Isokern Standard 36, Standard 46, Standard 42, Magnum 28, Magnum 48 Installation, Operation, Maintenance And Owner's Manual

Isokern® Standard Fireplace
Magnum Fireplace
with Fire-Lite Application
and DM Chimney System
Installation, Operation, Maintenance and Owner’s Manual
Isokern Standard Models 36, 42 & 46
Magnum Models 28, 36, 42, & 48
A PRODUCT OF EARTHCORE
Important: This manual contains assembly rules, installation steps, guidelines, use and maintenance instructions
for the Isokern Standard and Magnum Series replaces, DM chimney system, and Fire-Lite Application with the FTF-13 Chimney System. This manual must become the property of and be reviewed by all current and
future users of this product. It is the responsibility of the general contractor and the installer of this product to ensure that the instructions in this manual are followed exactly and that any allowed gas log appliance
used in this product be installed in strict accordance with NFPA 58, NFPA 54/ANSI Z223.1 and the gas log
manufacturer’s explicit installation, sizing and operation instructions. It is the responsibility of the general
contractor to provide adequate clearances from all rebox surfaces as specied in this manual.
INSTALLER: Leave this manual with the appliance
CONSUMER: Retain this manual for future reference
Be Sure to Read Entire Manual Before Beginning Construction.
Contents of this manual may change without prior notication.
THESE FIREPLACES ARE DESIGNED for USE with
SOLID WOOD LOGS, PLUMBED PROPANE
(LP) or NATURAL GAS (NG), ONLY
WARNING: If the information in this manual is not followed exactly, a re or explosion may
result causing property damage, personal injury or loss of life.
SBCCI NO. 9626 NYC-MEA 241-90-E ICC Report NO. ESR-2316 LA RR NO. 25483 Issued: September 2012 Revision: 005
INTERTEK TESTING SERVICES REPORT NO. 3159656MID-008
© 2007 Earthcore Industries, L.L.C.
THIS MANUAL CAN ONLY BE REPRODUCED IN ITS ENTIRETY
TABLE OF CONTENTS
General Information .......................................................................................................................................
Intended Use Statement ......................................................................................................................................
Safety Instructions ..............................................................................................................................................
Warnock-Hersey Listing Label ...........................................................................................................................
Assembled Firebox & Smoke Dome Dimensions -Isokern Standard Series .......................................................
Component List & Dimensions ..........................................................................................................................
Assembled Firebox & Smoke Dome Dimensions -Magnum Series ...................................................................
Component List & Dimensions ...........................................................................................................................
Required Clearance to Combustibles .................................................................................................................
Rough Framing Dimensions & Corner Location Layout ...................................................................................
Assembly Instructions .................................................................................................................................
Access Modication ...........................................................................................................................................
Firebrick Installation ..........................................................................................................................................
Flush Wall Finish Detail .....................................................................................................................................
Required Clearances (When sheathing protrudes beyond front of rebox) .......................................................
Required Clearance to Combustible Framing ....................................................................................................
Flush Wall Fire Brick Finish Detail ....................................................................................................................
Interior Masonry Veneer Fireplace Finishes & Clearances...................................................................
Masonry Veneer Construction Details ..................................................................................................
Non Combustible Finished Facing Requirements & Clearance to Combustible Trim .......................................
Concrete Support ...............................................................................................................................................
DM Chimney System ........................................................................................................................................
General Information ............................................................................................................................
Component List & Dimensions.............................................................................................................
Component Weights .............................................................................................................................
Installation ...........................................................................................................................................
Lateral Support ....................................................................................................................................
Offset Block .........................................................................................................................................
Brick Ledge Installation .......................................................................................................................
Brick Ledge Load Capacity ..................................................................................................................
Flashing & Crown Caps ........................................................................................................................
Height Requirements ...........................................................................................................................
Structural Information ..........................................................................................................................
Common Chimney Terminations .........................................................................................................
Metal Flue ..........................................................................................................................................................
Specialty Applications .......................................................................................................................................
See-Thru Applications ..........................................................................................................................
Two Story Stacked Installations ..........................................................................................................
Fire-Lite Application ..........................................................................................................................................
Fire-Lite Application General Information ..........................................................................................
Fire-Lite Application - Required Clearance to Combustibles ..............................................................
Fire-Lite Application - Load Calculations ...........................................................................................
Fire-Lite Application - Hearth Conditions ...........................................................................................
FTF-13 or Equivalent Chimney System .............................................................................................................
FTF-13 Installation Components ........................................................................................................................
FTF-13 Offset Elevation Chart ...........................................................................................................................
FTF-13 Vertical Elevation Chart ........................................................................................................................
Summary .............................................................................................................................................................
Registration Card .....................................................................................................................................................
3 4 5-6 7 8 9 10 11 12 13 14-17 18 19 20 21 22 23 24 25 26 27 28-39 28 29 30 31 32 33-35 36 37 38 39 40 41 42 43-45 43 44-45 46-51 46 47 48 49 50-51 52 53 54 55-56 57
3
General Information
The Fireplaces referenced in this installation manual
and DM chimney system are prefabricated, refractory
modular replaces and a chimney system designed for eld
assembly. The systems consist of interlocking precast parts which are glued together with a masonry adhesive.
The parts of the Fireplaces and DM chimney system
are precast using a proprietary mixture of volcanic pumice aggregate and cement. It includes all the parts necessary for
assembly of a complete rebox, smoke dome and chimney
system.
Each precast replace component is designed for a specic part of the replace such that only one means for
assembly is possible.
The rebox and smoke dome are designed to be tted with a traditional cast iron, poker-style throat damper,
however alternate dampers are an option.
The replaces require a standard refractory re brick liner be applied to the interior of the rebox. Fire brick
must be a minimum thickness of one and one-eighth inches
(1-1/8”). Isokern Fireplaces are available in nine sizes, seven
of which are covered in this manual: Isokern Standard sizes:
thirty-six (36), forty-two (42), and forty-six (46). Magnum sizes: twenty-eight (28), thirty-six (36), forty-two (42) and forty-eight (48). The Magnum is also available in two larger
sizes; information located online @ www.earthcore.co and detailed in a separate installation manual. All Isokern Standard units have a thirty-one and a
half inch (31-1/2”) rough opening height and the Magnum units have a thirty-eight inch (38”) rough opening height before re brick. The only parts which differ among the
available sizes are width and depth related pieces. The DM chimney system is a dual module refractory chimney system. The basic chimney consists of an outer casing block and an
inner liner. The chimney components are eld assembled using Earthcore (EC) Mortar to glue the components together.
The DM chimney system also includes an offset chimney block component, used to create 30° offsets to the vertical run of the chimney. A brick ledge component is available, designed to support chimney top brick veneer
nishes. Prefabricated masonry chimney termination caps
are also available.
The various replaces and the DM chimney
components will be described and illustrated in the following pages. Close attention should be paid to each component
group’s specications and installation requirements as
described in this manual.
Important: Due to heat and weight issues, the replaces and
DM chimney system installations require that the system be built upon a non-combustible concrete slab with no wood underpinnings supported to footings with concrete or steel and
designed to carry the total weight of the replace and chimney
system.
The Fire-Lite application of the replaces is designed to be built upon a combustible oor system and will also require a design that will support the total weight of the Isokern replace and chimney system. The FTF-13 or equivalent chimney system only must be used with the Fire-Lite application. Please refer to
pages 46-51 for installation instructions.
Recommended minimum overall height for the Isokern replace and DM chimney system for an indoor
application is 18’-0” when the chimney is straight and 21’-0” when a chimney is offset. Maximum overall height is 82’ - 0”,
however, heights above those listed below require additional structural support.
Maximum DM ue height without additional support needed:
Isokern Standard Series:
36 54’-0” 42 40’-0” 46 41’-0”
Magnum Series:
28 50’-0” 36 54’-0” 42 40’-0” 48 41’-0”
For heights above those listed above, consult a
structural engineer for additional structural support for the
DM chimney system. These heights do not reect information regarding metal ue. Any UL 103 or Class A metal ue can be used on an Isokern replace. See metal ue manufacturers
installation instructions for information relating to height
requirements/restrictions. For outdoor applications, there is no minimum height requirement for the DM chimney ue system. Any UL 103 or Class A metal ue can be used on an Isokern replace. See metal ue manufacturers installation instructions for information relating to height requirements/restrictions.
3
Intended Use Statement
Intended Product Use Statement:
The Fireplaces and DM chimney system are intended
to burn solid wood fuel, propane or natural gas.
Note:
Installation of a gas pipe must comply with the Standard for
Decorative Gas Appliances for Installation in Vented Fireplaces, ANSI Z21.60. This replace is not designed to sit directly on a combustible oor system. The Fire-Lite application listed in the
back section of this manual is designed to sit on a combustible
oor. See pages 46-51 for specic installation requirements. This replace is intended for use as a supplemental
heat source only and is not intended for heavy use as a primary heating system.
Overring, abusive burning or mistreatment will void
any claims (eg. burning construction debris or other highly
ammable material; tossing, kicking or otherwise forcing logs into the rebox). Isokern replaces and the DM chimney system are conventional indoor or outdoor replaces designed to appear like traditional masonry replaces. Fireplaces and DM chimney
system units are intended for installation in residential homes and other buildings of conventional construction.
WARNING:
This replace has not been tested for use with doors. To reduce the risk of re or injury, do not install
doors. Operable doors are acceptable and if doors are required by the local authority having jurisdiction, doors
must be kept in the fully open position when the replace
is in operation.
Note: Do not scale drawings. Illustrations in this manual
are not to scale and are intended to show “typical”
installations. Nominal dimensions are given for design and framing reference only, since actual installations may vary
due to job specic design preferences. Always maintain
the stated minimum clearances to combustible materials.
Do not violate any specic installation requirements. The replaces and DM chimney system are tested and listed by Warnock Hersey (Intertek Testing Service) -
Report No. 3159656MID-008 and Report No. 315653MID­006 - to UL 127, and UL 103HT - 2006 respectively.
Fireplace systems are also designed for installation in accordance with the National Fire Protection Association Standard for chimneys, replaces, vents and Solid Fuel-Burning Appliances (NFPA 211).
Note: The local authority having code jurisdiction, should be consulted before installation to determine the need to obtain a permit. Important areas of concern with the installation of these
replaces are: construction of proper load bearing foundation
and concrete support slab; code required hearth extension substrates and supports; proper assembly of components; clearance to combustible materials; height of chimney; and,
techniques employed in applying nishing materials to the replace opening and hearth extension. Suitable standard residential, minimum four inch (4”) thick, 2500 psi concrete foundations on properly compacted ll can support installations up to thirty feet (30’) overall height (brick ledge installations not included)
Each of these important topics will be covered in detail throughout this manual. Installation personnel must give special attention to each topic as the installation progresses.
All work performed on, near and adjoining the replace and chimney installation must meet or exceed the specications
and requirements in this manual and the prevailing local building code. Subsequent renovations, additions of cabinets and
storage spaces in the enclosure surrounding the replace are also limited to the specications in this manual and to the prevailing
local building code. Earthcore is not responsible for other construction
work around the replace unit.
Important: The top plate of the rebox is not meant to be used
as a structural support of any veneer. Please consult structural engineer for structural support of any veneer bearing weight on the Isokern top plate.
5
Safety Instructions
1. Before starting the replace and DM chimney installation,
read these installation instructions carefully to be sure you
understand them completely. Failure to follow them could cause replace malfunction resulting in serious injury or
property damage.
2. Always check local building codes governing replaces and replace installations. The Fireplace and DM chimney
installation must comply with all local, regional, state and national codes and regulations.
3. Fireplaces and DM chimney systems are intended for use in any application where a traditional masonry type replace
would apply. The chimney system must always vent vertically to the outside of the building.
4. Creosote and soot formation and the need for removal: When wood is burned slowly, it produces tar and other organic vapors which combine with expelled moisture to form creosote. The creosote vapors condense in the relatively
cool chimney ue of a slow burning re. As a result, creosote residue accumulates on the ue lining. When ignited this creosote makes an extremely hot re.
Because of creosote and soot buildup it is necessary
to inspect and clean the replace and chimney prior to use
and periodically during the heating season. Cleaning of the
replace and the chimney system should be done annually at
a minimum. In colder climates, chimney cleaning may need to be done more often, periodically throughout the heating season.
5. Before servicing, allow the replace to cool. Always shut off any electricity or gas to the replace while working on it.
10. These replaces are not intended to heat an entire home
or to be used as a primary heat source. They are designed to ensure homeowner comfort by providing supplemental heat to the room.
11. Always ensure that an adequate supply of replacement
air from the outside of the house is accessible to the re to support normal combustion. Fireplaces consume large volumes of air during the normal ring process.
In the event the home is tightly sealed and has
modern energy efcient features, the optional combustion air
supply kits may not provide all the air required to support
combustion and the proper ow of combustion gases up the
chimney. The manufacturer is not responsible for any smoking or related problems that may result from the lack of adequate
air supply owing into the house. It is the responsibility of the builder/contractor to ensure that adequate air supply has been provided for the replace.
12. “Smoke free” operation is not warranted nor is the
manufacturer responsible for inadequate system draft caused by mechanical systems, general construction conditions, inadequate chimney heights, adverse wind conditions or any unusual environmental conditions or factors beyond the manufacturer’s control. It is acceptable to use mechanical draft systems, if the venting companies do the engineering calculations and
make the necessary recommendations for fan size and ue vent diameter following the guidelines of NFPA 211/2006,
pg. 211-13. Installation of such systems must also follow the mechanical drafting company’s explicit installation and operation instructions.
6. Use only solid fuel or natural or LP gas log sets in this
unit. Do not use articial wax based logs, chemical chimney cleaners or ame colorants in this replace.
7. Never use gasoline, kerosene, gasoline-type lantern fuel,
charcoal lighter uid, or similar liquids to start or “freshen up” a re in this replace. Keep all ammable liquids at a safe distance from the replace.
8. Always keep the ue damper open when heat is present in the replace.
9. Do not use a product not specied for use with Isokern replaces and the DM chimney system unless written authorization is given by Earthcore. Failure to heed this warning may cause a re hazard and will void the Earthcore
warranty.
Caution: When used with the replace systems, all gas
log sets must be operated with the damper clamped in the
fully open position. Only listed “vent free” log sets may be
operated with the damper in the closed position.
13. When in doubt about a component’s usability - has visible or suspected physical damage - consult your Isokern distributor or authorized Isokern representative for advice.
6
Safety Instructions - (cont.)
14. Modications to replace components not mentioned in
this manual may void claims, listings and approvals and could result in an unsafe and potentially dangerous installation.
Alterations to the rebox are allowed with prior
written approval and instructions from Earthcore Industries.
The installer indemnies the manufacturer of all claims and
under no circumstances will manufacturer be liable for consequential, incidental, indirect, punitive or other damages of any kind or nature, whether foreseeable or not, based
on any claim by any party as to the modications of the replaces.
15. Keep all insulation, vapor barriers, “house wrap” paper and other insulating type membranes and products,
including berglass, cellulose and other insulation,
(anything that carries an “R” rating) a minimum of three
inches (3”) away from all rebox and chimney surfaces.
See exception. (Figure 34, Page 22)
Exception: If insulation is used in walls surrounding the
replace, insulation may be installed behind sheathing of
gypsom board, plywood, particle board or other material on the side facing the Isokern. The facing material cannot be
within 1 1/2” to the replace sidewalls.
WARNING Do not pack required air spaces with insulation or other materials.
16. Never leave children unattended when there is a re burning in the replace.
17. Burning some fuels (such as charcoal) can be hazardous
due to the possibility of producing carbon monoxide, a colorless, odorless gas. Early signs of carbon monoxide
poisoning resemble u symptoms including headaches,
dizziness or nausea. Over exposure to carbon monoxide can lead to illness and death. It is strongly recommended to
install smoke and carbon monoxide alarm / detector devices wherever replaces are in use.
7
Warnock Hersey Listing Label
CONTACT BUILDING OFFICIAL PRIOR TO INSTALLATION
ONLY UNVENTED GAS LOG SETS WHICH HAVE BEEN FOUND TO COMPLY WITH THE STANDARD FOR UNVENTED ROOM
HEATERS, ANSI/IAS/AGA Z21.11.2, ARE TO BE INSTALLED IN THIS FIREPLACE
SEE INSTALLATION AND OPERATING INSTRUCTIONS FOR THIS MODEL AND ICC # ESR-2316,
LA.RR # 25483, MEA #2490E.
