOL resistors across all unused zone (loop) inputs and GND (common on Hardwire Input Module).
14. Power Supervision Module is required for supervised (UL-investigated) applications. Wire multiple or super­vised hardwire smoke/heat detectors only as shown.
15. For nonsupervised applications, replace the power supervision module with singl e EOL resistor acro s s ter m i­nals 3 and 4 of the last detector in the chain.
16. Some telephones are polarity-sensitive. Green and red wires may need to be reversed.
17. P ho ne jack tampering is optional. If used, assignment to sensor group 8 (specia l int r usion) is recommended.
PHONE
CONNECTIONS
ZONE3ZONE
GND
4.7k Ohm
EOL RESISTOR
49-365
26
NOTE 13:
NORMALLY
CLOSED
(N/C) CONTACTS IN SERIES
GND
4
27 28 29
ZONE5ZONE
NOTE 13:
NORMALLY
OPEN
(N/O)
CONTACTS
IN PARALLEL
4.7k Ohm
EOL RESISTOR
49-365
6
30
BLACK
BLACK
GREEN
DUAL DB-8
PHONE CORD
49-426
NOTE 16: RJ-31X
(CA-38A)
PHONE JACK
BRN
GRN
GREEN(C)
TELCO
PROTECTOR
BLOCK
(A)
GRN RED
GRY
RED
(B)
RED(D)
DUAL DB-8
PHONE CORD 49-425
TO PANEL
NOTE 17: TAMPERING THE
RJ-31X (CA-38A)
PHONE JACK (OPTIONAL)
4.7k Ohm
EOL RESISTOR
49-365
WHITE OR YELLOW
RED
SPLICE
WIRE
WHITE OR YELLOW
TO
PREMISES
PHONES
6, BLU
7, YEL
TO PANEL HARDWIRE
3, ORG
2, BLK
ZONE TERMINALS.
8557139C.DS4
Page 64
Figure F.1 UL-Listed System Wiring
NOTE 4: STANDARD
TRANSFORMER
NOTE 4: LINE CARRIER
TRANSFORMER
NOTE 5:
16.5 VAC 50 VA
LOWER
RIGHT
CHASSIS
SCREW
EARTH
GROUND
16.5 VAC
TERMINAL
STRIP 1
N/C – INDICATES NO CONNECTION SHALL BE MADE.
NOTE 1: HARDWIRE INTERIOR SIREN, 60-278
RED
BLACK
17
NOTES 1 & 2: SPEAKER/PIEZO
60-252
BLACK
RED
60-679
OR
60-678
LINE
CLASS 2
LOAD
1 2
16.5
+DC
VAC
(SIREN)
BLACK
NOTE 3: HARDWIRE
EXTERIOR SIREN
ITI PART NO. 07-001 DIODE
(LOCATE AT PIEZO)
18
17
NOTE 3
SIREN
GND
COM
3 4 5
N/C N/C N/C N/C N/C N/C
13-046
SIREN
SIREN
RED
N/C
6 7
VOICE
VOICE
N/O
SIREN
SIREN
8 9
ITI PART NO. 49-365
(LOCATE AT PIEZO)
THERMOSTAT
TO FURNACE
NOTE 16
TP
VOICETPVOICE
10
4.7k Ohm
EOL RESISTOR
1
+12V
DC OUT
11
12 13 14 15
NOTE 10:
HARDWIRE
LOOP INPUT
NOTE 7 & 8: SUPERBUS
ENERGY SAVER MODULE
60-620
2 3 4 5
BUS
BUS
BFTC
GND
A
YELLOW
6
16
BLACK WHITE GREEN RED
NOT USED WIRING
HARNESS 49-283
NOTES 7 & 9: SUPERBUS
ALPHANUMERIC TOUCHPAD
NOTES 7,11,12 & 13: SUPERBUS
BLACK RED
ITI PART NO. 07-001 DIODE
(LOCATE AT SIREN)
4.7k Ohm
EOL RESISTOR
ITI PART NO. 49-365
(LOCATE AT SIREN)
18
-INT
+INT
SIREN
SIREN
17 18 19 20
TAB SLOT (4)
60-586
HARDWIRE INPUT MODULE
(HIM) 60-584
COMMON
LOOP 2
LOOP 3
COMMON
67
LOOP 4
LOOP 5
9
8
COMMON
LOOP 6
12345
LOOP 1
NOTES 1 & 6: SLIM LINE HARDWIRE
INTERIOR SIREN AND PIEZO, 60-483-01
17
NOTE 12: LISTED PIR MOTION SENSOR
4.7k Ohm
EOL RESISTOR
ITI PART NO. 49-365
(LOCATE AT SENSOR)
AVM MIC
GND
10
LOOP 7
11 12
COMMON
LOOP 8
TERMINAL
STRIP 2
14 15
13
16
18
-
+
NOTE 17
+12V
DC SW
21
1234
1234
LP
LN
ZONE
GND
NOTES 12 & 13:
LISTED HARDWIRE
SMOKE/HEAT
DETECTOR SUCH
AS ESL 449AT
USE IN AND OUT
WIRING METHODS ONLY
NOTES 13: POWER SUPERVISON
ZONE
1
22 23 24 25
(DAISY-CHAIN)
RED
BLACK GREEN WHITE
(INSTALL AT LAST DEVICE)
2
MODULE
ITI PART NO. 60-391
1. Wir e multiple piezo locations in parallel (dais y chai n). Mou nt th e re qu ire d diod e at ea ch pie zo locati on as
Table F.1 UL-Listed System Wiring Notes
shown with the cathode (band marking) towards the piezo device terminal. Mount a single EOL resistor at the last piezo in the chain.
