Itelco-Clima units MQL4, MQL8M, MQL8T, MQL10M, MQL10T Installation And Maintenance Manual

...
English
Air cooled water chillers and air-to-water reverse cycle heat pumps
Refroidisseurs de liquide à condensation par air et pompes à chaleur réversibles air-eau
Installation and maintenance manual Manuel d’installation et de maintenance
IOM MQLH-N.1GBF
MQL/MQH 4 ÷ 17
4.5
16.5 kW
4.6
18.4 kW
Français
Page 1
Table of contents
English
1 FOREWORD
1.1 Introduction 2
1.2 Warranty 2
1.3 Emergency stop/Normal stop 2
1.4 An introduction to this manual 2
2 SAFETY
2.1 Foreword 3
2.2 Definitions 3
2.3 Access to the unit 4
2.4 General precautions 4
2.5 Precautions against residual risks 4
2.6 Precautions during maintenance operations 5
2.7 Safety labels 6
2.8 Safety regulations 7
3 TRANSPORT, LIFTING
AND POSITIONING
3.1 Inspection 10
3.2 Unit Handling 10
3.3 Anchoring 10
3.4 Storage 10
4 INSTALLATION
4.1 Installation advices 11
4.2 Water connections 13
4.3 Pressure Drop in Tubes and Accessories 14
4.4 Hydraulic connection 14
4.5 Principle diagram of water circuit
4.6 Draining the defrosting waste water (for heat pump unit only) 14
4.7 Power supply 15
4.8 Electrical connections 15
5 START-UP
5.1 Preliminary check 16
5.2 Start-up 16
5.3 Checking the operation 17
5.4 Delivery to the customer 17
6 MINICHILLER CONTROL
6.1 Operating instructions 18
6.2 Failure Diagnostics 19
7 GENERAL DESCRIPTION
7.1 Introduction 20
7.2 General specifications 20
7.3 Compressors 21
7.4 Coolant Circuit 21
7.5 Water-exchanger 21
7.6 Air exchanger 21
7.7 Fans 21
8 TECHNICAL DATA
8.1 Technical Data 24
8.2 Unit Electrical Data 28
8.3 Overall dimensions 30
8.4 Clearances 31
9 MAINTENANCE
9.1 General requirements 32
9.2 Planned maintenance 32
9.3 Refrigerant charge 33
9.4 Compressor 33
9.5 Condenser 33
9.6 Fans 33
9.7 Dehydrating filter 33
9.8 Thermostatic expansion valve (only MQL-MQH 4-8) 34
9.9 Evaporator 34
10 TROUBLESHOOTING 35 11 SPARE PARTS
11.1 Spare parts list 37
11.2 Oil for compressors 37
11.3 Wiring diagram 37
12 DISMANTLING, DEMOLITION
AND SCRAPPING
12.1 Generalities 38
Table of contents
Manuale MQL-MQH 10.6.2005 12:25 Pagina 1
Page 2
Foreword
1 FOREWORD
1.1 Introduction
Itelco-Clima units, manufactured to state-of-the-art de­sign and implementation standards, ensure top per­formance, reliability and fitness to any type of air­conditioning system.
These units are designed for cooling water or gly­coled water* (and for water heating in heat pump models) and are unfit for any purposes other than those specified in this manual.
This manual includes all the information required for a proper installation of the units, as well as the rele­vant operating and maintenance instructions.
It is therefore recommended to read this manual carefully before installation or any operation on the machine. The chiller installation and maintenance must be carried out by skilled personnel only (where possible, by one of Itelco-Clima’s Authorised Service Centers).
The manufacturer may not be held liable for any damage to people or property caused by improper installation, start-up and/or improper use of the unit and/or failure to implement the procedures and in­structions included in this manual.
1.2 Warranty
These units are delivered complete, tested and ready for being operated. Any form of warranty will be­come null and void in the event that the appliance is modified without Itelco-Clima’s preliminary written authorisation.
This warranty shall apply providing that the installa­tion instructions have been complied with (either is­sued by Itelco-Clima, or deriving from the current practice).