DO NOT USE A FIREPLACE INSERT OR OTHER PRODUCTS NOT SPECIFIED FOR USE WITH THIS PRODUCT. “WARNING” THIS FIREPLACE HAS NOT BEEN TESTED FOR USE WITH GLASS DOORS. TO REDUCE THE RISK OF FIRE OR INJURY, DO NOT INSTALL GLASS DOORS. IF DOORS ARE USED, OPERATE FIREPLACE WITH DOORS FULLY OPEN. WHEN BURNING A DECORATIVE GAS APPLIANCE IN THE FIREPLACE, LOCK THE DAMPER TO THE FULLY OPEN POSITION. ONLY UNVENTED GAS LOG SETS WHICH HAVE BEEN FOUND TO COMPLY WITH THE STANDARD FOR UNVENTED ROOM HEATERS, ANSI/IAS/AGA Z21.11.2, ARE TO BE INSTALLED IN THIS FIREPLACE. DO NOT OPERATE AN UNVENTED GAS LOG SET IN THIS FIREPLACE WITH THE CHIMNEY REMOVED.
USE SOLID WOOD FUEL OR LISTED DECORATIVE GAS VENTED OR UNVENTED APPLIANCE. ALSO FOR USE WITH LISTED METAL CHIMNEY.
FIRE-LITE APPLICATION TO USE FTF13 OR EQUIVALENT CHIMNEY ONLY.
(38 mm) (610 mm) (229 mm) (965 mm) (1219 mm) (838 mm) (305 mm)
(305 mm) N/A (76 mm)
= 0 in. = 1.5 in. = 24 in. = 9 in. = 38 in. = 48 in. = 33 in.
= 33 in. = 12 in. = N/A = 3 in.
(38mm) (203mm) (203mm) (356mm) (660mm) (508mm) (305mm)
(305mm) (102mm) (76mm)
= 0 in. = 1.5 in. = 8 in. = 8 in. = 14 in. = 26 in. = 20 in.
= 20 in. = 12 in. = 4 in. = 3 in.
UNIT FRONT AND ISOKERN CHIMNEY UNIT SIDES AND REAR COMBUSTIBLE SHEATHING ABOVE OPENING TOP SHEATHING OR TRIM TO OPENING SIDES MANTLE ABOVE OPENING OPENING TO SIDEWALL HEA
HEARTH EXTENTION BEYOND FRONT HEARTH EXTENTION BEYOND SIDES COMBUSTIBLE FLOOR INSULATION FROM FIREBOX
28”, 36”, 42”, 48” 60” & 72”
CLEARANCE TO COMBUSTIBLES:
JACKSONVILLE, FL 32256
EARTHCORE INDUSTRIES, LLC.
MADE IN USA
MADE IN DENMARK
COMPLIES WITH APPLICABLE REQ. OF UL 127, ULC S610
MAGNUM: 28” 36” 42” 48” 60” 72”
MODULAR REFRACTORY FIREPLACE
- Facsimile -
FIGURE 1 - ISOKERN STANDARD SERIES
Isokern Fireplace and Chimney Systems are tested and listed to UL standards: UL 127, ULC S610, and UL 103HT. The listing labels shown in Figures 1 and 2 above outline the listed clearances to combustibles and indicates that the units are
suitable for use with solid fuel or listed gas appliances. Refer to the manufacturer’s installation manual for detailed description of clearances to combustibles and all other installation information.
A metal listing label similar to those shown above is afxed to each replace. Do not remove the listing label from the replace.
Prior to beginning installation, contact your local building ofcial to determine the need to obtain a permit.
FIGURE 2 - MAGNUM SERIES
8
Assembled Firebox & Smoke Dome Dimensions
MODEL A B C D E F G I J MINIMUM FRAMING WEIGHT
36 43” 25 1/4” 63 1/4“ 31 1/2” 36 1/8“ 27 1/4” 33” 20 1/4” 5” (46”W)x(65”H)x(26 3/4”D) 1205 lbs
42 49” 25 1/4” 63 1/4“ 31 1/2” 43 1/8” 33 1/4“ 33” 20 1/4” 5” (52”W)x(65”H)x(26 3/4”D) 1325 lbs
46 53” 25 1/4” 63 1/4“ 31 1/2” 47 1/8“ 37 1/4“ 43” 20 1/4” 5” (56”W)x(65”H)x(26 3/4”D) 1450 lbs
TOP PLATE, MEDIUM Part No. Model Qty 77 36 1 77 42 1
TOP PLATE, LARGE Part No. Model Qty 81 46 1
25 1/4”
33”
4 3/4”
10 3/4”
10 3/4”
25 1/4”
4 3/4”
43”
J
C
33”
G
D
A
I
B
E
F
SIDE VIEW
FRONT VIEW
PLAN VIEW
TOP PLAN VIEW
25 1/4”"
14"
10 3/4”
Isokern Standard Series 36, 42 & 46
9
Component List & Dimensions Isokern Standard Series 36, 42 & 46
Part No.:
22 23
Fireplace Model:
42 46
Qty:
1 1
21 36 1
A
49” 53”
43”
BASE PLATE
Part No.:
11
Fireplace Model:
42
Qty:
2
11 36 2
SMOKE DOME - MEDIUM
Part No.:
Fireplace Model: Qty:
13 46 2
SMOKE DOME - LARGE
Part No.:
34
Fireplace Model:
42
Qty:
2
34 36 2
TOP-SLOPING
Part No.:
20 20
Fireplace Model:
42 46
Qty:
6 6
20 36 6
SIDE WALL
25 1/4”
10 1/2”
Part No.:
28 31
Fireplace Model:
42 46
Qty:
3 3
25 36 3
BACK WALL
10 1/2”
5”
Part No.:
95L 95L
Fireplace Model:
42 46
Qty:
1 1
95L 36 1
DAMPER SUPPORT - LEFT
Part No.:
95R 95R
Fireplace Model:
42 46
Qty:
1 1
95R 36 1
DAMPER SUPPORT - RIGHT
Part No.:
69 70
Fireplace Model:
42 46
Qty:
2 2
68 36 2
DAMPER BEAM
A
49” 53”
43”
A
8”
25 1/4”
16”
3”
53”
16”
4”
16”
43”
4”
3”
A
25 1/4”
A:
32 1/4” 37”
26 3/4”
A
10
TOP PLATE, LARGE
56"W x 71"H x 29 1/2"D
FIREPLACE
48
MINIMUM FRAMING:
46"W x 71"H x 29 1/2"D
52"W x 71"H x 29 1/2"D
TOP PLATE, MEDIUM
77 77
PART NO.:
1 36
42 1
FIREPLACE Model:
QTY:
81
PART NO.: Model:
"C"
33”
43"
33”
48
36
42
MODEL
28”
53"
43"
49"
"A"
28"
28”
"B"
SIDE VIEW
48 1/2"
38 3/8"
44 1/2"
38”
38”
38”
"D"
"E"
FRONT VIEW
1
QTY:
PLAN SECTION A-A
TOP PLAN VIEW
E
B
F
28"
“F”
G
A
D
14"
4 3/4"
25 1/4"
32 3/4"
43"
25 1/4"
27 1/4"
AA
33 1/4”"
C
5"
2 3/4"
“G”
69 3/4"
69 3/4"
37 1/4"
69 3/4"
28 *
35 1/2"
28" 22 1/4"
31"
19 3/4"
39"W x 61 1/2”H x 29 1/2"D
60 1/4"
28 1/2”
WEIGHT
1040 lbs
1300 lbs
1420 lbs
1600 lbs
4 3/4"
* Model 28 comes with three (3) sidewalls and some components must be “field cut”.
3"
TOP PLATE, SMALL
36
PART NO.:
1 28
FIREPLACE Model:
QTY:
10 3/4"
4 3/4"
25 1/4"
22 1/2"
10 3/4”
10 3/4"
10 3/4"
Assembled Firebox & Smoke Dome Dimensions
Magnum Series 28, 36, 42 & 48
Firebox & Smoke Dome Components List
11
Component List & Dimensions Magnum Series 28, 36, 42 & 48
A
53”
A
A
2”
28”
9 ½”
9 ½”
28”
3”
16”
16”
4”
4”
8”
8”
5”
2 3/4”
25 ¼”
*16”
Front of
Smokedome
(above)
Part No.:
91 92 93
Fireplace Model:
36 42 48
Qty:
1 1 1
Part No.:
90 90 90
Fireplace Model:
36 42 48
Qty:
8 8 8
Part No.:
65 66 67
Fireplace Model:
36 42 48
Qty:
4 4 4
Part No.:
94L 94L 94L
Fireplace Model:
36 42 48
Qty:
1 1 1
TOP - SLOPING
BASE PLATE
SIDE WALL
DAMPER SUPPORT (LEFT)
DAMPER SUPPORT (RIGHT)
BACK WALLS
Part No.:
34 34 34
Fireplace Model:
36 42 46
Qty:
2 2 2
91 28 1
Size A:
Cut to 35 1/2”
43” 49” 53”
Part No.:
11 11 13
Fireplace Model:
36 42 48
Qty:
2 2 2
SMOKE DOME
12 28 2
Size A:
32 1/2”
43” 43” 53”
* True Height When Installed
34 28 2
90 28 6
9 ½”
G
5”
12”
* Model 28 Only
Field Cut Back Walls
65 28 3
G:
Cut to 20”
* Cut as shown in the field; mortar pieces together and stagger joints when stacking for installation.
26 3/4” 32 1/4” 37”
9 ½”
G
5”
94L 28 1
Part No.:
94R 94R 94R
Fireplace Model:
36 42 48
Qty:
1 1 1
94R 28 1
Part No.:
68 69 70
Fireplace Model:
36 42 48
Qty:
2 2 2
DAMPER BEAMS
68 28 2
A:
Cut to 35 1/2”
43” 49” 53”
REAR
FRONT
12
0” CLEARANCE
20”
MIN.
1 1/2”
No Combustible Underpinnings
1 1/2”
Required Clearance to Combustibles
The replaces and DM chimney systems are tested and listed for installation with “clearance to combustibles” as
follows:
The Isokern Standard and Magnum Series rebox side walls and back wall require 1-1/2” clearance. (Figures 3 & 4) The smoke dome front wall requires 0” clearance. All DM chimney components require 0” clearance to combustibles. (Figure 3) Note: “Combustibles” are dened as “normal construction materials” and are considered to be: wood framing materials, particle board, mill board, plywood sub-ooring, plywood paneling and wood ooring.
Sheathing materials, such as plywood, particle board
and drywall may cover the smoke dome front at 0” clearance.
All combustible sheathing materials that protrude beyond
front of rebox must be held 8” away from the sides of the rebox opening and 8” above the top of the rebox opening.
Wherever insulation is used, the Fireplaces must
not be placed directly against it. Keep all insulation, vapor barriers, “house wrap” paper and other insulating type
membranes and products, including berglass, cellulose
and other insulation, (anything that carries an “R” rating)
a minimum of three inches (3”) away from all rebox and
chimney surfaces.
FIGURE 3
Exception: If insulation is used in walls surrounding the replace,
insulation may be installed behind sheathing of gypsom board, plywood, particle board or other material on the side facing
the Isokern. The facing material cannot be within 1 1/2” to the replace sidewalls.
Notes:
A. The replaces must sit upon a concrete support slab designed to bear the total installed weight of the replace
and DM chimney system. These support slabs can have no
wood underpinnings. (Figure 4) The replaces are rated for installation on a combustible oor system when using the Fire-Lite application only. See pages 46-51 for Fire-Lite installation instructions. B. Concrete support slabs for replaces must provide
the noncombustible hearth extension substrate needed to support the code required noncombustible hearth extension
nish materials. (Figure 4) C. All replaces shall have hearth extensions of
approved noncombustible material such as brick, tile, or stone that is properly supported, with no combustible material against the underside thereof. Wooden forms used during the construction of hearths and hearth extensions must be removed when the construction is complete.
D. If a raised replace oor and raised hearth
extension are preferred, the raised underlying structure must be built of noncombustible material and must sit on noncombustible substrate.
FIGURE 4
13
B
D
FRAMED OPENING
FRAMED OP'G.
C
MINIMUM
A
Rough Framing Dimensions
Rough Framing Dimensions
Model Width Height Depth A B C Magnum
Model 28 38 1/2” 61 1/2” 29.5” Model 36 46” 71” 29.5” Model 42 52” 71” 29.5” Model 48 56” 71” 29.5”
Isokern Standard
Model 36 46” 65” 26 3/4” Model 42 52” 65” 26 3/4” Model 46 56” 65” 26 3/4”
Notes:
1. “B” includes the 3” thick base plate. “B” is reduced by 3” if the base plate is eliminated to create a “ush hearth”.
2. “Raised hearth” requires additional rough opening height at “B”
equal to the height of the raised hearth detail.
3. Rough framing dimension for width “A” allows for the required 1-1/2” clearance at the sides of the Fireplaces.
FIGURE 5
4. Rough framing dimension for depth “C” allows for the required 1-1/2” clearance at the back of the Fireplaces.
Corner Location Layout
The following chart of dimensions is intended to aid in the positioning
of a replace in a corner condition where the DM chimney must turn 45°
degrees to align with overhead framing.
Magnum A B C D
Model 28 33 1/2” 18 1/4” 24” 65 1/2” Model 36 43” 16 3/4” 32” 78 3/4” Model 42 49” 26 1/2” 36” 83” Model 48 53” 28 1/2” 39” 85 3/4”
C
A
Isokern Standard
Model 36 43” 49” 35” 72” Model 42 49” 52” 37” 75” Model 46 53” 54” 39” 79”
To turn ue 45°, rst set one offset block on the rebox so that the chimney offsets 3” toward the back of the rebox. (Figure 6)
Set a DM outer casing onto this offset block so that the outer
casing is at 45° to the rebox and square to the overhead framing system.
Run the vertical DM chimney through the overhead framing. More offset blocks can be used - if necessary to align with overhead framing - before running the vertical DM chimney outer casing and liner.
FIGURE 6
Note: Support the third offset down to footings and at each third offset
block thereafter (see pages 33 & 34).
14
ECI MORTAR
SHIM IF REQUIRED TO ACHIEVE CORRECT HEIGHT
FIGURE 7
Assembly Instructions
General Isokern Assembly Instructions:
Earthcore Mortar (a thin-set type masonry adhesive) is used to glue all Isokern components together during eld
assembly of the unit. The mortar is supplied dry, in 50 pound pails. Earthcore mortar is mixed with clean water to a
smooth, workable texture (without lumps or dry pockets) of a “toothpaste” consistency. This mixture is suitable for
application onto Isokern components by using a masonry grout bag supplied with the unit. Attention should be paid that the mortar mixture is not too thin or runny, as this will not allow the mortar to reach its maximum bonding strength. Earthcore mortar is squeezed from a grout bag onto
the contact surfaces of the Isokern components as they are tted
together.
It is important that a 1/2” bead of mortar on all the components’ contact surfaces is applied at about 1/2” in from all edges of the contact surface of the component. (Figure 8)
When setting the next component onto the mortared
contact surface of the rst component, some mortar should
squeeze out along the face of the entire joint as a sign of complete and proper sealing of the joint. On broader contact surfaces it is advisable to apply
several additional 1/2” beads of the Earthcore Mortar to the area
to assure proper sealing of the joint.
Properly mortared rebox and smoke dome assembly requires approximately 30 pounds (dry measure) of Earthcore
mortar.
FIGURE 8
FIGURE 9
Broken Components: Components broken into 2 or 3 pieces can be repaired
by using Earthcore mortar along the break line as the component is set into place. Components broken into multiple small pieces should be discarded and replaced.
Leveling and Aligning Components: Be sure to assemble all Isokern components level and
ush with adjoining components.
Earthcore mortar is not intended to create a mortar joint of any thickness for leveling purposes. Therefore, leveling and alignment adjustments are made by the use of small plastic
shims supplied with the unit. (Figure 9)
The shims can be inserted under a component to level and align it with adjacent Isokern components. Be sure to re­grout any and all gaps resulting from shim insertion to maintain components to full bearing.
Notes:
1. Do not mix Earthcore mortar with spirits or anti-freeze agents.
2. The maximum recommended mortar joint thickness at
Isokern components is 1/4”.
15
FIRST COURSE SIDEWALL
BASE PLATE
EC MORTAR
EC MORTAR
Assembly Instructions - (cont.)
3. Earthcore mortar can be troweled over the face of a joint where it has squeezed out while setting components. It is not intended that the exposed faces of the Isokern components be completely covered with mortar.
Installation:
Step 1: Set the base plate in a full bed of Earthcore Mortar at
on a proper concrete support foundation. (Figure 10). Do not
set the base plate so that it is in span. Level the base plate by
oating it in a bed of Earthcore Mortar to full bearing against
the underlying noncombustible support surface.
