ITech IT8511+, IT8512C+, IT8512A+, IT8512B+, IT8511A+ User Manual

...
DC Programmable Electronic
Loads
Series IT8500plus Users Manual
Model:IT8511+/
+/IT8512B+/IT8512C+/IT8512H+/IT8513A+/IT8513C +
/IT8514C+/IT8514B+/IT8516C+
Version:2.0
IT8511A+/IT8511B+/IT8512+/IT8512A
Notices
© Itech Electronic, Co., Ltd. 2015 No part of this manual may be reproduced in any form or by any means (including electronic storage and retrieval or translation into a foreign language) without prior permission and written consent from Itech Electronic, Co., Ltd. as governed by international copyright laws.
Manual Part Number
IT8500+-402008
Revision
Second Edition: May 09, 2017
Itech Electronic, Co., Ltd.
Trademarks
Pentium is U.S. registered trademarks of Intel Corporation.
Microsoft, Visual Studio, Windows and MS Windows are registered trademarks of Microsoft Corporation in the United States and/or other countries and regions.
Warranty
The materials contained in this document are provided as is, and is subject to change, without prior notice, in future editions. Further, to the maximum extent permitted by applicable laws, ITECH disclaims all warrants, either express or implied, with regard to this manual and any information contained herein, including but not limited to the implied warranties of merchantability and fitness for a particular purpose. ITECH shall not be held liable for errors or for incidental or indirect damages in connection with the furnishing, use or application of this document or of any information contained herein. Should ITECH and the user enter into a separate written agreement with warranty terms covering the materials in this document that conflict with these terms, the warranty terms in the separate agreement shall prevail.
Technology Licenses
The hardware and/or software described herein are furnished under a license and may be used or copied only in accordance with the terms of such license.
Safety Notices
A CAUTION sign denotes a hazard. It calls attention to an operating procedure or practice that, if not correctly performed or adhered to, could result in damage to the product or loss of important data. Do not proceed beyond a CAUTION sign until the indicated conditions are fully understood and met.
A WARNING sign denotes a hazard.
It calls attention to an operating procedure or practice that, if not correctly performed or adhered to, could result in personal injury or death. Do not proceed beyond a WARNING sign until the indicated conditions are fully understood and met.
Restricted Rights Legend
Restricted permissions of the U.S. government. Permissions for software and technical data which are authorized to the U.S. Government only include those for custom provision to end users. ITECH follows FAR 12.211 (technical data), 12.212 (computer software). DFARS 252.227-7015 (technical data--commercial products) for national defense and DFARS 227.7202-3 (permissions for commercial computer software or computer software documents) while providing the customized business licenses of software and technical data.
NOTE
A NOTE sign denotes important hint. It calls attention to tips or supplementary information that is essential for users to refer to.
IT8500+ Users Manual
Direct current
ON (power on)
Alternating current
OFF (power off)
Both direct and alternating current
Power-on state
Protective conductor terminal
Power-off state
Earth (ground) terminal
Reference
Caution, risk of electric shock
Positive terminal
Warning, risk of danger (refer to this manual for specific Warning or Caution information)
Negative terminal
Frame or chassis terminal
-
-

Quality Certification and Assurance

We certify that series IT8500+ electronic load meets all the published specifications at time of shipment from the factory.

Warranty

ITECH warrants that the product will be free from defects in material and workmanship under normal use for a period of one (1) year from the date of delivery (except those described in the Limitation of Warranty below).
For warranty service or repair, the product must be returned to a service center designated by ITECH.
The product returned to ITECH for warranty service must be shipped
PREPAID. And ITECH will pay for return of the product to customer.
If the product is returned to ITECH for warranty service from overseas, all
the freights, duties and other taxes shall be on the account of customer.

Limitation of Warranty

This Warranty will be rendered invalid in case of the following: Damage caused by circuit installed by customer or using customer own
products or accessories;
Modified or repaired by customer without authorization; Damage caused by circuit installed by customer or not operating our
products under designated environment;
The product model or serial number is altered, deleted, removed or made
illegible by customer;
Damaged as a result of accidents, including but not limited to lightning,
moisture, fire, improper use or negligence.

Safety Symbols

Copyright © Itech Electronics Co., Ltd. i
terminal
IT8500+ Users Manual

Safety Precautions

The following safety precautions must be observed during all phases of operation of this instrument. Failure to comply with these precautions or specific warnings elsewhere in this manual will constitute a default under safety standards of design, manufacture and intended use of the instrument. ITECH assumes no liability for the customers failure to comply with these precautions.
Series IT8500+ electronic load supports 110V/220VAC input and need to
switch the input voltage before operation.
Do not use the instrument if it is damaged. Before operation, check the
casing to see whether it cracks. Do not operate the instrument in the presence of inflammable gasses, vapors or dusts.
The electronic load is provided with a three-core power line during delivery
and should be connected to a three-core junction box. Before operation, be sure that the instrument is well grounded.
Make sure to use the power cord supplied by ITECH. Check all marks on the instrument before connecting the instrument to
power supply.
Use electric wires of appropriate load. All loading wires should be capable
of bearing maximum short-circuit current of electronic load without overheating. If there are multiple electronic loads, each pair of the power cord must be capable of bearing the full-loaded rated short-circuit output current
Ensure the voltage fluctuation of mains supply is less than 10% of the
working voltage range in order to reduce risks of fire and electric shock.
Do not install alternative parts on the instrument or perform any
unauthorized modification.
Do not use the instrument if the detachable cover is removed or loosen. To prevent the possibility of accidental injuries, be sure to use the power
adapter supplied by the manufacturer only.
Never use the instrument with a life-support system or any other equipment
subject to safety requirements.
Failure to use the instrument as directed by the manufacturer may render
its protective features void.
Always clean the casing with a dry cloth. Do not clean the internals. Make sure the vent hole is always unblocked.
Copyright © Itech Electronics Co., Ltd. ii
IT8500+ Users Manual
Environmental Conditions
Requirements
Operating temperature
C to 40°C
Operating humidity
20%-80% (non-condensation)
Storage temperature
-20°C to 70 °C
Altitude
Operating up to 2,000 meters
Pollution degree
Pollution degree 2
Installation category
II
The CE mark indicates that the product complies with all the relevant European
gal directives. The specific year (if any) affixed refers to the year when the design was approved.
The instrument complies with the WEEE Directive (2002/96/EC) marking
product label
indicates that you must not discard the
trical/electronic product in domestic
This symbol indicates the time period during which no hazardous or toxic substances are expected to leak or deteriorate during normal use. The
roduct can be used safely
year Environment Friendly Use Period (EFUP). Upon expiration of the EFUP, the product must be immediately recycled.
(WEEE) Directive
This product complies with the WEEE Directive (2002/96/EC) marking requirement. This affix product label indicates that you
household waste.
Product Category

Environmental Conditions

The instrument is designed for indoor use and an area with low condensation. The table below shows the general environmental requirements for the instrument. The speed of fan will change intelligently by the temperature of radiator. When the temperature is up to 40°C, the fan will be on and adjust intelligently when temperature changes.
Note
To make accurate measurements, allow the instrument to warm up for 30 min before operation.

Regulatory Markings

le
requirement. This affixed elec
household waste.
expected service life of the product is 10 years. The p during the 10-

Waste Electrical and Electronic Equiment (WEEE) Directive

Copyright © Itech Electronics Co., Ltd. iii
2002/96/EC Waste Electrical and Electronic Equipment
must not discard the electrical/electronic product in domestic
IT8500+ Users Manual
With reference to the equipment classifications described in the
of the WEEE Directive, this instrument is classified as a
ITECH office.
Annex I Monitoring and Control Instrument. To return this unwanted instrument, contact your nearest
Copyright © Itech Electronics Co., Ltd. iv
IT8500+ Users Manual
IEC 61326-1:2012/ EN 61326-1:2013 ¹²³
Reference Standards
CISPR 11:2009+A1:2010/ EN 55011:2009+A1:2010 (Group 1, Class A)
IEC 61000-4-2:2008/ EN 61000-4-2:2009
IEC 61000-4-3:2006+A1:2007+A2:2010/ EN 61000-4-3:2006+A1:2008+A2:2010
IEC 61000-4-4:2004+A1:2010/ EN 61000-4-4:2004+A1:2010
IEC 61000-4-5:2005/ EN 61000-4-5:2006
IEC 61000-4-6:2008/ EN 61000-4-6:2009
IEC 61000-4-11:2004/ EN 61000-4-11:2004

Compliance Information

Complies with the essential requirements of the following applicable European Directives, and carries the CE marking accordingly:
Electromagnetic Compatibility (EMC) Directive 2014/30/EU Low-Voltage Directive (Safety) 2014/35/EU
Conforms with the following product standards:
EMC Standard
1. The product is intended for use in non-residential/non-domestic environments. Use of the product in residential/domestic environments may cause electromagnetic interference.
2. Connection of the instrument to a test object may produce radiations beyond the specified limit.
3. Use high-performance shielded interface cable to ensure conformity with the EMC standards listed above.
Safety Standard
IEC 61010-1:2010/ EN 61010-1:2010
Copyright © Itech Electronics Co., Ltd. v
IT8500+ Users Manual
Content
DC PROGRAMMABLE ELECTRONIC LOADS ................................................................................................ 1
QUALITY CERTIFICATION AND ASSURANCE ....................................................................................................................... 1
WARRANTY .............................................................................................................................................................. 1
LIMITATION OF WARRANTY .......................................................................................................................................... 1
SAFETY SYMBOLS ....................................................................................................................................................... 1
SAFETY PRECAUTIONS ................................................................................................................................................. 2
ENVIRONMENTAL CONDITIONS ...................................................................................................................................... 3
REGULATORY MARKINGS ............................................................................................................................................. 3
WASTE ELECTRICAL AND ELECTRONIC EQUIMENT (WEEE) DIRECTIVE .................................................................................... 3
COMPLIANCE INFORMATION ......................................................................................................................................... 5
CHAPTER1 INSPECTION AND INSTALLATION ...................................................................................................... 1
1.1 VERIFYING THE SHIP MENT ...................................................................................................................................... 1
1.2 INSTRUMENT SIZE INTRODUCTION ............................................................................................................................ 1
1.3 ADJUSTMENT OF LOAD HANDLE............................................................................................................................... 3
1.4 DISASSEMBLY OF LOAD HANDLE ............................................................................................................................... 4
1.5 RACK MOUNTING ................................................................................................................................................ 5
1.6 CONNECTING THE POWER CORD .............................................................................................................................. 5
CHAPTER2 QUICK START .................................................................................................................................... 6
2.1 BRIEF INTRODUCTION............................................................................................................................................ 6
2.2 FRONT PANNEL INTRODUCTION ............................................................................................................................... 7
2.3 VFD DI SP LAY ANNUNCIATORS ................................................................................................................................. 8
2.4 FRONT PANEL KEYS ............................................................................................................................................... 8
2.5 COMBINATION KEYS .............................................................................................................................................. 9
2.6 REAR PANNEL INTRODUCTION ............................................................................................................................... 10
2.7 POWER-ON SELFTEST .......................................................................................................................................... 11
CHAPTER3 FUNCTIONS AND CHARACTERISTICS .............................................................................................. 14
3.1 LOCAL MODE/REMOTE MODE .............................................................................................................................. 14
3.2 OP ER ATI ON MODE ............................................................................................................................................. 14
3.2.1 Constant Current Mode (CC) ............................................................................................................ 14
3.2.2 Constant Voltage Mode (CV) ............................................................................................................. 15
3.2.3 Constant Resistance Mode (CR) ...................................................................................................... 15
3.2.4 Constant Power Mode (CW).............................................................................................................. 15
3.3 INPUT ON/OFF CONTROL .................................................................................................................................... 16
3.4 SHORT-CIRCUIT ANALOG FUNCTION ....................................................................................................................... 16
3.5 SYSTEM MENU (SYSTEM) ..................................................................................................................................... 16
3.6 CONFIG MENU (CONFIG) ..................................................................................................................................... 17
3.7 TRIGGER FUNCTION ............................................................................................................................................ 19
3.8 TRANSIENT FUNCTION ......................................................................................................................................... 19
3.8.1 Continuous Mode ............................................................................................................................... 19
3.8.2 Pulse Mode ......................................................................................................................................... 19
3.8.3 Toggled Mode ..................................................................................................................................... 20
3.9 LIST OPE R ATI ON ................................................................................................................................................ 20
3.10 SAVING AND RECALLING SETTINGS ....................................................................................................................... 20
3.11 VON FUNCTION .............................................................................................................................................. 21
3.12 OCP OP ER AT IO N ............................................................................................................................................. 22
3.13 OPP OP ER AT IO N ............................................................................................................................................. 23
3.14 BAT TE RY TE ST.................................................................................................................................................. 24
3.15 CR-LED TEST FUNCTION ................................................................................................................................... 26
3.16 MEASUREMENT OF VOLTAG E RISE TIME................................................................................................................. 26
3.17 PROTECTION FEATURES ...................................................................................................................................... 27
3.17.1 Over Voltage Protection (OVP) ....................................................................................................... 27
3.17.2 Over Current Protection (OCP) ....................................................................................................... 27
3.17.3 Over Power Protection (OPP) ......................................................................................................... 28
3.17.4 Over Temperature Protection (OTP) .............................................................................................. 28
3.17.5 Reverse Voltage Protection (LRV) .................................................................................................. 28
3.18 KEY LOCK FUNCTION ......................................................................................................................................... 28
Copyright © Itech Electronics Co., Ltd. vi
IT8500+ Users Manual
3.19 THE TERMINALS ON THE REAR PANEL .................................................................................................................... 28
3.19.1 Remote Sensing ............................................................................................................................... 28
3.19.2 External Triggering ........................................................................................................................... 29
3.19.3 Current Monitoring (I Monitor) ......................................................................................................... 29
3.19.4Ripple Function .................................................................................................................................. 30
CHAPTER4 BASIC OPERATION .......................................................................................................................... 31
4.1 CONSTANT CURRENT OP E R AT I O N ........................................................................................................................... 31
4.2 CONSTANT VOLTA GE OP E R AT I ON ........................................................................................................................... 31
4.3 CONSTANT POWER OPERATION ............................................................................................................................. 32
4.4 CONSTANT RESISTANCE OPE R AT I O N ........................................................................................................................ 32
4.5 TRANSIENT TEST OP E R AT IO N ................................................................................................................................ 32
4.5.1 Continuous Transient Operation ....................................................................................................... 33
4.5.2 Pulse Transient Operation ................................................................................................................. 34
4.5.3 Toggle Transient Operation ............................................................................................................... 34
4.6 LIST OP ER AT IO N................................................................................................................................................. 35
4.7 TEST FILES ........................................................................................................................................................ 37
CHAPTER5 COMMUNICATION INTERFACES...................................................................................................... 42
5.1COMMUNICATION MODULES INTRUDUCTION ............................................................................................................ 42
5.2 COMMUNICATION WITH PC .................................................................................................................................. 43
5.3USB IN TE RFAC E.................................................................................................................................................. 45
CHAPTER6 SPECIFICATIONS.............................................................................................................................. 46
SPECIFICATIONS ....................................................................................................................................................... 46
SUPPLEMENTARY CHARACTERISTICS.............................................................................................................................. 54
APPENDIX ............................................................................................................................................................... 55
SPECIFICATIONS OF RED AND BLACK TEST LINES .............................................................................................................. 55
Copyright © Itech Electronics Co., Ltd. vii
Inspection and Installation
The IT8500+ series include:
T8514C+/IT8514B+/IT8516C+
User may select an appropriate
Cord
It contains IT8500+ electronic load
documentations.
Ex-factory Test Report
It is the test report of the instrument before delivery.