In order for this warranty to be valid, the following conditions shall be met:
h
Maintenance must be performed only by skilled personnel - from one of Itelco-Clima’s Authorised After-Sales Centers.
h
Use only original Itelco-Clima spare parts.
h
Carry out all the planned maintenance provided for by this manual in a timely and proper way.
Failure to comply with any of these conditions will automatically void the warranty.
1.3 Emergency stop / Normal stop
The emergency stop of the unit can be enabled using the master switch on the control panel (move down the lever).
For a normal stop, press the relevant push-buttons. To restart the appliance, follow the procedure de-
tailed in this manual.
1.4 An introduction to the manual
For safety reasons, it is imperative to follow the in­structions given in this manual. In case of any dam­age caused by non-compliance with these instruc­tions, the warranty will immediately become null and void.
Conventions used throughout the manual:
The Danger sign recalls your attention to a certain procedure or practice which, if not followed, may result in serious damage to people and property.
The Warning sign precedes those proce­dures that, if not followed, may result in seri­ous damage to the appliance.
The Notes contain important observations.
The Useful Tips provide valuable informa­tion that optimises the efficiency of the ap­pliance.
This manual and its contents, as well as the docu­mentation which accompanies the unit, are and re­main the property of Itelco-Clima, which reserves any and all rights thereon. This manual may not be copied, in whole or in part, without Itelco-Clima’s written authorization.
USEFUL TIPS
*Note: minimum leaving water temperature from evapo-
rator: + 5°C.
Manuale MQL-MQH 10.6.2005 12:25 Pagina 2
Page 3
English
Safety
2 SAFETY
2.1 Foreword
These units must be installed in conformity with the provisions of Machinery Directive 98/37/EC, Low Voltage Directive 73/23/EC, Pressure Vessels Direc­tive 97/23/EC, Electromagnetic Interference Direc­tive 89/336/EC, as well as with other regulations applicable in the country of installation. If these pro­visions are not complied with, the unit must not be operated.
The unit must be grounded, and no installa­tion and/or maintenance operations may be carried out before deenergising the elec­trical panel of the unit.
Failure to respect the safety measures mentioned above may result in electrocution hazard and fire in the presence of any short-circuits.
Inside the heat exchangers, the compres­sors and the refrigeration lines, this unit contains liquid and gaseous refrigerant un­der pressure. The release of this refrigerant may be dangerous and cause injuries.
The units are not designed to be operated with natural refrigerants, such as hydrocar­bons. Itelco-Clima may not be held liable for any problems deriving from the replace­ment of original refrigerant or the introduc­tion of hydrocarbons.
Itelco-Clima units are designed and manufactured according to the requirements of European Standard PED 97/23/EC (pressure vessels).
– The used refrigerants are included in group II (non-
hazardous fluids).
– The maximum working pressure values are men-
tioned on the unit’s data plate.
– Suitable safety devices (pressure switches and safe-
ty valves) have been provided, to prevent any anomalous overpressure inside the plant.
– The vents of the safety valves are positioned and
oriented in such a way as to reduce the risk of con­tact with the operator, in the event that the valve is operated. Anyway, the installer will convey the dis­charge of the valves far from the unit.
– Dedicated guards (removable panels with tools)
avoid contacts with potential dangerous zones.
.
The guards of the fans must be always mounted and must never be removed be­fore de-energising the appliance.
It is the User’s responsibility to ensure that the unit is fit for the conditions of intended use and that both installation and mainte­nance are carried out by experienced per­sonnel, capable of respecting all the recom­mendations provided by this manual. It is important that the unit is adequately sup­ported, as detailed in this manual. Non­compliance with these recommendations may create hazardous situations for the personnel.
The unit must rest on a base which meets the characteristics specified in this manual; a base with inadequate characteristics is likely to become a source of serious injury to the personnel.
The unit has not been design to withstand loads and/or stress that may be transmitted by adjacent units, piping and/or structures. Each external load or stress transmitted to the unit may break or cause breakdowns in the unit’s structure, as well as serious dan­gers to people. In these cases, any form of warranty will automatically become null and void.
The packaging material must not be dis­posed of in the surrounding environment or burnt.
2.2 Definitions
OWNER: means the legal representative of the com­pany, body or individual who owns the plant where Itelco-Clima unit has been installed; he/she has the responsibility of making sure that all the safety regu­lations specified in this manual are complied with, along with the national laws in force.