Notes: If the design preference is for a “ush hearth” (replace oor ush with the room’s oor), the base plate can be omitted from the assembly and the rebox walls built directly on the concrete support slab. The re brick oor of the rebox is then set directly to the concrete support slab. This makes the replace nished re brick oor approximately one and one-half inches (1-1/2”) above the top of the concrete support slab. (Figure 11) If the design preference is for a raised hearth (oor of the replace elevated above the room’s oor), then the base
plate can be set on a noncombustible platform that is built up to the desired raised hearth height on the concrete support
slab. (Figure 12)
When calculating raised hearth height be sure to
allow for the three inch (3”) thick base plate plus the one and one half inch (1-1/2”) thick re brick oor in addition to the
height of the platform.
Whether a ush hearth is preferred or a raised hearth, the combustible oor on front of the replace must be covered
with a noncombustible hearth extension set tight against the
replace front and extending at least 20 inches out from the nished replace and at least 12 inches beyond the nished sides of the replace opening. For all “raised hearth” construction where concrete
blocks are used to create the raised platform, it is necessary to use the base plate. Be sure to mortar the concrete block platform together. CMU used for base plate support should be rated ASTM 90.
Step 2: Set the rst course of the rebox back wall and side
walls into place.
It may be convenient to dry set the rst course of
side wall and back wall into place on the Isokern base plate and then to trace their position on the base plate with a pencil. After outlining the dry set pieces, remove them and apply Earthcore Mortar to the areas traced on the base plate where the side walls and back wall are to sit. By doing this,
the rst layer of Wall components can be set directly into
mortar already applied to the proper areas on the base plate. Be sure to put Earthcore Mortar on the contact surfaces of the vertical joints where the side wall and back wall components
connect. (Figure 13)
FIGURE 10
FIGURE 11
FIGURE 12
FIGURE 13
16
TWO COURSES BACKWALL
EC MORTAR
FIRST DAMPER SUPPORT IN PLACE
CAST IRON DAMPER
FRONT DAMPER SUPPORT
FIGURE 14
Assembly Instructions - (cont.)
Note: At all component placement, be sure to mortar all component contact surfaces with Earthcore Mortar. Check for complete sealing of each contact joint while assembly progresses.
Step 3: Continue assembly of the consecutive courses of the
rebox side wall and back wall. (Three courses for the Isokern Standard Series, Four courses for the Magnum Series). Apply
mortar to the top of each layer of wall components, set the next course above into place. Be sure to mortar all vertical joints of the side wall to back wall connection when setting each component
to its mate. (Figure 14)
Look for some mortar to squeeze out along the joints of all contact surfaces as a sign that the joint is thoroughly sealed with the approved mortar.
Step 4: When all of the rebox wall components are set, check the top surface of the rebox for level. If necessary, adjust the top
surface of the box assembly for level by inserting a shim between the lowest wall component and the top surface of the base plate.
(Figure 9)
Any gap created under the wall components during the
Shim leveling process must be lled with mortar to full bearing
against the base plate.
FIGURE 15
FIGURE 16
Step 5: Make sure that the rebox assembly has been set level
and square. Adjust as required while the mortar is still wet.
Make a nal inspection of all contact joints in the rebox assembly to be sure they are properly sealed. Fill any and
all gaps in the assembly, as necessary, with the approved mortar.
Step 6: The replaces come with an eight inch (8”) thick damper
beam assembly, a four piece component group that is to be
assembled on top of the rebox sidewalls.
The damper beam assembly consists of two long lintel pieces and two short damper beam side pieces.
The damper side pieces are designed to sit on the rebox
side wall between the front lintel and the back lintel. Each of the
damper side pieces is designed specically for its own side of the unit. When properly set, each damper side piece ts ush with the outside face of the rebox sidewall so that its interior bottom edge aligns with the interior angle of the rebox side wall that it sits on. (Figure 15)
The two long lintels are identical in shape, size and in
length, equal to the width of the replace model that they serve. Properly placed, one lintel is to sit on top of the rebox back wall and ush with it; the other lintel sits ush with the front of the rebox, spanning the rebox opening. These components both sit
on their narrow base so that their beveled face points down and
into the rebox interior. (Figure 16)
Be sure to mortar all damper beam components to the
top surfaces of the rebox.
Mortar the contact surfaces of each damper side component where it meets the front and back damper beam lintel components.
17
DAMPER
1"
FRONT
REAR
REAR
FRONT
Damper Beam
END
END
17”
10 3/4”
NOTE: Magnum Series Shown for Illustration only. Isokern Standard Series Front Smoke Dome Will Sit Flush With Front of Damper Beam
Assembly Instructions - (cont.)
Step 7: With the damper beams assembled and mortared together, set the cast iron throat damper (unless another
damper type is being used) on top of the damper beam and
over the smoke chamber opening. The cast iron damper’s
operating plate should face toward the rear of the replace. (Figure 17) The ange at all four sides of the cast iron damper
should be supported by the damper beam’s top surface.
Before adjusting the cast iron damper to its nal
position proceed to Step 8.
Note: A Damper is not required for exterior installations.
Step 8: Position the cast iron damper so that its front ange
is approximately one inch (1”) away from the inside face of the front smoke dome component. (Figure 17)
Run a thin bead of mortar around the four sides of
the cast iron damper or tack the corners of the ange to avoid
movement of the damper as it gets opened and closed. Set the rear smoke dome component across the damper beam
in a bed of mortar and ush with the back face of the back damper beam lintel. (Figure 18)
Set the Isokern Standard front smoke dome
component in mortar across the front damper beam and ush
with it. Set the Magnum front smoke dome component in
mortar accross the front damper beam and 2 -1/4 inches
back from the front of the front damper beam lintel. This
placement should create a space of 17 inches (17”) between
the front and rear smoke dome components.
Step 9: Position the smoke dome’s sloping sidewalls at each
end of the smoke dome components. (Figure 18) The sloping sidewalls t in between the front and rear smoke dome components and also t into the haunches
at the ends of the front and rear smoke dome components. Mortar all contact surfaces thoroughly. The smoke dome sloping sidewalls have a beveled bottom edge so that they
will sit tight onto the at top of the damper beam assembly.
Make sure that the top plate is set so that the ue
hole is closer to the back wall of the smoke dome assembly.
Be sure to set the smoke dome top plate ush with
the front, back and sides of the smoke dome assembly. All contact surfaces must be properly sealed with the approved mortar.
Note: The completed smoke dome assembly should present
a stable and level surface for setting the ue components. (Figure 19)
FIGURE 17
FIGURE 18
Step 10: Make sure that all component contact surfaces have been properly sealed with approved mortar. Check smoke dome front and rear walls to see that they are plumb, level and in alignment with mating components. Check alignment of the smoke dome sloping sidewall components to see that they are fully seated.
Step 11: Set the top plate into position on top of the smoke
dome wall assembly. (Figure 19)
One side of the top plate shows a thickened center. This side is the bottom face.
The ue hole in the top plate is centered in the
smoke dome from side to side but is offset from front to back,
the center being 10 3/4” from the back of the rebox.
FIGURE 19
18
Flex Duct To Fireplace, (All Parts Noncombustible)
Exterior Wall
Exterior Air Vent With Dress Plate
Typical Placement of Gas or Electric Conduit (See Detail Below)
Supply Air Ventilation (If Required By Code)
CAUTION: All access holes must be grouted with mortar - after line or conduit feed to seal any gaps or cracks around line feed conduits
Fire Brick Side
Gas or Electric Conduit
NOTE: Fill Any Gaps Around Conduit With Mortar
FIGURE 20
Access Modication
Through-Wall Accesses:
1. Combustion Air Inlet: Combustion air inlet kits though
not required by Earthcore may help improve replace
operation in homes tightly sealed and with other ventilating
appliances installed (Figures 20 & 21). Check local codes for combustion air inlet requirements.
The following is a general representation of a generic combustion air kit and not a requirement of Earthcore Industries. Local building codes prevail and should be checked before installation.
Generic replace combustion air kits typically consist of a sliding stainless steel access door afxed to a three inch (3”) or four inch (4”) diameter stainless steel sleeve approximately twelve inches (12”) long. An exterior vent
with dress plate, weather hood and rodent prevention screen
of a maximum one-quarter inch (1/4”) wire mesh completes the kit. (Figure 20) The access door is tted into the nished re brick lining at the interior sidewall of the rebox. The twelve inch (12”) long sleeve can be introduced into the rebox side wall
by core drilling an appropriately sized hole at the selected
rebox location. Keep the top of the access hole no more than six inches (6”) above the nished rebrick oor. The hole size should allow for a one-quarter inch (1/4”) mortar joint
around the air access sleeve for heat expansion.
The sleeve passes through the rebox side wall and must be connected to metal pipe (by others) - either exible
or rigid - that leads to the source for outside combustion air,
as directly as possible from the replaces (Few to no bends) with a maximum length of sixty feet (60’).
FIGURE 21
FIGURE 22
WARNING: Do not use combustible duct material. Avoid installing a combustion air inlet where the opening could be blocked by snow, bushes or other obstacles. Air inlet must terminate a minimum of three feet below the chimney cap level. Air inlet ducts shall not terminate in attic spaces.
2. Gas Line Feed: For a replace having the provision for
installation of a gas pipe, the provision is intended only for connection to a decorative gas appliance.
CAUTION: When using the decorative appliance, the
replace damper must be set in the fully open position. Gas line for gas log sets used in the Isokern rebox can be routed through the side wall of the rebox by drilling an appropriately sized hole using a masonry drill bit (Figure 21).
3. Electrical Line Feed can be routed through the rebox
side walls by drilling an appropriately sized hole using a
masonry drill bit (Figure 21). Be sure to follow the gas log
Appliance Manufacturer’s explicit electrical line connection
instructions for vented masonry replace installations. Gas
line and electric line must be fed through separate access
holes. Be sure to ll any gaps around conduit with EC mortar. (Figure 22)
19
Fire Brick Installation
Fire Brick Installation:
The manufacturer requires that the replace reboxes be lined with a minimum one and one-eighth (1-1/8”) thick re brick. Thicker re brick may be used as an option. The pattern for the re brick lining is an owner option. Standard N or S type brick mortar is suitable mortar for the replace. Fire brick mortar needs to be suitable to both adhere the re brick to the inside of the rebox and to create the nished face joints of the brick work. Based on a history of eld applications and experience, a suitable mortar would be
as follows:
Mix:
* 1 bucket masonry mortar (S or N type)
* 5 lbs Earthcore mortar
* Six parts sand (1 1/2 bucket) * One part Fire Clay (optional)
* Water to a sticky, toothpaste consistancy
These instructions may vary because of different climates and conditions. The use of good masonry practices for your area should also be considered. It takes about 25 lbs.
of mortar mix (dry measure) to re brick line a replace.
Installation Instructions:
1. Wet mop the inside of the replace with a damp sponge to remove dust and loose particles from the interior
before re-bricking.
Expansion 1/2” Gap
FIGURE 23
Expansion 1/2” Gap
HINT: Dip each rebrick into water before applying.
2. Face joint dimensions of 1/4” to 3/8” in the brick work is recommended and has the best appearance. Other face joint dimensions are acceptable however smaller joints may
not leave room for heat expansion of re brick.
3. Start the re brick at the front edge of the oor of the Isokern rebox, proceeding inward toward the back. Let the oor brick gap approximately 1/2” off the back wall and side walls. This air space allows heat expansion of the re brick and is to be left empty of mortar. (Figure 23)
4. Next, apply re brick to the back wall of the unit. The back wall re brick covers the 1/2” expansion gap left at the brick oor along the back wall of the rebox. (Figure 25)
5. Set the side wall re brick by starting at the front edge of
the unit’s side wall and working inward toward the back wall
re brick. The side wall re brick, when completed, covers the 1/2” expansion gaps where both the oor re brick and the back wall re brick were held off the units side walls. (Figure
24)
All required through-wall accesses (gas and electrical
line feeds and combustion air supply access holes) should be drilled before the required re brick lining is installed.
Earthcore makes no claims as to the performance
of re brick or re brick mortar(s). It is typical for heat stress cracks to appear in the re brick in replaces.
Fire Brick Floor (Built First)
FIGURE 24
No Gaps
Fire Brick Floor and Back Wall (Built First)
FIGURE 25
20
Magnum Series
Flush Wall Finish Detail
Framing Protrudes Past Firebox Front
FIGURE 26
8” Minimum Noncombustible Facing Material To Span Framing Members
Isokern Standard Series
FIGURE 27
Fireplaces are designed to be installed so that the rough front face of the rebox and damper beam project into the room approximately one-half inch (1/2”) beyond the face of the rough framing members that create the room’s wall surface. The Magnum smoke dome front sits two and three-fourths inches (2-3/4”) back from the rough face of the rebox and damper beam. This set back dimension allows for one and one-half inch (1-1/2”) framing plus one-half inch (1/2”) thick wall board to pass in front of the smoke dome and at the same time align ush with the room face of the Magnum damper beam. Set in this position, framing and wall board are kept to the required eight inches (8”) above the rebox opening top (Figure 26).
Drywall Flush with Firebox Front
FIGURE 28
The Isokern Standard smoke dome front sits ush with the rough face of the rebox and damper beam. Eight inches (8”) of noncombustible facing material must span framing members for drywall to keep the required eight inches (8”) above the rebox opening top; It is after this noncombustible material that framing members can be placed as shown above. Eight inches (8”) on each side of the rebox opening is also required to be covered in noncombustible material. (Figure 27)
Important: Do not build a frame wall in front of the Magnum or Isokern Standard rebox and damper beam. (Figure 28)
21
Required Clearances (when sheathing protrudes beyond front of rebox)
FIGURE 29
Plywood Sheathing
Noncombustible Facing
1 1/2” MIN TO COMBUSTIBLE FRAMING
8”
MIN
8”
MIN
FINISHED OPENING
WOOD (COMBUSTIBLE) SHEATHING
8”
MIN
FIRE BRICK
8”
MIN
8”
MIN
FIGURE 30
Combustible sheathing such as plywood and particle board may be used to cover the front face of the smoke dome and be
in direct contact with it. If sheathing protrudes in front of the rebox, application of such combustible sheathing must assure that the sheathing is held a minimum of eight inches (8”) away from each side of the nished rebox opening and a minimum of eight inches (8”) above the top of the nished rebox opening. (Figure 29 & 30)
Do not build a combustible framed wall out in front of the rebox.
If sheathing and framing are to be installed across the front face of the rebox smoke dome, then the framing and sheathing must be held a minimum of eight inches (8”) above the top of the rebox opening. This means that framing and sheathing across the
smoke dome front must be kept at or above the damper beam.
22
1 1
/2"
MI
N.
1 1/2”
MIN
8”
MIN
1 1/2”
MIN
8”
MIN
Hearth Extension
20” min
12” min
12” min
Insulation Behind sheathing with 1 1/2” Clearance When Supported
3” min When Unsupported
1 1/2”
min
1 1/2”
NOT PERMITTED
1 1/2”
MIN
Do Not Place Sheathing WIthin the 1 1/2” Required Clearance to Combustibles
COMBUSTIBLE FRAMING
1 1/2”
MIN
1 1/2”
MIN
1 1/2”
MIN
FACE OF COMBUTIBLE FRAMING
1 1/2”
MIN
1 1/2”
MIN
FACE OF COMBUTIBLE FRAMING
8”
MIN
8”
MIN
FIGURE 31
FIGURE 32
Required Clearance to Combustible Framing
Fireplaces are tested and listed for one and one-half inch (1-1/2”) clearance to combustible framing material at the rebox sides and back.
Installation and use practices that are beyond the control of the manufacturer* can result in situations where clearance requirements (as determined through testing and
as stated by the manufacturer) are not maintained due to
construction subsequent to the installation of the Isokern unit. It is the general contractor’s responsibility to assure that listed clearances to combustible framing and to insulation are maintained throughout the construction of the project subsequent to the installation of the Isokern unit.
To avoid causing a re resulting in damage to property, personal injury or loss of life, do not pack or ll the required air
spaces with insulation or other material. No material is allowed
in these areas. (Figures 31 & 32)
*The manufacturer is not responsible for installation and use
practices that are beyond the scope of the product as dened in
the product listing and in the installation manual.
The rebox backwall, side walls and the smoke dome back require 1 1/2” clearance to combustibles. (Figure 33)
Keep all insulation, vapor barriers, “house wrap” paper and other insulating type membranes and products,
including berglass, cellulose and other insulation,
(anything that carries an “R” rating) a minimum of three
inches (3”) away from all rebox and chimney surfaces. See
exception. (Figure 34)
FIGURE 33
FIGURE 34
Exception: If insulation is used in walls surrounding the replace,
insulation may be installed behind sheathing of gypsom board, plywood, particle board or other material on the side facing
the Isokern. The facing material cannot be within 1 1/2” to the replace sidewalls.
When Fireplace installations are surrounded by walls
that are to be insulated, the walls must have enough clearance
to the Isokern unit in order to maintain the three inch (3”)
minimum clearance to insulation for unsupported insulation.
(Figure 34)
Never spray the Fireplaces with any type of sealer, insulation or other material.