2. A maximum of two speakers are allowed. Wire multiple speakers in series only. Wiring more than two speakers or multiple speakers in parallel can result in permanent damage to the panel.
3. Jumper ter m in als 4 to 5 to supply GND to exterior SIREN COM ter m in al. To avoid bothering neighbors unnec­essarily during initial system testing, leave exterior siren(s) disconnected at the panel until you are ready to test them.
4. Both line carrier (60-678) and nonline carrier (60-679) AC power transformer types are wired the same. Do not plug transformer into any AC receptacle controlled by a switch. AC power must not be interrupted. Do not short the transformer outputs together. The transformer contains an internal fuse that will permanently disable the output if shorted.
5. Con ne ct the r ig ht-bottom panel board mounting screw to electr ical ground (if the inst al la tion site has a true electrical ground). Cold water pipe groundin g can be used if it is an uninte rrupted metal pipe.
6. Only hig h-volume Slim -L in e siren sounds are used. Internal jumper s and switches have no effect.
7. All superbus devices such as Energy Saver and Hardwire Input Modules and Alphanumeric Touchpads must have unique unit number (address) settings. Devices with the same (conflicting) address will not function prop­erly. Default settings are ok for one module and one touchpad. Refer to instructions text for setting unit numbers (addresses).
8. Refer to Installation Instructions shipped with the Energy Saver Module for thermostat wiring details.
9. If mo re tha n on e alph anu me r ic tou ch pa d is requ ire d, wire all touchpad harnesses in parallel , but only conn e ct one touchpad until programming is complete and tested. Additional touchpads require their touchpad unit num­bers to be changed from the factory default. Refer to touchpad installation instructions text.
10. The touchpad hardwire loop is supplementary and is not intended for use as a primary initiating circuit because the loop is not end-of-line supervised. Refer to touchpad installation instructions text for further restrictions.
11. Wir e Hard wire Input Module hardwire zones as shown for the panel. Mount a single EOL resistor as shown at the last device in the chain.
12. Zone (loop) terminal shown is an example. Any zone (loop) terminal may be used. Install EOL resistors across all unused zone (loop) inputs and GND (common on Hardwire Input Module).
13. Power Supervision Modu le is requir ed . Wire multip le or supervised hardwire smoke/heat detectors only as shown.
14. Som e teleph on es are po larity-sensitive. Green and red wires may need to be reversed.
15. Pho ne ja ck tamper ing is option al . If used, assignm e nt to se nso r group 8 (special in tr usion) is recommended.
16. Terminal 12 (+12VDC OUT) is rated 10.4 to 12VDC; refer to installation instructions for maximum current rat­ings.
17. Terminal 17 (+12VDC SW) is rated 9.9 to 12VDC: refer to installation instructions for maximum current ratings.
PHONE
CONNECTIONS
ZONE3ZONE
GND
26
4.7k Ohm
EOL RESISTOR
ITI PART NO. 49-365
NOTE 12:
NORMALLY
CLOSED
(N/C) CONTACTS IN SERIES
GND
4
27 28 29
ZONE5ZONE
6
30
NOTE 12:
NORMALLY OPEN
(N/O) CONTACTS
IN PARALLEL
4.7k Ohm
EOL RESISTOR
ITI PART
NO. 49-365
BLACK
BLACK
GREEN
DUAL DB-8
PHONE CORD
49-426
NOTE 16: RJ-31X
(CA-38A)
PHONE JACK
BRN
GRN
GREEN(C)
TELCO
PROTECTOR
BLOCK
(A)
(B)
GRN RED
GRY
RED
RED(D)
DUAL DB-8
PHONE CORD 49-425
TO PANEL
NOTE 15: TAMPERING THE
RJ-31X (CA-38A)
PHONE JACK (OPTIONAL)
4.7k Ohm
EOL RESISTOR
49-365
WHITE OR YELLOW
RED
SPLICE
WIRE
WHITE OR YELLOW
TO
PREMISES
PHONES
6, BLU
7, YEL
TO PANEL HARDWIRE
ZONE TERMINALS.
8557150B.DS4
3, ORG
2, BLK
Loading...