Document Number: 466-1541 Rev. C
November 1999
ITI Part No. 60-742
Installation Instructions
Product Summary
The ITI Learn Mode™ Freeze Sensor detects a furnace failure in a home or business. The Freeze Sensor contains a
bimetallic switch wired to a transmitter. It activates the
switch when the surrounding temperature drops to about
41°F. After the sensor is tripped, the Freeze Sensor will
send a restore signal to the panel when the temperature rises
to 50°F.
Tools and Equipment Needed
❑ Slotted screwdriver, if using screws instead of the
included double-faced tape
❑ The panel installation instructions, for more detailed
instructions on programm ing sensors
❑ Ice cube
❑ Plastic bag
Installation Guidelines
Do
❑ Keep the transmitter within 100 feet of the panel. In
open air, the transmitter has a range of 500 feet, but the
indoor range will be shorter.
❑ Locate the sensor in an area that is likely to get cold
first.
❑ Locate the sensor on an interior wall where there is free
movement of air.
❑ Program and test the Freeze Sensor before you perma-
nently attach it to anything.
Do not
❑ Locate the sensor in the same room as a furnace, water
heater, or any other heat source that may stay warm
after the furnace fails.
❑ Locate the sensor on an outside wall or near the base-
ment floor.
❑ Place in areas with excessive metal or electrical wiring;
these may keep the sensor’s signals from reaching the
panel.
❑ Place sensor in an area where it will be exposed to
moisture.
❑ Place sensor in a location where the temperature will
exceed the sensor’s operating limits of 10° to 120°F.
Programming
Follow these instructions to program the freeze sensor:
1. Open the control panel cover.
2. Enter Utility Access Code 1 or 2 using the red-numbered buttons.
3. Press Add from the Start Menu.
4. Press the Sensor/Remote button from the Main menu
until you hear the location you wish to use with the sensor.
The order of names the Control Panel uses are: keychain remote, touchpad remote, front door, back door,
garage door, bedroom, guest room, child’s room, utility room, living r oom, dining ro om, bathroom, lau ndry
room, kitchen, office, den, garage, special chime,
basement, upstairs, downstairs, hallway, medicine
cabinet, closet, attic. Each name may be used more
than once.
When adding sensors, if you wish to use a more
descriptive location you may press the option button to
use the compass directions (north, north east, east,
south east, south, south west, west, north west).
5. Press DONE.
6. Enter the sensor type number (29) with the red numbered keys.
If you wish t o use a sens or numbe r other than the ne xt
available, enter a 2 digit sensor number with the red
numbered keys immediately after entering the sensor
type.
7. Press the button on the top of the sensor (cover
removed) until the control panel confirms the programming. If the button is not held down long enough, SYSTEM STATUS will report the sensor is open.
Testing
Perform Sensor Test
The following steps describe the guidelines for testing sensors.
Learn Mode Freez e Se ns or
1

Installation
1. Open the Control Panel cove r.
2. Enter the Utility Access Code 1 or 2 using the red-numbered buttons.
3. Press the Test button once.
4. Press DONE.
5. Trip the sensor by pressing the button on the top of the
sensor (cover removed) until the control panel indicates
the number of RF packets received. If the button is not
held down long enough, SYSTEM STATUS will report
the sensor is open.
6. Note the number of siren beeps indicating how many
RF packets the Control Panel received from the sensor.
You should hear 7-8 beeps.
To test sensor operation:
1. Make sure the Freeze Sensor is in its secure (nonalarm) state.
2. From the panel, begin a sensor test, as explained above.
3. To trip the Freeze Sensor, use a piece of ice in a plastic
bag to cool the bimetallic switch. When the bimetallic
switch reaches approximately 41°F, the sensor sends an
RF signal to the panel.
4. Note the number of beeps, which indicates the device’ s
signal strength.
5. The Freeze Sensor will reset when the surrounding
temperature reaches 50°F.
Installation
In case there are problems with the Freeze Sensor, permanently install it only after programming and testing it.
CAUTION
You must be free of all static electricity when handling
sensors. Touch a grounded metal object before
handling the circuit board.
5. Location of screw mounting holes
6. Replace the batteries.
7. Replace the sensor’s outer cover.
Specifications
Battery: two 1.5 VDC alkaline AAA batter-
ies
Battery life: 4 to 5 years
Compatibility: Simon™, Generic Loop Receiver
Dimensions: 4.5'' × 1.13'' × 0.88'' (L × W × D)
Temperature range: 10° to 120°F
Supervisory signal
transmission: Every 64 minute s
Transmitter range: 500 feet in open air
Transmitter type: SAW (Surface Acoustical Wave),
319.5 MHz r adio frequency
FCC NOTICE
This gdevice complies with FCC Rules Part 15. operation is subject to the following two conditions:
1) This may not cause harmful interference.
2) This device must accept any interference that may be received, including interference that may
cause undesired operation.
Changes or m odifica tions not exp ressly approved by Interac tiv e Technologies, In c. can vo id t he
user’s authority to operate the equipment.
.
1. Secure the sensor base to the clean, dry, nonporous
mounting surface using the double-faced tape.
Or—Follow steps 2 through 7 to secure the sensor base to
the mounting surface using the screws (included).
2. Remove the Freeze Sensor’s outer cover by pressing
the round button on the end of the sensor.
3. Remove the batteries from the sensor to access the
screw mounting holes underneath it.
4. Use the included #6 pan head screws to secure the sensor base to the mounting surface. If mounting on plaster, use the appropriate fasteners. Use the slotted
mounting hole for alignment (see Figure 5).
SCREW MOUNTING HOLES
2
9255G02A.DSF
651-777-2690
651-779-4890
ITI is a regis tered tra demar k of Int erac tive Technologi es, Inc. Lear n Mode a nd Sim on a re t ra demarks of Interactive Technologies, Inc.
Learn Mode Freeze Sensor