23
Flush Wall Fire Brick Finish Detail
Drywall Flush With Firebox Front
Noncombustible Facing Material
1 1/2”
1 1/2”
8”
Min
FILL ANY GAPS WITH EC MORTAR TO AVOID FA LSE CHIMNEYS
Recommended Fire Brick Detail: When drywall is the wall nish at the rebox face and ush with the rough face of the rebox and damper beam, it is recommended when installing the required re brick lining to the interior of the rebox, that the leading edge of the re brick - at the oor and at the side walls of the rebox - be set ush with the rough rebox front. This will aid in the overall t and nish of the replaces front when the code required noncombustible nished facings are applied.
This alignment of re brick application as shown, (Figure 35), allows the re brick lining to be in the same plane with the room’s wall nish surface. With the re brick set in this fashion the noncombustible nish facing material can be set tight against the leading edge (or, “room edge”) of the re brick at the sides of the replace opening. At the same time the nished facing material can lay at against the room’s nished wall surface.
Important: Since there is no re brick set along the top of the rebox opening, when setting the noncombustible nished facing material (code required and supplied by others) across the top of the rebox opening there may be a gap between the back of the noncombustible nish material and the rough front face of the replace damper beam. Be sure to check for and ll any such gap with
noncombustible Earthcore Mortar in conjunction with
placement of the code required noncombustible nish facing material set across the top of the rebox opening. (Figure 36)
FIGURE 35
WARNING: Avoid false chimneys.
Important: Failure to seal any gaps between the front face
of the damper beam and the back of the noncombustible
nished facing material will create what is known as a “false chimney”. A “false chimney”, in this case, is the narrow gap (mentioned above) between the back of the noncombustible facing material at the top of the rebox opening and the rough front of the replace damper beam. If left unlled this gap creates a “false chimney” which can draw smoke, heat and re out of the rebox into the space behind the noncombustible nish facing and on up into overhead framed spaces causing a re hazard. It is acceptable to apply noncombustible nish facing to the front and below the rebox opening to create
an arched look, etc. When doing so, make sure to check
for and ll any such gap with noncombustible Earthcore
Mortar in conjunction with placement of the code required
noncombustible nish facing material.
NOTE: You must still keep a minimum 8” from the rebox
opening to any combustible materials.
FIGURE 36
24
4"
6"
BEARING
4 x 6 STEEL “L”
ISOKERN UNIT WIDTH DIM'N.
EXTENT OF STEEL “L”
MASONRY VENEER
MASONRY VENEER
ALIGN
ALIGN
3 1/2"
COMBUSTIBLE SHEATHING
END OF ISOKERN FIREBOX UNIT and STEEL “L” ALIGN
2"
MIN
4 x 6 STEEL “L” ANGLE
2"
MIN
2"
MIN
Interior Masonry Veneer Fireplace Finishes & Clearances
FIGURE 37
Stucco Finish Application:
Any nish can be applied to an Isokern replace however with each nish there are different application techniques which can help with the longevity of your nish. When applying a stucco nish to the Isokern material, it is recommended that a scratch coat is applied rst to provide a strong base for the system. It is embedded in a wire lathe (not felt backed) which is screwed with care to the replace unit. Use 1 1/4” Tapcon screws to attach the lathe to the rebox using the minimum amount needed to secure the wire lathe. A brown coat is applied next to create an even surface for the nish coat. The nish coat is applied last, creating the decorative nish on the wall surface.
25
COMBUSTIBLE SHEATHING
MIN. CLEARANCE
2"6"
4" 2"
BEARING
FIGURE 38
Masonry Veneer Construction Details
Brick, stone or other masonry veneer nished fronts to replaces are possible. Special attention is required with regards
to:
(1) the placement of the proposed masonry veneer facing and its interface with the re brick lining, and (2) the masonry veneer and clearance to combustible framing and sheathing from any steel “L” support used in the masonry veneer around the front of the replace unit behind the
veneer facing. Any proposed brick, stone or other masonry veneer
facing must have sufcient foundation to support the full weight
of the veneer work. This may require review by a local structural engineer prior to construction.
MIN. CLEARANCE
BRICK VENEER
The veneer facing, when installed, must present a tight
seal with the leading edge - the room edge - of the re brick lining at the sides of the rebox opening. (Figure 39) A steel “L” will need to span the top of the nished replace opening to carry the masonry veneer as it spans over the rebox opening. (Figure 37) By code requirement this steel “L” must have a minimum four inch (4”) end bearing. This bearing surface area shall be provided in the veneer work. (Figure 39) It is important that the steel “L” is set tight against the damper beam front and set in a mud joint to avoid creating a “false chimney” between the back of the steel “L” and the damper beam front. (Figure 39)
Steel “L” or “angle” used to support masonry veneer as it spans the rebox opening must, in all cases, have a two inch (2”) minimum clearance to all combustible materials. The vertical leg of the steel “L” cannot exceed six inches (6”) in
height.
Note: Properly placed combustible sheathing is kept a
minimum of eight inches (8”) away from the rebox opening
sides and top.
Important: Combustible framing members, normally set at
one and one-half inch (1-1/2”) clearance to the sides of the rebox must be moved to at least two inch (2”) clearance to the rebox sidewalls to maintain minimum two inch (2”) clearance to the steel “L” to avoid a potential re hazard. Moving framing members two inches (2”) away from the rebox side walls will maintain the minimum required two inch (2”) clearance from the steel “L” and, at the same time allow full four inch (4”) end bearing required for the steel “L”. (Figure 38)
AIR SPACE
COMBUSTIBLE SHEATHING
MASONRY VENEER
2"6"
4x6 STEEL “L”
MASONRY BEYOND
MORTAR JOINT
FIGURE 39
26
Non-combustible Finished Facing Requirements &
Clearance to Combustible Trim
Hearth Extensions:
All Fireplaces shall have hearth extensions of brick,
concrete, stone, tile or other code approved noncombustible
material. Suitable hearth extension material for the replaces
shall be placed on the hearth extension’s noncombustible
substrate and must extend to at least twenty inches (20”) in front of the replace’s nished opening and must extend to at least twelve inches (12”) beyond the sides of the nished replace opening. (Figure 41)
WARNING: The noncombustible hearth extension, by code, must sit on noncombustible substrate which shall have no wood underpinnings.
This means that off-grade wood oor systems shall be constructed in such a way that all wood oor joists and subooring shall stop twenty inches (20”) out from the front of the rebox. (Figure 40)
Mantle and Mantle Shelf Clearances: Fireplaces are subject
to the same building code safety clearances to combustible
trim as with any radiant heat replace.
All combustible trim shall be kept at least eight inches
(8”) from the nished replace opening.
Combustible trim located along the sides of the
replace opening, which project more than one and one­half inches (1-1/2”) from the face of the replace, shall have additional clearance from the eight inches (8”) equal to the
projection. Combustible projecting mantles - up to twelve inches
(12”) of projection - shall not be placed less than fouteen inches (14”) from the top of the replace opening. Combustible mantles which project more than twelve inches (12”) from the face of the replace, shall have additional clearance from the fourteen inches (14”) equal to the projection.
COMBUSTIBLE MANTLE SHELF
20” HEARTH EXTENSION
FIGURE 40
12"
14”
8”
COMBUSTIBLE FLOOR SYSTEM
ADJOINING ROOM WALL
Note: The local authority having jurisdiction may require greater clearances for projecting combustible mantle shelves. Be sure to check local building codes regarding required clearances to projecting combustible mantles.
Adjoining Walls. Side walls and walls to rooms adjoining
replace installations cannot be closer than twenty-six inches (26”) to the nished replace opening. (Figure 41)
Note: “Clearance to Combustible Trim” are those distances required to ensure that a replace mantle or facing will not catch re. In most cases the distances should also be adequate
to prevent any discoloration or warping due to heat. However each installation presents a unique and completely different set of circumstances involving many variables.
These include paint or nish composition, previous exposure to heat, methods and quality of construction, air ow
patterns, etc. Because of these variables, the manufacturer does not guarantee that heat warping or discoloration will never occur.
FIGURE 41
27
26"
HEARTH EXTENSION
4"8"
20"
12”
Concrete Support
The Fireplaces are not rated for installation on a combustible oor system unless used in the Fire-Lite application. Fireplaces must be
built upon a concrete support slab with no wood underpinnings. Proper
reinforced concrete support slab for replace installations may include
the following types:
1. Slab on grade: standard residential, minimum four inch (4”) thick, 2500 psi concrete foundation on properly compacted ll. This type foundation can support Isokern installations up to thirty feet (30’)* overall height
without additional structural support. (brick ledge installations not
included) (Figure 42) * Minimum height. See page 3 for specic models.
2. Slab-on-grade foundations, thickened and reinforced: for additional
load carrying. (Figure 43)
FIGURE 42
FIGURE 43
3. Off-grade slab on foundation walls and footings
Projects with off-grade oor systems as well as upper story
installations require this type of support. When building off-grade support slabs the code required hearth extension substrate should be
built as a continuation of the support slab for the replace unit. (Figure
44). Supports for off grade slabs must be concrete or steel and capable of
supporting the slab, Isokern unit and the chimney.
For multi-oor and back-to-back installations proper weight
computation on an individual basis is required. Consult a local structural engineer for load bearing requirements.
Important: Foundations and footings must meet local code and be approved by the local building authority. For any foundation design
and load requirements check with a local structural engineer. It is the responsibility of the General contractor to insure adequate foundations.
Fireplace weights* and “foot print” areas:
The total replace weight and footprint for each model listed below includes: Fireplace pumice components only:
A. Model Magnum 28: 1040 lbs. - 35.5” x 28” = 6.90 sf. B. Model Magnum 36: 1300 lbs. - 43” x 28” = 8.36 sf. C. Model Magnum 42: 1420 lbs. - 49” x 28” = 9.52 sf. D. Model Magnum 48: 1600 lbs. - 53” x 28” = 10.3 sf.
A. Isokern Standard 36 - 1205 lbs. - 43” x 25 25” = 7.54 sq. ft. B. Isokern Standard 42 - 1325 lbs. - 49” x 25.25” = 8.59 sq. ft. C. Isokern Standard 46 - 1450 lbs. - 53” x 25.25” = 9.29 sq. ft.
FIGURE 44
*Totals are exclusive of any chimney components. See page 30 for Isokern DM chimney component weights.
“Footprint” areas listed above are base plate dimensions
for each model and are exclusive of manufacturer’s required hearth extension areas. See page 26 for hearth extension dimensions.
Note: Additional support slab area may be required at the side or back
of the replace unit to provide bearing for structural supports to a DM
offset chimney sequence. (See pages 33-35 for offset chimney support
requirements.)
28
DM Chimney System: General Information
The DM chimney system is a dual module, refractory masonry chimney system. It is composed of two precast, mating components, the outer casing block and an inner liner.
General Information:
This chimney system is designed for installation in accordance
with the National Fire Protection Standard for Chimneys and Solid Fuel-Burning Appliances, NFPA 211 and in accordance with codes such as ICC, BOCA Basic/National Codes, the standard Mechanical
Code and the Uniform Building Code.
Note: Illustrations shown reect “typical” installations with nominal
dimensions and are for design and framing reference only. Always maintain minimum required clearances to combustible materials and
do not violate any specic installation requirements.
Required DM Chimney Clearance:
The DM chimney system, rated UL 103HT, is listed for zero clearance to normal construction materials. The DM chimney system may be enclosed in a wood chimney chase at zero clearance to wood framing members.
WARNING: Keep all insulation minimum of three inches (3”)
away from all DM chimney components. If insulation is used in walls surrounding the chimney, insulation may be installed behind sheathing of gypsom board, plywood, particle board or other material on the side facing the Isokern material. The facing material cannot be
within 1 1/2” to the chimney outer casing. Failure to use manufacture’s
provided parts or variations in techniques and construction materials
or practices other than those described in this manual may create a re
hazard and void the limited warranty.
Note: A restop is required wherever a chimney passes between one
zone of a building to another. Ex: When the chimney passes through the ceiling into the attic area, there must be a sealed area around the
chimney so there isn’t a chaseway for a re to get to the attic.
When lateral support is required for DM chimneys, the framing members will be in contact with the DM chimney system.
Important: “Combustibles” are dened as “normal construction materials” and are considered to be: framing materials, particle board, mill board, drywall, plywood paneling, plywood sub ooring, and wood ooring.
Mechanical Vent Systems:
It is acceptable to use mechanical draft systems, if the venting companies do the engineering calculations and make the necessary
recommendations for fan size and ue vent diameter following the guidelines of NFPA 211/2006, pg. 211-13. Installation of such
systems must also follow the mechanical drafting company’s explicit installation and operation instructions.
29
DM Chimney Component List & Dimensions
16 1/2” 14”
6” HIGH INNER STARTER LINER
16 1/2”
12” HIGH INNER LINER DM 54
Note: DM 44 12” High Inner Liner will have a 6” or 8” Diameter Flue hole.
21 1/2” 21 1/2”
6”
12” or 14”
12”
12”
26 1/4”
SMALL CROWN CAP
37 1/2”
LARGE CROWN CAP
26 1/4”
13/16”
3”
37 1/2”
13/16”
3”
OUTER CASING
21 1/2”
25”
OFFSET BLOCK
OFFSET BLOCK STACKED
11”
3”
6”
3”
31 1/2”
BRICK LEDGE
31 1/2”
3”
30
DM Chimney: Component Weights
Isokern DM Chimney Weights:
Total installed Isokern DM chimney weight will vary
according to each specic installation. Total installed chimney weight will be based on the overall height and the conguration of
the chimney system. Chimneys may be straight vertical stacks of DM outer casing and inner liner but may also include the use of offset
chimney blocks, brick ledges, chimney reinforcement, brick/stone
veneers, cement crown caps and chimney shrouds.
The DM chimney component weights are as follows:
Small crown cap: 80 lb. Large crown cap: 100 lb. Brick ledge: 110 lb.
14” diameter inner liner: 45 lb.
Outer casing block: 90 lb. Offset block*: 84 lb.
*Construction of an offset block sequence will shift a portion, if
not all of the chimney load off of the rebox and smoke dome.
Additional reinforced concrete footing and slab area may need to be provided adjacent to or as a continuation of the primary support slab area for bearing the steel or masonry support required for an
offset sequence. (See pages 33-35) Consult a structural engineer for specic, individual structural requirements.
Notes:
Plan chimney conguration carefully before constructing
the required reinforced concrete support foundation for the
replaces. Be sure that enough structural masonry area is available
to support any offset chimney sequence included in the proposed
chimney design. (See Page 35)
SMALL CROWN CAP
LARGE CROWN CAP
BRICK LEDGE
Earthcore is not responsible for site specic structural support details and load specications for replaces and DM
chimney system installations. Consult local structural engineer
for proper job-specic support structure design, sizing and load bearing specications.
Unless otherwise noted, all oor drawings in this manual
are merely illustrations to indicate the presence of an underlying
noncombustible support structure to the replace installation.
INNER LINER
OUTER CASING
OFFSET BLOCK
31
10 3/4”
OUTER CASING
12” HIGH INNER LINER
6”HIGH STARTER INNER LINER
3 3/4”
Magnum Fireplace Shown For Illustration Purposes Only
FIGURE 45
FIGURE 46
FIGURE 47
FIGURE 48
DM Chimney System: Installation Instructions
DM Chimney Alignment:
Where the chimney run is to be a straight vertical run the DM outer casing block sits directly onto the Isokern smoke dome lid. The DM outer casing block, properly set is intended
to be ush with the back face of the rebox smoke dome assembly (Figures 48 and 49 ).
Set in this way the DM outer casing block will sit
three and three fourths inches (3-3/4”) back from the front face of the smoke dome. (Figure 48).
This total set-back distance makes it possible for
a three and one-half inches (3-1/2”) thick bearing header to pass over the rebox smoke dome assembly and for the DM
chimney to run straight up the back side of the bearing header
(Figure 49).
Installation of the DM chimney:
Begin straight DM chimney runs by setting a DM outer casing block in a bed of mortar on top of the smoke dome lid with the outer casing block centered on the lid from side to
side and ush with the back of the smoke dome lid. Be sure that the outer casing block aligns with the ue
hole in the smoke dome lid.
Next set the DM inner liner’s six inch (6”) tall starter piece (Figure 47) inside the rst outer casing block. The “factory” version of the six inch (6”) tall inner liner starter piece has a female end and a at end. Set this inner liner starter with the at end down. Set the downward end into Earthcore
Mortar so that it is fully sealed to the smoke dome lid.
WARNING: Do not mortar the air space between the inner liners and the outer casing blocks.
FIGURE 49
Starting with the six inch (6”) tall inner liner starter piece creates six inch (6”) staggered horizontal joints between
the inner liner and the outer casing block. Both the outer casing block and the inner liner components have tongue and groove type detailing on each end to assure alignment and interlock of the pieces as they are stacked and glued together.
