ITI 60-770 - Security SuperBus 2000 4-Zone Output Module, SuperBus 2000 60-770 Installation Instructions Manual

ITI Part No. 60-770
SuperBus
®
2000
4-Relay Output Module
Document Number: 466-1608 Re v. B November 2000
Product Summary
Each SuperBus 2000 4-Relay Output module adds four pro­grammable relay outputs to a compatible panel.
Examples of module uses include:
Turning on a CCTV camera during a burglary alarm. Turning on exit lights during a fire alarm. Activating backup cellular phones or long-range radios
if primary communications are inoperable.
Each module comes complete with mounting hardware. Power for the module is provided by the panel.
®
Advent programmed) output points.
UltraGard of 32 output points.
For additional security, the plastic case accommodates a magnetic reed switch to provide tamper protection . Simply connect a UL listed reed switch to the module built-in zone input or to one of the fire/security panel hardwire input zones.
SuperBus 2000 vs. SuperBus
panels can be expanded to a total of 124 (24 pre-
®
and Concord™ panels can be expanded to a total
8557109A.DS4
Installation Instructions
Module Components
Figure 1 shows the main module components and Table 1 describes them.
UNIT NUMBER DIP SWITCHES
BUS STATUS LED (RED)
POWER LED (GREEN)
OUTPUT RELAYS (4) SOFTWARE
VERSION LABEL SUPERBUS 2000
DEVICE ID NUMBER LABEL
WIRING TERMINALS
9710G01A.DSF
Figure 1. Module Circuit Board Components
SuperBus 2000 panels have the ability to auto-address mod­ule unit numbers. When the panel is initially powered up, the panel automatically reads the unique SuperBus 2000 device ID number and assigns a unit number to the module. This eliminates manually setting DIP switches and the chance of identical unit number conflicts.
SuperBus 2000 Panels
Advent Concord (software versions 2.0 and later)
SuperBus panels communicate with SuperBus 2000 mod­ules but require the mod ule unit number to first be set man­ually with DIP switches.
SuperBus Panels
UltraGard Concord (software versions 1.0–1.6)
SuperBus® 2000 4-Relay Output Module
Table 1: Module Component Descriptions
Component Function
Unit Number DIP Switches
BUS LED (Red) Flashes to indicate normal
POWER LED (Green)
Output Relays Form C (dry contact) output relays rated
SuperBus 2000 Device ID Number Label
Software Version Label
Wiring Terminals Used for power, bus, and output wiring
Used for manually setting module unit number (SuperBus panels).
communication with the panel. Indicates module power status.
4A @ 24VDC, 4A @ 24VAC, 1A @ 70VAC maximum.
Identifies the unique device ID (SuperBus 2000).
Identifies the installed software version.
connections. All terminals are Class 2 power limited.
1
Installation Guidelines
PRESS DOWN HERE AND PULL AWAY FROM BASE
8557G47B.DS4
Installation Guidelines
For the maximum number of bus devices and
touchpads per panel see Table 2.
Table 2: Maximum Bus Devices Per Panel
Panel Maximum Bus
Devices
Advent 62 UltraGard 8 Concord
(software versions 2.0 and later) Concord
(software versions 1.0–1.6)
(up to eight 4-Relay
Do not exceed the panel total DC output power rating
when using panel power for bus devices and hardwired detectors (see specific panel Installation Instructions).
Do not exceed the maximum wire length from the
panel to the module (see Table 3).
Table 3: Maximum Wire Lengths
Panel Maximum Wire Length
Advent
22 ga. 200 ft./18 ga. 500 ft.
UltraGard 22 ga. 500 ft./18 ga. 1000 ft.
16
16
Output modules)
Installation
The relay output module can be mounted:
On a wall. Inside an Advent cabinet. Inside a Concord cabinet. Inside a SuperBus Module cabinet (60-698). Refer to
the cabinet Installation Instructions for installation procedures.
CAUTION
To prevent damaging the panel or card, disconnect the panel AC Power and backup battery(s) before installation.
CAUTION
You must be free of all static electricity when handling electronic components. Touch a bare metal surface before touching the circuit board.
Mounting the Module
Note
If connecting th e modu le to an UltraGar d panel it must be mounted on a wall. The module will not fit in the UltraGard cabinet.
Mounting the Module on a Wall
Concord
22 ga. 350 ft./18 ga. 900 ft.
When using self or remotely powered devices with an
Advent panel, do not exceed the maximum recom­mended wire length of 4000 feet using 22-gauge or larger wire.