INSTALLER: means the legal representative of the company who has been given by the owner the job of positioning and performing the hydraulic, electric and other connections of Itelco-Clima unit to the plant: he/she is responsible for handling and prop­erly installing the appliance, as specified in this man­ual and according to the national regulations in force.
Manuale MQL-MQH 10.6.2005 12:26 Pagina 3
Page 4
Safety
OPERATOR: means a person authorised by the own­er to do on Itelco-Clima unit all the regulation and control operations expressly described in this manu­al, that must be strictly complied with, without ex­ceeding the scope of the tasks entrusted to him.
ENGINEER: means a person authorised directly by Itelco-Clima or, in all EC countries, excluding Italy, under his full responsibility, by the distributor of Itel­co-Clima product, to perform any routine and extra­ordinary maintenance operations, as well as any regulation, control, servicing operations and the re­placement of pieces, as may be necessary during the life of the unit.
2.3 Access to the unit
The unit must be placed in an area which can be ac­cessed also by OPERATORS and ENGINEERS; oth­erwise the unit must be surrounded by a fence at not less than 2 meters from the external surface of the machine.
OPERATORS and ENGINEERS must enter the fenced area only after wearing suitable clothing (safety shoes, gloves, helmet etc.). The INSTALLER personnel or any other visitor must always be accompanied by an OPERATOR.
For no reason shall any unauthorised personnel be left alone in contact with the unit.
2.4 General precautions
The OPERATOR must simply use the controls of the unit; he must not open any panel, other than the one providing access to the control module.
The INSTALLER must simply work on the connections between plant and machine; he must not open any panels of the machine and he must not enable any control.
When you approach or work on the unit, follow the precautions listed below:
h
do not wear loose clothing or jewellery or any oth­er accessory tat may be caught in moving parts
h
wear suitable personal protective equipment (gloves, goggles etc.) when you have to work in the presence of free flames (welding operations) or with compressed air
h
if the unit is placed in a closed room, wear ear pro­tection devices
h
cut off connecting pipes, drain them in order to balance the pressure to the atmospheric value be­fore disconnecting them, disassemble connections, filters, joints or other line items
h
do not use your hands to check for any pressure drops
h
use tools in a good state of repair; be sure to have understood the instructions before using them
h
be sure to have removed all tools, electrical cables and any other objects before closing and starting the unit again
2.5 Precautions against residual risks
Prevention of residual risks caused by the control system
h
be sure to have perfectly understood the operating instructions before carrying out any operation on the control panel
h
when you have to work on the control panel, keep always the operating instructions within reach
h
start the unit only after you have checked its perfect connection to the plant
h
promptly inform the ENGINEER about any alarm involving the unit
h
do not reset manual restoration alarms unless you have identified and removed their cause
Prevention of residual mechanical risks
h
install the unit according to the instructions provid­ed in this manual
h
carry out all the periodical maintenance opera­tions prescribed by this manual
h
before opening any panelling of the machine, make sure that it is secured to it by hinges
h
do not touch air condensation coils without wear­ing protective gloves
h
do not remove the guards from moving elements while the unit is running
h
check the correct position of the moving elements’ guards before restarting the unit
Prevention of residual electrical risks
h
connect the unit to the mains according to the in­structions provided in this manual
h
periodically carry out all the maintenance opera­tions specified by this manual
h
disconnect the unit from the mains by the external disconnecting switch before opening the electrical board
h
check the proper grounding of the unit before start­up
h
check all the electrical connections, the connecting cables, and in particular the insulation; replace worn or damaged cables
Manuale MQL-MQH 10.6.2005 12:26 Pagina 4
Page 5
English
Safety
h
periodically check the board’s internal wiring
h
do not use cables having an inadequate section or flying connections, even for limited periods of time or in an emergency
Prevention of other residual risks
h
make sure that the connections to the unit conform to the instructions provided in this manual and on the unit’s panelling
h
if you have to disassemble a piece, make sure that it has been properly mounted again before restart­ing the unit
h
do not touch the delivery pipes from the compres­sor, the compressor and any other piping or com­ponent inside the machine before wearing protec­tive gloves
h
keep a fire extinguisher fir for electrical appliances near the machine
h
on the units installed indoor, connect the safety valve of the refrigeration circuit to a piping net­work that can channel any overflowing refrigerant outside
h
remove and leak of fluid inside and outside the unit
h
collect the waste liquids and dry any oil spillage
h
periodically clean the compressor compartment, to remove any fouling
h
do not store flammable liquids near the unit
h
do not disperse the refrigerant and the lubricating oil into the environment
h
weld only empty pipes; do not approach flames or other sources of heat to refrigerant pipes
h
do not bend/hit pipes containing fluids under pres­sure
2.6 Precautions during maintenance operations
Maintenance operations can be carried out by au­thorised technicians only. Before performing any maintenance operations:
h
disconnect the unit from the mains with the external disconnecting switch
h
place a warning sign “do not turn on - mainte­nance in progress” on the external disconnecting switch
h
make sure that on-off remote controls are inhibited
h
wear suitable personal protective equipment (hel­met, safety gloves, goggles and shoes etc.)