Notes: If the “factory” inner liner starter piece is broken or otherwise unavailable then a full twelve inch (12”) tall inner liner piece can be cut to six inches (6”) in height to make an
inner liner starter piece.
DM chimney inner liners can be stacked with either the male or the female end up. In either case start the inner
liner stack with a six inch (6”) starter piece.
After setting the DM inner liner starter piece, apply mortar to the top of the starter liner. Continue the straight chimney run by placing a full height inner liner onto the six
inch (6”) starter liner. The top of this full height inner liner will sit 6” above the top of the outer casing block that was
previously set.
32
DM Chimney System: Lateral Support
This six inch (6”) offset between joints of the inner
liner stack and the joints of the outer casing stack continues to the top of the chimney run. Continue the straight vertical DM chimney by setting an outer casing block onto the mortared top surface of the preceding outer casing. The grooves on the bottom end of the
upper outer casing block t onto the tongues on the top of the
lower outer casing block. This assures proper alignment of the two components. Next place a full height inner liner onto the mortared top end of the previously set inner liner. Proceed this alternate stacking of outer casing blocks and inner liners until the desired
height of the ue is attained. Mortar all outer casing blocks
together and mortar all inner liners together. Do not mortar or
ll the space between the outer casing and the inner liner.
Lateral Support for DM Chimneys:
Though not required, it is recommended that where the DM chimney is built up along an exterior wall the vertical chimney system can be connected to the structural wall system
at a minimum of four foot (4’) intervals. This connection can
be made using 18 gauge strap ties (Simpson Strong Tie CS coil
strap, or equivalent).
Starting on one side of the DM chimney, at four foot
(4’) intervals up the structural wall adjoining the chimney,
connect one 18 gauage strap tie to the structural wall with
two, three inch (3”) #8 (minimum) wood screws or masonry
anchors, as appropriate. Next fold the strap around the three exposed sides of the outer casing. Connect the strap to each of the three outer
casing faces with two, one and one-half inch (1-1/2”) long masonry anchors, such as “Tapcon” or “Titen” screws. Fasten the strap back to the structural wall with two three inch (3”) # 8 (minimum) wood screws or masonry screws, as appropriate. (Figure 50)
Where DM chimneys are built up from the interior walls the DM chimney outer casing block is to be laterally braced at ceiling and roof penetrations.
Pressure treated two inch (2”) by four inch (4”) blocks, set at each side of the ue between the trusses or rafters
and fastened to the pre-engineered roof trusses or rafters with two 16d common nails at each end, provides lateral support,
parallel with the framing. Additionally, a two inch (2”) by four inch (4”) by six feet (6’) minimum pressure treated member (“rat run”) installed on each side of and butted up to the outer
casing block will provide lateral support perpendicular to the direction of the truss or rafter framing system.
Fasten the perpendicular member with two 16d
common nails to each intersecting truss or rafter. The perpendicular bracing should be installed on the top side the ceiling level framing as well as on the bottom side of the rafters.
(Figure 51) Note: A restop is required wherever a chimney passes between
one zone of a building to another. Ex: When the chimney passes through the ceiling into the attic area, there must be a sealed
area around the chimney so there isn’t a chaseway for a re to
get to the attic.
FIGURE 50
FIGURE 51
33
3”
FIGURE 52
DM Chimney System: Offset Block
DM Offset Chimney Block:
For vertical DM chimney to bypass overhead obstructions,
the Isokern offset chimney block is used. Offset blocks are six inch
(6”) thick, single module chimney components, measuring twenty-one and one-half inch (21-1/2”) wide by twenty-ve inches (25”) long. The fourteen inch hole passes through the block at thirty (30°) degrees. An offset chimney block can be set as the rst ue component on top of the replace smoke dome.
FIGURE 53
When building offset sequences it is necessary to support the third offset block in the sequence and every third offset block thereafter. When using only one or two offset blocks no additional support is required. Offset sequences are best when built as low as possible in the chimney run to maximize performance. Do not make support columns of brick, stone or wood. All support columns must bear onto proper noncombustible foundations.
Isokern Offset Chimney Block Installation:
Isokern offset chimney blocks are stacked in a stair step fashion with each successive block overhanging the previous offset
block by three inches (3”), allowing the ue to rise at an angle of thirty (30°) degrees off of vertical. (Figure 52) When building offset sequences check the interior ue
alignment as each offset block is set to avoid creating overhanging
ledges on the inside of the ue. Such internal overhangs will inhibit ue drafting.
Each offset block is to be set fully in a bed of Earthcore Mortar, completely sealing each offset block to the underlying component. Offset chimney block sequences can be built to shift the
chimney run to the left, right or to the rear of the rebox/smoke dome
assembly. Offset blocks can also be set in a spiraling rotation, thus moving the chimney to a point that is diagonally away from its starting point.
Offset blocks require a 1 1/2” clearance to combustible
framing.
FIGURE 54
Offsets to the Left or Right:
When offsetting chimneys to the left or right of the rebox it
is not possible to build a support column directly under the third offset block. To create proper support, construct a support column against
the rebox from bearing up to the level of the smoke dome. Bridge
from the column over to bearing on the smoke dome with two pieces
of four inch (4”) by four inch (4”) by ve-eighths inch (5/8”) steel
angle. On the steel angles build a masonry or steel support column up
to the underside of the third offset block in the sequence. (Figure 53)
Note: For offset chimney block sequences that clear the side
wall of the rebox below, it is allowable to support the rst offset block that clears the the rebox side wall and then to proceed with
supports at each third offset block thereafter. (Figure 54)
34
DM Chimney System: Offset Block (cont.)
With straight chimneys the front of the DM outer casing block sits approximately three and three-quarters inch
(3- 3/4”) back from the front of the smoke dome. This allows for a nominal 4” thick wall to be ush with the room side face
of smoke dome assembly while the DM chimney passes up the backside of the wall.
For a nominal 2” by 6” wall thickness the chimney can be offset 3” rearward. Set the rst DM outer casing block ush
to the back end of this offset block. This will leave a distance of
6-3/4” from the face of the rebox smoke dome assembly to the
face of the DM outer casing block. This allows for the smoke
FIGURE 55
dome to sit ush with the inside face of the 2” by 6” wall and the straight chimney to run up the outside of the wall. (Figure 55). For a wall thickness of 9”, nominal 8” CMU plus 1-1/2” furring strip - rst set two offset chimney blocks in sequence, rearward. This leaves a distance of 9-3/4” from the front face of
the smoke dome to the front face of the DM outer casing once
the outer casing block is set in position. (Figure 57)
Greater offset distances can be accomplished by
building with more offset chimney blocks. (Figure 56)
Offset block Support Foundations:
FIGURE 56
FIGURE 57
It is required that every third Isokern offset chimney block in the sequence be supported down to footings via concrete block or steel support columns.
Plan replace and DM chimney systems carefully
before foundations are laid to assure that proper footings are available to support Isokern offset blocks chimney run.
Calculate Offset Distance:
To calculate the distance of Isokern offset chimney travel in a
straight line to the right, left or to the rear of the rebox/smoke
dome assembly, proceed as follows:
Refer to Figure 58: temporarily dry set a DM outer
casing block in its proper location on top of the completed
rebox/smoke dome assembly as though starting a straight
chimney. If the offset sequence is to move to the left then, starting from the right side of the temporary DM outer casing measure left ward to the far face of the overhead obstruction that needs to be bypassed by the vertical chimney run.
For accurate measuring drop a plumb line down from
the far face of overhead obstruction to the level of the top of the smoke dome assembly. Measure from the far side of the temporary DM outer casing to the plumb line. This measurement, taken in inches and divided by
three (three inches of horizontal travel per offset block) gives
the total number of offset blocks needed to accomplish the required travel distance. To calculate the height that the offset block sequence will require, take the total number of offset blocks
needed to accomplish the travel distance (described above) multiplied by 6”. This number is the height (inches) that the
offset sequence will require.
35
PLUMBLINEPLUMBLINE
MEASURE TRAVEL DISTANCE
OVERHEAD OBSTRUCTION
TRAVEL DISTANCE
31 1/2”
BRICK LEDGE
31 1/2”
3”
DM Chimney System: Offset Block (cont.)
When establishing the “far face” of the overhead
obstruction, be sure that the DM chimney blocks can run straight to chimney termination without further overhead obstruction .
(Figure 59) Be sure that there is sufcient space beyond the “far face” of the overhead obstruction to accept the DM chimney’s outer casing dimension of 21 1/2”. Support all offset sequences
down to bearing as discussed on previous pages.
Notes:
A) Always support the last offset block in a sequence
for full support of the DM chimney where it returns to vertical. Support columns often carry the majority of the total load of the vertical chimney that is set onto the last offset block.
B) The total chimney weight above the last offset
block will be the total weight of the vertical chimney plus any additional allowable loads such as the Isokern brick ledge, its related brick or stone veneers, and any crown caps, or other chimney terminations.
C) Be sure the foundation under all support columns
is made of concrete or steel and designed to support the loads applied to it.
D) Check with local codes and a structural engineer to conrm loading and foundation requirements. E) Maximum horizontal distance of offset is six feet (6’) and represents twenty-four offset blocks in sequence. F) By code the maximum angle of offset for a chimney
system is 30° off of vertical.
FIGURE 58
DM Brick Ledge:
The DM brick ledge is a 3” thick, 31-1/2” square, steel reinforced, concrete and pumice slab (Figure 60). The Brick ledge provides a 5” ledge at all four sides
of the outer casing block and is designed to support masonry veneers to DM chimneys starting below the rafters and
continuing to termination. (Figure 61)
The component is cast with an octagonal hole in its center so that the DM octagonal inner liner can pass through it.
The brick ledge has four 2-1/2” holes through it that
align with the hole in each of the four corners of the DM outer casing block. These four holes are provided for reinforcement
of the chimney stack by the insertion of #4, minimum, steel reinforcing rods and subsequent grouting. (Figure 60 & 61)
The brick ledge is intended for use in chimneys that rise through the roof only where all four sides of the chimney are bounded by the roof.
WARNING: To maintain structural performance the DM brick ledge must not be cut or altered in any way.
FIGURE 59
FIGURE 60
36
DM Chimney System: Brick Ledge Installation
Brick Ledge
DM Brick Ledge Installation:
Use of the brick ledge will require a roof framing rough
opening of at least 34” in width. The required opening dimension
along the length of the rafter, where the chimney is to penetrate the
roof line, will increase above 34” relative to the pitch of the roof.
As the DM outer casing and inner liner assembly approaches the roof penetration set an outer casing block to a level
as close to the the low side of the roof framing as possible. (Figure
62)
The alignment tongues on the top of this outer casing
block must be ground off to leave a at contact surface for the brick ledge. Temporarily leave out the inner liner that ts this outer
casing block.
Set the Isokern brick ledge onto the at top surface of the
outer casing in a full bed of Earthcore Mortar. Be sure to align the
four 2-1/2” holes in the brick ledge with the matching holes in the
outer casing block below it. Return to setting the next inner liner in the sequence. This inner liner comes up from below and passes through the octagonal hole in the brick ledge. The liner’s top end
will be approximately 3” above the top surface of the brick ledge.
Set the next outer casing block onto the top of the brick ledge in a bed of Earthcore Mortar.
Insert one piece of #4 (minimum) steel reinforcing rod into each of the four 2-1/2” holes in the brick ledge. The reinforcement rods must start from a depth of at least 18” below the bottom of the
brick ledge, (In some cases, a minimum recommendation could be
5’).
FIGURE 61
Consult local structural engineer for proper job-specic support structure design, sizing and load bearing specications.
If short lengths of steel rods are used be sure to properly lap and wire tie all splices in the rebar. As the reinforcing
progresses, completely ll the holes with grout. Suitable grout can
be a pourable mixture of Portland cement and sand or Portland cement, sand and pea gravel. The rebar must be fully embedded in grout.
Leave enough of the #4 steel reinforcing rod exposed
above the brick ledge so that as the stacking of outer casing blocks continues to termination the reinforcing rods and grout can continue through the stack. Reinforcing shall continue to chimney termination. All DM chimneys that include the brick ledge must be reinforced as described above.
CAUTION: When using the Isokern brick ledge it is required that
the rebox/smoke dome assembly include the placement of a 4” by 4” by 3/8” minimum steel angle across the rebox opening. (See page 40 for “Structural Information” for details regarding specication and placement of steel angles in replaces.)
37
DM Chimney System: Brick Ledge Load Capacity
ISOKERN BRICK LEDGE
Lateral Support for Isokern Brick ledge Chimneys:
Once the DM chimney and brick ledge are assembled and after the intended masonry veneer has been installed on the brick ledge, be sure to brace the chimney following the guidelines on page 32 of this manual for Lateral Support of DM chimneys.
Load Capacity for Brick Ledge:
The sources of load delivered into the Isokern brick ledge are:
(1) the total physical load of brick, stone or other
masonry veneer on the brick ledge, and
(2) loading due to the force of wind delivered against
the exposed height of the chimney mass.
The required height of any chimney is governed by
applicable local building codes. The overall nished height of any chimney varies based upon site-specic conditions (eg.
elevation of roof line, roof pitch, distance of the chimney from
the ridge, etc.).
It is relatively simple to calculate the total physical load on the brick ledge resulting from the physical weight of applied veneers built to code height, however calculation values for load
to the brick ledge due to wind are site specic and based on local variables such as wind speed zone, exposure classication,
eave height and roof pitch of the structure, as well as height of chimney mass exposed to wind.
The total of physical load and load due to wind must not
exceed ninety four hundred (9400) pounds.
Notes:
Calculation of wind load requires the services of a local
structural engineer who can evaluate wind load for the specic
structure and site in question.
Do not subject the brick ledge to unequal loading when applying veneers. Build veneers equally on all four sides of the brick ledge.
FIGURE 62
38
INNER FLASHING
SMALL CROWN CAP
LARGE CROWN CAP
FIGURE 63
FIGURE 64
DM Chimney System: Flashing & Crown Caps
Brick ledge Veneer Finish and Flashing Details:
When applying brick, stone or other masonry veneer to the Isokern brick ledge standard good building practices for
masonry veneer work should govern weather-proong details and the placement of ashings. A typical ashing detail would be to eld fabricate an aluminum or galvanized sheet metal ashing, approximately thirty-two inches (32”) square with a twenty inch (20”) square hole in it, to serve as an inner ashing. (Figure 63) Place the inner ashing on the rst DM outer casing block that fully clears the roof line. Keep the ashing to about a one-half inch (1/2”) lap onto the top of the outer casing block. The twenty inch (20”) square hole in the ashing should t to the outside of
the alignment grooves on top of the DM outer casing. Continue the DM chimney up to the required termination height.
Once the masonry veneer is in progress the inner ashing
is set into a horizontal joint in the veneer at a level above all
other roof deck ashings, chimney-to-roof ashings and counter ashings. Weep holes should open to the outer face of the veneer at vertical mortar joints located at the level of the inner ashing. (Figure 64)
Where moisture may develop between the DM outer
casing and the chimney veneer, inner ashings as described above
will help to divert such moisture to exterior face of the veneer by way of the weep holes and thereby keep such moisture from working its way down between the veneer acing and the DM outer casing and into the interior of the structure below.
DM Small Crown Cap (Figure 65)
The DM small crown cap is a prefabricated cement
weather cap that measures 26- 1/2” square and 3” thick. The small
crown cap is designed and installed the same as the large crown cap. The small crown cap is intended for use where DM chimneys are to receive thin veneers and cultured stone that do not require the installation of the Isokern brick ledge. The small crown cap is also suitable where DM chimneys are to receive
a stucco nish. Other chimney terminations are possible with
DM chimneys. Check local codes for use of custom chimney terminations and decorative shrouds.
FIGURE 65
FIGURE 66
DM Large Crown Cap (Figure 66)
The DM large crown cap is a prefabricated cement weather cap for masonry veneer chimneys. The large crown cap
measures 37-1/2” square and is 3” thick at its center.
The component has an octagonal hole at its center so that the top inner liner of the DM chimney stack can pass through it. The crown cap then sits on the top most DM outer casing block. To set the large crown cap the last inner liner should be at
least 3” above the last outer casing block in the chimney stack.
Mortar the top of the last outer casing block. Set the large crown cap over the inner liner and onto the top of the last outer casing in the stack. Caulk or mortar the joint between the octagonal liner and the crown cap where the liner comes through the top surface of the large crown cap.