Chapter1 Inspection and Installation

1.1 Verifying the Shipment

Unpack the box and check the contents before operating the instrument. If wrong items have been delivered, if items are missing, or if there is a defect with the appearance of the items, contact the dealer from which you purchased the instrument immediately. The package contents include:
Checkl i st o f P ackage Contents
Item Qty. Model Remarks
IT8511+/IT8511A+/IT8511B+/IT85
Electronic Loads x1 IT8500+ series
12+/IT8512A+/IT8512B+/IT8512C +/IT8512H+/IT8513A+/IT8513C+/I
IT-E171/IT-E172
Power cord
CD x1 -
NOTE
Upon verification of the shipment, keep the package and relevant contents thereof in a safe place. When returning the instrument for warranty service or repair, the specified packing requirements shall be met.
x1
x1 -
/IT-E173/IT-E17 4

1.2 Instrument Size Introduction

The instrument should be installed at well-ventilated and rational-sized space. Please select appropriate space for installation based on the electronic load size.
IT8500+ series electronic load different models are not the same size, the detail size of the electronic load are shown as below.
power cord that matches the specifications of power socket used in the area. See the Section Connecting the Power
for details.
Users Manual, Programming Guide and other user
Copyright © Itech Electronics Co., Ltd. 1
Inspection and Installation
IT8511+/IT8511A+/IT8511B+/IT8512+/IT8512B+/IT8512C+/IT8512H+ Model
Detialed Dimension Drawing
IT8513A+/IT8513C+ Model
Detailed Demension Drawing
Dimension: Width: 214.5mm Height: 88.2mm Depth: 354.6mm
Dimension: Width: 214.5mm Height: 88.2mm Depth: 453.5mm
Copyright © Itech Electronics Co., Ltd. 2
Inspection and Installation
IT8514B+/ IT8514C+ Model
Detialed Dimension Drawing
IT8516C+ Model
Detailed Dimension Drawing
Dimension: Width: 436.5.5mm Height: 88.2mm Depth: 463.5mm
Dimension: Width: 482.5mm Height: 174.5mm Depth: 531.5mm

1.3 Adjustment of Load Handle

Copyright © Itech Electronics Co., Ltd. 3
IT8511+/IT8511A+/IT8511B+/IT8512+/IT8512A+/IT8512B+/IT8512C+/IT8512H /IT8513A+/IT8513C+ series loads are equipped with a handle for user to easily carry and place it.
Inspection and Installation
The load handle may be adjusted based on three methods (as shown in icons below). Be sure that appropriate force is applied to adjust the load handle to appropriate position.

1.4 Disassembly of Load Handle

Please disassemble the load handle before installing equipment on the support. Disassembly steps:
1. Adjust the handle to the position as shown in the figure below.
NOTE
To easily disassemble handle, align the locking mouth and locking device, which is between the handle and the instrument.
2. Align the locking mouth, and pull out the handle towards two sides.
NOTE
Do not use too much force and mind your hands during disassembly of load handle.
Copyright © Itech Electronics Co., Ltd. 4
Inspection and Installation
IT-E172
E
N L
E
L N
E
N L
E
L N

1.5 Rack Mounting

IT8511+/IT8511A+/IT8511B+/IT8512+/IT8512A+/IT8512B+/IT8512C+/IT8512H +/IT8513A+/IT8513C+ loads can be installed on standard 19-inch rack. ITECH provides user with IT-E151/IT-E151A rack, as an optional mount kit. The detailed operation please refer to the User Manual of your mount kit.
IT8514B+/IT8514C+/IT8516C+ need not mount on rack, they can installed on cabinet directly by screw.

1.6 Connecting the Power Cord

Connect the power cord after checking that the power switch of the instrument is turned OFF. Only use the power cord supplied as a standard accessory.
Select from the following Schedule of Power Cord Specifications an appropriate power cord that matches the voltage for the area in which you use the instrument. If the power cord included in the instrument you purchased does not match the voltage, contact the dealer or manufacturer for change.
China
IT-E171
United States &
Canada
Europe
IT-E173
England
IT-E174
Copyright © Itech Electronics Co., Ltd. 5
Quick Start
Model
Voltage
Current
Power
Communication Interface
IT8511+
120V
30A
150W
DB9(TTL)
IT8511A+
150V
30A
150W
DB9(TTL)
IT8511B+
500V
10A
150W
DB9(TTL)
IT8512+
120V
30A
300W
DB9(TTL)
IT8512A+
150V
30A
300W
DB9(TTL)
IT8512B+
500V
15A
300W
DB9(TTL)
IT8512C+
120V
60A
300W
DB9(TTL)
IT8512H+
800V
5A
300W
DB9(TTL)
IT8513A+
150V
60A
400W
DB9(TTL)
IT8513C+
120V
120A
600W
DB9(TTL)
IT8514B+
500V
60A
1500W
USB/RS232
IT8514C+
120V
240A
1500W
standard USB/RS232
IT8516C+
120V
240A
3000W
Standard USB/RS232

Chapter2 Quick Start

This chapter introduces the front panel, the rear panel, key functions and VFD display function of the electronic load, make sure that you can quickly know the appearance, instruction and the key function before you operate the load, Help you make better use of this series of electronic load.

2.1 Brief Introduction

IT8500plus series DC electronic loads are single channel programmable electronic load which can provide multiple solutions according to the requirements of your design and test. This series have international advanced functions and features.
High-visibility vacuum fluorescent display (VFD) Measurement resolution: 0.1mV,0.1mA Voltage and current Measurement speed: up to 40KHZ Four operation modes:CV(Constant Voltage),CC,CR,CW Battery test function OCP test , OVP test Auto test function: Short circuit function Remote Sense function Memory capacity to save/recall setting parameters: 100 registers Intelligent fans Build-in Buzzer as alarm signal Power off memory function Rotary knob, making the operation more convenient Measure test function,test the rising/dropping time of the voltage List modes
Copyright © Itech Electronics Co., Ltd. 6
Quick Start
IT8511+/IT8511 A+/IT8511B+/IT8512+/IT8512A+/IT8512B+/IT8512C+/IT8512H+/IT8513A+/IT 8513C+ Model
Power switch
s function by key
Function key:
IT8514B+/IT8514C+ Model
Power switch
s function by key
Function key:

2.2 Front Pannel Introduction

IT8500+ series electronic load different models have different front pannels, the front panels and keyboards of different models are shown as below.
vacuum fluorescent display (VFD) Compound key and the local switch key Number key:
Set the parameters value, achieve the menu combination
Set the operation mode Control the input state: On/Off
Direction function Rotary knob Input terminal
vacuum fluorescent display (VFD) Compound key and the local switch key Number key:
Set the parameters value, achieve the menu combination
Copyright © Itech Electronics Co., Ltd. 7
Set the operation mode Control the input state: On/Off
Direction function Rotary knob Input terminal
Quick Start
OFF
The load is off.
Error
An error has occurred.
CC
Constant current mode
Trig
Waiting for the trigger signal
CV
Constant voltage mode
Sense
Remote sensing is on.
CR
Constant resistance mode
Prot
OCP function is on.
CW
Constant power mode
Auto
Voltage range automatically seleted function is open
Rmt
Instrument is in the remote state.
Lock
The keyboard is locked.
Timer
LOAN ON is on.
Shift
Shift button has been pressed.
( Blue-green)
Shift button is a composite key.
IT8516C + Model
Power switch
s function by key
Function key:
vacuum fluorescent display (VFD) Com p ound key and the local switch key Num ber key:
Set the parameters value, achieve the menu combination
Set the operation mode Control the input state: On/Off
Direction function Rotary knob Input terminal

2.3 VFD Display Annunciators

2.4 Front Panel Keys

Copyright © Itech Electronics Co., Ltd. 8
Quick Start
Local button is used to switch local and remote mode.
Power on button
Decimal point
The escape key
OFF is high
impedance state).
[ Shift ]+ [ 1 ] (Short)
Turn short circuit on or off.
+ [ 2 ] (Tran)
+ [ 3 ] (List)
Set LIST operation parameters.
[ Shift ] + [ 4 ] (Save)
+ [ 5 ] (Battery)
Turn on or off battery testing function.
+ [ 6 ] (Prog)
Enter auto test function.
[ Shift ] + [ 7 ] (Info)
Display products Model/SN/Version.
+ [ 8 ] (System)
System menu setting
+ [ 9 ] (Config)
Configure menu setting
[ Shift ] + [ 0 ] (Pause)
Press this button if you need a pause when runing an auto test file.
+ [ ]
Cause an immediate trigger.
[ Shift ] + [ CC ] (OCP)
Enter OCP test function.
+ [ CV ] (Setup)
Set detailed parameters in CC/CV/CW/CRmode.
[ Shift ] + [ CW ] (OPP)
Enter OPP test function.
+ [ Enter ] (Recall)
Recall the DC Load state from non-volatile memory.
[ Shift ] + [ On/Off ] (Lock)
Key lock function
0
9
ESC
(Gray) (Gray-white)
~ Enter the digits 0 to 9.
Choose constant current mode. Choose constant voltage mode. Choose constant resistance mode. Choose constant power mode.
Enter the selected value or setting. Turns DC Load ON or OFF (
Scroll up key
Scroll down key
Scroll left and right key

2.5 Combination Keys

Press [ Shift ] button first and then other keys to achieve all kinds functions in the following table.
[ Shift ]
[ Shift ]
[ Shift ] [ Shift ]
[ Shift ] [ Shift ]
Start or stop transient condition.
Store the DC Load state in non-volatile memory.
[ Shift ]
(Trigger)
[ Shift ]
[ Shift ]
Copyright © Itech Electronics Co., Ltd. 9
Quick Start
IT8511+/IT8511A +/ IT8511B+/IT8512+/ IT8512B+/IT8512C+/IT8512H/IT8513A+/IT8513C+ Model
Thermal window Line voltage selection
3 pin IEC320 AC input connector
Current monitoring T erminal
IT8514B+/IT8514C+Model
Thermal window Line voltage selection
Current monitoring T erminal