Maximum module current draw with all output s ener-
gized is 180 mA. Each module draws 12 mA typical when outputs are not energized (idle).
Do not exceed the module output relay contact ratings
(
4A @ 24VDC, 4A @ 24VAC, 1A @ 70VAC maximum).
Tools and Supplies Needed
Screwdrivers Drill with bits Wire cutters/strippers 3/8-inch #6-32 self-tapping screws (included) 22-gauge or larger stranded wire (18-gauge or larger
for commercial applications)
1/4-inch press-fit reed switch and magnet (not
included) for cover tamper
1/4-inch #6-32 self tapping screws (not included) for
Advent cabinet mounting
Support standoff (included with Concord cabinet)
1. Remove the module cover and set it aside (Figure 2).
Figure 2. Removing the Cover
2. Place the back-plate on the wall and mark the mount­ing holes (Figure 3).
3. Drill holes and insert appropriate anchors.
4. Secure the back-plate to the wall with included screws.
2
SuperBus® 2000 4-Relay Output Module
Note
MOUNTING HOLES
9
SUPPORT STANDOFF
8573g64A.DSF
PANEL
END
MODULE
END
Installation
Mounting the Module in a Concord Cabinet
1. Remove AC panel power and disconnect the backup battery.
2. Remove and discard the module cover (Figure 2).
3. Insert a support standoff as shown in Figure 5 (sup­plied with panel) into the panel circuit board.
12345
6
MAGNET
CLIP
910111213
REED SWITCH
HOLDER
14 15
18
16
17
9710G02B.DSF
78
Figure 3. Mounting Holes
Mounting the Module in an Advent Cabinet
1. Remove panel AC power and disconnect the backup battery(s).
2. Remove the module cover and set it aside (Figure 2).
3. Turn the module upside down and line up the holes on the back-plate at the desired location (Figure 4).
4. Secure the back-plate to the cabine t using three ¼-inch #6-32 self-tapping screws (not included).
PANEL CABINET
(COVER NOT SHOWN)
Figure 5. Support Standoff
4. Slide the module back-plate onto the two clips located on the top-left corner or center of the cabinet (Figure 6).
The two mounting clips in the top-right corner of the cabinet are designated for a receiver module, but if a receiver module is not being used, the mounting clips may be used for the 4-Relay Output Module.
5. Push the lower-right corner of the module onto the support standoff (see detail in Figure 6).
6. Gently press the module up and onto the cabinet side tab.
USABLE MOUNTING
CLIPS (6)
CARD ON
MODULE
BACK-PLATES
SIDE TAB
MOUNTED MODULE
ROOM FOR 3RD
712G11A.DSF
MODULE
Figure 4. Mounting Module in Advent Cabinet
SuperBus® 2000 4-Relay Output Module
MOUNT WITH
SELF TAPPING
SCREWS
PANEL CABINET
(COVER NOT SHOWN)
9712G08A.DSF
DETAIL
SUPPORT STANDOFF
(Included with Concord
panel accessory package)
Figure 6. Mounting Module in Concord Cabinet
3
Installation
F
)
Wiring
Note
A) Class 2, Class 3, and power-limited fire alarm cir­cuits must be installed using FPL, FPLR, FPLP, or substitute cable permitted by the National Electrical Code ANSI/NFPA 70. Wire that extends beyond the cable jacket m ust be separated f rom all other conduc­tors by a minimum of 1/4-inch or by a nonconductive barrier. OR (B) Class 2, Class 3, and power-limited fire alarm cir­cuit conductors must be installed as Class 1 or higher circuits.
Wiring the Module to a Panel
Important!
On Advent panels, the BUS 1 and BUS 2 headers must be used only for fire or burglary applications. Do not mix fire and burglary bus devices on either header.
Auxiliary power supplies must be power limited.
1. Turn off (or disconnect) the panel power and discon­nect the panel backup battery(s).
2. Wire the module to the panel as shown in Figure 7 and Table 4.
Note
For specific wiri ng details, see the panel
Instructions
.