39
DM Chimney System: Height Requirements
10’-0”
LESS THAN 10’-0”
CRICKET
3’-0” MIN
ROOF RIDGE WORK POINT
SECTION THRU ROOF
CHIMNEY
2’-0”
WORK POINT
CRICKET
CHIMNEY
3’-0” MIN
SECTION THRU ROOF
2’-0”
3’-0” MIN
Chimney Height Requirement:
The required minimum chimney height above the roof
and adjacent walls and buildings is specied by all major building
codes and is summed up in what is known as “the 2 foot in 10 foot
rule”:
FIGURE 67
FIGURE 68
(1) If the horizontal distance from the roof ridge to the opening
of the chimney is less than 10’, the top of the chimney must be at
least 2’ above the roof ridge. (Figure 67)
(2) If the horizontal distance from the opening of the chimney
to the roof ridge is more than 10’ then a chimney height “work
point” is established on the roof surface 10’ horizontally from the
opening of the chimney. The top of the chimney must be at least
2’ above this work point. (Figure 68)
(3) In all cases, the chimney cannot be less than 3’ above the roof at the edge of the chimney. (Figure 67 & 68)
A simple example of this would be if the roof is at
then the chimney would need to be at least 3’ above the roof surface. Or, if the chimney penetrates the roof at the ridge then
the chimney must be at least 3’ above the ridge. (Figure 69)
Note: The “2 foot in 10 foot rule” is necessary in the interest of re safety but does not ensure smoke-free operation of the replace. Trees, buildings, adjoining roof lines, adverse wind conditions, etc. may require a taller chimney for the replace to
draft properly.
Chase Enclosures: DM chimneys can be enclosed within a wood framed chase at zero clearance to wood framing members. Chase enclosures need to be built to local wind load requirements and shall be structurally independent of the Isokern chimney. As with all chimney installations, avoid overhead obstructions such as trees, power lines, etc.
FIGURE 69
WARNING: Keep all insulation minimum of three inches (3”)
away from all DM chimney components. If insulation is used in walls surrounding the chimney, insulation may be installed behind sheathing of gypsom board, plywood, particle board or other material on the side facing the Isokern material. The facing
material cannot be within 1 1/2” to the chimney outer casing. Failure to use manufacture’s provided parts or variations in
techniques and construction materials or practices other than
those described in this manual may create a re hazard and void the limited warranty. Do not pack insulation around the replace
or chimney. Do not insulate the chase cavity with blown or loose-
ll type insulation materials.
Chase Top Flashings:
Non-combustible, weather tight chase ashing must be
used to cover the top of the chimney chase. Be sure to seal the
joint where the DM liner passes through the chase top ashing for positive weather seal. Chase ashings may be supplied by others.
40
STEEL ANGLE 4x4x3/8 MIN
FRONT DAMPER SUPPORT
CAST IRON DAMPER (IF USED)
STEEL ANGLE 4x4x3/8 MIN
Top Plate
Structural Information
The rebox/smoke dome assembly has a load capacity that allows for the replace system to carry a limited amount of
straight, vertical DM chimney sections. The load capacity for each model, stated as maximum DM chimney heights without additional structural support, are listed on page 3. These chimney heights are for straight chimneys (no
offsets) and are exclusive of the brick ledge.
Important: DM chimneys taller than the listed maximum
heights require a steel angle (minimum of 4” x 4” x 3/8”) be set across the rebox opening when assembling the unit as a
structural lintel. Consult a structural engineer to design proper structural support.
This steel angle shall span the rebox opening, bearing fully on the front 4 inches of the rebox side wall components.
The vertical leg of the angle steel lintel should turn up and sit in
front of the damper plate component. (Figure 70)
Important: The application of the steel angle as described
above is also required in all replace installations where the
brick ledge is used. This required steel lintel placement is in addition to the reinforcing required for DM chimneys with brick ledge as described on pages 36 and 37.
Important: For DM chimneys with both offsets and a brick
ledge it is important to fully support the last offset block where the chimney returns to vertical. This is required in order to provide complete vertical support for the brick ledge and its related loads.
Important: When placing steel angles or any other steel support
members into the Fireplaces structure maintain a 2” minimum
air space around steel members for clearance to combustible members and combustible surfaces.
Wind Load Calculations: Using the required Earthcore Mortar to install the DM chimney system, the maximum height above the roof line of a one story residence with an exposure
classication C without additional structural support is:
90 MPH 26’-0” 100 MPH 24’-0” 110 MPH 21’-8” 120 MPH 19’-8” 130 MPH 18’-0” 140 MPH 17’-6” 146 MPH 16’-8” 150 MPH 16’-4” For two story residences, please call the Technical Department
at: 800-642-2920.
FIGURE 70
Important: The top plate of the rebox is not meant to be
used as a structural support of any veneer. Consult a structural engineer for structural support of any veneer bearing weight on the Isokern top plate for additional structural support.
41
LARGE CROWN CAP
SMALL CROWN CAP
Common Chimney Terminations
Two chimney terminations are offered by Isokern, the DM large crown cap and the DM small crown caps. These are cement crown caps designed to provide a weather cap to the DM chimney system. Their design is typical of the cement caps found on traditional masonry chimneys. Due to owner preference and architectural design criteria other chimney terminations can be used alone or in conjunction with the crown caps. Special design caps may be designed and constructed by
others and must be fashioned so as not to restrict the ow of smoke and gasses out the top of the ue opening. Figure 71 depicts some common
chimney terminations. Check with local building codes to establish the need for chimney caps and spark arrestors or for any limitations to their design and use.
FIGURE 71
42
METAL FLUE
Metal Flue
Fireplaces are tested and listed for use with factory-built metal, Class “A” (solid fuel) chimneys as an option. Any Class “A” or UL 103 listed metal chimney system is accetable for use on any Isokern system. (Figure 72)
Metal Flue Types:
The selected factory-built metal chimney for use with
the replaces, at a minimum, must be listed by a recognized
agency for solid fuel and as tested to UL 103, for continuous use
of one thousand degrees (1000°) Fahrenheit and intermittent use of seventeen hundred degrees (1700°) Fahrenheit.
The factory-built metal ue design can be from the following
types:
1. Non-insulated completely thermal siphoning, double-wall, air­cooled solid fuel rated chimneys listed to UL 103, ULC S629.
2. Double-wall with solid-pack insulation.
3. A combination of double-wall, solid-pack insulation and air
space (triple-wall).
FIGURE 72
FIGURE 73
ANCHOR PLATE
INSWOOL BLANKET
4. Triple-wall air space solid fuel chimney.
5. Listed chimney liners conforming with the seventeen hundred
degree (1700°) Fahrenheit requirements of UL 1777 or ULCS635 or ULC640 may also be used with Isokern replaces.
Note:
The selected, approved chimney manufacturer must
provide the masonry anchor plate designed to t their ue system. (Figure 73)
All chimneys and chimney liners must be installed in accordance with the manufacturer’s installation instructions and
under the terms of their listing for use with open faced replaces.
Maximum height of a metal ue system is not required as all the load can be taken off the rebox.
Refer to metal ue manufacturer for number of offsets,
approved chimney shrouds, clearance to combustibles and any
information specic to that ue system. Earthcore does not
manufacture these components and defers to manufacturers instructions.
SMOKE DOME TOP PLATE
43
A
B
STEEL ANGLE 4 x 4 x 3/8 MIN
VERTICAL SIDE FACE INSIDE FIREBOX (BOTH SIDES)
NOTCH FOR STEEL ANGLE PLACEMENT (BOTH SIDES)
FRONT VIEW
STEEL ANGLE
MODEL A B
28 35 1/2” 45 1/2“ 36 43” 53” 42 49” 59” 46/48 53” 63”
1 1/2” MIN *
1 1/2” MIN *
HEARTH EXTENSION MINIMUMS
VERTICAL FACE IN
1 1/2” OVERHANG
The See-Thru application of the replace is built with a replace kit, omitting the back walls. To support the smoke
dome and chimney, steel angle is required to be installed as described. Note that due to the large opening area of a two-
sided replace this type of replace can be difcult to get to
reach and to maintain proper drafting.
Constructing a See -Thru Unit:
1) Set the base plate in place. Notes: If the design preference is for a “ush hearth” (replace
oor ush with the room’s oor), the base plate can be omitted from the assembly and the rebox walls built directly on the
concrete support slab as long as there are no combustible underpinnings underneath the concrete slab.
Whether a ush hearth is preferred or a raised hearth, the combustible oor on front of the replace must be covered
with a noncombustible hearth extension set tight against both
open sides of the replace and extending at least 20 inches out from the replace opening and at least 12 inches beyond the nished sides of the replace opening.
2) The rebox back wall components are not used. The rebox side walls are set, reversed from their normal position, their ared faces set to the outside of the rebox. (Figure 74) The rebox side walls must sit a full 3” on the front & rear of the base plate. Since the side wall components air from 3” at the narrow front end to 8” on the wide rear end, the side walls will overhang the base plate by approximately 5” at the rear of the unit. (Figure 76)
3) Once the side wall assembly is complete it is
necessary to place a steel angle minimum 4”x 4”x 3/8” across
each face of the two sided opening before building the smoke dome assembly. Notch the ends of each sidewall equal to the thickness of the steel as shown. Each end of the steel angles
must bear fully at least 3” onto the side wall assembly. (Figure
74)
4) Since there is no back wall assembly and no side wall ledge for placement of a cast iron throat damper, the smoke
dome for the See-Thru replace is built by placing one long damper beam on top of the rebox back wall and ush with it; the other long damper beam sits ush with the front of the Isokern Standard rebox, spanning the rebox opening.
These components both sit on their narrow base so that
their beveled face points down and into the rebox interior.
5) The damper plate end pieces are designed to sit on
the rebox side wall between the front and back long damper beams. Place the vertical face of each piece 1-1/2” to the inside of the inside sidewall of the rebox. This will allow the re brick to align ush with the damper end pieces. (Figure 75)
6) Once the smoke dome assembly is built and the DM chimney is installed, a chimney top damper is set at the top of
the ue or a bottom mount damper is installed to the inside of
the top plate.
Specialty Applications - See-Thru
FIGURE 74
FIGURE 75
FIGURE 76
44
Specialty Applications - Two Story Stacked Installations
General Information:
To install one Fireplace and DM chimney system above
one another, as in a two story stacked installation, both the upper
and lower replace installations require a structurally designed
support down to footings designed by a structural engineer.
Frequently in two story stacked installations the lower
unit is supported by a slab-on-grade, whereas the upper unit is a typical off-grade support. The off-grade slab for the upper unit
must be built with sufcient width in order to accommodate the width of the upper replace plus the width of the by-passing chimney system rising from the lower unit. (Figure 77) Dimensions for each replace unit can be found on the
website at: www.earthcore.co. The slab for the lower unit will need to be built with
enough width to provide support for the lower replace unit
plus the bearing surface for the support columns needed to carry
the offset chimney sequence of the lower system. (Figure 77)
Floor-to-Floor Height Considerations:
In order for the lower replace installation to have
enough overhead height clearance for its chimney to rise at a
thirty degree (30°) angle of offset (maximum angle of offset as allowed by code) and bypass to one side of the rebox in the upper location there are minimum required oor-to-oor height dimensions. (See chart, page 45 - Dimension “F”) The minimum oor-to-oor height required for an
installation is determined by calculating the total horizontal
distance the lower ue must travel to the left or right for it to bypass to one side of the upper replace. (see calculating offsets on pages 34 & 35)
The total amount of horizontal chimney offset travel distance will be determined by two factors:
1. The width dimension of the upper unit; and
2.The horizontal distance between centerlines of the proposed upper and lower units.
Example:
If the upper replace and the lower replace sit on the same centerline then the required oor-to-oor dimension is at a maximum (See Figure 78 and chart, page 45 dimension, column “F”.) For every 3” of horizontal distance separating the
centerlines of the upper and lower units the overall height of the
offset sequence is reduced by one offset block or by 6”.
Notes:
A raised hearth at the lower replace will increase the minimum oor-to-oor height requirement by the height
dimension of the raised hearth. In the interest of clarity the drawing on pages 44 and
45, (Figures 77 & 78) of the offset chimney sequence does not
show the offset block support columns as required for offset
sequences and as described on pages 33 & 34 of this manual.
FIGURE 77
45
Specialty Applications - Two Story Stacked Installations (cont.)
D
B
C
E
F
A
The following chart gives important dimensions needed
when laying out two story stacked replace units. Chart dimensions assume that both the upper and lower replace units sit on the same
centerline.
Note: Widths of both Isokern Standard and Magnum replaces are the same. Only the depth of the rebox and the height of the nished opening differ.
Upper/Lower A B C D E F
36/36 43 51 30 81 70 142 36/42 43 51 33 84 70 142 36/48 43 51 35 86 70 142 42/36 49 54 33 87 70 148 42/42 49 54 33 87 70 148 42/48 49 54 35 89 70 148 48/36 53 56 35 91 70 149 48/42 53 56 35 91 70 149 48/48 53 56 35 91 70 149
Chart Dimension Description: (Figure 78) “A” is the outside width dimension of the Fireplace model chosen
for the upper unit. “B” dimension represents distance (taken in the direction of the
chimney offset) from the centerline of the lower replace to the outside face of the eight inch (8”) thick bearing wall underpinning the upper unit’s oor system.
“C” dimension is the distance (taken away from the direction of
the chimney offset) from the centerline of the lower or the upper replace, whichever is the larger plus eight inches (8”) to the outside of the eight inch (8”) thick bearing wall for the upper unit’s
support slab.
“D” is the outside-to-outside dimension of the two eight inch (8”) thick bearing walls underpinning the upper unit’s support slab. “D” is also the width of the upper unit”s support slab and includes the
additional space for the width of the DM chimney as it bypasses the
upper unit. “D” is also the sum of “B” plus “C”. “E” is the height of the Fireplaces chosen for the lower unit and
includes the Isokern three inch thick base plate. “F” is the dimension from the top of the support slab of the lower
unit to the top of the oor of the upper unit.
Notes: If raised hearths are planned for the lower unit then “F”
dimension will increase by the height of the raised hearth at the lower unit. In the interest of clarity the drawings on page 44 and 45
(Figures 77 & 78) of the offset chimney sequence do not show the
offset block support columns as required for offset sequences. See
pages 33 & 34 for complete offset support instructions.
Consult local structural engineer for support slab load calculations.
FIGURE 78
46
Fire-Lite Application - General Information
General Information:
The Fire-Lite is an application of the Isokern Standard and Magnum replaces designed, tested and listed with the ability to be installed on a combustible oor system. The design and installation require that the system use Class A metal ue, or equivalent. The Fire-Lite assembled unit must sit on a raised, noncombustible platform allowing a minimum 4” air space between the Isokern base plate and the combustible oor. Many of the requirements for the Fire-Lite such as re
brick installation, safety precautions and installation instructions
for the Isokern Standard and Magnum replaces will apply and
are referred to in previous pages of this manual. Refer to those instructions for additional information. The following pages will refer to installation
requirements specic to the Fire-Lite system.
Intended Use Statement:
The Fire-Lite replace is designed to sit on a combustible oor system and is intended to burn solid wood fuel, propane or natural gas. The replace is intended for use as
a supplemental heat source only and is not intended for heavy use as a primary heating system.
Notes:
The local authority having code jurisdiction should be consulted before installation to determine the need to obtain a permit. Refer to page 4 of this manual for areas of concern. Do not scale drawings. Illustrations in this manual are
not to scale and are intended to show “typical” installations.
Nominal dimensions are given for design and framing reference
only, since actual installations may vary due to job specic
design preferences. Always maintain the stated minimum
clearances to combustible materials. Do not violate any specic
installation requirements.
The Fire-Lite has been tested and listed by Warnock Hersey (Report Nos. J20004277-231 and 632-912500) to UL
127-1999. These units are intended for installation in residential homes, and other buildings of conventional construction.
Fire-Lite replace systems are also designed for installation in accordance with the National Fire Protection Association Standard for chimneys, replaces, vents and Solid Fuel-Burning Appliances (NFPA 211).
Though any Class A or UL 103 metal chimney can be
installed with a Fire-Lite, the following installation instructions refer to the FTF-13 chimney system. If an equivalent metal chimney system is used, follow the metal ue manufacturer’s
explicit installation instructions.
Safety Instructions:
Because the Fire-Lite is an application of the Magnum or Isokern Standard Series replaces, the safety instructions are listed on pages 5 & 6 of this manual. Please refer to them and read them carefully before installing your Fire-Lite system.
FIGURE 79
47
FTF 13 Metal Chimney (or equivalent)
2” min. 2” min.
1 ½” min. to Combustible Framing
Fire-Lite Stand
(4” min)
Combustible Floor System
1 ½” min.
Noncombustible
Hearth Extension
Zero Clearance
20” min
Hearth Extension Support with Noncombustible Material.
*8 1/2” min
20” min
3” min When Unsupported
1 1/2”
Min
12” min
12” min
1 1/2” min When Supported*
Plus width of backing
Combustibles Must Have 1 1/2”” min Clearance
Combustibles Must Have 1 1/2”” min Clearance.