2.6 Rear Pannel Introduction

IT8500+ series electronic load different models have different rear pannels, the rear panels and keyboards of different models are shown as below.
switch( 110V/220V )
switch( 110V/220V )
3 pin IEC320 AC input connector
9-Pin serial port interface connector 4 pin trigger and remote sensing connector
RS232 communication cable interface 4 pin trigger and remote sensing connector
USB communication cable interface
Copyright © Itech Electronics Co., Ltd. 10
Quick Start
IT8516C+Model
Thermal window Line voltage selection
Current monitoring T erminal
0.0000V 0.0000A
OFF CC Auto
switch( 110V/220V )
3 pin IEC320 AC input connector

2.7 Power-on Selftest

A successful test process indicates that the instrucment meets the factory specifications and can be operated well.
Before operation, please confirm that you have fully understood the safety instructions.
To avoid burning out, be sure to confirm that power voltage matches with
supply voltage.
Be sure to connect the main power socket to the power outlet of protective
grounding. Do not use terminal board without protective grounding. Before operation, be sure that the power supply is well grounded.
To avoid burning out, pay attention to marks of positive and negative
polarities before wiring.
RS232 communication cable interface 4 pin trigger and remote sensing connector
USB communication cable interface
Selftest steps
Normal selftest procedures:
1. Correctly connect the power cord. Press [ Power ] key to start up.
2. After selftest, VFD display information below.
Copyright © Itech Electronics Co., Ltd. 11
0.00W CC=0.000A
Information description:
The first line display actual voltage and current value. The second line display the actual power value and the setting
current/voltage/power/resistance value
Quick Start
(220VAC)
Fuse specification
(110VAC)
The third line display the input state/operation mode.
3. Press [ Shift ] + [ 7 ], VFD display products information. You can press
direction buttons to examine products model/SN/software version.
Error Information References
The following error information may occur when an error occurs during Power On self-test:
If the EEPROM was damaged, the VFD will display Eeprom Fail. If the lastest operation data in EEPROM is lost, then VFD will display
Config Data Lost.
If the calibration data in EEPROM is lost, then VFD will display Cal data
lost”.
If the system setting data in EEPROM is lost, the VFD will displayEeprom
data lost.Please press [ Shift ] + [ 4 ] and [ 0 ] to save after setting parameters.
Exception handling
If the electronic load cannot start normally, please check and take measures by reference to steps below.
1. Check whether the power line is correctly connected and confirm whether
the electronic load is powered. Correct wiring of power line => 2 Incorrect wiring of power line => Re-connect the power line and check whether the exception is removed.
2. Check whether the power in On.[ Power ] key is under On
status. Yes => 3 No => Please check the [ Power ] key to start power and check whether the exception is removed.
3. Check whether set power voltage of electronic load is larger than the power
supply voltage. If set power voltage is 220 V and the supply voltage is 110V, the electronic load cannot start.
4. Check whether the fuse of electronic fuse is burned out.
If yes, change fuse. Detailed steps: Pull out power line and take out the fuse box at power line jack with a
small screw driver. As shown below.
If the fuse is fused, please change fuse of same specification based on
machine m odel. See the table blow for matching information of fuse and machine model.
Model
Fuse specification
Copyright © Itech Electronics Co., Ltd. 12
IT8511+ T0.5A 250V T1.25A 250V IT8511A+ T0.5A 250V T1.25A 250V IT8511B+ T0.5A 250V T1.25A 250V
Quick Start
Fuse specification
(110VAC)
Model
Fuse specification
(220VAC)
IT8512A+ T0.5A 250V T1.25A 250V
IT8512A+ T0.5A 250V T1.25A 250V IT8512B+ T0.5A 250V T1.25A 250V IT8512C+ T0.5A 250V T1.25A 250V IT8512H+ T0.5A 250V T1.25A 250V IT8513A+ T1.25A 250V T2.5A 250V IT8513C+ T1.25A 250V T2.5A 250V IT8514B+ T1.25A 250V T2.5A 250V IT8514C+ T1.25A 250V T2.5A 250V IT8516C+ T2.5A 250V T5A 250V
After replacement, install the fuse box back to original position, as
shown below.
Copyright © Itech Electronics Co., Ltd. 13
Functions and Characteristics

Chapter3 Functions and Characteristics

This chapter elaborates on the functions and characteristics of electronic loads.Contents following sections:
Switching of local/remote operation modes Constant-status operation mode Input On/Off function Keyboard locking function
Short -circuit analog function System setup function
Triggering function List mode Test function Save/Recall VON function Full protection function,OCP,OVP,OTP,OPP,Reverse voltage Remote Sense function Current monitoring function
Ripple function

3.1 Local Mode/Remote Mode

There are two types of control modes for IT8500+ series products:Local mode and Remote mode.
In remote mode, you can operate the electronic loads through PC v ia communication cable(optional). While After power on electronic loads, it defaults in local mode and all buttons are avaiable in this mode.In remote control mode, the keys on the front pannel can not work except local key.Customers could through [ Local ] key to switch the control mode.

3.2 Operation Mode

There are four operation modes of IT8500+ series products:
Constant current mode (CC) Constant voltage mode (CV) Constant resistance mode (CR) Constant power mode(CW)

3.2.1 Constant Current Mode (CC)

In constant current mode, the DC load will comsume a constant current, regardless of the voltage at its terminals.
Copyright © Itech Electronics Co., Ltd. 14
Functions and Characteristics
Load current
Input voltage
I V
Slope is equal To the setting resistance
CR mode
Input voltage
I
V
Setting voltage
CV mode
Load current
Input voltage
I V Setting current
CC mode
Diagram 3-1 I-V curve in CC mode

3.2.2 Constant V oltage Mode (CV)

In constant voltage mode, the DC load will cause a constant voltage to appear at its terminals.
Input current
Diagram 3-2 I-V curve in CV mode

3.2.3 Constant Resistance Mode (CR)

In constant resistance mode, the DC load will behave as a fixed resistance value.As shown below,the load linearly changes the current value with the rising of input voltage.

3.2.4 Constant Power Mode (CW)

Copyright © Itech Electronics Co., Ltd. 15
Diagram 3-3 I-V curve in CR mode
In constant power mode,the DC load will cause a constant power to be dissipated in the load.As shown below,the load current is decreasing with the rising of input voltage,while power always maintain the setting value.
Functions and Characteristics
POWER-ON
Power on state of instrument
RST(default)
Do not remember state in SAVE 0.Customer can save the DC load next time.
SAV0
Remember state in SA VE 0
BUZZER
ON(default)
Enable audible beep when key is pressed
OFF
No sound when key is pressed
KNOB
Diagram 3-4 I-V curve in CP mode

3.3 Input On/Off Control

[ On/Off ] button on the front panel is used to manually toggle the instrument
between its set mode and an infinite impedance state, i.e control input on and off. [ On/Off ] button lighted indicates the load input is on, meanwhile the [ OFF ] indicator will disappear.

3.4 Short-circuit Analog Function

Short circuit simulation and short circuit current measurement:you may press [ Shift ] + [ 1 ] botton to emulate a short state.It can be used to check whether the tested instruments short protection is avaiable.
In short mode,the DC load will draw maximum current from the DC supply in any of the four operation modes(CC,CV,CW or CR).In CC,CV,or CR mode,you may press [ Shift ] + [ 1 ] to stop short.The DC load will return to its previous operation.However,in CW mode,the short current will continue to be drawn.To stop the short,you must press the [On/Off] key after you press [ Shift ] + [ 1 ].
When emulating a Short in CC, CW or CR mode, the maximum allowable short current is equal to the 110% of c urrent range. Under CV mode, short circuit current is equivalent to that constant voltage value of load is 0 V.

3.5 System Menu (System)

Press [ Shift ] + [ 8 ] (system) to enter the system menu.
POWER-ON
a often used data in SAVE 0 to recall when power on
BUZZER
KNOB
Copyright © Itech Electronics Co., Ltd. 16
Functions and Characteristics
UPDA TE(default)
The value modified with knob during operation will be
the setting
OLD
As explained above, after the DC load is turned on with knob.
SOURCE
Set trigger mode
MANUAL(Def)
Triggered from the
+ [ ] key
EXTERNAL
Triggered from a TTL high signal at the trigger connector on rear panel
BUS
Triggered from a serial bus command 5AH
HOLD
Receving a command 9DH
MEMORY
Recall the prestored datas
GROUP= 0
0:indicates1-10 group;1:indicates 11-20group, by parity of reasoning
DISP-TIMER
Timer function
ON
Enable timer function
OFF(default)
Disable timer function
RS-232
4800_8N 1
Baudrate 4800, data bit 8, n one parity, stop bit 1
9600_8N 1
Baudrate 9600, data bit 8, none parity, stop bit 1
19200_8N 1
Baudrate 19200, data bit 8, none parity, stop bit 1
38400_8N 1
Baudrate 38400, data bit 8, none parity, stop bit 1
SCPI
Select SCPI protocol
FRAME
Select FRAME protocol
ADDRESS= 0
Set the instruments address(0~31)
RUN
Runing mode at power on
NORMA L
Normal mode
BATTERY
Default in battery test mode at power on
PROG_TEST
Default in autotest mode at power on
OCP_TEST
Default in OCP test mode at power on
OPP_TEST
Default in OPP test mode at power on
DEFA ULT
NO
Do not return instrument to factory default settings.
YES
Retrun instrument to factory default settings
saved after load is off.For example; the DC load is set to 1A by press [CC] and turned on the input.Then increase the setting value to 2A with knob.When customer turn off load and trun on again, value changes to 2A.
again,the setting value is 1A instead of 2A changed
[ Shift ]
TRIGGER
MEMORY
DISPLA Y
RS-232
PROTOCOL
ADDRESS
RUNMODE
DEFAULT

3.6 Config Menu (Config)

PROTECT
Copyright © Itech Electronics Co., Ltd. 17
Press [ Shift ]+ [ 9 ] (Config) to enter the menus.
Max-P Set hardware power protection
MAX POWER=150.00W Set hardware OPP value
Functions and Characteristics
A-LIMIT Set software current protecting state A-LIMIT
ON Enable software over current protection function A-LIM POIN=30.000A Set the software OCP level A-LIM DELAY=3S Set the OCP delay time OFF Disable the software OCP funtion
P- LIMIT Set software power protecting state. P-LIM POIN=150.00W Set the software OPP level.
P-LIM DELAY=3S Set the OPP delay time. TIMER Set load on timer
LOAD-TIMER ON Enable load-on timer LOAD-TIMER=10.0S Set the load on time(0.1S~9999.9S)
OFF Disable load on timer V-RANGE Voltage auto-rangefuntion
MEASURE
CR-LED
SENSE
V-RANGE ON Enable voltage auto range function OFF Disable voltage auto range function
FILT ER Set the filter parameter FILTER COUNT = 2^14 Filter count set, range 2~16
TIME-V1 TIME-VOLT1=0.000V Set the start time, to measure the voltage rise/fall time. TIME-V2
TIME-VOLT2=120.00V Set the end time, to measure the voltage rise/fall time CR-LED Imitate LED (in CR mode)
ON
Open the function(in CR mode,press [ Shift ]+ [ CV ] to set Vd value)
OFF Disenable the function REM- SENSE Remote sense function ON Enable remote sense function
OFF Disable remote sense function VON Set the load’s VON point LIVING VON point living state
VON
VON POINT = 0.10V Set the VON value LAT CH VON point latch state, ON /OFF
VON POINT = 0.10V Set the VON value RESET Reset the config menu
RESET
NO Do not reset YES Reset
Copyright © Itech Electronics Co., Ltd. 18
Functions and Characteristics

3.7 Trigger Function

Triggering is used with the transient operation; list operation and test function.There are four types of triggers you can use for IT8500+ products.
Manual: An immediate trigger is created by pressing [ Shift ]+ [ ] (Trigger) on the front panel.
External(TTL signal): An external trigger is a TTL low signal applied to the trigger connection on the rear panel.This TTl signal must last for more than 10us.
Bus: The instrument will be triggered if command 5AH is sent via the communication interface.
Hold: The instrument will be triggered if command 9DH is sent via the communication interface.

3.8 Transient Function

The transient test allows switching between two different load values.A common application is to test the dynamic characteristics of DC source.
There are three different types of transient operation: continuous, pulse,
toggled.