Installation
ID: XXXXXXXX
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
NO 1
NC 1
COM 1
NO 2
NC 2
COM 2
NO 3
NC 3
COM 3
NO 4
NC 4
COM 4
TO OUTPUT 1
DEVICE
*ALSO OUTPUT AND AUX. SUPPLY
**ALSO OUTPUT AND AUX. SUPPLY GND (COMMON
DEVICE
TO OUTPUT 2
DEVICE
TO OUTPUT 3
DEVICE
TO OUTPUT 4
ZONE 1
+12 VDC
BUS A (GRN)
BUS B (WHT)
GND
**
(BLK)
*
(RED)
TO PANEL SUPERBUS
TERMINALS OR
CONNECTOR
(SEE TABLE)
INPUT DEVICE(S)
Figure 7. General Module Wiring
18
ZONE COM
TO ZONE 1
9710G03A.DS
3. Wire multiple modules in “daisy-chain” fashion (in parallel) to the panel terminals or connector.
Table 4: Module SuperBus/Panel Wiring
Module
Terminals
Advent* Ultra-
Gard
Concord
13 (+12VDC) Red 12 4 14 (BUS A) Green 13 5 15 (BUS B) White 14 6 16 (GND) Black 15 3
* Panel SuperBus device connector wiring harness.
(Connect to either panel connector.)
4. Wire the module outputs as shown in Figures 7 and 8. For specific wiring details, see the device Installation Instructions.
4
SuperBus® 2000 4-Relay Output Module
Installing a Cover Tamper Switch
+
T
Connecting Devices to Outputs
Note
All terminals are Class 2 power limited.
COM 2
COM 1
NC 2
NO 1
NC 1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
NO 2
NC 3
COM 3
NO 3
*
OUTPUT
DEVICE
(N.O. INPUT)
* DO NOT EXCEED RELAY CONTACT VOLTAGE AND CURRENT RATINGS
**
DO NOT EXCEED PANEL +12V POWER CONSUMPTION
LIMITS (SEE PANEL INSTALLATION INSTRUCTIONS)
Figure 8. Module Typical Output Wiring
NC 4
COM 4
12 VDC
NO 4
**
2K OHM
1/2 W
(TYPICAL)
LED
GND
ZONE COM
ZONE 1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
18
NORMALLY
CLOSED
(N/C)
CONTACTS
IN SERIES
< OR >
2.0K Ohm EOL RESISTOR 46-467 (INSTALL AT LAST DEVICE)
18
NORMALLY
OPEN
(N/O)
CONTACTS
IN PARALLEL
9710G04A.DSF
Figure 9. Module Zone Input Wiring
Installing a Cover Tamper Switch
Connecting Devices to the Zone Input
Follow the maximum zone input wire length (run) guide­lines in Table 5 based on the type of wire used.
Important!
For Advent UL-8 64 L iste d In stal lat ions , all inp uts must be dedicated to either fire or burglary applications. Do not mix fire and burglary on
any
module in
any
partition for these installations.
Table 5. Zone Input Wire Runs
Gauge Max. Wire Run*
18 750 Feet 22 300 Feet *Wire run based on 10 ohms maximum wire and
device resistance including 2.0K ohm EOL resistor.
Figure 9 shows an example of how to connect normally closed (N/C) or normally open (N/O) intrusion circuits to the module zone input.
If you are mounting the module in its own plastic or mount­ing it inside a metal cabinet, you must add module tamper detection for UL Listed systems.
To do this, install a UL listed ¼-inch press-fit reed switch on the module back-plate and wire the switch to the modul e zone input terminals or unused panel hardwire input termi­nals. Once programmed, if someone opens the module cover, the tamper switch opens and causes an alarm.
The tamper switch holder is located at the lower-right side of the back-plate as shown in Figure 10. The plastic cover holds the magnet.
MAGNET
MODULE COVER
9712G12A.DSF
MODULE BACK-PLATE
MAGNET CLIP
O ANY ZONE
INPUT
2.0K OHM EOL RESISTOR (49-467)
REED SWITCH
Figure 10. Installing the Reed Switch
SuperBus® 2000 4-Relay Output Module
5
Setting the Module Unit Numbers
To install the tamper reed switch:
1. Slide the reed switch into the holder located on the module back-plate.
2. Insert the reed switch magnet into the nibs on the module cover (not shown). Press the magnet clip (sup­plied) down over the magnet until it clicks into place.
3.
On Advent and Concord (software versions 2.0 and later) Systems:
Connect the normally closed reed switch (in series with a 2.0K ohm [ITI part number 46-467] EOL resis­tor) to the module ZONE 1 (17) and ZONE COM­MON (18) terminals (Figure 9).
On UltraGard Systems:
Connect the reed switch in series with 4.7K ohm (ITI part number 49-365) EOL resistor and to the panel GND and unused panel hardwire zone input terminals.
On Concord (software versions 1.0–1.6) Systems:
Connect the reed switch in series with a 2.0K ohm (ITI part number 46-467) EOL resistor to the panel ZONE COMMON/GND and unused panel hardwire zone input terminals.