DO NOT ENCROACH ON CLEARANCE WITH COMBUSTIBLES!
1 1/2”
1 1/2”
CORRECT
INCORRECT
* Height based on the use of 1 1/4” fire-brick and a 1/4” mortar bed. This height may vary based on the firebrick used.
The Fire-Lite is tested and listed for installation with “clearance to combustibles” as follows:
1) Four inches (4”) clearance to the combustible oor.
2) Zero inch (0”) clearance at the Isokern smoke dome front wall
(Figure 77).
3) One and one half inches (1-1/2”) clearance at the Isokern rebox
back walls and side walls.
4) Two inches (2”) minimum air space to combustibles at all FTF-
13 metal chimney components’ outer layer.
Important: “Combustibles” are dened as “normal construction materials” and are considered to be: wood framing materials, particle board, mill board, plywood sub-ooring, plywood paneling and wood ooring. Sheathing materials, such as plywood, particle
board and drywall may cover the smoke dome front at zero inch
(0”) clearance. All combustible sheathing materials must be held eight inches (8”) away from the sides of the rebox opening and eight inches (8”) above the top of the rebox opening. The rebox backwall, side walls and the smoke dome back require 1 1/2” clearance. (Figures 80 & 81)
Fire-Lite Application - Required Clearance To Combustibles
FIGURE 80
Keep all insulation, vapor barriers, “house wrap” paper and other insulating type membranes and products, including
berglass, cellulose and other insulation, (anything that carries
an “R” rating) a minimum of three inches (3”) away from all
rebox and chimney surfaces.
Exception: If insulation is used in walls surrounding the replace,
insulation may be installed behind sheathing of gypsom board, plywood, particle board or other material on the side facing the
Isokern. (Figure 81)
The sheathing material holding back the insulation cannot be
closer than 1 1/2” to the replace sidewalls, backwall or chimney
system. (Figure 83)
When Fireplace installations are surrounded by walls
that are to be insulated, the walls must have enough clearance to
the Isokern unit in order to maintain the three inch (3”) minimum
clearance to insulation for unsupported insulation. Never spray the Fireplace or chimney system with any type of sealer, insulation or other material.
Notes:
The Fire-Lite Application is designed, tested and approved for installation at a minimum of four inches (4”) above combustible oor systems per the installation specications given in this manual. Any portion of the combustible oor system left exposed under the base plate is to be covered with minimum 1” thick ceramic ber insulation board or equivalent rated to 2100 degrees Fahrenheit (Figure 79). All Fire-Lite Series result in the nished re brick oor of the rebox being at least eight inches (8 1/2”)* above the combustible oor system (Figure 80).
FIGURE 81
FIGURE 82
FIGURE 83
48
Fire-Lite Application - Load Calculations
Floor framing for a Fire-Lite installation will need to
be designed and built to accept substantial dead loads spread
over a relatively small oor area.
The following weights and sizes can be used to
calculate Fire-Lite loading. Consult with local structural engineer for proper sizing of structural oor frame members for specic installations.
Load Calculations: Total dead load amounts include (but are not necessarily
limited to) the following items and their corresponding weight
estimates listed below:
1. Fire-Lite unit model weights: MFP = Magnum Series - SFP = Isokern Standard Series a. Model 36 MFP: 1300 lbs. - 36 SFP: 1205 lbs. b. Model 42 MFP: 1420 lbs. - 42 SFP: 1325 lbs. c. Model 48 MFP: 1600 lbs. - 46 SFP: 1450 lbs.
2. Damper, re brick and mortar: 450 - 500 lbs.
3. Raised platform: 40 lbs.
4. Fireplace nished facing: approx. 200 lbs. (dependant on facing used)
5. Weight of metal ue: negligible By adding the weight of the appropriate Fire-Lite Model listed in #1 above to the allowance given for each item in 2 through 5, above, the total weight of the Fire-Lite Series can
be estimated.
The oor area for each model is as follows:
Magnum:
Model 28 FP @ 35.5” x 28” = 6.90 sq.ft. Model 36 FP @ 43” x 28” = 8.36 sq.ft. Model 42 FP @ 49” x 28” = 9.52 sq.ft. Model 48 FP @ 53” x 28” = 10.3 sq.ft.
Isokern Standard:
Model 36 FP @ 43” x 25.25” = 7.54 sq.ft. Model 42 FP @ 49” x 25.25” = 8.59 sq.ft. Model 48 FP @ 53” x 25.25” = 9.29 sq.ft.
Notes:
These dead load totals are in addition to the live load
and other dead load requirements for the specic site’s proposed oor.
The load estimates given above for items are estimates
only and may not accurately dene total loads related to the completed replace due to material choices that are at owner option. Consult your local structural engineer for proper oor system design, sizing and specications. Isokern is not responsible for structural oor support details for the Fire-Lite replace. Unless otherwise noted all oor framing drawings in this manual are merely illustrations to indicate the presence of an underlying oor system.
FIGURE 84
Magnum Series Shown for Illustration Purposes Only
49
1 ½” min.
25 ¼”
Fire-Lite Stand 4” or 8” Heights Available
Combustible Floor System
14GA. Metal Joists @ 12” O.C. with a 3” Dia. Hole for Air Dissipation
Noncombustible 20” Hearth Substrate
Air Dissipation
26 Gauge Metal
Safety Strip
8 ½”
MIN
Insboard or Inswool Cut and Placed Between Sections
Fire-Lite Application - Hearth Conditions
Noncombustible Hearth Extension Required 20” min
Support Hearth Extension With Noncombustible Material
Secure Fire-Lite Stand To Trusses
Floor Framing By Others
1 1/2” min
1 1/2” min
1 1/2” min
SIDE VIEW
FRONT VIEW
PLAN VIEW
Hearth Extension
Required
12” min
20” min
Field Verify Dimensions:
Magnum Series:
28 55 3/4”W x 49 1/2”D 36 58 1/2”W x 49 1/2”D 42 65 1/2”W x 49 1/2”D 48 69 1/2”W x 49 1/2”D
Field Verify Dimensions:
Isokern Standard Series:
36 58 1/4”W x 46 3/4”D 42 64 1/4”W x 46 3/4”D 48 68 1/4”W x 46 3/4”D
Note: Field Verified Dimensions Should Make Allowance for Hearth Extensions in Front (20”) and Sides (12” ea.) From Fireplace Opeining. Also Fireplce Sides and Rear, 1 1/2” Clearance to Combustibles
** Consult Local Structural Engineer for Specific Structural Suppot. Use Metal Flue Only.
The noncombustible raised platform must be set with a
minimum one and one half inch (1-1/2") clearance to the wall to the sides and directly behind the Fire-Lite assembly.
Raised Platform:
Nominal four inch (4") metal base. (Figure 85). Set the Fire-Lite base plate in a mortar bed on to the non-combustible
raised platform.
Metal safety strip - a generic 26 ga., four inch (4”) wide
galvanized metal strip - must be inserted to approximately two
inch (2”) beneath the platform at the front of the noncombustible
raised platform. The safety strips must extend out from the
front of the raised platform at least two inches (2”) and must extend to at least two inches (2”) beyond the ends of the raised
platform. Any overlaps in the length of the safety strips should
be a minimum of two inches (2”) for continual coverage of the combustible oor at the front of the replace (Figure 85). The exposed combustible oor within the perimeter
formed by the noncombustible raised platform must be
completely covered with Inswool or Insboard ceramic ber insulation (Figure 84). The Inswool or Insboard is dry laid to the oor within the block perimeter. The ceramic ber must have a thermal conductivity rating equal to or greater than 0.4 Btu-in/hrsq. ft-degree Fahrenheit. (Reference: Harbison-Walker, 600 Grant St., Pittsburgh, PA 15219, ph. 412-562-6200: “Insboard 2100” or equivalent.)
FIGURE 85
Fire Brick Installation: Follow instructions on page 19 of this
manual.
Recessed Fire-Lite:
If the design preference is for a ush hearth Fire-Lite application (oor of the replace at the same level the room’s oor), with advanced planning, the metal stand can be lowered, set and attached to the joist system. (Figure 86) When calculating ush hearth height be sure to allow for the four or eight inch (4” or 8”) metal stand, three inch (3”) thick base plate plus the one and one half inch (1-1/2”) thick re brick oor. Whether a ush hearth is preferred or a raised hearth, the combustible oor in front of the replace must be covered
with a noncombustible hearth extension set tight against the
replace front and extending at least 20 inches out from the nished replace and at least 12 inches beyond the nished sides of the replace opening. For all “Fire-Lite” construction, it is necessary to use the base plate. Be sure to secure the Fire-Lite metal stand to the oor framing system, then mortar the base plate to the metal
stand for stability.
*For seismic anchorage design and instructions of the iush
hearth application, please contact the Technical Department at 1-800-642-2920.
FIGURE 86
50
FTF-13 or Equivalent Chimney System
The Fire-Lite is designed, tested and listed for use with
UL 103 or Class A metal chimney system, or equal.
Do not modify or alter metal ue or metal ue
components as this could result in an unsafe and potentially dangerous installation that may cause a serious hazard and void the listings, approvals and the limited warranty of the system.
The following installation instructions refer to FTF­13 chimney system. If “equal” metal chimney systems are used, follow the metal ue manufacturer’s explicit installation
instructions.
General Information:
This chimney system is designed for installation in
accordance with the National Fire Protection Standard for chimneys and solid fuel burning appliances, NFPA 211 and in accordance with codes such as BOCA Basic/National codes, the
Standard Mechanical Code and the Uniform Building Codes.
Note: Illustrations shown reect “typical” installations with
nominal dimensions and are for design and framing reference only. Actual installations may vary due to individual design preferences. However, always maintain minimum required
clearances to combustible materials and do not violate any specic
installation requirements.
WARNING: Failure to use manufacture’s provided parts,
variations in techniques and construction materials or practices other than those described in this or the manufacturers manual
may create a re hazard and void the limited warranty.
Chimney Clearance Requirements:
The FTF-13 chimney’s outer layer requires a minimum two inch (2”) air space to combustibles.
The chimney system must be enclosed when installed in or passing through a living area where combustibles or people may come in contact with it. This is important to prevent possible
personal injury or re hazard. The FTF-13 chimney’s re stop spacer and roof ashing (not chase ashings) may be placed directly on or against normal
construction materials.
Note: “Normal construction materials” are considered to be:
framing materials, particle board, mill board, plywood, paneling,
ooring, and drywall.
Chimney Height Requirements:
Refer to ue manufacturer for chimney height
requirements and recommendations.
FIGURE 87
51
FTF-13 or Equivalent Chimney System (cont.)
Installation of the FTF-13 Metal Chimney System for the Isokern Fire-Lite:
Transition from the Isokern to the FTF-13 Metal Chimney System:
The FTF-13 metal ue attaches to the smoke dome’s top
plate by use of the AP-ISO masonry anchor plate. The Anchor
Plate is tted with an octagonal base plate to afx it to the smoke
dome’s top plate. The anchor plate also has starter rings for both
the inner and the outer sleeves of the metal ue (Figure 89).
Step 1. Lay a twenty-four inch (24”) square, half inch (1/2”) thick (minimum) piece of ceramic ber high temperature blanket (“Inswool” Ceramic Fiber HP Blanket, rated for temperatures up to 2400 degrees F., or equal.) on the top of the top plate. Cut a hole approximately 11” in diameter in the center of the high temperature blanket and align the blanket on the ue hole in the top plate (Figure 89).
Step 2. Fit the AP-ISO Anchor Plate assembly onto the Inswool so that the inner ue sleeve projecting out the bottom of the anchor
plate is inserted through the high temperature blanket and into the hole in the top plate. The high temperature blanket is held between
the anchor plate and the top plate as a gasket (Figure 89). Attach
Anchor Plate to the top plate with masonry attachment screws through holes provided in the anchor plate into the top plate. Do
not over torque masonry screws into the Isokern material. (Figure
90)
FIGURE 88
UL 103 or Class A
Anchor Plate
Inswool Blanket
Chimney Terminations:
FTF-13 chimney pipe requires a termination component to be installed at or near the top of the chimney chase ashing. The FTF-13-CTD Round Termination is the recommended termination. (See page 52)
Installation:
Step 1. Hold the FTF-13-CTD over top of last chimney section. Step 2. Center inner slip section in inner ue pipe and slip down. Step 3. Center outer locking section over outer ue pipe. Push down until locking tabs are rmly engaged. Step 4. Pull up slightly on CTD to ensure locking joint has rmly
engaged.
Note: It is recommended that all exterior exposed metal chimney
components - such as terminations, ashings, and ue - be painted
with a premium quality, high temperature, rust preventative paint designed for metal. This is especially important when installations are made in abnormally adverse or corrosive environments such as near lakes and oceans or, in areas with consistently high humidity conditions. Consult the paint manufacturer’s instructions for proper preparation and application.
Chimney Height Requirements:
FIGURE 89
UL 103 or Class A
Top Plate
Anchor Plate
Inswool Blanket
Refer to page 39 of this manual.