3.8.1 Continuous Mode

In continuous transient operation, the load is continuously switched between two load values.An example is shown in the following figure:

3.8.2 Pulse Mode

In pulse operatrion,the load operates at the A value that has been entered until a trigger is received.At the trigger,the load switches to the B value and stays at that level for the B timing value.Then the load switches back to the A value and stays there until another trigger is received.
Copyright © Itech Electronics Co., Ltd. 19
Functions and Characteristics
10A
5A
TRG
TRG
Toggled Transient Operation
Trigger
10 2 3 4 5
List count=1 List count=2
List sequence

3.8.3 Toggled Mode

In toggled transient operation,the load starts at the stored parameters for the mode.When a trigger is received,the load switches to B value.When another trigger is received,the load switches to the A level.It stays at the A value until another trigger is received,at which point it switches to the B value.Here’s an example:

3.9 LIST Operation

List mode allows you to generate a complex current sequence. Moreover, the mode.
change can be s ynchronized with an internal or external signal, to accomplish dynamic and precise test A list file includes following parameters: file name,
step counts (range 2-84), time width of single step(0.00005s~3600s),step value and slope.The edited list file can be saved in nonvolatile memory, can be
recalled easily.The DC load provides 7 nonvolatile registers to save list files for recall later.
In list mode,the DC load start to run the list file once receiving a trigger signal, continue to run once receiving another trigger signal.To illustrate the use of a list,we’ll create a list that runs the following constant current profile on a power supply:

3.10 Saving and Recalling Settings

We can save some often-used parameters in the non volatile memory, including working mode, voltage/current value and so on.IT8500plus series provide 100 non-volatile registers.
They are divided into 10 Memory groups: Group0-9.You can set it in the system
Copyright © Itech Electronics Co., Ltd. 20
menu.Group0 means you can save and recall parameters in 0-10 registers.
Functions and Characteristics
Group1 means you can save and recall parameters in 11-20 registers. Group2-Group9 can be concluded in the same manner.
Save and Recall operation
For example: the instrucment works in CC mode, setting value is 1A, Memory Group is 6. Save CC 1A in the 61th register and then recall.
1. Set the parameters ok. To save the instrument's settings to a register, press [ Shift ]+ [4] (Save). Enter number [6] and [1].
2. Then press [Enter], The setting is saved.
3. To recall the instrument's settings from a register, press [ Shift ]+ [Enter] (Recall).
4. Enter [1].Then the setting is recalled.
NOTE
Saving operation will overwrite any values previously saved in that register. Recalling operation will light the Enter . You should press [ESC] to escape the recalling state
before setting other parameters.

3.11 VON Function

The DC load can be set to only turn on if the voltage is above a set value(VON set) under configure menu by pressing [ Shift ]+ [9].There are two types of VON function:Living and Latch.The following will have detailed description for the two types.
NOTE
VON set is used to ensure an electronic system under test will not have power applied unless the supply voltage is above a certain value.If you have no such testing request, do not set this value arbitrarily.If your instrument can not work normally, for example, set CC=1A, after turn on the input while the current is still 0A instead of setting value 1A, then you should check VON set firstly.If VON set is not 0V, then please modify to 0V.
VON LIVING MODE In Living mode, when power is applied to the DC load, the voltage must rise
above VON setting before the load draws current from the source.If the voltge below VON setting on the load’s terminals, the load will turn off input.
Copyright © Itech Electronics Co., Ltd. 21
Functions and Characteristics
OCP TEST
1.VON LEVEL=0.000V
Set Voltage threshold
2.VON DELAY=0.00S
After delay certain time,the DC load starts to draw current.
3.RANGE=3.000A
Set current range
4.STAR T=0.1000A
Set start current
5.STEP=0.1000A
Set step current
6.STEP DEL=0.20S
Set delay time of each step
7.END=2.0000A
Set end current
8.OCP VOL T=2.000V
Set OVP value
9.MAX TRIP =1.5000A
Upper limit of OCP value
10.MIN TRIP=0.9000A
Lower limit of OCP value
SAVE OCP FILE=1
Save OCP test file (1-10)
Operation
Display on front pannel
0.0000V 0.000A
VON LATCH MODE In Latch mode,as before,the load will turn on only when the voltage exceed
VON setting,but once on,it will now stay on,even if the voltage drops to zero.

3.12 OCP Operation

OCP test process: After input voltage reaches VON point,the DC load start to
draw a current from the source after a delay time.The current value will increase by a certain step size at regular intervals.Simultaneously, the DC load will judge whether the input voltage is lower than OCP voltage you’ve set.If it is,then the present current value will be compared to see if it is in the current range you’ve set,in this range,the OCP test will Pass or fail.On the contrary,the DC load will continue to increase drawing current and compare the voltage.
To start an OCP test,press [ Shift ]+ [ ] (Trigger). Press [ Shift ]+ [ CC ] (OCP) to enter OCP operation.
EDIT
Set the power on mode to be OCP test mode:
Copyright © Itech Electronics Co., Ltd. 22
1.Press [ Shift ]+ [ 8 ] (system) enter into sysmtem menu
POWER-ON BUZZER
Functions and Characteristics
2.Press right key,select RUNMODE and confirm
[ Enter ]
0.0000V 0.000A RUN <NORMAL
3.Press direction key to select OCP_TEST,Press
0.0000V 0.000A
4,Press [ Esc ] button to quit the set.
0.0000V 0.000A
OPP TEST
STOP
Run OPP test file
OPP TEST
Recall OPP File=1
Recall OPP test file(range file1-file10)
OPP TEST
1.VON LEVEL=0.000V
Set Voltage on value
2.VON DELAY=0.01S
Set Voltage on delay time
3.RANGE=5A
Set working current range
4.START =0.1W
Set start power value
5.STEP =1W
Set step power value
6.STEP DEL=1S
Set step delay time
7.END =12W
Set cut-of f power value
8.OPP VOL T=7V
Set OPP value
9.MAX TRIP =6.5W
Upper limit of OPP value
10.MIN TRIP =5.6W
Lower limit of OPP value
SAVE OPP FILE=1
Save OPP test file
Operation
Display on front pannel
1.Press [ Shift ]+ [ 8 ] (system) enter into
0.0000V 0.000A
2.Press right key,select RUNMODE and confirm with [ Enter ] button
0.0000V 0.000A RUN <NORMAL
with [ Enter ] to confirm.
button
After above steps,press [ ] (Trigger) button to run ocp test file.
Recall OCP File:
1. Press [ Shift ]+ [ Enter ] button to select programe file,the panel displays CALL OCP FILE= 1.Enter the file name(1-10),press [ Enter ] button to confirm.
2. According to the following steps to escape OCP mode:press [ Shift ]+ [ 8 ] (system)------“RUNMODE-----[Enter]-------select “NORMAL”mode----[ Enter ].

3.13 OPP Operation

OPP test process:When the input voltage has reached VON point, power will
begin to work after a delay time.The power value will increase by a step size at regular intervals.Simultaneously,the DC load will judge wether the input voltage is lower than OPP voltage(you need to set).If it is,then the present current value will be compared to see if it is in the current range you’ve set,in this range,the OPP test will Pass or fail.On the contrary,the power will continue to increase within the cut-off current range.And then compare OPP voltage with input voltage too.
RUN <OCP_TEST
STOP 0.000A
OPP TEST
To start a OPP test, press [ Shift ]+ [ ] (Trigger). Press [ Shift ]+ [CW] (OPP) to enter OPP test operation.
RUN
CALL
EDIT
Set the power on mode to be OPP test mode
sysmtem menu
Copyright © Itech Electronics Co., Ltd. 23
POWER-ON BUZZER
Functions and Characteristics
3.Press direction key to select
0.0000V 0.000A
4,Press [ Esc ] button to quit the set.
0.0000V 0.000A
Step
Operation
Display
1
Press
(Battery),set current range
0.0000V 0.000A RANGE = 0.00A
2
Set discharge current,for example 2A
CURRENT = 2.000A
3
Set the stop voltage,for example 2V, then press
[ Enter ] to confirm.
STOP VOLT=2V
4
Set the stop capability to maximum 999.999AH,
[ Enter ]
STOP CAP=999.999AH
5
Set the stop timer to maximum 99999S, press
[ Enter ] to confirm.
STOP TIMER=99999S
6
Save the battery test to specified file
0.0000V 0.000A SAVE BATT FILE 1(1-10)
6
Press [ Enter ] to confirm
0.0000V 0.000A
Off cc
Step
Operation
Display
1
Press
(Battery),set current range
0.0000V 0.000A RANGE = 0.00A
2
Set discharge current,for example 2A
CURRENT = 2.000A
3
Set the stop voltage to 0V, then press [ Enter ] to confirm.
STOP VOLT=0V
4
Set the stop capability, for example,7AH,then press [ Enter ] to confirm.
STOP CAP=7AH
5
Set the stop timer to maximum 99999S, press
STOP TIMER=99999S
OCP_TEST,Press [ Enter ] to confirm.
After above steps,press [ ] (Trigger) button to run OPP test file.
Recall OPP File
1. Press [ Shift ]+ [ Enter ] button to select programe file,the panel displays CALL OPP FILE= 1.Enter the file name(1-10),press [ Enter ] button to confirm.
2. According to the following steps to escape OPP mode:press [ Shift ]+ [8] (system)------”RUNMODE----[ Enter ]------select“NORMAL”mode----[ Ente
r ].

3.14 Battery Test

IT8500plus series products test the battery capability in CC/CW/CR mode. The test m ode should be set first, and then the discharge stop conditions.
There are three discharge stop conditions to be set for IT8500 plus series products. When user only need to do battery testing in one or two stop conditions, the other conditions should be set to the specified value (STOP VOLT:0V;STOP CAP:999.999AH;STOP TIMER:99999S). When the system checks the discharging time or battery voltage or capacity is equal to the setting stop value or under an insecurity state, the battery test will stop, and the E-Load will turn off. The battery voltage, discharge current, discharge time and discharged capability are displayed on the VFD while testing.
RUN <OPP_TEST
STOP 0.000A
Take CC mode for example, the operations are as below:
( 1 )Voltage-threshold Cut Off
[ Shift ]+ [ 5 ]
press
(2)Capacity-threshold Cut Off
[ Shift ]+ [ 5 ]
to confirm.
0.00W I = 2.00A
Copyright © Itech Electronics Co., Ltd. 24
Functions and Characteristics
[ Enter ] to confirm.
6
Save the battery test to specified file
0.0000V 0.000A SAVE BATT FILE 1(1-10)
7
Press [ Enter ] to confirm
0.0000V 0.000A Off cc
Step
Operation
Display
1
0.0000V 0.000A RANGE = 0.00A
2
Set discharge current,for example 2A
CURRENT = 2.000A
3
Set the stop voltage to 0V, then press [ Enter ] to confirm.
STOP VOLT=0V
4
Set the stop capability to maximum 999.999AH, press [ Enter ] to confirm.
STOP CAP=999.999AH
5
Set the stop timer, for example, 3800S, press
[ Enter ] to confirm.
STOP TIMER=3800S
6
Save the battery test to specified file
0.0000V 0.000A SAVE BATT FILE 1(1-10)
7
Press [ Enter ] to confirm
0.0000V 0.000A Off cc
Step
Operation
Display
1
Press
(Battery),set current range
0.0000V 0.000A RANGE = 0.00A
2
Set discharge current,for example 2A
CURRENT = 2.000A
3
Set the stop voltage as needed,for example,2V,then press [ Enter ] to confirm.
STOP VOLT=2V
4
Set the stop capbility as needed,for example,7AH,then press [ Enter ] to confirm.
STOP CAP=7AH
5
Set the stop timer as needed,for example,3800S,then press [ Enter ] to confirm.
STOP TIMER=3800S
6
Save the battery test to specified file
0.0000V 0.000A SAVE BATT FILE 1(1-10)
7
Press [ Enter ] to confirm
0.0000V 0.000A Off cc
Operation
Display on front pannel
1.Press [ Shift ]+ [ 8 ] (system) enter into
0.0000V 0.000A
2.Press right key,select RUNMODE and confirm with [ Enter ] button
0.0000V 0.000A RUN <NORMAL
3.Press direction key to select
0.0000V 0.000A
4,Press [ ESC ] button to quit menu set
0.0000V 0.000A
0.00W I = 2.00A
(3)Time-out Cut Off
Press [ Shift ]+ [ 5 ] (Battery),set current range
0.00W I = 2.00A
(4) Any of the Three Conditions Cut Off
[ Shift ]+ [ 5 ]
(5)Go into Battery Test Mode
sysmtem menu
0.00W I = 2.00A
POWER-ON BUZZER
OCP_TEST,Press [ Enter ] to confirm.
(6)Start Battery Test
Press [ ] (trigger) to provide a signal to start battery test.The discharing process will be auto terminated when stop conditions are reached.
(7)Recall Battery File
Press [ Shift ] + [ Enter ] button to select programe file,the panel displays RECALL BATTERY 1.Enter the file name(1-10),press [ Enter ] button to
Copyright © Itech Electronics Co., Ltd. 25
RUN <BATTERY
0S 0.000AH
Functions and Characteristics
confirm.
(8)Pannel Locked in case of Error Operations
Press button is enabled. According to the following steps to escape OPP mode: Press
[ Shift ]+ [ On/Off ] (Lock) button to lock the panel.In this mode,only [ Shift ] and [ On/Off ]
[Shift ]+ [ 8 ] (system)---”RUNMODE”---[ Enter ]----select NORMAL” mode---[ Enter ]