UNIT NUMBER 0
ON
M A
1234
567
UNIT NUMBER 3
ON
M A
1234
567
UNIT NUMBER 6
ON
M A
1234
567
UNIT NUMBER 9
ON
M A
1234
567
UNIT NUMBER 12
ON
M A
1234
567
UNIT NUMBER 1
ON
M A
1
234567
8
UNIT NUMBER 4
ON
M A
1
34
2
8
UNIT NUMBER 7
ON
M A
1234
8
UNIT NUMBER 10
ON
M A
1
34
2
8
UNIT NUMBER 13
ON
M A
1
34
2
8
56
56
56
56
UNIT NUMBER 2
ON
M A
1
8
UNIT NUMBER 5
ON
M A
1
8
7
UNIT NUMBER 8
ON
M A
1
8
7
UNIT NUMBER 11
ON
M A
1
8
7
UNIT NUMBER 14
ON
M A
1
8
7
3
2
234567
34
2
234567
234567
UNIT NUMBER 15--Do not use in Concord RF system s.
ON
M A
1234
567
8
9712G09A.DSF
4
567
56
8
8
8
7
8
8
Setting the Module Unit Numbers
On Concord (software version 2.0 or later) and Advent Panels
Locate the DIP switches on the module circuit boar d and set all switches to “A” (for automatic). The unit number will be automatically set when powering up the system.
On Concord (software versions 1.0–1.6) and UltraGard Panels
Note
Concord panels with software versions 1.0–1.6 will only recognize 4- Rela y Out put mod ules with u nit nu m­bers set from 0 to 7.
Locate the DIP switches on the module circuit board. Set switch 1 to “M” (on for manual). Set the remaining switches for the desired unit number (Figure 1 1).
Unit Number 0-7 for UltraGard Unit Number 0-7 for Concord (software versions 1.0–
1.6)
Figure 11. Module Unit Number DIP Switch Settings
(Non-SuperBus 2000 systems)
Power Up and Bus Communication
This section describes how to power up the panel and the module for both new and existing installations.
Advent and Concord Panels
New Installations
1. Verify that all wiring between the panel, touchpad and module is correct.
2. Connect the panel battery(s) and restore panel AC power. Alphanumeric touchpad displays should come on.
3. Both the green and red LEDs will turn on for one sec­ond. The green POWER LED will remain on and the red BUS status LED should flash to indicate success­ful communication with the panel.
Note
If the green POWER LED is not on or t he red BUS status LED does not flash, remove AC panel power, disconnect the battery(s), and see Table 6 “Trouble­shooting.”
6
Existing Installations
Concord Panels- Same as new installation. Advent Panels-
1. Verify that all wiring between the panel and modu le is correct.
SuperBus® 2000 4-Relay Output Module
Programming and Testing
2. Connect the panel battery(s) and restore panel AC power. Alphanumeric touchpad displays should come on. Both the green and red LEDs turn on for one sec­ond, then the green POWER LED will remain on.
3. Press 8 for System Menu.
4. Press 0 for Program Menu.
5. Enter your Install Code (default 0123).
6. Enter Item Number 48001 to add SuperBus 2000 devices. All installed devices are automatically added (learned) into panel memory when Devices Added is indicated.
7. Press * twice to return to the Main Menu.
8. The red BUS status LED should flash to indicate suc­cessful communication with the panel.
Note
If the green POWER LED is not on or th e red BUS status LED does not f lash, remove AC pane l power, disconnect t he battery(s), and see Table 6 “Trouble­shooting.”
UltraGard Panels
1. Verify that all wiring at the panel an d the module is correct.
2. Verify nonconflicting bus unit number settings.
3. Connect the panel battery a nd rest ore pa nel AC pow er.
4. Turn on the panel AC power.
5. Set the
UltraGard
panel RUN/PROGRAM switch to
PROGRAM.
If the alphanumeric touchpad displays 1-OFF and the 1 is flashing, you must enter the 4-digit installer access code to get the panel into program mode.
Alphanumeric touchpads should display PROGRAM MODE and the red BUS status LED on the module should be flashing continuously, indicating successful communica­tion to the panel.
Note
If the green POWER LED is not on or th e red BUS status LED does not flash, set the RUN/PROGRAM switch (UltraGard) to RUN, remove AC panel power, disconnect the backup battery, and see Table 6 “Trou­bleshooting.”
Programming and Testing
Refer to the specific panel Installation Instructions for configuring module outputs, adding (learning) hardwire sensors, and testing.
Troubleshooting
Use the following table to determine possible solutions to module problems.
Table 6: Troubleshooting
Problem Solution
The green POWER LED stays off.