FIGURE 90
52
FTF-13 Installation Components
Round Termination
Fire Stop Spacer
Chimney Flue Section
Fire Stop Spacer (30° Offset)
Offset Return Package (30°)
Stabilizer
Locking Band
Combination Offset Return Elbow
Anchor Plate
53
FTF-13 Offset Elevation Chart
A
Offset
Inches
B
Height
Inches
FTF-13-ES30
Offset/Return
Elbow Set
FTF-13-S4
Stabilizer
Number of FTF-13
Chimney Section
12”
18” 36”
4 9
12
14 1/4
17 1/4 20 1/4
21
22 1/4
25 1/4 26 1/4 28 1/4 29 1/4
31 1/4 21 1/2 34 1/4 36 1/4
37 1/4 38 1/4 39 1/4 41 1/2
43 1/4 44 1/2 45 1/4 46 1/4
48 1/4 49 1/2 51 1/4 54 1/4
55 1/4 56 1/2 59 1/2 61 3/4
64 3/4
67 69 70
73 75 79
80 1/4
82 87
15 3/4 24 1/2 29 3/4 33 1/2
38 1/2 43 3/4 45 1/4 47 1/2
52 1/2 54 1/4 57 3/4 59 1/4
63
65 68 1/4 71 3/4
73 1/4
75
77 80 1/2
83 3/4 85 3/4 87 1/2
89
91 1/2 94 1/2 97 3/4
103
104 1/2 106 1/2 111 3/4
116
121 1/4 124 3/4 127 3/4
130
135 1/4 138 3/4 145 1/2 147 1/2
150 3/4 159 1/2
1 1 1 1
1 1 1 1
1 1 1 1
1 1 1 1
1 1 1 1
1 1 1 1
1 1 1 1
1 1 1 1
1 1 1 1
1 1 1 1
1 1
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 1
1 1 1 1
1 1 1 1
1 1
0 1 0 2
1 0 0 2
1 1 0 0
2 4 1 3
0 0 2 1
1 3 0 0
2 1 1 0
0 2 1 1
0 2 1 1
0 2 1 3
0 1
0 0 1 0
1 2 0 1
2 0 3 1
0 1 1 0
2 0 1 4
0 1 3 1
0 5 1 2
0 1 2 0
1 0 3 1
2 1 0 1
1 1
0 0 0 0
0 0 1 0
0 1 0 1
1 0 1 1
1 2 1 0
2 1 1 2
2 0 2 2
3 2 2 3
3 3 2 3
3 3 4 3
4 4
54
FTF-13 Vertical Elevation Chart
Height of
Chimney Only
No. of FTF-13
Chimney Lengths
12”
18” 36”
11
17 21 3/4 27 1/4
33 1/4
35 37 1/4 43 1/4
51 1/4 55 1/4 61 1/4 67 1/4
69 1/4 79 1/4 85 1/4 89 1/2
95 1/4
103 1/4
113 1/2 119 1/2
123 3/4 129 1/3 137 1/2 147 3/4
153 3/4
158 164
171 3/4
182 188 192
198 206
215 3/4
222
226 1/4 232 1/4
240
250 1/4
256 1/4 260 1/2 266 1/2 274 1/4
284 1/2 290 1/2 294 3/4 300 3/4
Height of
Chimney Only
No. of FTF-13
Chimney Lengths
Height of
Chimney Only
No. of FTF-13
Chimney Lengths
Inches Feet Inches
12”
18” 36”
Inches Feet Inches
12”
18” 36”
Inches Feet Inches
0 1 1 1
2 2 3 3
4 4 5 5
5 6 7 7
7 8 9 9
10 10 11 12
12 13 13 14 15 15 16
16 17 17 18
18 19 20 20
21 21 22 22
23 24 24 25
11
5 9 1/4 9 1/4
9 1/4
11 1 1/4 7 1/4
3 1/4 7 1/4 1 1/4 7 1/4
9 1/4 7 1/4 1 1/4 5 1/2
11 1/2
7 1/4 5 1/2
11 1/2
3 3/4 9 3/4 5 1/2 3 3/4
9 3/4
2 8
3 3/4
2 8 0
6 2
11 3/4
6
10 1/4
4 1/4
0
10 1/4
4 1/4 8 1/2 2 1/2
10 1/4
8 1/2 2 1/2 6 3/4
3/4
1 0 2 2
0 0 2 1
0 2 1 0
0 1 0 2
1 0 1 0
2 1 0 1
0 2 1 0 1 0 2
1 0 1 0
2 1 0 1
0 2 1 0
1 0 2 1
0 1 0 0
2 0 1 2
1 0 1 2
0 0 1 0
1 0 0 1
0 1 0 0
1 0 1 0 0 1 0
1 0 0 1
0 1 0 0
1 0 1 0
0 1 0 1
0 0 0 0
0 1 0 0
1 1 1 1
2 2 2 2
2 3 3 3
3 3 4 4
4 4 4 5 5 5 5
5 6 6 6
6 6 7 7
7 7 7 8
8 8 8 8
308 1/2 318 3/4 324 3/4 328 3/4
334 3/4 342 3/4 352 3/4 358 3/4
363 369
376 3/4
387
393 397 1/4 403 1/4
411
421 1/4 427 1/4 431 1/2 437 1/2
445 1/4 445 1/2 461 1/2 465 1/2 471 1/2 479 1/2
489 1/2 495 1/2 499 3/4 505 3/4
513 1/2 523 3/4 529 3/4
534
540 547 3/4
558
564
568 1/4 574 1/4
582 592 1/4
598 1/4 602 1/4
25 26 27 27
27 28 29 29
30 30 31 32
32 33 33 34
35 35 36 36
37 37 38 38 39 39
40 41 41 42
42 43 44 44
45 45 46 47
47 47 48 49
49 50
8 1/2 8 3/4
3/4
4 3/4
10 3/4
6 3/4 4 3/4
10 3/4
3 9
4 3/4
3
9 1 1/4 7 1/4
3
1 1/4 7 1/4
11 1/2
5 1/2
1 1/4
11 1/2
5 1/2 9 1/2 3 1/2
11 1/2
9 1/2 3 1/2 7 3/4 1 3/4
9 1/2 7 3/4 1 3/4
6
0 7 3/4
6
0
4 1/4
10 1/4
6 4 1/4
10 1/4
2 1/4
0 1 0 2
1 0 1 0
2 1 0 1
0 2 1 0
1 0 2 1
0 1 0 2 1 0
1 0 2 1
0 1 0 2
1 0 1 0
2 1 0 1
0 2
0 0 1 0
1 0 0 1
0 1 0 0
1 0 1 0
0 1 0 1
0 0 1 0 1 0
0 1 0 1
0 0 1 0
1 0 0 1
0 1 0 0
1 0
9 9 9 9
9 10 10 10
10 10 11 11
11 11 11 12
12 12 12 12
13 13 13 13 13 14
14 14 14 14
15 15 15 15
15 16 16 16
16 16 17 17
17 17
608 1/4 616 1/4 626 1/4 632 1/4 636 1/2 642 1/2 650 1/4 660 1/2 666 1/2
670 3/4 676 3/4 684 1/2 694 3/4
700 3/4
705 711
718 3/4
729 735 739 745
753 763 769
773 1/4
779 1/4
787 797 1/4 803 1/4
807 1/2 813 1/2 821 1/4 831 1/2
837 1/2 841 3/4 847 3/4 855 1/2
865 3/4 871 3/4 875 3/4 881 3/4
889 3/4 899 3/4 905 3/4
910
916
924
50 51 52 52 53 53 54 55 55
55 56 57 57
58 58 59 59
60 61 61 62
62 63 64 64
64 65 66 66
67 67 68 69
69 70 70 71
72 72 72 73
74 74 75 75 76 77
8 1/4 4 1/4 2 1/4 8 1/4
1/2 6 1/2 2 1/2
1/2 6 1/2
10 3/4
4 3/4
1/2
10 3/4
4 3/4
9 3
10 3/4
9 3 7 1
9 7 1
5 1/4
11 1/4
7
5 1/4
11 1/4
3 1/2 9 1/2 5 1/4 3 1/2
9 1/2 1 3/4 7 3/4 3 1/2
1 3/4 6 3/4
11 3/4
5 3/4
1 3/4
11 3/4
5 3/4
10
4 0
1 0 1 0 2 1 0 1 0
2 1 0 1
0 2 1 0
1 0 2 1
0 1 0 2
1 0 1 0
2 1 0 1
0 2 1 0
1 0 2 1
0 1 0 2 1 0
1 0 0 1 0 1 0 0 1
0 1 0 0
1 0 1 0
0 1 0 1
0 0 1 0
1 0 0 1
0 1 0 0
1 0 1 0
0 1 0 1
0 0 1 0 1 0
17 18 18 18 18 18 19 19 19
19 19 20 20
20 20 20 21
21 21 21 21
22 22 22 22
22 23 23 23
23 23 24 24
24 24 24 25
25 25 25 25
26 26 26 26 26 27
55
Summary
1. WARNING: Fireplace and chimney systems will only draft properly when they are installed according to the instructions, in an appropriate location and with the proper chimney
height. Installing the replace according to the manufacturers
instructions, choosing an appropriate location, and choosing an appropriate chimney height are the responsibility of the designer and the building contractor. Tightly insulated and sealed homes, two story interior spaces and high vaulted ceilings can cause negative air pressures within the house which can impair drafting performance. HVAC
return air ducts near the replace opening will adversely affect the replace drafting performance.
It is the responsibility of the designer, the building contractor and their mechanical contractor to determine that the building’s internal air pressures are conducive to positive
replace drafting. Avoid placing any replace in an area near tall trees,
tall buildings, or high land masses. These structures can reduce
ambient air ow pressure as well as produce down drafts, either of which can impair replace drafting performance.
Earthcore Industries L.L.C. does not warrant drafting and is not responsible for it.
2. Fireplace Curing Instructions:
It is critical that the refractory elements in the Isokern
rebox and smoke dome components be dry before ring of the
unit. Moisture left in the Isokern components from exposure during storage and shipping, as well as moisture from the installation phase, must be eliminated before the unit is put to its intended use.
The rst step in reducing the ambient moisture is to be sure that the completed replace rest in a dried-in setting for a
minimum of 28 days after construction of the unit is complete.
The next step in curing the replace is to be sure that the rst ve or six res are of short duration. The rst re of the unit can take place once the minimum twenty-eight day drying period has passed. This re should be
especially short.
Start the rst re slowly with a small amount of paper and kindling (small dry wood splits or twigs) and a maximum load of four to six pounds of dry rewood, estimated to be no more than two or three logs each of about three inches (3”) to four inches (4”) diameter. The rst re should burn for no more than thirty to sixty minutes and then allowed to go out. Do not refuel the replace during the rst lighting.
A cooling off period of twenty-four hours, at a minimum,
should follow the rst re. The second re should be the same as the rst re.
A twenty-four hour cooling off period must be observed following second lighting.
After rst and second re, continue use of the unit with three or four small res of short duration (sixty minutes or so)
and small fuel loads.
After these rst ve or six small res of short duration, normal use of the replace can proceed. For normal use the
maximum recommended fuel load is twelve to sixteen pounds
of dry rewood at a time. This fuel load is considered to be approximately three to ve cured hardwood logs of about three inches (3”) to six inches (6”) in diameter. As the re burns
down, refueling should be only one or two logs added at a time.
Important: Do not burn construction debris or trash of any
kind in the replace.
It is not uncommon for construction debris and refuse
to be burned in a replace by site personnel on a project that is
under construction, this activity must be avoided. It is the responsibility of the building contractor to insure that the required dry-in period is met and that the required lighting sequence is performed by the owner or by the owner’s agent.
3. Log grates are required for burning solid fuel in the
Isokern replace. Grates allow for easy air ow up through the burning logs thus creating a more complete and efcient
burning of the fuel.
4. How to Build a Fire:
First set the replace damper in the full open position. Begin laying the re by placing several pieces of wadded up
paper directly on the log grate. Place kindling (small splits of
dry pine or other dry softwood) on top of the paper, enough
to loosely cover the paper. Next arrange several small, dry hardwood or softwood logs or log splits on top of the kindling layer.
Finally, arrange two or three larger hardwood logs (oak, hickory, etc.) or log splits on top of the stack. Ignite the
paper at the bottom of the stack. The burning paper will ignite
the kindling which will, in turn, set the remaining fuel on re. Be sure to stack all rewood in such a way that it will
settle into the log grate as the paper and kindling layers are
burned away. Additional logs can be set onto the re as each
fueling burns down. Ideally, fuel logs should be of a hardwood species that have been air dried for one year or longer. Use of cured or uncured pine logs and uncured hardwood logs for fuel should be avoided. Pine logs and uncured hardwood logs will tend to smolder and burn at relatively low temperatures producing high levels of soot and creosote.
Important: Do not throw, toss, jam, kick or otherwise force
logs into the replace.
56
Summary
WARNING: Never use gasoline, gasoline type lantern fuel,
kerosene, charcoal lighter uid or other similar liquids to start or “freshen up” the re in this or any replace.
WARNING: If processed solid fuel relogs are used, do not poke or stir the logs while they are burning. Use only relogs that have been evaluated for the application in replace and refer to relog warnings and caution markings on packaging
prior to use.
5. Avoid over-ring. Some examples of over-ring are:
a. Burning of scrap lumber, construction debris, pine branches and brush or cardboard boxes; b. Burning small diameter twigs, branches or any other small sized combustible materials in quantities which
exceed the volume of the normal log re; c. Use of articial wax base logs, trash or other
chemicals or chemically treated combustibles.
WARNING: Over-ring can permanently damage this replace system.
6. Fireplace Doors and Screens:
This replace has not been tested for use with doors. To reduce the risk of re or injury, do not install doors.
Operable doors are acceptable and if doors are required by the local authority having jurisdiction, then doors must be kept
in the fully open position when the replace is in operation. Isokern does not limit the use of replace screens.
7. Disposal of Ashes:
It is recommended that the rebox be cleaned of
excessive ashes before each use. It is necessary to remove
ashes from the open front of the replace. To do so, proceed in
the following manner:
Allow the re to go out and the ashes to cool for at
least six to eight hours. After the cooling period, carefully pick up the ashes
from the rebox with a small, metal replace shovel or other
metal scoop and place them in a metal container with a tight
tting lid.
If possible do not sweep the ashes as this will stir them into the air and disperse them into the room. The closed container of ashes should be placed on
a noncombustible oor or on the ground, well away from all combustible materials, pending nal disposal. If the ashes are
disposed of by burial in soil or otherwise locally dispersed, they should be retained in the closed container until all cinders have thoroughly cooled.
8. Inspection and Cleaning:
At least twice a year in warm climates or monthly during the heating season in colder climates, thoroughly
inspect the replace and chimney system. Chimneys must be
installed so that access is provided for inspection and cleaning. The chimney should be inspected monthly during the heating season.
Inspect the entire ue from the top down for
obstructions such as birds’ nests, leaves, etc. Such obstructions must be removed.
Check spark arrestor screens for clear ow of smoke
every two to four weeks during the heating season. Inspect the
ue periodically during the heating season for the presence of
soot and creosote build up. If creosote or soot has accumulated,
it should be removed to reduce the risk of chimney re.
Have your chimney cleaned by a professional chimney sweep if you have doubts about your ability to do it. Use a plastic, wood or steel brush to clean the chimney. Scrub
the spark arrestor/chimney cap with a wire brush. Remove any chimney cap for ue cleaning from the top. Open the damper in the rebox for cleaning access from below. Clean the inner portion of the ue by using a exible
handled chimney cleaning brush.
For straight run ue the proper size brush can be pulled up through the ue from the rebox with the damper
open. If the chimney has an offset chimney section, brush
cleaning from the chimney top down to the offset/return and then from the rebox up to the offset section is the proper
method.
In either case, cover the replace opening with a damp sheet (sealed to the opening with masking tape) before
brush cleaning. Do not remove sheet until the soot has settled. It is advised to vacuum loosened soot. Do not sweep loosened soot as sweeping will disperse soot into the air and about the room.
WARNING: Do not use chemical replace and chimney cleaners that are poured on a hot re. These can be dangerous and generally work only on the ue section nearest the re, leaving the rest of the ue unaffected.
9. Exterior Maintenance:
Annually, at a minimum, check all metal ashings and
weather seals around the exterior chimney where it penetrates the roof surface; inspect any chimney top spark arrestors, metal cowlings and weather hoods to make sure they are secure and weather tight.
Seal any cracks or gaps in chimney-to-roof ashings
to prevent possible roof and chimney chase leaks. Inspect any cement chimney cap or clay chimney pot terminations to make sure they are not diverting water into the structure. Seal any suspected cracks or gaps in these masonry components.
57
Registration Card
Please tear out along dashed lines and send to:
Earthcore Industries Attn: Technical Dept. 6899 Phillips Industrial Blvd. Jacksonville, FL. 32256
Or register your Isokern online at: www.earthcore.co
WARRANTY CARD Purchased From:
Date of Purchase: _______________________________________________________
Name: _______________________________________________________
Address: _______________________________________________________
City, State & Zip: _______________________________________________________
Phone No: _______________________________________________________
Gas Log Burner Size: (Circle One) 24” 30” Other__________
Fireplace Series/Size: Magnum _____ Isokern Standard _____ IBV ______ Vent-Free _____
Green Tech _____ ISO’ven _______ Fire-Lite Stand? (Circle One) Yes No
Gas Control Valve Type: (Circle One) Remote Control Safety Pilot
Gas Type: (Circle One) Natural Gas Propane
Buyer:
Date of Installation: (Completed) ________________________________________________
Name: _______________________________________________________
Address: _______________________________________________________
City, State & Zip: _______________________________________________________
Phone No: _______________________________________________________
Fireplace Serial Number: (Located on Rating Plate Inside Fireplace) ___________________
Installed By: _______________________________________________________
Address: _______________________________________________________
Phone Number _______________________________________________________
58
Notes
59
Warranty & Disclaimer
Isokern FIreplace
ISOKERN offers a lifetime warranty for all Isokern components, to be free from defects in materials that negatively affect system performance from the date of purchase, subject to the terms and conditions of this limited warranty.
This warranty covers only the above stated components, and NO WARRANTY, EXPRESS OR IMPLIED,
EXTENDS TO ANY OF THE HARDWARE, FOOTING, VENTS, DUCTING, METAL FLUES, FIRE BRICK OR ACCESSORIES. THIS WARRANTY DOES NOT COVER DRAFTING, SMOKING OR PUFFING OF THE FIREPLACE SYSTEM. Factors beyond the manufacturer's control affect replace drafting, smoking, and pufng, and ISOKERN cannot guarantee these aspects of performance.
If a component is found to be defective under the terms of this warranty the party to whom this warranty is
extended shall, notify ISOKERN, 6899 Philips Industrial Blvd, Jacksonville, Florida 32256, in writing, by registered mail, within thirty (30) days following the discovery of the defect within the lifetime warranty period. The notice shall contain (1) the date of purchase; (2) place of purchase; (3) address of installation; (4) name, ad­dress and phone number of the owner; and (5) a brief description of the defect.
ISOKERN, or any division thereof, is not responsible for any labor costs or indirect costs incurred for the replacement of defective components.
ISOKERN is not responsible for misuse or mishandling of components. Nothing in this warranty makes ISOKERN, or any division thereof, liable in any respect for any injury or damage to the building or structure in
which the replace or chimney system has been installed or to persons or property therein arising out of the use,
misuse, or installation of properly manufactured ISOKERN product.
ISOKERN, OR ANY DIVISION THEREOF, SHALL NOT BE HELD LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES OR EXPENSES ARISING OUT OF THE USE OF THE FIREPLACES OR CHIMNEY SYSTEMS. ALL SUCH DAMAGES AND EXPENSES ARE HEREBY
EXCLUDED.
This warranty is null and void when the replace or chimney systems are not installed pursuant to the
installation instructions provided by ISOKERN or local building codes have not been followed completely.
This warranty applies only to those replace and chimney systems installed in the continental United States,
Alaska, and Canada. If any part of this warranty is found to be unenforceable, the remaining parts shall remain in force and effect.
ISOKERN HEREBY DISCLAIMS ALL GUARANTEES AND WARRANTIES, EXPRESS OR IMPLIED, BE-
YOND THE WARRANTIES SET FORTH HEREIN.
6899 PHILIPS INDUSTRIAL BLVD. • JACKSONVILLE, FLORIDA 32256
TEL (904) 363-3417 • TOLL 1 (800) 642-2920 • FAX (904) 363-3408
Loading...