To carry out any measurements or checks which re­quire the activation of the machine:
h
work with the electrical board open only for the necessary time
h
close the electrical board as soon as the measure­ment or check has been completed
h
for outdoor units, do not carry out any operations in the presence of dangerous climatic conditions (rain, snow, mist etc.)
The following precautions must be always adopted:
h
do not scatter the fluids of the refrigeration circuit in the surrounding environment
h
when replacing an eprom or electronic cards, use always suitable devices (extractor, antistatic bracelet, etc.)
h
o replace a compressor, the evaporator, the con­densing coils or any other weighty element, make sure that the lifting equipment is consistent with the weight to be lifted
h
in air units with independent compressor compart­ment, do not access the fan compartment unless you have disconnected the machine by the discon­necting switch on the board and you have placed a warning sign “do not turn on - maintenance in progress”
h
contact Itelco-Clima for any modifications to the re­frigeration, hydraulic or wiring diagram of the unit, as well as to its control logics
h
contact Itelco-Clima if it is necessary to perform very difficult disassembly and assembly operations
h
use only original spare parts purchased directly from Itelco-Clima or the official retailers of the com­panies on the recommended spare parts list
h
contact Itelco-Clima if it is necessary to handle the unit one year after its positioning on site or if you wish to dismantle it.
Manuale MQL-MQH 10.6.2005 12:26 Pagina 5
Page 6
Grounding connection - On the electrical
board, adjacent to the connection
Final Test Certificate -
Inside the external door
Fitting identification -
Adjacent to fittings
EIN - INLET
ENTRÉE - ENTRATA
AUS - OUTLET
SORTIE - USCITA
Safety
2.7 Safety labels
The labels below will be affixed to each unit in the indicated point:
Identification of the unit -
Outside, on the right-hand front column
Electrical warning
Adjacent to the master switch
Manuale MQL-MQH 10.6.2005 12:26 Pagina 6
Page 7
Safety
2.8 Safety regulations
English
Refrigerant data
Toxicity Low Contact with skin If sprayed, the refrigerant is likely to cause frost burns. If absorbed by
the skin, the danger is very limited; it may cause a slight irritation, and the liquid is degreasing. Unfreeze the affected skin with water. Remove the contaminated clothes with great care - in the presence of frost burns, the clothes may stick to the skin. Wash with plenty of warm wa­ter the affected skin. In the presence of symptoms such as irritation or blisters, obtain med­ical attention.
Contact with eyes
Ingestion
Inhalation
Recommendations
Prolonged exposure
Vapours do not cause harmful effects. The spraying of refrigerant may cause frost burns. Wash immediately with a proper solution or with tap water for at least 10 minutes, and then obtain medical attention.
Very unlikely - should something happen, it will cause frost burns. Do not induce vomiting. Only if the patient is conscious, wash out mouth with water and give some 250 ml of water to drink. Then, obtain medical attention.
