9
7 Installation dimensions
Type Height Width Depth
CR 42 20-3/4 15 18-3/4 (12-1/2)
CR 42 INOX 20-7/8 15-3/4 20-5/16 (14-15/16)
CR 49 20-3/4 15 18-1/2
CR 49 INOX 20-7/8 15-3/4 20-5/16
CR 65 20-7/8 17-3/4 20-3/8
CR 65 INOX 20-3/4 18-7/16 21-3/16
CR 85 24-5/8 18-3/4 20-1/4
CR 85 INOX 24-3/8 19-1/2 21-3/4
CR 130/CR 130 Drink 29-5/8 20-3/4 19-7/8
CR 130 INOX/
CR 130 Drink INOX
29-5/16 21-7/16 21-3/8
Please notice! Refrigerators with AC/DC electronic unit have a depth of 3/4” more than in the table above.
Dimension drawings can be seen on www.indelmarineusa.com
080515-LLG
CRman-us08.ind
6 Fault fi nding
Fault Possible cause Action
Fridge not cold, compressor will
not start.
No power supply.
Battery in poor condition.
Faulty thermostat.
Faulty electronic unit.
Check that power is present at electronic unit.
Check fuse.
Check polarity on connectors and cables.
Bridge the thermostat over T-C, see wiring diagram.
If compressor starts, this indicates a faulty thermostat. If the compressor does not start, this indicates a
faulty electronic unit or compressor.
Contact an authorized service agent.
A possible leak in the cooling system, contact an
authorized service agent.
Compressor makes only short
start attempts.
Bad power supply, too low voltage or
voltage drop at start attempts.
Discharged batteries.
Check cables, terminals and other connections, possible verdigris or corrosion, Clean.
Charge batteries, run the engine or connect a battery
charger. Voltage must be kept above 11.0 V at start
attempts.
Compressor runs but no refrigeration generated.
Loss of refrigerant. Leakage in pipes or
evaporator.
Pipes blocked.
Pressure and leak test. Check for pipe damages.
Repair possible leak, evacuate and re-fi ll refrigerant.
(All this to be made by refrigeration specialist).
Compressor runs long time but
not generating enough cold.
Bad ventilation. Condenser too warm.
Cooling fan not working
To o much frost on evaporator.
Door not closing well.
Condenser blocked by dust.
Improve ventilation for compressor.
Re-place fan.
Defrost.
Check/adjust door position and door seal.
Clean condenser.
Fuse blows. Wrong fuse size.
Faulty electronic unit.
Check fuse, 15 A-12 V / 7,5 A-24 V
Exchange electronic unit.
If a complicated fault does occur, such as reqouiring specialist assistance, please contact Indel Marine USA,
Inc or your local marine distributor for advice.