Learn Mode Rate-ofRise Heat Sensor
Document Number: 46-547 Rev. E
March 1998
Learn Mode Rate-of-Rise Heat Sensor
Equipment Needed
• Phillips or flathead screwdriver
• Appropriate learn mode control panel installation
instructions (for programming information)
4090G35A.DS4
60-460/60-752
INSTALLATION
INSTRUCTIONS
Product Summary
The Learn Mode Rate-of Rise Heat Sensor combines a
Chemtron Model 601 detector and an ITI learn mode
wireless transmitter in one unit. A built-in thermostat
trips the transmitter when the temperature at the sensor’s location reaches about 135°F.
Since many fires grow rapidly in intensity causing a
rapid temperature increase, the thermostat also trips
the transmitter if the temperature rises 15°F or more,
per minute.
The sensor is powered by a 9-volt battery (see note),
either alkaline or lithium type. The alkaline battery
can last 12 to 18 months. The lithium battery can last
twice as long as the alkaline type.
When the battery voltage gets low, the sensor sends a
low battery signal to the panel. The panel then activates sirens that emit trouble beeps to notify the customer that the sensor’s battery must be replaced.
Installation Guidelines
Use the following guidelines when installing the
Learn Mode Rate-of-Rise Heat Sensor:
• Heat sensors should be installed to provide property protection. Reliance should not be placed
only on heat detectors for life safety. Where life
safety is involved, smoke sensors must also be
installed.
• The sensor allows for normal temperature fluctuations; however, ceiling temperatures should not
exceed 100°F.
• Mount the sensor in a central location of the area
to be protected, either on the ceiling or on a wall.
If mounting on a ceiling, the sensor must be at
least 4 inches away from any walls.
If mounting on a wall, the top of the sensor must
be within 4 to 6 inches of the ceiling.
• The UL maximum spacing allowance of the sensor is 50’ x 50’. Refer to NFPA Standard 72 for
application requirements.
• Do not mount the sensor close to devices that
change temperature rapidly, such as ovens, heat
vents, a furnace, or boilers.
Programming
Note
Battery life depends on how often and length of time battery is used.
CAUTION: SX-V
Special
panels must have software
version 8.0 or later installed for correct
response from Learn Mode Rate-of-Rise
Heat Sensors. Do not install Learn Mode
Rate-of-Rise Heat Sensors if the panel
uses an earlier software version. If you
need assistance, please call ITI Technical
Services at 1-800-777-2624.
The panel must learn the sensor’s ID code in order to
respond to sensor signals. For complete programming
information, refer to the installation instructions for
the specific panel.
To add the sensor to panel memory:
1) Separate the sensor from the base by twisting the
sensor counter-clockwise and pulling it off the
base. Set the base aside.
2) Place the panel in program mode.
3) Enter the LEARN SENSORS mode.
4) When the panel prompts you for a sensor group
number, enter the number for the fire group.
5) Select the desired sensor number.
Page 1

Learn Mode Rate-of-Rise Heat Sensor
6) When the panel prompts you to trip the sensor,
press and release the tamper switch on the sensor
(see Figure 1).
BATTERY
TAMPER
SWITCH
1036G02D.DS4
Figure 1. Tamper Switch Location
7) Exit program mode.
Method 2
1) Plug in a portable hair dryer.
2) Hold the hair dryer about 12 to 18 inches away
from the sensor, aiming it at the side of the sensor.
CAUTION: Do not aim the hair dryer directly at the
round disc on the sensor; otherwise, you
must replace the sensor.
3) Listen for interior sirens and speakers to emit 7 to
8 beeps.
4) Exit sensor test.
The sensor should reset in less than 1 minute.
Mounting the Sensor
Secure the sensor to its permanent location as follows:
1) Locate the base mounting holes (inner pair and
outer pair) and mount the base to the wall or ceiling with the appropriate hardware (see Figure 2).
SENSOR
MOUNTING
HOLES
Testing
Before permanently securing the sensor to the wall or
ceiling, test the sensor from the area it will be located,
using one of the two methods below.
CAUTION: The Learn Mode Rate-of-Rise Heat Sensor
is a one-time device that prolonged heat
can destroy. When used with care, the
heat from a portable hair dryer (method 2)
can be used to test the sensor. If the
round disc on the sensor ever pops off,
the sensor must be replaced.
Method 1
1) Place the panel in the dealer sensor test mode.
2) Rub your hands together vigorously, until they
feel hot.
3) Place the palm of one hand on the round disc of
the sensor, for about 7 to 10 seconds.
4) Listen for interior sirens and speakers to emit 7 to
8 beeps.
5) Exit sensor test.
The sensor should reset in less than 1 minute.
BASE
MOUNTING
HOLES
1036G01D.DS4
Figure 2. Sensor and Base Mounting Hole Locations
2) Attach the sensor to the base.
Page 2

Learn Mode Rate-of-Rise Heat Sensor
Specifications
Compatibility: Learn mode family of control panels
Frequency: 319.5 MHz. (60-460), 433 MHz. (60-752)
Power Requirements: One 9-volt battery (alkaline or
lithium)
Operating Temperature Range: 40° to 120°F
Dimensions: 4.40” x 2.20” (Diameter x Depth)
FCC Notice
This device complies with FCC Rules Part 15. Operat ion i s su bjec t to t he fol lowing two
condition s:
This device may not cause harmful interference.
This device must accept any int erf erence that may be received, including i nterfe rence
that may cause undesired operation.
Changes or modifications n ot expressly approved by Interact ive Technologies, Inc. can
void the user’s authority to operate the equipment.
ITI is a registered trademarks of Interactive Technologies. Inc. Learn Mode is a trademark of
Interactive Technologies, Inc.
Page 3