The red BUS LED doesn’t flash to indicate communication with the panel.
Output(s) activate only momentarily, activate randomly, or module and/or touchpads lock up.
Module Zone input is inoperable. (UltraGard & Concord)
One output stays activated.
1. Check for incorrect wiring con­nections.
2. Make sure panel AC powe r is applied and the backup battery(s) are connected.
3. If the LED still remains off, replace the module.
1. Verify that the panel recognizes the module by entering program mode (see specific panel Installa- tion Instructions).
2. Check for incorrect wiring con­nections.
3. For Concord (software versions
1.0–1.6) and UltraGard panels make sure that module DIP switch 1 is set to “M.” For Concord (soft­ware versions 2.0 or later) and Advent panels make sure that module DIP switch 1 is set to “A.”
4. If the LED still doesn’t flash, replace the module.
1. For Concord (software versions
1.0–1.6) and UltraGard systems, check for bus devices with the same unit number setting.
2. Re-initialize the panel by discon­necting and reconnecting panel power.
3. Verify that the output/point is con­figured correctly (see specific panel Installation Instructions).
4. Make sure the zone has been “learned” into panel memory.
5. Verify that the panel recognizes the module by entering program mode (see specific panel Installa- tion Instructions).
6. Check module/panel wire routing and length.
7. Replace the module.
1. Some panels and panel versions do not read the module built-in zone input status. Use a panel zone input instead.
1. Check if the point is programmed for a 3 minute “on” time and if the triggering event for the point is repeatedly “resetting” the 3 minute timer (see specific panel Installation Instructions).
2. Output may have failed or been overloaded. Reprogram using a different (unused) module output or replace the module.
SuperBus® 2000 4-Relay Output Module
7
Specifications
Specifications
Compatibility: Advent, Concord, and UltraGard Power Requirements: 12V nominal, 12 mA typical (idle ), 180
mA maximum (all relays energized)
Inputs: One supervised, fire-rated, hardwire
zone
Outputs: Four, panel prog rammab le outputs wi th
“Form-C” relay contacts (COMMON, N/C, N/O). Relay contacts rated 4A @
24VDC, 4A @ 24VAC, 1A @ 70VAC maximum.
Storage Temperature: -30° to 140° F (-34° to 60° C) Operating Temperature: 32° to 140° F (0° to 60° C), up to 140°
F (60° C) under temporary
conditions Maximum Humidity: 90% relative humidity, non-condensing Dimensions: 5.25" x 4.125" x 1.0" (L x W x D) Color: Belgian grey Case Material: High-impact ABS plastic Installation: On wall or in panel cabinet
mounting Listings (for ancillary use only):
Notices
FCC Part 15 Information to the User
Changes or modifications not expressly approved by Interactive Technologies, Inc. can void the user’s authority to operate the equipment.
FCC Part 15 Class A
This equipment has been tested and found to comply with the limits for a class A digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case users will be required to correct the interference at their own expense.
FCC Part 15 Class B
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against interference in a residential installation.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interfer­ence to radio communications. However, there is no guarantee that interference will not occur in a particular installation.
If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encour­aged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna. Increase the separation between the equipment and receiver. Connect the affected equipment and the panel receiver to separate outlets,
on different branch circuits.
Consult the dealer or an experienced radio/TV technician for help.
UL 365 Police Station Connected
Burglar Alarm Units and Systems
UL 609 Local Burglar Alarm Units and
Systems
UL 864 Control Units for Fire
Protective Signaling Devices
UL 985 Household Fire Warning
System Units
UL 1023 Household Burglar Alarm
System Units
UL 1610 Central St ation Bur gla r Alarm
Units (Commercial Burglary)
UL 1637 Home Health Care Signaling
Equipment
CSFM California State Fire Marshall
(applied for)
FM Factory Mu tual (applied for)
MEA New York City Material
Equipment Acceptance (applied for)
DOD Sensitive Compartment
Informati on Fac. (appli ed for)
ULC Canada Commercial
Fire/Burglary Warning (applied for)
Note
See specific panel
Installation In st ruct ions
for complete UL installation requirements for the system you are installing.
2266 Second Street North North Saint Paul, MN 55109-2900 T: 651/777-2690 F: 651/779-4890 1-800-777-1415 www.itii.com
©2000 Interlogix Inc. Interlogix and Concord are trademarks of Interlogix, Inc. ITI, Advent, UltraGard, and SuperBus are registered trade­marks of Interlogix, Inc.
8
SuperBus® 2000 4-Relay Output Module
Loading...