R407C: remarkable concentrations in the air may have an anaesthetic effect, up to fainting. The exposure to considerable amounts may cause irregular heartbeat, up to the sudden death of the patient. Very high concentrations may result in the risk of asphyxia, due to the reduction in the oxygen percentage in the atmosphere. Remove the patient to fresh air and keep warm and at rest. If necessary, give oxygen. In case of breathing difficulties or arrest, pro­ceed with artificial respiration. In case of cardiac arrest, proceed with cardiac massage. Then, obtain medical attention.
Semiotics or support therapy is recommended. Cardiac sensitisation has been observed that, in the presence of circulating catecholamines such as adrenalin, may cause cardiac arrhythmia and accordingly, in case of exposure to high concentrations, cardiac arrest.
R407C: a study on the effects of exposure to 50,000 ppm during the whole life of rats has identified the development of benign testicle tu­mour. This situation should therefore be negligible for personnel ex-
posed to concentrations equal to or lower than professional levels. Professional levels Stability R407C: Not specified
R407C: Recommended threshold: 1000 ppm v/v - 8 hours TWA.
Conditions to avoid Do not use in the presence of flames, burning surfaces and excess hu-
midity.
Safety data: R407C
Hazardous reactions May react with sodium, potassium, barium and other alkaline metals.
Incompatible substances: magnesium and alloys with magnesium con-
centrations > 2%. Hazardous decomposition
products
R407C: Halogen acids produced by thermal decomposition and hy-
drolysis.
Manuale MQL-MQH 10.6.2005 12:26 Pagina 7
Page 8
Safety
Respiratory system protection
Storage
Protective clothing Accidental release measures
Disposal
Fire fighting information Cylinders
Protective fire fighting equipment
If you are in doubt about the concentration in the atmosphere, it is rec-
ommended to wear a respirator approved by an accident-prevention
Authority, of the independent or oxygen type.
Cylinders must be stored in a dry and fresh place, free from any fire
hazard, far from direct sunlight or other sources of heat, radiators etc.
Keep a temperature below 45°C.
Wear overalls, protective gloves and goggles or a mask.
It is important to wear protective clothing and a respirator. Stop the
source of the leak, if you can do this without danger. Negligible leaks
can be left evaporating under the sun, providing that the room is well
ventilated. Considerable leaks: ventilate the room. Reduce the leak with
sand, earth or other absorbing substances. Make sure that the liquid
does is not channelled into gutters, sewers or pits where the vapours
are likely to create a stuffy atmosphere.
The best method is recovery and recycling. If this method is not practi-
cable, dispose according to an approved procedure, that shall ensure
the absorption and neutralization of acids and toxic agents.
R407C: Not flammable in the atmosphere.
In case of fire, wear an independent respirator and protective clothing.
The cylinders, if exposed to fire, shall be cooled by water jets; other-
wise, if heated, they may explode.
Do not inhale concentrated vapours. Their concentration in the atmos-
phere should not exceed the minimum preset values and should be
maintained below the professional threshold. Being more weighty than
the air, the vapour concentrates on the bottom, in narrow areas. There-
fore, the exhaust system must work at low level.
General precautions
Manuale MQL-MQH 10.6.2005 12:26 Pagina 8
Page 9
English
Safety
Refrigerant oil data Safety data: Polyolester oil (POE)
Classification Contact with skin
Contact with eyes Ingestion Inhalation Conditions to avoid
Protection of the respiratory system
Protective clothing
Accidental release measures
Disposal
Fire fighting information
Cylinders
Fire fighting protective equipment
Not harmful
May cause slight irritation. Does not require first aid measures. It is rec-
ommended to follow usual personal hygiene measures, including wash-
ing the exposed skin with soap and water several times a day. It is also
recommended to wash your overalls at least once a week.
Wash thoroughly with a suitable solution or tap water.
Seek medical advice immediately.
Seek medical advice immediately.
Strong oxidising substances, caustic or acid solutions, excess heat.
May corrode some types of paint or rubber.
Use in well ventilated rooms.
Always wear protective goggles or a mask. Wearing protective gloves
is not mandatory, but is recommended in case of prolonged exposure
to refrigerant oil.
It is important to wear protective clothing and, especially, goggles.
Stop the source of the leak. Reduce the leak with absorbing substances
(sand, sawdust or any other absorbing material available on the mar-
ket).