3.15 CR-LED Test Function

With adding of diode break-over voltage setting in the IT8500+ series electronic load under conventional CR mode, the electronic load only works when voltage applied at its both ends is higher than the diode break-over voltage to give a real simulation of diode working principle, i.e., the ripple current at real LED test.
Detailed steps of LED power test:
1. Start CR-LED Function
Press [Shift] + [9] keys to enter configuration menu. Press Right Key and select CR-LED. Press [Enter] key for entry. Select on” and press [Enter] key. Press [ESC] key to exit.
2. Set CR Mode and Resistance Value
Press [CR] key and set corresponding constant resistance (as R calculated below).
3. Set Vd Value
Press [Shift] + high=130V, low=0V, which may remain the original values. Vd will be set based on the calculation below.
Calculation method of Vd and R: Vd=V*0.8 R=0.2V/I Where: V: constant working voltage of load LED of LED constant current
source;
I: output current of LED constant current source; Vd: break-over voltage of diode (string); R: constant resistance;
[CV] keys for a series of related setting: range=7500.0,

3.16 Measurement of Voltage Rise Time

The IT8500+ series electronic load is provided with special v oltage rise/drop time measurement function. This function gives a simple analog of voltage rise/drop speed of oscilloscope test power.
Operation methods:
Set initial Voltage and Final Voltage
1. Press [Shift] + [9] keys to enter configuration menu. Press Right key. Select Measure” and press [Enter] key.
2. Press [ ] to select TimeV1”. Press [Enter] key. Press numeric keys to set initial voltage value and press [Enter] key.
3. Press [ ] to select TimeV2”. Press [Enter] key. Press numeric keys to set final voltage value and press [Enter] key.
4. Press [ESC] to exit setting.
Start timer function
Copyright © Itech Electronics Co., Ltd. 26
Functions and Characteristics
OFF CC
5. Press [Shift] +[8] keys to enter system menu. Press Right key till Displ flicks and press [Enter] key.
6. Press [ ] key to select On”. Start timer function and press [Enter] key.
7. Press [ESC] to exit setting.
8. VFD second line will display time 0.0000S between power value and set value.
0.0001V 0.0002A
0.00W 0.0000S CC=0.000A
Measurement of Rise Time
9. Connect DC power to be tested to the input terminal of the electronic load. The power is set with a value that is higher than the set final voltage value. Keep power output in OFF status.
10. Set a constant current value on the load and open the load input.
11. Open power output.
12. The electronic load timer starts timing. After ending, time will keep stable, which is rise time of voltage.
13. Close the power output. The electronic load VFD will display voltage drop time.

3.17 Protection Features

DC load protection features include: OVP, OCP, OPP, OTP, reverse voltageprotection(LRV/RRV).

3.17.1 Over Voltage Protection (OVP)

If input voltage exceeds the voltage limit set by the user, the DC load will turn the input OFF and the buzzer will sound. The display will show OVP.
Operations to clear the OVP state Disconnect the instrument under test. Press any key on the front panel, the
OVP on the VFD will disappear, then the DC load exits OVP protection state.

3.17.2 Over Current Protection (OCP)

The DC load includes both hardware and software over current protection features.
Hardware OCP: maximum input current of the DC load will be limited at about 110% of the current range, once the hardware OCP is activated, the status registers OC bit will be set; when the hardware OCP is removed, the status registers OC bit will be reset. Hardware over current protection won’t change the DC loads On/Off state.
Software OCP: users can set the DC loads software OCP value, steps: [Shift] +[9] > Protect > Alimit set ON, Apoint set OCP current value, Adelay
set delay time before alarm. When the software OCP function is actived, the DC load will automatically turn off, VFD displays OCP.
Operations to clear the OCP state Disconnect the instrument under test. Press any key on the front panel, the
OCP displayed on the VFD will disappear, the DC load exits OCP protection
state.
Copyright © Itech Electronics Co., Ltd. 27
Functions and Characteristics

3.17.3 Over Power Protection (OPP)

The DC load includes both hardware and software OPP features. Hardware OPP: the DC load allows user to set a power protection limit in
hardware which will limit the power in the range you set when the OPP occur. The hardware OPP protection will not change the ON/OFF state of the the DC load.
Software OPP: users can set the DC loads software OPP value, steps: [Shift] +[9] > Protect > P-LIMIT > P-LIM POIN set OPP power value, P-LIM DEL AY set alarm delay. If the the DC load’s power value reach OPP limit and after the delay time, the DC load will automatically turned off, VFD will display OPP.
Operations to Clear the OPP State
Disconnect the instrument under test. Press any key on the front panel, the
OPP displayed on the VFD will disappear, the DC load exits OPP protection
state.

3.17.4 Over T emperature Protection (OTP)

If internal temperature exceeds safety limits(85 ;185 °F), the Over temperature circuitry will be activated. The DC Load will turn off the input, the buzzer will sound, and the display will show OTP.
Operations to Clear the OTP State
When the DC load temperature drops to the protecting point, press any key on the front panel, the OTP) displayed on the front panel will d isappear, the DC load exits OTP protection state.

3.17.5 Reverse Voltage Protection (LRV)

This feature protects the DC load in case the DC input terminals are connected to a power source with reversed polarity. If a reverse voltage condition is detected, the buzzer will sound and will be displayed on the VFD.
Operations to Clear the Reverse Voltage State
Check whether the connection is reversed; if so disconnect the power source.

3.18 Key Lock Function

Press [Shift] +[On/Off] (Lock)key to lock the front panel keys,VFD will display a Lock label.In this state,setting values can not be modified,woriking mode can not be changed.Press [Shift] +[On/Off] (Lock)again will disable this function.

3.19 The Terminals on the Rear Panel

3.19.1 Remote Sensing

Remote sensing is used to counteract the effect of lead resistance. For example, if you connect a power supply to the DC Load, the voltage at the power supply's terminals will not be the same as the voltage at the DC Load's terminals if there is a current flowing because of the finite resistance from the wires. Using remote sensing, you can sense the voltage at the power supply's terminals, effectively removing the effect of the voltage drop in the connection wire.
When using remote sensing, the power displayed by the instrument includes both the power dissipated inside the instrument and the power dissipated in the
Copyright © Itech Electronics Co., Ltd. 28
Functions and Characteristics
leads from the power supply to the DC Load's input terminals. Steps to enable remote sensing in the menu:
1. Press [Shift] +[9] key into the menu
2. VFD displays > , press [Enter] key to confirm
3. Press [ ] to choose > , press [Enter] key to confirm
4. Press [ ] to choose >, press [Enter] key to confirm, then remote sense function has been set, and VFD display indicator.
Remote Sensing: SENSE (+) and SENSE () are the remote sensing inputs. By eliminating the effect of the inevitable voltage drop in the DC load leads, remote sensing provides greater accuracy by allowing the DC load to regulate directly at the source's output terminals.
Wiring Diagram for Remote Sensing:

3.19.2 External Triggering

EXTERNAL:An external trigger is a TTL low signal applied to the Trigger
connection on the back panel. This TTL signal must last for more than 5 ms. A trigger applied to this input can be used to change settings (voltage, current , resistance), toggle between settings in transient- toggle mode, or generate a pulse in pulse mode.
Operation to select the trigger source as external:
[Shift] +[8] (system)to enter the menu,use [ ] to select TRIGGER,press [Enter],and then select EXTERNAL.Press [ESC] to exit the menu.

3.19.3 Current Monitoring (I Monitor)

Current monitoring terminal will output 0-10V analog signal to corresponding to 0 to full range of input current. You can connect an external voltmeter or an oscilloscope to display the input currents changing
Copyright © Itech Electronics Co., Ltd. 29
Functions and Characteristics

3.19.4Ripple Function

IT8500plus series DC electronic loads have test ripple function.You can read ripple voltage and ripple current by sending instructions.See in IT8500+ programming guide.
Copyright © Itech Electronics Co., Ltd. 30
Basic Operation
Step
Operation
VFD Display
1
RANGE=30.000A
2
Set the current range,press
[Enter] to confirm
RANGE =10.000A
3
Press [Esc] to escape.
HIGH=120.00V
Steps
Operation
VFD Display
1
RANGE=120.00V
2
Set the voltage range, press
[Enter] to confirm
RANGE=10.00V
3
Press [Esc] to escape.
HIGH=30.000A

Chapter4 Basic Operation

4.1 Constant Current Operation

(Set the current from 0 to the current limit) There are three ways to set the current value:
1. In CC mode, rotate Rotary knob.
2. In CC mode, input value through number keys directly , press [Enter] to
confirm.
3. In CC mode, move the cursor to change the step value by pressing the
[ ], and then adjust the current by pressing the [ ].
To set current range, follow the steps:
Press [CC], and then [Shift]
+[CV] (Setup).
Note: when you set the current range to lo w range(within 3A),the resolution of current will rise.

4.2 Constant Voltage Operation

(Set the voltage from 0.1V to the setting voltage limit) There are three ways to change the voltage:
1. In CV mode, rotate Rotary knob.
2. In CV mode,input value through number key boards directly,press [Enter]
to confirm
3. In CV mode, move the stepping cursor by pressing [ ], and then
adjust the voltage by pressing [
To set voltage range, follow the steps:
Press [CV], then [Shift] +[CV].
].
Note: When you set the voltage range to low range,the resolution of voltage will rise.
Copyright © Itech Electronics Co., Ltd. 31
Basic Operation
Steps
Operation
VFD Display
1
Press [CW], then
.
RANGE=150.00W
2
Set the power range,press [Enter] to confirm
RANGE =100.00W
3
Press [Esc] to escape.
HIGH=120.00V
Steps
Operation
VFD Display
1
(Setup).
RANGE=7500.
2
Set the resistance range,press [Enter] to confirm
RANGE =2000Ω
3
Press [Esc] to escape.
HIGH=120.0V

4.3 Constant Power Operation

(Set a value from 0 to upper limit of power) There are three ways to set the power value:
1. In CW mode, rotate Rotary konb.
2. In CW mode, input value through number key boards directly,press [Enter]
to confirm
3. In CW mode, move the stepping cursor by pressing [ ], and then
adjust the power by pressing [ ].
To set power range, follow the steps:
[Shift] +[CV]

4.4 Constant Resistance Operation

(Allowed setting range is 0.05Ω to 750) There are three ways to set the resistance value:
1. In CR mode, rotate Rotary knob.
2. In CR mode, input value through number key boards directly,press [Enter]
to confirm
3. In CR mode, move the stepping cursor by pressing [ ], and then
adjust the resistance by pressing [ ]
To set resistance range, follow the steps:
Press [CR], then [Shift] +[CV]

4.5 Transient Test Operation

Transient operation enables the DC load to periodically switch between two levels.
To edit a transient test file, related parameters need to be set: A level, B level, time width (only in pulse mode), frequency, duty and running mode (Continuous/Pulse/Toggled). If in CC dynamic mode, user can set current rising and falling slope additionally.
Following is an example to illustrate the three transient operations.
Copyright © Itech Electronics Co., Ltd. 32
Basic Operation
Steps
Operation
VFD Display
Press [Shift]+[2] (Tran), move
[Enter] to confirm.
TRAN ON OFF
to select
ation mode as
indicator lamp
Trig will be lighted)
MODE CONTINUOUS >
Set the rising slope,press [Enter] to confirm
UP=1A/uS
Set the descending slope,press
[Enter] to confirm
DOWN=2/uS
Set level A,press [Enter] to confirm
LEVEL A=5A LEVEL B=10A
Set the frequency ,press [Enter] to confirm
FREQUNCE=50HZ(0.01-10000HZ)
Set the dutyfactor,press [Enter] to confirm
DUTY=98%(%0.1-99.9%)
Open the transient test function,
[Enter]
TRAN ON OFF
Then the VFD will display TRAN A
10.0000V 0.0000A Trig
(Trigger) to trigger
quit the transient test,if you

4.5.1 Continuous Transient Operation

Press [Shift] +[2] (Tran) to enter the transient operation setup menu:
1
2
3 4 5
6 7
8
9
10
[ ] key to select ON., press
Preess [ ] transient oper
CONTINUOUS (the
Set level B,press [Enter] to confirm
mentain on the onselection, press
to confirm.
and Trig
0.00W TRAN. 0
11
12
Copyright © Itech Electronics Co., Ltd. 33
Turn on the load, press [Shift]+[ ]
Press anyone of [CC/CV/CW/CR] button can want to continue the test again, please repeat 1-11 steps
Basic Operation
Steps
Operation
VFD Display
1
Press
(Tran),
key to
to confirm.
TRAN ON OFF
2
to select
transient operation mode lamp Trig will be lighted)
MODE CONTINUOUS >
3
Set the rising slope, press
[Enter] to confirm
UP=1A/US
4
Set the descending confirm
DOWN=2A/US
5
Set level A,press [Enter] to confirm
Level A=5.000A
6
Set level B,press [Enter] to confirm
Level B=10.000A
7
Set the time width,press
[Enter] to confirm
WIDTH=5S(0.00005-3600S)
8
Open the transient test function, mentain on the
on”selection , press
[Enter] to confirm
TRAN ON OFF
9
Then the VFD will display
10.0000V 0.0000A Trig
10
Turn on the load, press
trigger
11
Press anyone of [CC/CV/CW/CR] button will quit the

4.5.2 Pulse Transient Operation

Press [Shift]+[2] (Tran) enter the transient operation setup menu:
[Shift]+[2]
move [ ] select ON., press [Enter]
Press [ ] as PULSE(the indicator
slope,press [Enter] to
TRAN and Trig
0.00W TRAN. 0
[Shift]+[ ] (Trigger) to
transient test,if you want to continue the test again,please repeat 1-10 steps.