The refrigerant oil and its waste will be disposed of in an approved in-
cinerator, in conformity with the provisions and the local regulations
applicable to oil waste.
In the presence of hot liquid or flames, use dry powder, carbon dioxide
or foam. If the leak is not burning, use a water jet to remove any
vapours and to protect the personnel responsible for stopping the leak.
The cylinders exposed to a fire will be cooled with water jets in case of
fire.
In case of fire, wear an independent respirator.
Manuale MQL-MQH 10.6.2005 12:26 Pagina 9
3 TRANSPORT, LIFTING
AND POSITIONING
Refrigerators are supplied assembled. The equip­ment are full of refrigerant and oil (except to the con­densing unit), in the quantity required for a proper operation.
3.1 Inspection
When the unit is delivered, it is recommended to check it carefully and to identify any damage oc­curred during transportation. The goods are shipped ex-factory, at the buyer’s risk. Check that the delivery includes all the components listed in the order.
In case of damage, note it down on the carrier’s de­livery note and issue a claim according to the instruc­tions provided in the delivery note.
In the presence of any serious damage, that does not affect the surface only, it is recommended to inform Itelco-Clima immediately.
Please note that Itelco-Clima may not be held liable for any damage to the equipment during transporta­tion, even though the carrier has been appointed by the factory.
3.2 Unit Handling
Sharp edges and coil surfaces are a poten­tial hazard. Avoid contact with them.
Be careful to avoid rough handling of the unit. Do not push or pull the unit anything other than the base. Block the pushing vehicle away from the unit to prevent damage to the sheet metal cabinet and end frame (see picture 1).
Page 10
3.3 Anchoring
It is not essential to secure the unit to the foundations, unless in areas where there is a serious risk of earth­quake, or if the appliance is installed on the top of a steel frame.
3.4 Storage
When the unit is to be stored before installation, adopt a few precautions to prevent any damage or risk of corrosion or wear:
h
plug or seal every single opening, such as water fittings
h
do not store the appliance in a room where the temperature exceeds 50°C for the units using R407C and, if possible, do not expose to direct sunlight
h
it is recommended to store the unit in a roof where traffic is minimized, to prevent the risk of acciden­tal damage
h
the unit must not be washed with a steam jet
h
take away and leave to the site manager all the keys providing access to the control board
Finally, it is recommended to carry out visual inspec­tions at regular intervals.
Transport, Lifting and Positioning
Blocking required across (full width)
Picture 1
Manuale MQL-MQH 10.6.2005 12:26 Pagina 10
Page 11
English
Installation
4 INSTALLATION
4.1 Installation advices
Unit placement
The MQL/MQH water chillers are cooled by air. Thereby, they must be installed in the open air, in an area where the flow of air to and from the con­denser coil must not be limited. A space restriction, which reduces the air flow, will decrease the cool­ing capacity, increase the power input and, in some cases, prevent the unit from operating because of an excess of condensation pressure.
The MQL/MQH water chillers are equipped with propeller type condenser fan. Therefore, they will not operate with ductwork on the fan outlet.
In case of installation in an area subject to be hit by strong wind, direct effect of the wind on the dis­charge surface of the fan should be avoided.
Care should be taken, at the time of installation, to leave enough clearances around the unit for mainte­nance works.
The minimum clearances are shown on picture 2 and must be considered, both to ensure that the unit operates correctly and to allow easy access.
Picture 2
MQL
The units should be installed on a flat and hard, preferably concrete base.
When fixing the unit, a slope of 1 cm/m is recom­mended to allow draining of rain water.
Units MQL/MQH 4 and 6 cannot be installed with advanced inclination to 10°.
For reverse cycle models, if the outdoor temperature is likely to fall below +1 °C, provide a system to prevent the condensates from freezing (e.g. heating cord).
For installation in difficult climates, temperatures below 0 °C, snow or humidity, it is recommended to elevate the unit about 20 cm above the floor.
The plastic grille is used to protect the operators from injury risks on heat exchanger at the time of handling and installation. However, risks of clogging by freeze or hoar frost can be occured on reverse cycle units installed in cold or mountainous regions and exposed to the elements. To prevent all risks, a shelter is to be pro­vided or simply remove the protective grille.