4.5.3 T oggle T ransient Operation

Copyright © Itech Electronics Co., Ltd. 34
Basic Operation
Steps
Operation
VFD Display
1
Press [Shift]+[2] (Tran), move
[Enter]
TRAN On Off
2
Set transient operation mode as
indicator lamp
Trig will be lighted)
MODE
3
Set the rising slope, press
[Enter] to confirm.
UP=1A/US
4
Set the descending slope,press
[Enter] to confirm
DOWN=2A/US
5
Set level A, press [Enter] to confirm
LEVEL A=5A
6
Set level B, press [Enter] to confirm
LEVEL B=10A
7
Open the transient test function, confirm
TRAN ON OFF
8
Then the VFD will display
10.0000V 0.0000A Trig
9
Turn on the load, press
10
Press anyone of [CC/CV/CW/CR] button will quit the
10A
5A
TRG
TRG
Toggled Transient Operation
Press [Shift]+[2] (Tran) to enter the transient operation setup menu
[ ] key to select on.,
press
to confirm.
TOGGLE(the
CONTINUOUS >
function,press [Enter] to
TRAN and Trig
0.00W TRAN. 0
[Shift]+[ ] (Trigger) to trigger transient test,if you want to continue the test again,please
repeat 1-9 steps.

4.6 List Operation

Before run a list file,you should edit the list file firstly and save it in a non-volatile memory.The following examples will help you understand the function well.In the example, the output voltage and current are 10V and 3A,and the DC load is
Copyright © Itech Electronics Co., Ltd. 35
in CC mode.
Basic Operation
Steps
Operation
VFD Display
1
Press [Shift]+[3] (List), make sure
is flashing,if not,press
[Enter] to confirm.
LIST ON
2
Set the current range.
LIST RANGE=3A
3
Set list step count by number confirm.
LIST STEP=2(2-84)
4
Set the first step’s current, press
[Enter] to confirm.
STEP 01 =1A
5
Set the first step’s rise slope, press [Enter]to confirm.
STEP 01 =0.1A/US
6
Set the first step’s time, such as 5S. Press Enter to confirm.
STEP 01 =5S
7
Set the second step’s current, confirm.
STEP 01 =2A
8
Set the second step’s rise slope, confirm.
STEP 01 =0.1A/US
9
Set the second step’s time, such as 5S. Press [Enter] to confirm.
STEP 01 =5S
10
Set repeat times, press [Enter] to confirm.
REAPEAT =3
11
Select the position to save file, confirm.
SAVE LIST =1(1-7)
12
Press [ ] to select ON,
[Esc].
LIST ON CALL
13
Turn on the DC load, press
14
Press any function ksys if you want to quit list mode
Steps
Operation
VFD Display
Trigger
10 2 3 4 5
List count=1 List count=2
List sequence
the ON
[Enter] to select ON,then press [ ] key to select EDIT,press
keys, and press [Enter] to
such as 1A, press [Enter] to
such as 1A/uS press [Enter] to
CALL EDIT
such as 1, press [Enter] to
press [Enter] to confirm (the Trig indicator will be light now),press
[Shift]+[ ] (Trigger) to trigger.
If you want to run a list file you’ve saved, please recall it first.The steps is:
Copyright © Itech Electronics Co., Ltd. 36
EDIT
Basic Operation
1
Press [Shift]+[3] (List),
is f lashing,if not,press
[Enter] to confirm.
LIST ON CALL
2
[Enter]
confirm.
RECALL LIST =1
3
-
LIST ON CALL EDIT
Steps
Operation
VFD Display
1
Press
(Prog),
ACTIVE =0987654321
2
Press [1] ,[2] and [3], Press
[Enter] to confirm.
ACTIVE =0987654YYY
3
Select the step that needs to
can continue the test.
PAUSE
4
Step 3 short circuit testing, to confirm.
SHORT
5
Set Ton for the first step, if you
Ton range 0~60S
SEQ01 ON =2S
Set Toff for the first step, if you
Toff range 0~60S
SEQ01 OFF =2S
7
Set testing delay time, range 0~60S e.g. 1S, press [1].
SEQ01 P/F =1S
make sure
the ON
EDIT
[Enter] to select ON,then press
[ ] to select CALL,press

4.7 Test Files

Test files are a generalization of liststhey let you generate a sequence of tests using different modes, mode parameters, and durations. They are useful for executing a set of tests on a device, then displaying whether the tests passed or failed. We will illustrate how to use test files by a short example.
You can edit up to 10 groups of testing files, each file has 10 steps, it can edit up to 100 steps which can be saved in EEPROM (address).
Suppose we have a small AC to DC power supply (a "wall-wart") and we want to set up an acceptance test for a number of these devices. Our test will consist of two steps:
1. Set the DC load to constant current mode to draw the rated current of 1.2A
from the device. The output voltage of the device at the rated current must be between 4.4V and 4.6V.
2. Set the DC load to constant voltage 3V. The output current of the device is
between 2A and 3A.
Select the list file.Press
to
3. When the device operates into a short, the supplied current must be larger
than 3.0 A.
[Shift]+[6]
pause during the test.
=NNNNNNN32Y
When it is paused,press [ ]
press [3]. And press [Enter]
=NNNNNNNY21
want to load on 2S, press [2], and then press [Enter] to confirm.
6
want to load off 2S, press [2], then press [Enter] to confirm
Copyright © Itech Electronics Co., Ltd. 37
Basic Operation
Steps
Operation
VFD Display
8
Set Ton for the second step, if you want to load 2S, press
confirm
SEQ02 ON =2S
9
Set Toff of the second step, if then press [Enter] to confirm.
SEQ02 OFF =2S
10
Set testing delay time of the second step, e.g. 1S, press
[1]
SEQ02 P/F =1S
11
Set Ton for the third step, if
confirm
SEQ03 ON =3S
12
Set To ff of the third step, if you
[Enter] to confirm.
SEQ03 OFF =2S
13
Set testing delay time of the third step, e.g. 2S, press [2].
SEQ03 P/F =2S
14
set start voltage.Please refer
function of auto start
voltage”.
AUTO START=0.000V
15
Set stop condition
STOP COMP FA ILURE
[2], then press [Enter] to
you need 2S, press [2], and
you want to load on 3S, press [3], then press [Enter]to
need 2S, press [2], then press
to
Function of Auto Start Voltage:
1. Auto start=0V.
Auto test file start to run when receive a trigger signal by pressing [shift]+[trigge]r or providing a external trigger signal.
2. Auto start is not equal to 0V(Take 2V as an example)
In this condition,user only need to connect the charger to input termianls of E-load.The unit can auto start to run test file when detect a rising edge from 0-2V.Auto start voltage is not suggested to be a big value.2V is suitable.
Ton, Toff and Tpf (P/F) Relation:
Copyright © Itech Electronics Co., Ltd. 38
Basic Operation
15
Set stop conditions: COMP means
[Enter] key to confirm.
STOP COMP
16
Select the test file to link if youd like to. The linked file must be saved
key to
confirm.
CHAIN PROGRAM
PROGRAM 1 Sequence
1 2 3 4 5 6 7 8 9
10
Save Group
1 2 3 4 5 6 7 8 9
10
PROGRAM 2 Sequence
1 2 3 4 5 6 7 8 9
10
Save Group
11
12
13
14
15
16
17
18
19
20
PROGRAM 10 Sequence
1 2 3 4 5 6 7 8 9
10
Save Group
91
92
93
94
95
96
97
98
99
100
17
Save the edited files in EEPROM,
[Enter]
SAVE PROGRAM
18
Select a operation mode and then
to set related
parameters
10.0000V 0.0000 A
19
Edit the three steps of the test file,
You need to recall the test file before runing it
Step
Operation
VFD Display
1
Press [CC] button,and then
to enter
the setting interface
RANGE=30.000A
2
Set the current range,press
[Enter]
RANGE =1.2A
3
set the upper limit of voltage,
[Enter]
HIGH=4.6V
4
Set the lower limit of voltage,
[Enter]
LOW=4.4V
5
Set the rise speed of current, press [Enter] to confirm
UP=1A/uS
6
Set the fall speed of current, press [Enter] to confirm
DOWN=1A/uS CC
7
Finish the setup
10.0000V 0.000 A
0.00W CC=0.000A
Tpf is the delay time for a step
stop test when all the steps are completed, FAILURE means stop test when the testing fails. Press
FAILURE
=0(0-10)
before. 0 stands for not linking to other files. Press [Enter]
you can save up to 10 groups of files, e.g please press [1] to save the edited file in group 1, and then press
to confirm.
=1(1-10)
press [Shift]+[CV]
details refer to below procedure. After all the steps are set , Press [ESC] to exit setup, and then press
[Shift]+[4] to save.
Set the steps of a test file in the example CC Mode, 1.2A, Voltage Range 4.4V~4.6V
[Shift)+[CV] (Setup)
to confirm
press
press
to confirm
to confirm
0.00W CC=1.000A
CC
CC
CC
CC
Copyright © Itech Electronics Co., Ltd. 39
CC
Basic Operation
Steps
Operation
VFD Display
1
Press [CV] button,press
to set related
parameters
RANGE=120.00V
2
Set the voltage range,press
[Enter]
RANGE=3.00V
3
set the upper limit of current,press [Enter] to confirm
HIGH=3A
4
Set the lower limit of current,press [Enter] to confirm
LOW=2A
5
Finish the setup
10.0000V 0.000 A
0.00W CV=10V
Steps
Operation
VFD Display
1
Press [CW] button,press
to set re lated
parameters
RANGE=150.00W
2
Set the power range,press
[Enter]
RANGE =1.00W
3
Set the upper limit of
[Enter]
HIGH=120.00V
4
Set the lower limit of
[Enter]
LOW=0.000V
5
Finish the setup
10.0000V 0.000 A
0.00W CW=1.00W
Steps
Operation
VFD Display
1
Press [CR] button,press
to set
related parameters
RANGE=7500.
2
Set the resistance range,press
[Enter]
RANG E = 2 Ω
3
set the upper limit of
[Enter]
HIGH=120.0V
4
Set the lower limit of
[Enter]
LOW=0.000V
5
Finish the setup
10.0000V 0.000 A
0.00W CR=2.000Ω
Operation
Display on Front Pannel
1.Press [Shift]
(system) enter
0.0000V 0.000A
2.Press right key,select RUNMODE and confirm with [Enter] button
0.0000V 0.000A
CV Mode, 3V, Current Range 2A~3A
[Shift]+[CV]
to confirm
The CW and CR is set as the same way: CW Mode
[Shift]+[CV]
voltage,press
voltage,press
CR Mode
[Shift]+[CV](Setup)
voltage,press
voltage,press
to confirm
to confirm
to confirm
to confirm
to confirm
to confirm
Go into Autotest Mode
into sysmtem menu
Copyright © Itech Electronics Co., Ltd. 40
+[8]
POWER-ON BUZZER
RUN <NORMAL
Basic Operation
3.Press direction key to select confirm.
0.0000V 0.000A 4,Press [Esc] button to quit menu
0.0000V 0.000A
OCP_TEST,Press [Enter] to
set
According to the following steps to escape OPP mode: Press [Shift]+[8] (system)---”RUNMODE---[Eneter]----select “NORMAL
mode---[Enter].
(6)Start Auto Test File
Press [ ](trigger) to provide a signal to start auto test file.The discharing process will be auto terminated when stop conditions are reached.
(7)Recall Test File
Press [Shift]+[Enter] button to select programe file,the panel displays RECALL PROGRAM= 1.Enter the file name(1-10),press [Enter] button to confirm.
If you need a pause, please press [Shift]+[0] (pause).Press [ ] can continue the test.
RUN <PROG_TEST
P01
Copyright © Itech Electronics Co., Ltd. 41
Communication Interfaces

Chapter5 Communication Interfaces

DB9 in the rear panel of the DC load could connect with RS-232 through on TTL connector. The following description may help you to know how to control the output of the DC load through PC.
WA RNING: Don’t connect the DC load’s DB9 connector to a standard RS232 instrument; doing so may damage the instrument.

5.1Communication Modules Intruduction

IT-E121 Communication Module
The DB9 interface connector on the rear panel of the DC load is TTL voltage level; you can use the communication module IT-E121 and an a standard RS232 extension cable to connect the DB9 interface connector of the DC load and the RS-232 interface connector of computer for the communication.
IT-E121A Communication Module
The DB9 interface connector on the rear panel of the DC load is TTL voltage level; you can use the communication module IT-E121A and an a standard RS232 extension cable to connect the DB9 interface connector of the DC load and the RS-232 interface connector of computer for the communication.
IT-E121A is derived on the basis of IT-E121,the main difference between them is that the DB9 interface connector of the RS232 changes from female to male ,so that can be directly connected to the standard LAN interface.
IT-E121A communication cable
IT-E122 Communication Module
The DB9 interface connector on the rear panel of the DC load is TTL voltage level;
Copyright © Itech Electronics Co., Ltd. 42
Communication Interfaces
IT-E122 has a USB interface on one end,you can use IT-E122 and an a standard USB extension cable to connect the DB9 interface connector of the DC load and the USB interface connector of computer for the communication.
IT-E123 Communication Module
The DB9 interface connector on the rear panel of the DC load is TTL voltage level;
The interface on both side port of IT-E123 are DB9 interface and RS485 interface, you
can use the communication module IT-E123 and an a standard RS485-RS232 conversion cable to connect the DB9 interface connector of the DC load and the RS-232 interface connector of computer for the communication.
RS485 pins

5.2 Communication with PC

Before using the remote operation mode, please make sure that the baud rate and communication address in the DC load are the same as in the computer software, otherwise, the communication will fail, you can change the baud rate and communication address from the front panel or from computer.
Copyright © Itech Electronics Co., Ltd. 43
Communication Interfaces
Base Pin
Description
1
No conjunction
2
TXD, data transmission
3
RXD, data receiving
4
No conjunction
5
GND, grounding
6
No conjunction
7
CTS, clear to send
8
RTS, request to send
9
No conjunction
DB9 Serial Port
In order for the computer to communicate with the DC load, both must be set to the same RS-232 settings. These communication settings are:
1. Address: the range is from 0 to 31, default setting is 0
2. Baud rate: 4800,9600,19200 and 38400 are selectable, default setting is
9600. Refer to chaptor 1.7.
3. Data bit: 8 bit
4. Stop bit: 1
5. Parity: None,Even, Odd, default is None, refer to chaptor1.7.
Parity=None Start Bit 8 Data Bits Stop Bit
RS-232
IT8514B+/IT8514C+/IT8516C+ series electronic load have a DB9 interface on rear panel. Connect E-load and computer by cable of COM ends (DB9). Composite key [Shift]+[8] on front board can be used to enter system menu for activation.
RS-232 Interface In RS-232 interface, all SCPI commands can be used for programming. If
RS-232 interface is selected, in accordance with internal connection of data terminal equipment (DTE) and data communication equipment (DCE) as defined in EIA RS-232, the load is connected to another DTE (e.g., PC COM interface) with direct-connected Modem cable.
Number
RS232 Pins of Plug
Copyright © Itech Electronics Co., Ltd. 44
Communication Setup Please ensure the PC and the load have the same configuration in the following
items. Baudrate: 9600(480096001920038400).You could enter the system menu
Communication Interfaces
to set the baudrate. Data bit: 8 Stop bit: 1 Parity bit: (none,even,odd)
EVEN 8 data bits have even parity ODD 8 data bits have odd parity NONE 8 data bits have no parity
Native machine address: ( 0 ~31, factory default is 0)
Start Bit 8 Data Bits Parity=None Stop Bit

5.3USB Interface

Connect the load and the computer using a cable with two USB interfaces (each end). All functions of the load can be programmed via USB.
After connecting the load and computer by USB, you need to install IT-E122 driver or IT-E132 driver ( see in ITECH CD or contact ITECH agent). The device manager of PC will display Prolific USB-to-Serial COM Port after installing.
Notes: Only IT8514B+/8514C+/IT8516C+ m odels have the USB commucation interface. Just use USB line to connect in commucation. ( Please don’t connect DB9 interface at the same time). Don’t need to set the menu.
Copyright © Itech Electronics Co., Ltd. 45
Specifications
input voltage
0~120V
0~120V
input power
150W
300W
Minimum
value
±(0.05%+0.025%F
S)
0~30A
1mA
resolution
accuracy
0.01%+0.0008S
range
resolution
accuracy
Dynamic mode
accuracy
minimum rise time *5
Measuring range
Protection range
OPP
Protection
OCP
Protection
OVP
Protection
OTP
Protection

Chapter6 Specifications

Specifications

Model IT8511+ IT8512+
Rated
input current
0~3A 0~30A 0~3A 0~30A
value
( 0~40 )
CV mode
CC mode
operation
range
resolution
accuracy
range
resolution
0.14V at 3A 1.4V at 30A 0.12V at 3A 1.2V at 30A
0.1~18V 0.1~120V 0.1~18V 0.1~120V 1mV 10mV 1mV 10mV
±(0.05%+0.02%FS) ±(0.05%+0.025%FS) ±(0.05%+0.02%FS)
0~3A 0~30A 0~3A
0.1mA 1mA 0.1mA
accuracy
CR mode
*1
CP mode
*3
range
0.05Ω~1 10Ω~7.5KΩ 0.05Ω~10Ω 1~7.5KΩ 16bit 16bit
0.01%+0.08S *2
±(0.1%+0.1%FS) ±(0.1%+0.1%FS)
0.01%+0.0008S
150W 300W
10mW 10mW
CC
T1T2
Rising/Falling slope *4
0.0001~0.2A/uS 0.001~1.5A/uS 0.0001~0.2A/uS 0.001~1.5A/uS
20uS~3600S /Res:1 uS 20uS~3600S /Res:1 uS
2u100ppm 2u100ppm
10uS 10uS 10uS 10uS
±(0.05%+0.05%FS)
0.01%+0.08S *2
Readback
voltage
Readback
current
Readback power
Short
range
resolution
accuracy
range
resolution
accuracy
range
resolution
accuracy
current(CC) voltage(CV)
3.3A
0~18V 0~120V 0~18V 0~120V
0.1 mV 1 mV 0.1 mV 1 mV ±(0.025%+0.025%FS)
0~3A 0~30A 0~3A 0~30A
0.1mA 1mA 0.1mA 1mA ±(0.05%+0.05%FS) ±(0.05%+0.05%FS)
150W 300W
10mW 10mW
±(0.1%+0.1%FS) ±(0.1%+0.1%FS)
160W
33A 3.3A 33A
125V
320W
125V
85 85
Specification
3.3/3A 33/30A 3.3/3A 33/30A
0V 0V 0V 0V
Copyright © Itech Electronics Co., Ltd. 46
Specifications
resistance(C
R)
input
e
Model
IT8511A+
IT8512A+
input voltage
0~150V
0~150V
input current
0~3A
0~30A
0~3A
0~30A
input power
150W
300W
Minimum
operation value
±(0.05%+0.025%F
S)
range
0~3A
0~30A
0~3A
0~30A
±(0.05%+0.05%
FS)
range
0.05Ω~10Ω
10Ω~7.5KΩ
0.05Ω~10Ω
10Ω~7.5KΩ
resolution
16bit
16bit
accuracy
0.01%+0.08S *2
0.01%+0.0008S
0.01%+0.08S *2
0.01%+0.0008S
range
150W
300W
resolution
10mW
10mW
accuracy
±( 0.1%+0.1%FS )
±( 0.1%+0.1%FS )
20uS~3600S /Res:1 uS
2uS±100ppm
±(0.025%+0.025%
OPP
on
OCP
on
OVP
on
OTP
on
45mΩ 45mΩ 40mΩ 40mΩ
Impendanc
Dimension
214.5mm*88.2mm*354.6mm 214.5mm*88.2mm*354.6mm
150KΩ 150KΩ
Rated
value
( 0~40
)
0.25V at 3A 2.5V at 30A 0.14V at 3A 1.4V at 30A
range 0.1~18V 0.1~150V 0.1~18V 0.1~150V
CV
resolution 1mV 10mV 1mV 10mV
mode
±(0.05%+0.02%FS) ±(0.05%+0.025%FS) ±(0.05%+0.02%FS)
CC
accuracy
resolution 0.1mA 1mA 0.1mA 1mA
mode
accuracy ±(0.05%+0.05%FS) ±(0.05%+0.05%FS) ±(0.05%+0.05%FS)
CR
mode
*1
CP
mode
*3
Dynamic mode( CC mode )
T1T2
20uS~3600S /Res:1 uS
accuracy 2uS±100ppm
Rising/Falling slope *4 0.0001~0.2A/uS 0.001~1.5A/uS 0.0001~0.2A/uS 0.001~1.5A/uS
minimum rise time *5 10uS 10uS 10uS 10uS
Measuring range
Readba
ck
voltage
Readba
ck
current
range 0~18V 0~150V 0~18V 0~150V
resolution 0.1 mV 1 mV 0.1 mV 1 mV
accuracy
±(0.025%+0.025%FS) ±(0.025%+0.025%FS) ±(0.025%+0.025%FS)
FS)
range 0~3A 0~30A 0~3A 0~30A
resolution 0.1mA 1mA 0.1mA 1mA
accuracy ±(0.05%+0.05%FS) ±(0.05%+0.05%FS)
range 150W 300W
Readbac
k power
resolution 10mW 10mW
accuracy ±(0.1%+0.1%FS) ±(0.1%+0.1%FS)
Protection range
320W
Protecti
160W
Protecti
Protecti
Protecti
Copyright © Itech Electronics Co., Ltd. 47
3.3A 33A 3.3A 33A
160V 160V
85 85
Specifications
resistance( CR
)
input
ance
Dimensi
on
input voltage
0~500V
input current
0~3A
0~10A
input power
150W
Minimum
value
range
0.5Ω~10Ω
10Ω~7.5KΩ
resolution
16bit
accuracy
0.01%+0.08S *2
0.01%+0.0008S
range
150W
resolution
10mW
accuracy
0.1%+0.2%FS
CC mode
T1T2
Rising/Falling
slope*4
minimum rise
*5
Protection range
Specification
3.3/3A 33/30A 3.3/3A 33/30A
80mΩ 80mΩ 40mΩ 40mΩ
Short
current( CC )
voltage( CV ) 0V 0V 0V 0V
Impend
Rated value
( 0~40 )
CV mode
CC mode
CR mode*1
CP mode
*3
150KΩ 150KΩ
214.5mm*88.2mm*354.6mm 214.5mm*88.2mm*354.6mm
Model IT8511B+
operation
range 0.1~50V 0.1~500V
resolution 1mV 10mV
accuracy ±(0.05%+0.05%FS) ±(0.05%+0.05%FS)
range 0~3A 0~10A
resolution 0.1mA 1mA
accuracy ±(0.05%+0.05%FS) ±(0.05%+0.05%FS)
1.2V at 3A 4V at 10A
Dynamic mode
20uS~3600S /Res:1 uS
Dynamic mode
accuracy 2uS±100ppm
0.0001~0.2A/uS 0.001~0.8A/uS
time
10uS 10uS
Measuring range
Readback
voltage
Readback
current
Readback power
OPP Protection OCP Protection OVP Protection OTP Protection
Copyright © Itech Electronics Co., Ltd. 48
range 0~50V 0~500V
resolution 1 mV 10 mV
accuracy ±(0.025%+0.025%FS) ±(0.025%+0.025%FS)
range 0~3A 0~10A
resolution 0.1mA 1mA
accuracy ±(0.05%+0.05%FS)
range 150W
resolution 10mW
accuracy ±(0.1%+0.2%FS)
160W
3.3A 11A
530V
85
Specifications
resistance( C
R )
input
Impendance
input voltage
0~500V
0~120V
input power
300 W
300 W
Minimum
value
resolution
1mV
10mV
1mV
10mV
±(0.05%+0.025%F
S)
range
0.3Ω~10Ω
10Ω~7.5KΩ
0.3Ω~10Ω
10Ω~7.5KΩ
resolution
16bit
16bit
range
300W
300W
resolution
10mW
10mW
accuracy ±(0.1%+0.1%FS)
0.1%+0.1%FS)
CC mode
OPP
Protection
OCP
Protection
OVP
Protection
Specification
Short
Dimension
Model IT8512B+ IT8512C+
Rated value
( 0~40 )
CV mode
CC mode
current( CC )
voltage( CV ) 0V 0V
input current 0~3A 0~15A 0~6A 0~60A
operation
range 0.1~50V 0.1~500V 0.1~18V 0.1~120V
accuracy
range 0~3A 0~15A 0~6A 0~60A
resolution 0.1mA 1mA 0.1mA 1mA
accuracy ±(0.05%+0.05%FS)
0.6V at 3A 3V at 15A 0.25V at 6A 2.5V at 60A
±(0.05%+0.02%FS) ±(0.05%+0.025%FS) ±(0.05%+0.02%FS)
3.3/3A 11/10A
400mΩ 400mΩ
1
214.5mm*88.2mm*354.6mm
CR mode
*1
accuracy 0.01%+0.08S *2 0.01%+0.0008S 0.01%+0.08S *2 0.01%+0.0008S
CP mode
*3
±(
Dynamic mode
T1T2 20uS~3600S /Res:1 uS 20uS~3600S /Res:1 uS
accuracy
Rising/Falling slope *4
minimum rise time *5 10uS 10uS 10uS 10uS
0.0001~0.2A/uS 0.001~0.8A/uS 0.0001~0.3A/uS 0.001~3A/uS
2uS±100ppm 2uS±100ppm
Measuring range
Readback
voltage
Readback
current
Readback power
range 0~50V 0~500V 0~18V 0~120V
resolution 1 mV 10mV 1 mV 10mV
accuracy ±(0.025%+0.025%FS)
range 0~3A 0~15A 0~6A 0~60A
resolution 0.1mA 1mA 0.1mA 1mA
accuracy ±(0.05%+0.05%FS) ±(0.05%+0.05%FS)
range 300W 300W
resolution 10mW 10mW
accuracy ±(0.1%+0.1%FS) ±(0.1%+0.1%FS)
Protection range
320W
320W
Copyright © Itech Electronics Co., Ltd. 49
3.3A 16A 6.5A 65A
530V 125V
Specifications
OTP
Protection
resistance( C
R )
input
e
input voltage
0~800V
input current
0~1A
0~5A
input power
300W
Minimum
value
accuracy
±(0.05%+0.05%FS)
±(0.05%+0.05%FS)
range
2Ω~10Ω
10Ω~7.5KΩ
resolution
16bit
accuracy
0.01%+0.08S *2
0.01%+0.0008S
range
300W
resolution
10mW
accuracy
0.2%+0.2%FS
minimum rise
*5
Protection range
85 85
Specification
current( CC ) 3.3/3A 16/15A 6.5/6A 65/60A
Short
voltage( CV ) 0V 0V 0V 0V
180mΩ 180mΩ 40mΩ 40mΩ
Impendanc
1 150KΩ
Dimension 214.5mm*88.2mm*354.6mm 214.5mm*88.2mm*354.6mm
Model IT8512H+
Rated value
( 0~40 )
CV mode
CC mode
CR mode*1
operation
range 0.1~80V 0.1~800V
resolution 1mV 10mV
range 0~1A 0~5A
resolution 0.1mA 1mA
accuracy ±(0.05%+0.1%FS) ±(0.05%+0.05%FS)
1.4V at 1A 7V at 5A
CP mode
*3
Dynamic mode
Readback
voltage
Readback
current
Readback power
Dynamic mode
CC mode
T1T2
accuracy 2uS±100ppm
Rising/Falling
slope*4
time
0.0001~0.04A/uS 0.001~0.2A/uS
20uS 20uS
20uS~3600S /Res:1 uS
Measuring range
range 0~80V 0~800V
resolution 1 mV 10 mV
accuracy ±(0.025%+0.025%FS) ±(0.025%+0.025%FS)
range 0~1A 0~5A
resolution 0.1mA 1mA
accuracy ±(0.05%+0.05%FS)
range 300W
resolution 10mW
accuracy ±(0.2%+0.2%FS)
OPP Protection 320W OCP Protection
Copyright © Itech Electronics Co., Ltd. 50
1.1A 5.5A
Specifications
Specification
resistance( C
R )
input
Impendance
input voltage
0~150V
input current
0~6A
0~60A
input power
400W
Minimum
value
range
0.1Ω~10Ω
10Ω~7.5KΩ
accuracy
0.01%+0.08S *2
0.01%+0.0008S
range
400W
resolution
10mW
accuracy
±(0.2%+0.2%FS)
Rising/Falling
slope*4
minimum rise
*5
Protection range
OVP Protection 850V OTP Protection 85
Short
Dimension
Rated value
( 0~40 )
CV mode
CC mode
current( CC )
voltage( CV ) 0V 0V
1.1/1A 5.5/5A
1.
2
214.5mm*88.2mm*354.6mm
Model IT8513A+
operation
range 0.1~18V 0.1~150V
resolution 1mV 10mV
accuracy ±(0.05%+0.02%FS) ±(0.05%+0.025%FS)
range 0~6A 0~60A
resolution 0.1mA 1mA
accuracy ±(0.05%+0.05%FS) ±(0.05%+0.05%FS)
0.25V at 6A 2.5V at 60A
CR mode*1
CP mode
*3
Dynamic
mode
Readback
voltage
Readback
current
Readback power
resolution 16bit
Dynamic mode
CC mode
T1T2 20uS~3600S /Res:1 uS
accuracy
time
0.001~0.15A/uS 0.01~1 A/uS
50uS 60uS
2Us100ppm
Measuring range
range 0~18V 0~150V
resolution 0.1 mV 1mV
accuracy ±(0.025%+0.025%FS) ±(0.025%+0.025%FS)
range 0~6A 0~60A
resolution 0.1mA 1mA
accuracy ±(0.05%+0.05%FS)
range 400W
resolution 10mW
accuracy ±(0.2%+0.2%FS)
OPP
Copyright © Itech Electronics Co., Ltd. 51
420W
Specifications
Protection
OCP
Protection
OVP
Protection
OTP
Protection
Specification
resistance( C
R )
input
e
Model
IT8513C+
IT8514C+
input voltage
0~120V
0~120V
input current
0~12A
0~120A
0~24A
0~240A
input power
600 W
1500W
Minimum
value
±(0.05%+0.025%F
range
0~12A
0~120A
0~24A
0~240A
resolution
16bit
16bit
accuracy
0.01%+0.08S *2
0.01%+0.0008S
0.02%+0.08S *2
0.02%+0.0008S
range
600W
1500W
resolution
10mW
10mW
accuracy ±(0.2%+0.2%FS)
±(0.2%+0.2%FS)
Dynamic mode
Rising/Falling slope *4
Measuring range
range
0~18V
0~120V
0~18V
0~120V
resolution
0.1 mV
1mV
0.1 mV
1mV
6.6A 66A
165V
85
current( CC ) 6.6/6A 66/60A
Short
Impendanc
Dimension
Rated value
( 0~40 )
CV mode
CC mode
CR mode
*1
voltage( CV )
280KΩ
214.5mm*88.2mm*453.5mm
operation
range 0.1~18V 0.1~120V 0.1~18V 0.1~120V
resolution 1mV 10mV 1mV 10mV
accuracy
resolution 1mA 10mA 1mA 10mA
accuracy
range 0.05Ω~10Ω 10Ω~7.5KΩ 0.05Ω~10Ω 10Ω~7.5KΩ
0.2V at 12A 2V at 120A 0.25V at 24A 2.5V at 240A
±(0.05%+0.02%FS) ±(0.05%+0.025%FS) ±(0.05%+0.02%FS)
±(0.05%+0.05%FS) ±(0.1%+0.1%FS)
0V
30mΩ
S)
CP mode
*3
minimum rise time *5 60uS 60uS 60uS 60uS
Readback
voltage
Readback
current
Readback
power
Copyright © Itech Electronics Co., Ltd. 52
T1T2
accuracy
accuracy ±(0.025%+0.025%FS)
resolution 1mA 10mA 1mA 10mA
accuracy ±(0.05%+0.05%FS) ±(0.05%+0.05%FS)
resolution 10mW 10mW
CC mode
100uS~3600S /Res:1 uS 100uS~3600S /Res:1 uS
10uS±100ppm 10uS±100ppm
0.001~0.2A/uS 0.01~1.6A/uS 0.001~0.3A/uS 0.01~3.2A/uS
range 0~12A 0~120A 0~24A 0~240A
range 600W 1500W
Specifications
Protection range
OPP
Protection
OCP
Protection
OVP
Protection
OTP
Protection
Specification
voltage( CV )
0V
0V
0V
0V
resistance( C
R )
input
e
Model
IT8514B+
IT8516C+
input voltage
0~500V
0~120V
input current
0~6A
0~60A
0~24A
0~240A
input power
1500 W
3000W
Minimum
value
±(0.05%+0.025%F
range
0~6A
0~60A
0~24A
0~240A
range
0.05Ω~10Ω
10Ω~7.5KΩ
0.05Ω~10Ω
10Ω~7.5KΩ
resolution
16bit
16bit
accuracy
0.02%+0.08S *2
0.02%+0.0008S
0.02%+0.08S *2
0.02%+0.0008S
range
1500W
3000W
resolution
10mW
10mW
accuracy
±( 0.2%+0.2%FS )
±( 0.2%+0.2%FS )
Dynamic mode
Rising/Falling slope *4
Measuring range
range
0~50V
0~500V
0~18V
0~120V
resolution
0.1 mV
1mV
0.1 mV
1mV
accuracy ±(0.2%+0.2%FS) ±(0.2%+0.2%FS)
620W
13A 130A 26.7A 267A
125V 125V
95 85
current( CC ) 13/12A 130/120A 26.7/24A 267/240A
1550W
Short
15mΩ 15mΩ 8 8
Impendanc
150KΩ 150KΩ
Dimension 214.5mm*88.2mm*453.5mm 436.5mm*88.2mm*463.5mm
Rated value
( 0~40 )
operation
0.25V at 6A 2.5V at 60A 0.15V at 24A 1.5V at 240A
CV mode
CC mode
CR mode
*1
CP mode
*3
minimum rise time *5 60uS 60uS 70uS 70uS
Readback
voltage
Readback
current
Readback
power
Copyright © Itech Electronics Co., Ltd. 53
resolution 1mV 10mV 1mV 10mV
accuracy
resolution 1mA 10mA 1mA 10mA
accuracy
T1T2
accuracy
accuracy ±(0.025%+0.025%FS)
resolution 1mA 10mA 1mA 10mA
accuracy ±(0.05%+0.05%FS) ±(0.1%+0.1%FS)
resolution 10mW 10mW
accuracy ±(0.2%+0.2%FS) ±(0.2%+0.2%FS)
range 0.1~50V 0.1~500V 0.1~18V 0.1~120V
±(0.05%+0.02%FS) ±(0.05%+0.025%FS) ±(0.05%+0.02%FS)
±(0.05%+0.05%FS)
CC mode
100uS~3600S /Res:1 uS 120uS~3600S /Res:1 uS
10uS±100ppm 10uS±100ppm
0.001~0.15A/uS 0.01~0.8A/uS 0.001~0.3A/uS 0.01~2.8A/uS
range 0~6A 0~60A 0~24A 0~240A
range 1500W 3000W
±(0.1%+0.1%FS)
S)
Specifications
Protection range
OPP
Protection
OCP
Protection
OVP
Protection
OTP
Protection
Specification
voltage( CV )
0V
0V
0V
0V
resistance( C
R )
input
e
3050W
current( CC )
1550W
6.7A 67A 26A 260A
530V 125V
85 85
6.7/6A 67/60A 26/24A 260/240A
Short
30mΩ 30mΩ 5 5
Impendanc
Dimension
436.5mm*88.2mm*463.5mm 436.5mm*176mm*463.5mm
150KΩ 150KΩ
*1 The voltage/current input is no less than 10% FS *2 The scope of read-back resistance is:( 1/(1/R+(1/R)*0.01%+0.08),1/(1/R-(1/R)*0.01%-0.08) )
IT8514B+/14C+/16C+: ( 1/(1/R+(1/R)*0.02%+0.08),1/(1/R-(1/R)*0.02%-0.08) )
The voltage/current input is no less than 10% FS
*3 *4 .Ascending/descending slope: 10%-90% current ascending slope from 0 to maximum current *5 Minimum rise time: 10%-90% current rise time
* The above specifications may be subject to change without prior notice.

Supplementary Characteristics

Memory capacity:100 registeres
Suggested calibration frequency:Once a year
AC input level(A transfer switch is selectable on the rear panel)
Option Opt.1: 220V ±10% 50Hz/60Hz Option Opt.2: 110V ±10% 50Hz/60Hz
Cooling type
Intelligent fans
Fans working principle:
Fans running speed is determined by radiator temperature.When temperature reaches 40,fans start to work and intelligently adjust its speed with temperature v ariation.
Copyright © Itech Electronics Co., Ltd. 54
Appendix
Model
Specification
Cross Section
Length
IT-E301/10A
10A
-
1m
IT-E301/30A
30A
6mm2
1.2m
IT-E301/30A
30A
6mm2
2m
IT-E301/60A
60A
20mm2
1.5m
IT-E301/120A
120A
50mm2
2m
IT-E301/240A
240A
70mm2
1m
IT-E301/240A
240A
70mm2
2m
IT-E301/360A
360A
95mm2
2m
AWG
10
12
14
16
18
20
22
24
26
28
The
40
25
20
13
10 7 5
3.5
2.5
1.7

Appendix

Specifications of Red and Black Test Lines

ITECH provides you with optional red and black test lines, which individual sales and you can select for test. For specifications of ITECH test lines and maximum current values, refer to the table below.
For maximum current of AWG copper wire, refer to table blow.
Maximum Current Value( A)
Note: AWG ( American Wire Gage), it means X wire ( marked on the wire). The table above lists current capacity of single wire at working temperature of 30°C. For reference only.
Copyright © Itech Electronics Co., Ltd. 55
Contact Us
Thanks for purchasing ITECH products. In case of any doubts, please contact us as follows:
1.
Refer to accompanying data disk and relevant manual. Visit ITECH website: www.itechate.com.
2.
3. Select the most convenient contact method for further information.
Loading...